About this file

This document contains a life safety plan and construction specifications for a medical/dental clinic building project. The project involves renovating approximately 11,918 square feet and adding approximately 16,367 square feet for a total gross area of 43,543 square feet. The building will be Type II-B non-rated construction with a fully sprinklered system. Fire resistance ratings are specified for various building elements. Occupancy classifications, allowable areas, heights, and egress requirements are analyzed against applicable codes. Five exits will be provided to meet the required egress for the total calculated occupant load of 562 people.

The related federal contract opportunity is a solicitation from the Department of the Navy Naval Facilities Engineering Command for design-bid-build construction services for the P4040 French Creek Ambulatory Care Clinic located at Camp Lejeune, North Carolina. No further details are provided in the document about response dates, award dates, pricing terms, set asides, or incumbent contractors.

View the file

Other files

File Type Posted
N4008521R2524P00006.pdf PDF
AMEND 06 ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
AMD 5 ATTACH 2 Site Visit 6.17.21.pdf PDF
AMD 5 ATTACH 1 P4040 PPIs VER2.xlsx XLSX spreadsheet
N4008521R2524P0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003 Attachment (1) NC20210038 WGDET.pdf PDF
Amendment 0003 Attachment (2) PPIs.xlsx XLSX spreadsheet
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
MP501.pdf PDF
Interim MCMH French Creek_Drawing Set_Compiled.pdf PDF
Amendment 0001 Continuation Sheet.pdf PDF
N4008521R2524P00001.pdf PDF
Attachment B - Construction Experience Project Data Sheet.docx DOCX document
1430035dwg10of20_Architectural.pdf PDF
1430035dwg06of20_Civil.pdf PDF
1430035dwg15of20_FireSup.pdf PDF
1430035dwg20of20_Comm.pdf PDF
1430035dwg19of20_Electrical.pdf PDF
ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
ATTACHMENT D SMALL BUSINESS SUBCONTRACTING PLAN.docx DOCX document
1430035spc01of03.pdf PDF
RFP N4008521R2524.pdf PDF
1430035dwg16of20_FireAlarm.pdf PDF
1430035dwg07of20_Landscape.pdf PDF
1430035dwg09of20_Architectural.pdf PDF
1430035dwg12of20_Architectural.pdf PDF
1430035dwg04of20_Hazmat.pdf PDF
Attachment A - PPI Inquiry Log.xls XLS spreadsheet
1430035dwg14of20_Equipment.pdf PDF
1430035spc02of03.pdf PDF
1430035dwg13of20_Interiors.pdf PDF
ATTACHMENT C Past Performance Questionnaire.pdf PDF
1430035dwg11of20_Architectural.pdf PDF
1430035dwg05of20_Borings.pdf PDF
1430035dwg03of20_Phasing.pdf PDF
1430035spc03of03.pdf PDF
1430035dwg08of20_Structural.pdf PDF
1430035dwg17of20_Plumbing.pdf PDF
1430035dwg01of20_General.pdf PDF
1430035dwg18of20_Mechanical.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE RESISTANCE RATINGS

BUILDING ELEMENTS STRUCTURE

(TYPE 2B, IBC, TABLES 601 AND 602)

FLOOR WALLS

DOORS /

WINDOWS ROOF CONSTRUCTION

FLOOR CONSTRUCTION 0 4" REINFORCED SLAB-ON-GRADE OVER VAPOR RETARDER AND 4" OF POROUS FILL

STRUCTURAL FRAME

0COLUMNS STEEL

0JOISTS STEEL

0BEAMS STEEL

EXTERIOR WALLS

LOAD BEARING

NON LOAD BEARING

0 8" CMU

0 8" CMU WITH STEEL/GLASS STOREFRONT; 8" METAL STUDS

INTERIOR WALLS

LOAD BEARING 0 8" CMU

NON LOAD BEARING

ROOM PARTITIONS

WAYS OF EGRESS

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

SPECIAL ROOMS

ELECTRICAL

COMMUNICATIONS

JANITOR'S CLOSET

MECHANICAL

LOGISTICS

CLEAN

SOILED

EQUIPMENT

GAS STORAGE

MEDICAL WASTE (RMW)

