1717488Amendment0006_Specs.pdf
PDF 4 MB Posted
- Attached to
- N4008526R0037 P1574/P1591/P1592 MCB CAMP LEJEUNE
- Solicitation number
- N4008526R0037
About this file
Summary
This document package contains federal environmental permit approvals and technical specifications for the P1574, P-1591, and P-1592 MRSB Operational Support Facilities project at MCB Camp Lejeune, North Carolina. The package includes an Erosion and Sedimentation Control Plan Letter of Approval (dated 02/02/2026, Permit Number ONSLO-2026-0241) and a Post-Construction Stormwater Management Permit (Permit Number SW8 070847, effective through January 23, 2030). The project involves construction of built-upon areas with overall low-density development and areas of higher density, totaling 6.00 acres of land disturbance. MCB Camp Lejeune must obtain an NCG010000 Construction Stormwater General Permit with Certificate of Coverage prior to commencing any land-disturbing activity and must comply with all conditions and maintenance requirements throughout the permit term.
The Post-Construction Stormwater Management Permit details specific design standards for stormwater control measures (SCMs), including eighteen alternative design sand filters, fourteen standard sand filters, and five infiltration basins, along with vegetated conveyances and bioretention systems designed to manage runoff from the development. The permit establishes maximum built-upon area percentages (25 percent for the 613.37-acre tract and 12 percent for the 92.45-acre tract), requires vegetated buffers and setbacks, and specifies performance criteria for each stormwater management component. Upon project completion, MCB Camp Lejeune must submit a Designer's Certification noting any deviations from approved plans and specifications, recorded operation and maintenance agreements, and deed restrictions as applicable. The permittee is responsible for maintaining all stormwater systems according to a prescribed maintenance schedule, including semiannual inspections, sediment removal, and vegetation management, with records available for Division review upon request.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1574 1ST MRSB OPERATIONAL SUPPORT FACILITY (OSF) AMEND0006 1717488
MCB CAMP LEJEUNE, NC
PROJECT TABLE OF CONTENTS
DIVISION 05 - METALS
05 52 00 08/23 METAL RAILINGS
DIVISION 08 - OPENINGS
08 11 13 08/20 STEEL DOORS AND FRAMES
08 33 23 08/20, CHG 1: 02/22 OVERHEAD COILING DOORS
DIVISION 09 - FINISHES
09 90 00 02/21 PAINTS AND COATINGS
09 96 00 11/14 HIGH-PERFORMANCE COATINGS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 1
THIS PAGE INTENTIONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 2
SECTION 05 52 00
METAL RAILINGS
08/23
AMENDMENT 0006
ADDED SECTION
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2605 (2020) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO M 314 (1990; R 2013) Standard Specification for Steel Anchor Bolts
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A27/A27M (2020) Standard Specification for Steel Castings, Carbon, for General Application
ASTM A47/A47M (1999; R 2022; E 2022) Standard Specification for Ferritic Malleable Iron Castings
ASTM A53/A53M (2024) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2023) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A283/A283M (2013) Standard Specification for Low and Intermediate Tensile Strength Carbon Steel Plates
SECTION 05 52 00 Page 1 02/27/2026
ASTM A500/A500M (2023) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM C514 (2004; R 2020) Standard Specification for Nails for the Application of Gypsum Board
ASTM C1107/C1107M (2020) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM D1187/D1187M (1997; R 2018) Standard Specification for Asphalt-Base Emulsions for Use as Protective Coatings for Metal
ASTM E488/E488M (2022) Standard Test Methods for Strength of Anchors in Concrete Elements
ASTM F2329/F2329M (2015; R 2023) Standard Specification for Zinc Coating, Hot-Dip, Requirements for Application to Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 20 (2019) Zinc-Rich Primers (Type I, Inorganic, and Type II, Organic)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Steel Railings and Handrails ; G
SD-03 Product Data
Concrete Inserts ; G
Masonry Anchorage Devices ; G
Steel Railings and Handrails ; G
Fasteners ; G
Recycled Content ; S
Product data indicating percentage by weight of post-consumer and pre-consumer recycled content for products having recycled content specified in this Section. Submit per requirements in Section
01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING.
SD-05 Design Data
SECTION 05 52 00 Page 2 02/27/2026
Performance Requirements Verification; G
For products and systems indicated to validate compliance with specified railings performance requirements, provide calculations and design criteria, including engineering analysis data, signed and sealed by the qualified registered Professional Engineer responsible for their preparation.
SD-07 Certificates
Welder Qualification ; G
Welding Procedures ; G
SD-08 Manufacturer's Instructions
Installation Instructions
SD-11 Closeout Submittals
All sustainable design Submittlas for recycled content are included under SD-03 Product Data.
1.3 QUALITY CONTROL
1.3.1 Welding Procedures
Submit results of welding inspections testing in accordance with AWS D1.1/D1.1M by an approved testing laboratory at the Contractor's expense. Provide laboratory welding inspection results to Contracting Officer.
1.3.2 Welder Qualification
Submit certified welder qualification by tests in accordance with AWS D1.1/D1.1M In addition, perform tests on test pieces in positions and with clearances equivalent to those actually encountered. If a test weld fails to meet requirements, conduct an immediate retest of two test welds and ensure that each test weld passes. Failure in the immediate retest will require that the welder be retested after further practice or training and make a complete set of test welds.
PART 2 PRODUCTS
2.1 SUSTAINABLE DESIGN REQUIREMENTS
See Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REQPORTING for sustainable design requirements for the following, expcet as modified herein.
2.1.1 Recycled Content of Products
Provide products with post-consumer recycled content plus one-half of pre-consumer recycled content to the greatest extent possible, but not less than 10 percent.
2.2 FABRICATION
Provide complete and detailed fabrication drawings for railing systems, SECTION 05 52 00 Page 3 02/27/2026 either steel railing systems or aluminum railing systems, or both, as indicated. Include detailed setting drawings, diagrams, tempaltes for installation of anchorages, including concrete inserts, anchor bolts, and miscellaneous metal items having integral anchors.
Preassemble items in the shop to the greatest extent possible.
Disassemble units only to the extent necessary for shipping and handling.
Clearly mark units for reassembly and coordinated installation.
For the fabrication of work exposed to view, use only materials that are smooth and free of surface blemishes, including pitting, seam marks, roller marks, rolled trade names, and roughness. Remove blemishes by grinding, or by welding and grinding, before cleaning, treating, and applying surface finishes, including zinc coatings.
Use materials of size and thicknesses indicated or, if not indicated, of the size and thickness necessary to produce adequate strength and durability in the finished product for its intended use. Work the materials to the dimensions indicated on approved detail drawings, using proven details of fabrication and support. Use the type of materials indicated or specified for the various components of work.
Form exposed work true to line and level, with accurate angles and surfaces and straight sharp edges. Ensure that all exposed edges are eased to a radius of approximately 1/32 inch . Bend metal corners to the smallest radius possible without causing grain separation or otherwise impairing the work.
Weld corners and seams continuously and in accordance with the recommendations of AWS D1.1/D1.1M . Grind exposed welds smooth and flush to match and blend with adjoining surfaces.
Form the exposed connections with hairline joints that are flush and smooth, using concealed fasteners wherever possible. Use exposed fasteners of the type indicated or, if not indicated, use countersunk Phillips flathead screws or bolts.
Provide anchorage of the type indicated and coordinated with the supporting structure. Fabricate anchoring devices and space as indicated and as required to provide adequate support for the intended use of the work.
Railings shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated.
2.2.1 Steel Railings and Handrails
Fabricate railings to comply with requirements indicated for design, dimensions, details, finish, and member sizes, including wall thickness of tube, post spacings, and anchorage, but not less than that needed to withstand indicated loads. Provide steel pipe conforming to ASTM A53/A53M or structural tubing conforming to ASTM A500/A500M , Grade A or B of equivalent strength. Provide steel railings of 1-1/2 inch nominal size unless otherwise indicated.
a. Rails and Posts: Provide top and bottom rails and psots of sizes and configurations indicated.
b. Picket Infill: Where indicated, provide pickets of sizes, SECTION 05 52 00 Page 4 02/27/2026 configurations and spacing indicated.
c. Intermediate Rails Infill: Where indicated, provide intermediate rails of sizes and configurations indicated, and spaced as indicated, but not greater than 12 inches clear.
d. Gates: Where indicated, provide gates of same material as railings in configurations indicated. Provide standard gate latching system of corrosion-resistant materials.
e. Removable Railings: Provide removable railing sections matching fixed railings as indicated.
f. Kickplates: Provide kickplates between railing posts where indicated, and consisting of 1/8 inch steel flat bars not less than 6 inches high. Secure kickplates as indicated.
2.2.1.1 Jointing
Provide fabrication jointing by on of the following methods as required to suit project-specific conditions.
a. Flush-type rail fittings of commercial standard, welded and ground smooth, with railing splice locks secured with 3/8 inch hexagonal-recessed-head setscrews.
b. Mitered and welded joints made by fitting post to top rail and intermediate rail to post, mitering corners, groove-welding joints and grinding smooth. Butt railing splices and reinforce them by a tight-fitting interior sleeve not less than 6 inches long.
c. Railings may be bent at corners in lieu of jointing, provided that bends are made in suitable jigs and the pipe is not crushed.
2.3 STEEL FINISHES
2.3.1 Galvanized Railings
For galvanized railings, provide hot-dip galvanized fittings, brackets, fasteners, sleeves and other ferrous componenets. Galvanize exterior railings, including pipe, fittings, brackets, fasteners, and other ferrous metal components.
a. Hot-dip galvanize steel railings, including hardware, after fabrication.
b. Comply with ASTM A123/A123M for hot-dip glavanized railings.
c. Comply with ASTM A153/A153M for hot-dip glavanized hardware.
d. Do not quench or apply post galvanizing treatments that might interfere with paint adhesion.
e. Fill vent and drain holes that are exposed in the finished Work, unless indicated to remain as weep holes, by plugging with zinc solder and filling off smooth.
