The document is an Air Handler Schedule detailing technical specifications for multiple HVAC units at a military facility. The schedule includes three Trane M-17 air handling units located on the second and third floors of a mechanical room, each with specific performance characteristics such as air flow rates (6,650-8,170 CFM), chilled water coil specifications, and electrical requirements (208V, 10 HP). Each unit is specified to include UV light and variable frequency drive (VFD), with MERV 13 filters and designed for 100% outside air operation upon energy recovery ventilation (ERV) failure.
The related federal contract opportunity is a solicitation (N4008525R9023) by the Department of the Navy Naval Facilities Engineering Command for BEQ Chiller Repairs at MCAS New River, Camp Johnson, and Rifle Range. The solicitation is restricted to Mechanical MACC Contractors listed on the General Requirements cover page, indicating a targeted procurement process for specialized mechanical repair and maintenance services. The document suggests a focus on HVAC system repairs and upgrades, with detailed technical specifications provided to guide potential contractors in their proposal preparation.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 j 4 '.)
DAIR HANDLER SCHEDULE
SYM.
LOCATION FLOOR BLDG.
MFGR
MODEL
AIR FLOW
CHILLED WATER
COIL
ELECTRICAL SUPPLY FAN
OPER. WT.
(LBS)
FILTERS MERV 13
REMARKS
SUPPLY FAN
OSA
CFM
MBH
ENT AIR
LVG AIR
WATER
ROWS
FPI
CFM
ESP
DB
WB
DB
WB
FLOW
6P
ENT
LVG
VOLTAGE
HP
MECH RM. SECOND FLOOR
TRANE M-17
3"
256.1
81.l"F
69.2"F
55.0"F
53.2"F 51.3
GPM
3.13'
45°F
55°F
208-3
YES
PROVIDE WITH UV LIGHT AND VFD
MECH RM. SECOND FLOOR
TRANE M-17
3"
244.6
81.l"F
69.2"F
55.0"F
53.3"F 48.9
GPM
2.92'
45°F
55°F
208-3
MECH RM. THIRD FLOOR
TRANE M-17
3"
287.7
81.1"F
69.2"F
55.0"F
53.1"F 57.6
GPM
3.81' 45°F 55"F
208-3
* COIL SIZE & GPM BASED ON 100% OSA UPON ERV FAILURE. (OSA ENTERING 91'F db - 81°F wb)
ENERGY RECOVERY UNIT-DEDICATED OSA AHU
| LOCATION FLOOR BLDG. |
| MFGR |
MODEL
| AIR FLOW |
| SUMMER |
| WINTER |
| PREHEAT COIL |
| ELECTRICAL |
| OPER. WT. |
(LBS)
FILTERS MERV 13
| SUPPLY FAN |
| EXH FAN |
| OSA IN |
| RA |
| OSA OUT |
| MBH |
| ENT AIR |
| LVG AIR |
| WATER |
| ROWS |
| FPI |
| VOLTAGE |
| FLA |
| MCA |
| MOCP |
| SUP FAN |
| EXH FAN |
| CFM |
| ESP |
| CFM |
| ESP |
| DB |
| WB |
| DB |
| WB |
| DB |
| WB |
| ENT |
| LVG |
| DB |
| WB |
| DB |
| WB |
| FLOW |
| 6P |
| ENT |
| LVG |
| HP |
| HP |
<E�V)
| MECH RM. ATTIC |
| COOK |
OR EQUAL
3/4"
2.0"
91.0
81.0 76.0
50%
76.0
69.2
| 26'F |
| 53.9'F |
| 71.200 |
| 53.9° |
| 39.2' |
| 68.0° |
40% 7.1
GPM
2.13'
TBD
| 208-3 |
| 30.18 |
| 37.73 |
| 60 |
| 3 |
| 5 |
YES
CCHILLER SCHEDULE
MFGR. &
MODEL No.
SERVICE
LOCATION
TYPE
EVAPORATOR
CONDENSER
POWER
EEFICIENCIES
OPER. WT.
(LBS)
WATER
PD
CAPACITY
WATER
PD (FT)
FOULING FACTOR
AMBIENT DESIGN
V-PH
MCA
MOCP
KW/TON
EER
FLOW
IN
OUT
GPM
IN
OUT
CH
TRANE CGAM 70
FIRST FLOOR MECH RM
EXTERIOR
AIR COOLED
GPM
54 "F 44 "F
6.3
FT
65.4 TONS
91"F
208-3
354.5
0.98
11.9
SUPPLY DIFFUSER SCHEDULE
UNIT NO.
MANUFACTURER
MODEL
NECK SIZE
FRAME TYPE
RANGE C.F.M.
REMARKS
E9H
KRUEGER (OR EQUAL)
51240 6x6 0-120
PROVIDE AS 4-WAY
DISCHARGE PATTERN UNLESS SHOWN OTHERWISE ON PlANS
E9H
8x8
121-210
10x10
211-330
12x12
331-470
14x14
471-640
16x16
641-1000
E9
30x16 600-1300
DOUBLE DEFLECTION ADJUSTABLE GRILLE W/ ALUMINUM 08D
BOILER
SYM.
MANUFACTURER
& MODEL NO.
FLOOR BLDG.
LOCATION
INPUT
OUTPUT
DOE
SEASONAL EFF
FUEL
GPM
ENT. WATER TEMP.
LVG. WATER TEMP.
WATERd P
OPER. WT.
BURNER ELECTRICAL
BOILER HP
V-PH I AMPS
B
HYDROTHERM KN-4
FIRST FLOOR MECH RM
MECH RM.
399 MBH
349 MBH
92.7
NAT GAS
160'F 180°F
1360 LBS.
120-1
10.6
PROVIDE BOILER WITH
CIRCULATING PUMP 120V-1(ll-60hz
FIRST FLOOR MECH RM
MECH RM.
399 MBH
349 MBH
92.7
NAT GAS
160°F 180°F
1360 LBS.
120-1
10.6
PROVIDE BOILER WITH
FIRST FLOOR MECH RM
MECH RM.
399 MBH
349 MBH
92.7
NAT GAS
160°F 180'F
1360 LBS.
120-1
10.6
PROVIDE BOILER WITH
NOTES:
1. USE SURFACE MOUNT IN GYP. BOARD CEILING FRAME TYPE 1 SUBSCRIPT "H" WHERE SHOWN DENOTES GYP. BOARD CEILING.
BRETURN/EXHAUST REGISTER SCHEDULE
UNIT NO.
MANUFACTURER
MODEL
NECK SIZE
FRAME TYPE
RANGE C.F.M.
REMARKS
�H
KRUEGER (OR EQUAL)
S580H (SQUARE)
6x6 0-160
3/4" SPACED FIXED BLADE, 35" DEFLECTION
�H
8x8
161-280
1Ox10
281-435
12x12
436-625
E:9H
14x14
626-855
16x16
856-1110
18x18
1111-1800
S580H (RECTANGULAR)
36x16 750-2000
3/4" SPACED FIXED BLADE, 35" DEFLECTION
PUMPS
| MANUFACTURER & MODEL NO. |
| FLOW RATE |
| WATERd P |
RPM
| ELECTRICAL |
| OPER. WT. (LBS) |
| PUMP EFF. |
| BLDG FLOOR |
LOCATION
| VOLTAGE |
| HP |
| CHWP |
| BELL & GOSSET 1510 2 1/288 |
157 GPM
80 FT
208-3
7.5
74.88
FIRST FLOOR
MECH ROOM
| CHWP |
| BELL & GOSSET 1510 2 1/288 |
157 GPM
80 FT
208-3
7.5
74.88
FIRST FLOOR
MECH ROOM
STAND-BY
| HWP |
| BELL & GOSSET 1510 1 1 /2"BC |
85 GPM
80 FT
208-3
| 210 |
| 62.27 |
| FIRST FIRST |
MECH ROOM
WITH VFD
| HWP |
| BELL & GOSSET 1510 1 1 /2"BC |
85 GPM
80 FT
208-3
| 210 |
| 62.27 |
| FIRST FLOOR |
MECH ROOM
STAND-BY WITH VFD
A
NOTES:
1. USE SURFACE MOUNT IN GYP. BOARD CEILING FRAME TYPE 1 SUBSCRIPT "H" WHERE SHOWN DENOTES GYP. BOARD CEILING.
2. ALL RETURN AIR GRILLES FOR FAN POWERED BOXES SHALL BE MINIMUM 18X12 FILTER GRILLE WITH FILTERS.s
CONSULTING MECHANICAL ENGINEERS 140 WEST 3RD AVENUE PH.(760)735-8577
ESCONDIDO, CA 92025 FAX(760)735-8578
w- .stueven-eng(neering.com
1 ? 'i 4 -� AS-BUILT
D
C
(/) (.!)z
0"' 0"u' L,.J z ::c 0-, ll."'
<u(-
N N "a,'.L.,..J.