PHARMACY

MEDICAL RECORDS

ROOF CONSTRUCTION

LOW-SLOPE

HIGH-SLOPE

METAL DECK OVER STEEL JOISTS, TAPERED INSULATION, TPO ROOFING SYSTEM

PERFORATED METAL DECK WITH Z-CHANNELS OVER STEEL JOISTS, RIGID

INSULATION, STANDING SEAM METAL ROOF

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

8" CMU OR 8" CMU WITH 2-1/2" STUD FURRING WITH 1 LAYER OF GWB

3-5/8" STUD WITH TWO LAYER OF GWB

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

8" CMU (UL DESIGN NO. 905)

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

SMOKE

PARTITON

SMOKE

PARTITION

DERM STORAGE 3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

TRASH / RECYCLING 3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

SMOKE

PARTITION

NOTES:

REFER TO SHEET AE801 FOR PARTITION TYPE INFORMATION AND AE811 FOR TYPICAL PARTITION DETAILS.

NOTE 1: DOORS REQUIRED TO HAVE CLOSERS AND LATCH.

SMOKE

PARTITON

SMOKE

PARTITON

SMOKE

PARTITON

SMOKE

PARTITON

NOTE 1

NOTE 1

NOTE 1

NOTE 1

NOTE 1

NOTE 1

RADIOLOGY

LABORATORY

3-5/8" STUD OR 6" STUD WITH ONE LAYER OF GWB ON EACH SIDE AND LEAD

SHIELDING ON RAD ROOM SIDE

3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP

AUDIOBOOTH 3-5/8" STUD WITH ONE LAYER OF GWB ON EACH SIDE, TYP0

SMOKE

PARTITON

NOTE 1

NOTE 1

OCCUPANT LOAD

USE/ROOM AREA SF/PERSON LOAD

BUSINESS 28,452 SF 150 GROSS 190

ASSEMBLY 5,508 SF 15 NET 368

LOCKERS 1,606 SF 50 GROSS (IBC) 33

LABORATORIES 432 SF 50 GROSS 9

EXERCISE RM WITH EQUIPMENT 1,548 SF 50 GROSS 31

STORAGE / MECHANICAL 6,023 SF 500 GROSS 13

CLASSROOM 365 SF 20 NET 18

562 TOTAL

(NFPA 101, TABLE 7.3.1.2)

CODE ANALYSIS

BUILDING DESCRIPTION

MEDICAL / DENTAL CLINIC; BUILDING FC-308

OCCUPANCY CLASSIFICATION (IBC SECTION 304.1 AND NFPA 101, CHAPTERS 38/39)

BUSINESS: "B"

OCCUPANCY SEPARATION (IBC SECTIONS 706.1 AND 506; NFPA 101, 8.2.1.3.(1))

SINGLE OCCUPANCY - NO SEPARATION REQUIRED

TYPE OF CONSTRUCTION (IBC TABLE 601, SECTION 601)

TYPE II-B (000), NON-RATED, NON-COMBUSTIBLE CONSTRUCTION

FULLY SPRINKLERED PER NFPA 13

DESIGN GROSS AREA

EXISTING TO REMAIN: 15,258 +/- SQ FT

RENOVATION: 11,918 SQ FT

ADDITION: 16,367 SQ FT

TOTAL GROSS AREA: 43,543 +/- SQ FT

ALLOWABLE AREA PER FLOOR (S.F.) (IBC TABLE 506.2 & SECTION 506.2.3 & 506.3)

BASE (S1): 92,000 SQ FT

YARD INCREASE: 75% x 23,000 = 17,250 SQ FT

TOTAL ALLOWABLE: 109,250 SQ FT

ALLOWABLE BUILDING AREA (S.F.) (IBC TABLES 506.2):