SECTION 05 52 00 Page 5 02/27/2026
2.3.2 Shop-Painted Finish
Comply with Section 09 96 00 HIGH-PERFORMANCE COATINGS.
2.3.3 Color
Provide colros as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
2.4 ALUMINUM FINISHES
2.4.1 High Performance Organic Finish
Two-coat fluoropolymer finish compling with AAMA 2605 and containing not less than 70 percent PVDF resin by weight in color coat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.
2.4.1.1 Color
Provide colors as indicated; colors listed are not intended to limit the selection of equal colors from other manufacturers.
2.5 COMPONENTS
2.5.1 Concrete Inserts
Provide threaded-type concrete inserts consisting of galvanized ferrous castings, internally threaded to receive 3/4 inch diameter machine bolts;
either malleable iron conforming to ASTM A47/A47M or cast steel conforming to ASTM A27/A27M, hot-dip galvanized in accordance with ASTM A153/A153M .
Provide wedge-type concrete inserts consisting of galvanized box-type ferrous castings designed to accept 3/4 inch diameter bolts having special wedge-shaped heads, made of either malleable iron conforming to ASTM A47/A47M or cast steel conforming to ASTM A27/A27M and hot-dip galvanized in accordance with ASTM A153/A153M .
Provide carbon steel bolts having special wedge-shaped heads, nuts, washers, and shims, galvanized in accordance with ASTM A153/A153M . Provide slotted-type concrete inserts consisting of a galvanized 1/8 inch thick pressed-steel plate conforming to ASTM A283/A283M , made of box-type welded construction with a slot designed to receive 3/4 inch diameter square-head bolt with knockout cover; and hot-dip galvanized in accordance with
ASTM A123/A123M .
2.5.2 Masonry Anchorage Devices
Provide masonry anchorage devices consisting of expansion shields complying with AASHTO M 314, ASTM E488/E488M and ASTM C514 as follows:
Provide lead expansion shields for machine screws and bolts 1/4 inch and smaller; head-out embedded nut type, single-unit class, Group I, Type 1, Class 1.
Provide lead expansion shields for machine screws and bolts larger than 1/4 inch in size; head-out embedded nut type, multiple-unit class, Group I, Type 1, Class 2.
SECTION 05 52 00 Page 6 02/27/2026
Provide bolt anchor expansion shields for lag bolts; zinc-alloy, long-shield anchor class, Group II, Type 1, Class 1.
Provide bolt anchor expansion shields for bolts; closed-end bottom-bearing class, Group II, Type 2, Class 1.
2.5.3 Fasteners
Select fasteners of type, grade, and class required to produce connections suitable for anchoring railings capable of meeting specified performance requirements .
2.5.3.1 Galvanized Railings
Type 304 stainless steel or hot-dip zinc-coated steel fasteners complying with ASTM A153/A153M or ASTM F2329/F2329M for zinc coating.
2.6 MISCELLANEOUS MATERIALS
2.6.1 Galvanizing Repair Paint
High-zinc-dust-content paint complying with SSPC Paint 20 and compatible with paints specified to be used over it.
2.6.2 Bituminous Paint
Cold-applied asphalt emulsion complying with ASTM D1187/D1187M .
2.6.3 Nonshrink, Nonmettallic Grout
Factory-packaged, nonstaining, noncorrosive, nongaseous grout complying with ASTM C1107/C1107M . Provide grout specifically recommended by manufacturer for interior and exterior applications.
2.6.4 Anchoring Cement
Factory-packaged, nonshrink, nonstaining, hydraulic-controlled expansion cement formulation for mixing with water at Project site to create pourable anchoring, patching, and grouting compound.
PART 3 EXECUTION
3.1 INSTALLATION
Submit manufacturer's installation instructions for the following railing systems, as applicable:
h. Steel railings and handrails
3.1.1 Steel Railings and Handrail
3.1.1.1 Adjustment
Adjust railing systems before anchoring to ensure matching alignment at abutting joints. Space posts at spacing as indicated and as required by design loads. Plumb posts in each direction. Secure posts and rail ends to building construction as follow:
SECTION 05 52 00 Page 7 02/27/2026
a. Anchor posts to steel by welding directly to steel supporting members.
b. Ancor handrail ends to concrete and masonry with steel round flanges welded to rail ends and anchored with postinstalled anchors and bolts.
3.1.1.2 Attachment
Attach handrails to wall with wall brackets. Use type of bracket with flange tapped for concealed anchorage to thereaded hanger bolt. Provide bracket with 1-1/2 inch clearance from inside face of handrail and finished wall surface. Locate brackets at spacing required to support structural loads. Secure wall brackets to building construction as required to comply with performance requirements.
3.2 FIELD QUALITY CONTROL
3.2.1 Field Welding
Ensure that procedures of manual shielded metal arc welding, appearance and quality of welds made, and methods used in correcting welding work comply with AWS D1.1/D1.1M .
-- End of Section --
SECTION 05 52 00 Page 8 02/27/2026
SECTION 08 11 13
STEEL DOORS AND FRAMES
08/20
AMENDMENT 0006
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A879/A879M (2012; R 2017) Standard Specification for Steel Sheet, zinc Coated by the Electrolytic Process for Applications Requiring Designation of the Coating Mass on Each Surface
ASTM C578 (2019) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C591 (2021) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C612 (2014; R 2019) Standard Specification for Mineral Fiber Block and Board Thermal Insulation
ASTM D2863 (2019) Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM E1300 (2016) Standard Practice for Determining Load Resistance of Glass in Buildings
ASTM F2247 (2018) Standard Test Method for Metal Doors Used in Blast Resistant Applications (Equivalent Static Load Method)
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
ASTM F2927 (2012) Standard Test Method for Door Systems Subject to Airblast Loadings
SECTION 08 11 13 Page 1 02/27/2026
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2016) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2022) Standard for Fire Doors and Other Opening Protectives
NFPA 105 (2022) Standard for Smoke Door Assemblies and Other Opening Protectives
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 111 (2009) Recommended Details for Standard Steel Doors, Frames, and Accessories and Related Components
SDI/DOOR 113 (2013; R2018) Standard Practice for Determining the Steady-State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.4 (2018) Test Procedure and Acceptance Criteria for Physical Endurance for Steel Doors, Frames and Frame Anchors
SDI/DOOR A250.6 (2015) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2017) Specifications for Standard Steel Doors and Frames
SDI/DOOR A250.11 (2012) Recommended Erection Instructions for Steel Frames
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 4-010-01 (2018; with Change 1, 2020; Change 2, 2022) DoD Minimum Antiterrorism Standards for Buildings
UNDERWRITERS LABORATORIES (UL)
UL 10C (2016; Reprint May 2021) UL Standard for Safety Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SECTION 08 11 13 Page 2 02/27/2026
SD-02 Shop Drawings
Doors ; G
Frames ; G
Accessories
Schedule of Doors ; G
Schedule of Frames ; G
SD-03 Product Data
Doors ; G
Recycled Content for Steel Door Product ; S
Frames ; G
Recycled Content for Steel Frame Product ; S
Accessories
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Strap knock-down frames in bundles. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8 , except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00 DOOR HARDWARE. Undercut where indicated. Provide exterior doors with top edge closed flush and sealed to prevent water intrusion. Provide doors at 1-3/4 inch thick, unless otherwise indicated. Provide door material that uses a minimum of 25 percent recycled content. Provide data indicating percentage of recycled content for steel door product . Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300. Exterior doors must be tested in accordance with ASTM F2247 or ASTM F2927 to meet requirements of
UFC 4-010-01 .
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Heavy Duty Doors
SDI/DOOR A250.8 , Level 2, physical performance Level B, Model 2, with core construction as required by the manufacturer for interior doors, of size(s) and design(s) indicated. Provide Level 2 typically at mechanical rooms, and other interior locations as indicated.
SECTION 08 11 13 Page 3 02/27/2026
2.1.1.2 Maximum Duty Doors
SDI/DOOR A250.8 , Level 4, physical performance Level A, Model 2 with core construction as required by the manufacturer for interior doors and for indicated exterior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners must be filled with board insulation. Provide Level 4 typically at all exterior doors. Fabricate from metallic-coated steel sheet for exterior doors.
2.2 INSULATED STEEL DOOR SYSTEMS
Provide insulated steel doors and frames in accordance with SDI/DOOR 113 where indicated. Meet energy requirements including Solar Heat Gain Coefficient (SHGC) and U-factor. Provide insulated steel doors with a core of polyurethane foam; face sheets, edges, and frames of galvanized steel not lighter than 23 gage , 16 gage , and 16 gage respectively;
magnetic weatherstripping; nonremovable-pin hinges; thermal-break aluminum threshold; and vinyl door bottom. Finish doors and associated frames and louvers in accordance with section 09 96 00 HIGH-PERFORMANCE COATINGS.
Test doors in accordance with SDI/DOOR A250.4 and meet the requirements for Level C. Prepare doors to receive specified hardware. Provide doors 1-3/4 inch thick.
2.3 ACCESSORIES
2.3.1 Louvers
2.3.1.1 Interior Louvers
SDI/DOOR 111 . Where indicated, provide louvers of stationary sightproof where scheduled. Detachable moldings on room or non security side of door;
on security side of door, moldings to be integral part of louver. Form louver frames of 20 gage steel and louver blades of a minimum 24 gage .
2.3.1.2 Exterior Louvers
Provide louvers of the inverted "Y" type with minimum of 55 percent net-free opening. Weld or tenon louver blades to continuous channel frame and weld assembly to door to form watertight assembly. Form louvers of hot-dip galvanized steel of same gage as door facings. At louvers provide steel-framed bird screens secured to room side and readily removable.
Provide galvanized steel, 1/2 by 1/2 inch mesh hardware cloth, for bird screens. Net-free louver area to be before screening.
2.3.2 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors.
2.3.3 Moldings
Provide moldings around glass of interior and exterior doors and louvers of interior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings.
SECTION 08 11 13 Page 4 02/27/2026
2.4 INSULATION CORES
Provide insulating cores at all exterior doors, and provide an apparent U-factor of .48 in accordance with SDI/DOOR 113 and conforming to:
a. Rigid Cellular Polyisocyanurate Foam: ASTM C591, Type I or II, foamed-in-place or in board form, with oxygen index of not less than 22 percent when tested in accordance with ASTM D2863; or
b. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
c. Mineral board: ASTM C612, Type I.
