JL-9 N6945022R0028_Annual Chiller PM Reports_0003.pdf

PDF 345 KB Posted

Attached to
Base Operations Support (BOS) Services at NAS Key West, FL
Solicitation number
N6945022R0028
Issued by

About this file

This document contains chiller log sheets from various facilities at Naval Air Station Key West, Florida. The log sheets provide readings and inspection results for chillers and related equipment at multiple sites, including Fly Navy, Boca Chica, and Truman. Technicians performed annual inspections, cleaning, fluid changes, and other maintenance and checked chiller operations. Readings covered areas like compressor discharge temperature, motor parameters, evaporator and condenser pressures and temperatures, refrigerant levels, and capacity control settings. Comments indicate cleaning condenser and heat exchanger tubes, taking refrigerant samples, leak checks, and checking overall chiller conditions. The related federal contract opportunity is for Base Operations Support services at NAS Key West, including facility investment, pest control, integrated solid waste management, and utilities management for requirements like HVAC and refrigeration.

View the file

Other files

File Type Posted
JL-10 N6945022R0028_BOS Monthly Report_0003.pdf PDF
JL-7 N6945022R0028 GPI Responses_0003.pdf PDF
JL-11 N6945022R0028_FY21 WO Logs_0003.xlsx XLSX spreadsheet
N6945022R0028SectionF_0003.pdf PDF
N69450R20028SectionC_0003.pdf PDF
J-0200000-12 ELINS_0003.xlsx XLSX spreadsheet
JL-1 N6945022R0028_0003.xlsx XLSX spreadsheet
N6945022R0028SectionJ_0003.pdf PDF
N6945022R0028-0003.pdf PDF
JL-7 N6945022R0028 GPI Responses_0002.pdf PDF
JL-8 N6945022R0028 KW BOS Photos_0002.zip ZIP file
N6945022R0028 WD2015-4583(Rev.19)_0002.pdf PDF
N6945022R0028 Monroe Bldg FL20220022_0002.pdf PDF
N6945022R0028-0002.pdf PDF
N6945022R0028 Monroe Hvy FL20220096_0002.pdf PDF
N6945022R0028SectionC_0001.pdf PDF
JL-5 N6945022R0028 Site Visit Brief_0001.pdf PDF
N6945022R0028-0001.pdf PDF
JL-6 N6945022R0028 Site Visit Sign-In Sheet_0001.pdf PDF
J-0200000-10 KWSPCC.pdf PDF
J-0200000-12 ELINS.xlsx XLSX spreadsheet
JM-2 N6945022R0028 PPQ.doc DOC document
N6945022R0028 Monroe Bldg FL20220022.pdf PDF
N6945022R0028SectionF.pdf PDF
JL-4 N6945022R0028 Site Visit Itinerary.pdf PDF
JM-1 N6945022R0028 Corporate Experience.docx DOCX document
JL-1 N6945022R0028.xlsx XLSX spreadsheet
N6945022R0028 Monroe Hvy FL20220096.pdf PDF
N6945022R0028SectionJ.pdf PDF
J-0200000-05 Service Provider Information.xlsx XLSX spreadsheet
J-0200000-07 Specification Information.xlsx XLSX spreadsheet
J-0200000-08 Characteristic Meter Reading Information.xlsx XLSX spreadsheet
JL-3 N6945022R0028 SECNAV5512.pdf PDF
J-0200000-06 Asset Information.xlsx XLSX spreadsheet
N6945022R0028 WD2015-4583(Rev.18).pdf PDF
N6945022R0028SectionC.pdf PDF
JL-2 N6945022R0028 GPIF.xls XLS spreadsheet
N6945022R0028.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Chiller Log Sheets - Fly Navy CH-2

GENERAL

Job Information

Branch Activity Number Job Site Fly Navy CH-2 Unit Type YMC² Unit Model Number YMC2-S0992AAS Unit Serial Number SLBM086740 Run Hours 46965 Start/Stops 2025 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 79 Motor Input Power 23

Motor % Input FLA 15

Motor % Output FLA 15

Motor DC Buss Voltage 744

Magnetic Bearing Controller Motor Housing Temp 73

Magnetic Bearing Controller Rotor Elongation 58uM

Evaporator - Refrigerant Evaporator Pressure 38

Evaporator - Refrigerant Corresponding Temp. 43

Evaporator - Refrigerant Small Temp. Difference 0.0

Evaporator - Liquid Supply Temp. 44

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 45

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 64

Condenser - Refrigerant Corresponding Temp. 65

Condenser - Refrigerant Small Temp. Difference 0

SECTION READING RESULT

Condenser - Refrigerant Refrigerant Level 50 Condenser - Liquid Supply Temp. 63

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp.

