S06 - P000 - PLUMBING COVERSHEET.pdf
PDF 841 KB Posted
- Attached to
- Z2DA--695-22-117 CN New Audiology Clinic 5BN
- Solicitation number
- 36C25225B0024
About this file
This is a plumbing coversheet for a VA Milwaukee renovation project for Audiology 5BN located at 5000 W National Ave, Milwaukee, WI. The project number is 695-22-117, with a project number of 22010362.00, and is fully sprinklered. The document is a 100% Bid Document issued on September 9, 2024, by IMEG Corp. for the Office of Construction and Facilities Management of the U.S. Department of Veterans Affairs.
The plumbing sheet index includes seven sheets covering demolition plans for the fourth and fifth floors, plumbing plans for those floors, a roof plan, and plumbing diagrams. The plumbing fixture schedule details specific fixtures like water closets, lavatories, lab sinks, and break room sinks, providing detailed specifications for each, including manufacturers, model numbers, connection sizes, and specific installation requirements. The document includes comprehensive general notes for plumbing installation, renovation, and phasing, with extensive details on fixture mounting, pipe routing, and coordination requirements for the renovation project.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
ACID VENTAV
ACID WASTEAW
DOMESTIC COLD WATER - POTABLEDCW
DOMESTIC HOT WATER - POTABLEDHW
DOMESTIC HOT WATER RETURN - POTABLEDHWR
DOMESTIC HOT WATER - POTABLE NUMBER INDICATES TEMPDHW140
DOMESTIC HOT WATER RETURN - POTABLE NUMBER INDICATES TEMPDHWR140
NON-POTABLE COLD WATERNCW
NON-POTABLE HOT WATERNHW
PUMPED DISCHARGEPD
SANITARY DRAINAGESAN
SOFT COLD WATERSCW
SOFT HOT WATERSHW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
COMPRESSED AIRCA
DEIONIZED WATERDI
REVERSE OSMOSIS WATERRO
STW SOFT TEMPERED WATER
TW TEMPERED WATER
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
LAB VACUUMVAC
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)
T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
GRV GAS REGULATOR VENT
INSTRUMENT AIRIA
MEDICAL AIRMA
MEDICAL VACUUMMV
NITROGENN
OXYGENO
PURE WATERPW
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
BACKFLOW PREVENTER
EXPANSION JOINT
#.#" IS THE EXPANSION TRAVEL INCHESEJ-#
AIR ADMITTANCE VALVE
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
FLOOR SINKFS
GARBAGE DISPOSERGD
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
MH MANHOLE
MIXING VALVEMV
NEUTRALIZATION TANKNT
ROOF DRAINRD
SHOWERSH
SINKSK
SERVICE SINKSS
TRENCH DRAINTD
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WASH FOUNTAINWF
WATER HEATERWH
YARD CLEANOUTYCO
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
EXISTINGE
FLOW METERFM
WATER SOFTENERWS
WATER METERWM
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
UTILITY BOXUB
SHORT CIRCUIT CURRENT RATINGSCCR
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED IN
MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
T101
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR SHALL
VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL MATERIALS
REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.
ALL [FLOOR, FLOOR CEILING, AND ROOF CEILING] ASSEMBLIES SHALL BE DESIGNATED AS [1], [2], [3], [4] HOUR FIRE [/SMOKE], BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS WERE
ACQUIRED FROM THE ARCHITECTURAL PLANS DATED 08/24/23.
FIRE / SMOKE BARRIER DESIGNATIONS
1 HOUR FIRE BARRIER
SMOKE BARRIER
1 HOUR FIRE/SMOKE BARRIER OR
SHAFT ENCLOSURE
2 HOUR FIRE/SMOKE BARRIER
OR SHAFT ENCLOSURE
SMOKE PARTITION
FIRE PARTITION
2 HOUR FIRE BARRIER OR WALL
TEMPERATURE CONTROLS CONTRACTORT.C.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION.
THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND
THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY
NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF
NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE
ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR
EQUIPMENT ORDERS.
4. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE
TO OTHERS.
5. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
7. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC
FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE
AND COLOR WITH ARCHITECT.
8. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE
ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
9. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS
WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT
SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
10. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING,
DUCTWORK, ETC.
11. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY
CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK.
NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR PIPING BEFORE FABRICATION. RISES AND DROPS
MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE COR PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED
OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS.
