This monthly report details base operations support services provided at Naval Air Station Key West under solicitation N6945022R0028. The contractor conducted preventative maintenance and inspections of HVAC, fire protection, automatic doors, exhaust hoods and ducts, and water testing equipment across multiple buildings. Inspection findings included needed repairs to fire protection systems at several locations and replacement of automatic doors at one facility. The report provides labor hours by category for the reporting period as well as quality ratings and corrective actions from ongoing inspections of supported systems and facilities.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEBRUARY 15, 2022 – MARCH 14, 2022
MONTHLY REPORT
N69450-17-D-6010
BOS SERVICES NAS KEY WEST
SUMMARY OF REPORTS
PREVENTATIVE MAINTENANCE AND ITM ITEMS FOR CONTRACT
PERIOD: FEBRUARY 15, 2022 – MARCH 14, 2022
CONTACTOR QUALITY INSPECTION AND SURVEILLANCE REPORT
(0200000 / 2.6.7.3)
NUMBER OF REPORTS PER BASE
BOCA CHICA SIGSBEE TRUMBO TRUMAN
2 0 2 2
NUMBER OF REPORTS PER CATEGORY
SATISFACTORY SATISFACTORY NEEDS
IMPROVEMENT
UNSATISFACTORY
2 4 0
GREEN + FREE OF ANY VISUAL OR KNOWN
ISSUES
GREEN No serviceability issue or reliability issue GREEN - Slight or minimal overall reliability reduction AMBER Functional for the time being but overall marginal condition RED + Significant serviceability issues and many components are degraded RED Severe reliability and performance is minimal RED- Major component failures, not much salvageable
BOCA CHICA
HVAC
BUILDING LOCATION: Not applicable this month.
SUMMARY:
QUALITY / RATING:
SURVEILLANCE:
CORRECTIVE ACTION:
COLOR RATING:
FIRE PROTECTION
BUILDING LOCATION: A-4202
The wet system was left up. There is a full tank of water, (20,000) gals. The fire pump was tested after checking rotation.
Rotation was reversed so your electrician fixed that problem.
The fire pump runs well but the flow determination valve was not working so flow at 100% and 150% could not be determined.
The pre-action system is offline. 1 pressure switch # 14 is bad.
& Switch 18 is bad to the panel. All gages on the system need to be changed out. Damper switch on third floor is in trouble and wont reset. So wet system with jockey pump and fire pump is what fire protection you have currently. The FDC needs to be changed out on the side of the building the mechanical room is on.
QUALITY / RATING: Pass with Deficiencies SURVEILLANCE: Reference Gulf Coast Fire Report & Continuance of ITMs CORRECTIVE ACTION: Proceed with recommendations from Gulf Coast Fire Report
COLOR RATING: YELLOW
AUTOMATIC DOORS
BUILDING LOCATION: Not applicable for this report this month.
EXHAUST HOOD & DUCT CLEANING
SUMMARY
WATER TREATMENT AND TESTING
BUILDING LOCATION: A-936
Please reference South Florida Water Consultants February deliverables for additional information attached at the end of
AMR.
QUALITY / RATING: Pass SURVEILLANCE: Continuance of PMs CORRECTIVE ACTION: None at this time.
COLOR RATING: GREEN
UTILITY LOCATES
SIGSBEE
TRUMBO
BUILDING LOCATION: Not applicable for this report for this month.
BUILDING LOCATION: Not applicable for this report for this month.
BUILDING LOCATION: C-2076
Stanley master and slave motor components Condensation issue cleared up and now waiting on Stanley doors for scheduled install!
**PO: NGISKW-22-M-0003 issued on 12/3/2021**
QUALITY / RATING: Pass with Deficiencies SURVEILLANCE: QC checks when repairs complete; Continuance of PMs CORRECTIVE ACTION: Troubleshoot and repair system.
COLOR RATING: AMBER
BUILDING LOCATION: 4084
AMR.
