About this file

This solicitation is for an Indefinite Delivery/Indefinite Quantity Multiple Award Contract for environmental services and remedial actions at facilities located primarily in the Naval Facilities Engineering Command Mid-Atlantic Great Lakes Area of Responsibility. The contract has a one year base period and four one-year option periods, with a maximum total value of $30 million to be awarded across three to five basic contracts. Individual task orders will range from $50,000 to $250,000 and will be competed among awardees. The North American Industry Classification System code for this procurement is 562910, Environmental Remediation Services. This procurement is set aside 100% for competitive Service Disabled Veteran Owned Small Businesses located in the Midwest region. Services will include sites regulated by CERCLA, RCRA, UST, Clean Water Act, Clean Air Act, and other environmental programs requiring corrective action, mitigation, sampling, inspection, studies, or remedial action, with a focus on Naval Station Great Lakes and Naval Support Activity Crane facilities.

View the file

Other files

File Type Posted
Amendment 0008.pdf PDF
Amendment 0007.pdf PDF
Amendment 0006.pdf PDF
Fig 1_Lake Michigan Sampling Locations.pdf PDF
Attachment J2 REVISED 03.09.22 Price Proposal Form.xlsx XLSX spreadsheet
UST_drawings_1.pdf PDF
Fig 2_Skokie River Sampling Locations.pdf PDF
Amendment 0005.pdf PDF
61197 - Naval Station Great Lakes - Building 1 - Great Lakes - IL - 7212021 - Final.pdf PDF
61200 - Naval Station Great Lakes - Building 3402 - Great Lakes - IL - 7222021 - Final.pdf PDF
61196 - Naval Station Great Lakes - Building 400 - Great Lakes - IL - 7212021 - Final.pdf PDF
61197 - Naval Station Great Lakes - Building 1 - Great Lakes - IL - 7212021 - Final.pdf PDF
Amendment 0004.pdf PDF
N4004821R2534 Site Visit Sign In Sheet.pdf PDF
61199 - Naval Station Great Lakes - 8150 - Final.pdf PDF
FINAL_NAVSTA Great Lakes SPCC Plan - August 2021.pdf PDF
SWPPP 2020 IEPA Submittal_FINAL.pdf PDF
157304_NSGreatLakes_AnnualSampling2021_LtrRpt_FNL.pdf PDF
REVISED Attachment J2 Price Proposal Form.xlsx XLSX spreadsheet
Amendment 0003.pdf PDF
2016EPCRA Report(Period Jan-Dec2016) Combined Appendices.pdf PDF
RY2020_Annual_TierIIReport_NavalStationGreatLakes.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
ATTACHMENT J3 Change Order Mark Up.pdf PDF
Attachment J2 Price Proposal Form.xlsx XLSX spreadsheet
ATTACHMENT J5 Key Personnel.pdf PDF
J6 SCA Wage Determination.pdf PDF
N4008521R2534.pdf PDF
ATTACHMENT J4 Responsibility Eval Form.pdf PDF
J9 PTO 001 Combined Enclosures.pdf PDF
ATTACHMENT J7 PPQ.docx DOCX document
Attachment J8 Project Data Form.docx DOCX document
J1 PTO 001 Scope of Work.pdf PDF
Show all 34

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Dear r

If you

Resp

FG/

R u have any q pectfully subm

Ple

PO

P R O

RE:

uestions rega mitted, ase keep a

Box 80265 Sau

F E S S I O arding the atta a copy of th ukville, WI 530

O N A L T ached results he reports o

80 www.pro

A N K I N V s, please conta on site for tanic.com

V E S T I G A act your acco inspectors

(262) 268‐1

A T I O N C ount manager

C O R P .

r at (262) 268

8-1150.

PWD GREAT LAKES

Michelle Mosso

Building 1506

2021-07-22 Naval Station Great Lakes

NAVFAC MID ATLANTIC

aek

Thank you for choosing Protanic. We appreciate your business and will do our best to earn it every time. Below you will find a list of testing and/or inspections performed at the above mentioned location. Please review the following pages for results.

Ms. Mosso, Great Lakes, IL 60088

Results of Work Performed

GREAT LAKES, IL 60088-2814

2021-07-28

PO Box 80265 Saukville, WI 53080 www.protanic.com (262) 268-1150

P R O F E S S I O N A L T A N K I N V E S T I G A T I O N C O R P

REPAIR REQUEST

July 28, 2021

NAVFAC MID ATLANTIC

Attn: Michelle Mosso PWD Great Lakes Great Lakes, IL 60088-2814

Re: Sensor Fail / Work Performed July 22, 2021 Naval Station Great Lakes Building 1506 Great Lakes, IL 60088

Dear Ms. Mosso, While performing testing procedures at the above mentioned location, the Protanic test technician reported the following:

1. The E-85 interstitial sensor FAILS; the sensor does not function properly. The sensor is in ‘Sensor Out’ alarm and is mislabeled in the tank monitor.

2. A contractor should be employed to address the issue.

3. Upon completion of repairs, contact Protanic to schedule a retest of the E-85 interstitial sensor.

4. The technician replaced and installed one (1) stage one adapter cap for the E-85 tank;

the existing cap was leaking at the seal on arrival.

Sincerely, Frank Grebas Vice President FG/aek http://www.protanic.com/

Equipment Detail and Certifications

Alert Tank Tester Wis. Material Approval No. - 20170001

Technician Information

Respectfully submitted, Equipment Utilized

Comments

Customer Name and Address Site ID/Facility Name and Address Test Date

Product State ID Capacity Construction Volumetric Result GPH Score

Tank Tightness Test Results

Ullage Result

P R O F E S S I O N A L T A N K I N V E S T I G A T I O N C O R P .

PO Box 80265 Saukville, WI 53080 www.protanic.com (262) 268-1150

C28777Veeder Root bea843a6ALERT

IL-1413Illinois

492105WI Tank Tester

9fc213c0Petro-Tite

60088-2814ILGREAT LAKES

Doug Metzker

Concrete DW10000Bio-Diesel AST

PassConcrete DW10000E-85 AST

PassConcrete DW10000Regular AST

PWD GREAT LAKES

Michelle Mosso

60088ILGreat Lakes

Building 1506 2021-07-22

Naval Station Great Lakes

NAVFAC MID ATLANTIC

P R O F E S S I O N A L T A N K I N V E S T I G A T I O N C O R P .

PO Box 80265 Saukville, WI 53080 www.protanic.com (262) 268-1150

Pressure Vacuum (PV) Vent Cap Test Product

Type Result Pass Fail PV Valve

Manufacturer Model Number

Manufacturer’s Specified Positive Leak Rate

” wc Manufacturer’s Specified Negative Leak Rate

” wc

Measured Positive Leak Rate CFH Measured Negative Leak Rate CFH

Positive Cracking Pressure ” wc Negative Cracking Pressure ” wc

Type Result Pass Fail PV Valve

” wc Manufacturer’s Specified Negative Leak Rate

” wc

Type

Result Pass Fail PV Valve

” wc Manufacturer’s Specified Negative Leak Rate

” wc

Type

Result Pass Fail PV Valve

” wc Manufacturer’s Specified Negative Leak Rate

” wc

Type Result Pass Fail PV Valve

” wc Manufacturer’s Specified Negative Leak Rate

” wc

Comments

Technician Signature:

Customer Name and Address Site ID/Facility Name and Address Test Date

-8.1+3.2

.2.21

-8+3

623OPW✔E-85

-8.2+3.1 .2.21

-8+3

623OPW✔Regular

60088-2814ILGREAT LAKES

PWD GREAT LAKES

Michelle Mosso

60088ILGreat Lakes Building 1506

2021-07-22 Naval Station Great Lakes

Doug

Tank Product Tank Product

In-Tank Gauging Probe Model In-Tank Gauging Probe Model Fill Sump Sensor(s) Model Fill Sump Sensor(s) Model Tank Overfill/High-Level Sensor Model Tank Overfill/High-Level Sensor Model

Tank Product Tank Product

In-Tank Gauging Probe Model In-Tank Gauging Probe Model Fill Sump Sensor(s) Model Fill Sump Sensor(s) Model Tank Overfill/High-Level Sensor Model Tank Overfill/High-Level Sensor Model

Dispenser ID Dispenser ID

Dispenser Containment Sensor(s) Model Dispenser Containment Sensor(s) Model Dispenser Containment Float(s) Model Dispenser Containment Float(s) Model

Dispenser ID Dispenser ID

Dispenser Containment Sensor(s) Model Dispenser Containment Sensor(s) Model Dispenser Containment Float(s) Model Dispenser Containment Float(s) Model

Dispenser ID Dispenser ID

Dispenser Containment Sensor(s) Model Dispenser Containment Sensor(s) Model Dispenser Containment Float(s) Model Dispenser Containment Float(s) Model

Technician Name (Print): Technician Signature:

Facility Representative (Print): Facility Representative Signature:

Test DateCustomer Name and Address Site ID/Facility Name and Address

ATG Inspection

Certification

Inventory of Equipment Tested/Certified Check the appropriate boxes to indicate specific equipment inspected/serviced Make/Model of Monitoring System:

P R O F E S S I O N A L T A N K I N V E S T I G A T I O N C O R P .

PO Box 80265 Saukville, WI 5308 www.protanic.com (262) 268-1150 0

Mag 1✔

Bio-Diesel AST

Mag 1✔

E-85 AST

Mag 1✔

Regular AST

TLS-350

60088-2814ILGREAT LAKES

Doug Metzker

PWD GREAT LAKES

Michelle Mosso

60088ILGreat Lakes

Building 1506 2021-07-22

Naval Station Great Lakes

Software Version Installed:

Yes No Is the audible alarm operational at the tank monitor?

Yes No Is the visual alarm operational at the tank monitor?

Yes No Were all sensors visually inspected, functionally tested, and confirmed operational?

Yes No If alarms are relayed to a remote monitoring system, is all communications equipment (e.g. modem) operational?

Yes No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) Product Water If yes, describe causes in comments, below.

Yes No Is all monitoring equipment operational per manufacturer's specifications?

* In Comments below, describe how and when these deficiencies were or will be corrected.

Yes No Was accuracy of system product level readings tested?

Yes No Were all probes reinstalled properly?

Yes No Were all items on the equipment manufacturer's maintenance checklist completed?

Comments

In-Tank Gauging / SIR Equipment

Does the ATG have a battery backup? If yes, is the battery backup functional? Tested and confirmed functional.

The E-85 interstitial sensor FAILS; the sensor does not function properly. The sensor is in ‘Sensor Out’ alarm and is mislabeled in the tank monitor.

14.01 kyliek Typewritten Text N/A kyliek Typewritten Text N/A kyliek Typewritten Text N/A kyliek Typewritten Text N/A

PO Box 80265 Saukville, WI 5308 www.protanic.com (262) 268-1150

P R O F E S S I O N A L T A N K I N V E S T I G A T I O N C O R P

Customer Name and Address

Facility ID Facility Name and Address

Test Date

Sensor Inspection/Certification

Was as system setup printed?

Sensor Location Type

Sensor in proper position when

ARRIVED?

Sensor in Alarm when

ARRIVED?

Functionality Test Result (Pass/Fail)

Sensor in proper position when LEFT site?

Sensor in Alarm when LEFT site?

Water present below sensor?

Is the sensor programmed for positive shutdown?

Did sensor shut down sub motor?

Comments

Technician Signature:

Yes

The E-85 interstitial sensor FAILS; the sensor does not function properly. The sensor is in ‘Sensor Out’ alarm and is mislabeled in the tank monitor.

No

NoNoYesPassNoYesBellDiesel Interstitial

NoYesYesFailYesYesBellE-85 Interstitial

NoNoYesPassNoYesBellRegular Interstitial

60088-2814ILGREAT LAKES

PWD GREAT LAKES

Michelle Mosso

60088ILGreat Lakes Building 1506

2021-07-22Naval Station Great Lakes

NAVFAC MID ATLANTIC

http://www.protanic.com/

Facility #: __________________

Facility Address: ____________________________________________________________

Annual Walkthrough Inspection Report: 20___ (year)

A/B Operator Signature (if applicable): _______________________________________________

Print Name of A/B Operator (if applicable): ____________________________________________

Inspections Required Annually (Inspections of piping sump areas must be performed by a certified employee of a contractor licensed in either the Install/Retrofit or Tank Tightness Testing modules.) All piping sumps areas shall be checked annually. Sump lids must be lifted and dispenser cabinets opened to inspect piping containment sump areas.

Contractor must initial and enter date of Annual Walkthrough Inspection.

Day/Month/Year of Inspection

Contractor Initials

Enter comments below corresponding to inspections listed at left.

Visual check for damage to piping containment sump areas: Check lids, covers & containment for damage & leaks.

COMMENTS & ACTIONS TAKEN:

Check sumps for the presence of regulated substances or any indication that a release may have occurred. Remove any liquid or debris if present.

COMMENTS & ACTIONS TAKEN:

Check that interstices of double wall containment sumps are free of water or product.

COMMENTS & ACTIONS TAKEN:

If applicable: Check gauge stick (manual tank gauging) or bailer (GW monitoring).

COMMENTS & ACTIONS TAKEN:

Contractor Employee Conducting Annual Inspection of Piping Containment Sump Areas:

1) Signature: _____________________________________

2) Print Name & Title: _____________________________________

Annual Test & Inspection: May be Performed by Contractor or A/B Operator Contractor or A/B Operator must initial and enter date of Annual Emergency Stops Test.

Day/Month/Year of Emergency Stop Test

Contractor or A/B Operator Initials

Enter comments below regarding Annual Emergency Stops Test. Attach OSFM Operational Testing of Emergency Stops Report to Walkthrough Inspection Report & keep at facility.

Test Emergency Stops for interconnection and STP shutdown.

Attach OSFM report form.

COMMENTS:

Contractor or A/B Operator must initial and enter date of Annual Shear Valve Inspection.

Day/Month/Year of Shear Valve Inspection

Contractor or A/B Operator Initials

Enter comments below regarding Annual Shear Valve Inspection. Attach OSFM Annual Inspection of Shear Valves Report to Walkthrough Inspection Report & keep at facility.

Check shear valves for proper height, secure mounting & free operation of trip arm & poppet.

COMMENTS:

Dm07/23/2021

Dm07/23/2021

Dm07/23/2021

Dm 07/23/2021

Protanic Inc

Doug Metzker

Great LakesBuilding 1506

Site Survey Form
Tank Test Data Sheet Form
Tank Test Final Report
Line Test Data Sheet Form
Leak Detector Test Form
Line and LD Test Final Report
Pressure Decay Form
PV Vent Cap Form Report
Pressure Decay Final Report
Drop Tube Form
Cathodic Protection Report (Non-Wisconsin)
ATG Inspection Report - Protanic
Sensor Form Report
Overfill Prevention Equipment Inspection Report
Shear Valve Form Report
Shear Valve Report
Testing of Emergency Electrical Shutoff
Containment Sump Test Report
30 Day Walkthrough Inspection Report
Annual Walkthrough Inspection Report
Repair Request - Tech Form
Parts Replaced Form
Failed Test Results Report
Post Site Inspection Testing Checklist Form
Submit Page
ClientName: NAVFAC MID ATLANTIC
FacilityName: Naval Station Great Lakes
Date: 2021-07-22
FacilityAddress: Building 1506
FacilityCity: Great Lakes
FacilityState: IL
FacilityZip: 60088
ClientPrimaryContactFirstName: Michelle Mosso
ClientAddress: PWD GREAT LAKES
Technician: Doug Metzker
FacilityID: 1506
ClientCity: GREAT LAKES
ClientState: IL
ClientZip: 60088-2814
CertName1: Petro-Tite
CertNumber1: 9fc213c0
CertName2: WI Tank Tester
CertNumber2: 492105
CertName3: Illinois
CertNumber3: IL-1413
CertName4: ALERT
CertNumber4: bea843a6
CertName5: Veeder Root
CertNumber5: C28777
CertName6:
CertNumber6:
CertName7:
CertNumber7:
ID624SiteShutDown: 2
ID624TestStartTime: 1400
ID624TestEndTime: 1600
ID624TOTAL_NUMBER_OF_GAS_NOZZLES_AT_FACILITY: 8
FacilityCounty: Lake
CompanyName: Protanic Inc
TestingCompanyAddress: PO Box 80265
TestingCompanyCity: Saukville
TestingCompanyState: WI
TestingCompanyZip: 53080
TestingCompanyPhone: 2622681150