TOTAL ALLOWABLE: 109,250 SQ FT

YARDS / SEPARATIONS:

SITE CONSTRAINTS WILL ALLOW FOR +/- 30FT FIRE SEPARATION DISTANCE

ON ALL SIDES

BUILDING HEIGHT (IBC TABLES 504.3 AND 504.4)

ALLOWABLE ACTUAL

STORIES: 4 STORIES 1 STORY

FEET: 75 FT 23'-4" +/- FT

EGRESS DISTANCES (FT.) (NFPA 101, CHAPTER 7)

ALLOWABLE ACTUAL

TRAVEL DISTANCE 300 FT 198 FT 6 IN

COMMON PATH 100FT 84 FT

DEAD END CORRIDOR 50 FT 22 FT

EXITS (ACTUAL/REQUIRED) (NFPA 101, CHAPTER 7.4)

(BASED ON 758 TOTAL OCCUPANT LOAD AND 1-STORY)

REQUIRED ACTUAL

FIRST FLOOR: 3 EXITS, MIN. 5 EXITS PROVIDED

(OL > 500 BUT <1000)

CODES BASED ON:

2015 INTERNATIONAL BUILDING CODE (IBC)

2015 NFPA 1: FIRE CODE

2016 NFPA 13: INSTALLATION OF SPRINKLER SYSTEMS

2016 NFPA 24: STANDARD FOR THE INSTALLATION OF PRIVATE SERVICE MAINS

AND THEIR APPURTENANCES

2017 NFPA 70: NATIONAL ELECTRICAL CODE

2016 NFPA 72: NATIONAL FIRE ALARM CODE

2015 NFPA 90A: INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS

2015 NFPA 99: HEALTHCARE FACILITIES

2018 NFPA 101 LIFE SAFETY CODE

NOTE: ONLY CODE REVIEWED FOR UPDATING THE ORIGINAL DESIGN

DATED OCTOBER 4, 2016 FOR COMPLIANCE

2015 NFPA 220: STANDARD ON TYPES OF BUILDING CONSTRUCTION

2013 NFPA 241: STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION,

AND DEMOLITION OPERATIONS

2016 NFPA 291: RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING

OF HYDRANTS

UFC 1-200-01, GENERAL BUILDING REQUIREMENTS, JUNE 2016

UFC 3-600-01, DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES, AUGUST

2016 W/CHANGE 1, 28 NOVEMBER 2016

UFC 4-010-01, DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 12 DECEMEBER 2018

UFC 4-021-01, DESIGN AND O&M: MASS NOTIFICATION SYSTEM, APRIL 2008

W/CHANGE 1, JANUARY 2012

UFC 4-510-01, DESIGN: MEDICAL FACILITIES, MAY 2016 W/CHANGE 1, MAY 2016

PLUMBING FIXTURE SUMMARY

FIXTURE COUNT PROVIDED (PER GOVERNMENT'S PROGRAM FOR DESIGN (PFD)

PUBLIC RESTROOMS:

MALE:

(2) URINALS

(2) WATER CLOSETS

(3) LAVATORIES

FEMALE:

(4) WATER CLOSETS

(3) LAVATORIES

(3) STAFF (UNISEX) RESTROOMS PROVIDED, EACH EQUIPPED WITH 1 WATER

CLOSET AND 1 LAVATORY

(5) PATIENT (UNISEX) RESTROOMS PROVIDED, EACH EQUIPPED WITH 1 WATER

CLOSET AND 1 LAVATORY

(2) SHOWER STALLS PROVIDED - SEPARATE MALE / FEMALE, WITH ADDITIONAL

RESTROOMS EQUIPPED WITH 1 WATER CLOSET AND 1 LAVATORY

(1) "HI-LO" WATER FOUNTAINS WITH BOTTLE FILLER PROVIDED

(2) BARRIER FREE WATER FOUNTAINS PROVIDED, (1) IN PHYSICAL THERAPY

AND (1) NEAR DENTAL LOUNGE

(2) SERVICE SINKS

FIXTURE COUNT REQUIRED

UFC 3-420-01 - APPENDIX A-3, CHAPTER 4-D AND TABLES 403.1 AND 403.2

TOTAL NUMBER OF EMPLOYEES: 65

MINIMUM NUMBER OF FIXTURES REQUIRED FOR NAVY FACILITIES: 8

FOR "BUSINESS" OCCUPANCY:

(4) WATER CLOSETS

(4) LAVATORIES

(1) DRINKING FOUNTAIN

(1) SERVICE SINK

PER TABLE 403.1 AND 403.2

(4) WATER CLOSETS REQUIRED

(4) LAVATORIES

(1) DRINKING FOUNTAIN

EF

RT

I

N N

N O

L.

T E

N A

040804 E N G

R

NI E E R

OL

V

SEAL

S

A

SFORP

E

H C

I A L

OI N

OR L

T

JE

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

IO

N

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

D

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m ec

\D oc um en ts \4

0-

B

LD

G -1

-A

_r

_m ec rlf ae .c om .rv t

/2

5/

:5 4:

P

M

12" = 1'-0"

LI

F

E S

A F

E T

Y C

O D

E A

N A

LY

S

IS

A

N D

S Y

M B

O

LS

GC001

TJH MEC JL

12760424

11/18/20

DJD

mec Text Box

DSN

HM SMITH BOULEVARD

EXISTING PARKING

P A

T

IE

N T

V

IS

IT

O R

P A

R K

IN

G

STAFF PARKING

FH

FH

FH

T R

A V

E L P

A T

H : 1

'-6

TO FIRE LANE

140'-10"

T O

F

IR

E L

A N

E

0'

-2

T R

A V

E L P

A T

H

F D

C T

O F

IR

E

H Y

D R

A N

T

T O

F

IR

E H

Y D

R A

N T

TRAVEL PATH: 263'-6"

TO FIRE HYDRANT

T R A V E L

P A

TH

: 2

'-6

TO

F

IR

E H

YDRANT

TR

AVEL PATH

: 204'-6"

TO FIRE HYDRANT

TRAVEL PATH: 252'-0"

TO FIRE HYDRANT

TRAVEL

PATH: 2

'-0

TO F

IR

E H

YDRANT

FH

TRAVEL PATH: 147'-0"

TRAVEL PATH: 121'-0"

TO FIRE HYDRANT

TO FIRE HYDRANT

SITE LIFE SAFETY LEGEND

OPEN SPACE - WIDTH OF 60 FEET

FIRE DEPARTMENT VEHICLE ACCESS

EF

RT

I

N N

N O

L.

T E

N A

040804 E N G

R

NI E E R

OL

V

SEAL

S

A

SFORP

E

H C

I A L

OI N

OR L

T

JE

KEY NOTES 00

SHEET NOTES:

NOTES:

1" = 40' GRAPHIC SCALE

40'0 120'80' 160'20'

NPROJECT

NORTH

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m ec

\D oc um en ts \4

0-

B

LD

G -1

-A

_r

_m ec rlf ae .c om .rv t

/2

5/

:5 4:

P

M

As indicated

C O

D E

C O

M P

LI

A

N C

E S

IT

E

P

LA

N

GC100

TJH MEC JL

12760425

11/18/20

SCALE: 1" = 40'-0" A4

CODE COMPLIANCE SITE PLAN

1 MAIN ENTRANCE

2 SECONDARY ENTRANCE

3 NOT USED.

4 AMBULANCE PICK-UP / DELIVERIES

5 SERVICE AREA

6 REFUSE AREA

7 DROP-ARM GATE

8 FIRE HYDRANT, EXISTING

9 FIRE DEPARTMENT CONNECTION

10 WALL-MOUNTED INDICATOR VALVE

11 GAS STORAGE ENTRANCE

12 FIRE HYDRANT, NEW

A THE TOTAL PERIMETER OF THE BUILDING HAS MORE THAN 60 FEET WIDTH OF

OPEN SPACE.

DJD

mec

P

P

P

P

P

P

P

P

P

P

SMOKE PARTITION

1 HOUR FIRE BARRIER

1 HOUR FIRE & SMOKE BARRIER

TRAVEL DISTANCE TO EXIT, COMMON

PATH OR DEAD END CORRIDOR, AS

INDICATED

LIFE SAFETY SYMBOLS

FIRE EXTINGUISHER, CABINET

UNRATED PARTITION

FEC

SPEAKER / STROBE, WALL

FIRE EXTINGUISHER, WALL MOUNTEDFE

STROBE, WALL

WALL MOUNTED EXIT LIGHT

CEILING MOUNTED EXIT LIGHT

CEILING MOUNTED SMOKE DETECTOR

MANUAL PULL STATIONP

DOOR

EGRESS ELEMENT (DOOR, STAIR, HE)

EGRESS WIDTH (CLEAN INCHES)

EXIT WIDTH PER PERSON (INCHES)

CAPACITY (PEOPLE)

ACTUAL (PEOPLE)

5" STORZ FIRE DEPARTMENT CONNECTION

STROBE, CEILING

SPEAKER / STROBE, CEILING

SPEAKER, CEILING

EMERGENCY LIGHTING UNIT, WALL

XPXP

XPXP

XNXN XNXN

XMXM

XL.6XL.6

XLXL

XK.4XK.4

XJXJ

XFXF

XFXF

XH.5XH.5

XGXG

XEXE

XC.3XC.3

XRXR

XRXR

X1X1

X1X1

X2X2

X2X2 X3X3

X3X3 X4X4

X5X5

X5X5 X6X6 X7X7

X8X8

X8X8

X9X9

X9X9

X10X10

X10X10

X11X11

X11X11

X12X12

X12X12X4.5X4.5 X6.6X6.6 X7.2X7.2 X9.5X9.5 X9.8X9.8

X2.4X2.4 X3.2X3.2 X3.4X3.4 X3.5X3.5 X3.8X3.8 X4.3X4.3 X4.8X4.8 X6.2X6.2 X6.3X6.3 X6.5X6.5 X6.9X6.9 X7.3X7.3

X7.6X7.6 X7.7X7.7 X8.3X8.3 X8.4X8.4 X8.6X8.6 X8.8X8.8 X9.2X9.2 X9.4X9.4 X9.6X9.6

XC.6XC.6

XB.4XB.4

XBXB

XAXA

XCXC

XC.1XC.1

XDXD

XF.9XF.9

XKXK

XM.05XM.05

XM.1XM.1

XHXH

1 5 6

C

B

A

D

E

F

B.8

B.6

1.8

PROS LAB

x087

SUB-WAIT

x141

VEST

x124

PROS

x146

PROS

x145

GEN DTR

x144

GEN DTR

x143

CSR SOIL

x089

SURG SPRT

x090

SCRUB

x091

ORAL SURG

x092

SUPPLY ADMIN

x073

STOR

x074

BRANCH DIR

x075

ELEC

x069

MECHANICAL

x070

TEAM DTR

x134

CORR

x140

GEN DTR

x133

CONSULT

x132

GEN DTR

x138

CONSULT

x137

TEAM DTR

x136

GEN DTR

x135

CORR

x109

MALE TLT

x094

FEMALE TLT

x102

OFFICE

x108

PERIO

x101

PERIO SUPV

x093

PERIO

x100

FEMALE LCKR

x099

TLT

x098

X-RAY ADMIN

x104

ENDO SUPV

x103

FEMALE LCKR

x096

SURGERY SUPV

x097

XRAY

x105

CORR

x095

LCPO

x077

LPO

x078

MALE STAFF

x080ADMIN x076

SUPPLY

x084

CERAMICS

x085

CASTING

x086

ORAL DIAG

x107

ORAL DIAG

x106

CORR

x110

ORAL HYGIENE

x113

ENDO

x112

HOUSEKEEPING

x118

ORAL DIAG

x119

ORAL DIAG