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 199hz

Condenser - Capacity Control VGD Command 31%

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Arrived on site checked in with customer performed annual inspection on Chiller cleaned condenser tubes cleaned heat exchanger tubes changed out heat exchanger fluid leak check Chiller check all terminal connections motor connections and wiring

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - Fly Navy CH-2/SLBM086740 2022-01-28

Chiller Log Sheets - NASKW BOCA

CHICA CH-1

GENERAL

Job Information

Branch Activity Number Job Site NASKW BOCA CHICA CH-1 Unit Type YMC² Unit Model Number YMC2-S1020AAS Unit Serial Number SCBM911840 Run Hours 22961 Start/Stops 6770 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 102 Motor Input Power 55

Motor % Input FLA 30

Motor % Output FLA 30

Motor DC Buss Voltage 744

Magnetic Bearing Controller Motor Housing Temp 83

Magnetic Bearing Controller Rotor Elongation 34uM

Evaporator - Refrigerant Evaporator Pressure 39

Evaporator - Refrigerant Corresponding Temp. 44

Evaporator - Refrigerant Small Temp. Difference 1.0

Evaporator - Liquid Supply Temp. 45

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 48

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 87

Condenser - Refrigerant Corresponding Temp. 80

Condenser - Refrigerant Small Temp. Difference 0.3

Condenser - Liquid Supply Temp. 77

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp. 80

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 261

Condenser - Capacity Control VGD Command 19

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Performed annual inspection on chiller brushed condenser tubes, leak checked cleaned heat exchanger tubes flush VSD coolant, took refrigerant sample cleaned gauge ports. Checked chiller overall operation and performance.

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - NASKW BOCA CHICA CH-1/SCBM91184 2022-01-14

Chiller Log Sheets - NASKW BOCA

CHICA CH-2

GENERAL

Job Information

Branch Activity Number Job Site NASKW BOCA CHICA CH-2 Unit Type YMC² Unit Model Number YMC2-S1020AAS Unit Serial Number SDBM911730 Run Hours 22880 Start/Stops 8434 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 99*F Motor Input Power 35%

Motor % Input FLA 34%

Motor % Output FLA 35

Motor DC Buss Voltage 744

Magnetic Bearing Controller Motor Housing Temp 83

Magnetic Bearing Controller Rotor Elongation 95uM

Evaporator - Refrigerant Evaporator Pressure 36psig

Evaporator - Refrigerant Corresponding Temp. 41

Evaporator - Refrigerant Small Temp. Difference 2.2

Evaporator - Liquid Supply Temp. 44

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 47

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 84

Condenser - Refrigerant Corresponding Temp. 78

Condenser - Refrigerant Small Temp. Difference 0.5

Condenser - Refrigerant Refrigerant Level 40 Condenser - Liquid Supply Temp. 74

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp. 78

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 255

Condenser - Capacity Control VGD Command 19.1

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Performed annual on chiller brushed condenser tubes, cleaned heat exchanger for VSD, changed coolant, took refrigerant sample, leak checked chiller. Logged chiller and checked overall condition. Chiller operation normal at this time.

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - NASKW BOCA CHICA CH-2/SDBM91173 2022-01-14

Chiller Log Sheets - NASKW Fly Navy CH-1

Job Information

Branch Activity Number Job Site NASKW Fly Navy CH-1 Unit Type YMC² Unit Model Number YMC2-S10052AB Unit Serial Number SMFM266440 Run Hours 11264 Start/Stops 295 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 93 Motor Input Power 41

Motor % Input FLA 22

Motor % Output FLA 21

Motor DC Buss Voltage 782

Magnetic Bearing Controller Motor Housing Temp 76

Magnetic Bearing Controller Rotor Elongation 119uM

Evaporator - Refrigerant Evaporator Pressure 39

Evaporator - Refrigerant Corresponding Temp. 44

Evaporator - Refrigerant Small Temp. Difference 0.3

Evaporator - Liquid Supply Temp. 45

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 47

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 75

Condenser - Refrigerant Corresponding Temp. 72

Condenser - Refrigerant Small Temp. Difference 0.2

Condenser - Liquid Supply Temp. 69

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp. 72

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 189hz

Condenser - Capacity Control VGD Command 14.98%

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Arrived on site checked in with customer performed annual inspection on Chiller clean condenser, cleaned heat exchanger, changed VSD fluid, leak checked chiller took refrigerant sample.

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - NASKW Fly Navy CH-1/SMFM266440 2022-01-28

Chiller Log Sheets - NASKW

TRUMAN CH-1

GENERAL

Job Information

Branch Activity Number Job Site NASKW TRUMAN CH-1 Unit Type YMC² Unit Model Number YMC2-S1055AAS Unit Serial Number SDGM355710 Run Hours 12074 Start/Stops 1548 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 99 Motor Input Power 130

Motor % Input FLA 71

Motor % Output FLA 70

Motor DC Buss Voltage 745

Magnetic Bearing Controller Motor Housing Temp 84

Magnetic Bearing Controller Rotor Elongation 20uM

Evaporator - Refrigerant Evaporator Pressure 38

Evaporator - Refrigerant Corresponding Temp. 43

Evaporator - Refrigerant Small Temp. Difference 2.0

Evaporator - Liquid Supply Temp. 44

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 55

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 97

Condenser - Refrigerant Corresponding Temp. 86

Condenser - Refrigerant Small Temp. Difference 1.0

Condenser - Liquid Supply Temp. 75

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp. 85

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 258

Condenser - Capacity Control VGD Command 53

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Performed annual inspection on CH-1 at Truman 1352. Took refrigerant sample cleaned condenser tubes and heat exchanger tubes, also drained VSD fluid and changed out. Leak checked chiller tightened terminal connections for electrical. Chiller operation normal at this time.

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - NASKW TRUMAN CH-1/SDGM355710 2022-01-28

Chiller Log Sheets - NASKW

TRUMAN CH-2

Job Information

Branch Activity Number Job Site NASKW TRUMAN CH-2 Unit Type YMC² Unit Model Number YMC2-S10055 Unit Serial Number SEGM355720 Run Hours 7464 Start/Stops 706 Visit Type YMC²/Log Sheet

Log Sheet

SECTION READING RESULT

Compressor Discharge Temperature 99 Motor Input Power 52

Motor % Input FLA 38

Motor % Output FLA 39

Motor DC Buss Voltage 745

Magnetic Bearing Controller Motor Housing Temp 86

Magnetic Bearing Controller Rotor Elongation 27

Evaporator - Refrigerant Evaporator Pressure 39

Evaporator - Refrigerant Corresponding Temp. 44

Evaporator - Refrigerant Small Temp. Difference 0

Evaporator - Liquid Supply Temp. 44

Evaporator - Liquid Supply Pressure

Evaporator - Liquid Return Temp. 50

Evaporator - Liquid Return Pressure

Evaporator - Liquid Flow Rate GPM (if equipped)

Condenser - Refrigerant Condenser Pressure 89

Condenser - Refrigerant Corresponding Temp. 80

Condenser - Refrigerant Small Temp. Difference 1

Condenser - Liquid Supply Temp. 76

Condenser - Liquid Supply Pressure

Condenser - Liquid Return Temp. 80

Condenser - Liquid Return Pressure

Condenser - Liquid Flow Rate GPM (if equipped)

Condenser - Capacity Control VSD Command 240hz

Condenser - Capacity Control VGD Command 3.2

Condenser - Capacity Control HGBP Command (if equip)

Condenser - Capacity Control PRV Command (if equip)

Refrigerant Log

Additional Readings

FINAL COMMENTS

Submission Information

General Comments: Arrived on site checked in with customer performed annual inspection cleaned condenser tubes cleaned heat exchanger tubes, cleaned strainer, flushed VSD coolant, leak checked chiller took refrigerant sample tightened electrical connections and checked overall condition of chiller, operation and conditions normal at this time.

Attach pictures if needed Who else needs a copy of this submission?

(Enter as many email addresses as needed)

Technician Signature

Chiller Log Sheets PAGE 2 OF 2

Chiller Log Sheets - NASKW TRUMAN CH-2/SEGM355720 2022-01-28