About this file

This is a plumbing and mechanical design document prepared for Building 60 Repairs at Portsmouth Naval Shipyard in Kittery, Maine, under the Department of the Navy Naval Facilities Engineering Systems Command (NAVFAC). The document contains comprehensive schedules and specifications for plumbing fixtures, pumps, water heaters, mixing valves, backflow preventers, expansion tanks, automatic trap primers, floor drains, and radon mitigation equipment required for the project.

The key equipment and specifications include: a DHW recirculation pump (RP-1, Taco Genie 008 or Zoeller N152) located in Mechanical Room M106 with a packaged system featuring oil switch, float switch, and NEMA 4x alarm control panel; multiple plumbing fixtures such as water closets, lavatories, sinks, and emergency eyewash stations with specific mounting heights and ADA compliance requirements; two electric water heaters (EWH-1 and EWH-2, Lochinvar CHPA120PD and Rheem XE20 models) with capacities of 120-140 gallons and recovery rates at 95°F temperature differential; thermostatic mixing valves (Leonard XL32A-LF and 170-LF-SSTL) set to deliver 120°F domestic hot water and 78°F tempered water for eyewash stations; backflow preventers (Watts LP 009) for building water service and heating water make-up; expansion tanks (Amtrol ST series) for potable water systems; eight automatic trap primer assemblies (Precision Plumbing Products PT-4) located throughout the facility; and radon mitigation equipment (Fantech 4EC-4 fan) as an optional component. All specifications include detailed installation requirements, basis of design information, and manufacturer requirements. The document was finalized on October 1, 2025, with Amendment 008 approved on March 10, 2026.

View the file

Other files

File Type Posted
Att. GG) Amendment 0011 Attachment Table of Contents.pdf PDF
Solicitation Amendment N6247026R00120010 SF 30.pdf PDF
Att. T) Price Schedule AMD 0010.pdf PDF
01 30 10.00 22_AMENDMENT 010.pdf PDF
115_AE402_R1_AMENDMENT 010.pdf PDF
161_Q-601_R2_AMENDMENT 010.pdf PDF
170_P-102_R1_AMENDMENT 010.pdf PDF
171_P-103_R1_AMENDMENT 010.pdf PDF
175_P-107_R1_AMENDMENT 010.pdf PDF
677 attach Attic_AFPR.pdf PDF
Att. Y) PPI responses AMD 0009.pdf PDF
_B60_Continuation Sheet_Amendment 0009.pdf PDF
07 27 10_AMENDMENT 009.pdf PDF
95_AE104_R1_AMENDMENT 009.pdf PDF
216_M505_R1_AMENDMENT 009.pdf PDF
217_M601_R1_AMENDMENT 009.pdf PDF
262_EP603_R1_AMENDMENT 009.pdf PDF
268_EL104_R1_AMENDMENT 009.pdf PDF
Att. T) Price Schedule AMD 0009.pdf PDF
Att. EE) Amendment 0009 Attachment Table of Contents.pdf PDF
Att.pdf PDF
Att. Y) PPI responses AMD 0008.pdf PDF
_B60_Continuation Sheet_Amendment 008.pdf PDF
01 11 00.00 22_R1_AMENDMENT 008.pdf PDF
72_SF506_R1_AMENDMENT 008.pdf PDF
220_M-701_R1_AMENDMENT 008.pdf PDF
02 83 00.00 22_R1_AMENDMENT 008.pdf PDF
02 84 16.00 22_R1_AMENDMENT 008.pdf PDF
148_AE804_R1_AMENDMENT 008.pdf PDF
193_MD109_R1_AMENDMENT 008.pdf PDF
210_MP107_R1_AMENDMENT 008.pdf PDF
Att. CC) Site Visit Log.pdf PDF
Att. R) B60 ISRL AMD 0004.XLSX XLSX spreadsheet
Att. Y) PPI responses AMD 0004.pdf PDF
Att. AA) B60 AMD 004 Drawings 012726.pdf PDF
Att. F) Individual Small Business Subcontracting Plan AMD 0004.docx DOCX document
Att. Z) B60 Continuation Sheet AMD 004.pdf PDF
Att. W) DBIDS 5512 FORM.pdf PDF
AMD 0002 PPI responses.pdf PDF
Att. A) - Construction Experience Project Data.docx DOCX document
Att. D) - Historical Small Business Utilization.docx DOCX document
Att. E) - Small Business Participation Commitment Document (SBPCD).docx DOCX document
Att. F) - Individual Small Business Subcontracting Plan.docx DOCX document
Att. H) Specifications Volume 1.pdf PDF
Att. J) Specifications Volume 3.pdf PDF
Att. K) Drawings Volume 1a.pdf PDF
Att. R) B60 - ISRL.XLSX XLSX spreadsheet
Att. I) Specifications Volume 2.pdf PDF
Att. L) Drawings Volume 1b.pdf PDF
Att. P) 01 45 35a Statement_of_Special_Inspections.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNIT NO SERVES

RP-1

PUMP SCHEDULE

DHW RECIRC

LOCATION

MECH. M106

TYPE GPM

IN-LINE 3.0

TOTAL

HEAD

MOTOR DATA

SP-1 ELEV PIT ELEV SHAFT SUMP 50.0 10

NOTES: 1. PROVIDE STAINLESS STEEL PUMP FOR POTABLE WATER.

2. PROVIDE PACKAGED PUMP SYSTEM WITH OIL SWITCH, FLOAT SWITCH, AND NEMA 4x ALARM AND CONTROL PANEL WITH H-O-A SWITCH, AUDIO AND VISUAL ALARM

DEVICES, AND DRY ALARM CONTACT FOR DDC SYSTEM INTERFACE.

SUCTION/

DISCHARGE

(IN)

BASIS OF DESIGN NOTES

1/1 TACO GENIE 008 1

VOLTS/PHASE

115/1

HP

1/8

RPM

11.5 ZOELLER N152 OIL GUARD SYSTEM 24/10 115/1-

REMARKSHWVENTWASTEDESCRIPTIONUNIT NO

PLUMBING FIXTURE ROUGH-IN SCHEDULE

BASIS OF DESIGN

1. FOR FIXTURE, FAUCET, AND/OR FAUCET MOUNTING HEIGHTS, SEE AE002.

2. PROVIDE WITH ASSE 1070 TEMPERATURE LIMITING DEVICE, EITHER INTEGRAL WITH FAUCET OR SUPPLIED ON HOT WATER LINE TO FAUCET.

NOTES:

