1596300_dwg_02of35_V1_LifeSafety.pdf

PDF 4 MB Posted

Attached to
Design Bid-Build P228 ATC Tower and Air Operations, Marine Corps Air Station, Cherry Point, North Carolina
Solicitation number
N4008522R2504
Issued by

View the file

Other files

File Type Posted
AMEND 0010 UPDATED WAGE DETERMINATION FOR P228.pdf PDF
AMENDMENT 0011 FOR P228 ATC TOWER.pdf PDF
AMENDMENT 0009.pdf PDF
Amendment 0008.pdf PDF
AMENDMENT 0007 FOR P228.pdf PDF
UPDATED REVISED BID SCHEDULE FOR P228.pdf PDF
AMENDMENT 0006 FOR P228.pdf PDF
PPI LOG 04 FOR P228.pdf PDF
AMENDMENT 0005 FOR P228.pdf PDF
UPDATED BID SCHEDULE FOR P228.pdf PDF
P228 PPI LOG 03.pdf PDF
P228 AMENDMENT 0004.pdf PDF
PPI LOG 02 FOR P228.pdf PDF
P228 AMENDMENT 0003.pdf PDF
P228 AMENDMENT 0003 DOCUMENT FOR PPI 4-7.pdf PDF
P228 AMENDMENT 0002.pdf PDF
AMENDMENT 0002-DRAWING REFERENCES.pdf PDF
P228 PPI LOG 01.pdf PDF
AMENDMENT 0001 FOR P228.pdf PDF
Site Visit Log P228.pdf PDF
Attachment D - Past Performance Questionnaire.docx DOCX document
1596300_dwg_24of35_V2_Architectural.pdf PDF
1596300_dwg_16of35_V1_Civil.pdf PDF
1596300_dwg_28of35_V3_Equipment.pdf PDF
1596300_dwg_05of35_V1_Civil.pdf PDF
1596300_dwg_14of35_V1_Civil.pdf PDF
1596300_dwg_33of35_V4_Electrical.pdf PDF
1596300_dwg_12of35_V1_Civil.pdf PDF
1596300_dwg_06of35_V1_Civil.pdf PDF
1596300_dwg_21of35_V1_Landscape.pdf PDF
RFP FOR P228 ATC TOWER.pdf PDF
1596300_dwg_23of35_V2_Structural.pdf PDF
1596300_dwg_01of35_V1_General.pdf PDF
1596300_dwg_22of35_V2_General.pdf PDF
Attachment A - Pre-Propsal Injuiries Log.doc DOC document
1596300_dwg_17of35_V1_Civil.pdf PDF
1596300_dwg_09of35_V1_Civil.pdf PDF
1596300_dwg_15of35_V1_Civil.pdf PDF
Attachment E - Historical Small Business Utilization.docx DOCX document
1596300_dwg_04of35_V1_Survey-Geotechnical.pdf PDF
1596300_dwg_34of35_V4_Telecommunications.pdf PDF
1596300_dwg_26of35_V2_Interiors.pdf PDF
USCG MULTI-USE COMPLEX - 00 01 15 LIST OF DRAWINGS 100422.pdf PDF
Attachment F - Small Business Participation Commitment Document.docx DOCX document
ATTACHMENT B BID SCHEDULE FOR P228 ATC TOWER.pdf PDF
JA ML-23-07 CHPT P228 Fire Protection_Redacted.pdf PDF
Attachment H- PIEE Vendor Access Instructions.pdf PDF
1596300_dwg_35of35_V4_Telecommunications.pdf PDF
1596300_dwg_11of35_V1_Civil.pdf PDF
1596300_dwg_27of35_V3_General.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A- O

PS

-C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:2 9:

A

M

GI001

AI

R

O

PS

BU

IL

DI

NG

C

O

DE

A

ND

L

IF

E

SA

FE

TY

C

RI

TE

RI

A

LES

12801277

RJM RJM

1596300

9. OCCUPANT LOAD CALCULATIONS (NFPA 101 , UFC 3-600-01)

NFPA 101 Use Area SF.PerPerson Occupancy

SFType Calculated NFPA

Occupants

BASEMENT

BUILDING EQUIPMENT - 500 SF/PERSON 326 SF 500 GROSS 1

326 SF

FIRST FLOOR

ASSEMBLY USE: CONCENTRATED, WITHOUT FIXED

SEATING - 7 SF/PERSON

2404 SF 7 NET 344

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT

FIXED SEATING - 15 SF/ PERSON

1469 SF 15 NET 98

BUILDING EQUIPMENT - 500 SF/PERSON 2683 SF 500 GROSS 6

BUNKS - 50 SF/PERSON 534 SF 50 GROSS 11

BUSINESS - 150 SF/ PERSON 9805 SF 150 GROSS 66

CLASSROOM - 20 SF/PERSON 432 SF 20 NET 22

IT EQUIPMENT - 300 SF/PERSON 271 SF 300 GROSS 1

LOCKER - 50 SF/PERSON 338 SF 50 GROSS 7

STORAGE - 500 SF/PERSON 875 SF 500 GROSS 2

18811 SF

SECOND FLOOR

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT

FIXED SEATING - 15 SF/ PERSON

1343 SF 15 NET 90

BUILDING EQUIPMENT - 500 SF/PERSON 144 SF 500 GROSS 1

BUSINESS - 150 SF/ PERSON 3385 SF 150 GROSS 23

IT EQUIPMENT - 300 SF/PERSON 112 SF 300 GROSS 1

STORAGE - 500 SF/PERSON 162 SF 500 GROSS 1

5147 SF

Grand total 24284 SF

1. APPLICABLE CODES AND STANDARDS

ABBREVIATIONS TITLE EDITION

IBC INTERNATIONAL BUILDING CODE 2018

NFPA 1 FIRE CODE 2021

NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2022

NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022

NFPA 70 NATIONAL ELECTRICAL CODE 2020

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022

NFPA 80 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2022

NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND

VENTILATING SYSTEMS

NFPA 101 LIFE SAFETY CODE 2021

UFC 1-200-01 DOD BUILDING CODE CHANGE 1,

UFC 3-490-06 ELEVATORS CHANGE 1,

UFC 3-520-05 STATIONARY AND MISSION BATTERIES CHANGE 2,

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES CHANGE 6,

UFC 4-010-01 DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS CHANGE 1, UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS CHANGE 1, UFC 4-133-01 AIR TRAFFIC CONTROL AND AIR OPERATIONS FACILITIES CHANGE 2,

2. TYPE OF CONSTRUCTION (IBC 601)

BUILDING ELEMENT

TYPE OF

CONSTRUCTION

FIRE RESISTANCE

RATING

PRIMARY STRUCTURAL FRAME IIB 0 HR

BEARING EXTERIOR WALL IIB 0 HR

BEARING INTERIOR WALL IIB 0 HR *

NON-BEARING EXTERIOR WALL IIB 0 HR

NON-BEARING INTERIOR WALL IIB 0 HR *

FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND

JOISTS

IIB 0 HR *

ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IIB 0 HR

3. CLASSIFICATION OF OCCUPANCY

AREAS OCCUPANCY (IBC)

OCCUPANCY (NFPA

101)

BUNK ROOMS RESIDENTIAL, GROUP R-3 SECTION 310.4 LODGING OR ROOMING

HOUSE 6.1.8.1.2

CONFERENCE & BREAK > 750 SQ FT ASSEMBLY, GROUP A-3 SECTION 303.4 ASSEMBLY 6.1.2

TRAINING, BREAK < 750 SQ FT OFFICE,

UTILITY, RESTROOMS, CIRCULATION

BUSINESS, GROUP SECTION 304.1 BUSINESS 6.1.11

STORAGE ACCESSORY MODERATE-HAZARD STORAGE,

GROUP S-1 SECTION 311.2

STORAGE 6.1.13

4. BUILDING ALLOWABLE AREA (IBC 506.2)

OCCUPANCY ALLOWABLE AREA (SF) *

A-3 28,500 B 69,000

5. MODIFIED ALLOWABLE HEIGHT (IBC 504)

OCCUPANCY HEIGHT LIMIT (FT / STORY) *

A-3 75/3 B 75/4

6. NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

COMPONENT/ AREA REQUIRED RATING CODE SECTION

SHAFT ENCLOSED CONNECTING 3 OR

FEWER STORIES

1 HOUR BARRIER NFPA 101: 8.6.5

ELEVATOR MACHINE ROOM 1 HOUR BARRIER (1 HOUR

BARRIER PROVIDED)

