Interim MCMH French Creek_Drawing Set_Compiled.pdf

PDF 14 MB Posted

Attached to
SOLICITATION -Design-Bid-Build (DBB) construction project for the P4040 French Creek Ambulatory Care Clinic, Camp Lejeune, North Carolina.
Solicitation number
N4008521R2524
Issued by

About this file

This document provides details on a federal solicitation for construction services. The solicitation number is N4008521R2524 and is being issued by the Department of the Navy Naval Facilities Engineering Command for a Design-Bid-Build project to construct the P4040 French Creek Ambulatory Care Clinic at Camp Lejeune, North Carolina. Interested parties should review the attached drawings and specifications in the "Interim MCMH French Creek_Drawing Set_Compiled.pdf" file for requirements. The solicitation is for construction services and the response deadline has not been provided. The awarded contractor will be expected to complete the ambulatory care clinic as detailed in the drawings and specifications.

View the file

Other files

File Type Posted
N4008521R2524P00006.pdf PDF
AMEND 06 ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
AMD 5 ATTACH 2 Site Visit 6.17.21.pdf PDF
AMD 5 ATTACH 1 P4040 PPIs VER2.xlsx XLSX spreadsheet
N4008521R2524P0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003 Attachment (1) NC20210038 WGDET.pdf PDF
Amendment 0003 Attachment (2) PPIs.xlsx XLSX spreadsheet
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
MP501.pdf PDF
Amendment 0001 Continuation Sheet.pdf PDF
N4008521R2524P00001.pdf PDF
Attachment B - Construction Experience Project Data Sheet.docx DOCX document
1430035dwg10of20_Architectural.pdf PDF
1430035dwg06of20_Civil.pdf PDF
1430035dwg15of20_FireSup.pdf PDF
1430035dwg20of20_Comm.pdf PDF
1430035dwg19of20_Electrical.pdf PDF
ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
ATTACHMENT D SMALL BUSINESS SUBCONTRACTING PLAN.docx DOCX document
1430035spc01of03.pdf PDF
1430035dwg02of20_LifeSafety.pdf PDF
RFP N4008521R2524.pdf PDF
1430035dwg16of20_FireAlarm.pdf PDF
1430035dwg07of20_Landscape.pdf PDF
1430035dwg09of20_Architectural.pdf PDF
1430035dwg12of20_Architectural.pdf PDF
1430035dwg04of20_Hazmat.pdf PDF
Attachment A - PPI Inquiry Log.xls XLS spreadsheet
1430035dwg14of20_Equipment.pdf PDF
1430035spc02of03.pdf PDF
1430035dwg13of20_Interiors.pdf PDF
ATTACHMENT C Past Performance Questionnaire.pdf PDF
1430035dwg11of20_Architectural.pdf PDF
1430035dwg05of20_Borings.pdf PDF
1430035dwg03of20_Phasing.pdf PDF
1430035spc03of03.pdf PDF
1430035dwg08of20_Structural.pdf PDF
1430035dwg17of20_Plumbing.pdf PDF
1430035dwg01of20_General.pdf PDF
1430035dwg18of20_Mechanical.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

60016694

SHEET

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

COVER SHEET

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF01 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

INTERIM MCMH FACILITY

MARINE CORPS BASE CAMP LEJEUNE

CONTRACT NO. N40085-15-B-0091

INDEX OF DRAWINGS

NAVFAC NO. SHEET NO. TITLE

60016694 G-001 COVER SHEET

CG-501 DETAILS

CD-101 EXISTING CONDITIONS AND DEMOLITION PLAN

CG-101 SITE GRADING & EROSION CONTROL PLAN

CS-101 SITE LAYOUT AND UTILITY PLAN

CU-301 WATER MAIN PROFILE

60016698 60016699 60016700 60016701

60016703

CU-501 DETAILS60016704

S-1 TYPICAL DETAILS, GENERAL NOTES, & SECTIONS60016705

S-2 FOUNDATION PLAN60016706

A-1 FLOOR PLAN60016707

A-2 REFLECTED CEILING PLAN60016708

E-5 ELECTRICAL DETAILS

E-6 ELECTRICAL LIGHTING FIXTURE DETAILS

60016719 60016720

CS-501 DETAILS60016702

SITE PREP, FRENCH CREEK

A-7 DECK FRAMING & STAIR DETAILS

A-4 ENLARGED PLANS & INTERIOR ELEVATIONS

A-3 ROOF PLAN

A-5 BUILDING ELEVATIONS

60016709 60016710 60016711

60016713

A-8 SCHEDULES60016714

E-1 ELECTRICAL SYMBOLS & SCHEDULES60016715

E-3 ELECTRICAL FLOOR PLAN - POWER

60016716

E-4 ELECTRICAL SITE PLAN

60016717 60016718

A-6 BUILDING SECTIONS60016712

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

LICENSE NO. C-0706

T. H. BURTON

E-2 ELECTRICAL FLOOR PLAN - LIGHTING

LS-1 LIFE SAFETY PLAN AND CODE SUMMARY

FP-1 FIRE PROTECTION PLAN AND DETAILS

FA-1 FIRE ALARM PLAN AND DETAILS

60016695 60016696 60016697

60016698

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

EXISTING CONDITIONS AND DEMOLITION PLAN

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF05 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

H. M. SMITH BLVD

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

LICENSE NO. C-0706

T. H. BURTON

60016699

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

SITE LAYOUT AND UTILITY PLAN

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF06 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

H. M. SMITH BLVD

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

60016700

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

SITE GRADING & EROSION CONTROL PLAN

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF07 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

H. M. SMITH BLVD

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

60016701

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

WATER MAIN PROFILE

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF08 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

LICENSE NO. C-0706

T. H. BURTON

NOTE:

CONTRACTOR TO FIELD VERIFY UTILITY ELEVATIONS

PRIOR TO ENCASEMENT INSTALLATION, THIS AREA.

60016702

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

DETAILS

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF09 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

60016703

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

DETAILS

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF10 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

60016704

CODE IDENT. NOSIZE

SCALE: NOTED

80091F

DES.

CHK.

DESIGN DIR.

DR.

APPROVED: PWO OR OICC

SATISFACTORY TO:

J. C. AVOLIS, P.E.

J. K. AVOLIS, P.E.

MSP / WFF

SUBMITTED BY:

DETAILS

CAMP LEJEUNE, NORTH CAROLINA

DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND

MARINE CORPS BASE

SPEC. 05-15-0091

NAVFAC DRAWING NO.

INTERIM MCMH FACILITY

DATE

DATE

OF11 27

SITE PREP, FRENCH CREEK

MARINE CORPS BASE, CAMP LEJEUNE, NC

NEW BERN, NC 28561

PH.(252) 633-0068, FAX (252) 633-6507

AVOLIS ENGINEERING, P.A.

P.O. BOX 15564

MINI-SPLIT SYSTEM SCHEDULE

Unit Tag CFM CFM Fan Motor Cooling Performance Heating Performance Unit Electrical Outdoor Unit Remarks

High Low FLA Volts Phase EAT MBH Efficiency EAT Capacity MCA MOCP Unit Tag Fan Compressor MCA MOCP Volts Phase Total SEER MBH No. FLA(ea) No. LRA RLA

MSAH-1 380 290 0.33 208/230 1 80/67 18 15.3 70 19 1 15 MSHP-1 1 0.35 1 14 12 13 20 208/230 1 1-4

1. MOUNT INDOOR SECTION TIGHT TO BOTTOM OF CEILING AND WALL. 4. BASIS OF DESIGN IS MITSUBISHI.

2. INDOOR UNIT POWERED FROM OUTDOOR UNIT. COORDINATE POWER REQUIREMENTS.

3. REFRIGERANT LINES AND ACCESSORIES PER SPECS AND AS RECOMMENDED BY UNIT MFG.

FAN SCHEDULE

Unit Area Served CFM ESP Fan Sones Drive Watts Volts Phase Type Remarks

Tag (IN.) RPM

EF-1 SOILED UTILITY 100 .25 708 .6 DIRECT 128 115 1 CEILING MOUNTED 1-3

1. DISCONNECT BY MFG.

2. UNIT MOUNTED SOLID STATE SPEED CONTROL.

3. BACKDRAFT DAMPER.

SIEMON SYSTEMcabling

SD

THE SIEMON COMPANY

SD SD SD SD SD

SD

THE

SIEMON

COMPANY

1 2

3 4

5 6

7 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

31 32

33 34

35 36

37 38

39 40

41 42

43 44

45 46

47 48

SD

THE SIEMON COMPANY

SD SD SD SD SD

SD

THE SIEMON COMPANY

SD SD SD SD SD

SD

THE SIEMON COMPANY

SD SD SD SD SD

SD

CABLE MANAGER

CABLE MANAGER

SD

THE SIEMON COMPANY

SD SD SD SD SD

FIBER

Distribution

COPPER

Connecting BLOCKS

MicroMMAC-24E MicroMMAC-24E

E P IM

E P IM

MicroMMAC-24E MicroMMAC-24E

E P IM

E P IM

ST connectors A

B

C

D

On Backboard – PROTECTOR / BUILDING ENTRANCE (BEP), TMGB, Proper Bonding & Grounding, Cable Management and Slack on Ladder Rack.

Ladder rack should be from comm rack to at lease two walls .

Rack or Cabinet if in unsecure area

Number of telecommunications work outlets in building determine number of patch panels and need for additional racks

If 3 or more racks are used :

place the fiber and copper cable terminations in center racking to reduce patch cord length

Bottom 15 RU is reserved for DATA equipment

SD

THE

SIEMON

COMPANY

1 2

3 4

5 6

7 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

31 32

33 34

35 36

37 38

39 40

41 42

43 44

45 46

47 48

SD

THE

SIEMON

COMPANY

1 2

3 4

5 6

7 8

9 10

11 12

13 14

15 16

17 18

19 20

21 22

23 24

25 26

27 28

29 30

31 32

33 34

35 36

37 38

39 40

41 42

43 44

45 46

47 48

Work Area Outlet

387 A 388

385 A 386

Panel Dual Port Label

385 386

N40085-15-B-0091 DRAWINGS - PART 1
TITLE PAGE PLANS
60016694, G-1001, COVER SHEET
LIFE SAFETY PLANS
60016695, LS-1. LIFE SAFETY PLAN AND CODE SUMMARY
FIRE ALARM / FIRE PROTECTION PLANS
60016696, FA-1, FIRE ALARM PLAN AND DETAILS
60016697, FP-1, FIRE PROTECTION PLAN AND DETAILS
CIVIL PLANS
60016698, CD-101. EXISTING CONDITIONS AND DEMOLITION PLAN
60016698, CS-101, SITE LAYOUT AND UTILITY PLAN
60016700. CG-101. SITE GRADING & EROSION CONTROL PLAN
60016701. CU-301, WATER MAIN PROFILE
60016702. CS-501, DETAILS
60016703. CG-501, DETAILS
60016704, CU-501, DETAILS
STRUCTURAL PLANS
60016705, S-1, TYPICAL DETAILS, GENERAL NOTES & SECTIONS
60016706, S-2, FOUNDATION PLAN
ARCHITECTURAL PLANS
60016707, A-1, FLOOR PLAN
60016708, A-2, REFLECTED CEILING PLAN
60016709, A-3, ROOF PLAN
60016710, A-4, ENLARGED PLANS & INTERIOR ELEVATIONS
60016711, A-5, BUILDING ELEVATIONS
60016712, A-6, BUILDING SECTIONS
60016713, A-7, DECK FRAMING & STAIR DETAILS
60016714, A-8, SCHEDULES
ELECTRICAL
60016715, E-1, ELECTRICAL SYMBOLS & SCHEDULES
60016716, E-2, ELECTRICAL FLOOR PLAN - LIGHTING
60016717, E-3, ELECTRICAL FLOOR PLAN - POWER
60016718, E-4, ELECTRICAL SITE PLAN
60016719, E-5, ELECTRICAL DETAILS
60016720, E-6, ELECTRICAL FIXTURE DETAILS

File details come from the government source that posted it. Updated .