2.5 STANDARD STEEL FRAMES
SDI/DOOR A250.8 , Level 2, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners. Provide steel frames for doors, transoms, sidelights, mullions, cased openings, and interior glazed panels, unless otherwise indicated. Provide frame product that uses a minimum of 25 percent recycled content. Provide data indicating percentage of recycled content for steel frame product .
2.5.1 Welded Frames
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.5.2 Mullions and Transom Bars
Provide mullions and transom bars of closed or tubular construction with heads and jambs butt-welded together. Bottom of door mullions must have adjustable floor anchors and spreader connections.
2.5.3 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated not lighter than 18 gage .
2.5.3.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring or welding;
c. Completed openings: Secure frames to previously placed concrete or masonry with expansion bolts in accordance with SDI/DOOR 111 ;
and
SECTION 08 11 13 Page 5 02/27/2026
2.5.3.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member. Where floor fill occurs, terminate bottom of frames at the indicated finished floor levels and support by adjustable extension clips resting on and anchored to the structural slabs.
2.6 FIRE AND SMOKE DOORS AND FRAMES
Provide fire and smoke doors and frames in accordance with NFPA 80 and NFPA 105 and this specification.
2.6.1 Labels
Provide fire doors and frames bearing the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required.
Testing must be in accordance with NFPA 252 or UL 10C . Provide labels that are metal with raised letters, bearing the name or file number of the door and frame manufacturer. Labels must be permanently affixed at the factory to frames and to the hinge edge of the door. Do not paint door and labels.
2.6.2 Oversized Doors
For fire doors and frames which exceed the size for which testing and labeling are available, furnish certificates stating that the doors and frames are identical in design, materials, and construction to a door which has been tested and meets the requirements for the class indicated.
2.6.3 Astragal on Fire and Smoke Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements.
On smoke control doors, conform to NFPA 105 .
2.7 EXTERIOR FRAMES
Provide thermal insulation in all exterior frames. Provide frames of a minimum Level 4, with frames of a minimum thickness of 0.067 inch , 14 gage.
2.8 HARDWARE PREPARATION
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6 . For additional requirements refer to ANSI/BHMA A156.115 . Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Punch door frames, with the exception of frames that will have weatherstripping or soundproof gasketing, to receive a minimum of two rubber or vinyl door silencers on lock side of single doors and one silencer for each leaf at heads of double doors. Set lock strikes out to provide clearance for silencers.
2.9 FINISHES
2.9.1 Factory-Primed Finish
Thoroughly clean all surfaces of doors and frames then chemically treat
SECTION 08 11 13 Page 6 02/27/2026 and factory prime with a rust inhibiting coating as specified in
SDI/DOOR A250.8 .
2.9.2 Electrolytic Zinc-Coated Anchors and Accessories
Provide electrolytically deposited zinc-coated steel in accordance with ASTM A879/A879M , Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc-coated surfaces as specified in SDI/DOOR A250.8 .
2.10 FABRICATION AND WORKMANSHIP
Provide finished doors and frames that are strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Provide molded members that are clean cut, straight, and true, with joints coped or mitered, well formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints must be well formed and in true alignment. Conceal fastenings where practicable. On wraparound frames for masonry partitions, provide a throat opening 1/8 inch larger than the actual masonry thickness. Design frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
Set frames in accordance with SDI/DOOR A250.11 . Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction.
3.1.2 Doors
Hang doors in accordance with clearances specified in SDI/DOOR A250.8 .
After erection and glazing, clean and adjust hardware.
3.1.3 Fire and Smoke Doors and Frames
Install fire doors and frames, including hardware, in accordance with NFPA 80 . Install fire rated smoke doors and frames in accordance with NFPA 80 and NFPA 105 .
3.2 PROTECTION
Protect doors and frames from damage. Repair damaged doors and frames prior to completion and acceptance of the project or replace with new, as directed. Wire brush rusted frames until rust is removed. Clean thoroughly. Apply an all-over coat of rust-inhibitive paint of the same type used for shop coat.
3.3 CLEANING
Upon completion, clean exposed surfaces of doors and frames thoroughly.
Remove mastic smears and other unsightly marks.
SECTION 08 11 13 Page 7 02/27/2026
SECTION 08 11 13 Page 8 02/27/2026
SECTION 08 33 23
OVERHEAD COILING DOORS
08/20, CHG 1: 02/22
AMENDMENT 0006
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE FUN IP (2021) Fundamentals Handbook, I-P Edition
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B29.400 (2001; (R 2008) (R 2013) (R 2018))
Combination, "H" Type Mill Chains, and Sprockets
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A47/A47M (1999; R 2018; E 2018) Standard Specification for Ferritic Malleable Iron Castings
ASTM A53/A53M (2022) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A153/A153M (2016a) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2021) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A666 (2015) Standard Specification for Annealed
SECTION 08 33 23 Page 1 02/27/2026 or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM A780/A780M (2020) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A924/A924M (2022) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E330/E330M (2014; R 2021) Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference
ASTM F568M (2007) Standard Specification for Carbon and Alloy Steel Externally Threaded Metric Fasteners
DOOR AND ACCESS SYSTEM MANUFACTURERS ASSOCIATION (DASMA)
ANSI/DASMA 108 (2017) Standard Method for Testing Sectional Garage Doors, Rolling Doors and Flexible Doors: Determination of Structural Performance Under Uniform Static Air Pressure Difference
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA MG 1 (2021) Motors and Generators
NEMA ST 1 (1988; R 1994; R 1997) Specialty Transformers (Except General Purpose Type)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 1 2024; TIA 24-1; TIA 25-2)
National Electrical Code
SECTION 08 33 23 Page 2 02/27/2026
UNDERWRITERS LABORATORIES (UL)
UL 325 (2017; Reprint Feb 2020) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Overhead Coiling Doors ; G
Electric Door Operators ; G
Installation Drawings ; G
SD-03 Product Data
Overhead Coiling Doors ; G
Hardware ; G
Electric Door Operators ; G
SD-05 Design Data
Overhead Coiling Doors ; G
Hardware ; G
Electric Door Operators ; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Manuals , Data Package 2; G
SD-11 Closeout Submittals
Warranty ; G
1.3 QUALITY CONTROL
1.3.1 Warranty
Furnish a written guarantee that the helical spring and counterbalance mechanism are free from defects in material and workmanship for not less than two years after completion and acceptance of the project.
Warrant that upon notification by the Government, any defects in material, workmanship, and door operation are immediately correct within the same time period covered by the guarantee, at no cost to the Government.
SECTION 08 33 23 Page 3 02/27/2026
1.3.2 Operation And Maintenance Submittals
Submit 6 copies of the operation and maintenance manuals 30 calendar days prior to testing the Overhead Coiling Door Assemblies. Update and resubmit data for final approval no later than 30 calendar days prior to cContract completion.
Submit Operation and Maintenance Manuals for Overhead Coiling Door Assemblies, including the following items:
Electric Door Operators
Hood
Counterbalancing Mechanism
Painting
Provide operation and maintenance manuals which are consistent with manufacturer's standard brochures, schematics, printed instructions, operating procedures, and safety precautions.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the jobsite wrapped in a protective covering with the brands and names clearly marked thereon. Store doors in an adequately ventilated dry location that is free from dirt and dust, water, or other contaminants. Store in a manner that permits easy access for inspection and handling. Handle doors carefully to prevent damage. Remove damaged items that cannot be restored to like-new condition and provide new items.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide overhead coiling doors with interlocking slats, complete with anchoring and door hardware, guides, hood, and operating mechanisms, and designed for use on openings as indicated. Doors must be spring counterbalanced, rolling type, and designed for use on exterior openings, as indicated. Doors must be operated by electric-power with auxiliary hand chain operation. Doors to be surface-mounted type with guides at jambs set back a sufficient distance to provide a clear opening when door is in open position. Mount exterior doors as indicated.
2.1.1 Design Requirements
2.1.1.1 Door Detail Shop Drawings
Provide installation drawings for door assemblies which show: elevations of each door type, shape and thickness of materials, finishes, details of joints and connections, details of guides and fittings, rough opening dimensions, location and description of hardware, anchorage locations, and counterbalancing mechanism and door operator details. Show locations of replaceable fusible links on wiring diagrams for power, signal and controls. For motor-operated doors include supporting brackets for motors, location, type, and ratings of motors, and safety devices.
Include a schedule showing the location of each door with the drawings.
SECTION 08 33 23 Page 4 02/27/2026
2.1.2 Performance Requirements
2.1.2.1 Wind Loading
Design and fabricate door assembly to withstand the wind loading pressure of at least per lmits noted in the Structural drawings and in accordace with ANSI/DASMA 108 . Provide test data showing compliance with ASTM E330/E330M . Sound engineering principles may be used to interpolate or extrapolate test results to door sizes not specifically tested. Ensure that the complete assembly meets or exceeds the requirements of ASCE 7-16 .
2.1.2.2 Operational Cycle Life
Design all portions of the door, hardware and operating mechanism that are subject to movement, wear, or stress fatigue to operate through a minimum number of 12 to 20 cycles per day. One complete cycle of door operation is defined as when the door is in the closed position, moves to the fully open position, and returns to the closed position.
2.2 COMPONENTS
2.2.1 Overhead Coiling Doors
2.2.1.1 Curtain Materials and Construction
Provide curtain slats fabricated from Type 304 stainless steel sheets conforming to ASTM A666; sheet thickness as required by the size of the door to meet the required windload. Provide stainless steel curtain slats containing a minimum of 20 percent recycled content. Submit data identifying percentage of recycled content for stainless steel curtain slats.
Provide slats filled with manufacturer's standard thermal insulation, complying with the maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E84. Enclose the insulation completely within the slat faces on the interior surface of the slats.
2.2.1.2 Insulated Curtains
Form curtains from manufacturer's standard shapes of interlocking slats.
Supply a slat system with a minimum R-value of 4 when calculated in accordance with ASHRAE FUN IP . Slats to consist of a urethane core not less than 11/16 inch thick, completely enclosed within metal facings.
Slat steel thickness as required by the size of the door to meet specified performance requirements. The insulated slat assembly requires a flame spread rating of not more than 25 and a smoke development factor of not more than 50 when tested in accordance with ASTM E84.
2.2.1.3 Curtain Bottom Bar
Install curtain bottom bars as pairs of angles or using extrusions from the manufacturer's standard steel, stainless and aluminum extrusions not less than 2.0 by 2.0 inches by 0.188 inch. Do not use aluminum on doors more than 16 feet wide. Ensure steel extrusions conform to ASTM A36/A36M.
Stainless steel extrusions conforming to ASTM A666, Type 304. Aluminum extrusions conforming to ASTM B221. Galvanize angles and fasteners in accordance with ASTM A653/A653M and ASTM A924/A924M . Coat welds and abrasions with paint conforming to ASTM A780/A780M . Comply with section
SECTION 08 33 23 Page 5 02/27/2026
09 96 00 HIGH PERFORMANCE COATINGS for steel angle finish.
Provide two minimum 2 inch by 2 inch by 1/8 inch structural steel angles.
2.2.1.4 Endlocks (and Windlocks)
Provide endlocks of Grade B cast steel conforming to ASTM A47/A47M, galvanized in accordance with ASTM A153/A153M . Secure locks at every other curtain slat. In addition to endlocks, exterior doors which are more than 16 feet wide or which have a design wind load of more than 20 pounds per square foot , must have windlocks of manufacturer's standard design. Windlocks must prevent curtain from leaving guide because of deflection from wind pressure or other forces.
2.2.1.5 Weather Stripping
Provide a hood baffle inside the hood that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber or equivalent. Provide guide weather stripping that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber, or equivalent.
Provide bottom bar weather-stripping that is a minimum 1/16 inch thick sheet of vinyl, neoprene rubber, or equivalent.
2.2.1.6 Locking Devices
Ensure that the slide bolt engages through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
2.2.1.7 Safety Interlock
Equip power-operated doors with a safety interlock switch to disengage power supply when the door is locked, or provide an operator with an internal lock sensing device to prevent the door opening when the door is locked.
2.2.2 Hardware
Ensure that all hardware conforms to ASTM A153/A153M , ASTM A307, and
ASTM F568M.
2.2.2.1 Guides
Fabricate curtain jamb guides from the manufacturer's standard angles or channels of same material and finish as curtain slats unless otherwise indicated. Provide guides with sufficient depth or incorporate a steel locking bar to retain the curtain in place under the wind pressure specified. Ensure curtain operates smoothly. Slot bolt holes for track adjustment. Securely attach guides to adjoining construction with not less than 3/8 inch diameter bolts, spaced near each end and not over 30 inches apart.
2.2.2.2 Hood
Provide a hood with a minimum stainless steel sheet metal, flanged at top for attachment to header and flanged at bottom to provide longitudinal stiffness. The hood encloses the curtain coil and counterbalance mechanism.
SECTION 08 33 23 Page 6 02/27/2026
Hoods for openings more than 12 feet in width must have intermediate support brackets to prevent excessive sag. Provide a weather baffle at the lintel or inside the hood of each exterior door.
2.2.3 Counterbalancing Mechanism
Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted, around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed or self-lubricating bearings for rotating members.
2.2.3.1 Brackets
Provide the manufacturer's standard mounting brackets with one located at each end of the counterbalance barrel conforming to ASTM A36/A36M.
Provide brackets of hot-rolled steel.
2.2.3.2 Counterbalance Barrels
Curtain must roll up on a barrel supported at head of opening on brackets and be balanced by a torsion spring system in the barrel. Fabricate spring barrel of manufacturer's standard hot-formed, structural-quality, welded or seamless carbon-steel pipe, conforming to ASTM A53/A53M or equivalent. Ensure the barrel is of sufficient diameter and wall thickness to support rolled-up curtain without distortion of slats. Limit barrel deflection to not more than 0.03 inch per foot of span under full load.
a. Barrel
Provide steel pipe capable of supporting curtain load with maximum deflection of 0.03 inches per foot of width.
b. Spring Balance
Provide an oil-tempered, heat-treated steel helical torsion spring assembly designed for proper balance of door. Ensure that effort to operate manually operated units does not exceed 25 lbs . At least 80 percent of the door weight must be counterbalanced at any position.
Provide wheel for applying and adjusting spring torque.
2.2.4 Electric Door Operators
Provide electrical wiring and door operating controls conforming to the applicable requirements of NFPA 70 and UL 325 . The door manufacturer must furnish automatic control and safety devices, including extra flexible type SO cable and spring-loaded automatic takeup reel or equivalent device, as required for proper operation of the doors. Conduit, wiring, and mounting of controls are specified in Section 26 20 00 INTERIOR
DISTRIBUTION SYSTEM.
Electrical materials, equipment, and devices for installation in hazardous locations, as defined by NFPA 70 , must be specifically approved by Underwriters Laboratories or an independent testing agency using equivalent standards, for the particular chemical group and the class and division of hazardous location involved.
SECTION 08 33 23 Page 7 02/27/2026
Electric door-operator assemblies need to be the sizes and capacities recommended and provided by the door manufacturer for specified doors.
Furnish complete assemblies with electric motors and factory-prewired motor controls, starter, gear reduction units, solenoid-operated brakes, clutch, remote-control stations, manual or automatic control devices, and accessories as required for proper operation of the doors.
Design the operators so that motors may be removed without disturbing the limit-switch adjustment and affecting the emergency auxiliary operators.
Provide a manual operator of crank-gear or chain-gear mechanisms with a release clutch to permit manual operation of doors in case of power failure. Arrange the emergency manual operator so that it may be put into and out of operation from floor level, and its use does not affect the adjustment of the limit switches. Provide an electrical or mechanical device that automatically disconnects the motor from the operating mechanism when the emergency manual operating mechanism is engaged.
2.2.4.1 Door-Operator Types
Provide an operator mounted to the right or left door head plate with the operator on coil side of the door-hood assembly and connected to the door drive shaft with drive chain and sprockets. Front clearance is required for this type of mounting.
2.2.4.2 Electric Motors
Provide motors which are the high-starting-torque, reversible, constant-duty electrical type with overload protection of sufficient torque and horsepower to move the door in either direction from any position. Ensure they produce a door-travel speed of not less than 8 nor more than 12 inches per second without exceeding the horsepower rating.
Provide motors which conform to NEMA MG 1 designation, temperature rating, service factor, enclosure type, and efficiency to the requirements specified.
2.2.4.3 Electrical Characteristics
208 volt, 3 phase connection, as indicated on Electrical drawings.
2.2.4.4 Motor Bearings
Select bearings with bronze-sleeve or heavy-duty ball or roller antifriction type with full provisions for the type of thrust imposed by the specific duty load.
Pre-lubricate and factory seal bearings in motors less than 1/2 horsepower .
Equip motors coupled to worm-gear reduction units with either ball or roller bearings.
Equip bearings in motors 1/2 horsepower or larger with lubrication service fittings. Fit lubrication fittings with color-coded plastic or metal dust caps.
In any motor, bearings that are lubricated at the factory for extended
SECTION 08 33 23 Page 8 02/27/2026 duty periods do not need to be lubricated for a given number of operating hours. Display this information on an appropriate tag or label on the motor with instructions for lubrication cycle maintenance.
2.2.4.5 Motor Starters, Controls, and Enclosures
Provide each door motor with: a factory-wired, unfused, disconnect switch;
a reversing, across-the-line magnetic starter with thermal overload protection; 24-volt operating coils with a control transformer limit switch; and a safety interlock assembled in a NEMA ICS 6 type enclosure as specified herein. Ensure control equipment conforms to NEMA ICS 1 and
NEMA ICS 2 .
Provide adjustable switches, electrically interlocked with the motor controls and set to stop the door automatically at the fully open and fully closed position.
2.2.4.6 Control Enclosures
Provide control enclosures that conform to NEMA ICS 6 for general purpose NEMA Type 1.
2.2.4.7 Transformer
Provide starters with 230/460 to 115 volt control transformers with one secondary fuse when required to reduce the voltage on control circuits to 24volts or less. Provide a transformer conforming to NEMA ST 1 .
2.2.4.8 Sensing-Edge Device
Provide each door with a pneumatic or electric sensing device that meets UL 325 , extends the full width of the door, and is located within a U-section neoprene or rubber astragal, mounted on the bottom rail of the bottom door section. Device needs to immediately stop and reverse the door upon contact with an obstruction in the door opening or upon failure of the device or any component of the control system and cause the door to return to its user-defined open position. Any momentary door-closing circuit must be automatically locked out and the door must be operable manually or with constant pressure controls until the failure or damage has been corrected. A sensing device is not a substitute for a limit switch.
Connect sensing device to the control circuit through a retracting cord and reel.
2.2.4.9 Speed-Reduction Units
Provide speed-reduction units consisting of hardened-steel worm and bronze worm gear assemblies or planetary gear reducers running in oil or grease and inside a sealed casing, coupled to the motor through a flexible coupling. Drive shafts need to rotate on ball- or roller-bearing assemblies that are integral with the unit.
Provide minimum ratings of speed reduction units in accordance with AGMA provisions for class of service.
Ground worm gears to provide accurate thread form; machine teeth for all other types of gearing. Surface harden all gears.
SECTION 08 33 23 Page 9 02/27/2026
Provide antifriction type bearings equipped with oil seals.
2.2.4.10 Chain Drives
Provide roller chains that are a power-transmission series steel roller type conforming to ASME B29.400 , with a minimum safety factor of 10 times the design load.
Heat-treat or otherwise harden roller-chain side bars, rollers, pins, and bushings.
Provide high-carbon steel chain sprockets with machine-cut hardened teeth, finished bore and keyseat, and hollow-head setscrews.
2.2.4.11 Brakes
Provide 360-degree shoe brakes or shoe and…