This solicitation is for a design-bid-build construction project for the P4040 French Creek Ambulatory Care Clinic located at Camp Lejeune, North Carolina. The Navy seeks a contractor to design and construct additions and alterations to the existing clinic to include new exam rooms, waiting areas, administrative spaces, and support spaces. Bids are due by January 31, 2022 with award anticipated by March 2022. The period of performance is 730 calendar days from notice to proceed. The Navy will evaluate bids using best value criteria considering technical approach, past performance, and price. This opportunity is set aside for small businesses.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FACP
FIRE ALARM MASS NOTIFICATION SYSTEM FIRE ALARM NOTES:
1. INSTALL ALL FIRE ALARM SYSTEM WIRING IN 3/4" MINIMUM CONDUIT
UNLESS NOTED OTHERWISE. INCOMING AND OUTGOING CLASS A WIRING
SHALL BE INSTALLED IN SEPARATE CONDUIT PER NFPA 72.
2. CONDUIT SIZES AND QUANTITIES ARE SHOWN FOR REFERENCE ONLY.
PROVIDE CONDUIT SIZES, QUANTITIES, AND CONFIGURATION IN
ACCORDANCE WITH MANUFACTURERS APPROVED SHOP DRAWINGS.
3. PROVIDE CONTROL MODULE FOR EACH MOTOR STARTER AND VARIABLE
FREQUENCY DRIVE (VFD) SERVING HVAC SYSTEM SUPPLY AND RETURN
FANS EVEN IF THEY ARE NOT SPECIFICALLY SHOWN ON THE FIRE ALARM
PLANS, UNLESS OTHERWISE NOTED. MOUNT CONTROL MODULE WITHIN
36" OF THE STARTER OR VFD SERVED. CONTROL MODULE SHALL SHUT
DOWN ASSOCIATED FAN AS INDICATED ON THE FIRE ALARM SEQUENCE OF
OPERATION.
4. PROVIDE MONITOR MODULE FOR FIRE SPRINKLER SYSTEM FLOW AND
TAMPER SWITCH EVEN IF THEY ARE NOT SPECIFICALLY SHOWN ON THE
FIRE ALARM PLANS. MOUNT MONITOR MODULE WITHIN 36" OF DEVICE
SERVED.
5. REFER TO A4/FA601 FOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
RISER DIAGRAM AND FA001 FOR SEQUENCE OF OPERATIONS MATRIX.
6. PROVIDE EQUIPMENT IDENTIFICATION LABELS FOR FIRE ALARM
EQUIPMENT INSTALLED UNDER THIS PROJECT. SEE C3/ET501 FOR LABEL
DETAILS.
72" AFF TO TOP,
UON
SYMBOL DESCRIPTION MOUNTING
SURFACE MOUNTED FIRE ALARM SYSTEM EQUIPMENT.
SUBSCRIPTS INDICATE THE FOLLOWING:
48" AFF TO THE
OPERATING
HANDLE
WALL MOUNTED MANUAL PULL STATION.
CEILINGSMOKE DETECTOR, PHOTOELECTRIC TYPE.
ADDRESSABLE INTERFACE DEVICE, CONTROL MODULE.
SUBSCRIPTS INDICATE THE FOLLOWING:
MOUNT WITHIN
36" OF ITEM
MONITORED
P
ADDRESSABLE INTERFACE DEVICE, MONITOR MODULE.
SUBSCRIPTS INDICATE THE FOLLOWING:
MOUNT WITHIN
36" OF ITEM
MONITORED
DUCT MOUNTED SMOKE DETECTOR FOR INDICATED
EQUIPMENT. SUBSCRIPTS INDICATE THE FOLLOWING:
DUCT MOUNTED
FOR INDICATED
EQUIPMENT
AOM
AIM
AHU/1.1
COMBINATION VOICE EVACUATION SPEAKER/STROBE UNIT
WITH CLEAR LENS. SUBSCRIPTS INDICATE THE FOLLOWING:
80" AFF TO
CENTER, UON.
FLUSH CEILING MOUNTED SPEAKER. CEILING
FAAP
FACP
FRTP
DACT
LOC
RFCU
MNRS
FIRE ALARM REMOTE ANNUNCIATOR PANEL
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
FIRE ALARM RADIO TRANSMITTER PANEL
DIGITAL ALARM COMMUNICATOR TRANSMITTER
MASS NOTIFICATION LOCAL OPERATOR CONSOLE
REMOTE FIRE ALARM CONTROL UNIT (ie. POWER
SUPPLY BATTERIES, AUDIO AMPLIFIER, ETC)
BASE-WIDE MASS NOTIFICATION SYSTEM REMOTE
STATION. PROVIDE 4" x 4" x 2" DEEP BOX, FLUSH
MOUNTED. PROVIDE CONDUIT AND AUDIO CABLE AS
INDICATED ON A4/FA601. LABEL BOX AND CONDUIT
"FOR MNS USE". MOUNT 54" AFF TO CENTER.
R S
RETURN DUCT.
SUPPLY DUCT.
WP WEATHER PROOF COVER, UL LISTED FOR USE IN
WET LOCATIONS.
FLUSH CEILING MOUNTED SPEAKER/STROBE UNIT WITH
CLEAR LENS. NUMERAL INDICATES CANDELA RATING.
CEILING
FS
TS
FIRE SPRINKLER FLOW SWITCH
FIRE SPRINKLER TAMPER SWITCH
PA
DDC
OFS
PUBLIC ADDRESS SPEAKERS
HVAC DDC SHUTDOWN NOTIFICATION
DEACTIVATION OF FIRE SHUTTER OVERHEAD DOOR
FIRE ALARM MASS NOTIFICATION STROBE WITH CLEAR LENS
MARKED "ALERT". NUMERAL INDICATES CANDELA RATING.
80" AFF TO
BOTTOM, UON.
FIRE ALARM MASS NOTIFICATION STROBE WITH CLEAR LENS
MARKED "ALERT". NUMERAL INDICATES CANDELA RATING..
CEILING
CONNECTION TO SPRINKLER SYSTEM FLOW SWITCH. N/A
CONNECTION TO SPRINKLER SYSTEM TAMPER SWITCH. N/A
15 CANDELA RATING.-
FLUSH WALL MOUNTED WEATHER PROOF SPEAKER. 10'-0" AFF TO
CENTER, UONWP
7'-8" TO CENTER
OF DEVICE, 10'
FROM FUEL FIRED
EQUIPMENT
CO
CARBON MONOXIDE DETECTOR.
WP WEATHER PROOF COVER, UL LISTED FOR USE IN
WET LOCATIONS.
15 CANDELA RATING.-
FIRE ALARM SYSTEM
SEQUENCE OF OPERATION MATRIX
SYSTEM INPUTS
S
Y S
T E
M O
U T
P U
T S
ACTIVATE NOTIFICATION APPLIANCE STROBE
LIGHTS AND SPEAKERS
M A
N U
A L
P U
LL
S
T A
T
IO
N
W A
T E
R F
LO
W
S W
IT
C
H
S P
R
IN
K
LE
R V
A
LV
E T
A M
P E
R S
W
IT
C H
G R
O U
N D
F A
U
LT
C O
N D
U C
T O
R B
R E
A K
DISPLAY ALARM INDICATION AT FACP AND
FAAP
TRANSMIT ALARM SIGNAL TO THE FIRE
DEPARTMENT
RECORD INFORMATION ON CPU
S M
O K
E D
E T
E C
T O
R S
S M
O K
E D
E T
E C
T O
R A
T F
IR
E
S H
U T
T E
R
D U
C T
M O
U N
T E
D S
M O
K E
D E
T E
C T
O R
M A
S S
N O
T
IF
IC
A
T
IO
N L
IV
E
V O
IC
E
M E
S S
A G
E
LO
C
DISPLAY SUPERVISORY CONDITION AT FACP
AND FAAP
TRANSMIT SUPERVISORY SIGNAL TO THE FIRE
DEPARTMENT
DISPLAY TROUBLE CONDITION AT FACP AND
FAAP
TRANSMIT TROUBLE SIGNAL TO FIRE
DEPARTMENT
TEMPORARILY OVERRIDE FIRE ALARM AUDIBLE
AND VISUAL SIGNALS AND DISPLAY A DISTINCT
SUPERVISORY SIGNAL AT THE FACP
SHUT DOWN AIR HANDLING UNITS
A C
T
IV
A T
IO
N
O F
M A
S S
N O
T
IF
IC
A
T
IO
N S
Y S
T E
M A
U T
O N
O M
O U
S C
O N
T R
O L
U N
IT
LI
V E
V O
IC
E
M E
S S
A G
E
LO
S
S O
F A
C P
O W
E R
LO
W
B A
T T
E R
Y V
O
LT
A G
E
R E
M O
V A
L O
F A
LA
R
M O
R S
U P
E R
V
IS
O R
Y P
A N
E L
M O
D U
LE
S
ACTIVATE LIVE MASS NOTIFICATION VOICE
ANNOUNCEMENT
F
IR
E A
LA
R
M S
Y S
T E
M
LI
V E
V O
IC
E
M E
S S
A G
E
A B PC I J K L M ND E F G H O
14MUTE PUBLIC ADDRESS SYSTEM SPEAKERS
C O
D E
T E
C T
O R
A C
T
IV
A T
IO
N
ACTIVATE FIRE ALARM NOTIFICATION
APPLIANCE STROBE LIGHTS AND SPEAKERS
(CO ALARM MESSAGE AND TEMPORAL 4 TONE)
TRANSMIT CO ALARM SIGNAL TO THE FIRE
DEPARTMENT 5
C O
D E
T E
C T
O R
C E
LL
E
N D
O F
L
IF
E
15RELEASE OVERHEAD FIRE SHUTTER DOORS
GENERAL FIRE ALARM SYTEM SEQUENCE OF
CONSTRUCTION NOTES
FIRE ALARM SYSTEM SEQUENCE OF CONSTRUCTION NOTES
A. FIRE ALARM SYSTEM WORK MUST BE PHASED IN ORDER TO MAINTAIN SERVICE TO THE
EXISTING PORTION OF THE CLINIC DURING CONSTRUCTION AND TO PROVIDE NEW
SERVICE TO RENOVATED AND EXPANDED BUILDING. ALL WORK ASSOCIATED WITH
REPLACING THE EXISTING FIRE ALARM SYSTEM ON THE DENTAL PORTION OF THE CLINIC
AND RECONNECTING TO THE NEW FIRE ALARM SYSTEM SHALL BE PERFORMED DURING
THE 30-DAY PERIOD SCHEDULED FOR THE DENTAL SIDE TO BE VACATED. COORDINATE
SCHEDULE WITH CONTRACTING OFFICER. DURATION OF SERVICE OUTAGES MUST BE
MINIMIZED TO THE GREATEST EXTENT POSSIBLE. PROVIDE ALL POSSIBLE ROUGH-IN
WORK PRIOR TO DISCONNECTION OF EXISTING WIRING TO HELP MINIMIZE OUTAGE
DURATIONS.
B. INSTALL AND TEST ALL NEW FIRE ALARM SYSTEM EQUIPMENT PRIOR TO
DISCONNECTING AND REMOVING EXISTING SYSTEM PANEL AND DEVICES.
C. PROVIDE A FIRE WATCH FOR THE DURATION OF THE SWITCHOVER FROM THE EXISTING
TO THE NEW SYSTEM.
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
IO
N
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
D
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
12" = 1'-0"
F
IR
E A
LA
R
M L
E G
E N
D A
N D
S E
Q U
E N
C E
O F
O P
E R
A T
IO
N
M A
T R
IX
FA001
NGZ SSS DRS
12760646
11/18/20
DSN
mec Text Box
DSN
P P
P
P
P
X12X12X11X11X10X10X9.8X9.8X9.5X9.5X9X9X8X8X7.2X7.2X7X7X6.6X6.6X6X6X5X5X4.5X4.5
X4X4X3X3
X2.4X2.4X2X2 X3.2X3.2 X3.4X3.4 X3.5X3.5 X3.8X3.8 X4.3X4.3 X4.8X4.8 X6.2X6.2 X6.3X6.3 X6.5X6.5 X6.9X6.9 X7.3X7.3 X7.6X7.6 X7.7X7.7 X8.3X8.3 X8.4X8.4 X8.6X8.6 X8.8X8.8 X9.2X9.2 X9.4X9.4 X9.6X9.6
XC.3XC.3
XEXE
XFXF
XGXG
XH.5XH.5
XJXJ
XK.4XK.4
XLXL
XL.6XL.6
XMXM
XM.1XM.1
XM.05XM.05
XNXN
XPXPXRXR
XHXH
XF.9XF.9
XKXK
XC.6XC.6
XB.4XB.4
XBXB
XAXA
XCXC
XC.1XC.1
FRTP
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
KEY NOTES 00
SHEET NOTES:
NOTES:
0 10'
1/16" = 1'-0" GRAPHIC SCALE
20' 40' 60'
NPROJECT
NORTH
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
1/16" = 1'-0"
E
LE
C T
R
IC
A L
P
LA
N S
, D E
M O
LI
T
IO
N
F
IR
E
A
LA
R M
FD101
NGZ SSS DRS
12760647
11/18/20
A. THIS DRAWING REPRESENTS GENERAL ITEMS, SIZES, QUANTITY AND
LAYOUT OF ITEMS TO BE REMOVED. VERIFY THE ACTUAL CONDITION AND
COMPOSITION OF WORK TO BE PROVIDED.
B. UNLESS SPECIFICALLY NOTED OTHERWISE, REMOVE ALL EXISTING FIRE
ALARM SYSTEM DEVICES LOCATED IN THE WALLS, AND CEILINGS
SCHEDULED FOR DEMOLITION. REMOVAL SHALL INCLUDE ALL BACK BOXES,
CONDUITS AND WIRING BACK TO THE HEADEND EQUIPMENT. CONDUIT
WHICH PASSES THROUGH EXISTING AREAS TO REMAIN MAY BE
ABANDONED IN PLACE. REFER TO ARCHITECTURAL DEMOLITION PLANS
FOR EXTENT OF DEMOLITION.
C. REFER TO SHEET FA001 FOR CONSTRUCTION SEQUENCE NOTES.
SCALE: 1/16" = 1'-0" A4
DEMOLITION - FIRE ALARM
1 REMOVE EXISTING FIRE ALARM PANEL.TURN PANEL OVER TO
CONTRACTING OFFICER AFTER REMOVAL. REMOVAL SHALL
OCCUR AFTER THE NEW DEVICES IN EXISTING TO REMAIN AREAS
ARE INSTALLED AND OPERATIONAL THROUGH THE NEW FACP.
2 REMOVE ALL EXISTING FIRE ALARM SYSTEM DEVICES. REMOVE
ALL ASSOCIATED WIRING, RACEWAYS, AND CABLE TRAYS. NOT ALL
EXISTING FIRE ALARM DEVICES TO BE REMOVED IN THIS AREA ARE
SHOWN. SEE FIRE ALARM SYSTEM PLANS FOR ADDITIONAL
REQUIREMENTS REGARDING EXISTING DEVICES.
DSN
mec
P
1G22
LOUNGE
1G20
JAN
1G18
CONF
1E23
CHIEF
(SMO)
1E21
RN MNGR
1E19
LCPO /
LPO
1G17
TLT
1G15
COMM
1E26
TREAT
1E28
SOILED
1E14
TLT
1E27
TREAT
1E29
CLEAN
1E11
EXAM
1E09
EXAM
1E12
EXAM
1E17
EKG
1E13
VISION
SCREEN
1E18
MCMH
TEAM
LEAD
1F04
EQUIPMENT
1E35
EXAM
1E39
EXAM
1E37
EXAM
1E41
EXAM
1E07
EXAM /
CONSULT
1E05
EXAM /
CONSULT
1E03
EXAM /
CONSULT
1E44
EXAM
1E43
TLT
1D02
WAIT / OBS
1E24
OBS / HYD
1EC5
CORR
1EC4
CORR
1G12 M
LOCKERS
1G14 F
LOCKERS
1G14B
SHWR
1G12B
SHWR
1G12A
TLT
1G14A
TLT1G14C
SHWR
1G12C
SHWR
1A10
WAIT
1A09
WAIT
1E32
LACTATION
1GC4A
ICE
1E16
EXAM
1F02
REHAB
1E01
RECEPTION
1EC2A
MEASURES
1E06
TEAM
COLLABORATION
1EC6
CORR
1EC1
CORR
1EC3
CORR
1GC3
CORR
1GC4
CORR
1EC2
CORR
B
B.6
B.8
C
D
E
F
1 1.8 2 2.2 2.6 3 3.3 3.7 3.8 4
XC.6XC.6
XB.4XB.4
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
1F01
PHYSICAL
THERAPY
15 15
WP
WP
1G19
ELEC
1E33
DERM
STORAGE
1AC4
CORR
WP WP
75 75
75 75
WP
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
NPROJECT
NORTH
KEYPLAN
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
1/8" = 1'-0"
F
IR
E A
LA
R
M , S
E C
T O
R
FA101-1
NGZ SSS DRS
12760648
11/18/20
SCALE: 1/8" = 1'-0" A4
FIRE ALARM PLAN, SECTOR 1
DSN
mec
P
P x089
CSR SOIL
x090
SURG
SPRT
x091
SCRUB
x073
SUPPLY
ADMIN
x074
STOR
x069
ELEC
x070
MECHANICAL
1H02
GAS STOR
1G09
EQUIPMENT
1D17
TLT 1C12
RN (BH)
1C06
LAB 1C02
DRAWING
1C04
SPECIMEN
TLT
1C10
PROV (BH)
1A04
CLASS
1G03
DENTAL
LOUNGE x066
CSR
CLEAN
x072
CONFERENCE
1GC1
CORR
1GC2
CORR
1G01
ELEC
1G08
LOGISTICS
1D15
TLT
1D19
EXAM
1D18
MCMH
TEAM
LEAD
1G07
TRASH /
RECYC
1G04
RMW 1G02
JAN
1DC5
CORR
1CC6
CORR
1D23
EXAM
MATCH LINE
SEE A4/FA101-3
MATCH LINE
SEE A4/FA101-3
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
A
B
B.6
B.8
C
4 4.8
XKXK
1DC3
CORR
1D21
AUDIOBOOTH
1D21
AUDIOBOOTH
1AC2
CORR
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
WP
1G10
MAIN
COMM
1H01
MAIN ELEC
1G06
MECH
R
AHU/1
S
AHU/1
S
AHU/2
R
AHU/2
AIM
AIM
TS
TS
AOM
AOM
AOM
AOM
AOM
AOM
DC-03
DC-04
VFD-AHU-1 FAN 1
VFD-AHU-1 FAN 2
VFD-AHU-2 FAN1
VFD-AHU-2 FAN 2 FCU-A.1
AIM
FS
FCU-A.2
CO
CO
CO
CO
AOM
PA
AIM
TS
AOM
AOM
VFD-FCU-A.1
AOM
FCU-A.2
75 75
75 75
WP
S
FACP DACT
RFCU-1
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
KEY NOTES 00
SHEET NOTES:
NOTES:
KEYPLAN
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
NPROJECT
NORTH
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
1/8" = 1'-0"
F
IR
E A
LA
R
M , S
E C
T O
R
FA101-2
NGZ BTB DRS
12760649
11/18/20
SCALE: 1/8" = 1'-0" A4
FIRE ALARM PLAN, SECTOR 2
1 DUCT DETECTOR FOR EXISTING ROOF MOUNTED AIR HANDLER.
2 INTERFACE CONTROL MODULE FOR SHUTDOWN OF EXISTING ROOF
MOUNTED AIR HANDLER.