NOTIFY THE COR OF AFFECTED AREAS PRIOR TO BIDDING.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT
CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW
FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN
ACTIVE.
8. OBTAIN PERMISSION FROM COR BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON.
MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE
INSTALLED.
MECHANICAL PHASING NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE
PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS AND FRONT END SPECIFICATIONS FOR GENERAL
DESCRIPTION OF PHASES. COORDINATE WITH GENERAL CONTRACTOR'S CONSTRUCTION
SCHEDULE FOR PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL,
ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE
MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND
METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH
AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS,
ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
6. ALL WORK OUTSIDE OF THE CONSTRUCTION AREA SHALL COMPLY WITH THE INFECTION
CONTROL REQUIREMENTS OF THE PROJECT.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY
OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE
CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A
COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS
BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE
CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
5. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY ALL
ELEVATIONS BEFORE BEGINNING WORK.
6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO BEGINNING
ANY WORK.
7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO PLUMBING
FIXTURES.
8. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL
SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL
DEMOLITION INFORMATION.
9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL P.C.
SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED
OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.
PLUMBING GENERAL NOTES:
ROUTE TEMPERED
WATER TO FIXTURE.
HW ANGLE STOP.
MOUNT MIXING VALVE
AS CLOSE TO FIXTURE
TRIM AS POSSIBLE.
INSTALL ENCLOSURE IF
CALLED FOR IN
MATERIAL LIST.
C W
H W
HOT WATER FIXTURE REFER
TO PLANS AND MATERIAL
LIST FOR TYPE.
PROVIDE SEPARATE CW
AND HW SUPPLIES TO
FIXTURE IF APPLICABLE.
H W
C
ROUTE HOT WATER
CIRCULATION FROM TEE
FITTING CONCEALED IN
WALL, MAXIMUM
LENGTH FROM HWC
CONNECTION TO
FIXTURE PER IECC TABLE
C404.5.1.
SINGLE
PROVIDE BALANCING
VALVE IN ACCESSIBLE
LOCATION
CW ANGLE STOP.
HOSE BIBB
MINIMUM 24" ABOVE
FINISHED ROOF
SKIRT AROUND PIPE
ROOF FLASHING
ROOF DECK
RIGIDLY SUPPORT TO
STRUCTURE
INSULATION - SEE
SPECIFICATIONS
NORMALLY CLOSED CW VALVE
IN ACCESSIBLE AREA.
3/4"
CW
CEILING
3/4"
CW
PLUMBING SHEET INDEX
P000 PLUMBING COVERSHEET
PD104 FOURTH FLOOR PLAN - PLUMBING - DEMOLITION
PD105 FIFTH FLOOR PLAN - PLUMBING - DEMOLITION
P204 FOURTH FLOOR PLAN - PLUMBING
P205 FIFTH FLOOR PLAN - PLUMBING
P206 ROOF PLAN - PLUMBING
P300 PLUMBING DIAGRAMS
GRAND TOTAL: 7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
DWG. ___ OF XX
7GAE PROJECT NO.: 221236
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
2850 Eisenhower Ave, Suite 310
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
FULLY SPRINKLERED
PLUMBING COVERSHEET VA MILWAUKEE RENOVATE 111
AUDIOLOGY 5BN
5000 W NATIONAL AVE, MILWAUKEE, WI 53295
695-22-117
PROJECT DIRECTOR
September 9, 2024 KRICOT RYALIN
100%
BID DOCUMENTS
P000
2310 CROSSROADS DR
SUITE 3000
MADISON, WI 53718
P: 608.223.9600 F: 608.223.9601 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #22010362.00
PLUMBING FIXTURE SCHEDULE
MARK
PLUMBING
FIXTURE DESCRIPTION
BASIS OF DESIGN
MANUFACTURER AND MODEL
CONNECTION SIZES (IN)
CW HW WASTE VENT
P-115 WATER CLOSET
FLOOR MTD
WATER CLOSET (FLOOR MOUNTED, ASME A112.19.2) SIPHON JET, 6 L (1.6 GALLONS PER FLUSH. TOP OF SEAT WILL BE 280 MM TO 430 MM (11 TO 19 INCHES) ABOVE
FINISH FLOOR, DEPENDING ON AGE GROUP (REFER TO ADA STANDARD FOR GUIDANCE).
