This document provides details for a federal solicitation notice. The Department of the Navy Naval Facilities Engineering Command is seeking proposals for the NOAA OMAO Ship and Support Facility Relocation project at Naval Station Newport in Newport, Rhode Island. The solicitation involves specifications and drawings for relocating the NOAA OMAO ships and support facilities. Interested offerors must view the specifications and drawings through the PIEE Solicitation Module link provided in the notice under the solicitation number N4008523R2527. No other details on products, services, pricing, or response timing are included in this document.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DIRECT/INDIRECT LED LUMINAIRE
RCR
REVISED: NOVEMBER 2020 TYPE: A1, A2
CU
LIGHTING PLATE:
NOMINAL 20W INPUT/
2,000 LUMENS
LPW - 100
MINIMUM
RCR
CU
NOMINAL 30W INPUT/
3,200 LUMENS
LPW - 107
MINIMUM
TYPE A1 TYPE A2
1.03 0.89 0.78 0.69
1.03 0.89 0.78 0.69
1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL OR DIE CAST ALUMINUM. SIZE SHOWN
AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS WITH DIE FORMED COLD
ROLLED SHEET STEEL REFLECTORS.
3. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 100 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED
IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND
< 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS
INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, ROHS COMPLIANT. DLC
QUALIFIED. COMPLIES WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
7. OPTIONS - EMERGENCY BATTERY BACK-UP, INTEGRAL OCCUPANCY/VACANCY SENSOR,
VARIOUS SIZE AND OUTPUT OPTIONS, SURFACE-MOUNTING KIT.
LUMINAIRE REQUIREMENTS:
3"AND 6" RECESSED DOWNLIGHT
REVISED: NOVEMBER 2020 TYPE: C1, C2, AND C4LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
RCR
CU
1.14 1.08 1.03 0.98
NOMINAL 8W INPUT/
600 LUMENS
LPW - 75
MINIMUM
TYPE C1
RCR
CU
1.14 1.08 1.03 0.98
NOMINAL 6W INPUT/
530 LUMENS
LPW - 88
MINIMUM
TYPE C2
1. HOUSING - COLD-ROLLED STEEL OR DIE CAST ALUMINUM, WITH HEAT SINK AND FIELD AIMING
CAPABILITY. APERTURE SIZE AND SHAPE AS INDICATED IN LUMINAIRE SCHEDULE.
2. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 80 CRI UON, AND MINIMUM
EFFICACY OF 70 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE
SCHEDULE.
3. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON/OFF CONTROL
AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
4. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION. COMPLIES WITH IES LM79, LM80 AND
TM21 TESTING STANDARDS.
5. MOUNTING - RECESSED IN HARD OR ACOUSTICAL TILE CEILING. PROVIDE T-BAR HANGERS FOR
INSTALLATION IN ACOUSTICAL TILE CEILINGS OR TABS WHEN MOUNTING IN HARD CEILINGS.
6. OPTIONS - EMERGENCY BATTERY BACK-UP, VARIOUS ACRYLIC OR POLYCARBONATE LENSES,
REFLECTORS, LOUVERS, AND TRIMS. VARIOUS BEAM ANGLES. IC-RATED HOUSING.
RCR
CU
1.14 1.08 1.03 0.98
NOMINAL 10W INPUT/
800 LUMENS
LPW - 80
MINIMUM
TYPE C4
DIRECT WALL-MOUNTED LINEAR
RCR
REVISED: NOVEMBER 2020 TYPE: D1
CU
1.06 0.96 0.87 0.80
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
NOMINAL 39W INPUT/
4300 LUMENS
LPW - 110
MINIMUM
TYPE D1
1. HOUSING - COLD ROLLED STEEL, EXTRUDED ALUMINUM, OR DIE CAST ALUMINUM BODY
WITH DIE CAST END CAPS AND STAINLESS STEEL HARDWARE. SIZE AS INDICATED IN
LUMINAIRE SCHEDULE.
2. OPTICS - REFRACTIVE LENS OPTIMIZED FOR ASYMMETRIC DISTRIBUTION.
3. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 85 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED
IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND
< 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS
INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION. COMPLIES WITH IES LM79,
LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - WALL SURFACE MOUNTED.
7. OPTIONS - VARIOUS PROFILE DIMENSIONS AND RUN LENGTHS.
LINEAR LENSED LED
RCR
REVISED: NOVEMBER 2020 TYPE: E1,E2
CU
1.04 0.91 0.80 0.70
LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
NOMINAL 41W INPUT/
3,000 LUMENS
LPW - 73
MINIMUM
TYPE E2
1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL, EXTRUDED ALUMINUM, OR DIE CAST
ALUMINUM BODY. SIZE AS INDICATED IN LUMINAIRE SCHEDULE.
2. OPTICS - FROSTED ACRYLIC OR POLYCARBONATE LENS. LAMBERTIAN, NARROW, WIDE,
OR ASYMMETRIC LIGHT DISTRIBUTION AS INDICATED IN LUMINAIRE SCHEDULE.
3. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 80 CRI UON, AND MINIMUM
EFFICACY OF 90 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED IN LUMINAIRE
SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM 0.9 PF,
OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON-OFF
CONTROL AND FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN LUMINAIRE
SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION, DLC QUALIFIED. COMPLIES
WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - PENDANT, STEM, OR SURFACE MOUNTED WITH STAINLESS STEEL MOUNTING
HARDWARE, OR RECESSED IN HARD OR ACOUSTICAL TILE CEILING.
7. OPTIONS - INTEGRAL OCCUPANCY/VACANCY SENSOR, VARIOUS PROFILE DIMENSIONS
AND RUN LENGTHS, AND VARIOUS CLEAR OR FROSTED POLYCARBONATE LENSES,
BAFFLES, OR LOUVERS.
RCR
CU
1.04 0.91 0.80 0.70
NOMINAL 32W INPUT/
2,000 LUMENS
LPW - 62.5
MINIMUM
TYPE E1
LUMINAIRE REQUIREMENTS:
REVISED: NOVEMBER 2020 TYPE: S1LIGHTING PLATE:
4 0.72
RCR
1.06
0.82 0.93
CU
LED UP/DOWN WALL SCONCE
NOMINAL 12W INPUT/
3,500 LUMENS
TYPE S1
LPW - 291
MINIMUM
1. HOUSING - ALUMINUM OR STAINLESS STEEL HOUSING.
2. FINISH - REFER TO SHEET A-242 FOR EXTERIOR FINISH SCHEDULE.
3. OPTICS - DIFFUSE ACRYLIC LENS.
4. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 90 CRI UON, AND
MINIMUM EFFICACY OF 80 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
5. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH
MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT,
AND < 20% THD. ON/OFF CONTROL AND FULLY DIMMABLE DOWN TO 10%
MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
6. CERTIFICATION - UL LISTED FOR DRY OR DAMP LOCATION. COMPLIES WITH IES
LM79, LM80 AND TM21 TESTING STANDARDS.
7. MOUNTING - SURFACE MOUNTED WITH STAINLESS STEEL MOUNTING
HARDWARE.
8. OPTIONS - VARIOUS PROFILES AND SHAPES.
5 1/2" NOM.
