1748123Amendment0006_Specs.pdf
PDF 4 MB Posted
- Attached to
- N4008526R0037 P1574/P1591/P1592 MCB CAMP LEJEUNE
- Solicitation number
- N4008526R0037
About this file
This document is a collection of federal contract specifications and permits for construction projects at MCB Camp Lejeune, North Carolina, specifically the P-1592 2nd MRSB Operational Support Facility project and related MARSOC Complex development.
The specifications include detailed technical requirements for steel doors and frames (Section 08 11 13), overhead coiling doors (Section 08 33 23), paints and coatings (Section 09 90 00), and high-performance epoxy coatings (Section 09 96 00). Steel doors must comply with SDI/DOOR A250.8 standards with minimum 25% recycled content; exterior doors require Level 4 classification and blast-resistant testing per ASTM F2247 or ASTM F2927, with insulated systems meeting U-factor of 0.48. Overhead coiling doors must feature Type 304 stainless steel slats, spring counterbalance systems, and electric operators with safety interlocks, designed for 12-20 operational cycles daily and meeting ANSI/DASMA 108 wind loading standards. Paint specifications reference MPI standards for various substrates (metal, concrete, masonry, wood), with minimum dry film thickness of 1.5 mils per coat and low-VOC institutional products required. High-performance coatings require polyamide-cured epoxy resins with 4-mil minimum dry film thickness on exterior surfaces and specialized primers per MPI 101.
Additionally, the file includes North Carolina environmental permits: an Erosion and Sedimentation Control Plan approval (Permit ONSLO-2026-0241, issued February 2, 2026) for 6.00 acres of land disturbance, and a Post-Construction Stormwater Management Permit (SW8 070847, effective through January 23, 2030) governing stormwater control measures including 18 alternative sand filters, 14 standard sand filters, and 5 infiltration basins. The stormwater permit establishes built-upon area limits of 25% for the 613.37-acre tract and 12% for the 92.45-acre tract, with detailed design criteria, maintenance schedules requiring semiannual inspections and sediment removal, and designer certification requirements upon project completion.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1592 2ND MRSB OPERATIONAL SUPPORT FACILITY (OSF) AMEND0006 1748123
MCB CAMP LEJEUNE, NC
PROJECT TABLE OF CONTENTS
DIVISION 08 - OPENINGS
08 11 13 08/20 STEEL DOORS AND FRAMES
08 33 23 08/20, CHG 1: 02/22 OVERHEAD COILING DOORS
DIVISION 09 - FINISHES
09 90 00 02/21 PAINTS AND COATINGS
09 96 00 11/14 HIGH-PERFORMANCE COATINGS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 1
THIS PAGE INTENTIONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 2
SECTION 08 11 13
STEEL DOORS AND FRAMES
08/20
AMENDMENT 0006
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A879/A879M (2012; R 2017) Standard Specification for Steel Sheet, zinc Coated by the Electrolytic Process for Applications Requiring Designation of the Coating Mass on Each Surface
ASTM C578 (2019) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C591 (2021) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C612 (2014; R 2019) Standard Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM D2863 (2019) Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM E1300 (2016) Standard Practice for Determining Load Resistance of Glass in Buildings
ASTM F2247 (2018) Standard Test Method for Metal Doors Used in Blast Resistant Applications (Equivalent Static Load Method)
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
ASTM F2927 (2012) Standard Test Method for Door Systems Subject to Airblast Loadings
SECTION 08 11 13 Page 1 02/27/2026
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2016) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2022) Standard for Fire Doors and Other Opening Protectives
NFPA 105 (2022) Standard for Smoke Door Assemblies and Other Opening Protectives
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 111 (2009) Recommended Details for Standard Steel Doors, Frames, and Accessories and Related Components
SDI/DOOR 113 (2013; R2018) Standard Practice for Determining the Steady-State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.4 (2018) Test Procedure and Acceptance Criteria for Physical Endurance for Steel Doors, Frames and Frame Anchors
SDI/DOOR A250.6 (2015) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2017) Specifications for Standard Steel Doors and Frames
SDI/DOOR A250.11 (2012) Recommended Erection Instructions for Steel Frames
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 4-010-01 (2018; with Change 1, 2020; Change 2, 2022) DoD Minimum Antiterrorism Standards for Buildings
UNDERWRITERS LABORATORIES (UL)
UL 10C (2016; Reprint May 2021) UL Standard for Safety Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SECTION 08 11 13 Page 2 02/27/2026
SD-02 Shop Drawings
Doors ; G
Frames ; G
Accessories
Schedule of Doors ; G
Schedule of Frames ; G
SD-03 Product Data
Doors ; G
Recycled Content for Steel Door Product ; S
Frames ; G
Recycled Content for Steel Frame Product ; S
Accessories
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Strap knock-down frames in bundles. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8 , except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00 DOOR HARDWARE. Undercut where indicated. Provide exterior doors with top edge closed flush and sealed to prevent water intrusion. Provide doors at 1-3/4 inch thick, unless otherwise indicated. Provide door material that uses a minimum of 25 percent recycled content. Provide data indicating percentage of recycled content for steel door product . Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300. Exterior doors must be tested in accordance with ASTM F2247 or ASTM F2927 to meet requirements of
UFC 4-010-01 .
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Heavy Duty Doors
SDI/DOOR A250.8 , Level 2, physical performance Level B, Model 2, with core construction as required by the manufacturer for interior doors, of size(s) and design(s) indicated. Provide Level 2 typically at mechanical rooms, and other interior locations as indicated.
SECTION 08 11 13 Page 3 02/27/2026
2.1.1.2 Maximum Duty Doors
SDI/DOOR A250.8 , Level 4, physical performance Level A, Model 2 with core construction as required by the manufacturer for interior doors and for indicated exterior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners must be filled with board insulation. Provide Level 4 typically at all exterior doors. Fabricate from metallic-coated steel sheet for exterior doors.
2.2 INSULATED STEEL DOOR SYSTEMS
Provide insulated steel doors and frames in accordance with SDI/DOOR 113 where indicated. Meet energy requirements including Solar Heat Gain Coefficient (SHGC) and U-factor. Provide insulated steel doors with a core of polyurethane foam; face sheets, edges, and frames of galvanized steel not lighter than 23 gage , 16 gage , and 16 gage respectively;
magnetic weatherstripping; nonremovable-pin hinges; thermal-break aluminum threshold; and vinyl door bottom. Finish doors and associated frames and louvers in accordance with section 09 96 00 HIGH-PERFORMANCE COATINGS.
Test doors in accordance with SDI/DOOR A250.4 and meet the requirements for Level C. Prepare doors to receive specified hardware. Provide doors 1-3/4 inch thick.
2.3 ACCESSORIES
2.3.1 Louvers
2.3.1.1 Interior Louvers
SDI/DOOR 111 . Where indicated, provide louvers of stationary sightproof where scheduled. Detachable moldings on room or non security side of door;
on security side of door, moldings to be integral part of louver. Form louver frames of 20 gage steel and louver blades of a minimum 24 gage .
2.3.1.2 Exterior Louvers
Provide louvers of the inverted "Y" type with minimum of 55 percent net-free opening. Weld or tenon louver blades to continuous channel frame and weld assembly to door to form watertight assembly. Form louvers of hot-dip galvanized steel of same gage as door facings. At louvers provide steel-framed bird screens secured to room side and readily removable.
Provide galvanized steel, 1/2 by 1/2 inch mesh hardware cloth, for bird screens. Net-free louver area to be before screening.
2.3.2 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors.
2.3.3 Moldings
Provide moldings around glass of interior and exterior doors and louvers of interior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings.
SECTION 08 11 13 Page 4 02/27/2026
2.4 INSULATION CORES
Provide insulating cores at all exterior doors, and provide an apparent U-factor of .48 in accordance with SDI/DOOR 113 and conforming to:
a. Rigid Cellular Polyisocyanurate Foam: ASTM C591, Type I or II, foamed-in-place or in board form, with oxygen index of not less than 22 percent when tested in accordance with ASTM D2863; or
b. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
c. Mineral board: ASTM C612, Type I.
2.5 STANDARD STEEL FRAMES
SDI/DOOR A250.8 , Level 2, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners. Provide steel frames for doors, transoms, sidelights, mullions, cased openings, and interior glazed panels, unless otherwise indicated. Provide frame product that uses a minimum of 25 percent recycled content. Provide data indicating percentage of recycled content for steel frame product .
2.5.1 Welded Frames
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.5.2 Mullions and Transom Bars
Provide mullions and transom bars of closed or tubular construction with heads and jambs butt-welded together. Bottom of door mullions must have adjustable floor anchors and spreader connections.
2.5.3 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated not lighter than 18 gage .
2.5.3.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring or welding;
c. Completed openings: Secure frames to previously placed concrete or masonry with expansion bolts in accordance with SDI/DOOR 111 ;
and
SECTION 08 11 13 Page 5 02/27/2026
2.5.3.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member. Where floor fill occurs, terminate bottom of frames at the indicated finished floor levels and support by adjustable extension clips resting on and anchored to the structural slabs.
2.6 FIRE AND SMOKE DOORS AND FRAMES
Provide fire and smoke doors and frames in accordance with NFPA 80 and NFPA 105 and this specification.
2.6.1 Labels
Provide fire doors and frames bearing the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required.
Testing must be in accordance with NFPA 252 or UL 10C . Provide labels that are metal with raised letters, bearing the name or file number of the door and frame manufacturer. Labels must be permanently affixed at the factory to frames and to the hinge edge of the door. Do not paint door and labels.
2.6.2 Oversized Doors
For fire doors and frames which exceed the size for which testing and labeling are available, furnish certificates stating that the doors and frames are identical in design, materials, and construction to a door which has been tested and meets the requirements for the class indicated.
2.6.3 Astragal on Fire and Smoke Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements.
On smoke control doors, conform to NFPA 105 .
2.7 EXTERIOR FRAMES
Provide thermal insulation in all exterior frames. Provide frames of a minimum Level 4, with frames of a minimum thickness of 0.067 inch , 14 gage.
2.8 HARDWARE PREPARATION
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6 . For additional requirements refer to ANSI/BHMA A156.115 . Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Punch door frames, with the exception of frames that will have weatherstripping or soundproof gasketing, to receive a minimum of two rubber or vinyl door silencers on lock side of single doors and one silencer for each leaf at heads of double doors. Set lock strikes out to provide clearance for silencers.
