RFQQ 2631 Attach D Answers UWMC NWH Rep.pdf

PDF 2 MB Posted

Attached to
FIRE SPRINKLER SYSTEM TESTING AND INSPECTION
Solicitation number
UWM 2631
Issued by
Adams County, Asotin County, Benton County, Chelan County, Clallam County, Clark County, Columbia County, Cowlitz County, Douglas County, Ferry County, Franklin County, Garfield County, Grant County, Grays Harbor County, Island County, Jefferson County, King County, Kitsap County, Kittitas County, Klickitat County, Lewis County, Lincoln County, Mason County, Okanogan County, Pacific County, Pend Oreille County, Pierce County, San Juan County, Skagit County, Skamania County, Snohomish County, Spokane County, Stevens County, Thurston County, Wahkiakum County, Walla Walla County, Whatcom County, Whitman County, Yakima County, Asotin City, Clarkston City, Clarkston Heights-Vineland CDP, West Clarkston-Highland CDP, Benton City, Chelan City, Chelan Falls CDP, Clallam Bay CDP, Lewisville CDP, Rock Island City, Pacific Beach CDP, Whidbey Island Station CDP, Mercer Island City, Pacific City, Bainbridge Island City, Kingston CDP, Kitsap Lake CDP, Kittitas City, Klickitat CDP, Okanogan City, Anderson Island CDP, Fort Lewis CDP, Fox Island CDP, Herron Island CDP, Ketron Island CDP, North Fort Lewis CDP, Raft Island CDP, Stevenson City, Hat Island CDP, Lake Stevens City, Snohomish City, Spokane City, Spokane Valley City, Puget Island CDP, Garfield Town, Yakima City, Washington

About this file

This document is a Request for Qualifications and Quotations (RFQQ) issued by UW Medicine to establish a pool of qualified and experienced Bidders to provide Automatic Fire Sprinkler System Testing & Inspection at Harborview Medical Center (HMC), UWMC Montlake and UWMC Northwest and its campus buildings, as well as other related Fire Sprinkler Services on an as needed basis. The contract term is unspecified, but the RFQQ requires that Bidders follow the proposal due date provided in the RFQQ document, which supersedes the closing date on WEBS. The RFQQ covers several counties and jurisdictions within the state of Washington.

The RFQQ does not provide details on pricing terms, set asides, incumbents, funding requirements and sources, or contract amounts. It also does not specify any legal language, contract clauses, or other non-essential information. Bidders are expected to submit their qualifications and quotations in response to the RFQQ.

View the file

Other files

File Type Posted
RFQQ 2631 Attach D Answers Final.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part1.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part11.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part12.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part4.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part6.pdf PDF
RFQQ 2631 FIRE SPR SYS TEST INSPECT AMEND 1.doc DOC document
RFQQ 2631 FIRE SPR SYS TEST INSPECT AMEND 3.doc DOC document
RFQQ 2631 Attach D Answers HMC Rep.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part14.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part2.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part3.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part5.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part7.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part9.pdf PDF
RFQQ 2631 Attach D Bidders Questions Final.xlsx XLSX spreadsheet
RFQQ 2631 FIRE SPR SYS TEST INSPECT AMEND 2.doc DOC document
RFQQ 2631 FIRE SPR SYS TEST INSPECT AMEND 4.doc DOC document
RFQQ 2631 Attach D Answers UWMC MTLK Part16.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part8.pdf PDF
RFQQ 2631 Attach D Answers Equip.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part10.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part13.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part15.pdf PDF
RFQQ 2631 Attach D Answers UWMC MTLK Part17.pdf PDF
RFQQ 2631 FIRE SPR SYSTEM TESTING INSPECT.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinklers - Wet Page 1 of 2

Seattle Fire Department Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Building Representative (signature) ___________________________________________________ wet system make: wet system model:

Sprinklers - Wet Page 2 of 2

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

22. Was a signal received at the Central Station monitoring company? N/A Yes No

Sprinklers - Dry Page 1 of 2

Confidence Test Report

Phone 206-386-1448 Confidence Testing Officer 206-615-1068 (fax)