4" N
O M
REVISED: NOVEMBER 2020 TYPE: H1,H2LIGHTING PLATE:
LUMINAIRE REQUIREMENTS:
1. HOUSING - HEAVY GAUGE COLD ROLLED STEEL OR CAST ALUMINUM HOUSING.
2. OPTICS - POLYCARBONATE DIFFUSE LENS.
3. LIGHT SOURCE - SOLID STATE LEDS, 3500K CCT UON, MINIMUM 80 CRI UON, AND MINIMUM EFFICACY
OF 140 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS INDICATED LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DIMMABLE DRIVER WITH MINIMUM 0.9 PF, OPERATING VOLTAGE OF 120-277V, THERMAL MANAGEMENT, AND < 20% THD. ON/OFF CONTROL AND
FULLY DIMMABLE DOWN TO 10% MINIMUM OR AS INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR DAMP OR WET LOCATION, DLC QUALIFIED. COMPLIES WITH IES
LM79, LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - PENDANT, STEM, OR SURFACE MOUNTED WITH STAINLESS STEEL MOUNTING
HARDWARE.
7. OPTIONS - INTEGRAL OCCUPANCY SENSOR, EMERGENCY BATTERY BACK-UP, VARIOUS OPTICAL
DISTRIBUTIONS.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE A CERTAIN MANUFACTURER
OR PREFERENCE.
RCR
CU
1.05 0.92 0.81 0.72
NOMINAL 78W INPUT/
9,400 LUMENS
LPW - 120
MINIMUM
TYPE H1
RCR
CU
NOMINAL 43W INPUT/
6,300 LUMENS
LPW - 146
MINIMUM
TYPE H2
LED INDUSTRIAL HIGH/LOW - BAY
1.05 0.92 0.81 0.72
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
EL501
LI
G
H
TI
N G
D E
TA
IL
S
JC
12874258
JR BG
JAS
LIGHT FIXTURE SCHEDULE
FIXTURE LAMP INFORMATION FIXTURE INFORMATION
NOTESTYPE TYPE COLOR TEMP
FIXTURE
LUMENS VOLTAGE WATTAGE DESCRIPTION MOUNTING
A1 LED 4000 K 2213 lm 277 V 20 W 2' X 2' RECESSED VOLUMETRIC LED TROFFER CEILING, RECESSED
A2 LED 4000 K 3239 lm 277 V 30 W 2' X 2' RECESSED VOLUMETRIC LED TROFFER CEILING, RECESSED
C1 LED 4000 K 600 lm 277 V 8 W 6" LED RECESSED OPEN DOWN LIGHT CEILING, RECESSED
C2 LED 4000 K 530 lm 277 V 6 W 3" LED DISPLAY CABINET LIGHT CEILING, RECESSED
C4 LED 4000 K 767 lm 277 V 10 W 6" LED RECESSED WET DOWN LIGHT CEILING, RECESSED
D1 LED 4000 K 4326 lm 277 V 39 W 4' LED WALL MOUNTED WALL, SURFACE 1
D2 LED 4000 K 4065 lm 277 V 34 W 4' LED WALL MOUNTED, GASKETED AND DUSTTIGHT HOUSING WALL, SURFACE
E1 LED 4000 K 2249 lm 277 V 32 W 4' LED STRIPLIGHT WITH DIFFUSER CEILING, SURFACE, PENDANT
E2 LED 4000 K 3467 lm 277 V 41 W 4' LED STRIPLIGHT WITH DIFFUSER CEILING, SURFACE, PENDANT
F LED 4000 K 1980 lm 277 V 36 W 2.25" X 8' LINEAR LED CEILING, RECESSED
G1 LED 4000 K 3048 lm 277 V 24 W 6" X 3' LINEAR LED CEILING, RECESSED
G2 LED 4000 K 3048 lm 277 V 24 W 6" X 4' LINEAR LED CEILING, RECESSED
G3 LED 4000 K 3048 lm 277 V 30 W 6" X 5' LINEAR LED CEILING, RECESSED
H1 LED 4000 K 9396 lm 277 V 78 W 4' LED STRIPLIGHT WITH DIFFUSER PENDANT
H2 LED 4000 K 6248 lm 277 V 43 W 4' LED LOW BAY PENDANT
M1 LED 4000 K 2007 lm 277 V 18 W 2' X 2' RECESSED GENERAL LED LENSED CEILING, RECESSED
P LED 4000 K 116889 lm 480 V 838 W LED PIER HIGH MAST MOUNTED LIGHT HIGH MAST 2
S1 LED 4000 K 3512 lm 277 V 12 W EGRESS WALLPACK WALL EXTERIOR
S2 LED 4000 K 4500 lm 277 V 35 W 10" X 10" LED CANOPY LUMINAIRE CEILING, SURFACE 3
T2 LED 4000 K 8395 lm 277 V 69 W LED PARKING LOT POLE MOUNTED LIGHT (TYPE II DISTRIBUTION) POLE MOUNTED 4
T2S LED 4000 K 8395 lm 277 V 69 W LED TRESTLE POLE MOUNTED LIGHT (TYPE II DISTRIBUTION) POLE MOUNTED
T3 LED 4000 K 8360 lm 277 V 69 W LED PARKING LOT POLE MOUNTED LIGHT (TYPE III DISTRIBUTION) POLE MOUNTED
T4 LED 4000 K 8370 lm 277 V 69 W LED PARKING LOT POLE MOUNTED LIGHT (TYPE IV DISTRIBUTION) POLE MOUNTED
V1 LED 4000 K 1285 lm 277 V 18 W 2' WALL MOUNTED LED VANITY WALL, SURFACE
X LED 277 V 25 W EMERGENCY WALL PACK SURFACE, WALL
X1 LED 277 V 5 W CEILING MOUNTED LED EXIT SIGN CEILING, SURFACE
X2 LED 4000 K 277 V 5 W LED EXIT SIGN WALL, SURFACE
NOTES
1. PROVIDE TYPE D1 FIXTURES THAT ARE MOUNTED IN STAIRWELLS WITH INTEGRAL MOTION SENSOR THAT WILL AUTOMATICALLY DIM FIXTURES TO 20% WHEN NOT OCCUPIED.
2. PROVIDE THREE (3) FIXTURES PER MAST AT 100' AFF ON PIER AND TWO (2) FIXTURES PER MAST ON SITE PARKING. REFER TO SHEET EL504.
3. PROVIDE FIXTURE WITH INTEGRAL OCCUPANCY SENSOR TO AUTOMATICALLY DIM FIXTURES TO 30% ILLUMINATION AFTER 15 MINUTES, AND TO ILLUMINATE TO 100% UPON MOTION
ACTIVATION.
4. PROVIDE PHOTCELL ATOP LIGHTING FIXTURES TYPE LOCATED NEAR BUILDING 11'S PARKING LOT. REFER TO SHEET ES111. THE REMAINING TYPE T2 FIXUTES MUST BE CONTROLLED BY
WAREHOUSE BUILDING'S PHOTOCELL AND CONTROL PANEL.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
U
P D
A T
E H
IG
H
M A
S T
V O
LT
A
G E
//1
5/
M
M
M
J
P
P
P
5 8
44 13
14 15 15 15 15
15 15 15 15 14
44 13
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
EJ 18192021222324252627
CL
B
C
A
D
HTP-05
HTP-06
P1
P2
Hot Box Enclosure-01
Hor Box Enclosure-02
P1 - 1,3
P2 - 1,3
B-1 - 3
B-2 - 3
44 12
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
EP114
P
IE
R
P O
W E
R P
LA
N
A
R E
A D
JC
12874267
JR BG
JAS
SHEET KEYNOTES
1. TELECOM CIRCUITS. SEE SHEET TN103.
2. UNIT SUBSTATION B-1. SEE ELEVATION ON DETAIL A2 / EP503.
3. UNIT SUBSTATION B-2. SEE ELEVATION ON DETAIL A2 / EP503.
4. UNIT SUBSTATION IP-1. SEE DETAIL B2 / EP503.
5. UNIT SUBSTATION IP-2. SEE DETAIL B2 / EP503.
6. PROVIDE CONTROL WIRING IN 3" SCHD40 PVC CONDUIT FOR SHIP SHORE
POWER.