UFC 3-600-01: 4-16.2.1

ELECTRICAL ROOM W/ TRANSFORMER

> 112-1/2 kVA

1 HOUR BARRIER NFPA 70: 450.21(B)

MECHANICAL ROOM W/ BOILER 0 HOUR SMOKE PARTITION NFPA 101: 38.3.2.1

BUNK ROOM 0 HOUR SMOKE PARTITION NFPA 101: 26.3.5

COMM ROOMS, BASE NODE 1 HOUR BARRIER UFC 4-133-01, 3-6.7.1

ELEVATOR SHAFT 1 HOUR BARRIER IBC 3002.1

UPS, ELECTRICAL 153 2 HOUR BARRIER UFC 3-520-05,2-1.2, NFPA 1, 52.2.2.3.4

OPEN ENTRY BETWEEN FIRST AND

SECOND FLOOR

0 HOUR SMOKE BARRIER NFPA 101: 4.5.6, 8.6.1

7. BUILDING SEPARATION (IBC TABLE 602)

OCCUPANCY FIRE SEPARATION DISTANCE (FT)*

FIRE RESISTIVE RATING OF EXTERIOR

WALL

A-3, B ≥ 10 NONE

8. OPENING PROTECTION FOR FIRE AND SMOKE RESISTIVE CONSTRUCTION

COMPONENT DOORS DUCT PENETRATIONS

OTHER

PENETRATIONS CODE SECTION

2 HOUR FIRE BARRIER 90 MINUTES 90 MINUTE FIRE DAMPER 2 HR NFPA 90A:

5.3.1.1, NFPA

101: 8.3.3

0 HR SMOKE BARRIER 0 HR (SELF OR

AUTOMATIC

CLOSING)

SMOKE DAMPER 0 HR NFPA 101 8.5

1 HR FIRE BARRIER FOR

MEANS OF EGRESS

(INCLUDING

STAIRWELLS)

1 HR NOT PERMITTED 1 HR NFPA 101:

7.1.3.2, 8.3.3

OTHER 1 HR FIRE

BARRIERS

3/4 HR 0 HOUR DUCT, 1-1/2 HR AIR

TRANSFER

1 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101:

8.3.3

0 HR SMOKE PARTITION 0 HR (SELF

CLOSING)

SMOKE DAMPER ON TRANSFER

DUCT ONLY

0 HR NFPA 101:8.4

10. MINIMUM EXITS OR EXIT ACCESSES FROM A SPACE OR AREA (NFPA 101)

OCCUPANCY

CONDITION PERMITTING ONE

EXIT

CONDITION REQUIRING TWO OR

MORE EXITS CODE SECTION

ASSEMBLY N/A ALL CONDITIONS 12.2.4.1

BUSINESS 100 FT OR LESS COMMON PATH COMMON PATH EXCEEDS 100 FT 38.2.4

11. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (NFPA 101, TABLE A.7.6)

OCCUPANCY COMMON PATH LIMIT (FT) DEAD END LIMIT (FT) TRAVEL DISTANCE LIMIT (FT)

ASSEMBLY 20 20 250

BUSINESS 100 50 300

LODGING/ROOMING (BUNK

ROOMS)

12. MINIMUM EGRESS WIDTHS

COMPONENT REQUIREMENT WIDTH (IN) NFPA 101 SECTION

DOORS IN EGRESS ACCESS MINIMUM 32 7.2.1.2.3.2

CORRIDOR SERVING 50 OR MORE OCCUPANTS MINIMUM 44 12.2.3.8

CORRIDOR SERVING LESS THAN 50 OCCUPANTS MINIMUM 36 7.3.4

STAIRS IN EGRESS ACCESS MINIMUM 44 7.2.2.2.1.2

LEVEL EGRESS COMPONENTS PER OCCUPANT 0.2 7.3.3.1

STAIRWAYS PER OCCUPANT 0.3 7.3.3.1

13. MINIMUM INTERIOR FINISH RATINGS (NFPA 101, TABLE A.10.2.2)

OCCUPANCY EXITS

EXIT ACCESS

CORRIDORS OTHER SPACES

ASSEMBLY CLASS B CLASS C CLASS C

BUSINESS CLASS C CLASS C CLASS C

LODGING/ROOMING

(BUNK ROOMS)

CLASS C CLASS C CLASS C

14. FIRE SUPPRESSION REQUIREMENTS (UFC 3-600-01 CHAPTER 9)

SPRINKLERS STANDPIPE FIRE EXTINGUISHERS

PROVIDED THROUGHOUT NOT REQUIRED REQUIRED

15. FIRE ALARM REQUIREMENTS (UFC 3-600-01 CHAPTER 9)

MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION

MANUAL FIRE ALARM PULL

STATIONS PROVIDED AT EXITS,

LOCAL OPERATING CONSOLE FOR

VOICE MESSAGING

SPRINKLER SYSTEM WATER FLOW

AND VALVE TAMPER SWITCHES,

SPOT SMOKE DETECTOR ABOVE

FIRE ALARM PANELS, DUCT SMOKE

DETECTORS, CARBON MONOXIDE

DETECTION

VOICE MESSAGING AND CLEAR

LENS ALERT STROBES

* EXCEPT AS REQUIRED FOR NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

* PER IBC 602. FIRE SEPARATION DISTANCE IS DEFINED AS THE DISTANCE FROM THE

BUILDING'S FACE TO THE CLOSEST INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET,

ALLEY, OR PUBLIC WAY, OR TO AN IMAGINARY LINE BETWEEN TWO BUILDINGS.

* PER IBC 504 FOR TYPE IIB CONSTRUCTION, SPRINKLER BUILDING. THE MOST RESTRICTIVE OCCUPANCY LIMITATIONS ARE USED.

* PER IBC 506.2 FOR TYPE IIB CONSTRUCTION, MULTIPLE STORY, SPRINKLERED

BUILDING. THE MOST RESTRICTIVE OCCUPANCY LIMITATIONS ARE USED.

16.1 ACTUAL OCCUPANT - REQUIRED PLUMBING FIXTURES* (IBC 2902.1)

OCCUPANCY

MALE * FEMALE *

DRINKING FOUNTAINSWATERCLOSET

URINALS ALLOWED

TO REPLACE LAVATORIES WATERCLOSETS LAVATORIES

ACTUAL

OCCUPANCY

LOAD

7.40 3.28 6.49 6.42 4.33 3.47

TOTAL REQUIRED 6.53 2.95 5.67 5.77 3.78 3.08

TOTAL PROVIDED 7 2 8 8 7 3

* MALE/ FEMALE BALANCE BASED ON 60/40 RATIO

17. FIRE EXTINGUISHER DISTRIBUTION (NFPA 10)

OCCUPANCY

PRIMARY CLASSIFICATION

OF FIRE AND HAZARD

MINIMUM

RATING

MAXIMUM FLOOR

AREA PER A (SF)

MAX TRAVEL

DISTANCE (FT)

ALL CLASS A:C - ORDINARY 2A 1,500 75

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

/20

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A- R

AN

G

E- C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:3 2:

