These architectural construction documents for the Grand Village of the Natchez Indians Expansion project in Natchez, Mississippi, detail floor plans and reflected ceiling plans for a new tribal history center. The documents, prepared by Eley Guild Hardy Architects on April 17, 2025, show a comprehensive design for a facility featuring multiple functional spaces including a permanent exhibit gallery, offices, conference rooms, restrooms, break rooms, lobbies, and support areas. The floor plans (A103) and reflected ceiling plans (A202 and A203) provide precise architectural layouts with detailed measurements, room designations, and technical annotations, indicating a total building footprint with multiple interconnected sections and grid-based structural design.
The architectural drawings include extensive technical notes specifying construction requirements, such as interior dimension measurements, ceiling types, mechanical and electrical fixture coordination, and specific construction guidelines. The plans reveal a complex building design with varying ceiling heights, multiple ceiling systems (including acoustical tiles, gypsum board, and metal soffit panels), and precise spatial relationships between different functional areas. Specific design elements like control joints, sprinkler head placements, and access panel requirements are meticulously documented, suggesting a high-detail approach to the museum and cultural center's construction that will support the project's goal of preserving and presenting Natchez Indian history.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ref.
AA
BB
CC
DD
EE
FF
GG
HH
JJ
A304
A304
15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0"
CONFERENCE
OFFICE 1
DIRECTOR
BREAK ROOM
OFFICE 3
ASSISTANT DIR.
WAITING & CUBICLES
PERMANENT EXHIBIT GALLERY
MANAGER/STORAGE
CLEAN STORAGE
FAM. REST./LACTATION
CUSTODIAL
VESTIBULE
OFFICE 2
LOBBY / ATRIUM
MEN'S RESTROOM
WOMEN'S RESTROOM
VESTIBULE
CORRIDOR
CORRIDOR
170A
170B
186A 186B
180A
146B 166A
M A
T C
H L
IN
E
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
166B
HVAC
30' - 4 1/2" 14' - 7 1/2" 15' - 5"
61' - 9 1/4"
HVAC
HVAC
10' - 2 1/4"
A407
A507
A507
A504
C.J. C.J. C.J. C.J. C.J. C.J.
C.J.
A505
A505 -
9 9
11 11
4"
3 7/8"
148A
148B
A106
A106
A106
A106
A106
154A
154B
A106
A106
A106
A106
A106
A106
A106
A106
A107
A107
A106
A107
A106
LINE OF ROOF EAVE
DOTTED ABOVE
A107
F.D.
E.D.F.
BOTTLE FILLER
A107
A106
A106
A106
A107
A107
A107
A107
A107
A107
14' - 8" 61' - 2" 10' - 7" 6' 7 1/4" 30' - 9" 11' - 2 3/4"
1' - 1 5/8"
A107
1' - 1 5/8" 60' - 10" 14' - 3 3/4" 18' - 9 1/4" 4'- 11 1/2" 10' - 0" 11' - 1 1/2"
1' - 1 5/8"
A105
A105
A107
G
G
H
J
J
K
G
G
K
/8
/8
/4
/2
/4
/8
/2
/2
/8
/8
A407
/8
/2
/4
/4
/8
/8
/4
/2
/4
A300
A301
A302
A303
A303
A407
/4
3"
3' - 5 3/8"
7' - 6" 2' - 8" 1' - 1 5/8" 60' - 0" 1' - 1 5/8" 13' - 10 3/8" 3" 7' - 2 5/8" 30' - 0" 8' - 8"
136' - 1 5/8" (OVERALL FROM GRID LINE 19)
A407
SIMILAR
FD
FDFD
FD
/4
/4
F.F.E. 111.39
M.T.
EFB EFB EFB EFB
EFB EFB EFB EFB
EFB EFB EFB EFB
EFB EFB EFB EFB
MECH. MECH.
M E
C H
M
E C
H
158 160
REFRIGERATOR
(DOTTED N.I.C.)
DISHWASHER
(DOTTED N.I.C.)
+111.35
+111.17
+111.17
+111.35 +111.35 +111.35
+111.35
+111.17 111.17+
+109.50
+109.50
+109.50111.35+
+109.50
+109.50
+110
+110
+110
+110.50
A B C
1. DO NOT SCALE DRAWIINGS. IF DIMENSIONS ARE IN QUESTION, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION
FROM THE ARCHITECT BEFORE CONTINUING WITH THE CONSTRUCTION.
2. ALL INTERIOR DIMENSIONS ARE TAKEN FROM FACE OF METAL STUDS
UNLESS OTHERWISE NOTED.
3. SEE "I" SHEETS FOR INTERIOR FINISH INFORMATION.
4. SEE "LS" SHEETS FOR LIFE SAFETY INFORMATION INCLUDING
REQUIRED FIRE RATINGS AND FIRE EXTINGUISHER, FIRE EXTINGUISHER
CABINET LOCATIONS.
5. SEE SHEETS A200,A202, AND A203 FOR REFLECTED CEILING PLANS (RCP)
6. SEE SHEET A124 ROOOF PLAN FOR ROOF INFORMATION, AND SHEETS
A202, AND A203 FOR ROOF DETAILS.
7. SEE SHEET A500 FOR PARTITION TYPES.
8. ALL DOOR FRAMES SHALL BE 4" FROM ADJACENT WALLS UNLESS NOTED
OTHERWISE.
9. CONTRACTOR SHALL COORDINATE SLAB RECESSES WITH STRUCTURAL
DRAWINGS. WHERE RECESSES ARE IN QUESTION, PLEASE CLARIFY
LOCATION AND DEPTHS WITH ARCHITECT PRIOR TO POURING ANY
CONCRETE.
10. SEE CONSULTANG DRAWINGS FOR CIVIL, STRUCTURAL, FIRE PROTECTION,
MECHANICAL, PLUMBING,M AND ELECTRICAL INFORMATION.
11. EXISTING OPENING TO BE CLOSED WITH 8" AND 4" CMU MATCHING EXISTING
MASONRY WALL CONSTRUCTION.
12. EXTEND EXISTING STUCCO PILASTERS TO DIMENSIONS SHOWN ON
PLAN. INSTALL 4" CMU BACKUP AS SHOWN HATCHED ON PLAN AND
APPLY STUCCO FINISH WALL SYSTEM TO MATCH EXISTING STUCCO
THICKNESS AND TEXTURE. ANCHOR 4" CMU BACKUP TO EXISTING
CMU SUBSTRATE WITH 1" CORRUGATED GALVANIZED WALL TIES AT
2 PER BLOCK COURSE AT 16" O.C. VERTICALLY.
FLOOR PLAN GENERAL NOTES
FLOOR PLAN LEGEND
ELECTRICAL FLOOR BOX - SEE ELECTRICAL DRAWINGS
FLOOR DRAIN - SEE PLUMBING DRAWINGS
EFB
F.D.
M.T. METAL THRESHOLD
C.J. CONCRETE CONTROL JOINT
CHECKED:
DRAWN:
NUMBER:
N O
T F O
R
C O
N S
TR
U C
TIO
N
DATE:
D A
T E
D
E S
C R
IP
T
IO
N
R
E V
E
A S
T C
A P
IT
O
L S
T R
E E
T
J A
C K
S O
N
M S
.3
.2
P
A R C H I T E C T S eleyguildhardy.com
A R
C H
I T
E C
T
BW
Checker
April 17, 2025
23-057
G ra n d
V il la g e o f th e N a tc h e z I n d ia n s E x p a n s io n
N a tc h e z M is s is s ip p i C o n s tr u c ti o n
D o c u m e n ts
F L
O O
R P
L A
N C
A103 23 -0
G ra nd
V illa ge o f t he
N at ch ez
In di an s
Ex pa ns io n, N at ch ez , M is si ss ip pi
C on st ru ct io n D oc um en ts
1/8" = 1'-0"A103
1 FLOOR PLAN C
N O
R T
H
SCALE: 1/8"=1'-0"
0' 16'8'8'
E1 E2
EB
EA
AA
BB
CC
DD
EE
FF
GG
HH
JJ
A303
A303
A304
A304
19' - 0"
29' - 0"
AUDITORIUM / CLASSROOM
CHAIR/TABLE STO.
AV / IT
CATERING KITCHEN
122 BREAK OUT
VESTIBULE
LOBBY / ATRIUM
VESTIBULE
138 VESTIBULE
PORCH
RETAIL
MANAGER/STORAGE
112' - 0"
INTRO EXPERIENCE
M A
T C
H L
IN
E
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
M A
T C
H L
IN
E
F L
O O
R P
L A
N A
F L
O O
R P
L A
N B
F L
O O
R P
L A
N A
F L
O O
R P
L A
N B
112' - 0"
18' - 0" 19' - 0"
412' - 0"412' - 0"
412' - 0"
412' - 0"
110' - 0"
A304
A304
A404
110' - 2"
A405
PROJECTOR
A202
A202
A202
A202
A404
512' - 0"1
A405
TRACK LIGHTNING
C.J.
C.J.
C.J.
E.J.
C.J.
C.J.
C.J.
E.J.
E.J.
SLOT DIFFUSERS
18' - 0"
A125
A125
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.C.J.
C.J. C.J.
A4062
A406
A406
A303
A303
SUPER SIMPLEX
DISAPPEARING STAIRWAY
WITH NON-RATED
ALUMNIUM DOOR
2 - 2X2 ACOUSTICAL
CEILING TILE KITCHEN
DUTY
RCP LEGEND
4 - METAL SOFFIT PANELS
RECESS CAN LIGHT
-SEE ELEC
2X2 OR 2X4 RECESSED
DIRECT/INDIRECT -SEE
ELEC
SIDE WALL REGISTER
-SEE MECH
SUPPLY DIFFUSER
-SEE MECH
RETURN DIFFUSER
-SEE MECH
EXHAUST GRILLE
-SEE MECH
LINEAR FIXTURE
RECESSED -SEE ELEC
LINEAR FIXTURE WALL
MOUNTED -SEE ELEC
EXIT SIGN
-SEE ELEC
5 - EXTERIOR SUSPENDED
STUCCO SOFFIT SYSTEM
c CAMERA
-SEE ELEC
M MOTION SENSOR
-SEE ELEC
RCP GENERAL NOTES
1. SEE MECHANICAL AND ELECTRICAL TO VERIFY SIZE, TYPE, NUMBER, AND LOCATION OF FIXTURES.
2. SEE MECHANICAL AND ELECTRICAL LEGENDS FOR OTHER SYMBOLS SHOWN ON RCP BUY NOT SHOWN ON
ARCHITECTURAL RCP LEGEND.
3. ALL LIGHTS TO BE CENTERED IN 2X2 GRID (TYPICAL).
4. PROVIDE PAINTABLE ACCESS PANELS IN GYP BD CEILING AS REQ'D FOR ACCESS TO MECH AND PLUMB EQUIP. SEE
MECH AND PLUMB FOR LOCATIONS WHETHER SHOWN ON PLANS OR NOT.
5. ALL SPRINKLER HEADS SHALL BE CENTERED IN 2X2 GRID (TYPICAL).
6. PROVIDE ACCESS PANELS @ GYP BD CEILINGS FOR ACCESS TO PLUMBING VALVES, MECH UNIT VALVES, HVAC DAMPERS, AND TO OTHER ITEMS CALLED OUT ON ENGINEER DRAWINGS. SEE MECHANICAL, ELECTRICAL, PLUMBING, TELECOMM, AND FIRE PROTECTION, WHETHER SHOWN ON PLAN OR NOT.
3 - SUSPENDED GYPSUM
BOARD CEILING SYSTEM
WITH 5/8" GYP.BD.
XX'-X" CLEAR HEIGHT
ABOVE TOP OF SLAB
X CEILING TYPE
XX'-X" X
PAINTED EXP STRUCT
SPRINKLER
-SEE PLUMBING
CEILING CONTROL JOINT
C.J.
1 - 2X2 ACOUSTICAL
CEILING TILE
CORNER BEAD
5/8" GYPSUM BOARD
CONT. PERIMETER
CEILING EDGE
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 1/2" SOUND ATTENUATION
BATTING
3 5/8" METAL STUDS AT
16" O.C.
3 1/2" SOUND ATTENUATION
BATTING
'-0
CORNER BEAD
5/8" GYPSUM BOARD
CONT. PERIMETER ACT
CEILING EDGE
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 1/2" SOUND ATTENUATION
BATTING
3 5/8" METAL STUDS AT
16" O.C.
3 1/2" SOUND ATTENUATION
BATTING
SUSPENDED ACT CEILING
SYSTEM
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 1/2" SOUND
ATTENUATION BATTING
SUSPENDED PRE-
FINISHED TONGUE AND
GROOVE METAL CEILING
SYSTEM
5/8" PLYWOOD
HSS8X8X1/4
CONT. PERIMETER
CEILING EDGE
SUSPENDED STUCCO
CEILING SYSTEM SUSPENDED PRE-
FINISHED TONGUE AND
GROOVE METAL CEILING
SYSTEM
5/8" PLYWOOD
HSS8X8X1/4
CONT. PERIMETER
CEILING EDGE
A B C
CHECKED:
DRAWN:
NUMBER:
N O
T F O
R
C O
N S
TR
U C
TIO
N
DATE:
D A
T E
D
E S
C R
IP
T
IO
N
R
E V
E
A S
T C
A P
IT
O
L S
T R
E E
T
J A
C K
S O
N
.3
.2
P
A R C H I T E C T S eleyguildhardy.com
A R
C H
I T
E C
April 17, 2025
23-057
G ra n d
V il la g e o f th e N a tc h e z I n d ia n s E x p a n s io n
N a tc h e z
M is s is s ip p i
C o n s tr u c ti o n D o c u m e n ts
R E
F L
E C
T E
D C
E
IL
IN
G
P L
A N
B
A202 23 -0
G ra nd
V illa ge o f t he
N at ch ez
In di an s
Ex pa ns io n, N at ch ez , M is si ss ip pi
C on st ru ct io n D oc um en ts
1/8" = 1'-0"A202
1 REFLECTED CEILING PLAN B
N O
R T
H
SCALE: 1/8"=1'-0"
0' 16'8'8'
1" = 1'-0"A202
2 CEILING DETAIL 01
1" = 1'-0"A202
3 CEILING DETAIL 02
1" = 1'-0"A202
4 Detail 03
1" = 1'-0"A202
5 Detail 04
AA
BB
CC
DD
EE
FF
GG
HH
JJ
A304
A304
18' - 0"
18' - 0"
29' - 0"
19' - 6"
19' - 6"
19' - 6"
19' - 6"19' - 6"
19' - 6"
19' - 6"
18' - 0"
VESTIBULE
PERMANENT EXHIBIT GALLERY
BREAK ROOM
OFFICE 3
DIRECTOR
OFFICE 2
OFFICE 1
ASSISTANT DIR.
WAITING & CUBICLES
CONFERENCE
VESTIBULE
MANAGER/STORAGE
WOMEN'S RESTROOM
MEN'S RESTROOM
CLEAN STORAGE
CUSTODIAL
FAM. REST./LACTATION
112' - 0"
CORRIDOR
CORRIDOR
/4
M A
T C
H L
IN
E
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
F L
O O
R P
L A
N B
F L
O O
R P
L A
N C
18' - 0"
412' - 0"
412' - 0"
412' - 0"
412' - 0"
19' - 0"
19' - 0"19' - 0"
18' - 6"
19' - 0" 19' - 0"
HVAC
HVAC
HVAC
A407
19' - 0"
29' - 0"
A203
A203
A203
512' - 8"
18' - 0"
18' - 0"
C.J.
C.J.
C.J.C.J.
C.J.
C.J.
C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J.
C.J.
C.J.
C.J.
C.J.
C.J. C.J. C.J. C.J. C.J.C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.C.J.C.J.C.J.C.J.C.J.
A125
A303
A303
C.J. C.J.
C.J.C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
C.J.C.J.
C.J.
C.J.
C.J.
C.J.
C.J.
2 - 2X2 ACOUSTICAL
CEILING TILE KITCHEN
DUTY
RCP LEGEND
4 - METAL SOFFIT PANELS
RECESS CAN LIGHT
-SEE ELEC
2X2 OR 2X4 RECESSED
DIRECT/INDIRECT -SEE
ELEC
SIDE WALL REGISTER
-SEE MECH
SUPPLY DIFFUSER
-SEE MECH
RETURN DIFFUSER
-SEE MECH
EXHAUST GRILLE
-SEE MECH
LINEAR FIXTURE
RECESSED -SEE ELEC
LINEAR FIXTURE WALL
MOUNTED -SEE ELEC
EXIT SIGN
-SEE ELEC
5 - EXTERIOR SUSPENDED
STUCCO SOFFIT SYSTEM
c CAMERA
-SEE ELEC
M MOTION SENSOR
-SEE ELEC
RCP GENERAL NOTES
1. SEE MECHANICAL AND ELECTRICAL TO VERIFY SIZE, TYPE, NUMBER, AND LOCATION OF FIXTURES.
2. SEE MECHANICAL AND ELECTRICAL LEGENDS FOR OTHER SYMBOLS SHOWN ON RCP BUY NOT SHOWN ON
ARCHITECTURAL RCP LEGEND.
3. ALL LIGHTS TO BE CENTERED IN 2X2 GRID (TYPICAL).
4. PROVIDE PAINTABLE ACCESS PANELS IN GYP BD CEILING AS REQ'D FOR ACCESS TO MECH AND PLUMB EQUIP. SEE
MECH AND PLUMB FOR LOCATIONS WHETHER SHOWN ON PLANS OR NOT.
5. ALL SPRINKLER HEADS SHALL BE CENTERED IN 2X2 GRID (TYPICAL).
6. PROVIDE ACCESS PANELS @ GYP BD CEILINGS FOR ACCESS TO PLUMBING VALVES, MECH UNIT VALVES, HVAC DAMPERS, AND TO OTHER ITEMS CALLED OUT ON ENGINEER DRAWINGS. SEE MECHANICAL, ELECTRICAL, PLUMBING, TELECOMM, AND FIRE PROTECTION, WHETHER SHOWN ON PLAN OR NOT.
3 - SUSPENDED GYPSUM
BOARD CEILING SYSTEM
WITH 5/8" GYP.BD.
XX'-X" CLEAR HEIGHT
ABOVE TOP OF SLAB
X CEILING TYPE
XX'-X" X
PAINTED EXP STRUCT
SPRINKLER
-SEE PLUMBING
CEILING CONTROL JOINT
C.J.
1 - 2X2 ACOUSTICAL
CEILING TILE
'-0
CORNER BEAD
5/8" GYPSUM BOARD
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 1/2" SOUND ATTENUATION
BATTING
3 5/8" METAL STUDS AT
16" O.C.
3 1/2" SOUND ATTENUATION
BATTING
SUSPENDED PRE-
FINISHED TONGUE AND
GROOVE METAL CEILING
SYSTEM
5/8" PLYWOOD
CORNER BEAD
5/8" GYPSUM BOARD
CONT. PERIMETER
ACT CEILING EDGE
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 5/8" METAL STUDS AT
16" O.C.
3 1/2" SOUND
ATTENUATION BATTING
SUSPENDED ACT
CEILING SYSTEM
CORNER BEAD
5/8" GYPSUM BOARD
CONT. PERIMETER
CEILING EDGE
SUSPENDED 5/8" GYPSUM
BOARD CEILING SYSTEM
3 1/2" SOUND ATTENUATION
BATTING
3 5/8" METAL STUDS AT
16" O.C.
3 1/2" SOUND ATTENUATION
BATTING
SUSPENDED ACT
CEILING SYSTEM
A B C
CHECKED:
DRAWN:
NUMBER:
N O
T F O
R
C O
N S
TR
U C
TIO
N
DATE:
D A
T E
D
E S
C R
IP
T
IO
N
R
E V
E
A S
T C
A P
IT
O
L S
T R
E E
T
J A
C K
S O
N
.3
.2
P
A R C H I T E C T S eleyguildhardy.com
A R
C H
I T
E C
April 17, 2025
23-057
G ra n d
V il la g e o f th e N a tc h e z I n d ia n s E x p a n s io n
N a tc h e z
M is s is s ip p i
C o n s tr u c ti o n D o c u m e n ts
R E
F L
E C
T E
D C
E
IL
IN
G
P L
A N
C
A203 23 -0
G ra nd
V illa ge o f t he
N at ch ez
In di an s
Ex pa ns io n, N at ch ez , M is si ss ip pi
C on st ru ct io n D oc um en ts
1/8" = 1'-0"A203
1 REFLECTED CEILING PLAN C
N O
R T
H
SCALE: 1/8"=1'-0"
0' 16'8'8'
1" = 1'-0"A203
2 DETAIL 05
1" = 1'-0"A203
3 Detail 06
1" = 1'-0"A203
4 Detail 07
| RFQ 3140004202 Attachment A.pdf |
| RFQ 3140004202 Attachment A.pdf |
| RFQ 3140004202 Attachment A.pdf |
| RFQ 3140004202 Attachment A.pdf |
| Pages from MDAH GVNI 98pct CD Drawings-7.pdf |
| Pages from MDAH GVNI 98pct CD Drawings.pdf |
| Pages from MDAH GVNI 98pct CD Drawings-2.pdf |
File details come from the government source that posted it. Updated .