7. PROVIDE CONNECTION TO POLE MOUNTED EXTERIOR CAMERAS. REFER
TO EMLV1-5 ON SHEET E-741 FOR BRANCH CIRCUIT INFORMATION.
8. ROUTE HEAT TRACE PANEL (HTP) AND HOT BOX HEATER FEEDER
CONDUIT THROUGH SLAB.
1/8" = 1'-0" A1
POWER PLAN - AREA D
PLAN
NORTH
ABD CEFG
H
KEY PLAN
PLAN
NORTH
4' 8' 16'0'
1. SEE SHEET ES101 FOR THE ELECTRICAL AND TELECOM FEEDER
SCHEDULE.
2. THE DIMENSIONS OF THE UNIT SUBSTATIONS ON THE PIER CANNOT BE
EXCEEDED AS TO NOT INTRUDE INTO THE PIER FIRE LANE. ALL NEC
CLEARANCES MUST BE OBSERVED. PRIMARY AND SECONDARY
SECTIONS MUST BE FRONT ACCESS ONLY.
3. PRIOR TO FINAL DESIGN FABRICATION AND INSTALLATION OF PLATFORM,
COORDINATE UNIT SUBSTATION MOUNTING POINTS WITH THE PLATFORM
STRUCTURE TO AVOID MISALIGNMENT WITH THE UNIT SUBSTATION
MOUNTING LOCATIONS.
SHEET NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
B
A S
E B
ID
U
P D
A T
E
/2 7/
U
P D
A T
E D
U N
IT
S
U B
S T
A T
IO
N
S
/2 7/
U
P D
A T
E D
H E
A T
IN
G
B O
X L
O A
D
/1 7/
U
P D
A T
E D
C O
N D
U
IT
S R
O U
T E
/1
5/
P P
P
11 1 1
8 9
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
8 9
272829303132333435
CL
B
C
A
D
1514 15 15 15 8 9
98 14 15 15 15 15
4" ø
HTP-08
HTP-07
B-3 - 1
B-4 - 1
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
EP115
P
IE
R
P O
W E
R P
LA
N
A
R E
A E
JC
12874268
JR BG
JAS
SHEET KEYNOTES
1/8" = 1'-0" A1
POWER PLAN - AREA E
PLAN
NORTH
ABD CEFG
H
KEY PLAN
PLAN
NORTH
4' 8' 16'0'
1. TELECOM CIRCUITS. SEE SHEET TN104.
2. PIER INDUSTRIAL POWER LVCB. SEE DETAIL A2 / EP505.
3. PIER SHORE POWER LVCB. SEE DETAIL A2 / EP508.
4. PROVIDE CONTROL WIRING IN 3" SCHD40 PVC CONDUIT FOR PIER SHORE
POWER.
5. ROUTE HEAT TRACE PANEL (HTP) AND FEEDER CONDUIT THROUGH SLAB.
1. SEE SHEET ES101 FOR THE ELECTRICAL AND TELECOM FEEDER
SCHEDULE.
SHEET NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
B
A S
E B
ID
U
P D
A T
E
/2 7/
U
P D
A T
E D
S H
E E
T K
E Y
N O
T E
S
/1 5/
U
P D
A T
E D
C O
N D
U
IT
S R
O U
T E
/1
5/
M
M
14 15 15 15 15
14 15 15 15 15
13 44
8 9
13 44
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
M A
T C
H L
IN
E
R E
F E
R T
O A
/ E
P
3536373839404142
CL
B
C
A
D
4" ø
Hot Box Enclosure-04
Hot Box Enclosure-03
HTP-10
B-3 - 2
HTP-09
B-4 - 2 P4 - 1,3
P3 - 1,3
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
EP116
P
IE
R
P O
W E
R P
LA
N
A
R E
A F
JC
12874269
JR BG
JAS
SHEET KEYNOTES
1. TELECOM CIRCUITS. SEE SHEET TN105.
2. UNIT SUBSTATION IP-3. SEE DETAIL B2 / EP503.
3. UNIT SUBSTATION IP-4. SEE DETAIL B2 / EP503.
4. UNIT SUBSTATION B-3. SEE DETAIL A2 / EP503.
5. UNIT SUBSTATION B-4. SEE DETAIL A2 / EP503.
6. PIER INDUSTRIAL POWER LVCB. SEE DETAIL A2 / EP505.
7. PIER SHORE POWER LVCB. SEE DETAIL A2 / EP508.
8. PROVIDE CONTROL WIRING IN 3" SCHD40 PVC CONDUIT FOR PIER SHORE
POWER.
9. ROUTE HEAT TRACE PANEL (HTP) AND HOT BOX HEATER FEEDER
CONDUIT THROUGH SLAB.
1/8" = 1'-0" A1
POWER PLAN - AREA F
PLAN
NORTH
ABD CEFG
H
KEY PLAN
PLAN
NORTH
4' 8' 16'0'
1. SEE SHEET ES101 FOR THE ELECTRICAL AND TELECOM FEEDER
SCHEDULE.
2. THE DIMENSIONS OF THE UNIT SUBSTATIONS ON THE PIER CANNOT BE
EXCEEDED AS TO NOT INTRUDE INTO THE PIER FIRE LANE. ALL NEC
CLEARANCES MUST BE OBSERVED. PRIMARY AND SECONDARY
SECTIONS MUST BE FRONT ACCESS ONLY.
3. PRIOR TO FINAL DESIGN FABRICATION AND INSTALLATION OF PLATFORM,
COORDINATE UNIT SUBSTATION MOUNTING POINTS WITH THE PLATFORM
STRUCTURE TO AVOID MISALIGNMENT WITH THE UNIT SUBSTATION
MOUNTING LOCATIONS.
SHEET NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
B
A S
E B
ID
U
P D
A T
E
/2 7/
U
P D
A T
E D
U N
IT
S
U B
S T
A T
IO
N
S
/2 7/
U
P D
A T
E D
H E
A T
IN
G
B O
X L
O A
D
/1 7/
U
P D
A T
E D
S H
E E
T K
E Y
N O
T E
S
/1 5/
U
P D
A T
E D
C O
N D
U
IT
S R
O U
T E
/1
5/
NOTES:
THIS DETAIL DOES NOT PRECLUDE THE REQUIREMENTS OF
NEC ART. 250 OR NFPA 780. STRICTLY ADHERE TO NEC ART. 250, WHICH
SUPERCEDES THIS DETAIL.
COMPLY WITH TIA-607B FOR TELECOMMUNICATIONS BONDING AND
GROUNDING, EXCEPT WHERE NEC SUPERCEDES.
1.
MAIN ELECTRICAL ROOM
PANEL
N
G
MAIN GND BUS
(MGB) TYPICAL FLOOR
ROOF
SEE PLAN FOR
ROUTING OF COUNTERPOISE
GROUNDING ELECTRODE CONDUCTOR
LIGHTNING AIR
TERMINAL (TYP)
TYP OF ALL
MAJOR ELEC
EQUIPMENT
TYP BLDG
STEEL
ROOF MOUNTED
EQUIPMENT (TYP)
TELECOM CLOSET OR
EQUIPMENT ROOM
GB
BOND GB AT SAME LOCATION AS
SEPARATELY DERIVED SYSTEM
GROUNDING ELECTRODE CONDUCTOR
GROUNDING
ELECTRODE
CONDUCTOR
2.
SEPARATELY DERIVED
SYSTEM,
TRANSFORMER &
PANEL LOCATED IN
OTHER TELECOMM/AV
ROOMS
PB TX
n g n g
PB
n g
GROUNDING
ELECTRODE
CONDUCTOR
TO INCOMING
WATER
SERVICE
EQUIPMENT
POWER CONDUCTORS, TYP
COUPLING, TYP
CONDUIT, TYP
#4/0 AWG STRANDED
CU GROUND CABLE
BOX ADAPTOR, TYP
SOLDERLESS LUG,
TIN PLATED, TYP
GROUND BUS,
CONNECT TO SOURCE
GROUND
GROUNDING BUSHING
INCOMING
CONDUIT LOCKNUT
GROUNDING LUG
BONDING JUMPER
GROUNDING
TERMINAL STRIP
PANEL
CABINET
BONDING JUMPER
GROUNDING LUG
NOTES:
CONDUIT
GROUNDING
BUSHING
CONDUIT
LOCKNUTS
EQUIPMENT GROUNDING
CONDUCTOR
NEUTRAL
TERMINAL STRIP
1. ALL WIRES MUST BE NEATLY LACED.
2. AT THE POINT OF ATTACHMENT OF THE GROUNDING TERMINAL STRIP
TO THE CABINET, THE SURFACES MUST BE SCRAPPED FREE OF PAINT
AND THOROUGHLY CLEANED TO INSURE PROPER BONDING.
3. NEUTRAL CONDUCTOR NOT SHOWN FOR CLARITY.
GATE JUMPER WITH
EXOTHERMIC WELD
GROUND CONDUCTOR
WITH EXOTHERMIC WELD
BOTH SIDES OF GATE #4/0 AWG BARE COPPER
CONDUCTOR TO GROUND ROD.
#6 AWG INSULATED COPPER
#6 AWG COPPER WIRE
CLAMPED, BRAZED, OR WELDED TO FENCE POST.
#6 AWG BARE COPPER WIRE
FENCE REINFORCING WIRE WEAVED
IN AND OUT OF FENCE PICKETS EVERY
THREE(3) PICKETS.
GROUND ROD DRIVEN 10'
OR TO REFUSAL
GROUND LEVEL
NOTES:
1. THREAD REINFORCING WIRE THROUGH
CHAIN LINK FENCE THREE LINKS AT A TIME
AND PULL WIRE TO REMOVE ALL SLACK.
REPEAT PROCESS ALONG THE ENTIRE LENGTH
OF FENCE.
2. COPPER WIRE MUST BE CONTINUOUS BETWEEN
POSTS. PROVIDE SPLICES AS REQUIRED AT
POSTS TO MAINTAIN CONTINUITY.
3. REINFORCING WIRE MUST BE BONDED AT EVERY
FENCE POST WITH AN EXOTHERMIC WELD. BOND TO
GROUND RODS MUST BE EXOTHERMIC.
4. GROUND RODS MUST BE INSTALLED AT 100'
INTERVALS ALONG THE LENGTH OF THE FENCE.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
EP507
P O
W E
R D
E
TA
IL
S
JC
12874284
JR BG
JAS
NOT TO SCALE
A3
TYPICAL GROUNDING RISER SCHEMATIC
NOT TO SCALE
C4
TYPICAL ELECTRICAL
EQUIPMENT GROUNDING DETAIL
NOT TO SCALE
C1
PANELBOARD BONDING DETAIL
NOT TO SCALE
C2
GATE GROUNDING DETAIL
NOT TO SCALE
A1
FENCE GROUNDING DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
U
P D
A T
E D
D E
T A
IL
/1 5/
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
E-710
P
IE
R
P A
N E
LB
O
A R
D S
C H
E D
U
LE
S
JC
12874301
JR BG
JAS
DEMAND WITH EXPANSION: 2196 A
TOTAL ESTIMATED DEMAND CURRENT: 1830 A
TOTAL CONNECTED CURRENT: 1904 A
TOTAL ESTIMATED DEMAND LOAD: 1521445 VA
TOTAL CONNECTED LOAD: 1582956 VA
SWITCHBOARD TOTALS
16 SPD 3 60 A 100 A 0 VA
15 SPACE 1 -- -- -- --
14 SPACE 1 -- -- -- --
13 SPACE 1 -- -- -- --
12 SPACE 1 -- -- -- --
11 SPACE 1 -- -- -- --
10 SPACE 1 -- -- -- --
9 PIER INDUSTRIAL REC 200A REFER TO ES101 FEEDER #12 3 200 A 400 A 133022 VA
8 PIER SHORE POWER REC #5 REFER TO ES101 FEEDER #14 3 30 A 100 A 19953 VA
7 PIER SHORE POWER REC #4 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
6 PIER SHORE POWER REC #3 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
5 PIER SHORE POWER REC #2 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
4 PIER SHORE POWER REC #1 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
3 HTP-05 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
2 HTP-03 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
1 HTP-01 4#4, #4G. IN 1-1/4"C 3 50 A 100 A 33255 VA
CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES
TRIP
RATING
FRAME SIZE Load COMMENTS
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 3000 A
MOUNTING: FLOOR WIRES: 3 MAINS RATING: 3000 A
SUPPLY FROM: PHASES: 3 MAINS TYPE: MCB
LOCATION: VOLTAGE: 480/277 Delta A.I.C. RATING: 65,000
SWITCHBOARD: B-1
DEMAND WITH EXPANSION: 2196 A
TOTAL ESTIMATED DEMAND CURRENT: 1830 A
TOTAL CONNECTED CURRENT: 1904 A
TOTAL ESTIMATED DEMAND LOAD: 1521445 VA
TOTAL CONNECTED LOAD: 1582956 VA
SWITCHBOARD TOTALS
16 SPD 3 60 A 100 A 0 VA
15 SPACE 1 -- -- -- --
14 SPACE 1 -- -- -- --
13 SPACE 1 -- -- -- --
12 SPACE 1 -- -- -- --
11 SPACE 1 -- -- -- --
10 SPACE 1 -- -- -- --
9 PIER INDUSTRIAL REC 200A REFER TO ES101 FEEDER #12 3 200 A 200 A 133022 VA
8 PIER SHORE POWER REC #5 REFER TO ES101 FEEDER #14 3 30 A 100 A 19953 VA
7 PIER SHORE POWER REC #4 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
6 PIER SHORE POWER REC #3 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
5 PIER SHORE POWER REC #2 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
4 PIER SHORE POWER REC #1 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
3 HTP-06 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
2 HTP-04 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
1 HTP-02 4#4, #4G. IN 1-1/4"C 3 50 A 100 A 33255 VA
CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES
TRIP
RATING
FRAME SIZE Load COMMENTS
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 3000 A
MOUNTING: FLOOR WIRES: 3 MAINS RATING: 3000 A
SUPPLY FROM: UNIT SUBSTATION B-2 PHASES: 3 MAINS TYPE: MCB
LOCATION: BERTH-2 VOLTAGE: 480/277 Delta A.I.C. RATING: 65,000
SWITCHBOARD: B-2
DEMAND WITH EXPANSION: 2196 A
TOTAL ESTIMATED DEMAND CURRENT: 1830 A
TOTAL CONNECTED CURRENT: 1904 A
TOTAL ESTIMATED DEMAND LOAD: 1521445 VA
TOTAL CONNECTED LOAD: 1582956 VA
SWITCHBOARD TOTALS
16 SPD 3 60 A 100 A 0 VA
15 SPACE 1 -- -- -- --
14 SPACE 1 -- -- -- --
13 SPACE 1 -- -- -- --
12 SPACE 1 -- -- -- --
11 SPACE 1 -- -- -- --
10 SPACE 1 -- -- -- --
9 PIER INDUSTRIAL REC 200A REFER TO ES101 FEEDER #12 3 200 A 200 A 133022 VA
8 PIER SHORE POWER REC #5 REFER TO ES101 FEEDER #14 3 30 A 100 A 19953 VA
7 PIER SHORE POWER REC #4 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
6 PIER SHORE POWER REC #3 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
5 PIER SHORE POWER REC #2 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
4 PIER SHORE POWER REC #1 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
3 HTP-11 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
2 HTP-09 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
1 HTP-07 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES
TRIP
RATING
FRAME SIZE Load COMMENTS
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 3000 A
MOUNTING: FLOOR WIRES: 3 MAINS RATING: 3000 A
SUPPLY FROM: UNIT SUBSATION B-3 PHASES: 3 MAINS TYPE: MCB
LOCATION: BERTH-3 VOLTAGE: 480/277 Delta A.I.C. RATING: 65,000
SWITCHBOARD: B-3
DEMAND WITH EXPANSION: 2196 A
TOTAL ESTIMATED DEMAND CURRENT: 1830 A
TOTAL CONNECTED CURRENT: 1904 A
TOTAL ESTIMATED DEMAND LOAD: 1521445 VA
TOTAL CONNECTED LOAD: 1582956 VA
SWITCHBOARD TOTALS
16 SPD 3 60 A 100 A 0 VA
15 SPACE 1 -- -- -- --
14 SPACE 1 -- -- -- --
13 SPACE 1 -- -- -- --
12 SPACE 1 -- -- -- --
11 SPACE 1 -- -- -- --
10 SPACE 1 -- -- -- --
9 PIER INDUSTRIAL REC 200A REFER TO ES101 FEEDER #12 3 200 A 200 A 133022 VA
8 PIER SHORE POWER REC #5 REFER TO ES101 FEEDER #14 3 30 A 100 A 19953 VA
7 PIER SHORE POWER REC #4 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
6 PIER SHORE POWER REC #3 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
5 PIER SHORE POWER REC #2 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
4 PIER SHORE POWER REC #1 REFER TO ES101 FEEDER #15 3 500 A 800 A 332554 VA
3 HTP-12 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
2 HTP-10 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
1 HTP-08 4#6, #10G. IN 1"C 3 50 A 100 A 33255 VA
CKT LOAD NAME DESIGN WIRE AND CONDUIT POLES
TRIP
RATING
FRAME SIZE Load COMMENTS
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 3000 A
MOUNTING: FLOOR WIRES: 3 MAINS RATING: 3000 A
SUPPLY FROM: UNIT SUBSTATION B-4 PHASES: 3 MAINS TYPE: MCB
LOCATION: BERTH-4 VOLTAGE: 480/277 Delta A.I.C. RATING: 65,000
SWITCHBOARD: B-4
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
U
P D
A T
E D
B R
E A
K E
R S
IZ
E
/1
5/
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
E-711
P
IE
R
P A
N E
LB
O
A R
D S
C H
E D
U
LE
S
JC
12874302
JR BG
JAS
DEMAND WITH EXPANSION: 82 A
TOTAL ESTIMATED DEMAND... 68 A
TOTAL CONNECTED CURRENT: 68 A
TOTAL ESTIMATED DEMAND LOAD: 24677 VA
TOTAL CONNECTED LOAD: 24677 VA
PANEL TOTALS
TOTAL AMPS: 73 A 68 A 65 A
TOTAL LOAD: 8715 VA 8115 VA 7848 VA
29 0 -- SPACE 1 -- 30
27 0 -- SPACE 1 -- 28
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 26
23 -- 1 SPACE -- 0 SPARE 1 20 24
21 -- 1 SPACE -- 0 SPARE 1 20 22
19 20 1 SPARE 0 600 2#12, #12G. IN 1/2"C IP-1 RELAY BATTERY 1 20 20
17 20 1 B-1 RELAY BATTERY 2#12, #12G. IN 1/2"C 600 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #3 1 20 18
15 20 1 SHORE POWER MOUND HEATER 2#10, #10G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #2 1 20 16
13 20 1 INDUSTRIAL POWER MOUND HEATER 2#10, #10G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #1 1 20 14
11 20 1 SECONDARY UNIT SUB IP-1 HEATER 2#12, #12G. IN 1/2"C 1000 1664 12
9 20 1 PRIMARY UNIT SUB IP-1 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #3 2 20
7 20 1 SECONDARY UNIT SUB B-1 HEATER 2#12, #12G. IN 1/2"C 1000 1664 8
5 20 1 PRIMARY UNIT SUB B-1 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #2 2 20
3 867 1664 4
20 2 HOT BOX HEATER - 01 2#12, #12G. IN 1"C
867 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #1 2 20
# B... P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 4 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: UNIT SUBSTATION IP-1 PHASE: 3 MAINS TYPE: MCB
LOCATION: BERTH 1 VOLTAGE: 120/208 Wye A.I.C. RATING: 22,000
PANELBOARD: P1
DEMAND WITH EXPANSION: 82 A
TOTAL ESTIMATED DEMAND... 68 A
TOTAL CONNECTED CURRENT: 68 A
TOTAL ESTIMATED DEMAND LOAD: 24677 VA
TOTAL CONNECTED LOAD: 24677 VA
PANEL TOTALS
TOTAL AMPS: 73 A 68 A 65 A
TOTAL LOAD: 8715 VA 8115 VA 7848 VA
29 0 -- SPACE 1 -- 30
27 0 -- SPACE 1 -- 28
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 26
23 -- 1 SPACE -- 0 SPARE 1 20 24
21 -- 1 SPACE -- 0 SPARE 1 20 22
19 20 1 SPARE 0 600 2#12, #12G. IN 1/2"C IP-2 RELAY BATTERY 1 20 20
17 20 1 B-2 RELAY BATTERY 2#12, #12G. IN 1/2"C 600 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #3 1 20 18
15 20 1 SHORE POWER MOUND HEATER 2#10, #10G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #2 1 20 16
13 20 1 INDUSTRIAL POWER MOUND HEATER 2#10, #10G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #1 1 20 14
11 20 1 SECONDARY UNIT SUB IP-2 HEATER 2#12, #12G. IN 1/2"C 1000 1664 12
9 20 1 PRIMARY UNIT SUB IP-2 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #3 2 20
7 20 1 SECONDARY UNIT SUB B-2 HEATER 2#12, #12G. IN 1/2"C 1000 1664 8
5 20 1 PRIMARY UNIT SUB B-2 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #2 2 20
3 867 1664 4
20 2 HOT BOX HEATER - 02 2#12, #12G. IN 1"C
867 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #1 2 20
# B... P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 4 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: UNIT SUBSTATION IP-2 PHASE: 3 MAINS TYPE: MCB
LOCATION: BERTH 2 VOLTAGE: 120/208 Wye A.I.C. RATING: 22,000
PANELBOARD: P2
DEMAND WITH EXPANSION: 82 A
TOTAL ESTIMATED DEMAND... 68 A
TOTAL CONNECTED CURRENT: 68 A
TOTAL ESTIMATED DEMAND LOAD: 24677 VA
TOTAL CONNECTED LOAD: 24677 VA
PANEL TOTALS
TOTAL AMPS: 73 A 68 A 65 A
TOTAL LOAD: 8715 VA 8115 VA 7848 VA
29 0 -- SPACE 1 -- 30
27 0 -- SPACE 1 -- 28
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 26
23 -- 1 SPACE -- 0 SPARE 1 20 24
21 -- 1 SPACE -- 0 SPARE 1 20 22
19 20 1 SPARE 0 600 2#12, #12G. IN 1/2"C IP-3 RELAY BATTERY 1 20 20
17 20 1 B-3 RELAY BATTERY 2#12, #12G. IN 1/2"C 600 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #3 1 20 18
15 20 1 SHORE POWER MOUND HEATER 2#12, #12G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #2 1 20 16
13 20 1 INDUSTRIAL POWER MOUND HEATER 2#12, #12G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #1 1 20 14
11 20 1 SECONDARY UNIT SUB IP-3 HEATER 2#12, #12G. IN 1/2"C 1000 1664 12
9 20 1 PRIMARY UNIT SUB IP-3 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #3 2 20
7 20 1 SECONDARY UNIT SUB B-3 HEATER 2#12, #12G. IN 1/2"C 1000 1664 8
5 20 1 PRIMARY UNIT SUB B-3 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #2 2 20
3 867 1664 4
20 2 HOT BOX HEATER - 03 2#12, #12G. IN 1/2"C
867 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #1 2 20
# B... P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 4X MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: UNIT SUBSTATION IP-3 PHASE: 3 MAINS TYPE: MCB
LOCATION: BERTH 3 VOLTAGE: 120/208 Wye A.I.C. RATING: 22,000
PANELBOARD: P3
DEMAND WITH EXPANSION: 82 A
TOTAL ESTIMATED DEMAND... 68 A
TOTAL CONNECTED CURRENT: 68 A
TOTAL ESTIMATED DEMAND LOAD: 24677 VA
TOTAL CONNECTED LOAD: 24677 VA
PANEL TOTALS
TOTAL AMPS: 73 A 68 A 65 A
TOTAL LOAD: 8715 VA 8115 VA 7848 VA
29 0 -- SPACE 1 -- 30
27 0 -- SPACE 1 -- 28
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 26
23 -- 1 SPACE -- 0 SPARE 1 20 24
21 -- 1 SPACE -- 0 SPARE 1 20 22
19 20 1 SPARE 0 600 2#12, #12G. IN 1/2"C IP-4 RELAY BATTERY 1 20 20
17 20 1 B-4 RELAY BATTERY 2#12, #12G. IN 1/2"C 600 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #3 1 20 18
15 20 1 SHORE POWER MOUND HEATER 2#12, #12G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #2 1 20 16
13 20 1 INDUSTRIAL POWER MOUND HEATER 2#12, #12G. IN 1"C 1000 1920 ES101 FEEDER #13 PIER INDUSTRIAL POWER L5-20R #1 1 20 14
11 20 1 SECONDARY UNIT SUB IP-4 HEATER 2#12, #12G. IN 1/2"C 1000 1664 12
9 20 1 PRIMARY UNIT SUB IP-4 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #3 2 20
7 20 1 SECONDARY UNIT SUB B-4 HEATER 2#12, #12G. IN 1/2"C 1000 1664 8
5 20 1 PRIMARY UNIT SUB B-4 HEATER 2#12, #12G. IN 1/2"C 1000 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #2 2 20
3 867 1664 4
20 2 HOT BOX HEATER - 04 2#12, #12G. IN 1/2"C
867 1664
ES101 FEEDER #13 PIER INDUSTRIAL POWER L10-20R #1 2 20
# B... P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P B... #
NOTES:
ENCLOSURE: NEMA 4X MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: UNIT SUBSTATION IP-4 PHASE: 3 MAINS TYPE: MCB
LOCATION: BERTH 4 VOLTAGE: 120/208 Wye A.I.C. RATING: 22,000
PANELBOARD: P4
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
U
P D
A T
E D
H E
A T
IN
G
B O
X L
O A
D
/1 7/
A
D D
E D
P O
W E
R T
O R
E
LA
Y
/1 7/
U
P D
A T
E D
W
IR
E S
IZ
E
/1
5/
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
E-745
A D
M
IN
W
A R
E H
O U
S E
P
A N
E
LB
O A
R D
S C
H E
D U
LE
S
JC
12874307
JR BG
JAS
DEMAND WITH EXPANSION: 37 A
TOTAL ESTIMATED DEMAND... 31 A
TOTAL CONNECTED CURRENT: 31 A
TOTAL ESTIMATED DEMAND LOAD: 25482 VA
TOTAL CONNECTED LOAD: 25482 VA
PANEL TOTALS
TOTAL AMPS: 41 A 32 A 22 A
TOTAL LOAD: 10900 VA 8577 VA 6006 VA
41 0 -- SPACE 1 -- 42
39 0 -- SPACE 1 -- 40
60 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 38
35 -- 1 SPACE -- -- SPACE 1 -- 36
33 -- 1 SPACE -- -- SPACE 1 -- 34
31 20 1 SPARE 0 -- SPACE 1 -- 32
29 20 1 SPARE 0 0 SPARE 1 20 30
27 1257 0 SPARE 1 20 28
20 2 HIGH MAST CKT #3 ES101 - FEEDER #6
1257 0 SPARE 1 20 26
23 582 450 24
21 582 466 22
20 3 JOCKEY PUMP: 137 3#10, #10G IN 3/4" C
582 1996
REFER TO SHEET E-641 FOR
SINGLE LINE
PANEL LS2 3 100
17 60 200 18
15 876 1100 16
100 3 PANEL LS-3
REFER TO SHEET E-641
FOR SINGLE LINE
1279 3200
REFER TO SHEET E-641 FOR
SINGLE LINE
T-FP 3 25
11 1257 1700 2#6, #8G IN 1-1/4" C SITE HIGH MAST LIGHTING 1 20 12
20 2 HIGH MAST CKT #1 ES101 - FEEDER #6
1257 1000 2#6, #8G IN 1-1/4" C SITE LIGHTING 1 20 10
7 20 1 LTG: 214,125,128,129 2#10, #10G IN 1/2" C 558 1257 8
5 20 1 TRESTLE CKT #1 ES101 - FEEDER #6 500 1257
ES101 - FEEDER #6 HIGH MAST CKT #2 2 20
3 20 1 LTG: 130,131,132,133,134,135 2#10, #10G, IN 3/4" C 660 1379 2#10, #10G, IN 3/4" C LTG: 122,123,127,135 1 20 4
1 20 1 LTG: EXTERIOR NORTH 2#10, #10G, IN 3/4" C 271 500 ES101 - FEEDER #6 TRESTLE CKT #2 1 20 2
# B... P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
1 - PROVIDE RED / LOCKABLE CIRCUIT BREAKERS FOR FIRE ALARM.
2 - NOT USED.
3 - BID OPTION - FLOATING DOCK SYSTEM. FOR ADDITIONAL INFORMATION REFER TO SHEET ES104 NOTE 19.
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 200 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 225 A
SUPPLY FROM: ATS-LS PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECT 136 VOLTAGE: 480/277 Wye A.I.C. RATING: 22,000
PANELBOARD: LS1
DEMAND WITH EXPANSION: 4 A
TOTAL ESTIMATED DEMAND... 4 A
TOTAL CONNECTED CURRENT: 4 A
TOTAL ESTIMATED DEMAND LOAD: 2912 VA
TOTAL CONNECTED LOAD: 2912 VA
PANEL TOTALS
TOTAL AMPS: 7 A 2 A 2 A
TOTAL LOAD: 1996 VA 466 VA 450 VA
41 0 -- SPACE 1 -- 42
39 0 -- SPACE 1 -- 40
60 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 38
35 -- 1 SPACE -- -- SPACE 1 -- 36
33 -- 1 SPACE -- -- SPACE 1 -- 34
31 -- 1 SPACE -- -- SPACE 1 -- 32
29 -- 1 SPACE -- -- SPACE 1 -- 30
27 -- 1 SPACE -- -- SPACE 1 -- 28
25 -- 1 SPACE -- -- SPACE 1 -- 26
23 -- 1 SPACE -- -- SPACE 1 -- 24
21 -- 1 SPACE -- -- SPACE 1 -- 22
19 -- 1 SPACE -- -- SPACE 1 -- 20
17 -- 1 SPACE -- -- SPACE 1 -- 18
15 -- 1 SPACE -- -- SPACE 1 -- 16
13 20 1 SPARE 0 0 SPARE 1 20 14
11 20 1 SPARE 0 0 SPARE 1 20 12
9 20 1 SPARE 0 0 SPARE 1 20 10
7 20 1 LGT: 109, 110,137,138 2#10, #10G IN 1/2" C 488 48 2#12, #12G IN 1/2" C LTG: EXTERIOR SOUTH 1 20 8
5 20 1 LTG: 114,116,117,119 2#12, #12G IN 1/2" C 210 240 2#12, #12G IN 1/2" C LTG: STAIR A 118, STAIR B 111 1 20 6
3 20 1 LTG: 100,101,108,115 2#12, #12G IN 1/2" C 398 68 2#12, #12G IN 1/2" C LGT: ELEV EQUIP 121 1 20 4
1 20 1 LTG: 102,103,104,105,106 2#12, #12G IN 1/2" C 1222 238 2#12, #12G IN 1/2" C ELEVATOR SHAFT LIGHTS 1 20 2
# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: LS1 PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECT 109 VOLTAGE: 480/277 Wye A.I.C. RATING: 22,000
PANELBOARD: LS2
DEMAND WITH EXPANSION: 3 A
TOTAL ESTIMATED DEMAND... 3 A
TOTAL CONNECTED CURRENT: 3 A
TOTAL ESTIMATED DEMAND LOAD: 2215 VA
TOTAL CONNECTED LOAD: 2215 VA
PANEL TOTALS
TOTAL AMPS: 5 A 4 A 0 A
TOTAL LOAD: 1279 VA 876 VA 60 VA
... 0 -- SPACE 1 -- 42
... 0 -- SPACE 1 -- 40
60 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 38
... -- 1 SPACE -- -- SPACE 1 -- 36
... -- 1 SPACE -- -- SPACE 1 -- 34
... -- 1 SPACE -- -- SPACE 1 -- 32
... -- 1 SPACE -- -- SPACE 1 -- 30
... -- 1 SPACE -- -- SPACE 1 -- 28
... -- 1 SPACE -- -- SPACE 1 -- 26
... -- 1 SPACE -- -- SPACE 1 -- 24
... -- 1 SPACE -- -- SPACE 1 -- 22
... -- 1 SPACE -- -- SPACE 1 -- 20
... -- 1 SPACE -- -- SPACE 1 -- 18
... -- 1 SPACE -- -- SPACE 1 -- 16
... -- 1 SPACE -- -- SPACE 1 -- 14
... 20 1 SPARE 0 0 SPARE 1 20 12
9 20 1 SPARE 0 0 SPARE 1 20 10
7 20 1 SPARE 0 0 SPARE 1 20 8
5 20 1 LTG: EXTERIOR SOUTH 2ND FLOOR 2#12, #12G IN 1/2" C 60 0 SPARE 1 20 6
3 20 1 LTG: 215, 216 2#12, #12G IN 1/2" C 228 648 2#12, #12G IN 1/2" C LTG: 202,204,218,219,220,221,222,223,224,225 1 20 4
1 20 1 LTG:205,206,207,208,209,210,211,212,213 2#12, #12G IN 1/2" C 1010 269 2#12, #12G IN 1/2" C LTG: 201,210A,214 1 20 2
# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
NOTES:
ENCLOSURE: NEMA 1 MCB RATING: 100 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: LS1 PHASE: 3 MAINS TYPE: MCB
LOCATION: ELECT 215 VOLTAGE: 480/277 Wye A.I.C. RATING: 22,000
PANELBOARD: LS3
DEMAND WITH EXPANSION: 15 A
TOTAL ESTIMATED DEMAND... 12 A
TOTAL CONNECTED CURRENT: 12 A
TOTAL ESTIMATED DEMAND LOAD: 4500 VA
TOTAL CONNECTED LOAD: 4500 VA
PANEL TOTALS
TOTAL AMPS: 28 A 10 A 2 A
TOTAL LOAD: 3200 VA 1100 VA 200 VA
23 0 -- SPACE 1 -- 24
21 0 -- SPACE 1 -- 22
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 20
17 -- 1 SPACE -- -- SPACE 1 -- 18
15 -- 1 SPACE -- -- SPACE 1 -- 16
13 -- 1 SPACE -- -- SPACE 1 -- 14
11 -- 1 SPACE -- -- SPACE 1 -- 12
9 -- 1 SPACE -- -- SPACE 1 -- 10
7 20 1 NAC: 137 2#10, #10G, IN 1/2" C 100 100 2#10, #10G IN 1/2" C ESR (BY DIV 14): 121 1 20 8
5 20 1 RSFACU: 214 2#10, #10G, IN 1/2" C 100 100 2#8, #10G, IN 3/4" C AMP: 137 1 20 6
3 20 1 RSFACU: 108 2#10, #10G IN 1/2" C 100 1000 2#8, #10G, IN 3/4" C FAC: 137 1 20 4
1 20 1 FACU / ACU: 137 2#10, #10G, IN 1/2" C 2000 1000 2#8, #10G, IN 3/4" C FAC: 137 1 20 2
# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
PROVIDE RED / LOCKABLE CIRCUIT BREAKERS FOR FIRE ALARM.
NOTES:
ENCLOSURE: NEMA 1
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 50 A
SUPPLY FROM: T-FP PHASE: 3 MAINS TYPE: MLO
LOCATION: ELECT 136 VOLTAGE: 208/120 Wye A.I.C. RATING: 10,000
PANELBOARD: FP
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
B
A S
E B
ID
U
P D
A T
E
/2 7/
U
P D
A T
E H
IG
H
M A
S T
V O
LT
A
G E
//1
5/
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
TI
C
N A
V A
L S
T A
T
IO
N N
O R
F O
L K
N
O R
F O
L K
V
A
AS NOTED
N E
W P
O R
T , R
H O
D E
IS
LA
N D
M
ID
L A
N T
D C
B L
N A
V A
L S
T A
T
IO
N N
E W
P O
R T
N O
A A
O M
A O
S H
IP
S U
P P
O R
T F
A C
IL
IT
Y R
E L O
C A
T
IO
N
1562331
RS/RC
EJA
DSN
04OCT2022
Timothy Calohan, PE, NOAA Senior Project Manager
N4008523R2527
E-770
B O
A T
R E
P A
IR
P A
N E
LB
O
A R
D S
C H
E D
U
LE
S
JC
12874309
JR BG
JAS
DEMAND WITH EXPANSION: 634 A
TOTAL ESTIMATED DEMAND... 528 A
TOTAL CONNECTED CURRENT: 530 A
TOTAL ESTIMATED DEMAND LOAD: 439193 VA
TOTAL CONNECTED LOAD: 440465 VA
PANEL TOTALS
TOTAL AMPS: 540 A 521 A 532 A
TOTAL LOAD: 149222 VA 144336 VA 146906 VA
41 0 -- SPACE 1 -- 42
39 0 -- SPACE 1 -- 40
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 38
35 20 1 SPARE 0 -- SPACE 1 -- 36
33 -- 1 SPACE -- -- SPACE 1 -- 34
31 -- 1 SPACE -- -- SPACE 1 -- 32
29 -- 1 SPACE -- -- SPACE 1 -- 30
27 20 1 SPARE 0 -- SPACE 1 -- 28
25 20 1 SPARE 0 0 SPARE 1 20 26
23 20 1 SPARE 0 10448 24
21 27712 10448 22
19 27712 10448
3#8, #10G IN 3/4"C DWH-4 3 50
100 3 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #21
27712 3048 18
15 27712 3048 16
13 27712 3048
3#12, #12G IN 1/2"C GANTRY CRANE: 100 3 20
100 3 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #21
27712 27712 12
9 20 1 EXTERIOR LIGHTING 2#12, #12G IN 1/2" C 70 27712 10
7 20 1 LTG: 100 2#12, #12G IN 1/2" C 312 27712
REFER TO ES101 FEEDER #21 CONEX SAFETY SWITCH 3 100
5 22562 27712 6
3 19922 27712 4
175 3 TRANSFORMER T-B
REFER TO SINGLE LINE
DIAGRAM
24566 27712
REFER TO ES101 FEEDER #21 CONEX SAFETY SWITCH 3 100
# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
1 - BID OPTION - BOAT REPAIR BUILDING.
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 800 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 800 A
SUPPLY FROM: 500 KVA XFMR PHASE: 3 MAINS TYPE: MCB
LOCATION: BOAT REPAIR VOLTAGE: 480/277 Wye A.I.C. RATING: 35,000
PANELBOARD: BHV
DEMAND WITH EXPANSION: 219 A
TOTAL ESTIMATED DEMAND... 183 A
TOTAL CONNECTED CURRENT: 186 A
TOTAL ESTIMATED DEMAND LOAD: 65778 VA
TOTAL CONNECTED LOAD: 67050 VA
PANEL TOTALS
TOTAL AMPS: 208 A 166 A 191 A
TOTAL LOAD: 24566 VA 19922 VA 22562 VA
41 0 -- SPACE 1 -- 42
39 0 -- SPACE 1 -- 40
30 3 SPD
PER MANUFACTURER'S
INSTRUCTIONS
0 -- SPACE 1 -- 38
35 -- 1 SPACE -- 0 SPARE 1 20 36
33 -- 1 SPACE -- 0 SPARE 1 20 34
31 20 1 TPM-8: 100 2#12, #12G IN 1/2" C 50 0 SPARE 1 20 32
29 20 1 BOATHOUSE MEDIA CONVERTER 2#12, #12G IN 1/2" C 50 0 SPARE 1 20 30
27 20 1 GATE OPERATOR - NORTH AND ACU 2#6, #6G IN 1" C 1250 0 SPARE 1 20 28
25 3602 552 26
23 3602 552 24
30 3 HAZMAT CONTAINER LOAD CENTER REFER TO ES101 FEEDER #21
3602 552
3#12, #12G IN 1/2" C OVERHEAD COILING DOOR 3 20
19 6004 552 20
17 6004 552 18
50 3 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #22
6004 552
3#12, #12G IN 1/2" C OVERHEAD COILING DOOR 3 20
13 6004 1500 14
11 6004 1500
2#12, #12G IN 1/2" C RACK C1: 100 2 20
50 3 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #22
6004 180 2#12, #12G IN 1/2" C TELECOM REC: 100 1 20 10
7 30 1 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #23 3600 1800 2#12, #12G IN 1/2" C AIR COMPRESSOR REC: 100 1 20 8
5 30 1 CONEX SAFETY SWITCH REFER TO ES101 FEEDER #23 3600 696 2#12, #12G IN 1/2" C EF-7: 100 1 20 6
3 20 1 RECS GFI: 100 2#10, #10G IN 1/2" C 540 1236 2#12, #12G IN 1/2" C UH-12: 100 1 20 4
1 20 1 RECS GFI: 100 2#12, #12G IN 1/2" C 540 360 2#10, #10G IN 1/2" C OUTDOOR REC 1 20 2
# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #
1 - BID OPTION - BOAT REPAIR BUILDING.
2 - BID OPTION - HAZMAT CONTAINER.
NOTES:
ENCLOSURE: NEMA 4XSS MCB RATING: 400 A
MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A
SUPPLY FROM: T-B PHASE: 3 MAINS TYPE: MCB
LOCATION: SM BOAT REPAIR VOLTAGE: 120/208 Wye A.I.C. RATING: 18,000
PANELBOARD: BLV
1 1
SHEET NOTES
1. PANELS BHV / BLV MUST BE NEMA 4XSS IF THE BID OPTION IS NOT
EXECUTED AND THE PANELS AND TRANSFORMER REMAIN OUTDOORS. IF
THE BID OPTION IS EXECUTED, LOCATE THE PANELS AND TRANSFORMER
INSIDE THE BUILDING IN NEMA 1 ENCLOSURES.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
U
P D
A T
E D
W
IR
E S
IZ
E
S
/1 5/
| ES101 - ELECTRICAL & TELECOM SITE PLAN - AREA 1 |
| ES102 - ELECTRICAL & TELECOM SITE PLAN - AREA 2 |
| ES103 - ELECTRICAL & TELECOM SITE PLAN - AREA 3 |
| ES105 - ELECTRICAL & TELECOM SITE PLAN - AREA 5 |
| EL501 - LIGHTING DETAILS |
| EP114 - PIER -POWER PLAN -AREA D |
| EP115 - PIER -POWER PLAN -AREA E |
| EP116 - PIER -POWER PLAN -AREA F |
| EP507 - POWER DETAILS |
| E-710 - PIER -PANELBOARD SCHEDULES |
| E-711 - PIER -PANELBOARD SCHEDULES |
| E-745 - ADMIN / WAREHOUSE -PANELBOARD SCHEDULES |
| E-770 - BOAT REPAIR -PANELBOARD SCHEDULES |
| 2023-06-15T16:10:24-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:28-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:29-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:29-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:30-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:30-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:32-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:32-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:32-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:33-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:33-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:34-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-15T16:10:35-0400 | |
| Boris Goli | |
| I am signing to certify the authenticity of this document. |
| 2023-06-16T10:44:04-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:28-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:28-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:29-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:29-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:30-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:30-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:31-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:31-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:32-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:32-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:33-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:33-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:44:47-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:01-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:02-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:02-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:03-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:03-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:04-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:05-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:05-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:06-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:06-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2023-06-16T10:45:07-0400 | |
| Norfolk, VA | |
| James E. Donahue, R.A. | |