S06 - P000 - PLUMBING COVERSHEET.pdf

PDF 841 KB Posted

Attached to
Z2DA--695-22-117 CN New Audiology Clinic 5BN
Solicitation number
36C25225B0024
Issued by

About this file

This is a plumbing coversheet for a VA Milwaukee renovation project for Audiology 5BN located at 5000 W National Ave, Milwaukee, WI. The project number is 695-22-117, with a project number of 22010362.00, and is fully sprinklered. The document is a 100% Bid Document issued on September 9, 2024, by IMEG Corp. for the Office of Construction and Facilities Management of the U.S. Department of Veterans Affairs.

The plumbing sheet index includes seven sheets covering demolition plans for the fourth and fifth floors, plumbing plans for those floors, a roof plan, and plumbing diagrams. The plumbing fixture schedule details specific fixtures like water closets, lavatories, lab sinks, and break room sinks, providing detailed specifications for each, including manufacturers, model numbers, connection sizes, and specific installation requirements. The document includes comprehensive general notes for plumbing installation, renovation, and phasing, with extensive details on fixture mounting, pipe routing, and coordination requirements for the renovation project.

View the file

Other files

File Type Posted
36C25225B0024 0009.docx DOCX document
S06 - Response 12.31.25 Pre-Bid RFIs_695-22-117_1.14.26 RFI 154.xlsx XLSX spreadsheet
36C25225B0024 0008.docx DOCX document
36C25225B0024 0007.docx DOCX document
S06 - Response 12.31.25 Pre-Bid RFIs_695-22-117_1.12.26 RFIs 152_153.xlsx XLSX spreadsheet
S06 - Wage Determination 0006.txt TXT text file
0006 Narrative.pdf PDF
S06 - Response 12.31.25 Pre-Bid RFIs_695-22-117_12.9.25 RFIs 1 -151.pdf PDF
S06 - Amendment 0006 2of2 (1).pdf PDF
S06 - Amendment 0006 1of2.pdf PDF
S06 - 36C25225B0024 0006.pdf PDF
36C25225B0024 0005.docx DOCX document
36C25225B0024 0004.docx DOCX document
S06 - Pre-bid Site Visit 30 attended 20251120.pdf PDF
S06 - 36C25225B0024 0003.pdf PDF
S06 - 6a -695-22-117 VAMKE Audiology_100pc CD_Vol One Specifications Div 00-14.pdf PDF
S06 - 695_22_117 Drawing Sheet AI406 reissuse 13 Nov 2025.pdf PDF
Copy of S06 - Pre-Bid RFIs_695-22-117_11.18.25.xlsx XLSX spreadsheet
36C25225B0024 0002.docx DOCX document
S06 Spec section 00 01 15 list of Drawings sheets pp 123 w notes.pdf PDF
S06 - 6c-695-22-117-Drawings Vol 1 General_Site_AESOC_Code_HazMat_13_pages 02.pdf PDF
36C25225B0024 0001.docx DOCX document
S02 - MAP of East Entry for Site Visit 10.16.2025.pdf PDF
S02 - 695-22-117 Bldg Automation n HVAC Cntrl System Single Source Justification_Executed.pdf PDF
S02 - 695-22-117 Sole Source Justification_Nurse Call_Executed.pdf PDF
S02 - 695-22-117 VAMKE Audiology - 100pc CD - Vol Two Specifications Div 21-28.pdf PDF
S02 - 695-22-117 Drawings Vol 1_Architectural_Sec_Details_WallTypes Sheets 8.pdf PDF
S02- 695-22-117 Door Hardware Single Source Justification_Executed.pdf PDF
ATTACHMENT 1_VAAR 852.219-75 JAN2023_REQUIRED TO COMPLETE.pdf PDF
S02 - Wage Determination WI 20250905.pdf PDF
S02 - 695-22-117 Vol 2 Drawings Electrical Low Voltage Sheets 14.pdf PDF
S02 - 695-22-117 Drawings_ Vol 2 Plumbing_Med Gas_Pneumatic Tube Sheets 11.pdf PDF
S02 - 695-22-117 Drawings Vol 1 Furniture_7 sheets.pdf PDF
S02 - 695-22-117 Drawings Vol 1 Equip_Sound Booths_Interiors_Signage Sheets 12 02.pdf PDF
S02 -695-22-117 VAMKE Audiology - 100pc CD - Vol One Specifications Div 00-14.pdf PDF
S02 - 695-22-117 Drawings Vol 2_ FireProtection Sheets 6.pdf PDF
S02 - 695-22-117 Drawings Vol 2 Mechanical Sheets 17.pdf PDF
S02 - 695-22-117_Drawings Vol 1_Architectural Plans Sheets16.pdf PDF
S02 - 695-22-117 Fire Alarm System Single Source Justification_Executed.pdf PDF
36C25225B0024_1.docx DOCX document
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING SYMBOL LIST

SYMBOL: DESCRIPTION:

PIPE SERVING FIXTURE ON FLOOR ABOVE

(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

RD-1

6"(1000)

ROOF DRAIN PROPERTIES SYMBOL

SIZE (ROOF SQ. FT.)

DIELECTRIC CONNECTION

UNION/FLANGE

BALANCING VALVE (NUMBER INDICATES GPM)

GPM

CHECK VALVE

REDUCER - REFERENCE SPECIFICATION

FOR CONCENTRIC/ECCENTRIC AND FOT/FOB

METERM

ALIGNMENT GUIDE

PIPE ANCHOR

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

ACID VENTAV

ACID WASTEAW

DOMESTIC COLD WATER - POTABLEDCW

DOMESTIC HOT WATER - POTABLEDHW

DOMESTIC HOT WATER RETURN - POTABLEDHWR

DOMESTIC HOT WATER - POTABLE NUMBER INDICATES TEMPDHW140

DOMESTIC HOT WATER RETURN - POTABLE NUMBER INDICATES TEMPDHWR140

NON-POTABLE COLD WATERNCW

NON-POTABLE HOT WATERNHW

PUMPED DISCHARGEPD

SANITARY DRAINAGESAN

SOFT COLD WATERSCW

SOFT HOT WATERSHW

STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)

STS STORM DRAINAGE (SECONDARY)

VENTV

COMPRESSED AIRCA

DEIONIZED WATERDI

REVERSE OSMOSIS WATERRO

STW SOFT TEMPERED WATER

TW TEMPERED WATER

DRAIND

G NATURAL GAS

NOT ALL SYMBOLS MAY APPLY.

PRESSURE REDUCING VALVE (LIQUID/GAS)

LAB VACUUMVAC

SOLENOID VALVE

SAFETY/RELIEF VALVE

VACUUM BREAKER

PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P

TEMPERATURE SENSOR WITH WELL

T

THERMOMETER WITH WELL (DIAL TYPE)

T

THERMOMETER WITH WELL (FILLED TYPE)

PUMP

GRV GAS REGULATOR VENT

INSTRUMENT AIRIA

MEDICAL AIRMA

MEDICAL VACUUMMV

NITROGENN

OXYGENO

PURE WATERPW

PIPE CONTINUATION

PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P

ROUTE TO DRAIN

BACKFLOW PREVENTER

EXPANSION JOINT

#.#" IS THE EXPANSION TRAVEL INCHESEJ-#

AIR ADMITTANCE VALVE

PLUMBING ABBREVIATION KEY

BATHTUBBT

CO CLEANOUT

CLINICAL SINKCS

DRINKING FOUNTAINDF

EMERGENCY EYEWASHEE

FLOOR CLEANOUTFCO

FLOOR DRAINFD

FLOOR SINKFS

GARBAGE DISPOSERGD

HOSE BIBBHB

I.E. INVERT ELEVATION (FOR REFERENCE ONLY)

LAVATORYLAV

MOP BASINMB

MH MANHOLE

MIXING VALVEMV

NEUTRALIZATION TANKNT

ROOF DRAINRD

SHOWERSH

SINKSK

SERVICE SINKSS

TRENCH DRAINTD

TRAP PRIMERTP

URINALUR

WATER CLOSETWC

WALL CLEANOUTWCO

WASH FOUNTAINWF

WATER HEATERWH

YARD CLEANOUTYCO

EMERGENCY SHOWERES

EMERGENCY SHOWER/EYEWASHESE

ELECTRIC WATER COOLEREWC

VENT THROUGH ROOFVTR

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

BFP BACKFLOW PREVENTER

NOT IN CONTRACTNIC

ABBR: DESCRIPTION:

TYPICALTYP

UNLESS OTHERWISE NOTEDUON

EXISTINGE

FLOW METERFM

WATER SOFTENERWS

WATER METERWM

DIALYSIS BOXDB

CATCH BASINCB

CAST IRONCI

UTILITY BOXUB

SHORT CIRCUIT CURRENT RATINGSCCR

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED IN

MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N O R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

T101

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR SHALL

VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL MATERIALS

REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.