A

M

GI011

M

TR

AC

O

N -B

UI

LD

IN

G

C O

DE

A

ND

L

IF

E

SA

FE

TY

C

RI

TE

RI

A

LES

12801278

EV SF

1596300

9. OCCUPANT LOAD CALCULATIONS (NFPA 101 TABLE 7.3.1.2, UFC 3-600-01)

Section NFPA 101 Use Area SF.Per Person Occupancy

SF Type NFPA Fixed Occupants

ATCM ASSEMBLY USE: LESS CONCENTRATED,

WITHOUT FIXED SEATING - 15 SF/PERSON

1472 15 NET 99

ATCM BUILDING EQUIPMENT - 500 SF/PERSON 1515 500 GROSS 4

ATCM BUSINESS - 150 SF/PERSON 7468 150 GROSS 50

ATCM CLASSROOM - 20 SF/PERSON 903 20 NET 46

ATCM IT EQUIPMENT - 300 SF/PERSON 1228 300 GROSS 5

ATCM KITCHEN - 100 SF/PERSON 430 100 GROSS 5

ATCM LOCKER - 50 SF/PERSON 407 50 GROSS 9

ATCM STORAGE - 500 SF/PERSON 2978 500 GROSS 6

RANGE ASSEMBLY USE: LESS CONCENTRATED,

WITHOUT FIXED SEATING - 15 SF/PERSON

396 15 NET 27

RANGE BUILDING EQUIPMENT - 500 SF/PERSON 60 500 GROSS 1

RANGE BUSINESS - 150 SF/PERSON 4211 150 GROSS 29

RANGE CLASSROOM - 20 SF/PERSON 575 20 NET 29

RANGE IT EQUIPMENT - 300 SF/PERSON 243 300 GROSS 1

RANGE STORAGE - 500 SF/PERSON 498 500 GROSS 1

2. TYPE OF CONSTRUCTION (IBC 601)

BUILDING ELEMENT

TYPE OF

CONSTRUCTION

FIRE RESISTANCE

RATING

PRIMARY STRUCTURAL FRAME IIB 0 HR

BEARING EXTERIOR WALL IIB 0 HR

BEARING INTERIOR WALL IIB 0 HR *

NON-BEARING EXTERIOR WALL IIB 0 HR

NON-BEARING INTERIOR WALL IIB 0 HR *

FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IIB 0 HR *

ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IIB 0 HR

5. MODIFIED ALLOWABLE HEIGHT (IBC 504)

OCCUPANCY HEIGHT LIMIT (FT / STORY) *

B 75/4

S-1 75/3

3. CLASSIFICATION OF OCCUPANCY

AREAS OCCUPANCY (IBC)

OCCUPANY (NFPA

101) CONFERENCE > 750 SQ FT ACCESSORY ASSEMBLY, GROUP A-3 SECTION 303.4 ASSEMBLY SECTION 6.1.2

CONFERENCE & BREAK < 750 SQ FT OFFICE,

TRAINING, SERVER, UTILITY, RESTROOMS,

CIRCULATION

BUSINESS, GROUP B SECTION 304.1 BUSINESS SECTION 6.1.11

STORAGE MODERATE-HAZARD STORAGE, GROUP S-1 SECTION

311.2

STORAGE SECTION 6.1.13

4. BUILDING ALLOWABLE AREA (IBC 506.2)

OCCUPANCY ALLOWABLE AREA (SF) *

B 69,000

S-1 52,500

6. NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

COMPONENT/ AREA REQUIRED RATING CODE SECTION

ELECTRICAL ROOM W/ TRANSFORMER > 112-1/2

kVA

1 HOUR BARRIER NFPA 70: 450.21(B)

COMM 105, ATCM SERVER 121, EQUIPMENT

ROOM 150

1 HOUR BARRIER UFC 4-133-01, 3-6.7.1

MECHANICAL ROOM W/ BOILER 0 HOUR SMOKE PARTITION NFPA 101 38.3.2.1

ELECTRICAL ROOM SERVING TOWER 1 HOUR BARRIER NFPA 70, 700.10(D)

UPS ROOM, ELECTRICAL 173 2 HOUR BARRIER UFC 3-520-05,2-1.2, NFPA 1,52.2.2.3.4

7. BUILDING SEPARATION (IBC TABLE 602)

OCCUPANCY

FIRE SEPARATION

DISTANCE (FT)*

FIRE RESISTIVE RATING

OF EXTERIOR WALL

B, S-1 ≥ 10 NONE**

8. OPENING PROTECTION FOR FIRE AND SMOKE RESISTIVE CONSTRUCTION

COMPONENT DOORS DUCT PENETRATIONS

OTHER

PENETRATIONS CODE SECTION

3 HR FIRE WALL 3 HR NOT PERMITTED 3 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101: 8.3.3

2 HOUR FIRE BARRIER 90 MINUTE 90 MINUTE FIRE DAMPER 2 HR NFPA 90A: 5.3.1.1,

NFPA 101: 8.3.3

1 HR FIRE BARRIERS 3/4 HR 0 HOUR DUCT, 1-1/2 HR AIR TRANSFER,

1-1/2 HR FIRE/SMOKE DAMPER FOR DUCT

PENETRATIONS IN SERVER ROOMS PER

NFPA 75

1 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101:

8.3.3, NFPA 75:6.6.3

0 HR SMOKE PARTITION 0 HR (SELF

CLOSING)

SMOKE DAMPER ON TRANSFER DUCT

ONLY

0 HR NFPA 101:8.4

10. MINIMUM EXITS OR EXIT ACCESSES FROM A SPACE OR AREA (NFPA 101)

OCCUPANCY CONDITION PERMITTING ONE EXIT

CONDITION REQUIRING TWO OR

MORE EXITS

CODE

SECTION

ASSEMBLY N/A ALL CONDITIONS 12.2.4.1

BUSINESS 100 FT OR LESS COMMON PATH COMMON PATH EXCEEDS 100 FT 38.2.4

ORDINARY HAZARD

STORAGE

100 FT OR LESS COMMON PATH COMMON PATH EXCEEDS 100 FT 42.2.4

11. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (NFPA 101, TABLE A.7.6)

OCCUPANCY COMMON PATH LIMIT (FT) DEAD END LIMIT (FT)

TRAVEL DISTANCE LIMIT

(FT)

ASSEMBLY 20 20 250

BUSINESS 100 50 300

ORDINARY HAZARD STORAGE 100 100 400

12. MINIMUM EGRESS WIDTHS

COMPONENT REQUIREMENT WIDTH (IN) NFPA 101 SECTION

DOORS IN EGRESS ACCESS MINIMUM 32 7.2.1.2.3.2

CORRIDOR SERVING 50 OR MORE OCCUPANTS MINIMUM 44 12.2.3.8

CORRIDOR SERVING LESS THAN 50 OCCUPANTS MINIMUM 36 7.3.4

LEVEL EGRESS COMPONENTS PER OCCUPANT 0.2 7.3.3.1

13. MINIMUM INTERIOR FINISH RATINGS (NFPA 101, TABLE A.10.2.2)

OCCUPANCY EXITS

EXIT ACCESS

CORRIDORS OTHER SPACES

ASSEMBLY CLASS B CLASS C CLASS C

BUSINESS CLASS C CLASS C CLASS C

STORAGE CLASS C CLASS C CLASS C

14. FIRE SUPPRESSION REQUIREMENTS (UFC 3-600-01 CHAPTER 9)

SPRINKLERS STANDPIPE FIRE EXTINGUISHERS

PROVIDED THROUGHOUT NOT REQUIRED REQUIRED

15. FIRE ALARM REQUIREMENTS (UFC 3-600-01 5-1)

MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION

MANUAL FIRE ALARM PULL STATIONS

PROVIDED AT EXITS, LOCAL OPERATING

CONSOLE FOR VOICE MESSAGING

SPRINKLER SYSTEM WATER FLOW AND

VALVE TAMPER SWITCHES, SPOT SMOKE

DETECTOR ABOVE FIRE ALARM PANELS,

DUCT SMOKE DETECTORS, CARBON

MONOXIDE DETECTION

VOICE MESSAGING AND CLEAR

LENS ALERT STROBES

* EXCEPT AS REQUIRED FOR NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

* PER IBC 602. FIRE SEPARATION DISTANCE IS DEFINED AS THE DISTANCE FROM THE

BUILDING'S FACE TO THE CLOSEST INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET,

ALLEY, OR PUBLIC WAY, OR TO AN IMAGINARY LINE BETWEEN TWO BUILDINGS.

** THE ATCT AND THE MTRACON & RANGE FACILITIES WILL BE CONNECTED. THE WALLS

CONNECTING THE TWO FACILITIES WILL BE CONSTRUCTED AS A 3 HOUR RATED FIRE WALL

CONSISTING OF A DOUBLE WALL SO THE TWO FACILITIES CAN BE CONSIDERED SEPARATE

PER THE BUILDING CODE. AS SUCH, THE ATCT WILL REMAIN AS TYPE IA CONSTRUCTION

WHILE THE MTRACON & RANGE FACILITY WILL REMAIN AS TYPE IIB.

* PER IBC 504 FOR TYPE IIB CONSTRUCTION, SPRINKLER BUILDING. THE MOST

RESTRICTIVE OCCUPANCY LIMITATIONS ARE USED.

* PER IBC 506.2 FOR TYPE IIB CONSTRUCTION, SINGLE STORY, SPRINKLERED

BUILDING. THE MOST RESTRICTIVE OCCUPANCY LIMITATIONS ARE USED.

1. APPLICABLE CODES AND STANDARDS

ABBREVIATIONS TITLE EDITION

IBC INTERNATIONAL BUILDING CODE 2018

NFPA 1 FIRE CODE 2021

NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2022

NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022

NFPA 70 NATIONAL ELECTRICAL CODE 2020

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022

NFPA 75 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT 2020

NFPA 80 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2022

NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS 2021

NFPA 101 LIFE SAFETY CODE 2021

UFC 1-200-01 DOD BUILDING CODE CHANGE 1, 2020

UFC 3-520-05 STATIONARY AND MISSION BATTERIES CHANGE 2, 2020

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES CHANGE 6, 2021

UFC 4-010-01 DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS CHANGE 1, 2020

UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS CHANGE 1, 2010

UFC 4-133-01 AIR TRAFFIC CONTROL AND AIR OPERATIONS FACILITIES CHANGE 2, 2019

16. REQUIRED PLUMBING FIXTURES* (IBC 2902.1 AND UFC 3-420-01)

OCCUPANCY

MALE** FEMALE**

DRINKING

FOUNTAINSWATERCLOSETS

URINALS ALLOWED

TO REPLACE WC LAVATORIES WATERCLOSETS LAVATORIES

ASSEMBLY 2.00 1.34 0.89 2.00 0.59 0.59

BUSINESS 5.55 2.00 3.22 3.37 2.48 3

STORAGE 2.00 1.00 2.00 2.00 2.00 1

TOTAL REQUIRED 9.55 4.34 6.11 7.37 5.07 4.59

TOTAL PROVIDED 5 3 7 4 4 4

*REFER TO PLUMBING FIXTURE CALCULATIONS FOR MORE INFORMATION

** MALE/ FEMALE BALANCE BASED ON 70/30 RATIO

16.1 ACTUAL OCCUPANT - REQUIRED PLUMBING FIXTURES* (IBC 2902.1)

OCCUPANCY

MALE ** FEMALE **

DRINKING

FOUNTAINSWATERCLOSET

URINALS ALLOWED

TO REPLACE LAVATORIES WATERCLOSETS LAVATORIES

ACTUAL

OCCUPANCY

LOAD

4.63 2 2.64 2.75 2.10 3

TOTAL REQUIRED 4.63 2 2.64 2.75 2.10 3

TOTAL PROVIDED 5 3 7 4 4 4

*BASED ON 219 SEATS

** MALE/ FEMALE BALANCE BASED ON 70/30 RATIO

17. FIRE EXTINGUISHER DISTRIBUTION (NFPA 10)

OCCUPANCY

PRIMARY CLASSIFICATION

OF FIRE AND HAZARD

MINIMUM

RATING

MAXIMUM FLOOR

AREA PER A (SF)

MAX TRAVEL

DISTANCE (FT)

ALL CLASS A:C - ORDINARY 2A 1,500 75

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A-

AT

C -C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:2 6:

A

M

GI021

AT

CT

BU

IL

DI

NG

C

O

DE

A

ND

L

IF

E

SA

FE

TY

C

RI

TE

RI

A

LES

12801279

EV SF

1596300

2. TYPE OF CONSTRUCTION (IBC 601)

BUILDING ELEMENT

TYPE OF

CONSTRUCTION

FIRE RESISTANCE

RATING

PRIMARY STRUCTURAL FRAME IA 3 HR

BEARING EXTERIOR WALL IA 3 HR

BEARING INTERIOR WALL IA 3 HR

NON-BEARING EXTERIOR WALL IA 0 HR

NON-BEARING INTERIOR WALL IA 0 HR *

FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IA 2 HR

ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IA 1-1/2 HR**

3. CLASSIFICATION OF OCCUPANCY

AREAS OCCUPANCY (IBC) OCCUPANCY (NFPA 101)

CAB, TRAINING, BREAK, OFFICE, UTILITY,

RESTROOM, CIRCULATION

BUSINESS, GROUP B SECTION

304.1

BUSINESS SECTION 6.1.11

4. BUILDING ALLOWABLE AREA (IBC 506.2)

OCCUPANCY ALLOWABLE AREA (SF)

B UNLIMITED

5. MODIFIED ALLOWABLE HEIGHT (IBC 504)

OCCUPANCY HEIGHT LIMIT (FT / STORY)

B UNLIMITED

6. NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

COMPONENT/ AREA REQUIRED RATING CODE SECTION

SHAFT ENCLOSED CONNECTING 4 OR MORE

STORIES

2 HOUR BARRIER NFPA 101: 8.6.5

ELEVATOR MACHINE ROOM 2 HOUR BARRIER (2 HOUR BARRIER

PROVIDED)

UFC 3-600-01: 4-16.2.1

ELECTRICAL ROOM W/ TRANSFORMER > 112-1/2

kVA

1 HOUR BARRIER NFPA 70: 450.21(B)

FIRE PUMP ROOM 2 HOUR BARRIER NFPA 20:4.14.1.1.1

MECHANICAL ROOM W/ BOILER 0 HOUR SMOKE PARTITION NFPA 101: 38.3.2.1

COMM ROOMS 1 HOUR FIRE BARRIER UFC 4-133-01:3-6.7.1

ELEVATOR SHAFT 2 HOUR BARRIER IBC 3002.1

7. BUILDING SEPARATION (IBC TABLE 602)

OCCUPANCY

FIRE SEPARATION

DISTANCE (FT)*

FIRE RESISTIVE RATING

OF EXTERIOR WALL

B <30 1 HR **

B ≥ 30 NONE **

8. OPENING PROTECTION FOR FIRE AND SMOKE RESISTIVE CONSTRUCTION

COMPONENT DOORS DUCT PENETRATIONS

OTHER

PENETRATIONS

* CODE SECTION

2 HR FIRE BARRIER FOR MEANS

OF EGRESS (INCLUDING

STAIRWELLS)

1-1/2 HR NOT PERMITTED 2 HR NFPA 101: 7.1.3.2,

8.3.3

2 HR FIRE BARRIER FOR PUMP

ROOM

1-1/2 HR 1-1/2 HR FIRE DAMPER 2 HR NFPA 20: 4.14.1.1.1

3 HR FIRE WALL 3 HR NOT PERMITTED 3 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101: 8.3.3

OTHER 2 HR FIRE BARRIERS* 1-1/2 HR 1-1/2 HR FIRE DAMPER 2 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101: 8.3.3

1 HR FIRE BARRIER FOR MEANS

OF EGRESS (INCLUDING

STAIRWELLS)