2.9 FINISHES
2.9.1 Factory-Primed Finish
Thoroughly clean all surfaces of doors and frames then chemically treat
SECTION 08 11 13 Page 6 02/27/2026 and factory prime with a rust inhibiting coating as specified in
SDI/DOOR A250.8 .
2.9.2 Electrolytic Zinc-Coated Anchors and Accessories
Provide electrolytically deposited zinc-coated steel in accordance with ASTM A879/A879M , Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc-coated surfaces as specified in SDI/DOOR A250.8 .
2.10 FABRICATION AND WORKMANSHIP
Provide finished doors and frames that are strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Provide molded members that are clean cut, straight, and true, with joints coped or mitered, well formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints must be well formed and in true alignment. Conceal fastenings where practicable. On wraparound frames for masonry partitions, provide a throat opening 1/8 inch larger than the actual masonry thickness. Design frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
Set frames in accordance with SDI/DOOR A250.11 . Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction.
3.1.2 Doors
Hang doors in accordance with clearances specified in SDI/DOOR A250.8 .
After erection and glazing, clean and adjust hardware.
3.1.3 Fire and Smoke Doors and Frames
Install fire doors and frames, including hardware, in accordance with NFPA 80 . Install fire rated smoke doors and frames in accordance with NFPA 80 and NFPA 105 .
3.2 PROTECTION
Protect doors and frames from damage. Repair damaged doors and frames prior to completion and acceptance of the project or replace with new, as directed. Wire brush rusted frames until rust is removed. Clean thoroughly. Apply an all-over coat of rust-inhibitive paint of the same type used for shop coat.
3.3 CLEANING
Upon completion, clean exposed surfaces of doors and frames thoroughly.
Remove mastic smears and other unsightly marks.
-- End of Section --
SECTION 08 11 13 Page 7 02/27/2026
SECTION 08 11 13 Page 8 02/27/2026
SECTION 08 33 23
OVERHEAD COILING DOORS
08/20, CHG 1: 02/22
AMENDMENT 0006
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE FUN IP (2021) Fundamentals Handbook, I-P Edition
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B29.400 (2001; (R 2008) (R 2013) (R 2018))
Combination, "H" Type Mill Chains, and Sprockets
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A47/A47M (1999; R 2018; E 2018) Standard Specification for Ferritic Malleable Iron Castings
ASTM A53/A53M (2022) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A153/A153M (2016a) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2021) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A666 (2015) Standard Specification for Annealed
SECTION 08 33 23 Page 1 02/27/2026 or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM A780/A780M (2020) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A924/A924M (2022) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E330/E330M (2014; R 2021) Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference
ASTM F568M (2007) Standard Specification for Carbon and Alloy Steel Externally Threaded Metric Fasteners
DOOR AND ACCESS SYSTEM MANUFACTURERS ASSOCIATION (DASMA)
ANSI/DASMA 108 (2017) Standard Method for Testing Sectional Garage Doors, Rolling Doors and Flexible Doors: Determination of Structural Performance Under Uniform Static Air Pressure Difference
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA MG 1 (2021) Motors and Generators
NEMA ST 1 (1988; R 1994; R 1997) Specialty Transformers (Except General Purpose Type)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 1 2024; TIA 24-1; TIA 25-2)
National Electrical Code
SECTION 08 33 23 Page 2 02/27/2026
UNDERWRITERS LABORATORIES (UL)
UL 325 (2017; Reprint Feb 2020) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Overhead Coiling Doors ; G
Electric Door Operators ; G
Installation Drawings ; G
SD-03 Product Data
Overhead Coiling Doors ; G
Hardware ; G
Electric Door Operators ; G
SD-05 Design Data
Overhead Coiling Doors ; G
Hardware ; G
Electric Door Operators ; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Manuals , Data Package 2; G
SD-11 Closeout Submittals
Warranty ; G
1.3 QUALITY CONTROL
1.3.1 Warranty
Furnish a written guarantee that the helical spring and counterbalance mechanism are free from defects in material and workmanship for not less than two years after completion and acceptance of the project.
Warrant that upon notification by the Government, any defects in material, workmanship, and door operation are immediately correct within the same time period covered by the guarantee, at no cost to the Government.
SECTION 08 33 23 Page 3 02/27/2026
1.3.2 Operation And Maintenance Submittals
Submit 6 copies of the operation and maintenance manuals 30 calendar days prior to testing the Overhead Coiling Door Assemblies. Update and resubmit data for final approval no later than 30 calendar days prior to cContract completion.
Submit Operation and Maintenance Manuals for Overhead Coiling Door Assemblies, including the following items:
Electric Door Operators
Hood
Counterbalancing Mechanism
Painting
Provide operation and maintenance manuals which are consistent with manufacturer's standard brochures, schematics, printed instructions, operating procedures, and safety precautions.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the jobsite wrapped in a protective covering with the brands and names clearly marked thereon. Store doors in an adequately ventilated dry location that is free from dirt and dust, water, or other contaminants. Store in a manner that permits easy access for inspection and handling. Handle doors carefully to prevent damage. Remove damaged items that cannot be restored to like-new condition and provide new items.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide overhead coiling doors with interlocking slats, complete with anchoring and door hardware, guides, hood, and operating mechanisms, and designed for use on openings as indicated. Doors must be spring counterbalanced, rolling type, and designed for use on exterior openings, as indicated. Doors must be operated by electric-power with auxiliary hand chain operation. Doors to be surface-mounted type with guides at jambs set back a sufficient distance to provide a clear opening when door is in open position. Mount exterior doors as indicated.
2.1.1 Design Requirements
2.1.1.1 Door Detail Shop Drawings
Provide installation drawings for door assemblies which show: elevations of each door type, shape and thickness of materials, finishes, details of joints and connections, details of guides and fittings, rough opening dimensions, location and description of hardware, anchorage locations, and counterbalancing mechanism and door operator details. Show locations of replaceable fusible links on wiring diagrams for power, signal and controls. For motor-operated doors include supporting brackets for motors, location, type, and ratings of motors, and safety devices.
Include a schedule showing the location of each door with the drawings.
SECTION 08 33 23 Page 4 02/27/2026
2.1.2 Performance Requirements
2.1.2.1 Wind Loading
Design and fabricate door assembly to withstand the wind loading pressure of at least per lmits noted in the Structural drawings and in accordace with ANSI/DASMA 108 . Provide test data showing compliance with ASTM E330/E330M . Sound engineering principles may be used to interpolate or extrapolate test results to door sizes not specifically tested. Ensure that the complete assembly meets or exceeds the requirements of ASCE 7-16 .
2.1.2.2 Operational Cycle Life
Design all portions of the door, hardware and operating mechanism that are subject to movement, wear, or stress fatigue to operate through a minimum number of 12 to 20 cycles per day. One complete cycle of door operation is defined as when the door is in the closed position, moves to the fully open position, and returns to the closed position.
2.2 COMPONENTS
2.2.1 Overhead Coiling Doors
2.2.1.1 Curtain Materials and Construction
Provide curtain slats fabricated from Type 304 stainless steel sheets conforming to ASTM A666; sheet thickness as required by the size of the door to meet the required windload. Provide stainless steel curtain slats containing a minimum of 20 percent recycled content. Submit data identifying percentage of recycled content for stainless steel curtain slats.
Provide slats filled with manufacturer's standard thermal insulation, complying with the maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E84. Enclose the insulation completely within the slat faces on the interior surface of the slats.
2.2.1.2 Insulated Curtains
Form curtains from manufacturer's standard shapes of interlocking slats.
Supply a slat system with a minimum R-value of 4 when calculated in accordance with ASHRAE FUN IP . Slats to consist of a urethane core not less than 11/16 inch thick, completely enclosed within metal facings.
Slat steel thickness as required by the size of the door to meet specified performance requirements. The insulated slat assembly requires a flame spread rating of not more than 25 and a smoke development factor of not more than 50 when tested in accordance with ASTM E84.
2.2.1.3 Curtain Bottom Bar
Install curtain bottom bars as pairs of angles or using extrusions from the manufacturer's standard steel, stainless and aluminum extrusions not less than 2.0 by 2.0 inches by 0.188 inch. Do not use aluminum on doors more than 16 feet wide. Ensure steel extrusions conform to ASTM A36/A36M.
Stainless steel extrusions conforming to ASTM A666, Type 304. Aluminum extrusions conforming to ASTM B221. Galvanize angles and fasteners in accordance with ASTM A653/A653M and ASTM A924/A924M . Coat welds and abrasions with paint conforming to ASTM A780/A780M . Comply with section
SECTION 08 33 23 Page 5 02/27/2026
09 96 00 HIGH PERFORMANCE COATINGS for steel angle finish.
Provide two minimum 2 inch by 2 inch by 1/8 inch structural steel angles.
2.2.1.4 Endlocks (and Windlocks)
Provide endlocks of Grade B cast steel conforming to ASTM A47/A47M, galvanized in accordance with ASTM A153/A153M . Secure locks at every other curtain slat. In addition to endlocks, exterior doors which are more than 16 feet wide or which have a design wind load of more than 20 pounds per square foot , must have windlocks of manufacturer's standard design. Windlocks must prevent curtain from leaving guide because of deflection from wind pressure or other forces.
2.2.1.5 Weather Stripping
Provide a hood baffle inside the hood that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber or equivalent. Provide guide weather stripping that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber, or equivalent.
Provide bottom bar weather-stripping that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber, or equivalent.
2.2.1.6 Locking Devices
Ensure that the slide bolt engages through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
2.2.1.7 Safety Interlock
Equip power-operated doors with a safety interlock switch to disengage power supply when the door is locked, or provide an operator with an internal lock sensing device to prevent the door opening when the door is locked.
2.2.2 Hardware
Ensure that all hardware conforms to ASTM A153/A153M , ASTM A307, and
ASTM F568M.
2.2.2.1 Guides
Fabricate curtain jamb guides from the manufacturer's standard angles or channels of same material and finish as curtain slats unless otherwise indicated. Provide guides with sufficient depth or incorporate a steel locking bar to retain the curtain in place under the wind pressure specified. Ensure curtain operates smoothly. Slot bolt holes for track adjustment. Securely attach guides to adjoining construction with not less than 3/8 inch diameter bolts, spaced near each end and not over 30 inches apart.
2.2.2.2 Hood
Provide a hood with a minimum stainless steel sheet metal, flanged at top for attachment to header and flanged at bottom to provide longitudinal stiffness. The hood encloses the curtain coil and counterbalance mechanism.