206-233-7219 Red Tag Hotline

SPRINKLER – PREACTION Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type: Annual

Testers Name (Please Print):

SFD Certification Number: SCP-

Identification Number (Required): System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: ______________________ System Model: _____________________

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: Corrected By:

(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Job Number:

Sprinklers - Dry Page 2 of 2

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Yes No

Other Yes No

N/A Yes No

N/A Yes No

Yes No

N/A Yes No

Yes No

Yes

Yes

Yes No

Yes No

1. Trip test conducted?

2. System tripped in DT seconds.

3. Main Drain and Inspector’s Drain flow test conducted?

4. Static pressure:

5. Number of Sprinkler Heads?

6. 2-inch drain?

7. Flow switches, supervisory switches and alarm bells tested?

8. Alarm bell operates?

9. Air compressor refills system in 30 minutes or less?

10. Heat actuation devices tested on pre-action and deluge systems?

11. System inspected and lubricated?

12. Valves are sealed or supervised?

13. Signs are provided on valves?

14. Pumper connections and clapper valves unobstructed and turn freely?

15. Sprinkler heads replaced or successfully sample tested in last 10 years?Date of last test: ______________

16. Sprinkler coverage is acceptable? Yes No

17. Proper number of spare sprinkler heads available with appropriate wrench for each?

Yes No

18. System left in service? Yes No

19. System gauges replaced or calibrated within the last 5 years? Yes No

20. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

21. System drained and restored to normal operation? Yes No

22. Was debris found in the Fire Department Connection (FDC)? Yes No

23. Was the Fire Department Connection (FDC) back flushed in the last 5 years? Yes No

24. Was a signal received at the Central Station monitoring company? N/A Yes No

25. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7)

Yes No

26. Was an internal pipe and valve inspection performed within the last 5 years? Date Yes No

No

No

Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

FLOWS

Building :

Address:

Phone:

Contact: Date:

STAIRS FLOOR SUPERVISORY

WATER

FLOW TIME STAIRS FLOOR SUPERVISORY

WATER

FLOW TIME COMMENTS

Confidence Test Report

SPRINKLER – DRY SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number (Required): System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Building Representative (signature) ___________________________________________________

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General Yes No

Yes No

Other Yes No N/A Yes No N/A Yes No

Yes No

N/A Yes No

Yes No Yes No Yes No Yes No

1. Trip test conducted?

2. System tripped in seconds.

3. Main Drain and Inspector’s Drain flow test conducted?

4. Static pressure: psi

5. Number of Sprinkler Heads? ____

6. 2-inch drain?

7. Flow switches, supervisory switches and alarm bells tested?

8. Alarm bell operates?

9. Air compressor refills system in 30 minutes or less?

10. Heat actuation devices tested on pre-action and deluge systems?

11. System inspected and lubricated?

12. Valves are sealed or supervised?

13. Signs are provided on valves?

14. Pumper connections and clapper valves unobstructed and turn freely?

15. Sprinkler heads replaced or successfully sample tested in last 10 years?

Date of last test: ______________ Yes No

16. Sprinkler coverage is acceptable? Yes No

17. Proper number of spare sprinkler heads available with appropriate wrench for each? Yes No

18. System left in service? Yes No

19. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

20. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

21. System drained and restored to normal operation? Yes No

22. Was debris found in the Fire Department Connection (FDC)? Yes No

23. Was the Fire Department Connection (FDC) back flushed in the last 5 years?

Date of last back flush: Yes No

24. Was a signal received at the Central Station monitoring company? N/A Yes No

25. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

26. Was an internal pipe and valve inspection performed within the last 5 years? Date Performed: Yes No

SPRINKLER – DRY SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number (Required): System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Building Representative (signature) ___________________________________________________

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting

Yes No

Yes No

Other Yes No N/A Yes No N/A Yes No

Yes No

N/A Yes No

Yes No Yes No Yes No Yes No

1. Trip test conducted?

2. System tripped in seconds.

3. Main Drain and Inspector’s Drain flow test conducted?

4. Static pressure: psi

5. Number of Sprinkler Heads? ____

6. 2-inch drain?

7. Flow switches, supervisory switches and alarm bells tested?

8. Alarm bell operates?

9. Air compressor refills system in 30 minutes or less?

10. Heat actuation devices tested on pre-action and deluge systems?

11. System inspected and lubricated?

12. Valves are sealed or supervised?

13. Signs are provided on valves?

14. Pumper connections and clapper valves unobstructed and turn freely?

15. Sprinkler heads replaced or successfully sample tested in last 10 years?

Date of last test: ______________ Yes No

16. Sprinkler coverage is acceptable? Yes No

17. Proper number of spare sprinkler heads available with appropriate wrench for each? Yes No

18. System left in service? Yes No

19. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

20. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

21. System drained and restored to normal operation? Yes No

22. Was debris found in the Fire Department Connection (FDC)? Yes No

23. Was the Fire Department Connection (FDC) back flushed in the last 5 years?

Date of last back flush: Yes No

24. Was a signal received at the Central Station monitoring company? N/A Yes No

25. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

Confidence Test Report

206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline

SPRINKLER – WET SYSTEM Certification Given (One System per Report) RED YELLOW WHITE

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number: System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting and testing requirements.

General

Yes No

Other Yes No

N/A Yes No

N/A Yes No

N/A Yes No

Yes No

Yes No

1. Main Drain and Inspector’s Drain flow test conducted?

2. Static pressure: Flow pressure:

3. Number of Sprinkler Heads:

4. 2-inch drain?

5. Flow switches, supervisory switches and alarm bells tested?

6. Pressure regulating valves tested?

7. Alarm bell operates?

8. System inspected and lubricated?

9. Valves are sealed or supervised?

10. Signs are provided on valves? Yes No

Yes No

Yes No

Yes No

Yes No

Yes No

11. Pumper connections and clapper valves unobstructed and turn freely?

12. Sprinkler coverage is acceptable?

13. Have the sprinkler heads been replaced or successfully sample test in the last 50 years? Date of last test: ___________

14. Proper number of spare sprinkler heads available with appropriate wrenches for each?

15. System left in service?

16. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

18. Was debris found in the Fire Department Connection (FDC)? Yes No

19. Was the Fire Department Connection (FDC) back flushed within the last 5 years? Date of last back flush:____________ Yes No

20. Was an internal pipe and valve inspection performed within the last 5 years?

Yes No

21. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number (Required): System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Building Representative (signature) ___________________________________________________

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting

Yes No

Yes No

Other Yes No N/A Yes No N/A Yes No

Yes No

N/A Yes No

Yes No Yes No Yes No Yes No

1. Trip test conducted?

2. System tripped in seconds.

3. Main Drain and Inspector’s Drain flow test conducted?

4. Static pressure: psi

5. Number of Sprinkler Heads? ____

6. 2-inch drain?

7. Flow switches, supervisory switches and alarm bells tested?

8. Alarm bell operates?

9. Air compressor refills system in 30 minutes or less?

10. Heat actuation devices tested on pre-action and deluge systems?

11. System inspected and lubricated?

12. Valves are sealed or supervised?

13. Signs are provided on valves?

14. Pumper connections and clapper valves unobstructed and turn freely?

15. Sprinkler heads replaced or successfully sample tested in last 10 years?

Date of last test: ______________ Yes No

16. Sprinkler coverage is acceptable? Yes No

17. Proper number of spare sprinkler heads available with appropriate wrench for each? Yes No

18. System left in service? Yes No

19. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

20. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

21. System drained and restored to normal operation? Yes No

22. Was debris found in the Fire Department Connection (FDC)? Yes No

23. Was the Fire Department Connection (FDC) back flushed in the last 5 years?

Date of last back flush: Yes No

24. Was a signal received at the Central Station monitoring company? N/A Yes No

25. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

CONFIDENCE TEST REPAIRS

Occupancy Address: Occupancy Name:

Responsible Person First & Last Name: Phone Number:

Responsible Person Address, City, State, Zip:

Responsible Party E–Mail Address

Date of Inspection: Inspection Frequency/Type:

Testers Name (Please Print):

SFD Certification Number:

Identification Number (Required): System Location:

Central station monitoring?

Monitoring Required?

Yes Yes

No No

Monitoring Company Name:

System Make: System Model:

SEATTLE FIRE CODE VIOLATIONS FOUND: (If additional room is needed, please add a separate sheet)

CORRECTIONS MADE: Date Corrected: __________ Corrected By: ___________________________ (If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -

This certifies that this fire and life safety system has been properly inspected for reliability to cover the Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that discrepancies are noted and have been reported to the building Owner/Manager for corrective action.

Signature of Tester: Phone #

Building Representative (signature) ___________________________________________________

The items on the checklists below shall be inspected and tested. This list does not constitute all of the required inspecting and testing of the fire and life safety system. Refer to the Seattle Fire Department Fire Code for inspecting

Yes No

Yes No

Other Yes No N/A Yes No N/A Yes No

Yes No

N/A Yes No

Yes No Yes No Yes No Yes No

1. Trip test conducted?

2. System tripped in seconds.

3. Main Drain and Inspector’s Drain flow test conducted?

4. Static pressure: psi

5. Number of Sprinkler Heads? ____

6. 2-inch drain?

7. Flow switches, supervisory switches and alarm bells tested?

8. Alarm bell operates?

9. Air compressor refills system in 30 minutes or less?

10. Heat actuation devices tested on pre-action and deluge systems?

11. System inspected and lubricated?

12. Valves are sealed or supervised?

13. Signs are provided on valves?

14. Pumper connections and clapper valves unobstructed and turn freely?

15. Sprinkler heads replaced or successfully sample tested in last 10 years?

Date of last test: ______________ Yes No

16. Sprinkler coverage is acceptable? Yes No

17. Proper number of spare sprinkler heads available with appropriate wrench for each? Yes No

18. System left in service? Yes No

19. System gauges replaced or calibrated within the last 5 years?

Year changed: Yes No

20. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage? Yes No

21. System drained and restored to normal operation? Yes No

22. Was debris found in the Fire Department Connection (FDC)? Yes No

23. Was the Fire Department Connection (FDC) back flushed in the last 5 years?

Date of last back flush: Yes No

24. Was a signal received at the Central Station monitoring company? N/A Yes No

25. Is the hydraulic nameplate installed and visible on riser, if No then Yellow Tag.

(Ref: NFPA 25 5.2.7) Yes No

1560 N 115th - Q2 - 4.23.2024 (1)_Redacted.pdf
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
1550 N 115th - Q2 - 4.23.2024_Redacted.pdf
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
Sprinkler – Dry System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Trip test conducted?
3. Main Drain and Inspector’s Drain flow test conducted?
4. Static pressure: psi
19. System gauges replaced or calibrated within the last 5 years? Year changed:
Sprinkler – Dry System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Trip test conducted?
3. Main Drain and Inspector’s Drain flow test conducted?
4. Static pressure: psi
19. System gauges replaced or calibrated within the last 5 years? Year changed:
10330 Meridian - Q2 - 4.23.2024_Redacted.pdf
Sprinkler – Wet System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Main Drain and Inspector’s Drain flow test conducted?
2. Static pressure: 70. Flow pressure: 60 .
3. Number of Sprinkler Heads: unknown
5. Flow switches, supervisory switches and alarm bells tested?
8. System inspected and lubricated?
10. Signs are provided on valves?
16. System gauges replaced or calibrated within the last 5 years? Year changed: 2012
17. Sprinkler heads free of corrosion, paint, obstructions and/or physical damage?
Sprinkler – Dry System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Trip test conducted?
3. Main Drain and Inspector’s Drain flow test conducted?
4. Static pressure: psi
19. System gauges replaced or calibrated within the last 5 years? Year changed:
Sprinkler – Dry System
Certification Given
WHITE
CONFIDENCE TEST
YELLOW
RED
REPAIRS
Seattle Fire Code Violations Found: (If additional room is needed, please add a separate sheet)
Corrections Made:
Date Corrected: __________
Corrected By: ___________________________
(If additional room is needed, please add a separate sheet) SFD Certification Number: SCP -
This certifies that this fire and life safety system has been properly inspected for reliability to cover the
Items listed in this report and is consistent with Seattle Fire Department Fire Code standards, and that
discrepancies are noted and have been reported to the building Owner/Manager for corrective action.
General
1. Trip test conducted?
3. Main Drain and Inspector’s Drain flow test conducted?
4. Static pressure: psi
19. System gauges replaced or calibrated within the last 5 years? Year changed:
servicetrade_job_assets-wet_sprinkler-1-make: Gem
servicetrade_job_assets-wet_sprinkler-1-model: f2001
servicetrade_job_assets-pre_action_valve-1-make: Reliable DDX Single
servicetrade_job_assets-pre_action_valve-1-model: Interlock
1:
servicetrade_location_street: 1560 N 115th St
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow1:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow2:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow3:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow4:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow5:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row1:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row2:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row3:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row4:
servicetrade_location_city: Seattle
servicetrade_location_postal_code: 98145
servicetrade_job_dates: 04/23/2024 08:00am PDT
servicetrade_location_name: UW Medical Office NW
servicetrade_customer_phone:
Text16: P-07865
servicetrade_job_assets-wet_sprinkler-1-location_in_site: E Wing
servicetrade_job_assets-wet_sprinkler-1-monitoring_company_name:
Check Box20: Off
Check Box21: Off
Check Box22: Off
Check Box23: Yes
Check Box24: Yes
Check Box25: Yes
Check Box26: Off
servicetrade_job_number: 34363635
Check Box269: Yes
Check Box271: Off
servicetrade_job_assets-wet_sprinkler-1-make: Reliable
servicetrade_job_assets-wet_sprinkler-1-model: Alam
Date of last back flush: 1/22
Text28: 80
Text29: 65
servicetrade_job_assets-wet_sprinkler-1-head_qty:
Text31:
Text32:
Text33:
Check Box34: Off
Check Box35: Yes
Check Box36: Off
Check Box37: Yes
Check Box38: Off
Check Box39: Yes
Check Box40: Off
Check Box41: Yes
Check Box42: Off
Check Box43: Yes
Check Box44: Off
Check Box45: Yes
Check Box46: Off
Check Box47: Yes
Check Box48: Off
Check Box49: Yes
Check Box50: Off
Check Box51: Off
Check Box52: Yes
Check Box53: Yes
Check Box54: Off
Check Box55: Off
Check Box56: Yes
Check Box57: Off
Check Box58: Off
Check Box59: Yes
Check Box60: Yes
Check Box61: Off
Check Box62: Yes
Check Box63: Off
Check Box64: Yes
Check Box65: Off
Check Box66: Yes
Check Box67: Off
Check Box68: Off
Check Box69: Yes
Check Box70: Yes
Text79: 1/22
CORRECTIONS MADE Date Corrected:
Corrected By:
servicetrade_location_state: WA
servicetrade_location_email:
Check Box71: Off
Check Box72: Yes
Check Box73: Off
Check Box74: Yes
Check Box75: Off
Check Box76: Off
Check Box77: Yes
Check Box78: Off
Text1: Qt
Check Box19: Off
Check Box27: Off
servicetrade_contact_phone: (206) 598-2950
servicetrade_contact_email: clintms@uw.edu
Text39: P-07865
servicetrade_job_assets-pre_action_valve-1-location_in_site: MRI room
Text41:
Check Box2: Yes
Check Box3: Off
Check Box4: Yes
Check Box5: Off
Check Box6: Yes
Check Box7: Off
Check Box8: Off
Check Box9: Off
Check Box10: Off
Check Box11: Yes
Check Box12: Yes
Check Box13: Off
Check Box14: Off
Check Box15: Yes
Check Box16: Off
Check Box17: Yes
Check Box18: Off
Check Box28: Off
Check Box29: Yes
Check Box30: Off
Check Box31: Yes
Check Box32: Off
Check Box33: Yes
Text63: 3
Text64: 90
Text65:
Text67:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow1:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow2:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow3:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow4:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow5:
CORRECTIONS MADE Date Corrected:
Corrected By:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row1: 27 sec waterflow
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row2:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row3:
CORRECTIONS MADE Date Corrected Corrected By If additional room is needed please add a separate sheet SFD Certification Number SCP Row4:
servicetrade_location_street: 1560 N 115th St
servicetrade_location_city: Seattle
servicetrade_location_state: WA
servicetrade_location_postal_code: 98145
servicetrade_job_dates: 04/23/2024 08:00am PDT
servicetrade_location_name: UW Medical Office NW
servicetrade_customer_phone:
servicetrade_location_email:
Text16: P-07865
servicetrade_job_assets-wet_sprinkler-1-location_in_site: basement
servicetrade_job_assets-wet_sprinkler-1-monitoring_company_name:
Check Box20: Off
Check Box21: Off
Check Box22: Yes
Check Box23: Yes
Check Box24: Off
Check Box25: Yes
Check Box26: Off
servicetrade_job_number: 34363635
Text1: Qt
Check Box269: Off
Check Box271: Off
Date of last back flush: 1/22
Text28: 99
Text29: 65
servicetrade_job_assets-wet_sprinkler-1-head_qty:
Text31:
Text32:
Text33:
Check Box34: Yes
Check Box35: Off
Check Box36: Off
Check Box37: Off
Check Box38: Yes
Check Box39: Off
Check Box40: Yes
Check Box41: Off
Check Box42: Yes
Check Box43: Off
Check Box44: Off
Check Box45: Off
Check Box46: Yes
Check Box47: Off
Check Box48: Yes
Check Box49: Off
Check Box50: Yes
Check Box51: Off
Check Box52: Yes
Check Box53: Off
Check Box54: Yes
Check Box55: Off
Check Box56: Yes
Check Box57: Off
Check Box58: Yes
Check Box59: Off
Check Box60: Yes
Check Box61: Off
Check Box62: Yes
Check Box63: Off
Check Box64: Yes
Check Box65: Off
Check Box66: Yes
Check Box67: Off
Check Box68: Off
Check Box69: Yes
Check Box70: Yes
Check Box71: Off
Check Box72: Yes
Check Box73: Off
Check Box74: Yes
Check Box75: Off
Check Box76: Off
Check Box77: Yes
Check Box78: Off
Text79: 1/22
2:
SEATTLE FIRE CODE VIOLATIONS FOUND If additional room is needed please add a separate sheetRow5:
servicetrade_customer_phone:
Text16: P-07865
servicetrade_job_assets-wet_sprinkler-1-location_in_site: Easy street
servicetrade_job_assets-wet_sprinkler-1-monitoring_company_name:
Check Box20: Off
Check Box21: Off
Check Box22: Yes
Check Box23: Yes
Check Box24: Off
Check Box25: Yes
Check Box26: Off
Check Box269: Yes
Check Box271: Off
servicetrade_job_assets-wet_sprinkler-1-make: Central
servicetrade_job_assets-wet_sprinkler-1-model: Alam
Date of last back flush: 1/22
Text28: 80
Text29: 65
servicetrade_job_assets-wet_sprinkler-1-head_qty:
Text31:
Text32:
Text33:
Check Box34: Yes
Check Box35: Off
Check Box36: Off
Check Box37: Off
Check Box38: Yes
Check Box39: Off
Check Box40: Yes
Check Box41: Off
Check Box42: Yes
Check Box43: Off
Check Box44: Off
Check Box45: Off
Check Box46: Yes
Check Box47: Off
Check Box48: Yes
Check Box49: Off
Check Box50: Yes
Check Box51: Off
Check Box52: Yes
Check Box53: Off