CW

FLOOR MOUNTED, FLOOR OUTLET, MANUAL FLUSH VALVE, ADA HEIGHT1"-2"4"WATER CLOSETWC-1

FLOOR MOUNTED, FLOOR OUTLET, MANUAL FLUSH VALVE1"-2"4"WATER CLOSETWC-2

WALL HUNG, MANUAL FLUSH VALVE, ADA HEIGHT3/4"-1 1/2"2"URINALU-1

OVAL, STAINLESS STEEL, COUNTERTOP, UNDERMOUNT, MANUAL FAUCET, ADA HEIGHT1/2"1/2"1 1/2"1 1/2"LAVATORY, COUNTERL-1

SINGLE-BASIN, STAINLESS STEEL, COUNTERTOP, UNDERMOUNT, ADA HEIGHT1/2"1/2"1 1/2"2"SINK, KITCHENETTES-1

WALL MOUNTED, STAINLESS STEEL, THREE MANUAL FAUCETS, ADA HEIGHT3 @ 1/2"3 @ 1/2"1 1/2"2"3-STATION WASH SINKS-3

FLOOR MOUNTED, 24x24 NEO-ANGLE DROP FRONT TERAZZO, MANUAL WALL FAUCET1/2"1/2"1 1/2"3"MOP RECEPTORMR-1

WALL MOUNTED, BI-LEVEL, WITH BOTTLE FILLER, FIXTURE CARRIER, NO FILTER1/2"-1 1/2"1 1/2"ELECTRIC WATER COOLEREWC-1

SURFACE MOUNTED, CHROME FINISH, WHEEL HANDLE3/4"---HOSE BIBBHB

RECESSED, WITH INTEGRAL BALL VALVE1/2"---COFFE MAKER OUTLET BOXCOB

SEE DRAIN SCHEDULE1/2" TP-1 1/2"2"FLOOR DRAINFD-1

SEE DRAIN SCHEDULE1/2" TP-1 1/2"3"FLOOR DRAINFD-2

SEE DRAIN SCHEDULE1/2" TP-2"4"FLOOR DRAINFD-3

SEE DRAIN SCHEDULE1/2" TP-2"4"FLOOR SINKFS-1

WALL MOUNTED W/ COVER (*TEMPERED WATER), WITH EMERGENCY ALARM SYSTEM 1/2"*EMERGENCY EYEWASHEW-1

S-2 UTILITY SINK 2" 1 1/2" 1/2" 1/2" PLASTIC DEEP BASIN W/ STEEL LEGS, MANUAL FAUCET

WALL HUNG, CONCEALED CARRIER, MANUAL FAUCET, ADA HEIGHT1/2"1/2"1 1/2"1 1/2"LAVATORY, WALL HUNGL-2

AMERICAN STANDARD MADERA 2854.016

AMERICAN STANDARD MADERA 2858.016

AMERICAN STANDARD WASHBROOK 6590.501

ELKAY ASANA ELUH1511

SLOAN SS-3003

ELKAY ELUHAD 191655

ELKAY EWMA6020C

SWAN MODEL MF-F

FLORESTONE MODEL 96

HAWS MODEL 7360 BTWC, HAWS 9001.5

ELKAY EZSTLG8WSSK

WATTS LP 009 QTS14882"RPZBUILDING WATER SERVICEINSPECTION 112BFP-1

NOTESBASIS OF DESIGN

MAX WPD

@ DESIGN

(PSI)

DESIGN

FLOW

(GPM)

SIZETYPESYSTEM SERVEDLOCATIONUNIT NO

BACKFLOW PREVENTER SCHEDULE

MAX RELIEF FLOW

RATE @ 55 PSI

(GPM)

WATTS LP 009 QTS12151"RPZHEATING WATER MAKE-UPMECH 115BFP-2 150

1. PROVIDE WITH BALL TYPE ISOLATION VALVES AND AIR GAP FITTING FOR DRAIN.NOTES:

14045119CUSTODIAL M106EWH-1

STORAGE

GALLONS

LOCATIONUNIT NO BASIS OF DESIGN

LOCHINVAR CHPA120PD

NOTES

ELECTRIC WATER HEATER SCHEDULE

VOLTS /

PHASE

HW OUTLET

TEMP °F

460 / 3

TOTAL

INPUT

KW

12.0

NUMBER OF

ELEMENTS

WATTAGE

PER ELEMENT

MIN GPH

RECOVERY

@95°ΔT

CW INLET

TEMP °F

NOTES: 1.

OPEN OFF 2ND FLOOR 2.5 45 120 1440 1 1.44 120 / 1EWH-3 RHEEM XE02

1404520SHOP 111EWH-2 RHEEM XE20120 / 12.01200095

PRESSURE DROP

(PSIG)

120°DOMESTIC HOT WATERMECH M106

BASIS OF DESIGN

MIN

GPM

DESIGN

GPM

SUPPLY

TEMP °F

OUTLETINLETSERVESLOCATION

TMV-1

UNIT

NO

MIXING VALVE SCHEDULE

20 1.0 15.0

NOTES

1,23/4" 1" LEONARD XL32A-LF

NOTES:

1. PROVIDE VALVE IN MANUFACTURER'S LOCKABLE, PAINTABLE STEEL CABINET.

2. PROVIDE HIGH-LOW, DUAL MIXING VALVE ASSEMBLY WITH INTEGRAL MANUFACTURER'S OUTLET THERMOMETER.

3. PROVIDE VALVE IN MANUFACTURER'S RECESSED LOCKABLE, PAINTABLE STEEL CABINET.

4. PROVIDE VALVE IN MANUFACTURER'S SURFACE MOUNTED, LOCKABLE, PAINTABLE STEEL CABINET.

TMV-2 SHOP 111 DOMESTIC HOT WATER 1/2" 1/2" 120° 3 0.3 5.0 LEONARD 170-LF-STSTL EXP 3

EMV-1 SHOP 111 EYEWASH-SHIP 111 1/2" 1/2" 78° 3 5.0 GUARDIAN G6020

EMV-2 SHOP 207 EYEWASH-SHOP 207 1/2" 1/2" 78° 3 5.0 GUARDIAN G6020

NOTESBASIS OF DESIGN

DIMENSIONS

(IN)

ACCEPTANCE

VOLUME

SERVESLOCATIONUNIT NO

EXT-P1

EXPANSION TANK SCHEDULE

MECH M106 DOMESTIC WATER 3.2 12ø x 18 AMTROL ST-12C-DD

MIN TANK

VOLUME (GAL)

6.4 1

NOTES: 1. PROVIDE DIAPHRAGM TANK LISTED FOR USE WITH POTABLE WATER.