1.SEAT: COMMERCIAL WEIGHT, CHEMICAL RESISTANT, SOLID PLASTIC OPEN FRONT LESS COVER FOR INFANT BOWLS, INTEGRALLY MOLDED BUMPERS, CONCEALED
CHECK HINGE WITH STAINLESS STEEL POST. COLOR WILL BE WHITE.
2.FITTING AND ACCESSORIES: GASKETS-NEOPRENE, BOLTS WITH CHROMIUM PLATED CAP NUTS AND WASHERS.
3.FLUSH VALVE: LARGE CHLORAMINES RESISTANT DIAPHRAGM, SEMI-RED BRASS BODY, EXPOSED CHROME PLATED, NON-HOLD OPEN ADA APPROVED SIDE
OSCILLATING HANDLE, HARD-WIRED ELECTRIC WITH COURTESY FLUSH BUTTON FOR MANUAL OPERATION, WATER SAVER DESIGN, 25 MM (1 INCH) SCREWDRIVER
ANGLE CHECK STOP, ADJUSTABLE TAILPIECE, HIGH PRESSURE VACUUM BREAKER, CAST SET SCREW WALL FLANGES AND SPUD FLANGES, SWEAT SOLDER ADAPTER WITH COVER TUBE, SPUD COUPLING FOR 40 MM (1-1/2 INCH) TOP SPUD, SOLID-RING PIPE SUPPORT, AND WALL AND SPUD FLANGES. SET CENTERLINE INLET 292 MM (11-1/2 INCHES) ABOVE SEAT. VALVE BODY, COVER, TAILPIECE, AND CONTROL STOP WILL BE IN CONFORMANCE WITH ASTM ALLOY CLASSIFICATION FOR SEMI-RED
BRASS.
WATER CLOSET -
AMERICAN STANDARD
(3043.001)
FLUSH VALVE - ZURN
(ZEMS6000AV)
1.25 - 3 2
P-401 LAVATORY LAVATORY (ADA COMPLIANT, SENSOR CONTROL, WALL MOUNTED ASME A112.19.2) STRAIGHT BACK, APPROXIMATELY 508 MM BY 457 MM (20 INCHES BY 18 INCHES) AND A 102 MM (4 INCHES) MAXIMUM APRON, FIRST QUALITY VITREOUS CHINA. CENTRALLY LOCATED SINGLE HOLE PUNCH FOR RIGID GOOSENECK SPOUT FAUCET ON 102 MM (4 INCHES) CENTERS. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS. SUPPORT SINK WITH 10 GAGE CRS BRACKETS ON ASME A112.6.1M, TYPE I, CHAIR CARRIER AND SECURE FIXTURE WITH MINIMUM 10 MM (3/8 INCH) ALL-THREAD BRACKET STUDS AND NUTS.
1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING
VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.
2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE
P-418 IN THE SAME ROOM, WHERE APPLICABLE.
3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.
4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.
5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)
TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP
PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.
LAVATORY -
AMERICAN STANDARD
(0355.012)
LAVATORY TRIM - CHICAGO
FAUCET (116.606.AB.1)
0.5 0.5 2 1.5
P-516 LAB SINK SINK (CRS, SINGLE COMPARTMENT, WALL HUNG) 18 GAGE CRS, APPROXIMATELY 711 MM BY 508 MM (22 INCHES BY 19 INCHES) BY 191 MM (5 1/2 INCHES) DEEP WITH 102 MM (4 INCH) SPLASH BACK. PROVIDE ROLLED RIM ON FRONT AND ENDS. CORNERS AND EDGES WILL BE WELL ROUNDED. SUPPORT SINK WITH 10 GAGE CRS BRACKETS ON ASME A112.6.1M, TYPE I, CHAIR CARRIER AND SECURE FIXTURE WITH MINIMUM 10 MM (3/8 INCH) ALL-THREAD BRACKET STUDS AND NUTS. REFER TO
ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS.
1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING
VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.
2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE
P-418 IN THE SAME ROOM, WHERE APPLICABLE.
3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.
4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.
5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)
TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP
PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.
4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.
SINK - ELKAY (ELV2219)
SINK TRIM - CHICAGO FAUCET
(EQ-C11A-51ABCPT)
1 0.75 2 1.5
P-528-1 ALCOVE SINK SINK (CRS, SINGLE COMPARTMENT, COUNTERTOP ASME A112.19.2,) UNDERMOUNT, APPROXIMATELY 533 MM BY 559 MM (21 INCHES BY 22 INCHES) WITH SINGLE COMPARTMENT INSIDE DIMENSIONS APPROXIMATELY 406 MM BY 483 MM BY 191 MM (16 INCHES BY 19 INCHES BY 7 1/2 INCHES) DEEP. WILL BE MINIMUM OF 1.3 MM
THICK (18 GAUGE) CRS. CORNERS AND EDGES WILL BE WELL ROUNDED:
1.FAUCET: SOLID BRASS CONSTRUCTION, 8.3 L/M (2.2 GPM) DECK MOUNTED COMBINATION FAUCET WITH MONEL OR CERAMIC SEATS, REMOVABLE REPLACEMENT
UNIT CONTAINING ALL PARTS SUBJECT TO WARE, SWIVEL GOOSENECK SPOUT WITH APPROXIMATELY 203 MM (8 INCHES) REACH WITH SPOUT OUTLET 152 MM (6 INCHES ABOVE DECK AND 102 MM (4 INCHES) WRIST BLADES. FAUCET WILL BE POLISHED CHROME PLATED.
2.DRAIN: DRAIN PLUG WITH CUP STRAINER, STAINLESS STEEL.
3.TRAP: CAST COPPER ALLOY 38 MM (1 1/2 INCHES) P-TRAP WITH CLEANOUT PLUG. PROVIDE WALL CONNECTION AND ESCUTCHEON.
4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.
SINK - ELKAY (ELUH2115PD)
SINK TRIM - CHICAGO FAUCET
(200-GN8AE3-317XKAB)
1 0.75 2 1.5
P-528-2 BREAK/LOCKER
SINK
ADA SINK (CRS, SINGLE COMPARTMENT, COUNTERTOP ASME A112.19.2, KITCHEN SINKS) UNDERMOUNT, APPROXIMATELY 533 MM BY 559 MM (23 INCHES BY 18 INCHES) WITH SINGLE COMPARTMENT INSIDE DIMENSIONS APPROXIMATELY 406 MM BY 483 MM BY 191 MM (21 INCHES BY 16 INCHES BY 6 INCHES) DEEP. WILL BE
MINIMUM OF 1.3 MM THICK (18 GAUGE) CRS. CORNERS AND EDGES WILL BE WELL ROUNDED:
1.FAUCET: SOLID BRASS CONSTRUCTION, 8.3 L/M (2.2 GPM) DECK MOUNTED COMBINATION FAUCET WITH MONEL OR CERAMIC SEATS, REMOVABLE REPLACEMENT
UNIT CONTAINING ALL PARTS SUBJECT TO WARE, RIGID GOOSENECK SPOUT WITH APPROXIMATELY 203 MM (8 INCHES) REACH WITH SPOUT OUTLET 152 MM (6 INCHES ABOVE DECK AND 102 MM (4 INCHES) WRIST BLADES WITH HOSE SPRAY. FAUCET WILL BE POLISHED CHROME PLATED.
2.DRAIN: DRAIN PLUG WITH CUP STRAINER, STAINLESS STEEL.
3.TRAP: CAST COPPER ALLOY 38 MM (1 1/2 INCHES) P-TRAP WITH CLEANOUT PLUG. PROVIDE WALL CONNECTION AND ESCUTCHEON.
4.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.
SINK - ELKAY
(ELUHAD191655PD)
SINK TRIM - CHICAGO FAUCET
(200-GN8AE3-317XKAB)
0.75 0.75 2 1.5
P-540 PATIENT ROOM
SINK
SINK (SINGLE COMPARTMENT, INTEGRAL WITH COUNTER, REFER TO ARCHITECTURAL PLANS FOR DIMENSIONS AND MOUNTING).
1.FAUCET: SOLID CAST BRASS CONSTRUCTION, CHROME PLATED, GOOSENECK SPOUT 102 BY 127 MM (5 TO 6 INCHES) ABOVE THE RIM, ELECTRONIC SENSOR OPERATED, FOUR-INCH CENTER SET MOUNTING, WIRING BOX, 120/24 VOLT SOLENOID PLUG IN TRANSFORMER, TEE WITH CHECK VALVES, THERMOSTATIC MIXING
VALVE. PROVIDE LAMINAR FLOW CONTROL DEVICE.
2.VALVE: TYPE T/P COMBINATION THERMOSTATIC AND PRESSURE BALANCING WITH LEVER OPERATING HANDLE. VALVE BODY WILL BE COPPER ALLOY. INTERNAL PARTS WILL BE COPPER, NICKEL ALLOY, CRS OR THERMOSTATIC MATERIAL. VALVE INLET AND OUTLET WILL BE 13 MM (1/2 INCH) IPS. PROVIDE EXTERNAL SCREWDRIVER CHECKSTOPS AND TEMPERATURE LIMIT STOP. SET STOPS FOR A MAXIMUM TEMPERATURE OF 35 DEGREES C (95 DEGREES F). VALVE WILL ALSO SERVE
P-418 IN THE SAME ROOM, WHERE APPLICABLE.
3.DRAIN: CAST OR WROUGHT BRASS WITH FLAT GRID STRAINER OFFSET TAILPIECE, CHROME PLATED. PROVIDE COVER PER A.D.A 4-19.4.
4.STOPS: ANGLE TYPE, SEE PARAGRAPH “STOPS”. PROVIDE COVER PER A.D.A 4-19.4.
5.TRAP: CAST COPPER ALLOY, 38 MM BY 32 MM (1 1/2 INCHES BY 1 1/4 INCHES) P-TRAP. ADJUSTABLE WITH CONNECTED ELBOW AND 1.4 MM THICK (17 GAUGE)
TUBING EXTENSIONS TO WALL. EXPOSED METAL TRAP SURFACE AND CONNECTION HARDWARE WILL BE CHROME PLATED WITH A SMOOTH BRIGHT FINISH. SET TRAP
PARALLEL TO WALL. PROVIDE COVER PER A.D.A 4-19.4.
6.PROVIDE COVER FOR EXPOSED PIPING, DRAIN, STOPS AND TRAP PER A.D.A.
SINK TRIM - CHICAGO FAUCET
(116.427.AB.1T)
0.75 0.75 2 1.5
P-805 ROOF HOSE BIBB HOSE BIBB - FREEZELESS ROOF HYDRANT, ONE PIECE VARIABLE FLOW PLUNGER WITH ROD GUIDE, BUILT-IN STORAGE RESEVOIR AND VENTURI SYSTEM TO EVACUATE WATER AND ALLOW DRAIN BACK OPERATION FOR FREEZE PROOF WINTERIZATION WITHOUT A DRAIN CONNECTION, CAST IRON FLANGED HYDRANT SUPPORT WITH UNDER-DECK FLANGE, WELL SEAL BETWEEN SUPPORT AND HYDRANT PIPE WITH EDPM BOOT COVER. SET NOT LESS THAN 18 INCHES OR MORE THAN 36 INCHES ABOVE
ROOF.
PROVIDE WITH ASSE 1052 OR 1057 APPROVED, FIELD TESTABLE, DOUBLE CHECK VALVE BACK FLOW PREVENTER WITH 3/4" THREADED HOSE CONNECTION AT
HYDRANT OUTLET.
WOODFORD (SRH-MS), PRIER
(P-RH4), FREEZE FLOW
(2131RE)
0.75 - - -
NO SCALE
SINK MIXING VALVE
NO SCALE
ROOF HOSE BIBB
Revisions: Date:
35% SCHEMATIC DESIGN 04/20/2023
65% DESIGN DEVELOPMENT 06/16/2023
95% CONSTRUCTION DOCUMENTS 08/30/2023
95% CONSTRUCTION DOCUMENTS RESUBMITTAL 05/08/2024
100% CONSTRUCTION DOCUMENTS 09/09/2024
ACCOMPANYING 36C25225B0024 0002
| Sheets |
| P000 - PLUMBING COVERSHEET |
| P204 - FOURTH FLOOR PLAN - PLUMBING |
| P205 - FIFTH FLOOR PLAN - PLUMBING |
| P206 - ROOF PLAN - PLUMBING |
| P300 - PLUMBING DIAGRAMS |
| PD104 - FOURTH FLOOR PLAN - PLUMBING - DEMOLITION |
| PD105 - FIFTH FLOOR PLAN - PLUMBING - DEMOLITION |