x120

SICK CALL

x121

GEN DTR

x122

CONTROL / RECORDS

x117

ORAL DIAG SUPV

x115

ORAL HYGIENE

x114

ENDO

x111

CORR

x125

FEMALE STAFF

x126

COMM

x128

PROS SUPV

x129

COURTYARD

x150

CORR

x088

GEN DTR

x130

GEN DTR

x131

CORR

x142

SUB-WAIT

x123

CONFERENCE

x072

CSR CLEAN

x066

GAS STOR

1H02

LOUNGE

1G22

JAN

1G20

CHIEF (SMO)

1E23

RN MNGR

1E21

COMM

1G15

TLT

1G17

TLT

1E14

OBS / HYD

1E24

TREAT

1E26

SOILED

1E28

CLEAN

1E29

EQUIPMENT

1G09

TLT

1D17

TREAT

1E27

LCPO / LPO

1E19

EQUIPMENT

1F04

EKG

1E17

VISION SCREEN

1E13

EXAM

1E12

MCMH TEAM LEAD

1E18

EXAM / CONSULT

1E05

EXAM / CONSULT

1E07

EXAM

1E09

EXAM

1E11

EXAM / CONSULT

1E03

WAIT

1A05

VEST

1A01

LOBBY

1A02

MEASURES

1DC2A

IMMUNI

1D05

WAIT / OBS

1D02

TLT

1E43

EXAM

1E44

EXAM

1E41

EXAM

1E35

EXAM

1E37

EXAM

1E39

EXAM

1D13

TEAM COLLABORATION

1D08

RN (BH)

1C12

PROV (BH)

1C10

EXAM

1D25

TLT MALE

1A08

MEDICAL RECORDS

1B01

RECEPTION

1C01

RAD

1C03

JAN

1C08

PHARMACY

1C07

DRESS

1C05

WAIT

1A03

CLASS

1A04

DRAWING

1C02

SPECIMEN TLT

1C04

LAB

1C06

DENTAL LOUNGE

1G03

CONF

1G18

CORR

1EC5

CORR

1EC4

CORR

1CC1

CORR

1AC2

CORR

1GC1

SHWR

1G14C

SHWR

1G14B

F LOCKERS

1G14

TLT

1G14A

TLT

1G12A

SHWR

1G12B

SHWR

1G12C

M LOCKERS

1G12

TLT FEMALE

1A06

WAIT

1A10

WAIT

1A09

ELEC

1G01

LACTATION

1E32

ICE

1GC4A

EXAM

1E16

REHAB

1F02

RECEPTION

1E01

MEASURES

1EC2A

TEAM COLLABORATION

1E06

LOGISTICS

1G08

MCMH TEAM LEAD

1D18

EXAM

1D19

TRASH / RECYC

1G07

RMW

1G04

JAN

1G02

EXAM

1D11

TLT, ISO

1D27A

EXAM / CONSULT

1D03

TLT

1D29

EXAM

1D07

TLT

1D15

CORR

1DC5

CORR

1DC1

CORR

1DC2

CORR

1DC3

CORR

1DC4

CORR

1EC6

CORR

1CC6

CORR

1EC1

CORR

1EC3

CORR

1GC2

CORR

1GC3

CORR

1GC4

CORR

1EC2

RECEPTION

1D01

8 PERSON BOOTH

WAIT

1A09

0.2

DOOR

FEC

FEC FEC

FEC

FEC FEC

FEC

FEC FEC

FEC

FEC

FEC

FEC

0.2

DOOR

0.2

DOOR

0.2

DOOR

0.2

DOOR

0.2

DOOR

0.2

DOOR

EXAM, ISO

1D27

EXAM

1D24

EXAM

1D09

GEN DTR

x139

JAN

x081

WAITING

x109A

WAITING

x109B

EXAM

1D23

TRAVEL PATH: 160'-0"

T R

A V

E L P

A T

H

TRAVEL PATH: 121'-0"

TRAVEL PATH: 192'-0"

TRAVEL PATH: 114'-6"

4.1

4.1

EXAM

1D12

AUDIOBOOTH

1D21

KIOSK

1A05A

KIOSK

1A02A

PHYSICAL THERAPY

1F01

FE

FE

FE

TRAVEL PATH: 121'-6"

MAIN COMM

1G10

MAIN ELEC

1H01

MECH

1G06

TRAVEL PATH: 133'-6"

FEC

4.5

ELEC

1G19

DERM STORAGE

1E33

A.9

COMMON PATH: 84'-0"

T R

A V

E L P

A T

H

D E

A D

E N

D

D E

A D

E N

D

FE

198'-6"

3.7

3.7

3.8

3.8

0.2

DOOR

TRAVEL DISTANCES

PATH OF EGRESS TRAVEL DISTANCE

COMMON PATH 84'-0"

DEAD END 10'-6"

DEAD END 22'-0"

TRAVEL DISTANCE 121'-0"

TRAVEL DISTANCE 121'-6"

TRAVEL DISTANCE 192'-0"

TRAVEL DISTANCE 107'-0"

TRAVEL DISTANCE 133'-6"

TRAVEL DISTANCE 160'-6"

TRAVEL DISTANCE 66'-6"

TRAVEL DISTANCE 198'-6"

EF

RT

I

N N

N O

L.

T E

N A

040804 E N G

R

NI E E R

OL

V

SEAL

S

A

SFORP

E

H C

I A L

OI N

OR L

T

JE

SHEET NOTES:

NOTES:

KEYPLAN

KEYPLAN

KEYPLAN

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

NPROJECT

NORTH

KEYPLAN

KEYPLAN

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m ec

\D oc um en ts \4

0-

B

LD

G -1

-A

_r

_m ec rlf ae .c om .rv t

/2

5/

:5 4:

P

M

As indicated

A R

C H

IT

E

C T

U R

A L

LI

F

E S

A F

E T

Y P

LA

N

, C O

M P

O S

IT

E

GC101

TJH MEC JL

12760426

11/18/20

SCALE: 1/16" = 1'-0" A4

FIRST FLOOR OVERALL FLOOR PLAN

A REFER TO SHEET GI010 FOR GENERAL ABBREVIATIONS AND ARCHITECTURAL

SYMBOLS.

B THIS DRAWING IS FOR REFERENCE ONLY.

C DASHED LINES REPRESENT ITEMS ABOVE.

D REFER TO FIRE PROTECTION DRAWINGS FOR FIRE SPRINKLER / FIRE

PROTECTION INFORMATION.

E FIRE EXTINGUISHERS ARE PROVIDED BY OWNER. CONTRACTOR MUST

PROVIDE BRACKETS AND CABINETS ONLY.

F ALL EXIT SIGNS AND VISUAL NOTIFICATION APPLIANCES ARE TO BE MOUNTED

TO MAXIMIZE VISIBILITY.

G MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER IS 75 FT.

H REFER TO SHEETS AE800 SERIES FOR PARTITION TYPES AND PARTITION

DETAILS.

I REFER TO B2/AE831 FOR TYPICAL FEC (104400.B03) PLAN DETAIL.

J REFER TO 1/8" SCALE FLOOR PLANS FOR PARTITION TYPES.

K CONTINUE RATED WALLS TO INSIDE FACE OF EXTERIOR CMU WALLS.

DJD

mec

GC001 - LIFE SAFETY CODE ANALYSIS AND SYMBOLS
GC100 - CODE COMPLIANCE SITE PLAN
GC101 - ARCHITECTURAL LIFE SAFETY PLAN, COMPOSITE
2019-12-26T10:51:40-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2019-12-26T10:53:18-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2019-12-26T10:53:18-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2021-01-16T15:43:26-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T15:43:40-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T15:43:51-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T15:44:10-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T15:44:25-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T15:44:25-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .