Interim MCMH French Creek_Drawing Set_Compiled.pdf
PDF 14 MB Posted
- Solicitation number
- N4008521R2524
About this file
This document provides details on a federal solicitation for construction services. The solicitation number is N4008521R2524 and is being issued by the Department of the Navy Naval Facilities Engineering Command for a Design-Bid-Build project to construct the P4040 French Creek Ambulatory Care Clinic at Camp Lejeune, North Carolina. Interested parties should review the attached drawings and specifications in the "Interim MCMH French Creek_Drawing Set_Compiled.pdf" file for requirements. The solicitation is for construction services and the response deadline has not been provided. The awarded contractor will be expected to complete the ambulatory care clinic as detailed in the drawings and specifications.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
60016694
SHEET
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
COVER SHEET
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF01 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
INTERIM MCMH FACILITY
MARINE CORPS BASE CAMP LEJEUNE
CONTRACT NO. N40085-15-B-0091
INDEX OF DRAWINGS
NAVFAC NO. SHEET NO. TITLE
60016694 G-001 COVER SHEET
CG-501 DETAILS
CD-101 EXISTING CONDITIONS AND DEMOLITION PLAN
CG-101 SITE GRADING & EROSION CONTROL PLAN
CS-101 SITE LAYOUT AND UTILITY PLAN
CU-301 WATER MAIN PROFILE
60016698 60016699 60016700 60016701
60016703
CU-501 DETAILS60016704
S-1 TYPICAL DETAILS, GENERAL NOTES, & SECTIONS60016705
S-2 FOUNDATION PLAN60016706
A-1 FLOOR PLAN60016707
A-2 REFLECTED CEILING PLAN60016708
E-5 ELECTRICAL DETAILS
E-6 ELECTRICAL LIGHTING FIXTURE DETAILS
60016719 60016720
CS-501 DETAILS60016702
SITE PREP, FRENCH CREEK
A-7 DECK FRAMING & STAIR DETAILS
A-4 ENLARGED PLANS & INTERIOR ELEVATIONS
A-3 ROOF PLAN
A-5 BUILDING ELEVATIONS
60016709 60016710 60016711
60016713
A-8 SCHEDULES60016714
E-1 ELECTRICAL SYMBOLS & SCHEDULES60016715
E-3 ELECTRICAL FLOOR PLAN - POWER
60016716
E-4 ELECTRICAL SITE PLAN
60016717 60016718
A-6 BUILDING SECTIONS60016712
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
LICENSE NO. C-0706
T. H. BURTON
E-2 ELECTRICAL FLOOR PLAN - LIGHTING
LS-1 LIFE SAFETY PLAN AND CODE SUMMARY
FP-1 FIRE PROTECTION PLAN AND DETAILS
FA-1 FIRE ALARM PLAN AND DETAILS
60016695 60016696 60016697
60016698
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
EXISTING CONDITIONS AND DEMOLITION PLAN
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF05 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
H. M. SMITH BLVD
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
LICENSE NO. C-0706
T. H. BURTON
60016699
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
SITE LAYOUT AND UTILITY PLAN
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF06 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
H. M. SMITH BLVD
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
60016700
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
SITE GRADING & EROSION CONTROL PLAN
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF07 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
H. M. SMITH BLVD
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
60016701
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
WATER MAIN PROFILE
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF08 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
LICENSE NO. C-0706
T. H. BURTON
NOTE:
CONTRACTOR TO FIELD VERIFY UTILITY ELEVATIONS
PRIOR TO ENCASEMENT INSTALLATION, THIS AREA.
60016702
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
DETAILS
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF09 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
60016703
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
DETAILS
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF10 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
60016704
CODE IDENT. NOSIZE
SCALE: NOTED
80091F
DES.
CHK.
DESIGN DIR.
DR.
APPROVED: PWO OR OICC
SATISFACTORY TO:
J. C. AVOLIS, P.E.
J. K. AVOLIS, P.E.
MSP / WFF
SUBMITTED BY:
DETAILS
CAMP LEJEUNE, NORTH CAROLINA
DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND
MARINE CORPS BASE
SPEC. 05-15-0091
NAVFAC DRAWING NO.
INTERIM MCMH FACILITY
DATE
DATE
OF11 27
SITE PREP, FRENCH CREEK
MARINE CORPS BASE, CAMP LEJEUNE, NC
NEW BERN, NC 28561
PH.(252) 633-0068, FAX (252) 633-6507
AVOLIS ENGINEERING, P.A.
P.O. BOX 15564
MINI-SPLIT SYSTEM SCHEDULE
Unit Tag CFM CFM Fan Motor Cooling Performance Heating Performance Unit Electrical Outdoor Unit Remarks
High Low FLA Volts Phase EAT MBH Efficiency EAT Capacity MCA MOCP Unit Tag Fan Compressor MCA MOCP Volts Phase Total SEER MBH No. FLA(ea) No. LRA RLA
MSAH-1 380 290 0.33 208/230 1 80/67 18 15.3 70 19 1 15 MSHP-1 1 0.35 1 14 12 13 20 208/230 1 1-4
1. MOUNT INDOOR SECTION TIGHT TO BOTTOM OF CEILING AND WALL. 4. BASIS OF DESIGN IS MITSUBISHI.
2. INDOOR UNIT POWERED FROM OUTDOOR UNIT. COORDINATE POWER REQUIREMENTS.
3. REFRIGERANT LINES AND ACCESSORIES PER SPECS AND AS RECOMMENDED BY UNIT MFG.
FAN SCHEDULE
Unit Area Served CFM ESP Fan Sones Drive Watts Volts Phase Type Remarks
Tag (IN.) RPM
EF-1 SOILED UTILITY 100 .25 708 .6 DIRECT 128 115 1 CEILING MOUNTED 1-3
1. DISCONNECT BY MFG.
2. UNIT MOUNTED SOLID STATE SPEED CONTROL.
3. BACKDRAFT DAMPER.
SIEMON SYSTEMcabling
SD
THE SIEMON COMPANY
SD SD SD SD SD
SD
THE
SIEMON
COMPANY
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
43 44
45 46
47 48
SD
THE SIEMON COMPANY
SD SD SD SD SD
SD
THE SIEMON COMPANY
SD SD SD SD SD
SD
THE SIEMON COMPANY
SD SD SD SD SD
SD
CABLE MANAGER
CABLE MANAGER
SD
THE SIEMON COMPANY
SD SD SD SD SD
FIBER
Distribution
COPPER
Connecting BLOCKS
MicroMMAC-24E MicroMMAC-24E
E P IM
E P IM
MicroMMAC-24E MicroMMAC-24E
E P IM
E P IM
ST connectors A
B
C
D
On Backboard – PROTECTOR / BUILDING ENTRANCE (BEP), TMGB, Proper Bonding & Grounding, Cable Management and Slack on Ladder Rack.
Ladder rack should be from comm rack to at lease two walls .
Rack or Cabinet if in unsecure area
Number of telecommunications work outlets in building determine number of patch panels and need for additional racks
If 3 or more racks are used :
place the fiber and copper cable terminations in center racking to reduce patch cord length
Bottom 15 RU is reserved for DATA equipment
SD
THE
SIEMON
COMPANY
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
43 44
45 46
47 48
SD
THE
SIEMON
COMPANY
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
43 44
45 46
47 48
Work Area Outlet
387 A 388
385 A 386
Panel Dual Port Label
385 386
| N40085-15-B-0091 DRAWINGS - PART 1 |
| TITLE PAGE PLANS |
| 60016694, G-1001, COVER SHEET |
| LIFE SAFETY PLANS |
| 60016695, LS-1. LIFE SAFETY PLAN AND CODE SUMMARY |
| FIRE ALARM / FIRE PROTECTION PLANS |
| 60016696, FA-1, FIRE ALARM PLAN AND DETAILS |
| 60016697, FP-1, FIRE PROTECTION PLAN AND DETAILS |
| CIVIL PLANS |
| 60016698, CD-101. EXISTING CONDITIONS AND DEMOLITION PLAN |
| 60016698, CS-101, SITE LAYOUT AND UTILITY PLAN |
| 60016700. CG-101. SITE GRADING & EROSION CONTROL PLAN |
| 60016701. CU-301, WATER MAIN PROFILE |
| 60016702. CS-501, DETAILS |
| 60016703. CG-501, DETAILS |
| 60016704, CU-501, DETAILS |
| STRUCTURAL PLANS |
| 60016705, S-1, TYPICAL DETAILS, GENERAL NOTES & SECTIONS |
| 60016706, S-2, FOUNDATION PLAN |
| ARCHITECTURAL PLANS |
| 60016707, A-1, FLOOR PLAN |
| 60016708, A-2, REFLECTED CEILING PLAN |
| 60016709, A-3, ROOF PLAN |
| 60016710, A-4, ENLARGED PLANS & INTERIOR ELEVATIONS |
| 60016711, A-5, BUILDING ELEVATIONS |
| 60016712, A-6, BUILDING SECTIONS |
| 60016713, A-7, DECK FRAMING & STAIR DETAILS |
| 60016714, A-8, SCHEDULES |
| ELECTRICAL |
| 60016715, E-1, ELECTRICAL SYMBOLS & SCHEDULES |
| 60016716, E-2, ELECTRICAL FLOOR PLAN - LIGHTING |
| 60016717, E-3, ELECTRICAL FLOOR PLAN - POWER |
| 60016718, E-4, ELECTRICAL SITE PLAN |
| 60016719, E-5, ELECTRICAL DETAILS |
| 60016720, E-6, ELECTRICAL FIXTURE DETAILS |
File details come from the government source that posted it. Updated .