AS4006-4007.pdf
PDF 167 KB Posted
- Solicitation number
- N4008525R9023
About this file
This document is a mechanical systems schedule drawing focused on chiller, pump, expansion tank, and bypass feeder equipment specifications. The chiller schedule details an exterior air-cooled chiller with 110 tons capacity, operating at 1750 RPM, with electrical specifications of 460-3 voltage and 15 HP. The chilled water pump is configured for 256 GPM flow at 120 FT head pressure, running at 1750 RPM with 15 HP. The expansion tank is a 50 GAL bladder-type tank located in the mechanical yard, designed for the chilled water system with 12 PSI pre-charge and 15 PSI maximum pressure. The bypass feeder is a 5 GAL unit in the mechanical yard, with a 300 PSI maximum working pressure, serving the chilled water system. The drawing is a technical specification sheet (MS-001) providing comprehensive equipment details for HVAC system components, likely part of a construction or renovation project.
View the file
Other files
Show all 41
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .