Drawing Reference: A-101, A-501, A-553, A-820 and A-830
Description of Scope Change:
This Amendment is an update to the contract drawings to reflect design clarifications as follows:
CONTRACT DRAWINGS
On NAVFAC Dwg No. 12801455 (A-101) Partition at door 102A, delete partition type S3DA and replace with partition type S2DB.
Partition at door 102B, delete partition type S2FA and replace with partition type S2DB
On NAVFAC Dwg No. 12801496 (A-501) Partition type S2, delete 25 GA @ 24” O.C and replace with 20 GA studs @ 16” O.C.
Partition type S2 STC rating column, delete 45 and replace with 40.
Partition type S4, delete two layers of 5/8” gypsum wallboard on 25 GA studs @ 16” O.C and replace with 16 GA studs @ 16” O.C with two layers of 5/8” gypsum wallboard on one side only and two layers of 5/8” acoustical gypsum wallboard.
Partition type S4 STC rating column, delete 55 and replace with 52.
Partition type S3, delete 25 GA @ 24” O.C and replace with 20 GA studs @ 24” O.C.
Partition type S3 STC rating column, delete 50 and replace with 44.
Partition Types General Notes – Note #5, delete “PROVIDE METAL STUD DIAGONAL
BRACING @ 4'-0" O.C. (ALTERNATE DIRECTIONS) TO UNDERSIDE OF METAL DECK
FOR ALL WALLS GREATER THAN 16'-4" IN HEIGHT” and replace with “PROVIDE
METAL STUD DIAGONAL BRACING AS REQUIRED BY METAL STUD SUPPLIER TO
MEET DEFLECTION CRITERIA SPECIFIED, FOR THE GAUGES AND HEIGHT SPANS
INDICATED ON DRAWINGS”.
On NAVFAC Dwg No. 12801520 (A-553)
Detail A2, A3, & A4: delete “UL Design No. 428” and replace with “UL U415 System B”.
On NAVFAC Dwg No. 12801559 (A-820)
Detail A1, Add sign type S11B on the partitions of the Elevator Equipment Room within the Mechanical Room (2 Signs total) to identify the cap above the Elevator Equipment Room as non-load bearing.
On NAVFAC Dwg No. 12801560 (A-830) Add Sign Type S11B stating “WARNING - NON LOAD BEARING ABOVE”.
--End of Amendment--