ALL [FLOOR, FLOOR CEILING, AND ROOF CEILING] ASSEMBLIES SHALL BE DESIGNATED AS [1], [2], [3], [4] HOUR FIRE [/SMOKE], BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS WERE

ACQUIRED FROM THE ARCHITECTURAL PLANS DATED 08/24/23.

FIRE / SMOKE BARRIER DESIGNATIONS

1 HOUR FIRE BARRIER

SMOKE BARRIER

1 HOUR FIRE/SMOKE BARRIER OR

SHAFT ENCLOSURE

2 HOUR FIRE/SMOKE BARRIER

OR SHAFT ENCLOSURE

SMOKE PARTITION

FIRE PARTITION

2 HOUR FIRE BARRIER OR WALL

TEMPERATURE CONTROLS CONTRACTORT.C.C.

FIRE PROTECTION CONTRACTORF.P.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

MECHANICAL GENERAL NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE

DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.

DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,

AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION.

THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND

THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM

ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR

PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE

CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY

NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF

NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE

ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR

EQUIPMENT ORDERS.

4. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO

COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE

TO OTHERS.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,

FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS

RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

7. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC

FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE

AND COLOR WITH ARCHITECT.

8. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE

ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

9. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS

WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT

SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

10. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT

MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND

REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING,

DUCTWORK, ETC.

11. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.

MECHANICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY

CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK.

NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR PIPING BEFORE FABRICATION. RISES AND DROPS

MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND

SHALL NOTIFY THE COR PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED

OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS.

NOTIFY THE COR OF AFFECTED AREAS PRIOR TO BIDDING.

6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT

CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW

FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING

CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN

ACTIVE.

8. OBTAIN PERMISSION FROM COR BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON.

MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE

INSTALLED.

MECHANICAL PHASING NOTES:

THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE

PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS AND FRONT END SPECIFICATIONS FOR GENERAL

DESCRIPTION OF PHASES. COORDINATE WITH GENERAL CONTRACTOR'S CONSTRUCTION

SCHEDULE FOR PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL,

ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE

MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND

METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH

AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS,

ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

6. ALL WORK OUTSIDE OF THE CONSTRUCTION AREA SHALL COMPLY WITH THE INFECTION

CONTROL REQUIREMENTS OF THE PROJECT.

1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.

CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY

OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE

CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A

COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS

BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE

CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.

4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874

5. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY ALL

ELEVATIONS BEFORE BEGINNING WORK.

6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO BEGINNING

ANY WORK.

7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO PLUMBING

FIXTURES.

8. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL

SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL

DEMOLITION INFORMATION.

9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL P.C.

SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED

OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.

PLUMBING GENERAL NOTES:

ROUTE TEMPERED

WATER TO FIXTURE.

HW ANGLE STOP.

MOUNT MIXING VALVE

AS CLOSE TO FIXTURE

TRIM AS POSSIBLE.

INSTALL ENCLOSURE IF

CALLED FOR IN

MATERIAL LIST.

C W

H W

HOT WATER FIXTURE REFER

TO PLANS AND MATERIAL

LIST FOR TYPE.

PROVIDE SEPARATE CW

AND HW SUPPLIES TO

FIXTURE IF APPLICABLE.

H W

C

ROUTE HOT WATER

CIRCULATION FROM TEE

FITTING CONCEALED IN

WALL, MAXIMUM

LENGTH FROM HWC

CONNECTION TO

FIXTURE PER IECC TABLE

C404.5.1.

SINGLE

PROVIDE BALANCING

VALVE IN ACCESSIBLE

LOCATION

CW ANGLE STOP.

HOSE BIBB

MINIMUM 24" ABOVE

FINISHED ROOF

SKIRT AROUND PIPE

ROOF FLASHING

ROOF DECK

RIGIDLY SUPPORT TO

STRUCTURE

INSULATION - SEE

SPECIFICATIONS

NORMALLY CLOSED CW VALVE

IN ACCESSIBLE AREA.

3/4"

CW

CEILING

3/4"

CW

PLUMBING SHEET INDEX

P000 PLUMBING COVERSHEET

PD104 FOURTH FLOOR PLAN - PLUMBING - DEMOLITION

PD105 FIFTH FLOOR PLAN - PLUMBING - DEMOLITION

P204 FOURTH FLOOR PLAN - PLUMBING

P205 FIFTH FLOOR PLAN - PLUMBING

P206 ROOF PLAN - PLUMBING

P300 PLUMBING DIAGRAMS

GRAND TOTAL: 7

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

DWG. ___ OF XX

7GAE PROJECT NO.: 221236

Sprinkler:

600 E. Michigan Avenue, Suite B

Kalamazoo, MI 49007

P: 269.927.0144 www.7GenAE.com

2850 Eisenhower Ave, Suite 310

Alexandria, VA 22314

P: 202.617.8485 www.alliance.us.com

FULLY SPRINKLERED

PLUMBING COVERSHEET VA MILWAUKEE RENOVATE 111

AUDIOLOGY 5BN

5000 W NATIONAL AVE, MILWAUKEE, WI 53295

695-22-117

PROJECT DIRECTOR

September 9, 2024 KRICOT RYALIN

100%

BID DOCUMENTS

P000

2310 CROSSROADS DR

SUITE 3000

MADISON, WI 53718

P: 608.223.9600 F: 608.223.9601 www.imegcorp.com

IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,

TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING

AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND

SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT

WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

IMEG CORP. ©2023 IMEG CORP.

REF. SCALE IN INCHES

0 1 2 3

PROJECT #22010362.00

PLUMBING FIXTURE SCHEDULE

MARK

PLUMBING

FIXTURE DESCRIPTION

BASIS OF DESIGN

MANUFACTURER AND MODEL

CONNECTION SIZES (IN)

CW HW WASTE VENT

P-115 WATER CLOSET

FLOOR MTD

WATER CLOSET (FLOOR MOUNTED, ASME A112.19.2) SIPHON JET, 6 L (1.6 GALLONS PER FLUSH. TOP OF SEAT WILL BE 280 MM TO 430 MM (11 TO 19 INCHES) ABOVE

FINISH FLOOR, DEPENDING ON AGE GROUP (REFER TO ADA STANDARD FOR GUIDANCE).

1.SEAT: COMMERCIAL WEIGHT, CHEMICAL RESISTANT, SOLID PLASTIC OPEN FRONT LESS COVER FOR INFANT BOWLS, INTEGRALLY MOLDED BUMPERS, CONCEALED

CHECK HINGE WITH STAINLESS STEEL POST. COLOR WILL BE WHITE.

2.FITTING AND ACCESSORIES: GASKETS-NEOPRENE, BOLTS WITH CHROMIUM PLATED CAP NUTS AND WASHERS.

3.FLUSH VALVE: LARGE CHLORAMINES RESISTANT DIAPHRAGM, SEMI-RED BRASS BODY, EXPOSED CHROME PLATED, NON-HOLD OPEN ADA APPROVED SIDE

OSCILLATING HANDLE, HARD-WIRED ELECTRIC WITH COURTESY FLUSH BUTTON FOR MANUAL OPERATION, WATER SAVER DESIGN, 25 MM (1 INCH) SCREWDRIVER

ANGLE CHECK STOP, ADJUSTABLE TAILPIECE, HIGH PRESSURE VACUUM BREAKER, CAST SET SCREW WALL FLANGES AND SPUD FLANGES, SWEAT SOLDER ADAPTER WITH COVER TUBE, SPUD COUPLING FOR 40 MM (1-1/2 INCH) TOP SPUD, SOLID-RING PIPE SUPPORT, AND WALL AND SPUD FLANGES. SET CENTERLINE INLET 292 MM (11-1/2 INCHES) ABOVE SEAT. VALVE BODY, COVER, TAILPIECE, AND CONTROL STOP WILL BE IN CONFORMANCE WITH ASTM ALLOY CLASSIFICATION FOR SEMI-RED

BRASS.

WATER CLOSET -

AMERICAN STANDARD

(3043.001)

FLUSH VALVE - ZURN

(ZEMS6000AV)

1.25 - 3 2

P-401 LAVATORY LAVATORY (ADA COMPLIANT, SENSOR CONTROL, WALL MOUNTED ASME A112.19.2) STRAIGHT BACK, APPROXIMATELY 508 MM BY 457 MM (20 INCHES BY 18 INCHES) AND A 102 MM (4 INCHES) MAXIMUM APRON, FIRST QUALITY VITREOUS CHINA. CENTRALLY LOCATED SINGLE HOLE PUNCH FOR RIGID GOOSENECK SPOUT FAUCET ON 102 MM (4 INCHES) CENTERS. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS. SUPPORT SINK WITH 10 GAGE CRS BRACKETS ON ASME A112.6.1M, TYPE I, CHAIR CARRIER AND SECURE FIXTURE WITH MINIMUM 10 MM (3/8 INCH) ALL-THREAD BRACKET STUDS AND NUTS.

1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING

VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.

2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE

P-418 IN THE SAME ROOM, WHERE APPLICABLE.

3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.

4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.

5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)

TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP

PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.

LAVATORY -

AMERICAN STANDARD

(0355.012)

LAVATORY TRIM - CHICAGO

FAUCET (116.606.AB.1)

0.5 0.5 2 1.5

P-516 LAB SINK SINK (CRS, SINGLE COMPARTMENT, WALL HUNG) 18 GAGE CRS, APPROXIMATELY 711 MM BY 508 MM (22 INCHES BY 19 INCHES) BY 191 MM (5 1/2 INCHES) DEEP WITH 102 MM (4 INCH) SPLASH BACK. PROVIDE ROLLED RIM ON FRONT AND ENDS. CORNERS AND EDGES WILL BE WELL ROUNDED. SUPPORT SINK WITH 10 GAGE CRS BRACKETS ON ASME A112.6.1M, TYPE I, CHAIR CARRIER AND SECURE FIXTURE WITH MINIMUM 10 MM (3/8 INCH) ALL-THREAD BRACKET STUDS AND NUTS. REFER TO

ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS.

1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING

VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.

2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE

P-418 IN THE SAME ROOM, WHERE APPLICABLE.

3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.

4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.

5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)

TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP

PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.

4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.

SINK - ELKAY (ELV2219)

SINK TRIM - CHICAGO FAUCET

(EQ-C11A-51ABCPT)

1 0.75 2 1.5

P-528-1 ALCOVE SINK SINK (CRS, SINGLE COMPARTMENT, COUNTERTOP ASME A112.19.2,) UNDERMOUNT, APPROXIMATELY 533 MM BY 559 MM (21 INCHES BY 22 INCHES) WITH SINGLE COMPARTMENT INSIDE DIMENSIONS APPROXIMATELY 406 MM BY 483 MM BY 191 MM (16 INCHES BY 19 INCHES BY 7 1/2 INCHES) DEEP. WILL BE MINIMUM OF 1.3 MM

THICK (18 GAUGE) CRS. CORNERS AND EDGES WILL BE WELL ROUNDED:

1.FAUCET: SOLID BRASS CONSTRUCTION, 8.3 L/M (2.2 GPM) DECK MOUNTED COMBINATION FAUCET WITH MONEL OR CERAMIC SEATS, REMOVABLE REPLACEMENT

UNIT CONTAINING ALL PARTS SUBJECT TO WARE, SWIVEL GOOSENECK SPOUT WITH APPROXIMATELY 203 MM (8 INCHES) REACH WITH SPOUT OUTLET 152 MM (6 INCHES ABOVE DECK AND 102 MM (4 INCHES) WRIST BLADES. FAUCET WILL BE POLISHED CHROME PLATED.

2.DRAIN: DRAIN PLUG WITH CUP STRAINER, STAINLESS STEEL.

3.TRAP: CAST COPPER ALLOY 38 MM (1 1/2 INCHES) P-TRAP WITH CLEANOUT PLUG. PROVIDE WALL CONNECTION AND ESCUTCHEON.

4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.