1 HR NOT PERMITTED 1 HR NFPA 101: 7.1.3.2,

8.3.3

OTHER 1 HR FIRE BARRIERS 3/4 HR 0 HOUR DUCT, 1-1/2 HR AIR TRANSFER,

1-1/2 HR FIRE/SMOKE DAMPER FOR DUCT

PENETRATIONS IN SERVER ROOMS PER

NFPA 75

1 HR NFPA 90A: 5.3.1,

5.4.1, NFPA 101:

8.3.3, NFPA 75: 6.6.3

0 HR SMOKE PARTITION 0 HR (SELF

CLOSING)

SMOKE DAMPER ON TRANSFER DUCT

ONLY

0 HR NFPA 101:8.4

10. MINIMUM EXITS OR EXIT ACCESSES FROM A SPACE OR AREA (NFPA 101)

OCCUPANCY CONDITION PERMITTING ONE EXIT

CONDITION REQUIRING TWO OR

MORE EXITS CODE SECTION

BUSINESS 100 FT OR LESS COMMON PATH COMMON PATH EXCEEDS 100 FT 38.2.4

11. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (NFPA 101, TABLE A.7.6)

OCCUPANCY COMMON PATH LIMIT (FT) DEAD END LIMIT (FT)

TRAVEL DISTANCE LIMIT

(FT)

BUSINESS 100 50 300

12. MINIMUM EGRESS WIDTHS

COMPONENT REQUIREMENT WIDTH (IN) NFPA 101 SECTION

DOORS IN EGRESS ACCESS MINIMUM 32 7.2.1.2.3.2

CORRIDOR SERVING 50 OR MORE OCCUPANTS MINIMUM 44 12.2.3.8

CORRIDOR SERVING LESS THAN 50 OCCUPANTS MINIMUM 36 7.3.4

STAIRS IN EGRESS ACCESS MINIMUM 44 7.2.2.2.1.2

LEVEL EGRESS COMPONENTS PER OCCUPANT 0.2 7.3.3.1

STAIRWAYS PER OCCUPANT 0.3 7.3.3.1

13. MINIMUM INTERIOR FINISH RATINGS (UFC 4-133-01)

OCCUPANCY EXITS

EXIT ACCESS

CORRIDORS OTHER SPACES

BUSINESS - ATCT CLASS B CLASS B CLASS B

14. FIRE SUPPRESSION REQUIREMENTS (UFC 3-600-01 CHAPTER 9)

SPRINKLERS STANDPIPE FIRE EXTINGUISHERS

PROVIDED THROUGHOUT PROVIDED IN EXIT STAIRWAY REQUIRED

15. FIRE ALARM REQUIREMENTS (UFC 3-600-01 CHAPTER 9)

MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION

MANUAL FIRE ALARM PULL STATIONS

PROVIDED AT EXITS, LOCAL OPERATING

CONSOLE FOR VOICE MESSAGING

SPRINKLER SYSTEM WATER FLOW AND

VALVE TAMPER SWITCHES, SPOT SMOKE

DETECTOR ABOVE FIRE ALARM PANELS,

DUCT SMOKE DETECTORS, CARBON

MONOXIDE DETECTION, SMOKE DETECTION

THROUGHOUT ATCT

VOICE MESSAGING AND CLEAR LENS ALERT

STROBES. BLUE FLASHING INCANDESCENT

LIGHT AND LED TEXT SIGN PROVIDED AT

CAB EXIT.

* EXCEPT AS REQUIRED FOR NFPA 101 PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION

** NO RATING REQUIRED FOR ROOF CONSTRUCTION AT LEAST 20 FT ABOVE THE FLOOR BELOW

* PER IBC 602. FIRE SEPARATION DISTANCE IS DEFINED AS THE DISTANCE FROM THE BUILDING’S FACE TO THE CLOSEST INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET, ALLEY, OR PUBLIC

WAY, OR TO AN IMAGINARY LINE BETWEEN TWO BUILDINGS.

** THE ATCT AND THE MTRACON & RANGE FACILITIES WILL BE CONNECTED. THE WALLS

CONNECTING THE TWO FACILITIES WILL BE CONSTRUCTED AS A 3 HOUR RATED FIRE WALL

CONSISTING OF A DOUBLE WALL SO THE TWO FACILITIES CAN BE CONSIDERED SEPARATE PER THE

BUILDING CODE. AS SUCH, THE ATCT WILL REMAIN AS TYPE IA CONSTRUCTION WHILE THE

MTRACON & RANGE FACILITY WILL REMAIN AS TYPE IIB.

1. APPLICABLE CODES AND STANDARDS

ABBREVIATIONS TITLE EDITION

IBC INTERNATIONAL BUILDING CODE 2018

NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2022

NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022

NFPA 14 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS 2019

NFPA 20 STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION 2022

NFPA 70 NATIONAL ELECTRICAL CODE 2020

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022

NFPA 75 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT 2020

NFPA 80 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2022

NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND VENTILATING

SYSTEMS

NFPA 101 LIFE SAFETY CODE 2021

UFC 1-200-01 DOD BUILDING CODE CHANGE 1, 2020

UFC 3-490-06 ELEVATORS CHANGE 1, 2021

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES CHANGE 6, 2021

UFC 4-010-01 DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS CHANGE 1, 2020

UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS CHANGE 1, 2010

UFC 4-133-01 AIR TRAFFIC CONTROL AND AIR OPERATIONS FACILITIES CHANGE 2, 2019

16. REQUIRED PLUMBING FIXTURES* (IBC 2902.1)

OCCUPANCY

MALE** FEMALE**

DRINKING

FOUNTAINSWATERCLOSETS

URINALS ALLOWED TO

REPLACE WC LAVATORIES WATERCLOSETS LAVATORIES

ASSEMBLY 1.00 0.67 0.19 1.00 0.12 0.12

BUSINESS 1.25 0 1.54 1.50 1.69 0.12

FACTORY 1.86 0.62 1.86 1.24 1.24 0.12

STORAGE 1.00 0 1.00 1.00 1.00 0.12

TOTAL

REQUIRED

5.11 1.29 4.59 4.74 4.05 0.50

TOTAL

PROVIDED

1.00 0 1.00 1.00 1.00 0

*REFER TO PLUMBING FIXTURE CALCULATIONS FOR MORE INFORMATION

** MALE/ FEMALE BALANCE BASED ON 70/30 RATIO

9. OCCUPANT LOAD CALCULATIONS (NFPA 101, UFC 3-600-01)

NFPA 101 Use Area SF.PerPerson OccupancySFType

NFPA No.

Of

Occupants

FLOOR 1

BUILDING EQUIPMENT - 500 SF/ PERSON 686 SF 500 GROSS 2

BUSINESS - 150 SF/PERSON 447 SF 150 GROSS 4

IT EQUIPMENT - 300 SF/ PERSON 112 SF 300 GROSS 1

FLOOR 3

BUSINESS - 150 SF/PERSON 39 SF 150 GROSS 1

FLOOR 5

BUSINESS - 150 SF/PERSON 39 SF 150 GROSS 1

FLOOR 7

BUSINESS - 150 SF/PERSON 48 SF 150 GROSS 1

IT EQUIPMENT - 300 SF/ PERSON 232 SF 300 GROSS 1

FLOOR 8

BUSINESS - 150 SF/PERSON 516 SF 150 GROSS 4

FLOOR 9

ATCT OBSERVATION LEVEL - 40 SF/PERSON 466 SF 40 GROSS 12

BUSINESS - 150 SF/PERSON 46 SF 150 GROSS 1

FLOOR 10

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT FIXED

SEATING - 15 SF/PERSON

168 SF 15 NET 12

BUSINESS - 150 SF/PERSON 218 SF 150 GROSS 2

FLOOR 11

BUILDING EQUIPMENT - 500 SF/ PERSON 507 SF 500 GROSS 1

BUSINESS - 150 SF/PERSON 79 SF 150 GROSS 1

CAB SLAB/CATWALK FLOOR 12

ATCT OBSERVATION LEVEL - 40 SF/PERSON 598 SF 40 GROSS 15

Grand total 4201 SF

9.1 OCCUPANT LOAD SUMMARY AND MINIMUM EXITS FROM FLOOR

FLOOR OCCUPANTS

REQUIRED EXITS

(NFPA 101) REQUIRED EXIT SEPARATION

LEVEL 1 7 1 (7.4.1.1) N/A

LEVEL 2 THRU 12 15 (MAX) 1 (11.3.4.4.1) N/A

*THE LIFE SAFETY CODE PERMITS ONE EXIT FROM A TOWER THAT MEETS THE PRESCRIBED CRITERIA (15 MAXIMUM

OCCUPANTS)

ACTUAL OCCUPANT LOAD

6- ONE CREW, INCLUDING TRAINESS

6 - 2ND CREW ARRIVING AT SHIFT CHANGE

3- STAFF: CHIEF CONTROLLER, ASST. CHIEF CONTROLLER, TRAINER (MONDAY-FRIDAY)

15- MAXIMUM OCCUPANT LOAD AT SHIFT CHANGE MONDAY - FRIDAY

16.1 ACTUAL OCCUPANT - REQUIRED PLUMBING FIXTURES* (IBC 2902.1)

OCCUPANCY

MALE** FEMALE**

DRINKING FOUNTAINSWATERCLOSET

URINALS ALLOWED

TO REPLACE LAVATORIES WATERCLOSET LAVATORIES

ACTUAL OCCUPANCY

LOAD

0.82 0.91 0.88 0.88 0.93 1.00

TOTAL REQUIRED 0.82 0.91 0.88 0.88 0.93 1.00

TOTAL PROVIDED 1.00 0.00 1.00 1.00 1.00 0.00

*REFER TO PLUMBING FIXTURE CALCULATIONS FOR MORE INFORMATION

** MALE/ FEMALE BALANCE BASED ON 70/30 RATIO

*FOR CABLE THROUGH PENETRATIONS OF RATED WALL AND/OR FLOOR ASSEMBLIES, PROVIDE FIRESTOPPING SYSTEM THAT ALLOWS REPEATED REMOVAL AND REPLACEMENT (WITHOUT SPECIAL TOOLS) AS NECESSARY FOR THE CABLE INSTALLATION AND

TO SUPPORT CHANGING REQUIREMENTS.

17. FIRE EXTINGUISHER DISTRIBUTION (NFPA 10)

OCCUPANCY

PRIMARY CLASSIFICATION

OF FIRE AND HAZARD

MINIMUM

RATING

MAXIMUM FLOOR

AREA PER A (SF)

MAX TRAVEL

DISTANCE (FT)

ALL CLASS A:C - ORDINARY 2A 1,500 75

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

CP

SS SSS

CPSS S

SS S

S S

S S

S S

S S

S S

S S

S S

S S

S S

S S

SS SS S

S

S S

SS SS

SS SSS

S S

S S

S S

S S

S

S

S

SCP

SS S

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE PARTITION

CLEAR WIDTH

EXIT CAPACITY

OCCUPANTS SERVED

COMMON PATH

OF TRAVEL

TRAVEL

DISTANCE

EGRESS

PATH

COMMON PATH

TERMINATION

POINT

EXIT DOOR

REQUIRED WIDTH

36"

22"

1. REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL

INFORMATION REGARDING SYMBOLS AND

ABBREVIATIONS.

2. REFER TO GI001 FOR LIFE SAFETY NARRATIVE AND

BUILDING CODE ANALYSIS.

3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR

LOCATION OF EXIT SIGNS AND EMERGENCY

LIGHTING.

4. REFER TO THE FIRE SUPPRESSION AND ALARM

PLANS FOR LOCATION OF FIRE PROTECTION

DEVICES.

DOOR EGRESS TAG

FIRE RESISTIVE CONSTRUCTION

EGRESS PATH

TERMINATION OF

DEAD END

CORRIDOR

DEAD END DISTANCE

DEAD END CORRIDOR

100'

100'CP:666'

44" 44"

STAIR EGRESS TAG

A:B:C: TYPE

DRY CHEMICAL

4A-20B-C

PORTABLE FIRE EXTINGUISHERS

FE:SR

EXTINGUISHER TYPE

EXTINGUISHER

MOUNTING

-FE: FIRE EXTINGUISHER

-SR: SEMI-RECESSED CABINET

-BR: BRACKET MOUNTED

-SM: SURFACE MOUNT CABINET

-FR: FULLY RECESSED CABINET

GENERAL NOTES NFPA OCCUPANCY

USE HATCH LEGEND

MEN'S

WOMEN'S

ELEC

MECHANICAL

BASH

WX CLASSROOM

BUNK ROOM

BUNK ROOM

WX SUPERVISOR

WX SNCOIC

WX OIC

ELEVATOR

ELEV EQUIP

STAIR

KITCHEN / BREAK

FLIGHT PLANNING ROOM

BUNK ROOM

BUNK / LOCKER

F/C SNCOIC

F/C CIV

ODO

STAIR

LOUNGE

TOILET / SHOWER

JANITOR

TOILET / SHOWER

DISPATCH

BREAK

LOCKER

VAL SUPERVISOR

MEN

WOMEN

WOMEN

MEN

STORAGE BAY

VESTIBULE

PRE-SCREEN

POST-SCREEN

MECH

AIRFIELD LIGHTS

CORRIDOR

CORRIDOR

VESTIBULE

COMM

ENTRY

F/C

WX FLOOR

TOILET / SHOWER

QUIET

ADMIN STOR

BASE NODE

MOTHERS RM

WEAPON STOR

UPS

ASOS

WX SIPR

ASSEMBLY USE: CONCENTRATED, WITHOUT FIXED

SEATING - 7 SF/PERSON

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT FIXED

SEATING - 15 SF/ PERSON

BUILDING EQUIPMENT - 500 SF/PERSON

BUNKS - 50 SF/PERSON

BUSINESS - 150 SF/ PERSON

CLASSROOM - 20 SF/PERSON

IT EQUIPMENT - 300 SF/PERSON

LOCKER - 50 SF/PERSON

STORAGE - 500 SF/PERSON

68.0" 32"

33.5" 32"

68.0" 32"

68.0" 32"

68.0" 32"

68.0" 32"

33.5" 32"

68.0" 32"

68.0" 32"

33.5" 32"

FE:BR

C P:

68.0" 32"

33.5" 32"

33.5" 32"

33.5" 32"

C P:

68.0" 32"

33.5" 32"

39.5" 32"

FE:SR

FE

:S

R

FE

:S

R

FE

:S

R

FE

:S

R

FE

:S

R

FE:SR

FE

:B

R

FE

:B

R

FE:BR

FE:BRFE

:B

R

FE:BR

FE:BR

FE

:B

R

FE:BR

FE

:B

R

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A- O

PS

-C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:3 0:

A

M

GI101

AI

R

O

PS

LI

FE

S

AF

ET

Y

PL

AN

FI

RS

T

FL

O O

R

LES

12801280

AL SF

1596300

1/8" = 1'-0"B3 AIR OPS - LIFE SAFETY PLAN - FIRST FLOOR

PLAN

NORTH

4' 8' 16'0'

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

SS

S

S

S

S S

S S

CP

CP

SS SSS

ELEVATOR

STAIR

ATCO

CHIEF

MGYSGT

OSPO

CONFERENCE ROOM

CORRIDOR

RECEPTION

WOMEN'S

JAN

NAVAIR EASU

FOD CELL

AOPS

STORAGE

COMM

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT

FIXED SEATING - 15 SF/ PERSON

BUILDING EQUIPMENT - 500 SF/PERSON

BUSINESS - 150 SF/ PERSON

IT EQUIPMENT - 300 SF/PERSON

STORAGE - 500 SF/PERSON

33.5" 32"

44" 44"

44" 44"

77'CP:0'

MEN'S

KITCHEN

210A

EQUIP. CLOSET

201A

33.5" 32"

STAIR

FE:SR

FE

:S

R

1 HR FIRE BARRIER

CLEAR WIDTH

EXIT CAPACITY

OCCUPANTS SERVED

COMMON PATH

OF TRAVEL

TRAVEL

DISTANCE

EGRESS

PATH

COMMON PATH

TERMINATION

POINT

EXIT DOOR

REQUIRED WIDTH

36"

22"

1. REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL

INFORMATION REGARDING SYMBOLS AND ABBREVIATIONS.

2. REFER TO GI001 FOR LIFE SAFETY NARRATIVE AND BUILDING

CODE ANALYSIS.

3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR LOCATION

OF EXIT SIGNS AND EMERGENCY LIGHTING.

4. REFER TO THE FIRE SUPPRESSION AND ALARM PLANS FOR

LOCATION OF FIRE PROTECTION DEVICES.

DOOR EGRESS TAG

FIRE RESISTIVE CONSTRUCTION

EGRESS PATH

TERMINATION OF

DEAD END

CORRIDOR

DEAD END DISTANCE

DEAD END CORRIDOR

100'

100'CP:666'

44" 44"

STAIR EGRESS TAG

0 HR SMOKE BARRIER

GENERAL NOTES

NFPA OCCUPANCY

USE HATCH LEGEND

A:B:C: TYPE

DRY CHEMICAL

4A-20B-C

PORTABLE FIRE EXTINGUISHERS

FE:SR

EXTINGUISHER TYPE

EXTINGUISHER

MOUNTING

-FE: FIRE EXTINGUISHER

-SR: SEMI-RECESSED CABINET

-BR: BRACKET MOUNTED

-SM: SURFACE MOUNT CABINET

-FR: FULLY RECESSED CABINET

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A- O

PS

-C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:3 0:

A

M

GI102

AI

R

O

PS

LI

FE

S

AF

ET

Y

PL

AN

SE

CO

ND

F

LO

O

R

LES

12801281

AL SF

1596300

1/8" = 1'-0"B3 AIR OPS - LIFE SAFETY PLAN - SECOND FLOOR

PLAN

NORTH

4' 8' 16'0'

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

CP CP

SS SSSSSSSSS

S S

S S

S

SS SSS

CP

3 4 5 6 71

A

B

C

D

E

G

ATC IFR ROOM

OFFICE

ATCM SUPPLY BAY

123 CORRIDOR

SUPPLY DESK

BREAK ROOM

MEN

OFFICE

OFFICE

OFFICE

STORAGE

STORAGE

CLASSROOM

OFFICE

ENTRANCE

ELECTRICAL

UPS

MECHANICAL

ATCFO

ATC SNCOIC

ATC TRAINING OFFICE

ATCM UNION OFFICE

ATCM-SNOIC

ATC ADMIN STORAGE

STARS SIMULATOR

ATCM-OIC

ATC CONFERENCE ROOM

ATCM CLASSROOM

ATC BREAK ROOM

KITCHEN

ATCM BREAK ROOM

FWO

117 MOTHERS ROOM

JANITOR

TEST EQUIP.

WOMEN

MENS

VESTIBULE

45.5" 32"

68.0" 32"

68.0" 32"

68.0" 32"

68.0" 32"

FE:BR

FE:BR

161'CP:52'

C

P:

239'CP:94'

F

SET

EQUIPMENT ROOM

OFFICE

45.5" 32"

CORRIDOR

ATC UNION OFFICE

COMM

ATCM STORAGE

TOWER FOOT PRINT

ALL WALLS ARE 1 HR RATING

REFER TO SHEET GI121 ATCT LIFE SAFETY PLAN

ASSEMBLY USE: LESS CONCENTRATED,

WITHOUT FIXED SEATING - 15 SF/PERSON

BUILDING EQUIPMENT - 500 SF/ PERSON

BUSINESS - 150 SF/ PERSON

CLASSROOM - 20 SF/ PERSON

IT EQUIPMENT - 300 SF/ PERSON

KITCHEN - 100 SF/ PERSON

LOCKER - 50 SF/ PERSON

STORAGE - 500 SF/PERSON

OFFICE/OPS

LOCKERS

ATCM SERVER

JANITOR

OPEN OFFICE

RANGE CONTROL FACILITY

STORAGE

WOMEN

OFFICE

RADIO STORAGE

ATCM HAZMAT STORAGE

ATCM EQUIPMENT

FE:BR

4'

- 0

4.72.7 167 33.5" 32"

110 8

FE:BR

FE:BR

FE

:B

R

FE:BR FE:BR FE:BR

FE:SR

FE:SR

FE

:S

R

FE

:S

R

FE

:S

R

SMOKE PARTITION

1 HR FIRE BARRIER

2 HR FIRE BARRIER

3HR FIRE WALL

CLEAR WIDTH

EXIT CAPACITY

OCCUPANTS SERVED

COMMON PATH

OF TRAVEL

TRAVEL

DISTANCE

EGRESS

PATH

COMMON PATH

TERMINATION

POINT

EXIT

DOOR

REQUIRED WIDTH

36"

22"

1. REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL

INFORMATION REGARDING SYMBOLS AND

ABBREVIATIONS.

2. REFER TO GI011 FOR LIFE SAFETY NARRATIVE AND

BUILDING CODE ANALYSIS.

3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR

LOCATION OF EXIT SIGNS AND EMERGENCY

LIGHTING.

4. REFER TO THE FIRE SUPPRESSION AND ALARM

PLANS FOR LOCATION OF FIRE PROTECTION

DEVICES.

5. FINAL LOCATIONS OF FIRE EXTINGUISHERS SHALL BE

APPROVED BY THE AHJ PRIOR TO INSTALLATION.

DOOR EGRESS TAG

FIRE AND SMOKE RESISTIVE CONSTRUCTION

EGRESS PATH

TERMINATION OF

DEAD END

CORRIDOR

DEAD END DISTANCE

DEAD END CORRIDOR

100'

100'CP:666'

CLEAN AGENT

2A:10B:C

PORTABLE FIRE EXTINGUISHERS (GFGI)

FE:SR

EXTINGUISHER TYPE

EXTINGUISHER

MOUNTING

-FE: FIRE EXTINGUISHER

-BR: BRACKET MOUNTED

-SR: SEMI-RECESSED CABINET

A:B:C: TYPE DRY CHEMICAL

4A-20B-C

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D

EP

AR

TM

EN

T

O F

TH

E

N

AV

Y N

AV

AL

F

AC

IL

IT

IE

S

EN

G

IN

EE

R

IN

G C

O M

M

AN

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

M

ID

-A

TL

A N

TI

C

M

AR

IN

E

C O

R

PS

IP

T

N

AV

AL

S

TA

TI

O N

N

O R

FO

LK

, V A

EJA

M C

AS

C

H

ER

R Y

PO

IN

T C

H

ER

R Y

PO

IN

T, N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

FY

P -2

A

TC

T

O W

E R

A N

D A

IR

O

P E

R A

TI

O

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

FI

LE

N

AM

E:

PL

OT

TE

D:

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C :\R ev it_

Pr oj ec ts

\B

LD

G -P

8-

0-

A- R

AN

G

E- C en tra l_ pg re go ry bu rn sm cd

.c om

.rv t

8/

/2

:3 2:

A

M

GI111

M

TR

AC

O

N -L

IF

E

SA

FE

TY

P

LA

N

LES

12801282

AL SF

1596300

1/8" = 1'-0"A1 MTRACON - LIFE SAFETY PLAN

PLAN

NORTH

4' 8' 16'0'

GENERAL NOTES

NFPA OCCUPANCY

USE HATCH LEGEND

SY

M

DE

S C

RI

PT

I O N

DA

TE

AP

PR

IS

SU

ED

F

OR

B

ID

/18

SS SSS

S

S S

SS S

SS

S

S S

UP

S

S

DN

REF.

S

UP

DN

SMOKE PARTITION

1 HR FIRE BARRIER

2 HR FIRE BARRIER

3 HR FIRE WALL

CLEAR WIDTH

EXIT CAPACITY

OCCUPANTS SERVED

COMMON PATH

OF TRAVEL

TRAVEL

DISTANCE

EGRESS

PATH

COMMON PATH

TERMINATION

POINT

EXIT DOOR

REQUIRED WIDTH

36"

22"

1. REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL INFORMATION

REGARDING SYMBOLS AND ABBREVIATIONS.

2. REFER TO GI021 FOR LIFE SAFETY NARRATIVE AND BUILDING CODE

ANALYSIS.

3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR LOCATION OF EXIT

SIGNS AND EMERGENCY LIGHTING.

4. REFER TO THE FIRE SUPPRESSION AND ALARM PLANS FOR LOCATION

OF FIRE PROTECTION DEVICES.

5. FINAL LOCATIONS OF FIRE EXTINGUISHERS SHALL BE APPROVED BY

THE AHJ PRIOR TO INSTALLATION.

DOOR EGRESS TAG

FIRE AND SMOKE RESISTIVE CONSTRUCTION

EGRESS PATH

TERMINATION OF

DEAD END

CORRIDOR

DEAD END DISTANCE

DEAD END CORRIDOR

100'

100'CP:666'

CLEAN AGENT 2A:10B:C

PORTABLE FIRE EXTINGUISHERS

FE:SR

EXTINGUISHER TYPE

EXTINGUISHER

MOUNTING

-FE: FIRE EXTINGUISHER

-SR: SEMI-RECESSED CABINET

-BR: BRACKET MOUNTED

-SM: SURFACE MOUNT CABINET

-FR: FULLY RECESSED CABINET

44.5"

44"

STAIR EGRESS TAG

A:B:C: TYPE DRY CHEMICAL 4A-20B-C

ELEVATOR

EMERGENCY COMMAND CENTER

STAIRS

ELECTRICAL

FP

MECHANICAL

COMM

68.0"

32"

68.0"

32"

JANITOR

CORRIDOR

33.5"

32"

VESTIBULE

2 HR RATED ENCLOSURE AT CHASE ABOVE

FE:BR

FE:B

R

FE:B

R

FE:BR

ELEVATOR

CORRIDOR

STAIRS

SIMULATOR

33.5"

32"

44"

44"

41'

F E :B R

CAB ADMIN

ELEVATOR

CORRIDOR

STAIRS

33.5"

32"

44"

44"

41'

F E :B R

CORRIDOR

21102

STAIRS

21103

FE:BR

44"

44"

33.5"

32"

41'

MECHANICAL ROOM

21104

ELEVATOR EQUIPMENT

21201

STAIR

21105

FE:BR

CAB

21205

FE:BR

ASSEMBLY USE: LESS CONCENTRATED, WITHOUT

FIXED SEATING - 15 SF/PERSON

ATCT OBSERVATION LEVEL - 40 SF/PERSON

BUILDING EQUIPMENT - 500 SF/ PERSON

BUSINESS - 150 SF/PERSON

IT EQUIPMENT - 300 SF/ PERSON

STORAGE - 500 SF/ PERSON

BREAKROOM

21004

TOILET

21006

TOILET

21005

ELEVATOR

21001

CORRIDOR

21002

STAIRS

21003

39'

33.5"

32"

44"

44"

CHASE

ACCESS

TOILET ROOM CIRCULATION

F E :B R

2 HR RATED

HORIZONTAL

SEPARATION

AT TOP OF

ELEVATOR

SHAFT

33.5"

32"

COMM

FE:BR

33.5"

32"

44"

44"

ELEVATOR

STAIRS

CORRIDOR

CORRIDOR

ELEVATOR

STAIRS

44"

44"

33.5"

32"

F E :B R

SATISFACTORY TO

APPROVED

ACTIVITY

DATE

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y N

A V

A L

F A

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

C O

M M

A N

D

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

N A V A L F A C

IL

IT

IE

S E N G

IN

E E R

IN

G C O M M A N D M

ID

-A T L A N T

IC

M A

R

IN

E C

O R

P S

I P

T N

A V

A L

S T

A T

IO

N

N

O R

F O

L K

V

A

EJA

M C

A S

C H

E R

R Y

P O

IN

T

C H

E R

R Y

P O

IN

T

N

C

AS NOTED

1317 EXECUTIVE BLVD.

SUITE 300

CHESAPEAKE, VA 23320

F Y P -2 A T C T O W E R A N D A

IR

O P E R A T

IO

N S

DRAWFORM REVISION: 12 APRIL 2018

UNCLASSIFIED

UNCLASSIFIED

U N

C

LA

S S

IF

IE

D

FI

LE

N A

M E

P

LO

TT

E D

CJC/KDB

DSN

ALG

SAT-TO FORM SIGNED BY

DON ELLIOT 12/19/19

C

R e v it P ro je c ts

\B L D

G -P

-1

-A

-A T

C -C e n tr a l_

C to sl o s ki e b u rn sm c d .c o m

.r v t

/2

/2

:2 :4

P

M

GI121

A

TC

T

LI

F E S A F E

TY

P

LA

N

LES

12801283

AL SF

1596300

1/8" = 1'-0" C1

FLOOR 1

1/8" = 1'-0" B1

FLOOR 8

1/8" = 1'-0"

B2

FLOOR 9

1/8" = 1'-0" A1

FLOOR 11

1/8" = 1'-0"

A3

CAB SLAB/CATWALK FLOOR 12

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

GENERAL NOTES

1/8" = 1'-0" C2

TYPICAL BLIND SHAFT - FLOOR 2, 4 AND 6

1/8" = 1'-0" B3

FLOOR 10

PLAN

NORTH

4' 8' 16'0'

1/8" = 1'-0" A2

FLOOR 11.5

1/8" = 1'-0" C4

FLOOR 7

PLAN

NORTH

4' 8' 16'0'

PLAN

NORTH

4' 8' 16'0'

NFPA OCCUPANCY USE HATCH LEGEND

PLAN

NORTH

4' 8' 16'0'1/8" = 1'-0" C3

FLOOR 3 AND 5

S Y

M D

E S

C R

IP

TI

O N

D A

TE

A

P P

R

IS

S U

E D

F O

R B

ID

/1 8/

GI001 - AIR OPS - BUILDING CODE AND LIFE SAFETY CRITERIA
GI011 - MTRACON - BUILDING CODE AND LIFE SAFETY CRITERIA
GI021 - ATCT - BUILDING CODE AND LIFE SAFETY CRITERIA
GI101 - AIR OPS - LIFE SAFETY PLAN - FIRST FLOOR
GI102 - AIR OPS - LIFE SAFETY PLAN - SECOND FLOOR
GI111 - MTRACON - LIFE SAFETY PLAN
GI121 - ATCT - LIFE SAFETY PLAN

2022-10-28T12:09:22-0400

2022-10-28T12:09:35-0400

2022-10-28T12:09:36-0400

2022-10-28T12:09:37-0400

2022-10-28T12:09:37-0400

2022-10-28T12:09:38-0400

2022-10-28T12:09:39-0400

2022-10-28T12:10:07-0400

2022-10-28T12:10:25-0400

2022-10-28T12:10:26-0400

2022-10-28T12:10:27-0400

2022-10-28T12:10:27-0400

2022-10-28T12:10:28-0400

2022-10-28T12:10:29-0400

2022-11-07T15:21:00-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:16-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:16-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:17-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:18-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:18-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:19-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:37-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:52-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:52-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:53-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:54-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:55-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2022-11-07T15:21:56-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .