This document is an equipment schedule detailing mechanical system specifications for building P-632, including air handlers, chillers, boilers, pumps, and an energy recovery unit. The air handler schedule lists three Trane units located in mechanical rooms on the first, second, and third floors, with air flow rates ranging from 7,268 to 7,820 CFM and chilled water coil specifications. The chiller is a Trane CGAM060 air-cooled model with a 57.7-ton capacity, operating at 208-3 voltage. Two Hydrotherm KN-10 boilers are installed, each with a 1,000 MBH input and 880 MBH output, running on natural gas. The pump schedule includes four Bell & Gosset pumps: two chilled water pumps and two hot water pumps, with flow rates between 122-211 GPM. An additional SEMCO energy recovery unit is located in the attic mechanical room, with a 5,320 CFM supply air flow and 4,780 CFM exhaust air flow.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AIR HANDLER SCHEDULE
SYM.
LOCATION
FLOOR
BLDG.
MFGR
MODEL
AIR FLOW CHILLED WATER COIL
ELECTRICAL SUPPLY FAN
OPER.
WT.
(LBS)
FILTERS
MERV 8
(30%)
REMARKS SUPPLY FAN OSA
CFM
MBH
ENT AIR LVG AIR WATER
ROWS FPI
CFM ESP DB WB DB WB FLOW ,l',p ENT LVG VOLTAGE HP
®2
MECH RM.
FIRST
P-632
TRANE
MCCB012
2.25"
1,750
148.3
74.6'F
61.4'F
55 O'F
53.2'F 29.6
GPM
2.54'
45'F
55'F
208-3 7.5
YES
®2
MECH RM.
SECOND
P-632
MCCB012
1,690
134.7
74.6T
60.9T
55 OT
53.3T 26.85
2.13'
55T
208-3 7.5
®2
THIRD
P-632
MCCB014
1,880
158.1
74.6T
60.TF
54.8'F
53.0'F 31.5
2.63'
SST
208-3 10
151 8
CHILLER SCHEDULE
MFGR. &
MODEL No.
SERVICE
TYPE
EVAPORATOR CONDENSER POWER EEFI ClEN ClES (IPLV) OPER.
WT.
(LBS)
REMARKS WATER
PD CAPACITY
WATER PD
(FT)
FOULING
FACTOR
AMBIENT
AIR TEMP.
V-PH MCA MOCP KW/TON EER
FLOW IN OUT GPM IN OUT
CH
1-2
CGAM060
P-632
EXTERIOR AIR
COOLED
137.9
'F
'F
17.8
FT
57.7 TONS
90'F
208-3
287.9
0.764
15.7
BOILER
MANUFACTURER
& MODEL NO.
FLOOR
LOCATION INPUT OUTPUT
THERMA
EFF
FUEL
ENT.
WATER TEMP.
LVG.
WATER TEMP. WATER L'i. P
OPER.
WT.
BURNER ELECTRICAL
REMARKS
V-PH AMPS
B HYDROTHERM
KN-10
P-632
FIRST
MECH RM
1000 MBH
880 MBH
NAT GAS
160'F
180'F
1360 LBS.
120-1
1-4
B HYDROTHERM
KN-10
P-632
MECH RM
1000 MBH
880 MBH
NAT GAS
160'F 180'F
1360 LBS.
120-1
2-4
PUMPS
MANUFACTURER
& MODEL NO.
FLOW
RATE WATER L'i. P RPM
ELECTRICAL OPER.
WT.
(LBS)
PUMP
EFF.
BLDG
FLOOR
LOCATION
REMARKS
VOLTAGE HP
CHWP
1-4
BELL & GOSSET
1510 2 1/2BB
211 GPM
80 FT
73.4
MECH ROOM
CHWP
1510 2 1/2BB
211 GPM
73.4
STAND-BY
HWP
1-4
1510 1 1 /2" AC
122 GPM
7.5 418 65.1
HWP
1510 1 1 /2"BC
122 GPM
7.5 418 65.1
STAND-BY
ENERGY RECOVERY UNIT-DEDICATED OSA AHU
FLOOR
MFGR
MODEL
AIR FLOW CHILLED WATER COIL PREHEAT COIL ELECTRICAL OPER.
WT.
(LBS)
FILTERS
MERV 7
(30%)
REMARKS SUPPLY FAN EXH FAN
MBH
ENT AIR LVG AIR WATER
ROWS FPI
MBH
ENT AIR LVG AIR WATER
ROWS FPI VOLTAGE
SUP FAN EXH FAN
CFM ESP CFM ESP DB WB DB WB FLOWI 6P ENT LVG DB WB DB WB FLOWI 6P ENT LVG HP HP
®2
MECH RM.
ATTIC
P-632
SEMCO
CM7500
FV7500H
3/4"
1.25"
60.9'F
55 OT
53.3'F 46.6
55'F
60.9°F
55 O'F
53.3°F 11.7 s5·F
208-3 5 5
File details come from the government source that posted it. Updated .