RFQQ 2631 Attach D Answers UWMC MTLK Part6.pdf
PDF 4 MB Posted
- Attached to
- FIRE SPRINKLER SYSTEM TESTING AND INSPECTION
- Solicitation number
- UWM 2631
- Issued by
- Adams County, Asotin County, Benton County, Chelan County, Clallam County, Clark County, Columbia County, Cowlitz County, Douglas County, Ferry County, Franklin County, Garfield County, Grant County, Grays Harbor County, Island County, Jefferson County, King County, Kitsap County, Kittitas County, Klickitat County, Lewis County, Lincoln County, Mason County, Okanogan County, Pacific County, Pend Oreille County, Pierce County, San Juan County, Skagit County, Skamania County, Snohomish County, Spokane County, Stevens County, Thurston County, Wahkiakum County, Walla Walla County, Whatcom County, Whitman County, Yakima County, Asotin City, Clarkston City, Clarkston Heights-Vineland CDP, West Clarkston-Highland CDP, Benton City, Chelan City, Chelan Falls CDP, Clallam Bay CDP, Lewisville CDP, Rock Island City, Pacific Beach CDP, Whidbey Island Station CDP, Mercer Island City, Pacific City, Bainbridge Island City, Kingston CDP, Kitsap Lake CDP, Kittitas City, Klickitat CDP, Okanogan City, Anderson Island CDP, Fort Lewis CDP, Fox Island CDP, Herron Island CDP, Ketron Island CDP, North Fort Lewis CDP, Raft Island CDP, Stevenson City, Hat Island CDP, Lake Stevens City, Snohomish City, Spokane City, Spokane Valley City, Puget Island CDP, Garfield Town, Yakima City, Washington
About this file
This document is a Report of Inspection / Test for the Annual NFPA 25 and Annual NFPA 72 conducted at the University of Washington Medical Center (UWMC) Montlake Tower building located in Seattle, Washington. The report provides details on the inspection and testing of the facility's fire alarm system, including the fire pump, alarm systems monitoring, secondary power, notification appliances, emergency communication equipment, and auxiliary functions. It also includes information on the control panel and battery readings.
The state and local contract opportunity is for UW Medicine to establish a pool of qualified and experienced bidders to provide Automatic Fire Sprinkler System Testing & Inspection services at Harborview Medical Center (HMC), UWMC Montlake, and UWMC Northwest and its campus buildings. The contract will also cover other related fire sprinkler services on an as-needed basis. The solicitation is open to bidders across multiple Washington counties and cities.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report of Inspection / Test Annual NFPA 25, Annual NFPA 72
202~01-06 Conducted by: Mike Sanders - Technician w Property Account
Medicine UWMC - Montlake Tower Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street .
1959 NE Pacific St Seattle Washington 98195 u IV : HS IT Y II/ WA II ING I •
Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
Report of Inspection / Test for Asset - Fire Pump ATS #14
Transfer Switch Information
Description Fire Pump Manufacturer Russelectrl
ATS #14 C
Model FTA1930- Serial Number 630832-
AM200B 01RE
Inspection and Testing Form - UWMC - Montlake Tower - Alarm Systems
Monitoring Entity
Contact Name Simplex Telephone 18007522490
Reference Number 37-1080 Type Transmission Dialer
Approving Agency
Contact Name Seattle Fire Department Telephone N/A
Email N/A Service Type Seattle Fire Department
System Type
Control Unit Manufacturer Johson Controls Inc Model Number 4100ES
Circuit Styles Nodes Software Revision. 12.06
Date Last Serviced 2024-02-21 Last Date and Software or Configuration 2024-02-21 was Revised
Number of Circuits 1
Power Supply
Main Nominal Voltage 120 Main Nominal Amps N/A
Overcurrent Protection N/A Panel Board Location SA1007
Disconnecting Means Location N/A Secondary Standby NIA
Storage Battery: Amp Hour Rating NIA Calculated Capacity to operate system NIA (Hours)
Engine-driven generator dedicated to fire N/A Location of fuel storage N/A alarm system
Has Emergency System described In NFPA YES Has L1cally required standby described In YES 70, Article 700 NFPA 0, Article 701 .
Has Optional standby system described In YES NFPA 70, Article 702, which also meets the performance requirements of Article 700 ·or 701
C~pyrlght 2024 Inspect Point
Report of Inspection/ Test
2024-01-06 Conducted by: Mike Sanders - Technician w Property A.ccount
Medicine UWMC - Montlake Tower Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street 1959 NE Paclfli:: St Seattle Washington 98195 IVERSITY o.f \VA SIi iNG 0 Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
NOTIFICATIONS MADE PRIOR TO ANY TESTING Yes No N/A Who Time
Monitoring Entity 0 D D Dlsbatcher 6:00
Building Occupants 0 D D Aaron Schwelkl 6:00
Building Management 0 D D Mike Sanders 6:00
Other (Specify) 0 D D UWMC • Dlsbatch 6:00
AHJ Notified of Any Impairments 0 D D SFD 6:00
SYSTEM TESTS AND INSPECTIONS Visual Functional Pass/Fall Comments
Supervision Yes Yes Pass
Local Annunciator Yes Yes Pass
Remote Annunciator Yes Yes Pass
Power Extender Panels Yes Yes Pass
Isolation Modules Yes Yes Pass
Sound Pressure Level- Ambient Yes Yes Pass
Sound Pressure Level- Alarm Yes Yes Pass
System Intelligibility · CSI Yes Yes Pass
System Intelligibility- STI Yes Yes Pass
Functional Test Yes Yes Pass
Reset/Power down Test Yes Yes Pass
UPS Power Test Yes Yes Pass
CCU Security Mechanism Yes Yes Pass
Prerecorded Message Content NIA NIA NIA
Prerecorded Message Activation NIA NIA NIA
Software Backup Performed NIA NIA NIA
Test Backup Software Yes Yes Pass
Fire Alarm to MNS Interface Yes Yes Pass
MNS to Fire Alarm Interface Yes Yes Pass
In-building MNS to wide area MNS Yes Yes Pass
MNS to direct recipient MNS Yes Yes Pass
Other (Specify) NIA N/A NIA
SECONDARY POWER Visual Functional Pass/Fall Comments
Copyright 2024 Inspect Point i=
Report of Inspection/ Test Annual NFPA 25, Annual NFPA 72
2024-01-06 Conducted by: Mike Sanders - Technician w Property ·Account
Medicine UWMC - Montlake Tower Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street 1959 NE Pacific St Seattle Washington 98195 L IVEH SI y 11/ WA II ING Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
Battery Condition Yes Yes Pass
Load Voltage Yes Yes Pass
Discharge Test Yes Yes Pass
Charger Test Yes Yes Pass
Specific Gravity Yes Yes Pass
Transient Suppressors Yes Yes Pass
Remote Annunciators Yes Yes Pass
NOTIFICATION APPLIANCES Visual Functional Pass/Fail Comments
Audible Yes Yes Pass
Visual Yes Yes Pass
Speakers Yes Yes Pass
Voice Clarity Yes Yes Pass
EMERGENCY COMMUNICATION Visual Functional Pass/Fall Comments
EQUIPMENT
Phone Set NIA NIA NIA
Phone Jacks NIA NIA NIA
Off-Hook Indicator NIA NIA NIA
Ampllfler(s) Yes Yes Pass
Tone Generator(s) Yes Yes Pass
Call-In Signal NIA NIA NIA
System Performance Yes Yes Pass
System Audibility Yes Yes Pass
System Intelligibility Yes Yes Pass
Radio Communication Enhancement System Yes Yes Pass
Area of Refuge Communication System Yes Yes Pass
Elevator Emergency Communication System Yes Yes Pass
Other (Specify) N/A N/A N/A
AUXILIARY FUNCTIONS/INTERFACE Visual Functional Pass/Fall Comments
EQUIPMENT/SPECIAL HAZARDS
Door-Releasing Devices Yes Yes Pass
Fan Shutdown Yes Yes Pass
2024-01-06 Conducted by: Mike Sanders - Technician w Property Account
Medicine UWMC - Montlake Tower Built 2012 Unlversli of Washington Medical Center Building#: 3 1959 Ne aclflc Street 1959 NE Pacific St Seattle Washington 98195 NIVF. SITY 11J WA SII ING O 1• Seattle WA 98195 206-598-6247 .
Print Date: 2024-03-19 sandem3@uw.edu
Smoke Management/Smoke Control Yes Yes Pass
Smoke Damper Operation Yes Yes Pass
Smoke Shutter Release NIA N/A N/A
Door Unlocking Yes Yes Pass
Elevator Recall .Yes Yes Pass
Elevator Shunt-Trip Yes Yes Pass
MNS override of FA signals No No
Other (Specify) No No
SUPERVISING STATION MONITORING EC 02.03.05 Yes No N/A Who Time
EP0S
Alarm Signal 0 D D Dlsbatch 10:00
Alarm Restoration 0 D D Aaron Schwelkl 10:00
Supervisory Signal 0 ' D D Dlsbatch 6:00
Supervisory Restoration 0 D D Aaron Schwelkl 10:00
Trouble Restoral 0 D D Aaron Schwelkl 10:00
NOTIFICATIONS THAT TESTING IS COMPLETE Yes No N/A Who Time
Monitoring Agency 0 D D Dlsbatch 10:00
Building Occupants 0 D D Aaron Schwelkl 10:00
Building Management 0 D D Mike Sanders 10:00
AHJ Notified of Any Impairments 0 D D SFD 10:00
Other (Specify) 0 D D UWMC- FOMS& 10:00 Dlsbatch
ALARM INITIATING DEVICES AND CIRCUIT INFORMATION Qty Installed Qty Tested
Manual Stations
Ion Detectors
Photo Detectors
Duct Detectors
Heat Detectors
Waterflow Switches
Supervisory Switches
Other (Specify)
2024-01-06 Conducted by: Mike Sanders - Technician w Property Account ·
Medicine UWMC - Montlake Tower Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street 1959 NE Pacific St Seattle Washington 98195 1 IV RSI TY uf W.\'SII INGTO 1•
Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
ALARM INDICATING DEVICE INFORMATION Qty Installed Qty Tested
Bells
Horns
Chimes
Strobes
Horn Strobes
Speakers
Speaker Strobes
Other (Specify)
2024-01-06 Conducted by: Mike Sanders - Technician w Property Account
Medici UWMC - Montlake Tower e Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street 1959 NE Pacific St Seattle Washington 98195 U IVEH SITY 11/ W Sii lNGT N.
Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
Control Panel & Battery Readings control Panel Information
Location Manufacturer Model # of Batteries
3SA Simplex 4100ES 2
Battery Size Date Installed Replacement Date
110AH 03/01/2021 03/01/2026
Control Panel
Interface Equipment Yes · Lamps/ LEDs Yes
Fuses Yes Primary Power Supply (AC) Yes
Trouble Switches Yes Secondary Power Supply (DC) Yes
Disconnect Switches Yes Pass/ Fall Pass
Control Panel Batteries
Battery Voltage w Charger Battery Voltage w/o Charger
Lo.ad Test%
2024-01-06 Conducted by: Mike Sanders - Technician w Property Account
Medicine UWMC - Montlake Tower Built 2012 Unlverslt~ of Washington Medical Center Building#: 3 1959 Ne aclflc Street · 1959 NE Pacific St Seattle Washington 98195 ' I\' RS ITY 11/ WA SII ING N.
Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
Additional Control Panels ·
Control Panel Information
Location Manufacturer Model # of Batteries
CUP Simplex 4009 2
Battery Size Date Installed Replacement Date
7AH 02/01/2021 02/01/2026
Control Panel
Interface Equipment Yes Lamps I LEDs Yes
Fuses Yes Primary Power Supply (AC) Yes
Trouble Switches Yes Secondary Power Supply (DC) Yes
Disconnect Switches Yes Pass/ Fall Pass
Control Panel Batteries
Battery Voltage w Charger Battery Voltage w/o Charger
Load Test%
Control Panel Information
Location Manufacturer Model # of Batteries
1SA Simplex 4009 2
Battery Size Date Installed Replacement Date
7AH 02/01/2021 02/01/2026
Control Panel
Interface Equipment Yes Lamps/ LEDs Yes
Fuses Yes Primary Power Supply (AC) Yes
Trouble Switches Yes Secondary Power Supply (DC) Yes
Disconnect Switches Yes Pass/ Fall Pass
Control Panel Batteries
Battery Voltage w Charger Battery Voltage w/o Charger
Load Test%
Control Panel Information
Location Manufacturer Model # of Batteries
2SA· LOWER Simplex 4009 2
Copyright 2024 Inspect Point .
2024-01-06 Conducted by: Mike Sanders - Technician w Property Account
Medicine UWMC - Montlake Tower Built 2012 University of Washington Medical Center Building#: 3 1959 Ne Pacific Street 1959 NE Pacific St Seattle Washington 98195 1 IVERSITY o/ WA II ING .
Seattle WA 98195 206-598-6247 Print Date: 2024-03-19 sandem3@uw.edu
Battery Size, Date Installed Replacement Date
7AH 02/01/2021 02/01/2026
Control Panel
Interface Equipment Yes Lamps /LEDs Yes
Fuses Yes Primary Power Supply (AC) Yes
Trouble Switches Yes Secondary Power Supply (DC) Yes
Disconnect Switches Yes Pass/ Fall Pass
Control Panel Batteries
Battery Voltage w Charger Battery Voltage w/o Charger
Load Test%
Control Panel Information
Location Manufacturer Model # of Batteries
2SA· UPPER Simplex 4009 2
Battery Size Date Installed Replacement Date
7AH 02/01/2021 02/01/2026
Control Panel
Interface Equipment Yes Lamps/ LEDs Yes
Fuses Yes Primary Power Supply (AC) Yes
Trouble Switches Yes Secondary Power Supply (DC) Yes
Disconnect Switches Yes Pass/ Fall Pass
Control Panel Batteries
Battery Voltage w Charger Battery Voltage w/o Charger
Load Test%
Control Panel Information
Location Manufacturer Model # of Batteries
3SA Simplex 4009 2
Battery Size Date Installed Replacement Date
7AH 03/01/2023 02/29/0028
Control Panel
Interface Equipment Yes Lamps/LEDs Yes