EXT-P2 SHOP 111 DOMESTIC WATER 0.35 8ø x 13 AMTROL ST-51.4 1

NOTES:

TPA-1 CUSTODIAL 107 4 3 1/2" 120 / 1 PRECISION PLUMBING PRODUCTS PT-4

NOTESBASIS OF DESIGN

VOLTS /

PHASE

CONN

SIZE

NO OF

DESIGN

CONNECTIONS

NO OF

MANIFOLD

OPENINGS

MOUNTINGLOCATIONUNIT NO

AUTOMATIC TRAP PRIMER ASSEMBLY SCHEDULE

RECESSED

1. CAP UNUSED OUTLETS.

2. PROVIDE WITH MANUFACTURER'S LOCKABLE, PAINTABLE STEEL PANEL ACCESS DOOR.

1, 2

TPA-2

TPA-3

RECESSED

RECESSED

1 1/2"

1/2"

120 / 1

120 / 1

TPA-4

TPA-5

RECESSED

RECESSED

1/2"

1/2"

120 / 1

120 / 1

TPA-6

TPA-7

RECESSED

RECESSED

1/2"

1/2"

120 / 1

120 / 1

TPA-8 RECESSED 1/2" 120 / 1

INSPECTION 112

MECH 115

FIRE PUMP M107

MECH M106

MECH MEZZ M107

WOMEN 203

MEZZANINE M201

4 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

14 PRECISION PLUMBING PRODUCTS PT-4 1, 2

6" x 6"2"SQUARE DRAIN FOR FINISHED SPACESFLOOR DRAIN

NOTES

STRAINER

DIMENSIONS

PIPE SIZEDESCRIPTIONTYPE

FD-1

UNIT

NO

DRAIN SCHEDULE

BASIS OF DESIGN

ZURN EZ-PV2-S6 1,3

1. PROVIDE TRAP PRIMER CONNECTION TO FLOOR DRAIN OR FLOOR SINK.

2. PROVIDE WITH SEDIMENT BUCKET.

3. PROVIDE WITH CHROME PLATED FINISH.

NOTES:

7ø3"ROUND DRAIN FOR UNFINISHED SPACES W/ FUNNELFLOOR DRAINFD-2 1,2

7ø4"ROUND DRAIN FOR UNFINISHED SPACES W/ FUNNELFLOOR DRAINFD-3 1,2

6" x 6"4"1/2" GRATE, 6" DEEPFLOOR SINKFS-1 1,2

ZURN Z415E

ZURN Z415E

ZURN

2200RADON MITIGATIONRF-1

CFMSERVESUNIT NO ACCESSORIES

FANTECH 4EC-4

NOTES

RADON FAN SCHEDULE (OPTION 3)

VOLTS /

PHASE

DRIVE

TYPE

WATTS

FAN

RPM

FAN

TYPE

ESP IN

WC

IN-LINE

BASIS OF DESIGN

A, B, C1,2DIRECT 120 / 1

NOTES: 1. PROVIDE UNDER OPTION 3 ONLY

2. TYPICAL FOR 3 FANS

3. FOR DDC SYSTEM FAN MONITORING AND ALARM CONTROL POINTS, SEE C2/M-705.

ACCESSORIES: A. MFR INTEGRAL FAN SPEED CONTROLLER.

B. MFR ANTI-VIBRATION COUPLERS FOR 4" PVC PIPE.

C. WALL MOUNTING BRACKET FOR VERTICAL INSTALLATION.

ISOLATION BALL

VALVE (TYP)

3/4" CW

EXT-P2

MIXING VALVE

TMV-2

AND RECESSED

ENCLOSURE

EMERGENCY

EYEWASH, EW-1

1/2" CW (IN WALL)

3/4" DRAIN

WALL MOUNTED EQUIPMENT

PLATFORM WITH INTOGRAL

DRAIN PAN

1/2" HW(140°F) TO EYEWASH

MIXING VALVE, EMV-1

RELIEF VALVE

VACUMM BREAKER

EWH

EWC

1 UTILITY SINK, S-2

3/4" HW

1/2" (IN WALL)

1/2" (IN WALL)

3/4" (IN WALL)

78°F

TO 120V POWER

SOURCE

1/2" TEMPERED WATER

PIPING WITH

INSULATION AND PVC

JACKET WHERE

EXPOSED FROM

THERMOSTATIC MIXING

VALVE EMV-1

FLEXIBLE CONDUIT

FLOW SWITCH

1 1/2" VENT

1 1/4" TRAP IN WALL OR

PARALLEL TO WALL

2" WASTE

WALL MOUNTED

LIGHT, HORN, AND

SILENCE SWITCH

EMERGENCY

EYE/FACEWASH

STAINLESS STEEL

EYEWASH BOWL

WITH COVER

1 1/2" IPS DRAINl

FLOOR LINE

NOTE: INSTALL IN ACCORDANCE WITH MANUFACTURES'S

RECOMMENDED WRITTEN BARRIER FREE INSTALLATION INSTRUCTIONS.

EW-1

1/2" BALL VALVE (TYP OF 2) PROVIDE WARNING

TAG AS FOLLOWS: "SHUTOFF VALVE FOR

EMERGENCY EYEWASH UNIT TO BE CLOSED BY

AUTHORIZED PERSONNEL ONLY."

THERMOMETER

BALL VALVE WITH LEER

HANDLE REMOVED AND

ZIP-TIED TO PIPE AT VALVEPIPING TO EMERGENCY

EYEWAS: 1/2" TW TO EM-1

THERMOSTATIC MIXING VALVE, MOUNT

AT 72" AFF IN CABINET, ADJUST TO

THE FOLLOWING TEMPERED WATER

DISCHARGE TEMPERATURE: 78°F

T W

SATISFACTORY TO DATE

APPROVED

FOR COMMANDER NAVFAC

SEAL

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SHEET

NAVFAC DRAWING NO.

DESIGNER

DRAWN BY

CHECKED BY

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

DRAWFORM REVISION: 14 SEP 2023

DESIGN MANAGER

PROJECT MANAGER

FEAD/PM&E

FIRE PROTECTION

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G S

Y S

T E

M S

C O

M M

A N

D

M

ID

-A T

LA

N

T

IC

P O

R T

S M

O U

T H

N A

V A

L S

H

IP

Y A

R D

K

IT

T

E R

Y M

E

UNCLASSIFIED

UNCLASSIFIED

U N

C L

A S

S

IF

IE

D

ACTIVITY

1740579

T. CARLETON

L. LYONS

S. RUCINSKI

/2

/2

:1

:4

P

M

C U s e rs \m d o n o v a n \D o c u m e n ts \2

.2

B

L D

G

M

E C

H A

N

IC

A L

-V m d o n o v a n

V F

X R

.r v t

P-601

B R

E P

A

IR

S

P L U

M B

IN

G

S C

H E

D U

L E

S A

N D

D E

T A

IL

MSA

RNC

SRW

K

IT

T E

R Y

M

E P

O R

T S

M O

U T

H N

A V

A L S

H

IP

Y A

R D

R O

IC

C

-M E

P -6

SCALE: NOT TO SCALE

A3

ELECTRIC WATER HEATER

EWH-2 PIPING DETAIL

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

F

IN

A L

S U

B M

IS

S

IO

N

/0

1/

R

S H

A

M E

N D

M E

N T

/10 /2

R S

H

SCALE: NTS

A4

EMERGENCY EYEWASH DETAIL

SCALE: NTS

A5

TYPICAL EMERGENCY TEMPERED

WATER MIXING VALVE(EMV-_) DETAIL

Sheets
M-701 - MECHANICAL CONTROL DIAGRAMS 1
MD106 - FIRST FLOOR MEZZANINE MECHANICAL REMOVALS PLAN - WEST
MD108 - SECOND FLOOR MEZZANINE MECHANICAL REMOVALS PLAN
MD109 - ATTIC MECHANICAL REMOVALS PLAN
MP107 - ATTIC MECHANICAL PIPING PLAN
P-401 - ENLARGED PLUMBING PART PLANS 1
P-601 - PLUMBING SCHEDULES AND DETAIL