QUALITY / RATING: Pass with Deficiencies SURVEILLANCE: QC checks when repairs complete; Continuance of PMs
TRUMAN
BUILDING LOCATION: 1352
Chillers 1 & 2 – Daily inspections performed, checked refrigerant levels, pressures, water flow and VSD operation.
1. Chiller 1 is due for Cleaning.
QUALITY / RATING: Pass with Deficiencies SURVEILLANCE: QC checks when repairs complete; Continuance of PMs
BUILDING LOCATION: Not applicable this month.
BUILDING LOCATION: Not applicable for this report this month
BUILDING LOCATION: 1352
AMR.
QUALITY / RATING: Pass SURVEILLANCE: Continuance of PMs CORRECTIVE ACTION: None currently.
COLOR RATING: GREEN
MONTHLY ON-SITE LABOR REPORT
(0200000 / 2.97)
Monthly FEBRUARY 15th – MARCH 14th, 2022, On-Site Labor Report NAS/NAVFAC Contract # N69450-17-D-6010
Dec- Jan
Jan- Feb
Feb- Mar
Mar- Apr
Apr- May
May- Jun
Jun- Jul
Jul- Aug
Aug- Sep
Sept- Oct
Oct- Nov
Nov- Dec
Total
2021 2022 2022 2022 2022 2022 2022 2022 2022 2022 2021 2021
Totals
320 330 330 280 320 1580
HVAC 48 0 0 24 32 104
Fire Suppression Systems
0 208 16 288 80 592
Vent Hoods 8 0 0 0 0 8
Doors 0 0 0 0 16 16
Utility Locate Services
0 0 0 0 8 8
HVAC Water Treatment Services
12 12 12 12 12 60
Total 388 550 358 604 468 2188
SERVICE ORDER SUMMARY REPORT
(1502000 / 3.1)
FEBRUARY 15 - MARCH 14, 2022, MONTHLY SERVICE ORDER SUMMARY
REPORT
WORK ORDERS
Description Site Location WO# Status Scheduled
Start Priority Completion Date
TASK ORDERS
Description Site Location TO# Status Scheduled
Priority Completion Date
Inspection of sprinkler system
Boca Chica
A-4202 F0187 COMPLETED 2/22/2022 Routine COMPLETED February 25, 2022
NAF PURCHASE ORDERS
Description Site Location NAF PO# Status Scheduled
Priority Completion Date
Repairs to main entrance doors
Trumbo C-2076 NGISKW- 22-M-0003
In Progress 12/3/2021 NAF PO Anticipated March 2022
QUANTITES ORDERED VIA FEDMALL
(0200000 / 2.15.1.1)
DURING THE FEBRUARY 15 – MARCH 14, 2022, CONTRACT
PERIOD, NO NON-RECURRING WORK QUANTITIES WERE
ORDERED VIA FEDMALL.
INSPECTION, TESTING AND MAINTENANCE PROGRAM SUMMARY
(1502000 / 3.3)
** Not applicable this month**
INSPECTION, TESTING AND MAINTENANCE SCHEDULE &
EQUIPMENT CERTIFICATIONS REPORT
(1502000 / 3.1)
Location / Building Start Date Completion Date System(s) Ext Work Hours (Y/N) Remarks
TMBO / C-80 10/18/2021 10/18/2021 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 10/18/2021 10/18/2021 Pump Electrical N Water tanks require internal inspection.
TRMN / 289 10/18/2021 10/18/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 10/18/2021 10/18/2021 Pump Diesel N SIGSB / V-4189 10/18/2021 10/18/2021 Pump Electrical N
BCAF / A-229 10/19/2021 10/19/2021 Fire Alarm N
Inventory states there is a sprinkler in this building, but we did not locate a sprinkler system riser or sprinkler heads in this facility.
BCAF / A-437 10/19/2021 10/19/2021 Sprinkler N FKAA Assistance Required BCAF / A-438 10/19/2021 10/19/2021 Sprinkler N FKAA Assistance Required BCAF / A-515 10/20/2021 10/20/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-350 10/20/2021 10/20/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-324 10/21/2021 10/21/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-149 10/22/2021 10/22/2021 Fire Alarm N BCAF / A-131 10/22/2021 10/22/2021 Fire Alarm/Sprinkler N FKAA Assistance Required TMBO / C-2076 10/25/2021 10/28/2021 Fire Alarm/Sprinkler/Fire Pump N BCAF / A-626 10/29/2021 10/29/2021 Fire Alarm/Sprinkler/Preaction (Server Rm) N FKAA Assistance Required BCAF / A-629 10/29/2021 10/29/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-711 11/1/2021 11/1/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-718 11/1/2021 11/1/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-648 11/2/2021 11/2/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-649 11/3/2021 11/3/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-1112 11/4/2021 11/4/2021 Fire Alarm N BCAF / A-734 11/4/2021 11/4/2021 Fire Alarm N BCAF / A-824 11/5/2021 11/5/2021 Fire Alarm N BCAF / A-4165 11/5/2021 11/5/2021 Fire Alarm N
TMBO / C-80 11/8/2021 11/8/2021 Pump Diesel N Water tanks require internal inspection.
FIRE PROTECTION TRAINING FY2022 ITM SCHEDULE
OCTOBER 2021 - NOVEMBER 2021
TMBO / C-80 11/8/2021 11/8/2021 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 11/8/2021 11/8/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 11/8/2021 11/8/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 11/8/2021 11/8/2021 Pump Diesel N SIGSB / V-4189 11/8/2021 11/8/2021 Pump Electrical N BCAF / A-1004 11/9/2021 11/9/2021 Fire Alarm N BCAF / A-1019 11/9/2021 11/9/2021 Fire Alarm N BCAF / A-1020 11/9/2021 11/9/2021 Fire Alarm N BCAF / A-986 11/10/2021 11/10/2021 Fire Alarm N Need space on the floor BCAF / A-638 11/12/2021 11/12/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-639 11/12/2021 11/12/2021 Fire Alarm/Sprinkler N FKAA Assistance Required
OCTOBER 2021 - NOVEMBER 2021 (continued)
TMBO / C-80 12/13/2021 12/13/2021 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 12/13/2021 12/13/2021 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 12/13/2021 12/13/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 12/13/2021 12/13/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 12/13/2021 12/13/2021 Pump Diesel N SIGSB / V-4189 12/13/2021 12/13/2021 Pump Electrical N BCAF / A-727 12/14/2021 12/14/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-980 12/15/2021 12/15/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-4203 12/15/2021 12/15/2021 Fire Alarm/Sprinkler N FKAA Assistance Required BCAF / A-1125 12/16/2021 12/16/2021 Fire Alarm N BCAF / A-4191 12/16/2021 12/16/2021 Fire Alarm N BCAF / A-4194 12/17/2021 12/17/2021 Fire Alarm N BCAF / 4412 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4413 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4414 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4415 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4416 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4417 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4418 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4419 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4420 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4421 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4422 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4423 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N BCAF / 4424 12/17/2021 12/17/2021 Fire Alarm Pull Box (Marina) N
DECEMBER 2021
TMBO / C-80 1/24/2022 1/24/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 1/24/2022 1/24/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 1/24/2022 1/24/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 1/24/2022 1/24/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 1/24/2022 1/24/2022 Pump Diesel N SIGSB / V-4189 1/24/2022 1/24/2022 Pump Electrical N SIGS / V-4187 1/24/2022 1/24/2022 Wet Chem (Hood) N
TMBO / F1 1/25/2022 1/25/2022 Fire Alarm/Sprinkler N
Sprinkler water source is a pressurized water tank. The water tank is not on the fire protection inventory.
TMBO / F15 1/25/2022 1/25/2022 Fire Alarm/Sprinkler N
Sprinkler water source is a pressurized water tank. The water tank is not on the fire protection inventory.
BCAF / A-4202 1/26/2022 1/26/2022 Fire Alarm N
BCAF / A-4085 1/26/2022 1/26/2022 Fire Alarm N Secured facility behind Passenger Terminal
BCAF / A-4082 1/27/2022 1/27/2022 Fire Alarm N Secured facility
BCAF / A-4078 1/28/2022 1/28/2022 Fire Alarm N Hazardous Storage on other side of Boca Chica
BCAF / A-4240 1/28/2022 1/28/2022 Fire Alarm N
SIGS / V-4205 1/31/2022 1/31/2022 Fire Alarm N
To gain entry to this building, we must contact personnel at ITT, bldg V-4113 on Sigsbee to get the key.
SIGS / V-4193 1/31/2022 1/31/2022 Fire Alarm N
To gain entry into the Janitor's room, we must contact the RV Office at bldg V- 4113 on Sigsbee.
TRMN / 4214 2/1/2022 2/1/2022 Fire Alarm N BCAF / A-4013 2/1/2022 2/1/2022 Fire Alarm N TRMN / 507 2/2/2022 2/2/2022 Fire Alarm/Sprinkler N TRMN / 4180 2/2/2022 2/2/2022 Fire Alarm/Sprinkler N
JANUARY 2022 - FEBRUARY 2022
TRMN / 795 2/3/2022 2/3/2022 Fire Alarm/Sprinkler N Port Ops (located at pier outside Truman Annex)
TRMN / 284 2/3/2022 2/3/2022 Fire Alarm/Sprinkler N Port Ops (located at pier outside Truman Annex)
TRMN / 4407 2/3/2022 2/3/2022 Fire Alarm Pull Box N Port Ops (located at pier outside Truman Annex)
TRMN / 4408 2/3/2022 2/3/2022 Fire Alarm Pull Box N Port Ops (located at pier outside Truman Annex)
SIGS / V-4113 2/4/2022 2/4/2022 Fire Alarm N SIGS / V-4059 2/4/2022 2/4/2022 Fire Alarm N
SIGS / V-4111 2/7/2022 2/7/2022 Fire Alarm N The sprinkler system is not on the government inventory
SIGS / V-4189 2/7/2022 2/7/2022 Fire Alarm/Sprinkler N V-4189 Fire Pump SIGS / V-4189A 2/7/2022 2/7/2022 Fire Alarm/Sprinkler N V-4189 Fire Pump
SIGS / V-4114 2/8/2022 2/8/2022 Fire Alarm N
New Siemens fire alarm system and two sprinkler risers installed. The sprinkler risers are not currently on the government inventory
SIGS / V-4058 2/9/2022 2/9/2022 Fire Alarm N
TMBO / C-80 2/9/2022 2/9/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 2/9/2022 2/9/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 2/9/2022 2/9/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 2/9/2022 2/9/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 2/9/2022 2/9/2022 Pump Diesel N SIGSB / V-4189 2/9/2022 2/9/2022 Pump Electrical N
JANUARY 2022 - FEBRUARY 2022 (continued)
TMBO / C-80 3/21/2022 3/21/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 3/21/2022 3/21/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 3/21/2022 3/21/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 3/21/2022 3/21/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 3/21/2022 3/21/2022 Pump Diesel N SIGSB / V-4189 3/21/2022 3/21/2022 Pump Electrical N BCAF / A-990 3/21/2022 3/21/2022 Dry Chem (Paint Booth) N BCAF / A-931 3/22/2022 3/22/2022 Fire Alarm/Sprinkler/Dry Chem (Haz Storage Trailers) N FKAA Assistance Required BCAF / A-337 3/22/2022 3/22/2022 Wet Chem (Hood) N Schedule for afternoon BCAF / A-1132 3/23/2022 3/23/2022 Fire Alarm/Wet Chem (Hood) N Schedule for morning
TMBO / B-27 3/23/2022 3/23/2022 Fire Alarm/Sprinkler N
Sprinkler water source is a pressurized water tank. The water tank is not on the fire protection inventory.
TRMN / 1332 3/24/2022 3/24/2022 Fire Alarm/Wet Chem (Hood) N
TMBO / 4405 3/24/2022 3/25/2022 Fire Alarm Pull Box (MWR Trailer Park) N
Box removed as of Aug 2020. If the pull boxes are re-installed, this is when the ITM will take place.
TMBO / 4406 3/24/2022 3/25/2022 Fire Alarm Pull Box (MWR Trailer Park) N
Box removed as of Aug 2020. If the pull boxes are re-installed, this is when the ITM will take place.
TMBO / MODULAR TRAILERS 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N There are 38 new trailer homes TMBO / T-1400 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes TMBO / T-1401 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes TMBO / T-1402 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 6 Town Homes TMBO / T-1403 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes TMBO / T-1404 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes TMBO / T-1405 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 6 Town Homes TMBO / T-1406 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 4 Town Homes TMBO / T-1407 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes
MARCH 2022 - APRIL 2022
TMBO / T-1408 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 8 Town Homes TMBO / T-1414 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 4 Town Homes TRMN / 392 3/24/2022 3/25/2022 Smoke Alarms (MWR Vacation Rental) N This unit has 3 Town Homes TRMN / 437 3/28/2022 3/28/2022 Fire Alarm/Sprinkler N TRMN / 438 3/29/2022 3/29/2022 Fire Alarm/Sprinkler N TRMN / 439 3/30/2021 3/30/2021 Fire Alarm/Sprinkler N TRMN / 1350 3/31/2021 3/31/2021 Fire Alarm/Sprinkler N
TMBO / C-80 4/1/2021 4/1/2021 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 4/1/2021 4/1/2021 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 4/1/2021 4/1/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 4/1/2021 4/1/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 4/1/2021 4/1/2021 Pump Diesel N SIGSB / V-4189 4/1/2021 4/1/2021 Pump Electrical N
MARCH 2022 - APRIL 2022 (continued)
1353 Fire Pump - NOTE: The fire pump does not activate when inspector test valve opened.
TMBO / C-80 5/9/2022 5/9/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 5/9/2022 5/9/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 5/9/2022 5/9/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 5/9/2022 5/9/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 5/9/2022 5/9/2022 Pump Diesel N SIGSB / V-4189 5/9/2022 5/9/2022 Pump Electrical N TRMN / 4201 5/10/2022 5/10/2022 Fire Alarm/FM200 N
TRMN / 1351 5/10/2022 5/11/2021 Fire Alarm/Sprinkler N
1353 Fire Pump - NOTE: The fire pump does not activate when inspector test valve opened.
BCAF / A-981 5/12/2021 5/13/2022 Fire Alarm/Sprinkler/AFFF N FKAA Assistance Required
Location / Building Start Date Completion Date System(s) Ext Work Hours (Y/N) Remarks
TMBO / C-80 6/20/2022 6/20/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 6/20/2022 6/20/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 6/20/2022 6/20/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 6/20/2022 6/20/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 6/20/2022 6/20/2022 Pump Diesel N SIGSB / V-4189 6/20/2022 6/20/2022 Pump Electrical N BCAF / A-936 6/21/2022 6/23/2022 Fire Alarm/Sprinkler/AFFF N FKAA Assistance Required
MAY 2022
JUNE 2022
TMBO / C-80 7/18/2022 7/18/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 7/18/2022 7/18/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 7/18/2022 7/18/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 7/18/2022 7/18/2022 Pump Diesel N SIGSB / V-4189 7/18/2022 7/18/2022 Pump Electrical N SIGS / V-4187 7/19/2022 7/19/2022 Fire Alarm/Sprinkler/Wet Chem (Hood) Y TRMN / 289 (JIATF) 7/20/2022 7/20/2022 Sprinkler/FM200/Pump Electrical N TRMN / 290 (JIATF) 7/20/2022 7/20/2022 Sprinkler N TRMN / 291 (JIATF) 7/20/2022 7/20/2022 Sprinkler N TRMN / 1279 (JIATF) 7/20/2022 7/20/2022 Sprinkler N TMBO / C-1 7/21/2022 7/21/2022 Fire Alarm/Sprinkler N
Location / Building Start Date Completion Date System(s) Ext Work Hours (Y/N) Remarks
TMBO / C-80 8/22/2022 8/22/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 8/22/2022 8/22/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 8/22/2022 8/22/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 8/22/2022 8/22/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 8/22/2022 8/22/2022 Pump Diesel N SIGSB / V-4189 8/22/2022 8/22/2022 Pump Electrical N
JULY 2022
289 Fire Pump -- NOTE: Water tank requires internal inspection.
AUGUST 2022
TMBO / C-80 9/26/2022 9/26/2022 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 9/26/2022 9/26/2022 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 9/26/2022 9/26/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 9/26/2022 9/26/2022 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 9/26/2022 9/26/2022 Pump Diesel N SIGSB / V-4189 9/26/2022 9/26/2022 Pump Electrical N TRMN / 1332 9/26/2022 9/26/2022 Wet Chem (Hood) N BCAF / A-1132 9/27/2022 9/27/2022 Wet Chem (Hood) N BCAF / A-990 9/27/2022 9/27/2022 Dry Chem (Paint Booth) N BCAF / A-931 9/27/2022 9/27/2022 Dry Chem (Haz Storage Trailers) N BCAF / A-337 9/27/2022 9/27/2022 Wet Chem (Hood) N
Location / Building Start Date Completion Date System(s) Ext Work Hours (Y/N) Remarks
TMBO / C-80 10/11/2021 10/11/2021 Pump Diesel N Water tanks require internal inspection.
TMBO / C-80 10/11/2021 10/11/2021 Pump Electrical N Water tanks require internal inspection.
TMBO / C-2076 10/11/2021 10/11/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 289 10/11/2021 10/11/2021 Pump Electrical N Water tank requires internal inspection.
TRMN / 1353 10/11/2021 10/11/2021 Pump Diesel N SIGSB / V-4189 10/11/2021 10/11/2021 Pump Electrical N
OCTOBER 2022
SEPTEMBER 2022
OTHER RECURRING SERVICES PROGRAM REPORT
(1502000 / 3.4)
TREATMENT, SAMPLING AND TESTING SERVICES PROGRAM
(1502000 / 3.5)
NAVAL AIR STATION KEY WEST
(BOCA CHICA)
(TRUMAN ANNEX)
(TRUMBO POINT)
HVAC WATER TREATMENT SERVICE REPORTS – COOLING TOWERS
February 17th, 2022
I inspected the chemical treatment station and tested all equipment. The conductivity controller was calibrated to the current conditions. I also found there was adequate water flow through the station bypass piping. I tested both chemical feed pumps and found they were primed and online delivering products.
I sampled and tested the condenser water, and the test results show the condenser water chemistry to be within the desired control limits.
A new water meter was installed on the water make up bypass on the towers. Unable to quantify water usage for this month.
I found the condenser water system consumed ample amounts of inhibitor and non-oxidizing biocide to effectively prevent scale formation and bacterial growth in the open loop system.
I delivered 5/gallons of Biocide Isothiazolin KTND.
I manually added supplemental biocide to the cooling towers today. The towers got the solid halogen donor (Bromicide) product to complement the non-oxidizing biocide Isothiazolin (KTND) we feed on a timed weekly basis.
NAS Key West – BOCA CHICA BLDG: A 936 Date: 02/17/2022
TEST CITY WATER TOWER CONTROL
LIMITS
Conductivity 385 1616 1500-2000
CWT1644 0 157 40-80
Total Alkalinity 40 220 <300 Calcium Hardness 110 510 <600 pH 8.6 8.8 8.5-9.5 Chlorides 40 140 150-250 Chemical Inventory 14/12 gal inhib / gal biocide Water Meter 35475 Gallons
CWS Temp CWR Temp Refrig PSI Sat Refrig Temp Approach Load Chiller 1 77.6 82.6 91.8 83.0 0.4 45.5
No issues to report.
I inspected the chemical treatment station and tested all equipment. The conductivity controller was calibrated to the current conditions. I also found there was adequate water flow through the station bypass piping. I tested both chemical feed pumps and found they were primed and online delivering products.
I sampled and tested the condenser water, and the test results show the condenser water chemistry to be within the desired control limits.
I found the condenser water system consumed ample amounts of inhibitor and non-oxidizing biocide to effectively prevent scale formation and bacterial growth in the open loop system.
I delivered 10/gallons of inhibitor CWT-1644 and 5/gallons of Biocide Isothiazolin KTND.
I manually added supplemental biocide to the cooling towers today. The towers got the solid halogen
NAS Key West – TRUMBO POINT BLDG C-4084 – FLY NAVY Date: 02/17/2022
TEST CITY WATER TOWER #1 CONTROL
LIMITS
Conductivity 385 1754 1500-2000
CWT1644 0 150 40-80
Total Alkalinity 40 320 <300 Calcium Hardness 110 430 <600 pH 8.6 9.2 8.5-9.5 Chlorides 40 200 150-250 Chemical Inventory 15/16 gal inhib / gal biocide Water Meter 50250 Gallons
Chiller 1 80.6 85.9 97.6 86.3 0.2 50.2%
I arrived today and went to the chiller room. I inspected the current conditions of the chiller room and the equipment. The chiller was online providing 45° chilled water to the building. Everything regarding the chiller appeared and sounded to be operating normally.
I inspected the chemical treatment station and tested all equipment. The conductivity controller was calibrated to the current conditions. I also found there was adequate water flow through the station bypass piping. I tested both chemical feed pumps and found they were primed and online delivering products.
I manually added supplemental biocide to the cooling towers today. The towers got the solid halogen
NAS Key West – TRUMAN ANNEX BLDG 1352 Date: 02/17/2022
TEST CITY WATER TOWER
#1
TOWER
#2
CONTROL
LIMITS
Conductivity 385 offline 1557 1500-2000 CWT1644 0 Valved off 145 40-80 Total Alkalinity 40 220 <300 Calcium Hardness 110 460 <600 pH 8.6 9.3 8.5-9.5 Chlorides 40 140 150-250 Chemical Inventory 14/19 gal inhib / gal biocide
Chiller 1 78.9 84.5 95.0 84.9 0.4 47.4
I arrived today and went to the chiller room. I inspected the current conditions of the chiller room and the equipment. The chiller was online providing 45° chilled water to the building. Everything regarding the chiller appeared and sounded to be operating normally.
I inspected the chemical treatment station and tested all equipment. The conductivity controller was calibrated to the current conditions. I also found there was adequate water flow through the station bypass piping. I tested both chemical feed pumps and found they were primed and online delivering products.
I sampled and tested the condenser water and the test result show the condenser water chemistry is within the desired control limits.
I delivered 5/gallons of inhibitor CWT-1644.
I manually added supplemental biocide to the cooling towers today. The towers got the solid halogen
NAS Key West – TRUMAN ANNEX BLDG: 290- JIATF Date: 02/17/2022
TEST CITY WATER TOWER CONTROL
LIMITS
Conductivity 385 1592 1500-2000
CWT-1644 0 95 40-80
Total Alkalinity 40 210 <300 Calcium Hardness 110 430 <600 pH 8.6 9.2 8.5-9.5 Chlorides 40 160 150-250 Chemical Inventory 13/14 inhib / biocide Water Meter Gallons
Chiller 1 79.1 83.9 94.3 84.4 0.5 37.2%
UTILITY LOCATION REPORT
(1601000 / 3.1.1)
FEBRUARY 15 – MARCH 14, 2022, MONTHLY
UTILITY LOCATE REPORT
Description Location WO# Status Scheduled
Priority Site Competition
Date
** Not applicable this month**