SINK - ELKAY (ELUH2115PD)

SINK TRIM - CHICAGO FAUCET

(200-GN8AE3-317XKAB)

1 0.75 2 1.5

P-528-2 BREAK/LOCKER

SINK

ADA SINK (CRS, SINGLE COMPARTMENT, COUNTERTOP ASME A112.19.2, KITCHEN SINKS) UNDERMOUNT, APPROXIMATELY 533 MM BY 559 MM (23 INCHES BY 18 INCHES) WITH SINGLE COMPARTMENT INSIDE DIMENSIONS APPROXIMATELY 406 MM BY 483 MM BY 191 MM (21 INCHES BY 16 INCHES BY 6 INCHES) DEEP. WILL BE

MINIMUM OF 1.3 MM THICK (18 GAUGE) CRS. CORNERS AND EDGES WILL BE WELL ROUNDED:

1.FAUCET: SOLID BRASS CONSTRUCTION, 8.3 L/M (2.2 GPM) DECK MOUNTED COMBINATION FAUCET WITH MONEL OR CERAMIC SEATS, REMOVABLE REPLACEMENT

UNIT CONTAINING ALL PARTS SUBJECT TO WARE, RIGID GOOSENECK SPOUT WITH APPROXIMATELY 203 MM (8 INCHES) REACH WITH SPOUT OUTLET 152 MM (6 INCHES ABOVE DECK AND 102 MM (4 INCHES) WRIST BLADES WITH HOSE SPRAY. FAUCET WILL BE POLISHED CHROME PLATED.

2.DRAIN: DRAIN PLUG WITH CUP STRAINER, STAINLESS STEEL.

3.TRAP: CAST COPPER ALLOY 38 MM (1 1/2 INCHES) P-TRAP WITH CLEANOUT PLUG. PROVIDE WALL CONNECTION AND ESCUTCHEON.

4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.

SINK - ELKAY

(ELUHAD191655PD)

SINK TRIM - CHICAGO FAUCET

(200-GN8AE3-317XKAB)

0.75 0.75 2 1.5

P-540 PATIENT ROOM

SINK

SINK (SINGLE COMPARTMENT, INTEGRAL WITH COUNTER, REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS AND MOUNTING).

1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING

VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.

2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE

P-418 IN THE SAME ROOM, WHERE APPLICABLE.

3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.

4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.

5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)

TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP

PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.

6.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.

SINK TRIM - CHICAGO FAUCET

(116.427.AB.1T)

0.75 0.75 2 1.5

P-805 ROOF HOSE BIBB HOSE BIBB - FREEZELESS ROOF HYDRANT, ONE PIECE VARIABLE FLOW PLUNGER WITH ROD GUIDE, BUILT-IN STORAGE RESEVOIR AND VENTURI SYSTEM TO EVACUATE WATER AND ALLOW DRAIN BACK OPERATION FOR FREEZE PROOF WINTERIZATION WITHOUT A DRAIN CONNECTION, CAST IRON FLANGED HYDRANT SUPPORT WITH UNDER-DECK FLANGE, WELL SEAL BETWEEN SUPPORT AND HYDRANT PIPE WITH EDPM BOOT COVER. SET NOT LESS THAN 18 INCHES OR MORE THAN 36 INCHES ABOVE

ROOF.

PROVIDE WITH ASSE 1052 OR 1057 APPROVED, FIELD TESTABLE, DOUBLE CHECK VALVE BACK FLOW PREVENTER WITH 3/4" THREADED HOSE CONNECTION AT

HYDRANT OUTLET.

WOODFORD (SRH-MS), PRIER

(P-RH4), FREEZE FLOW

(2131RE)

0.75 - - -

NO SCALE

SINK MIXING VALVE

NO SCALE

ROOF HOSE BIBB

Revisions: Date:

35% SCHEMATIC DESIGN 04/20/2023

65% DESIGN DEVELOPMENT 06/16/2023

95% CONSTRUCTION DOCUMENTS 08/30/2023

95% CONSTRUCTION DOCUMENTS RESUBMITTAL 05/08/2024

100% CONSTRUCTION DOCUMENTS 09/09/2024

ACCOMPANYING 36C25225B0024 0002

Sheets
P000 - PLUMBING COVERSHEET
P204 - FOURTH FLOOR PLAN - PLUMBING
P205 - FIFTH FLOOR PLAN - PLUMBING
P206 - ROOF PLAN - PLUMBING
P300 - PLUMBING DIAGRAMS
PD104 - FOURTH FLOOR PLAN - PLUMBING - DEMOLITION
PD105 - FIFTH FLOOR PLAN - PLUMBING - DEMOLITION

File details come from the government source that posted it. Updated .