3 MASS NOTIFICATION SYSTEM ENCLOSURE. SEE A4/FA601 FOR
ADDITIONAL REQUIREMENTS.
4 PROVIDE A 24" x 24"x 1" PLYWOOD BACKBOARD. MOUNT AT 72" AFF TO
TOP. CLEARLY MARK PLYWOOD AS "BASE-WIDE MNS USE"
5 MOUNT INSIDE AUDIOBOOTH AND COORDINATE WITH AUDIO BOOTH
MANUFACTURER PRIOR TO INSTALLATION.
6 FIRE ALARM SYSTEM DOCUMENTATING AND SPARE PARTS CABINET.
COORDINATE EXACT LOCATION WITH CONTRACTING OFFICER.
A. PROVIDE ADDITIONAL FIRE ALARM SYSTEM DEVICES SUCH AS
CONTROL MODULES, MONITOR MODULES, DUCT DETECTORS,
SMOKE DETECTORS, FLOW SWITCHES, AND TAMPER
SWITCHES TO REPLACE EXISTING DEVICES BEING REMOVED
UNDER THE DEMOLITION PHASE THAT ARE ASSOCIATED WITH
EXISTING HVAC AND FIRE PROTECTION SYSTEMS.
B. EXISTING HVAC AND FIRE PROTECTION SYSTEM EQUIPMENT
SHALL INTERFACE WITH FIRE ALARM SYSTEM AND COMPLY
WITH SEQUENCE OF OPERATIONS MATRIX ON SHEET FA001.
INTERFACE OF ALL EXISTING SYSTEMS WITH FIRE ALARM
SYSTEM SHALL BE TESTED FOR PROPER OPERATION.
DSN
mec x092
ORAL
SURG
x094
MALE TLT
x093
PERIO
SUPV
1D05
IMMUNI
1D13
EXAM
1D25
EXAM
1A08
TLT MALE
1C05
DRESS
1C08
JAN
1C03
RAD
1A01
VEST
1A05
WAIT
1DC2A
MEASURES
1D08
TEAM
COLLABORATION
1B01
MEDICAL
RECORDS
1C01
RECEPTION
1A03
WAIT
1A02
LOBBY
1C07
PHARMACY
1CC1
CORR
1A06
TLT
FEMALE
1D11
EXAM
1D07
EXAM
1D03
EXAM /
CONSULT
1D29
TLT
1D27A
TLT, ISO
1DC1
CORR
1DC2
CORR
1DC3
CORR
1D01
RECEPTION
1D24
EXAM
1D27
EXAM, ISO
1D09
EXAM
MATCH LINE
SEE A4/FA101-2
MATCH LINE
SEE A4/FA101-2
D
E
F
4.8 X7.2X7.2X6.6X6.6X4.5X4.5
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
1D12
EXAM
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
75 75
15 15
15 15
15 15
LOCFAAP
1AC3
CORR
75 75
15 75
AOM
OFS
AOM
OFS
MNRS
AOM
OFS
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
KEY NOTES 00
SHEET NOTES:
NOTES:
KEYPLAN
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
NPROJECT
NORTH
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
1/8" = 1'-0"
F
IR
E A
LA
R
M , S
E C
T O
R
FA101-3
NGZ BTB DRS
12760650
11/18/20
SCALE: 1/8" = 1'-0" A4
FIRE ALARM PLAN, SECTOR 3
A. PROVIDE ADDITIONAL FIRE ALARM SYSTEM DEVICES SUCH AS CONTROL
MODULES, MONITOR MODULES, DUCT DETECTORS, SMOKE DETECTORS,
FLOW SWITCHES, AND TAMPER SWITCHES TO REPLACE EXISTING DEVICES
BEING REMOVED UNDER THE DEMOLITION PHASE THAT ARE ASSOCIATED
WITH EXISTING HVAC AND FIRE PROTECTION SYSTEMS.
B. EXISTING HVAC AND FIRE PROTECTION SYSTEM EQUIPMENT SHALL
INTERFACE WITH FIRE ALARM SYSTEM AND COMPLY WITH SEQUENCE OF
OPERATIONS MATRIX ON SHEET FA001. INTERFACE OF ALL EXISTING
SYSTEMS WITH FIRE ALARM SYSTEM SHALL BE TESTED FOR PROPER
OPERATION.
1 ROUTE FIRE ALARM CONDUIT THROUGH STORE FRONT ALUMINUM
CHANNEL TO DEVICE.
2 FIRE ALARM SYSTEM KNOX BOX. COORDINATE REQUIREMENTS AND
EXACT LOCATION WITH CONTRACTING OFFICER.
DSN
mec x087
PROS LAB
x141
SUB-WAIT
x124
VEST
x146
PROS
x145
PROS
x144
GEN DTR
x143
GEN DTR
x073
SUPPLY
ADMIN
x074
STOR
x075
BRANCH
DIR
x134
TEAM DTR
x140
CORR
x133
GEN DTR
x132
CONSULT
x138
GEN DTR
x137
CONSULT
x136
TEAM DTR
x135
GEN DTR
x109
CORR
x102
FEMALE
TLT
x108
OFFICE
x101
PERIO
x100
PERIO
x099
FEMALE
LCKR
x098
TLT
x104
X-RAY
ADMIN
x103
ENDO
SUPV
x096
FEMALE
LCKR
x097
SURGERY
SUPV
x105
XRAY
x095
CORR
x077
LCPO
x078
LPO
x080
MALE
STAFF
x076 ADMIN x084
SUPPLY
x085
CERAMICS
x086
CASTING
x107
ORAL DIAG
x106
ORAL DIAG
x110
CORR
x113
ORAL
HYGIENE
x112
ENDO
x118
HOUSEKEEPING
x119
ORAL DIAG
x120
ORAL DIAG
x121
SICK CALL
x122
GEN DTR
x117
CONTROL /
RECORDS
x115
ORAL DIAG
SUPV
x114
ORAL
HYGIENE
x111
ENDO
x125
CORR
x126
FEMALE
STAFF
x128
COMM
x129
PROS
SUPV
x150
COURTYARD
x088
CORR
x130
GEN DTR
x131
GEN DTR
x142
CORR
x123
SUB-WAIT
x139
GEN DTR
B
B.6
B.8
C
D
E
X12X12X11X11X10X10X9.8X9.8X9.5X9.5X9X9X8X8
X7.2X7.2X7X7
X6.9X6.9 X7.3X7.3 X7.6X7.6X7.7X7.7 X8.3X8.3X8.4X8.4 X8.6X8.6 X8.8X8.8 X9.2X9.2 X9.4X9.4 X9.6X9.6
XC.3XC.3
XEXE
XFXF
XGXG
XH.5XH.5
XJXJ
XK.4XK.4
XLXL
XL.6XL.6
XMXM
XM.1XM.1
XM.05XM.05
XNXN
XPXP
XRXR
XHXH
XF.9XF.9
XKXK
XC.6XC.6
XCXC
XC.1XC.1
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
M A
T C
H L
IN
E
S E
E A
4/ F
A
1-
WP
WP
15 15
15 15
15 15
15 15
30 30
RFCU-2
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
SHEET NOTES:
NOTES:
KEYPLAN
0 5'
1/8" = 1'-0" GRAPHIC SCALE
10' 20' 30'
NPROJECT
NORTH
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
1/8" = 1'-0"
F
IR
E A
LA
R
M , S
E C
T O
R
FA101-4
NGZ SSS DRS
12760651
11/18/20
SCALE: 1/8" = 1'-0" A4
FIRE ALARM PLAN, SECTOR 4
A. PROVIDE ADDITIONAL FIRE ALARM SYSTEM DEVICES SUCH AS
CONTROL MODULES, MONITOR MODULES, DUCT DETECTORS,
SMOKE DETECTORS, FLOW SWITCHES, AND TAMPER
SWITCHES TO REPLACE EXISTING DEVICES BEING REMOVED
UNDER THE DEMOLITION PHASE THAT ARE ASSOCIATED WITH
EXISTING HVAC AND FIRE PROTECTION SYSTEMS.
B. EXISTING HVAC AND FIRE PROTECTION SYSTEM EQUIPMENT
SHALL INTERFACE WITH FIRE ALARM SYSTEM AND COMPLY
WITH SEQUENCE OF OPERATIONS MATRIX ON SHEET FA001.
INTERFACE OF ALL EXISTING SYSTEMS WITH FIRE ALARM
SYSTEM SHALL BE TESTED FOR PROPER OPERATION.
DSN
mec
RM. 1G10 RM. X069
FACP DACT
RFCU-1
LOC
FAAP
LOBBY 1A02
LOBBY 1A02
NAC
SLC(I)
SERVES FIRST
FLOOR WEST
120V
(SEE EP401 FOR CIRCUIT)
SLC(I)
SLC(O)
DAL
SLC(O)
120V
(SEE EP402 FOR CIRCUIT)
120V
(SEE EP402 FOR CIRCUIT)
FIRST FLOOR
ROOF
WIRING LEGEND
SLC(I) INCOMING SIGNALING LINE CIRCUIT
NAC NOTIFICATION APPLIANCE CIRCUIT
DAL DIGITAL AUDIO LOOP
SLC(O) OUTGOING SIGNALING LINE CIRCUIT
RFCU-2
NAC
SERVES FIRST
FLOOR EAST
120V
(SEE EP101-4 FOR CIRCUIT)
SLC(I)
SLC(O)
DAL
DAL
SLC(I)
SLC(O)
RM. X128
120V
(SEE EP402 FOR CIRCUIT)
MNRS
ROOM
1C01
MNS
FACP
RFCU
NOTIFICATION APPLIANCE
CIRCUITS (NAC)
VFD
VFD
P
AOMS R
W 6
AIM
TS
AIM
FS
SIGNALING LINE CIRCUIT
(SLC)
AOM
PA
AOM
DDC
CO
DAA PS
C C
120V CIRCUIT
CONTROL MODULE
FOR ACTIVATION
OF STROBES
INCOMING SIGNALING LINE CIRCUIT
(SLC) BACKBONE FROM FACP
AUDIO CONTROL LOOP
TO ADDITIONAL RFCU
CLASS A BACKBONE WIRING
DIGITAL AUDIO
AMPLIFIER WITH
BATTERY BACKUP
TYPICAL REMOTE POWER
SUPPLY/AMPLIFIER
CABINET (RPSC)
AUDIO CONTROL LOOP
TO ADDITIONAL RFCU
OUTGOING SIGNALING LINE CIRCUIT
(SLC) BACKBONE TO FACP
CLASS A
BACKBONE WIRING
POWER SUPPLIES WITH
BATTERY BACKUP
TYPICAL CLASS A SPEAKER
CIRCUIT.
