FIRE ALARM / MNS LEGEND GENERAL NOTES:AUDIBLE DESIGN CRITERIA:ABBREVIATIONS:
ACH AIR CHANGES PER HOUR
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
ATCT AIR TRAFFIC CONTROL TOWER
AWG AMERICAN WIRE GAGE
CD CANDELA
CFM CUBIC FEET PER MINUTE
CIS COMMON INTELLIGIBILITY SCALE
CO CARBON MONOXIDE
DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER
DB DECIBEL
DBA DECIBEL A-WEIGHTED
DDC DIRECT DIGITAL CONTROL
DPDT DOUBLE POLE DOUBLE THROW
EMCS ENERGY MONITORING AND CONTROL SYSTEM
EPO EMERGENCY POWER OFF
FA FIRE ALARM
FDC FIRE DEPARTMENT CONNECTION
FM FM GLOBAL
FX FIRE SUPPRESSION
GFGI GOVERNMENT FURNISHED GOVERNMENT INSTALLED
HZ HERTZ
IAW IN ACCORDANCE WITH
IDC INITIATING DEVICE CIRCUIT
IFR INSTRUMENT FLIGHT RULES
MNS MASS NOTIFICATION SYSTEM
NAC NOTIFICATION APPLIANCE CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
RF RADIO FREQUENCY
SLC SIGNALING LINE CIRCUIT
TYP TYPICAL
UL UNDERWRITERS LABORATORY
WP WEATHER PROOF (NEMA 250, TYPE 3R)
S = SUPPLY
S P
CEILING MOUNTED SMOKE DETECTOR
S S
IN-DUCT PHOTOELECTRIC SMOKE DETECTOR
1. PROVIDE AUDIBLE NOTIFICATION APPLIANCES AS INDICATED TO
ACCOMPLISH THE FOLLOWING DESIGN CRITERIA WITH ALL DOORS,
FIRE SHUTTERS, AND WINDOWS CLOSED. WHERE THIS DESIGN
CRITERIA IS NOT ACCOMPLISHED DURING ACCEPTANCE TESTING,
PROVIDE ADDITIONAL DEVICES TO MEET THE MINIMUM DESIGN CRITERIA
WITHOUT EXCEEDING THE LIMITATIONS OF THE FACU/ACU, NAC,
OR AMP. (INCLUSIVE OF PRESCRIBED SAFETY FACTORS).
2. PROVIDE A QUANTITY OF SPEAKERS IN EACH ROOM/AREA TO
ACHIEVE THE REQUIRED SOUND POWER AND INTELLIGIBILITY
OUTLINED IN THESE CONTRACT DOCUMENTS. DEPENDING ON
THE QUALITY OF SPEAKER USED, SEVERAL SPEAKERS TAPPED AT A
LOWER SETTING MAY BE REQUIRED TO ACHIEVE THE PRESCRIPTIVE
CIS SCORE. THE QUANTITY OF SPEAKERS REQUIRED MAY DIFFER FROM
THE QUANTITY SHOWN ON THE PLANS DEPENDING ON SPEAKER QUALITY
AND/OR WATTAGE TAPS. PROVIDE QUANTITY OF SPEAKERS NECESSARY
TO COMPLY WITH THE AUDIBLE DESIGN CRITERIA.
3. IN SLEEPING ROOMS, PROVIDE A MINIMUM SOUND POWER OF 75 DBA
AND 15 DBA OVER THE AVERAGE AMBIENT SOUND LEVEL AS MEASURED
AT THE PILLOW. PROVIDE A PRE-TONE SIGNAL PRECEDING THE VOICE
MESSAGE CAPABLE OF A 520 HZ SQUARE WAVE +/- 10%. PROVIDE A
MULTI-CHANNEL ACU CAPABLE OF SIMULTANEOUSLY PROVIDING THE
520 HZ PRE-TONE IN THE SLEEPING ROOMS, AND OTHER PRE-TONES
THROUGHOUT THE REMAINDER OF THE BUILDING.
4. FOR NON-SLEEPING ROOM AREAS: PROVIDE A MINIMUM SOUND POWER
OF 70 DBA AND 15 DBA OVER THE AVERAGE AMBIENT SOUND LEVEL OR
5 DBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
LEAST 60 SECONDS, WHICHEVER IS GREATER, AT THE MOST REMOTE
LOCATION WITHIN THE ROOM/AREA MEASURED AT 5 FT AFF. MEASURE
THE SOUND POWER OFF THE TEMPORAL THREE TONE PATTERN. THE
FOLLOWING CRITERIA WILL BE USED FOR REVIEW AND APPROVAL OF
SHOP DRAWINGS.
A. REDUCE THE SOUND POWER BY 6 DB EACH TIME THE DISTANCE
BETWEEN THE APPLIANCE AND THE LISTENER IS DOUBLED.
STARTING DISTANCE IS PER MANUFACTURER'S DATASHEET,
TYPICALLY 10 FT.
B. REDUCE THE SOUND POWER IN ACCORDANCE WITH THE
MANUFACTURER'S DATASHEET FOR SOUND POWER
DISTRIBUTION NOT PERPENDICULAR TO THE FACE OF THE
APPLIANCE. REFER TO MANUFACTURER'S TYPICAL SOUND
OUTPUT DISTRIBUTION DIAGRAM.
C. IN LIEU OF THE MANUFACTURER'S PUBLISHED DB LOSS, ASSUME
A MINIMUM 15 DB LOSS THROUGH A STANDARD CLOSED DOOR.
5. PROVIDE EXTERIOR SPEAKERS MEETING A MINIMUM SOUND POWER
OF 70 DBA AND 15 DBA OVER THE AVERAGE AMBIENT SOUND LEVEL OR
5 DBA ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
LEAST 60 SECONDS, WHICHEVER IS GREATER, WITHIN A 16 FT RADIUS OF
DOORS WHERE EXTERIOR SPEAKERS ARE SHOWN MEASURED AT 5FT
ABOVE GRADE. MEASURE THE SOUND POWER OFF THE TEMPORAL
THREE TONE PATTERN. THE AVERAGE AMBIENT SOUND LEVEL IS THE
ROOT MEAN SQUARE, A-WEIGHTED, SOUND PRESSURE LEVEL
MEASURED OVER THE DURATION THE BUILDING IS NORMALLY
OCCUPIED.
6. MEET THE FOLLOWING INTELLIGIBILITY CRITERIA:
A. ACHIEVE A CIS SCORE OF 0.70 IN EACH ROOM MEASURED AT
5 FT AFF.
B. A LESSER CIS IS PERMITTED IN AREAS OF THE BUILDING WITH
EXCESSIVE SOUND REFLECTIONS, SUCH AS ROOMS WITH HARD
SURFACES (METAL, TILE, OR CONCRETE), WHERE THE OCCUPANT
CAN WALK NO MORE THAN 33 FT TO A LOCATION THAT ACHIEVES
THE MINIMUM CIS. THIS AREA MUST BE READILY ACCESSIBLE,
WITHOUT REQUIRING THE OCCUPANT TO WALK THROUGH A
SECURED DOOR/AREA OR EXIT THE BUILDING.
C. A LESSER CIS IS PERMITTED IN NORMALLY UNOCCUPIED ROOM
OF THE BUILDING, WHERE THE OCCUPANT CAN WALK NO MORE
THAN 50 FT TO A LOCATION THAT ACHIEVES THE MINIMUM CIS.
THIS AREA MUST BE READILY ACCESSIBLE, WITHOUT REQUIRING
THE OCCUPANT TO WALK THROUGH A SECURED DOOR/AREA OR
EXIT THE BUILDING. NORMALLY UNOCCUPIED ROOMS ARE
CONSIDERED TO BE STORAGE ROOMS < 100 SF, MECHANICAL /
ELECTRICAL ROOMS, COMMUNICATION CLOSETS, AND FIRE
PROTECTION ROOMS.
1. STROBES SHOWN ON THE DRAWINGS ARE INTENDED TO SHOW ROOMS
AND AREAS REQUIRING COVERAGE AND MAY NOT SHOW ALL APPLIANCES.
DEPENDING ON THE CANDELA RATINGS OF THE STROBES PROVIDED, THE
QUANTITY OF STROBES REQUIRED MAY DIFFER FROM THE QUANTITY
SHOWN ON THE PLANS.