SECTION 08 33 23 Page 6 02/27/2026
Hoods for openings more than 12 feet in width must have intermediate support brackets to prevent excessive sag. Provide a weather baffle at the lintel or inside the hood of each exterior door.
2.2.3 Counterbalancing Mechanism
Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted, around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed or self-lubricating bearings for rotating members.
2.2.3.1 Brackets
Provide the manufacturer's standard mounting brackets with one located at each end of the counterbalance barrel conforming to ASTM A36/A36M.
Provide brackets of hot-rolled steel.
2.2.3.2 Counterbalance Barrels
Curtain must roll up on a barrel supported at head of opening on brackets and be balanced by a torsion spring system in the barrel. Fabricate spring barrel of manufacturer's standard hot-formed, structural-quality, welded or seamless carbon-steel pipe, conforming to ASTM A53/A53M or equivalent. Ensure the barrel is of sufficient diameter and wall thickness to support rolled-up curtain without distortion of slats. Limit barrel deflection to not more than 0.03 inch per foot of span under full load.
a. Barrel
Provide steel pipe capable of supporting curtain load with maximum deflection of 0.03 inches per foot of width.
b. Spring Balance
Provide an oil-tempered, heat-treated steel helical torsion spring assembly designed for proper balance of door. Ensure that effort to operate manually operated units does not exceed 25 lbs . At least 80 percent of the door weight must be counterbalanced at any position.
Provide wheel for applying and adjusting spring torque.
2.2.4 Electric Door Operators
Provide electrical wiring and door operating controls conforming to the applicable requirements of NFPA 70 and UL 325 . The door manufacturer must furnish automatic control and safety devices, including extra flexible type SO cable and spring-loaded automatic takeup reel or equivalent device, as required for proper operation of the doors. Conduit, wiring, and mounting of controls are specified in Section 26 20 00 INTERIOR
DISTRIBUTION SYSTEM.
Electrical materials, equipment, and devices for installation in hazardous locations, as defined by NFPA 70 , must be specifically approved by Underwriters Laboratories or an independent testing agency using equivalent standards, for the particular chemical group and the class and division of hazardous location involved.
SECTION 08 33 23 Page 7 02/27/2026
Electric door-operator assemblies need to be the sizes and capacities recommended and provided by the door manufacturer for specified doors.
Furnish complete assemblies with electric motors and factory-prewired motor controls, starter, gear reduction units, solenoid-operated brakes, clutch, remote-control stations, manual or automatic control devices, and accessories as required for proper operation of the doors.
Design the operators so that motors may be removed without disturbing the limit-switch adjustment and affecting the emergency auxiliary operators.
Provide a manual operator of crank-gear or chain-gear mechanisms with a release clutch to permit manual operation of doors in case of power failure. Arrange the emergency manual operator so that it may be put into and out of operation from floor level, and its use does not affect the adjustment of the limit switches. Provide an electrical or mechanical device that automatically disconnects the motor from the operating mechanism when the emergency manual operating mechanism is engaged.
2.2.4.1 Door-Operator Types
Provide an operator mounted to the right or left door head plate with the operator on coil side of the door-hood assembly and connected to the door drive shaft with drive chain and sprockets. Front clearance is required for this type of mounting.
2.2.4.2 Electric Motors
Provide motors which are the high-starting-torque, reversible, constant-duty electrical type with overload protection of sufficient torque and horsepower to move the door in either direction from any position. Ensure they produce a door-travel speed of not less than 8 nor more than 12 inches per second without exceeding the horsepower rating.
Provide motors which conform to NEMA MG 1 designation, temperature rating, service factor, enclosure type, and efficiency to the requirements specified.
2.2.4.3 Electrical Characteristics
208 volt, 3 phase connection, as indicated on Electrical drawings.
2.2.4.4 Motor Bearings
Select bearings with bronze-sleeve or heavy-duty ball or roller antifriction type with full provisions for the type of thrust imposed by the specific duty load.
Pre-lubricate and factory seal bearings in motors less than 1/2 horsepower .
Equip motors coupled to worm-gear reduction units with either ball or roller bearings.
Equip bearings in motors 1/2 horsepower or larger with lubrication service fittings. Fit lubrication fittings with color-coded plastic or metal dust caps.
In any motor, bearings that are lubricated at the factory for extended
SECTION 08 33 23 Page 8 02/27/2026 duty periods do not need to be lubricated for a given number of operating hours. Display this information on an appropriate tag or label on the motor with instructions for lubrication cycle maintenance.
2.2.4.5 Motor Starters, Controls, and Enclosures
Provide each door motor with: a factory-wired, unfused, disconnect switch;
a reversing, across-the-line magnetic starter with thermal overload protection; 24-volt operating coils with a control transformer limit switch; and a safety interlock assembled in a NEMA ICS 6 type enclosure as specified herein. Ensure control equipment conforms to NEMA ICS 1 and
NEMA ICS 2 .
Provide adjustable switches, electrically interlocked with the motor controls and set to stop the door automatically at the fully open and fully closed position.
2.2.4.6 Control Enclosures
Provide control enclosures that conform to NEMA ICS 6 for general purpose NEMA Type 1.
2.2.4.7 Transformer
Provide starters with 230/460 to 115 volt control transformers with one secondary fuse when required to reduce the voltage on control circuits to 24volts or less. Provide a transformer conforming to NEMA ST 1 .
2.2.4.8 Sensing-Edge Device
Provide each door with a pneumatic or electric sensing device that meets UL 325 , extends the full width of the door, and is located within a U-section neoprene or rubber astragal, mounted on the bottom rail of the bottom door section. Device needs to immediately stop and reverse the door upon contact with an obstruction in the door opening or upon failure of the device or any component of the control system and cause the door to return to its user-defined open position. Any momentary door-closing circuit must be automatically locked out and the door must be operable manually or with constant pressure controls until the failure or damage has been corrected. A sensing device is not a substitute for a limit switch.
Connect sensing device to the control circuit through a retracting cord and reel.
2.2.4.9 Speed-Reduction Units
Provide speed-reduction units consisting of hardened-steel worm and bronze worm gear assemblies or planetary gear reducers running in oil or grease and inside a sealed casing, coupled to the motor through a flexible coupling. Drive shafts need to rotate on ball- or roller-bearing assemblies that are integral with the unit.
Provide minimum ratings of speed reduction units in accordance with AGMA provisions for class of service.
Ground worm gears to provide accurate thread form; machine teeth for all other types of gearing. Surface harden all gears.
SECTION 08 33 23 Page 9 02/27/2026
Provide antifriction type bearings equipped with oil seals.
2.2.4.10 Chain Drives
Provide roller chains that are a power-transmission series steel roller type conforming to ASME B29.400 , with a minimum safety factor of 10 times the design load.
Heat-treat or otherwise harden roller-chain side bars, rollers, pins, and bushings.
Provide high-carbon steel chain sprockets with machine-cut hardened teeth, finished bore and keyseat, and hollow-head setscrews.
2.2.4.11 Brakes
Provide 360-degree shoe brakes or shoe and drum brakes. Ensure the brakes are solenoid-operated and electrically interlocked to the control circuit to set automatically when power is interrupted.
2.2.4.12 Clutches
Ensure clutches are friction type or adjustable centrifugal type.
2.2.4.13 Weather/Smoke Seal Sensing Edge
Provide automatic stop control by an automatic sensing switch within neoprene astragal extending the full width of door bottom bar.
Provide an electric sensing edge device. Ensure the door immediately stops downward travel when contact occurs before door fully closes.
Provide a self-monitoring sensing edge connection to the motor operator.
2.2.5 Surface Finishing
Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
Noticeable variations in the same metal component are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of approved samples and are assembled or installed to minimize contrast. Comply with section 09 96 00 HIGH PERFORMANCE COATINGS.
PART 3 EXECUTION
3.1 INSTALLATION
Install overhead coiling door assembly, anchors and inserts for guides, brackets, motors, switches, hardware, and other accessories in accordance with approved detail drawings and manufacturer's written instructions.
Upon completion of installation, ensure doors are free from all distortion.
Install overhead coiling doors, motors, hoods, and operators at the mounting locations as indicated for each door in the Contract Documents and as required by the manufacturer.
Install overhead coiling doors, switches, and controls along accessible routes in compliance with regulatory requirements for accessibility and as required by the manufacturer.
SECTION 08 33 23 Page 10 02/27/2026
3.1.1 Field Painted Finish
Comply with section 09 96 00 HIGH PERFORMANCE COATINGS. Protect the weather stripping from paint. Ensure that the finishes are free of scratches or other blemishes.
3.2 ADJUSTING AND CLEANING
3.2.1 Acceptance Provisions
After installation, adjust the hardware and moving parts. Lubricate bearings and sliding parts as recommended by manufacturer to provide smooth operating functions for ease movement, free of warping, twisting, or distortion of the door assembly.
Adjust seals to provide a weather-tight fit around entire perimeter.
Engage a factory-authorized service representative to perform startup service and checks according to the manufacturer's written instructions.
Test the door opening and closing operation when activated by controls or alarm-connected fire-release system. Adjust controls and safeties.
Replace damaged and malfunctioning controls and equipment. Reset the door-closing mechanism after a successful test.
Test and make final adjustment of new doors at no additional cost to the Government.
3.2.1.1 Maintenance and Adjustment
Not more than 90 calendar days after completion and acceptance of the project, examine, lubricate, test, and re-adjust doors as required for proper operation.
3.2.1.2 Cleaning
Clean doors in accordance with manufacturer's approved instructions.
SECTION 08 33 23 Page 11 02/27/2026
SECTION 08 33 23 Page 12 02/27/2026
SECTION 09 90 00
PAINTS AND COATINGS
02/21
AMENDMENT 0006
PART 1 GENERAL
1.1 RELATED REQUIREMENTS
1.1.1 Painting Included
Where a space or surface is indicated to be painted, include the following unless indicated otherwise.
a. Surfaces behind portable objects and surface mounted articles readily detachable by removal of fasteners, such as screws and bolts.
b. New factory finished surfaces that require identification or color coding and factory finished surfaces that are damaged during performance of the work.
c. Existing coated surfaces that are damaged during performance of the work.
1.1.1.1 Exterior Painting
Includes new surfaces of the building and appurtenances. Comply with section 09 96 00 HIGH PERFORMANCE COATINGS for surfaces indicated.
1.1.1.2 Interior Painting
Includes new surfaces of the building and appurtenances as indicated and existing coated surfaces made bare by cleaning operations. Where a space or surface is indicated to be painted, include the following items, unless indicated otherwise.
a. Exposed columns, girders, beams, joists, and metal deck; and
b. Other contiguous surfaces.
1.1.2 Painting Excluded
Do not paint the following unless indicated otherwise.
a. Surfaces concealed and made inaccessible by panelboards, fixed ductwork, machinery, and equipment fixed in place.
b. Surfaces in concealed spaces. Concealed spaces are defined as enclosed spaces above suspended ceilings, furred spaces, attic spaces, crawl spaces, elevator shafts and chases.
c. Steel to be embedded in concrete.
d. Copper, stainless steel, aluminum, anodized aluminum, brass, and lead except existing coated surfaces.
e. Hardware, fittings, and other factory finished items.
SECTION 09 90 00 Page 1 02/27/2026
1.1.3 Mechanical and Electrical Painting
Includes field coating of interior and exterior new surfaces.
a. Where a space or surface is indicated to be painted, include the following items unless indicated otherwise.
(1) Exposed piping, conduit, and ductwork;
(2) Supports, hangers, air grilles, and registers;
(3) Miscellaneous metalwork and insulation coverings.
b. Do not paint the following, unless indicated otherwise:
(1) New zinc-coated, aluminum, and copper surfaces under insulation
(2) New aluminum jacket on piping
(3) New interior ferrous piping under insulation.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
ACGIH 0100 (2017; Suppl 2020) Documentation of the Threshold Limit Values and Biological Exposure Indices
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME A13.1 (2020) Scheme for the Identification of Piping Systems
ASTM INTERNATIONAL (ASTM)
ASTM D235 (2002; R 2012) Mineral Spirits (Petroleum Spirits) (Hydrocarbon Dry Cleaning Solvent)
ASTM D523 (2014; R 2018) Standard Test Method for Specular Gloss
ASTM D2240 (2015; E 2017) Standard Test Method for Rubber Property - Durometer Hardness
ASTM D2794 (1993; R 2019) Standard Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact)
ASTM D4214 (2007; R 2015) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films
ASTM D4263 (1983; R 2018) Standard Test Method for
SECTION 09 90 00 Page 2 02/27/2026
Indicating Moisture in Concrete by the Plastic Sheet Method
ASTM D4444 (2013; R 2018) Standard Test Method for Laboratory Standardization and Calibration of Hand-Held Moisture Meters
ASTM D6386 (2016a) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting
ASTM F1869 (2022) Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
CENTERS FOR DISEASE CONTROL AND PREVENTION (CDC)
Intelligence Bulletin 65 (2013) Occupational Exposure to Carbon Nanotubes and Nanofibers
MASTER PAINTERS INSTITUTE (MPI)
MPI 4 (2016) Interior/Exterior Latex Block Filler
MPI 47 (2016) Alkyd, Interior, Semi-Gloss (MPI Gloss Level 5)
MPI 48 (2016) Alkyd, Interior, Gloss (MPI Gloss Level 6-7)
MPI 49 (2015) Alkyd, Interior, Flat (MPI Gloss Level 1)
MPI 50 (2015) Primer Sealer, Latex, Interior
MPI 51 (2016) Alkyd, Interior, (MPI Gloss Level 3)2
MPI 56 (2012) Varnish, Interior, Polyurethane, Oil Modified, Gloss
MPI 57 (2012) Varnish, Interior, Polyurethane, Oil Modified, Satin
MPI 76 (2016) Primer, Alkyd, Quick Dry, for Metal
MPI 77 (2015) Epoxy, Gloss
MPI 90 (2012) Stain, Semi-Transparent, for Interior Wood
MPI 101 (2016) Primer, Epoxy, Anti-Corrosive, for Metal
MPI 107 (2016) Primer, Rust-Inhibitive, Water Based
MPI 116 (2012) Block Filler, Epoxy
SECTION 09 90 00 Page 3 02/27/2026
MPI 144 (2016) Latex, Interior, Institutional Low Odor/VOC, (MPI Gloss Level 2)
MPI 145 (2016) Latex, Interior, Institutional Low Odor/VOC, ( MPI Gloss Level 3)
MPI 146 (2016) Latex, Interior, Institutional Low Odor/VOC, (MPI Gloss Level 4)
MPI 147 (May 2016) Latex, Interior, Institutional Low Odor/VOC, Semi-Gloss (MPI Gloss Level 5)
MPI 149 (2016) Primer Sealer, Interior, Institutional Low Odor/VOC
MPI ASM (2019) Architectural Painting Specification Manual
MPI GPS-1-14 (2014) Green Performance Standard GPS-1-14
MPI MRM (2015) Maintenance Repainting Manual
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC 7/NACE No.4 (2007) Brush-Off Blast Cleaning
SSPC Glossary (2011) SSPC Protective Coatings Glossary
SSPC Guide 6 (2015) Guide for Containing Surface Preparation Debris Generated During Paint Removal Operations
SSPC Guide 7 (2015) Guide to the Disposal of Lead-Contaminated Surface Preparation Debris
SSPC PA 1 (2016) Shop, Field, and Maintenance Coating of Metals
SSPC SP 1 (2015) Solvent Cleaning
SSPC SP 2 (2018) Hand Tool Cleaning
SSPC SP 3 (2018) Power Tool Cleaning
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
SSPC SP 10/NACE No. 2 (2015) Near-White Blast Cleaning
SSPC VIS 1 (2002; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Dry Abrasive Blast Cleaning
SSPC VIS 3 (2004) Guide and Reference Photographs for Steel Surfaces Prepared by Hand and Power Tool Cleaning
SSPC-SP WJ-3/NACE WJ-3 (2012) Thorough Cleaning, Waterjet
SECTION 09 90 00 Page 4 02/27/2026
Cleaning of Metals
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2024) Safety -- Safety and Occupational Health (SOH) Requirements
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
EPA Method 24 (2000) Determination of Volatile Matter Content, Water Content, Density, Volume Solids, and Weight Solids of Surface Coatings
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-313 (2018) Material Safety Data, Transportation Data and Disposal Data for Hazardous Materials Furnished to Government Activities
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
29 CFR 1910.1001 Asbestos
29 CFR 1910.1025 Lead
29 CFR 1926.62 Lead
1.3 DEFINITIONS
1.3.1 Qualification Testing
Qualification testing is the performance of all test requirements listed in the product specification. This testing is accomplished by MPI to qualify each product for the MPI Approved Product List, and may also be accomplished by Contractor's third-party testing lab if an alternative to Batch Quality Conformance Testing by MPI is desired.
1.3.2 Batch Quality Conformance Testing
Batch quality conformance testing determines that the product provided is the same as the product qualified to the appropriate product specification. This testing must be accomplished by an MPI testing lab.
1.3.3 Coating
SSPC Glossary ; (1) A liquid, liquefiable, or mastic composition that is converted to a solid protective, decorative, or functional adherent film after application as a thin layer; (2) Generic term for paint, lacquer, enamel.
1.3.4 DFT or dft
Dry film thickness, the film thickness of the fully cured, dry paint or coating.
SECTION 09 90 00 Page 5 02/27/2026
1.3.5 DSD
Degree of Surface Degradation, the MPI system of defining degree of surface degradation. Five levels are generically defined under the Assessment sections in the MPI MRM, MPI Maintenance Repainting Manual.
1.3.6 EXT
MPI short term designation for an exterior coating system.
1.3.7 INT
MPI short term designation for an interior coating system.
1.3.8 Loose Paint
Paint or coating that can be removed with a dull putty knife.
1.3.9 mil / mils
The English measurement for 0.001 in or one one-thousandth of an inch .
1.3.10 MPI Gloss Levels
MPI system of defining gloss. Seven gloss levels (G1 to G7) are generically defined under the Evaluation sections of the MPI Manuals.
Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss refers to G5, and Gloss refers to G6.
Gloss levels are defined by MPI as follows:
Gloss Level Description Units at 60 degree angle
Units at 80 degree angle
G1 Matte or Flat 0 to 5 10 max
G2 Velvet 0 to 10 10 to 35
G3 Eggshell 10 to 25 10 to 35
G4 Satin 20 to 35 35 min
G5 Semi-Gloss 35 to 70
G6 Gloss 70 to 85
G7 High Gloss
Gloss is tested in accordance with ASTM D523. Historically, the Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and Gloss (G6).
1.3.11 MPI System Number
The MPI coating system number in each MPI Division found in either the MPI Architectural Painting Specification Manual or the Maintenance Repainting Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN).
SECTION 09 90 00 Page 6 02/27/2026
1.3.12 Paint
SSPC Glossary ; (1) Any pigmented liquid, liquefiable, or mastic composition designed for application to a substrate in a thin layer that is converted to an opaque solid film after application. Used for protection, decoration, identification, or to serve some other functional purposes; (2) Application of a coating material.
1.3.13 REX
MPI short term designation for an exterior coating system used in repainting projects or over existing coating systems.
1.3.14 RIN
MPI short term designation for an interior coating system used in repainting projects or over existing coating systems.
1.4 SCHEDULING
Allow paint, polyurethane, varnish, and wood stain installations to cure prior to the installation of materials that adsorb VOCs, including carpets, textiles, unprimed gypsum wallboard, acoustical ceiling panels.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
Samples of specified materials may be taken and tested for compliance with specification requirements.
SD-02 Shop Drawings
Piping Identification
SD-03 Product Data
Coating ; G
Product Data Sheets
SD-04 Samples
Color ; G
SD-07 Certificates
Qualification Testing laboratory for coatings; G
SD-08 Manufacturer's Instructions
Application Instructions
Mixing
Manufacturer's Safety Data Sheets
SECTION 09 90 00 Page 7 02/27/2026
SD-10 Operation and Maintenance Data
Coatings , Data Package 1; G
1.6 QUALITY ASSURANCE
1.6.1 Regulatory Requirements
1.6.1.1 Environmental Protection
In addition to requirements specified elsewhere for environmental protection, provide coating materials that conform to the restrictions of the local Air Pollution Control District and regional jurisdiction.
Notify Contracting Officer of any paint specified herein which fails to conform.
1.6.1.2 Lead Content
Do not use coatings having a lead content over 0.06 percent by weight of nonvolatile content.
1.6.1.3 Chromate Content
Do not use coatings containing zinc-chromate or strontium-chromate.
1.6.1.4 Asbestos Content
Provide asbestos-free materials.
1.6.1.5 Mercury Content
Provide materials free of mercury or mercury compounds.
1.6.1.6 Silica
Provide abrasive blast media containing no free crystalline silica.
1.6.1.7 Human Carcinogens
Provide materials…