TYPICAL CLASS A STROBE
CIRCUIT.
TYPICAL NOTIFICATION APPLIANCE CIRCUIT,
SEE A4/FA601 FOR QUANTITY OF CIRCUITS.
TYPICAL CLASS A SIGNALING LINE
CIRCUIT AND POWER CIRCUIT, SEE
A4/FA601 FOR QUANTITY OF
CIRCUITS.
CONTROL MODULE
FOR ACTIVATION
OF SPEAKERS
EF
RT
I
N N
N O
L.
T E
N A
040804 E N G
R
NI E E R
OL
V
SEAL
S
A
SFORP
E
H C
I A L
OI N
OR L
T
JE
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.:
SCALE:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y
F R
E N
C H
C R
E E
K A
M B
U
LA
T O
R Y
C A
R E
C
LI
N
IC
A D
D
IT
IO
N
A
LT
E
R A
T
V
IR
G
IN
IA
A V
E N
U E
JA
C
K S
O N
V
IL
LE
, N
C
N O
R F
O
LK
, V
IR
G
IN
IA
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
, A T
LA
N
T
IC
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
JE
U
N E
FP ENGINEER
CHIEF ENG/ARCH
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
1430035
DRAWFORM REVISION: 10 MARCH 2009
NOTE:
IF THIS DRAWING IS LESS THAN 34" X 22"
IT IS A REDUCED SIZE DRAWING
FOR OFFICIAL USE ONLY
4750 New Broad Street
Orlando, Florida 32814 www.rlfae.com
LICENSE #AA C000564 #EB 0000629
TBD
JGG / RSF
EJA
Approved by JOANNE KRAUSE, Director of Medical Facilities
Program Office, via Email
C :\U se rs
\m ec
\D oc um en ts \4
0-
B
LD
G -1
-E
_r
_m ec rlf ae .c om .rv t
/2
5/
:5 5:
P
M
NTS
F
IR
E A
LA
R
M A
N D
M A
S S
N O
T
IF
IC
A
T
IO
N S
Y S
T E
M R
IS
E
R D
IA
G
R A
M
FA601
NGZ SSS DRS
12760652
11/18/20
SCALE: NTS A4
FIRE ALARM & MASS NOTIFICATION SYSTEM RISER DIAGRAM
SCALE: NTS B3
TYPICAL FIRE ALARM DEVICE CONNECTION DIAGRAM
19 MASS NOTIFICATION SYSTEM ENCLOSURE. PROVIDE NON-METALLIC 18" H x 16"W x 10" DEEP NEMA 4X ENCLOSURE WITH RAISED COVER AND PAD
LOCKABLE LATCHES. MOUNT TO PLYWOOD BACKBOARD IN ELEC ROOM X069.
SEE FA101-2 FOR LOCATION.
20 EXTEND CONDUIT 4' BEYOND ROOF LINE AND PROVIDE UL LISTED WEATHER
HEAD. PROVIDE ROOFTOP OMNI DIRECTIONAL 2400MHz ANTENNA AND IN-LINE
LIGHTNING ARRESTOR. SEE LOCATION ON SHEET EQ103. COORDINATE WITH
RESIDENT OFFICER IN CHARGE OF CONSTRUCTION FOR FINAL LOCATION
PRIOR TO INSTALLATION OF CONDUIT AND ANTENNA.
21 3/4" CONDUIT WITH #18 AWG SHIELDED AUDIO CABLE.
22 1 1/2" RIGID GALVANIZED STEEL CONDUIT.
23 3/4" RIGID GALVANIZED STEEL CONDUIT WITH CIRCUIT CONDUCTORS FROM
CIRCUIT INDICATED. EXTEND CIRCUIT TO AN AC IN-LINE SURGE PROTECTION
DEVICE LOCATED IN THE LOWER RIGHT HAND CORNER OF THE MNS
ENCLOSURE. SURGE PROTECTIVE DEVICE SHALL BE WIRED IN SERIES WITH A
125V, 20A, DUPLEX RECEPTACLE MOUNTED INSIDE THE MNS ENCLOSURE
DIRECTLY ABOVE THE SURGE PROTECTIVE DEVICE.
24 24" x 24" x 1" PLYWOOD MOUNTING BOARD MARKED "FOR BASE-WIDE MNS
USE".
1 TYPICAL SIGNALING LINE CIRCUIT(S) AS REQUIRED. SEE C3/FA601 FOR
CONNECTION DIAGRAM.
2 TYPICAL NOTIFICATION APPLIANCE CIRCUIT(S) AS REQUIRED TO SERVE
SPEAKERS AND STROBES. SEE C3/FA601 FOR CONNECTION DIAGRAM.
3 SIGNALING LINE CIRCUIT (SLC) BACKBONE CABLING.
4 1" CONDUIT WITH TWO CAT 6 CABLES TO VOICE PATCH PANEL IN COMM
ROOM 1G10.
5 TYPICAL REMOTE FIRE ALARM CONTROL UNIT SERVING NOTIFICATION
DEVICES. SEE C3/FA601 FOR ADDITIONAL CONNECTIONS AND
REQUIREMENTS.
6 CONNECT TO ADDITIONAL DEVICES, SEE FIRE ALARM FLOOR PLANS FOR
QUANTITY.
7 CONTROL MODULE FOR AIR HANDLING UNIT SHUT-DOWN.
8 CONTROL MODULE SHALL PROVIDE NOTIFICATION TO THE HVAC DDC
SYSTEM FOR FIRE ALARM HVAC SHUTDOWN. SEE A3/EP502 FOR VFD
CONTROL WIRING DIAGRAM.
9 INITIATING LINE CIRCUIT CONNECTING MONITOR MODULE TO INITIATING
DEVICE.
10 LOCATE MONITOR MODULE WITHIN 36" OF FLOW OR TAMPER SWITCH WHICH
IT SERVES.
11 3/4" CONDUIT WITH WIRING AS REQUIRED.
12 CONTROL MODULE FOR MUTING OF PA SYSTEM SPEAKERS.
13 PA SYSTEM SPEAKER AMPLIFIER.
14 HVAC DIGITAL CONTROLLER.
15 3/4" RIGID GALVANIZED STEEL CONDUIT, MAXIMUM 15' LENGTH.
16 1 1/2" RIGID GALVANIZED STEEL CONDUIT TO ROOF ANTENNA. MAXIMUM
CONDUIT LENGTH FROM ANTENNA TO MNS CABINET SHALL NOT EXCEED 115'.
EXTEND CONDUIT TO A POINT 4'-0" ABOVE THE APEX OF THE ROOFLINE.
ROUTE CONDUIT IN THE MOST DIRECT VERTICAL ROUTE POSSIBLE. PROVIDE
ADDITIONAL PULL BOXES WHERE SHARP BENDS ARE NECESSARY. PROVIDE
UL LISTED WEATHERHEAD AT CONDUIT TERMINATION POINT. PROVIDE 50
OHM, LMR-400 RF CABLE FROM ANTENNA TO MNS ENCLOSURE WITH A 3'
SERVICE LOOP AT EACH END OF THE CABLE AT THE ROOF. LEAVE CABLE
UNTERMINATED AT THE MNS ENCLOSURE. LABEL CABLE "FOR MNS" AND
TEST FOR PROPER CONNECTIVITY.
17 EXTERNAL MNS AUDIO INPUT AND CONTACT CLOSURE.
18 8" x 8" x 8" DEEP PULL BOX.
SCALE: NTS C3
FIRE ALARM REMOTE POWER CONTROL UNIT (RFCU) CONNECTION DIAGRAM
NOTES:
KEY NOTES 00
DSN
mec
| FA001 - FIRE ALARM LEGEND AND SEQUENCE OF OPERATION MATRIX |
| FD101 - ELECTRICAL PLANS, DEMOLITION - FIRE ALARM |
| FA101-1 - FIRE ALARM, SECTOR 1 |
| FA101-2 - FIRE ALARM, SECTOR 2 |
| FA101-3 - FIRE ALARM, SECTOR 3 |
| FA101-4 - FIRE ALARM, SECTOR 4 |
| FA601 - FIRE ALARM AND MASS NOTIFICATION SYSTEM RISER DIAGRAM |
| 2019-12-26T10:54:25-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:02-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:02-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:03-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:04-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:05-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2019-12-26T10:55:06-0500 | |
| Jennifer L. Lovett | |
| I, Jennifer L. Lovett, am signing to approve this document. |
| 2021-01-16T19:02:02-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:43-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:44-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:44-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:45-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:53-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:02:54-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:25-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:38-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:38-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:39-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:39-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:40-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
| 2021-01-16T19:03:40-0500 | |
| James E. Donahue, R.A. | |
| I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed. |
File details come from the government source that posted it. Updated .