2. SPACE STROBES IN ACCORDANCE WITH THE CRITERIA OUTLINED IN NFPA
72, UNLESS OTHERWISE NOTED.
3. COLORED STROBE CANDELA SETTINGS MUST BE INCREASED
ACCORDINGLY FOR THE MANUFACTURER'S DERATING FACTOR TO
ACHIEVE THE SAME SPACING AS CLEAR STROBES OF THE SAME MODEL.
4. IN SLEEPING ROOMS, PROVIDE A STROBE WITHIN 16 FT OF THE PILLOW.
PROVIDE A 177 CD STROBE WHERE INSTALLED WITHIN 24 INCHES OF THE
CEILING,OR A 110 CD STROBE WHERE INSTALLED GREATER THAN 24
INCHES FROM THE CEILING.
1. PROVIDE AN ADDRESSABLE COMBINED FIRE ALARM / MASS
NOTIFICATION SYSTEM FOR EACH BULDING AS INDICATED ON THE
DRAWINGS.
2. COORDINATE ALL REQUIRED SYSTEMS TO THE SATISFACTION OF THE
ENGINEER AND AUTHORITY HAVING JURISDICTION. ANY
DEFICIENCIES, INCONSISTENCIES, OR POORLY COORDINATED
INSTALLATIONS MUST BE CORRECTED BY THE CONTRACTOR AT NO
ADDITIONAL COST.
3. THE FIRE ALARM DRAWINGS ARE SCHEMATIC IN NATURE AND SHOW A
MINIMAL QUANTITY OF DEVICES. DETERMINE THE FINAL QUANTITY
AND LOCATION OF ALL DEVICES IN ACCORDANCE WITH THE
SPECIFICATIONS, CONTRACT DRAWINGS, AND MANUFACTURER'S
WRITTEN RECOMMENDATIONS TO BE COMPLIANT WITH ALL
APPLICABLE CODES AND STANDARDS. PROVIDE ADDITIONAL DEVICES
WHEN REQUIRED FOR A FULLY FUNCTIONING FIRE ALARM SYSTEM AS
REQUIRED BY NFPA 72, UFC 3-600-01, UFC 4-133-01, AND UFC 4-021-01.
4. CONCEAL ALL CONDUITS IN WALLS OR ABOVE CEILINGS UNLESS
OTHERWISE INDICATED. EXCEPTION: CONDUIT IS ALLOWED TO BE
SURFACE MOUNTED ON WALLS AND CEILINGS IN UNFINISHED AREAS
(SUCH AS MECHANICAL ROOM, ELECTRICAL ROOM, FIRE PROTECTION
ROOM). WHERE A CONDUIT SUPPLIES A DEVICE NOT MOUNTED
DIRECTLY ON THE WALL OR CEILING, ROUTE THE CONDUIT AS A
SINGLE PENDENT DROP TO EACH DEVICE FROM THE CEILING
SURFACE ABOVE. DO NOT TRAPEZE CONDUIT ACROSS AN OPEN SPACE.
5. ALL FIRE ALARM JUNCTION BOXES, COVERS AND CONDUITS IN
UNFINISHED AREAS ARE TO BE PROVIDED PRE-FINISHED RED FROM THE
FACTORY. PAINT EXPOSED CONDUIT AND JUNCTION BOXES IN FINISHED
AREAS TO MATCH ADJACENT SPACES WITH JUNCTION BOXES INSIDE
COVER LABELED, "FIRE ALARM".
6. PROVIDE CONDUIT IN ACCORDANCE WITH THE REQUIREMENTS OF
THE ELECTRICAL SPECIFICATIONS, UNLESS OTHERWISE NOTED.
SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC SUCH AS
MAXIMUM 10 FT SUPPORT INTERVALS AND 3 FT FROM A
TERMINATION. TENSION ONLY HANGERS ARE NOT PERMITTED
SUCH AS BATWINGS. FLEXIBLE CONDUIT IS ONLY PERMITTED WHEN
CONNECTING TO THE FOLLOWING DEVICES AND APPLIANCES:
DEVICES LOCATED ON FIRE SUPPRESSION EQUIPMENT SUCH AS
FLOW SWITCHES, AND TAMPER SWITCHES; DEVICES AND APPLIANCES
LOCATED IN REMOVABLE CEILING TILES, OR WHERE SPECIFICALLY
NOTED.
7. PROVIDE CONDUCTOR SIZING NOT LESS THAN 18 AWG FOR SLC.
PROVIDE CONDUCTOR SIZING NOT LESS THAN 16 AWG FOR NAC,
SPEAKER CIRCUITS, AND IDC, PER UFC 3-600-01. CONSISTENTLY COLOR
COORDINATE ALL CONDUCTORS THROUGH THE SYSTEM IN RELATION TO
DEVICES THEY FEED SUCH AS SLC - BLACK/RED, STROBE - YELLOW/BLUE.
PROVIDE ADDRESSABLE SLC CIRCUITS WITH SHIELDED CONDUCTORS,
WHERE THE SHIELDING IS GROUNDED AT ONE END WHERE REQUIRED BY
THE MANUFACTURER. PROVIDE ALL CIRCUITS WITH LABELING AT THE
POINT OF TERMINATION SUCH AS SLC 1, NAC 8, IDC 4.
8. RUN CONDUCTORS FROM DEVICE TO DEVICE WITHOUT SPLICES. WIRE
NUTS ARE PROHIBITED. UTILIZE TERMINAL STRIPS WHERE
CONDUCTORS CANNOT BE DIRECTLY TERMINATED AT THE DEVICE
SUCH AS PIGTAILS OFF A HEAT DETECTOR.
9. DO NOT USE FIRE ALARM EQUIPMENT PANELS AS RACEWAY FOR
ROUTING POWER WIRING OR LOW VOLTAGE WIRING. ONLY ROUTE
WIRING TERMINATING WITHIN THE PANEL INTO THE PANEL. PROVIDE
1/4 INCH SEPARATION BETWEEN POWER-LIMITED FIRE ALARM
CIRCUITS AND POWER CIRCUITS.
10. MOUNTING DEVICES IN THE FACU/ACU, INCLUDING ANY SUBPANELS
SUCH AS AMP, NAC, AND FAC, WHICH ARE NOT UL LISTED OR FM
APPROVED AS PART OF THE UNIT IS PROHIBITED.
11. PROVIDE SURGE SUPPRESSORS TO PROTECT ALL POWER SUPPLY
CIRCUITS TO THE FACU/ACU, INCLUDING ANY SUBPANELS SUCH AS
AMP, NAC, FAC, AND ALL FIRE ALARM CIRCUITS LEAVING OR ENTERING
THE BUILDING. DEVICES AND APPLIANCES MOUNTED DIRECTLY ON THE
EXTERIOR OF THE BUILDING SUCH AS WALL MOUNTED EXTERIOR
SPEAKERS DO NOT REQUIRE SUPPRESSORS. MOUNT SURGE
SUPPRESSORS IN A SEPARATE ENCLOSURE, UNLESS IT IS UL LISTED
OR FM APPROVED AND INSTALLED IN THE CONTROL UNIT BY THE
FACTORY.
12. INSTALL FIRE ALARM BATTERIES IN THE ENCLOSURE OF THE
DEVICE/UNIT IT SUPPORTS SUCH AS FACU/ACU ENCLOSURE OR IN AN
INDEPENDENT DEDICATED ENCLOSURE.
13. PROVIDE GAIN CONTROL ON ALL MICROPHONES.
14. WHERE STROBES AND SPEAKERS ARE REQUIRED IN THE SAME AREA,
COMBINED APPLIANCES ARE PERMITTED.
15. REFER TO SHEET A-535 FOR TYPICAL FIRE-RATED PENETRATION DETAILS.
WF WATER FLOW DETECTOR / SWITCH (PROVIDED BY DIVISION 21)
F MANUAL FIRE ALARM PULL STATION
NAC NOTIFICATION CIRCUIT POWER BOOSTER
LOC LOCAL OPERATING CONSOLE
FPC FIRE PUMP CONTROLLER
FAC FIRE ALARM COMMUNICATOR (e.g. RF TRANSMITTER)
FAA FIRE ALARM ANNUNCIATOR
VS VALVE SUPERVISORY SWITCH (PROVIDED BY DIVISION 21)
SS SURGE SUPPRESSOR
PA PUBLIC ADDRESS SYSTEM
AMP AMPLIFIER
ASD AIR SAMPLING DETECTOR
HORN / STROBE COMBINATION
S SPEAKER
SPEAKER / STROBE COMBINATION
CLEAR STROBE
AOM ADDRESSABLE OUTPUT CONTROL MODULE
AIM ADDRESSABLE INPUT MONITOR MODULE
ANTENNA
CO
CARBON MONOXIDE DETECTOR
RL NON-ADDRESSABLE OUTPUT RELAY
IM ISOLATION MODULE
BATT SECONDARY POWER SUPPLY (BATTERY)
GROUND
VISIBLE DESIGN CRITERIA:
DACT DIGITAL ALARM COMMUNICATOR TRANSMITTER
B = BLUE
R = RED
XX = CANDELA RATING
ET EMERGENCY TEXTUAL VISIBLE DISPLAY
FACU/ACU COMBINATION FIRE ALARM CONTROL UNIT AND AUTONOMOUS CONTROL UNIT
ST SHUNT TRIP BREAKER (BY DIVISION 26)
ESR ELEVATOR SYSTEM RECALL PANEL (BY DIVISION 14)
P = PHOTOELECTRIC
L = LASER LIGHT SOURCE
(PROVIDED BY DIVISION 26)
ROOM TAG
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL TAG
ROOM NAME
ROOM NUMBER
? INTERIOR ELEVATION
TAG
INTERIOR ELEVATION NUMBER
SHEET WHERE DRAWN
DETAIL NUMBER
SCALE
SHEET
REFERENCED
FROM
EXTERIOR ELEVATION
TAG
ELEVATION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
WALL / PARTIAL
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
GENERAL PROJECT SYMBOLS
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
BUILDING
NEW WORK
KEYNOTE TAG
KEYNOTE NUMBER
PLAN
NORTH
SCALE
TRUE NORTH
SHEET
REFERENCED
FROM
(PROVIDED BY DIVISION 21)
FAC
MNS
MNS TRANSCEIVER (GFGI)
W = WALL MOUNTED
WP = WALL MOUNTED WEATHER PROOF
XX = CANDELA RATING
W = WALL MOUNTED
X
XX
XX
W
RTS
M MOTOR OPERATED CONTROL DAMPER (PROVIDED BY DIVISION 23)
BD
VD MANUAL BALANCING DAMPER (PROVIDED BY DIVISION 23)
FSD
BAROMETRIC RELIEF DAMPER (PROVIDED BY DIVISION 23)
FIRE/SMOKE DAMPER (PROVIDED BY DIVISION 23)
REMOTE TEST STATION
TWO-WAY TELEPHONE COMMUNICATION SYSTEM RECEIVER
MD MAINTENANCE/DISCONNECT SWITCH
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:4
A
M
FA001
F
IR
E A
LA
R
M N
O
TE
S , L
E G
E N
D A
N D
A B
B R
E V
IA
TI
O N
S
WRM
12801619
APL KPZ
1596300
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
F
F
F A
C U
/A C
U
S L
S P
S P
WF VS
V S2
S P
S P 3
S P S
P
COMM
STAIR
TOILET / SHOWER
WX OIC
WX FLOOR
WX SUPERVISOR
WX SNCOIC
ASOS
WX SIPR
119 ENTRY
VESTIBULE
WOMEN'S
MEN'S
MOTHERS RM
FLIGHT PLANNING ROOM
QUIET
CORRIDOR
ADMIN STOR
JANITOR
TOILET / SHOWER
STAIR
ODO
125F/C CIV
F/C SNCOIC
F/C
ELEVATOR
ELEV EQUIP
BUNK ROOM
BUNK / LOCKER
BUNK ROOM
BUNK ROOM
S P
F
WF
VS
W
W
S S
S
S
S
S
S
S
S
177177
S W
P
S
WP
S WP
M A
T C
H L
IN
E S
E E
S H
E E
T F
A
MATCHLINE SEE SHEET FA102
S
30W
W
15 15
S
F A
C
F A
C
M N
S
AOM 5
S L
MD
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA101
A
IR
O P
S
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
T
IO
N P
LA
N
F
IR
S
T F
LO
O
R
A R
E A
A
WRM
12801620
APL KPZ
1596300
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR ELEVATOR EQUIPMENT
ROOM. FLOW SWITCH MUST BE DPDT WITH ZERO TIME DELAY FOR SHUNT
TRIP OF THE ELEVATOR UPON SPRINKLER FLOW IN THE ELEVATOR
EQUIPMENT ROOM. REFER TO FIRE SUPPRESSION DRAWINGS FOR
QUANTITY AND / OR LOCATIONS OF DEVICE(S).
2. MONITOR TAMPER SWITCH FOR ELEVATOR PIT SPRINKLER. REFER TO FIRE
SUPPRESSION DRAWINGS FOR QUANTITY AND / OR LOCATIONS OF
DEVICE(S).
3. REFER TO FA001 SLEEPING ROOM CRITERIA.
4. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM.
ACTUATION OF FLOW SWITCH MUST REMOVE POWER TO ELECTRONIC
EQUIPMENT IN THIS ROOM PER UFC 4-133-01. PROVIDE SUPERVISED
MAINTENANCE DISCONNECT SWITCH TO PREVENT SHUNT TRIP DURING
WATER FLOW SWITCH TESTING.
5. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
6. PROVIDE EARLY WARNING LASER SMOKE DETECTOR WITH TWO ALARM
THRESHOLD LEVELS. FIRST THRESHOLD LEVEL MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. SECOND THRESHOLD LEVEL
MUST INITIATE NOTIFICATION APPLIANCES IN THE ENTIRE FACILITY.
GENERAL NOTES
WORK NOTES
SCALE IN FEET
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0" A1
AIR OPS - FIRE ALARM AND MASS NOTIFICATION PLAN - FIRST FLOOR -
AREA A
PLAN
NORTH
KEY PLAN
A
B
C
X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
F
F
S S
S S
F
AMP
NAC
WF
VS
WP
CO
WEAPON STOR
AIRFIELD LIGHTS
BASE NODE
MECHANICAL
BASH
CORRIDOR
WX CLASSROOM
ELEC
UPS
F
WF
VS 75
S
S
S
S
WP
S
WP
MATCHLINE SEE SHEET FA101
S S
S
F
WF
VS
AOM 7
AOM
S L
S L
S P
MD
BASE NODE VAULT
S L
S L
S
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA102
A
IR
O P
S
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
IR
S
T F
LO
O
R
A R
E A
B
WRM
12801621
APL KPZ
1596300
1/8" = 1'-0" A1
AIR OPS - FIRE ALARM AND MASS NOTIFICATION PLAN - FIRST FLOOR -
AREA B
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. WP HORN/STROBE ABOVE FDC.
3. QUANTITY BY CONTRACTOR'S DESIGN TO MEET DESIGN CRITERIA.
COORDINATE LOCATIONS WITH ELECTRICAL EQUIPMENT.
4. PROVIDE SUPPLY SIDE DUCT SMOKE DETECTORS FOR AHU-A1 AND DOAH-
A1. REFER TO MECHANICAL SHEETS FOR EXACT LOCATION.
5. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM AND
VAULT. ACTUATION OF FLOW SWITCH MUST REMOVE POWER TO
ELECTRONIC EQUIPMENT IN THIS ROOM AND VAULT PER UFC 4-133-01.
PROVIDE SUPERVISED MAINTENANCE DISCONNECT SWITCH TO PREVENT
SHUNT TRIP DURING WATER FLOW SWITCH TESTING.
6. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR UPS ROOM. ACTUATION
OF FLOW SWITCH MUST REMOVE POWER TO BATTERY CHARGERS IN THIS
ROOM PER UFC 3-520-05.
7. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
8. PROVIDE EARLY WARNING LASER SMOKE DETECTOR WITH TWO ALARM
THRESHOLD LEVELS. FIRST THRESHOLD LEVEL MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. SECOND THRESHOLD LEVEL
MUST INITIATE NOTFIFICATION APPLIANCES IN THE ENTIRE FACILITY.
PLAN
NORTH
KEY PLAN
A
B
CSCALE IN FEET
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0" C1
AIR OPS - FIRE ALARM AND MASS NOTIFICATION PLAN - BASE NODE
VAULT
SCALE IN FEET
0 4' 8' 16'
PLAN
NORTH
GENERAL NOTES
WORK NOTES X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
FF
F
F
CO
KITCHEN / BREAK
VESTIBULE
PRE-SCREEN
TOILET / SHOWER
LOUNGE
LOCKER
MEN
WOMEN
WOMEN
MEN
STORAGE BAY
VAL SUPERVISOR
DISPATCH
BREAK
POST-SCREEN
MECH
1 S S
15 15 15
30 30
S S
S
S WP
S WP S WP
S
WP
M A
T C
H L
IN
E S
E E
S H
E E
T F
A
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA103
A
IR
O P
S
F
IR
E A
LA
R
M A
N D
M A
S S
N O
T
IF
IC
A
TI
O
N P
LA
N
F
IR
S
T F
LO
O
R
A R
E A
C
WRM
12801622
APL KPZ
1596300
1/8" = 1'-0" A1
AIR OPS - FIRE ALARM AND MASS NOTIFICATION PLAN - FIRST FLOOR -
AREA C
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1. PROVIDE SUPPLY SIDE DUCT SMOKE DETECTORS FOR AHU-A2. REFER TO
MECHANICAL SHEETS FOR EXACT LOCATION.
PLAN
NORTH
KEY PLAN
A
B
C
SCALE IN FEET
0 4' 8' 16'
PLAN
NORTH
GENERAL NOTES
WORK NOTES X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
S P
CONFERENCE ROOM
RECEPTION
CORRIDOR
ELEVATOR
203 STORAGE
ATCO
NAVAIR EASU
STAIR
FOD CELL
AOPS
OSPO
MGYSGT
CHIEF
STAIR
MEN'S
WOMEN'S
COMM
JAN
KITCHEN
210A
EQUIP. CLOSET
201A
F
WF
VS
S S
SSS
S S
S
S
S
S
S
W
W
15 15
S P
AOM
S L
SS
S 5
5 5
MD
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:4
:0
A
M
FA104
A
IR
O P
S
F
IR
E A
LA
R
M A
N D
M A
S S
N O
T
IF
IC
A
TI
O
N P
LA
N
S
E C
O N
D F
LO
O
R
WRM
12801623
APL KPZ
1596300
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM.
ACTUATION OF FLOW SWITCH MUST REMOVE POWER TO ELECTRONIC
EQUIPMENT IN THIS ROOM PER UFC 4-133-01. PROVIDE SUPERVISED
MAINTENANCE DISCONNECT SWITCH TO PREVENT SHUNT TRIP DURING
WATER FLOW SWITCH TESTING.
2. SMOKE DETECTOR FOR RELEASE OF SMOKE SHUTTER.
3. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
4. PROVIDE EARLY WARNING LASER SMOKE DETECTOR WITH TWO ALARM
THRESHOLD LEVELS. FIRST THRESHOLD LEVEL MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. SECOND THRESHOLD LEVEL
MUST INITIATE NOTIFICATION APPLIANCES IN THE ENTIRE FACILITY.
5. PROVIDE DUCT SMOKE DETECTOR FOR SMOKE DAMPER ACTIVATION.
3/32" = 1'-0" A1
AIR OPS - FIRE ALARM AND MASS NOTIFICATION PLAN - SECOND
FLOOR
SCALE IN FEET
0 8' 16' 24'
PLAN
NORTH
GENERAL NOTES
WORK NOTES X
PLAN
NORTH
KEY PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
F F F F
F
F
F
S S
FACU/ACU
F
CO
F
F
E T
WF
VS
WP
ASD
S P
A M
P
N A
C
S P
L O
C
L O
C
MECHANICAL
UPS
ELECTRICAL
ATC IFR ROOM
ATCM SERVER
ATCM SUPPLY BAY
ATCM HAZMAT STORAGE
124 SUPPLY DESK
SET
VESTIBULE
COMM
ATCM UNION OFFICE
ATCM-SNOIC
ATCM-OIC
ATCFO
ATC SNCOIC
ATC TRAINING OFFICE
ATC ADMIN STORAGE
ATCM STORAGE
ATC UNION OFFICE
TEST EQUIP.
CORRIDOR
MENS
MOTHERS ROOM
WOMEN
FWO
STARS SIMULATOR
STORAGE
JANITOR
ATC CONFERENCE ROOM
ATCM CLASSROOM
130ATCM BREAK ROOM
KITCHEN
ATC BREAK ROOM
F
LOCKERS
F
S L
S S 5
WF
VS
WF
VS
WF VS
ENTRANCE
OFFICE/OPS
OFFICE
RADIO STORAGE
CORRIDOR
WOMEN
MEN
EQUIPMENT ROOM
RANGE CONTROL FACILITY
OFFICE
OFFICE
BREAK ROOM
OPEN OFFICE
STORAGE
JANITOR
OFFICE
OFFICE
OFFICE
OFFICE
CLASSROOM
STORAGE
ATCM EQUIPMENT
S
S
S
S
SS
S
S
S
S
S S
SS
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
S S
SS
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
S S
SS
S
S
S
S
S
S
S
S
SSS
S
S
S S
S
SS
S
S
S
30 30
30 30
30 30
30 30
15 15
WPWPWP
WP
S
WF
VS
FAC MNS
AOM
AOM
A O
M
AOM
FAC
ET
S L
S L
R R
75 75
1 2 2.7 3 4 4.7 5 6 7 8
A
B
C
D
E
F
S P
S P
S P
S P
S P
S P
S P
S P
MD
MD
MD
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-R A
N G
E -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:3
A
M
FA111
M
TR
A C
O N
F
IR
E
A
LA
R M
A N
D M
A S
S N
O
TI
F
IC
A T
IO
N
P
LA
N
WRM
12801624
APL KPZ
1596300
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. WP HORN/STROBE ABOVE FDC.
3. QUANTITY BY CONTRACTOR'S DESIGN TO MEET DESIGN CRITERIA.
COORDINATE LOCATIONS WITH ELECTRICAL EQUIPMENT.
4. PROVIDE PRIVATE MODE NOTIFICATION APPLIANCES PER NFPA 72 IN THIS
AREA.
5. PROVIDE SUPPLY SIDE DUCT SMOKE DETECTOR FOR AHU-M1 AND DOAH-
M1. REFER TO MECHANICAL SHEETS FOR EXACT LOCATION.
6. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM.
ACTUATION OF FLOW SWITCH MUST REMOVE POWER TO ELECTRONIC
EQUIPMENT IN THIS ROOM PER UFC 4-133-01. PROVIDE SUPERVISED
MAINTENANCE DISCONNECT SWITCH TO PREVENT SHUNT TRIP DURING
WATER FLOW SWITCH TESTING.
7. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR UPS ROOM. ACTUATION
OF FLOW SWITCH MUST REMOVE POWER TO BATTERY CHARGERS IN THIS
ROOM PER UFC 3-520-05.
8. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
9. PROVIDE EARLY WARNING LASER SMOKE DETECTOR WITH TWO ALARM
THRESHOLD LEVELS. FIRST THRESHOLD LEVEL MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. SECOND THRESHOLD LEVEL
MUST INITIATE NOTFIFICATION APPLIANCES IN THE ENTIRE FACILITY.
PROVIDE BOTH CEILING LEVEL AND UNDERFLOOR SMOKE DETECTION
(WHERE APPLICABLE) FOR ROOM.
10. PROVIDE AIR SAMPLING SMOKE DETECTOR WITH FOUR ALARM THRESHOLD
LEVELS. ALERT, ACTION, AND FIRE 1 LEVELS MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. FIRE 2 LEVEL MUST INITIATE
NOTFIFICATION APPLIANCES IN THE ENTIRE FACILITY. PROVIDE BOTH
CEILING LEVEL AND UNDERFLOOR SMOKE DETECTION FOR ROOM.
MAXIMUM COVERAGE AREA PER PORT MUST BE 200 SF AND MAXIMUM
TRANSPORT TIME FROM MOST REMOTE PORT TO THE DETECTION UNIT
MUST NOT EXCEED 60 SECONDS.
3/32" = 1'-0" A1
MTRACON - FIRE ALARM AND MASS NOTIFICATION PLAN
GENERAL NOTES
WORK NOTES
SCALE IN FEET
0 8' 16' 24'
PLAN
NORTH
X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
F
F A
C U
/A C
U
F
S P
F
CO
S P
LO
CFAA
N A C
A M
P
WP
S P
FP
C
V
SW
F
A B C
ELECTRICAL
MECHANICAL
FP
CORRIDOR
STAIRS
EMERGENCY COMMAND CENTER
JANITOR
COMM
VESTIBULE
WF
VS5
S P
WP
W
S
S
S
S
S
S
FAC
FAC
MNS
AOM
S L
S
L
AOM AIM AIMRL
S S
R
TS
AOM AIM
PS
AOM AIM
PS
AOM AIM
AIM
RL 12
AOM AIM AIM
RL 12
6.5
F.1
H
S P
S
S
ELEVATOR
AOM AIM AIMRL 8
AOM AIM AIMRL 8
AOM AIM
AIM
RL 12
MD
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:4
A
M
FA121
A
TC
T
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
LO
O
R
WRM
12801625
APL KPZ
1596300
GENERAL NOTES
WORK NOTES
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. MONITOR FIRE PUMP CONTROLLER. REFER TO FIRE ALARM MATRIX FOR
SIGNALS TO BE MONITORED.
3. WP HORN/STROBE ABOVE FDC.
4. QUANTITY BY CONTRACTOR'S DESIGN TO MEET DESIGN CRITERIA.
5. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM.
ACUTATION OF FLOW SWITCH MUST REMOVE POWER TO ELECTRONIC
EQUIPMENT IN THIS ROOM PER UFC 4-133-01. PROVIDE SUPERVISED
MAINTENANCE DISCONNECT SWITCH TO PREVENT SHUNT TRIP DURING
WATER FLOW SWITCH TESTING.
6. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
7. PROVIDE EARLY WARNING LASER SMOKE DETECTOR WITH TWO ALARM
THRESHOLD LEVELS. FIRST THRESHOLD LEVEL MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. SECOND THRESHOLD LEVEL
MUST INITIATE NOTFIFICATION APPLIANCES IN THE ENTIRE FACILITY.
8. PROVIDE ADDRESSABLE MODULES AND RELAY FOR MONITORING AND
CONTROL OF FIRE/SMOKE DAMPER. SEE MECHANICAL SHEET MH121 FOR
LOCATION OF FIRE/SMOKE DAMPER PROVIDED BY DIVISION 23.
COORDINATE LOCATION OF ADDRESSABLE MODULES AND RELAY IN AN
ACCESSABLE LOCATION WITHIN THE FACILITY.
9. DUCT SMOKE DETECTOR IN SUPPLY DUCT OF SPF-T1 AND REMOTE TEST
SWITCH TO BE LOCATED IN COORDINATION WITH DIVISION 23.
10. PROVIDE PRESSURE SWITCH, ADDRESSABLE INPUT & OUTPUT MODULE
FOR CONTROL OF SPF-T1. SEE MECHANICAL SHEET MH121 FOR LOCATION.
11. PROVIDE PRESSURE SWITCH, ADDRESSABLE INPUT & OUTPUT MODULE
FOR CONTROL OF SPF-T2. SEE MECHANICAL SHEET MH121 FOR LOCATION.
12. PROVIDE ADDRESSABLE OUTPUT MODULE, TWO ADDRESSABLE INPUT
MODULES, AND RELAY FOR MONITORING AND CONTROL OF MOTORIZED
DAMPER. REFERENCE MECHANICAL SHEET MH121 FOR COUNT AND
LOCATION OF MODULES AND RELAY.
13. PROVIDE TWO-WAY TELEPHONE COMMUNICATION SERVCE PANEL AND
CONROLS FOR FIRE DEPARTMENT USE. PROVIDE 24VDC POWER FROM THE
FIRE ALARM CONTROL UNIT.
14. PROVIDE SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS.
15. PROVIDE FIRE PUMP STATUS INDICATORS.
1/4" = 1'-0" A1
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR 1
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
A B C
S W
5 AIMAOMRL AIM
CORRIDOR
A B C
VS
WF 1
F
F
S P
ASD
WF
VS
COMM
STAIRS
S W
S
AOM 3
RL AOM 5AIM AIMRL AOM 5AIM AIM
ELEVATOR
MD
A B C
F
S W
5 AIMAOMRL AIM
S P
VS
WF 1
ELEVATOR
CORRIDOR
STAIR
5 AIMAOMRL AIM
5 AIMAOMRL AIM
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:4
A
M
FA122
A
TC
T
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
LO
O
R S
-7
WRM
12801626
APL KPZ
1596300
GENERAL NOTES
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1/4" = 1'-0" C1
ATCT - TYPICAL FIRE ALARM AND MASS NOTIFICATION PLAN -
LANDING FLOORS 2, 4 & 6
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR COMM ROOM.
ACTUATION OF FLOW SWITCH MUST REMOVE POWER TO ELECTRONIC
EQUIPMENT IN THIS ROOM PER UFC 4-133-01. PROVIDE SUPERVISED
MAINTENANCE DISCONNECT SWITCH TO PREVENT SHUNT TRIP DURING
WATER FLOW SWITCH TESTING.
3. PROVIDE AOM CONNECTED TO SHUNT TRIP MAIN CIRCUIT BREAKER FOR
SHUTDOWN OF EQUIPMENT UPON SPRINKLER WATER FLOW.
4. PROVIDE AIR SAMPLING SMOKE DETECTOR WITH FOUR ALARM THRESHOLD
LEVELS. ALERT, ACTION, AND FIRE 1 LEVELS MUST ONLY INITIATE
NOTIFICATION APPLIANCES IN COMM ROOM. FIRE 2 LEVEL MUST INITIATE
NOTIFICATION APPLIANCES IN THE ENTIRE FACILITY. MAXIMUM COVERAGE
AREA PER PORT MUST BE 200 SF AND MAXIMUM TRANSPORT TIME FROM
MOST REMOTE PORT TO THE DETECTION UNIT MUST NOT EXCEED 60
SECONDS.
5. PROVIDE ADDRESSABLE MODULES AND RELAY FOR MONITORING AND
CONTROL OF FIRE/SMOKE DAMPER. SEE MECHANICAL SHEET MH121-122
FOR LOCATION OF FIRE/SMOKE DAMPER PROVIDED BY DIVISION 23.
COORDINATE LOCATION OF ADDRESSABLE MODULES AND RELAY IN AN
ACCESSABLE LOCATION WITHIN THE FACILITY.
1/4" = 1'-0" C3
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR 7
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WORK NOTES X
1/4" = 1'-0" A1
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOORS
3 & 5
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
S P
A B C
CORRIDOR
ELEVATOR
STAIRS
VS
WF 1
15 30
S W
RL AOM AIM
AIM 2
RL AOM AIM
AIM 2
SIMULATOR
S P
S P
F
S P
A B C
CAB ADMIN
STAIRS
CORRIDOR
VS
WF 1
15 30
S W
RL AOM AIM
AIM 2
RL AOM AIM
AIM 2
ELEVATOR
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:4
A
M
FA123
A
TC
T
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
LO
O
R S
WRM
12801627
APL KPZ
1596300
GENERAL NOTES
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. PROVIDE ADDRESSABLE MODULES AND RELAY FOR MONITORING AND
CONTROL OF FIRE/SMOKE DAMPER. SEE MECHANICAL SHEET MH122 FOR
LOCATION OF FIRE/SMOKE DAMPER PROVIDED BY DIVISION 23.
COORDINATE LOCATION OF ADDRESSABLE MODULES AND RELAY IN AN
ACCESSABLE LOCATION WITHIN THE FACILITY.
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1/4" = 1'-0" A1
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR 8
1/4" = 1'-0"
A3
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR 9
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
WORK NOTES X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
P
A B C
VS
WF 1
S W
TOILET
21006
BREAKROOM
21004
CORRIDOR
21002
STAIRS
21003
ELEVATOR
21001
RL AOM AIM
AIM 4
RL AOM AIM
AIM 4
TOILET
21005
A B C
F
VS
WF 2
S
P
S P
S P
S S
S S
VS
WF 1
S W
S
S
CORRIDOR
21102
STAIRS
21103
RL AOM AIM
AIM 4
RL AOM AIM
AIM 4
ELEVATOR EQUIPMENT
21201
MECHANICAL ROOM
21104
AOM AIM AIMRL 5
S P
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA124
A
TC
T
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
LO
O
R S
WRM
12801628
APL KPZ
1596300
1/4" = 1'-0" A1
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. MONITOR FLOW SWITCH AND TAMPER SWITCH FOR ELEVATOR EQUIPMENT
ROOM. FLOW SWITCH MUST BE DPDT WITH ZERO TIME DELAY FOR SHUNT
TRIP OF ELEVATOR UPON SPRINKLER FLOW IN THE ELEVATOR EQUIPMENT
ROOM. REFER TO FIRE SUPPRESSION DRAWINGS FOR QUANTITY AND/OR
LOCATIONS OF DEVICE(S).
3. PROVIDE SUPPLY SIDE DUCT SMOKE DETECTOR FOR AHU-T1A AND AHU-
T1B. REFER TO MECHANICAL SHEETS FOR EXACT LOCATIONS.
4. PROVIDE ADDRESSABLE MODULES AND RELAY FOR MONITORING AND
CONTROL OF FIRE/SMOKE DAMPER. SEE MECHANICAL SHEET MH122-123
FOR LOCATION OF FIRE/SMOKE DAMPER PROVIDED BY DIVISION 23.
COORDINATE LOCATION OF ADDRESSABLE MODULES AND RELAY IN AN
ACCESSABLE LOCATION WITHIN THE FACILITY.
5. PROVIDE ADDRESSABLE MODULES AND RELAY FOR MONITORING AND
CONTROL OF SMOKE DAMPER. SEE MECHANICAL SHEET MH123 FOR
LOCATION OF FIRE/SMOKE DAMPER PROVIDED BY DIVISION 23.
COORDINATE LOCATION OF ADDRESSABLE MODULES AND RELAY IN AN
ACCESSABLE LOCATION WITHIN THE FACILITY.
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1/4" = 1'-0" A3
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
GENERAL NOTES
WORK NOTES X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
A B C
VS
WF
F
S P
S W
CAB
21205
F A
A
E T
S S
S P
S P
75B
75B
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA125
A
TC
T
F
IR
E A
LA
R
M A
N D
M A
S S
N O
TI
F
IC
A
TI
O
N P
LA
N
F
LO
O
R
1.
C
A B
WLM
12801629
APL KPZ
1596300
1. MONITOR FLOW SWITCHES AND TAMPER SWITCHES. COORDINATE WITH
FIRE SPRINKLER CONTRACTOR ON QUANTITY AND LOCATION.
2. PROVIDE PRIVATE MODE SPEAKERS AND BLUE FLASHING INCANDESCENT
LIGHTS IN LIEU OF FIRE ALARM STROBES. SPEAKERS AND LIGHTS MUST BE
ON SEPARATE CIRCUIT.
3. PROVIDE SMOKE DETECTORS WITH FLAT BLACK FINISH.
4. PROVIDE REMOTE ANNUNCIATOR PANEL CAPABLE OF SILENCING THE
SPEAKERS LOCATED IN THE CAB. ALARM INDICATIONS AT THE PANEL MUST
NOT BE CLEARED WHEN LOCAL AUDIBLE ALARMS ARE SILENCED.
5. ROUTE FIRE ALARM CONDUIT/CIRCUITS IN THIS APPROXIMATE LOCATION
UP TO ABOVE CEILING. ROUTE CONDUIT IN MULLION CAP. REFER TO QA100
FOR EXACT LOCATION OF MULLION.
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1/4" = 1'-0" A1
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN - FLOOR
11.5
1/4" = 1'-0" A3
ATCT - FIRE ALARM AND MASS NOTIFICATION PLAN -
CABSLAB/CATWALK FLOOR 12
SCALE IN FEET
0 2' 4' 8'
PLAN
NORTH
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS AND SYMBOLS.
GENERAL NOTES
WORK NOTES X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
3 FT (MIN)
12 INCHES
(MAX)FOR CEILING HEIGHTS LESS THAN 96
INCHES THE VISIBLE LENS MOUNTING
HEIGHT MUST BE WITHIN 6 INCHES OF
THE CEILING
TO EXIT
DOOR
5 FT (MAX)
48 INCHES
MAX
SYNCHRONIZE TWO OR
MORE APPLIANCES IN ANY
FIELD OF VIEW
IN
C H
E S
WALL MOUNTED
SMOKE DETECTOR
CEILING
MOUNTED
SMOKE
DETECTOR
SUPPLY OR
RETURN
DIFFUSER
CEILING
FINISHED FLOOR
WALL
MOUNTED
VISIBLE
APPLIANCE
MINIMUM 12 INCHES
FROM LIGHT SWITCH
PULL STATIONS
MUST NOT BE
LOCATED
BEHIND DOOR
SWINGS.
MAXIMUM DISTANCE BETWEEN SPEAKERS MUST
NOT EXCEED 30 FEET,
UNLESS OTHERWISE NOTED.
DO NOT EXCEED A DISTANCE OF 15
FEET, UNLESS OTHERWISE NOTED.
60 INCHES TO
TOP
BATT BATT
NAC
NAC
AMP
AMP
BATT
FACU
/ACU
ROUTE CONDUIT TO ACHIEVE
SEPARATION OF POWER-LIMITED FIRE
ALARM CIRCUITS AND POWER CIRCUITS
IN
S
T A
LL
N
O G
R E
A T
E R
T H
A N
IN
C
H E
S A
F F
FAC
F
FAA
LOC
SS SS
CEILING MOUNTED
VISIBLE APPLIANCE
ASD
AUDIBLE
ONLY WALL
MOUNTED
APPLIANCE
ET
3 FT (MIN)
CARBON MONOXIDE
DETECTOR
M O
U N
T A
S
IN
D
IC
A T
E D
P
R
J O
B S
P E
C
IF
IC
A
T
IO
N
DACT
IM IMFACU
FIRE ALARM
DEVICES
FLOOR 1
FLOOR 2
FLOOR 3
FLOOR 4 (TYPICAL FOR ADDITIONAL FLOORS)
IM IM
FIRE ALARM
DEVICES
FIRE ALARM
DEVICES
FIRE ALARM
DEVICES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA501
F
IR
E A
LA
R
M D
E
TA
IL
S
WRM
12801630
APL KPZ
1596300
NOT TO SCALE
A1
TYPICAL MOUNTING DETAIL
NOT TO SCALE
B3
CLASS B ISOLATION MODULE MOUNTING
GENERAL NOTES
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA, ABBREVIATIONS
AND SYMBOLS.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
LEVEL ONE
ATCT FLOOR AREA
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS, AND SYMBOLS.
2. THE SMOKE CONTROL SYSTEM DIAGRAM SHOWS THE INTENT OF THE
STAIRWELL PRESSURIZATION SYSTEM. NOT ALL DEVICES ARE SHOWN.
PROVIDE THE QUANTITY OF DEVICES
AS REQUIRED TO COMPLY WITH NFPA 92, UFC 3-600-01,
UFC 4-133-01, AND CONTRACT DOCUMENTS.
3. REFERENCE SHEET FA623 FOR ALL SYSTEM CRITERIA AND SEQUENCE OF
OPERATIONS.
4. BARAMETRIC RELIEF DAMPER PROVIDED BY DIVISION 23. SEE MH123 AND
MI732 FOR MECHANICAL DETAILS FOR PRESSURIZATION.
1. BAROMETRIC RELIEF DAMPER PROVIDED BY DIVISION 23. AIRFLOW IS 0 CFM
AT 0.15 W.C. AND 6,750 CFM AT 0.35 W.C.
LEVEL TWO
LEVEL SIX
ATCT VESTIBULE
LEVEL SEVEN
LEVEL EIGHT
LEVEL NINE
LEVEL TEN
LEVEL ELEVEN
CAB LEVEL
260 CFM
260 CFM
900 CFM
900 CFM
900 CFM
900 CFM
900 CFM
900 CFM
ATCT STAIRWELL AIR SHAFT
260 CFM
260 CFM
260 CFM
260 CFM
STAIRWELL DOOR (TYP)
ATCT FLOOR AREA
2275 CFM
EXTERIOR
LOUVERS
MOTOR OPERATED
CONTROL DAMPER
(BY DIV 23) (FAIL
OPEN)
SPF-T2
SPF-T1
900 CFM
900 CFM
900 CFM
900 CFM
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
FSD
M
M
VD
MANUAL BALANCING
DAMPER (BY DIV 23)
(TYP)
VD
VD
VD
VD
VD
VD
VD
VD
VD
S S
9000 CFM
LEVEL FIVE
LEVEL THREE
LEVEL FOUR
BD
UP TO
6750 CFM
260 CFM
260 CFM
260 CFM
260 CFM
260 CFM
260 CFM FSD
FIRE/SMOKE DAMPER (BY DIV 23) (TYP) (FAIL
CLOSED)(EXHAUST NORMALLY CLOSED)
(SUPPLY NORMALLY OPEN)
FSD
FSD
FSD
FSD 260 CFM
260 CFM
260 CFM
260 CFM
260 CFM
CORRIDOR DOOR (TYP)
195 CFM
FSD
EXHAUST AIR FLOW
TAKEN FROM FLOOR
AREA - LEVEL ONE
260 CFM
260 CFM 260 CFM FSD
260 CFM 260 CFM FSD
TAKEN FROM
VESTIBULE AREA
FSD
FSD
65 CFM
65 CFM
65 CFM
FSD FSD
M
NORMALLY
CLOSED
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-A T
C -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:3
:5
A
M
FA502
S M
O K
E C
O N
TR
O
L S
Y S
TE
M
D
IA
G R
A M
WRM
12801631
APL KPZ
1596300
NOT TO SCALE
A1
SMOKE CONTROL SYSTEM DIAGRAM
GENERAL NOTES
WORK NOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
FACU / ACU
NOTES WORK NOTES
S P
VS WF
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA,
ABBREVIATIONS, AND SYMBOLS.
2. THE FIRE ALARM RISER SHOWS THE INTENT OF THE FIRE ALARM
INFRASTRUCTURE. NOT ALL DEVICES ARE SHOWN.
PROVIDE THE QUANTITY OF DEVICES AS REQUIRED TO
COMPLY WITH NFPA 72, UFC 3-600-01, UFC 4-133-01, UFC 4-021-01
AND CONTRACT DOCUMENTS.
3. EACH FLOW AND TAMPER SWITCH MUST REPORT BACK TO THE FIRE
ALARM CONTROL UNIT WITH A SEPARATE ADDRESS. GROUPED
SWITCHES ON ONE ADDRESS ARE NOT ACCEPTABLE.
AOM
PA
BATT
SS
120 VAC
S
NAC
BATT
SS
120 VAC
AMP
FAC
AIM
S
WP
1. MASS NOTIFICATION TRANSCEIVER (BY GOVERNMENT).
PROVIDE CONDUIT, PULL STRINGS, AND OTHER ACCESSORIES AS
INDICATED. FINAL CONNECTIONS BY GOVERNMENT.
2. LOCK, LABEL "FIRE ALARM", AND PAINT CIRCUIT BREAKER RED. SEE
ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.
3. QUANTITY AND LOCATION BY CONTRACTOR'S DESIGN TO MEET DESIGN
CRITERIA.
4. REFER TO FIRE SUPPRESSION DRAWINGS FOR QUANTITY AND / OR
LOCATIONS OF DEVICE(S).
5. REFER TO FIRE ALARM PLANS FOR QUANTITY AND / OR LOCATIONS OF
DEVICE(S).
6. PROVIDE ADDRESSABLE INPUT AND/OR OUTPUT MODULE(S) AS REQUIRED
TO ACHIEVE THE FUNCTIONALITY INDICATED IN THE FIRE ALARM MATRIX.
7. PROVIDE ADDITIONAL BOOSTER PANELS AS REQUIRED PER
CONTRACTOR'S DESIGN. WHERE ADDITIONAL BOOSTER PANELS ARE
REQUIRED LOCATE AS INDICATED ON PLAN.
8. PROVIDE ADDITIONAL AMPLIFIERS AS REQUIRED PER CONTRACTOR'S
DESIGN. WHERE ADDITIONAL AMPLIFIERS ARE REQUIRED LOCATE AS
INDICATED ON PLAN.
9. PROVIDE SUPPLY DUCT SMOKE DETECTORS FOR DIRECT SHUT DOWN FOR
THE FOLLOWING UNITS: AHU-A1, AHU-A2, AND DOAH-A1. SHUTDOWN
THROUGH THE EMCS/DDC IS NOT PERMITTED.
10. EXTERIOR WP HORN STROBE OVER FDC.
11. EXTERIOR WP FIRE ALARM / MASS NOTIFICATION SPEAKERS.
12. 24 VDC TO FACU OR NAC PANEL.
13. COORDINATE CONNECTION LOCATION WITH DIVISION 26 OF SHUT DOWN
FOR PUBLIC ADDRESS SYSTEM.
14. PROVIDE ADDRESSABLE OUTPUT MODULE FOR RELEASE OF SMOKE
SHUTTER.
15. RELAY TO MONITOR INTEGRITY OF POWER SUPPLY.
16. RELAY TO ENABLE 120 VAC TO SHUNT TRIP BREAKER.
17. ELEVATOR SHUNT TRIP BREAKER (BY DIVISION 26).
18. PROVIDE 3/4 INCH CONDUIT WITH PULL STRING (25 FT MAX).
19. PROVIDE 1-1/2 INCH RIGID STEEL CONDUIT WITH PULL STRING TO ROOF
WITH UL LISTED WEATHERHEAD 3 FT ABOVE ROOF LINE. MAXIMUM CABLE
LENGTH MUST BE 125 FT.
20. DACT PHONE CORD (BACKUP LINE).
21. DACT TO CAT6 ADAPTER.
22. CAT6 CABLE TO TELEPHONE PATCH PANEL IN BASE NODE ROOM 156.
23. DACT PHONE CORD (PRIMARY LINE).
24. CAT6 CABLE.
25. BOSCH C900V2 (OR EQUAL) DIALER CAPTURE ETHERNET MODULE.
26. ETHERWAN EL100C-20 (OR EQUAL) MEDIA CONVERTER (CAT6 TO SINGLE
MODE FIBER).
27. SINGLE MODE FIBER TO FIBER PATCH PANEL IN BASE NODE ROOM 156.
28. SPEAKERS IN COMM ROOM REQUIRING LOCAL AUDIBILITY UPON SMOKE
THRESHOLD LEVEL PER MATRIX.
29. LOW FREQUENCY SPEAKERS IN BUNK ROOMS.
30. PROVIDE QUANTITY OF DUCT SMOKE DETECTORS AND CONNECTION TO
SMOKE DAMPERS AS INDICATED ON PLAN.
31. PROVIDE SUPERVISED DISCONNECT AND CONNECTION TO SHUNT TRIP
BREAKER.
CO
AOM
5 6
AOMS
S
RL
24 V FROM
VFD/STARTER
TO ENABLE INPUT
ON VFD/STARTER
POWER CIRCUIT
VISIBLE NOTIFICATION APPLIANCE CIRCUIT
(CLASS B)
AUDIBLE NOTIFICATION APPLIANCE CIRCUIT
(CLASS B)
SIGNALING LINE CIRCUIT (CLASS B)
AIM
AIMAIMAIM
RL
AIM
16 ST
AOM
CIRCUIT LEGEND
SYNCHRONIZATION CIRCUIT TO
NEXT NAC PANEL
WP
RL
AIM
-120 VAC
WF
ESR
+120 VAC
TO PROTECTED
DEVICE
DACT
AOM
MD
ELECTRONIC EQUIPMENT EPO SHUNT
TRIP BREAKER (BY DIVISION 26)
F
SS
120 VAC 2
BATT
FAC
MNS
FACU EXTERNAL
AUDIO INPUT
SS
120 VAC
25 26
23 24
S
3 28
S L
X
S
3 29
AOM
TO SMOKE SHUTTER
AOMS
RL
SMOKE
DAMPER
12120 VAC 6
AIM
GENERATOR CONTROLLER
AIM
ST
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:4
:0
A
M
FA601
A
IR
O P
S
F
IR
E A
LA
R
M
M A
S S
N O
T
IF
IC
A
TI
O
N R
IS
E
R
WRM
12801632
APL KPZ
1596300
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
FIRE ALARM CONTROL UNIT (FACU) FUNCTIONAL MATRIX
ANNUNCIATION AT
LOCAL PANEL
NOTIFICATION AUXILIARY
FUNCTION
A U
D
IO
-V
IS
IB
LE
F
IR
E A
LA
R
M
IN
D
IC
A T
IO
N
B Y
V
IC
E
A U
D
IO
-V
IS
IB
LE
T R
O U
B
LE
IN
D
IC
A
T
IO
N
V
IC
E
A U
D
IO
-V
IS
IB
LE
S U
P E
R V
IS
O
R Y
IN
D
IC
A
T
IO
N
V
IC
E
C O
M M
O N
T R
O U
B
LE
S
IG
N A
L T
O F
IR
P
A R
T M
E N
T
C O
M M
O N
S U
P E
R V
IS
O
R Y
S
IG
N A
L T
O F
P
A R
T M
E N
T
S H
U T
-D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D
LI
N G
Q U
IP
M
E N
T
E
LE
V A
T O
R R
E C
A
LL
T O
P R
IM
A
R Y
R E
C A
LL
F
LO
O
R
E
LE
V A
T O
R R
E C
A
LL
T O
S E
C O
N D
A R
Y R
E C
A
LL
LO
O
R
IN
IT
IA
T
E E
LE
V
A T
O R
S H
U N
T T
R
IP
ALARM SIGNALS
MANUAL FIRE ALARM STATIONS
PHOTOELECTRIC SMOKE DETECTOR (OTHER THAN ELEVATOR OR BUNK ROOM)
FLOW SWITCHES - WET-PIPE SYSTEM
FLOW SWITCH - ELEVATOR EQUIPMENT ROOM
SMOKE DETECTION - ELEVATOR MAIN FLOOR LOBBY
SMOKE DETECTION - ELEVATOR LOBBY OTHER THAN MAIN FLOOR
SMOKE DETECTION - ELEVATOR EQUIPMENT ROOM
AC POWER FAILURE
LOW BATTERY
OPEN CIRCUIT FAULT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
TROUBLE SIGNALS
COMPONENT COMMON TROUBLE
SUPERVISORY SIGNALS
COMPONENT COMMON SUPERVISORY
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
F
IR
E A
LA
R
M
M A
S S
N O
T
IF
IC
A
T
IO
N V
IS
IB
LE
O
T
IF
IC
A
T
IO
N
M A
S S
N O
T
IF
IC
A
T
IO
N A
N N
O U
N C
E M
E N
T
F
IR
E A
LA
R
M A
N N
O U
N C
E M
E N
T
S
IL
E N
C E
G E
N E
R A
L F
IR
E
A
LA
R M
N
O U
N C
E M
E N
T
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
D
IS
A B
LE
P
U B
LI
C
A D
D R
E S
S S
Y S
T E
M
X
X
X
X
X
X
X
IN-DUCT SMOKE DETECTORS X X X
X XMASS NOTIFICATION INPUT (LOCAL / BASE WIDE/TRANSCEIVER) XX X X
GENERAL VALVE SUPERVISORY X X
IN
IT
IA
T
E E
P O
O F
E
LE
C T
R O
N
IC
E Q
U
IP
M E
N T
IN
F E
C T
E D
R O
O M
CARBON MONOXIDE DETECTORS
M A
N U
A L
P U
LL
S
T A
T
IO
N A
LA
R
M S
IG
N
A L
E
D E
P A
R T
M E
N T
S M
O K
E D
E T
E C
T
IO
N A
LA
R
M S
IG
N
A L
T O
F
P A
R T
M E
N T
F
IR
E S
U P
P R
E S
S
IO
N A
C T
IV
A
T
IO
N A
LA
IG
N A
L T
O F
IR
E
D E
P A
R T
M E
N T
C A
R B
O N
M O
N O
X
ID
E A
LA
R
M S
IG
N
A L
T O
F
P A
R T
M E
N T
X
X
X
X
X
X
X
X
X
IN
IT
IA
T
E S
O
LI
D S
T A
T E
R E
D H
A T
S
IG
N A
L
V
A T
O R
IN
IT
IA
T
E F
LA
S
H
IN
G R
E D
H A
T S
IG
N
A L
V A
T O
R
X
X
X
XFLOW SWITCH - ELECTRONIC EQUIPMENT ROOM X X X
X X
C A
R B
O N
M O
N O
X
ID
E A
N N
O U
N C
E M
E N
T
X
A C
T
IV
A T
E W
E A
T H
E R
P R
O O
F H
O R
N /S
T R
O
O V
E F
D C
X
X
X
SMOKE DETECTION - BUNK ROOM XX
A C
T
IV
A T
E B
U N
K R
O O
M L
O W
F R
E Q
U E
N C
U
D
IB
LE
N
O T
IF
IC
A T
IO
N
X
S
LE
E P
IN
G
R O
O M
S M
O K
E D
E T
E C
T
IO
N S
IG
N
A L
T O
F
IR
E D
E P
A R
T M
E N
T
IN
IT
IA
T
E C
O M
M R
O O
M N
O T
IF
IC
A T
IO
P
LI
A
N C
E S
O N
LY
C
LO
S E
S M
O K
E S
H U
T T
E R
D O
O R
LASER SMOKE DETECTOR IN COMM ROOM - ALARM LEVEL 2 (2.0% / FT
OBSCURATION)
XX X X X X
LASER SMOKE DETECTOR IN COMM ROOM - ALARM LEVEL 1 (0.50% / FT
OBSCURATION)
X
X
X
X
X
X
X
X
X
X X X
C
LO
S E
A S
S O
C
IA
T E
D S
M O
K E
D A
M P
E R
DUCT SMOKE DETECTOR FOR SMOKE DAMPER X X X
GENERATOR RUNNING, FAULT, AND/OR SWITCH IN NONAUTOMATIC POSITION X X
ELECTRONIC EQUIPMENT ROOM WATER FLOW MAINTENANCE DISCONNECT SWITCH X X
PROVIDE SYSTEM WITH CAPACITY FOR TEN MESSAGES. ONLY
PROGRAM THE FIRE ALARM AND CARBON MONOXIDE MESSAGES
BELOW. THE REMAINING MESSAGES WILL BE PROGRAMMED BY THE
BASE. MASS NOTIFICATION MESSAGES MUST BE A FEMALE VOICE
AND STATE THE FOLLOWING.
1. (TEMPORAL THREE ALERT TONE)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR
ATTENTION PLEASE. A FIRE EMERGENCY HAS OCCURRED;
PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT. DO NOT
USE THE ELEVATORS."
<PAUSE 2 SECONDS> REPEAT MESSAGE.
2. (TEMPORAL FOUR ALERT TONE)
<TWO ROUNDS>
"MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR
ATTENTION PLEASE. CARBON MONOXIDE HAS BEEN DETECTED
IN THE BUILDING. PLEASE LEAVE THE BUILDING BY THE
NEAREST EXIT."
<PAUSE 2 SECONDS> REPEAT MESSAGE
MASS NOTIFICATION MESSAGES
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
C O
M M
A N
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
-A
T L A
N T
IC
M
A R
IN
E
C O
R P
S I P
T N
A V
A L
S T
A T
IO
N
N
O R
F O
L K
V
A
EJA
M C
A S
C H
E R
R Y
P O
IN
T
C H
E R
R Y
P O
IN
T
N
C
AS NOTED
1317 EXECUTIVE BLVD.
SUITE 300
CHESAPEAKE, VA 23320
F Y
P
-2 A
T C
T O
W E
R A
N D
A
IR
O P
E R
A T
IO
N
S
DRAWFORM REVISION: 12 APRIL 2018
UNCLASSIFIED
UNCLASSIFIED
U N
C
LA
S S
IF
IE
D
F
IL
E N
A M
E
P
LO
T T
E D
CJC/KDB
DSN
DSN
SAT-TO FORM SIGNED BY
DON ELLIOT 12/19/19
C
R e v it P ro je c ts
\B L D
G -P
-1
-F
-O P
S -C e n tr a l_ h jc h o b u rn s m c d .c o m
.r v t
/1
/2
:4
:0
A
M
FA602
A
IR
O P
S
F
IR
E A
LA
R
M M
A
TR
IX
WRM
12801633
APL KPZ
1596300
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
IS
S U
E D
F O
R B
ID
/1 8/
S P
VS WF
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN CRITERIA, ABBREVIATIONS,
AND SYMBOLS.
2.…