About this file

This solicitation is for a design-bid-build construction project at the P4040 French Creek Ambulatory Care Clinic located at Camp Lejeune, North Carolina. The solicitation seeks a general contractor to provide all labor, materials, equipment and supervision to complete renovations and alterations to the existing clinic building. Key requirements include expanding and renovating the existing clinic to meet current operational needs, with work comprised of interior demolition and construction. The period of performance is 730 calendar days from Notice to Proceed. The Navy intends to award a firm fixed-price contract. The anticipated award date is February 2022. Offerors must be licensed to perform construction in North Carolina and have experience with similar medical facility projects. The point of contact for any questions is listed.

View the file

Other files

File Type Posted
N4008521R2524P00006.pdf PDF
AMEND 06 ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
AMD 5 ATTACH 2 Site Visit 6.17.21.pdf PDF
AMD 5 ATTACH 1 P4040 PPIs VER2.xlsx XLSX spreadsheet
N4008521R2524P0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0003 Attachment (1) NC20210038 WGDET.pdf PDF
Amendment 0003 Attachment (2) PPIs.xlsx XLSX spreadsheet
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
MP501.pdf PDF
Interim MCMH French Creek_Drawing Set_Compiled.pdf PDF
Amendment 0001 Continuation Sheet.pdf PDF
N4008521R2524P00001.pdf PDF
Attachment B - Construction Experience Project Data Sheet.docx DOCX document
1430035dwg10of20_Architectural.pdf PDF
1430035dwg06of20_Civil.pdf PDF
1430035dwg20of20_Comm.pdf PDF
1430035dwg19of20_Electrical.pdf PDF
ATTACHMENT E PRICE PROPOSAL FORM.docx DOCX document
ATTACHMENT D SMALL BUSINESS SUBCONTRACTING PLAN.docx DOCX document
1430035spc01of03.pdf PDF
1430035dwg02of20_LifeSafety.pdf PDF
RFP N4008521R2524.pdf PDF
1430035dwg16of20_FireAlarm.pdf PDF
1430035dwg07of20_Landscape.pdf PDF
1430035dwg09of20_Architectural.pdf PDF
1430035dwg12of20_Architectural.pdf PDF
1430035dwg04of20_Hazmat.pdf PDF
Attachment A - PPI Inquiry Log.xls XLS spreadsheet
1430035dwg14of20_Equipment.pdf PDF
1430035spc02of03.pdf PDF
1430035dwg13of20_Interiors.pdf PDF
ATTACHMENT C Past Performance Questionnaire.pdf PDF
1430035dwg11of20_Architectural.pdf PDF
1430035dwg05of20_Borings.pdf PDF
1430035dwg03of20_Phasing.pdf PDF
1430035spc03of03.pdf PDF
1430035dwg08of20_Structural.pdf PDF
1430035dwg17of20_Plumbing.pdf PDF
1430035dwg01of20_General.pdf PDF
1430035dwg18of20_Mechanical.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F

F

GENERAL NOTES:

PIPING AND VALVES

FIRE PROTECTION SYMBOLS ABBREVIATIONS

PIPE FITTINGS

D

FZ

EZ

FDC FIRE DEPARTMENT CONNECTION

DESCRIPTION

AUTOMATIC

CAPACITY

CAST IRON

CONNECTION

ABOVE FINISHED FLOOR

AUTOMATIC SPRINKLER SYSTEM

BACKFLOW PREVENTER

ABB

A/S

AFF

AUTO

BFP

CAP

CI

CONN

DRAWING

EACH

CONTINUATION

ELEVATION

FIRE HOSE CABINET

ELECTRIC

FINISHED FLOOR ELEVATION

FLOOR

GALLON

HORSEPOWER

MAXIMUM

MINIMUM

IRON PIPE SIZE

HEATING/VENTILATING/AIR CONDITIONING

FIRE HOSE VALVE

NUMBER

NORMALLY CLOSED

NORMALLY OPEN

PRESSURE

REFERENCE

POST INDICATOR VALVE

NATIONAL PIPE THREAD

POUNDS PER SQUARE INCH

REQUIRED

REGULATING

STANDPIPE

SQUARE

TYPICAL

TEMPERATURE

REVOLUTIONS PER MINUTE

DWG

CONT

EA

ELEV

FHC

FFE

ELEC

FLR

HP

GAL

IPS

MAX

MIN

HVAC

FHV

PUMPED FIRE MAIN PIPING

SPRINKLER DRAIN PIPING

CHECK VALVE

RELIEF VALVE

GATE VALVE WITH TAMPER SWITCH

NO.

NPT

(N.C.)

(N.O.)

PIV

PSI

REF

PRESS

REG

REQD

RPM

SP

SQ

TEMP

TYP

FLANGED

FLOW SWITCH

PRESSURE GAGE

TEE

ELBOW (TURNED DOWN)

TEE (TURNED UP)

ELBOW (TURNED UP)

ELBOW (90°)

ELBOW (45°)

UNION

REDUCER - CONCENTRIC

CAPPED LINE

TEE (TURNED DOWN)

BLIND FLANGED CAP

REDUCER - ECCENTRIC, STRAIGHT CROWN

REDUCER - ECCENTRIC, STRAIGHT INVERT

WITHW/

FIRE DEPARTMENT CONNECTIONFDC

DIRECTION OF DOWNWARD SLOPE OF PIPING

(TYPICALLY DRAIN PIPING) BACKFLOW PREVENTER TEST CONNECTIONBFT

TYPICAL FIRE SPRINKLER ZONE PIPING

PIPING DEDICATED TO HORIZONTAL EXIT

UNDERGROUND NEW PUMPED FIRE MAIN PIPING

VARIABLE FREQUENCY DRIVEVFD

AUTOMATIC TRANSFER SWITCHATS

ABOVE CEILINGA/C

OVERHEAD AT STRUCTUREO/H

BELOW FLOORB/F

DRAIND

FIRE MAINF

PRE-ACTION SYSTEMPAS

FIRE PROTECTION DESIGN INFORMATION:

COMMUNICATIONCOMM

SQUARE FEETSF

REF.: NFPA 13, 24, AND 72

PROJECT AREA: CLINIC

UNLESS NOTED OTHERWISE, THE PRIMARY HAZARD CLASSIFICATION FOR THE CLINIC IS

LIGHT HAZARD (LH).

THE FOLLOWING SPACES SHALL BE DESIGNED FOR THE HAZARD CLASSIFICATION INDICATED:

ORDINARY HAZARD (OH): MECHANICAL ROOMS, BOILER ROOMS, ELECTRICAL ROOMS,

COMMUNICATION ROOMS, STORAGE ROOMS, LOADING DOCK.

EXTRA HAZARD (EH): BOTTLED OXIDIZER GAS ROOMS

WET PIPE SPRINKLER SYSTEM DESIGN CRITERIA

HAZARD: LH HAZARD: OH

MINIMUM DESIGN DENSITY: 0.10 GPM/SQ. FT. MINIMUM DESIGN DENSITY: 0.20 GPM/SQ. FT.

OUTSIDE HOSE STREAM: 250 GPM OUTSIDE HOSE STREAM: 250 GPM

*MINIMUM DESIGN AREA: 1,500 SQ. FT. *MINIMUM DESIGN AREA: 2,500 SQ. FT.

MINIMUM SPRINKLER K-FACTOR: 5.6 MINIMUM SPRINKLER K-FACTOR: 8.0

MINIMUM DURATION: 60 MINUTES MINIMUM DURATION: 60 MINUTES

HAZARD: EH

MINIMUM DESIGN DENSITY: 0.30 GPM/SQ. FT.

OUTSIDE HOSE STREAM: 500 GPM

*MINIMUM DESIGN AREA: 2,500 SQ. FT.

MINIMUM SPRINKLER K-FACTOR: 11.2

MINIMUM DURATION: 90 MINUTES

*DESIGN AREAS SHALL BE INCREASED BY 30 PERCENT FOR SLOPED CEILINGS THAT EXCEED

A PITCH OF TEN PERCENT. REDUCTIONS IN DESIGN DENSITY SHALL NOT BE PERMITTED.

THE SPRINKLER SYSTEM SHALL BE DESIGNED USING THE AREA/DENSITY METHOD OF NFPA

13, EXCEPT THE DESIGN DENSITY, DESIGN AREA, HOSE STREAM ALLOWANCE AND DURATION

OF SUPPLY REQUIREMENTS FOR NON-STORAGE OCCUPANCIES SHALL BE AS INDICATED. THE

DESIGN AREA REDUCTIONS IN NFPA 13 FOR QUICK-RESPONSE SPRINKLERS ARE NOT

PERMITTED.

MINIMUM SPRINKLER WATER SUPPLY REQUIREMENTS FOR LH:

1500 SQ. FT. x 0.10 GPM/SQ. FT. = 150 GPM

HOSE STREAM ALLOWANCE = 250 GPM

TOTAL WATER DEMAND = 400 GPM

MINIMUM SPRINKLER WATER SUPPLY REQUIREMENTS FOR OH:

2500 SQ. FT. x 0.20 GPM/SQ. FT. = 500 GPM

HOSE STREAM ALLOWANCE = 250 GPM

TOTAL WATER DEMAND = 750 GPM

FLOW TEST DATA:

DATE OF TEST: 12 JULY 2016

TIME OF TEST: 4:30 PM

STATIC PRESSURE: 67 PSIG

RESIDUAL PRESSURE: 64 PSIG

FLOW RATE: 1186 GPM

1. PROVIDE ELECTRONIC TAMPER SWITCH FOR ALL CONTROL

VALVES.

2. PIPE SIZES INDICATED ARE MINIMUMS AND SHALL NOT BE

REDUCED.

3. SHOP DRAWINGS OF SPRINKLER PIPING SYSTEM REQUIRED.

REFER TO SPECIFICATIONS. DO NOT PROCEED UNTIL SHOP

DRAWINGS APPROVED BY THE CONTRACTING OFFICER ARE

AVAILABLE AT THE SITE.

4. CENTER SPRINKLER HEADS IN CEILING TILES.

5. CONTRACTOR SHALL PERFORM A FLOW TEST, IN

ACCORDANCE WITH NFPA 291, PRIOR TO PERFORMING

HYDRAULIC CALCULATIONS.

6. COORDINATE THE PLACEMENT OF ADDITIONAL SPRINKLERS

BELOW DUCTWORK WITH THE FINAL HVAC LAYOUT IN

ACCORDANCE WITH NFPA 13.

7. SPRINKLER PIPING SHALL NOT PASS THROUGH ELECTRIC

ROOMS, COMMUNICATION ROOMS, SERVER ROOMS, OR

ELEVATOR EQUIPMENT ROOMS. PIPING SHALL ENTER

AFOREMENTIONED ROOMS OVER THE RESPECTIVE ROOM

DOOR AND SHALL ONLY SERVE SPRINKLERS IN THE ROOM.

8. DO NOT ROUTE PIPING OVER ELECTRICAL PANELS,

SWITCHBOARDS, SWITCHGEAR, TRANSFORMERS, OR

SIMILAR ELECTRICAL EQUIPMENT.

9. DO NOT LOCATE SPRINKLERS DIRECTLY ABOVE COMMUNICATIONS

RACKS. COMPLY WITH TIA-569-D STANDARD.

10. PROVIDE GUARDS ON ALL SPRINKLERS IN MECHANICAL,

ELECTRIC, AND COMMUNICATION ROOMS REGARDLESS

OF ELEVATION.

11. INSTALL ALL PIPING IN SUCH A MANNER THAT ALL VALVES

AND OTHER FIRE SUPPRESSION DEVICES ARE ACCESSIBLE.

12. SPRINKLER SYSTEM DESIGN VELOCITIES SHALL NOT EXCEED

20 FEET PER SECOND.

13. EXTENDED COVERAGE SPRINKLERS ARE NOT PERMITTED.

14. FLEXIBLE SPRINKLER HOSE WITH FITTINGS INTENDED FOR

DIRECT CONNECTION TO SPRINKLERS ARE NOT PERMITTED.

15. COORDINATE PROPOSED SHUTDOWN TIMES OF EXISTING

SYSTEMS WITH THE CONTRACTING OFFICER AND FIRE

DEPARTMENT. SHUTDOWN REQUESTS SHALL BE PROVIDED

IN WRITING A MINIMUM OF 21 DAYS PRIOR TO PROPOSED

SHUTDOWN OF EXISTING SYSTEMS.

16. PERFORM WORK WHICH MAY INTERRUPT ANY SERVICE TO

ADJACENT AREAS AT TIMES WHICH WILL CAUSE MINIMAL

DISRUPTION TO THE OPERATION OF THE FACILITY.

17. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS

PRIOR TO PROCEEDING WITH DEMOLITION WORK. NOTIFY THE

CONTRACTING OFFICER OF VARIATIONS IN EXISTING CONDITIONS

THAT MAY AFFECT NEW WORK. RECORD DISCREPANCIES ON

AS-BUILT DRAWINGS.

18. CONTRACTOR SHALL PROVIDE A FIREWATCH WHEN FIRE

SPRINKLER SYSTEM IS OUT OF SERVICE. COMPLY WITH NFPA,

FIRE DEPARTMENT AND CONTRACTING OFFICER REQUIREMENTS.

NOTE:

REFER TO FLOOR PLANS AND DETAILS FOR EXTENT OF SYMBOLS AND

ABBREVIATIONS USED. NOT ALL SYMBOLS SHOWN HEREIN MAY BE

FOUND WITHIN THE DRAWINGS.

GENERAL IDENTIFICATION

FP

(E) EXISTING EQUIPMENT/PIPING DESIGNATION

POINT OF CONNECTION BETWEEN

NEW AND EXISTING CONSTRUCTION

POINT OF REMOVAL - DEMOLITION

EQUIPMENT MARK

SCHEDULE REFERENCE

EQUIPMENT TYPE

HYDRAULIC CALCULATION NODE

NODE NUMBER/LETTER

OH HAZARD IDENTIFICATION MARK

SPRINKLER TYPES

PROVIDE CONCEALED PENDANT SPRINKLERS IN ALL LOBBY AREAS,

RADIOLOGY SPACES, LAB SPACES, PHARMACY, AND CORRIDORS.

CONCEALED SPRINKLER COVER PLATE COLOR SHALL MATCH CEILING

COLOR. CUSTOM COLORS SHALL BE FACTORY PAINTED, FIELD

PAINTING OF COVER PLATES IS PROHIBITED.

SPACES WITHOUT CEILINGS SHALL BE PROTECTED WITH UPRIGHT

SPRINKLERS WITH A BRASS FINISH.

PROVIDE RECESSED PENDANT SPRINKLERS IN ALL SPACES NOT

DESCRIBED ABOVE. WHERE CEILINGS ARE WHITE, THE SPRINKLER

FINISH SHALL BE WHITE. WHERE CEILINGS ARE NOT WHITE, THE

SPRINKLER FINISH SHALL BE CHROME.

EF

RT

I

N N

N O

L.

T E

N A

040804

E N G

R

NI E E R

OL

V

SEAL

S

A

SFO

R P

E

H C

I A

L

OI N

OR

L

T

J E

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

IO

N

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

D

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m jt\

D oc um en ts \4

0-

B

LD

G -1

-F

_r

_m jt@ rlf ae

.c om

.rv t

/3

0/

:1 2:

A

M

NTS

F

IR

E S

U P

P R

E S

S

IO

N S

Y M

B O

LS

A

N D

A B

B R

E V

IA

T

IO

N

S

FX001

MJT JAK BEF

12760642

11/18/20

BACKFLOW PREVENTER SCHEDULE

MARK SYSTEM LOCATION SIZE

FLOW

(GPM)

MAXIMUM PRESSURE

LOSS (PSIG) REMARKS

BFP/FP1 FIRE SUPPRESSION 070 MECHANICAL 4" 300 12 -

DSN

mec Text Box

DSN

B2

FX501

XPXP

XNXN

XMXM

XL.6XL.6

XLXL

XK.4XK.4

XJXJ

XFXF

XH.5XH.5

XGXG

XEXE

XC.3XC.3

XRXR

X1X1 X2X2

X3X3 X4X4 X5X5 X6X6 X7X7

X8X8 X9X9 X10X10 X11X11 X12X12

X4.5X4.5 X6.6X6.6 X7.2X7.2

X9.5X9.5 X9.8X9.8

X2.4X2.4 X3.2X3.2 X3.4X3.4 X3.5X3.5 X3.8X3.8 X4.3X4.3 X4.8X4.8 X6.2X6.2 X6.3X6.3 X6.5X6.5 X6.9X6.9 X7.3X7.3

X7.6X7.6 X7.7X7.7 X8.3X8.3 X8.4X8.4 X8.6X8.6 X8.8X8.8 X9.2X9.2 X9.4X9.4 X9.6X9.6

XC.6XC.6

XB.4XB.4

XBXB

XAXA

XCXC

XC.1XC.1

XDXD

XF.9XF.9

XKXK

XM.05XM.05

XM.1XM.1

XHXH

x001

LOUNGE

x003

OFFICE

x004

TREATMENT

x005

PHYSICIAN POD

x006

SCREENING

x007

SCREENING

x009

MALE LOCKER

x011

FEMALE LOCKER

x008

MALE TLT

x068

LOUNGE

x065

CORR

x012

CORR

x067

AUDIO

x028

COPY / STOR

x013

OFFICE

x014

TLT

x015

TLT

x016

OFFICE

x017

PROCESS

x018

SUPPORT

x020

CONTROL

x019

GENERATOR

x022

XRAY

x027

CORR

x023

DRESS

x024

DRESS

x021

ELEC

x032

OFFICE

x031

JAN

x029

TLT

x030

TLT

x025

PHA

x026

CONTROL

x034

OFFICE

x033

OFFICE

x041

EXAM

x040

EXAM

x039

PROV / EXAM

x038

PROV / EXAM

x037

PROV / EXAM

x036

PROV / EXAM

x043

EXAM

x044

EXAM

x045

EXAM

x046

SCREENING

x047

SCREENING

x048

SICK CALL / CONTROL

x055

ADMIN

x053

LPO

x049

LAB

x052

CONTROL

x051

SPECIMEN

x054

RECORDS

x056

FEMALE TLT

x057

MALE TLT

x042

CORR

x058

WAITING

x147

LOBBY

x062

PHARMACY

x061

CORR

x066

CSR CLEAN

x089

CSR SOIL

x090

SURGERY SUPPORT

x091

SCRUB

x092

ORAL SURGERY

x072

CONFERENCE

x073

SUPPLY ADMIN

x074

STOR

x075

BRANCH DIR

x069

ELEC

x070

MECHANICAL

x002

SECURE STOR

x010

FEMALE TLT

x059

VEST

x134

TEAM DTR

x140

CORR

x133 GEN DTR x132

CONSULT

x141

SUB-WAIT

x139 GEN DTRx138

GEN DTR

x137

CONSULT

x136

TEAM DTR

x135

GEN DTR

x109

CORR

x094

MALE TLT

x102

FEMALE TLT

x108

OFFICE

x101

PERIO

x093

PERIO SUPV

x100

PERIO

x099

F LCKR

x098

TLT

x104

X-RAY ADMIN

x103

ENDO SUPV

x096

F LCKR

x097

SURGERY SUPV

x105

XRAY

x095

CORR

x077

LCPO

x078

LPO

x080 MALE STAFFx076

ADMIN x084

SUPPLY

x085

CERAMICS

x086

CASTING

x087

PROS LAB

x124

VEST

x107

ORAL DIAG

x106

ORAL DIAG

x110

CORR

x113

ORAL HYGIENE

x112

ENDO

x118

HOUSEKEEPING

x119

ORAL DIAG

x120

ORAL DIAG

x121

SICK CALL

x122

GEN DTR

x117

CONTROL / RECORDS

x115

ORAL DIAG SUPV

x114

ORAL HYGIENE

x111

ENDO

x125

CORR

x126

FEMALE STAFF

x128

COMM

x129

PROS SUPV

x150

COURTYARD

x088

CORR

x130

GEN DTR

x131

GEN DTR

x142

CORR

x146

PROS

x145

PROS

x144

GEN DTR

x143

GEN DTR

x123

SUB-WAIT

x035

IMMUNIZATION

x050

VENIPUNCTURE

x148

OFFICE

x149

PSYCH TEST

x081

JAN

EF

RT

I

N N

N O

L.

T E

N A

040804

E N G

R

NI E E R

OL

V

SEAL

S

A

SFO

R P

E

H C

I A

L

OI N

OR

L

T

J E

KEY NOTES 00

SHEET NOTES:

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

NPROJECT

NORTH

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m jt\

D oc um en ts \4

0-

B

LD

G -1

-F

_r

_m jt@ rlf ae

.c om

.rv t

/3

0/

:1 1:

A

M

1/16" = 1'-0"

F

IR

E S

U P

P R

E S

S

IO

N D

E M

O

LI

T

IO

N P

LA

N

FD110

MJT JAK BEF

12760643

11/18/20

SCALE: 1/16" = 1'-0" A3

FIRE SUPPRESSION DEMOLITION PLAN

1 EXISTING BUILDING IS FULLY SPRINKLERED.

1 REMOVE SPRINKLERS AND SPRINKLER PIPING

IN THIS AREA. PROVIDE TEMPORARY CAPS AS

REQUIRED. EXISTING PIPING ROUTED THROUGH

RENOVATION AREAS SERVING AREAS OF THE

FACILITY NOT BEING RENOVATED SHALL REMAIN

IN SERVICE.

2 EXISTING COMBINATION FIRE SUPPRESSION AND

DOMESTIC WATER RISER TO REMAIN. REMOVE

SECTION OF RISER BETWEEN SPRINKLER SHUT-OFF

VALVE AND ELBOW ON RISER (INCLUDING FDC, MAIN

DRAIN, ETC.) TO FACILITATE BACKFLOW PREVENTER

INSTALLATION. PATCH WALL PENETRATIONS TO

MATCH INTERIOR AND EXTERIOR FINISHES.

3 REMOVE SPRINKLERS AND PROVIDE CAPS AS

NECESSARY TO MAINTAIN EXISTING SPRINKLER

SYSTEM IN NON-RENOVATED AREAS OPERATIONAL

AT ALL TIMES (TYPICAL).

4 REMOVE SPRINKLERS AND SPRINKLER PIPING.

PROVIDE TEMPORARY CAPS AS REQUIRED.

EXISTING PIPING ROUTED THROUGH RENOVATION

AREAS SERVING AREAS OF THE FACILITY NOT BEING

RENOVATED SHALL REMAIN IN SERVICE.

5 EXISTING SPRINKLER SYSTEM TO REMAIN.

MAINTAIN SPRINKLER PROTECTION DURING

PROJECT DURATION.

6 EXISTING SPRINKLER SYSTEM TO REMAIN. MAINTAIN

SPRINKLER PROTECTION IN LOBBY X147 DURING

PROJECT DURATION.

7 EXISTING SPRINKLER SYSTEM TO REMAIN.

8 SPRINKLER SUPPLY SERVING LOBBY X147. MAINTAIN

SERVICE DURING PROJECT DURATION.

9 EXISTING OPEN AIR COURTYARD - NO SPRINKLERS.

KEYPLAN

DSN

mec

T

T T

T

4321 5 6

C

B

A

D

E

F

1H02

GAS STOR

x066

CSR CLEAN

1A04

CLASS

1AC2

CORR

1GC1

CORR

1C02

DRAWING

1C04

SPECIMEN TLT

1C06

LAB

1C10

PROV (BH)

1C12

RN (BH)

1G12C

SHWR

1G12B

SHWR

1G12

M LOCKERS

1G12A

TLT

1G14A

TLT

1G14

F LOCKERS

1G14B

SHWR

1G14C

SHWR

1G18

CONF

1G20

JAN

1G22

LOUNGE

1GC2

CORR

1CC1

CORR

1C03

RAD

1C01

RECEPTION

1C05

DRESS

1C08

JAN

1D25

EXAM

1C07

PHARMACY

1A03

WAIT

1A01

VEST

1B01

MEDICAL RECORDS

1A05

WAIT

1A08

TLT MALE

1D08

TEAM COLLABORATION

1D05

IMMUNI

1D13

EXAM

1D17

TLT

1G09

EQUIPMENT

1E29

CLEAN

1E27

TREAT

1E41

EXAM

1E35

EXAM

1E37

EXAM

1E39

EXAM

1D02

WAIT / OBS

1E26

TREAT

1E28

SOILED

1E24

OBS / HYD

1E12

EXAM

1E44

EXAM1E03

EXAM / CONSULT

1E05

EXAM / CONSULT

1E07

EXAM / CONSULT

1E09

EXAM

1E11

EXAM

1E13

VISION SCREEN1E17

EKG

1E19

LCPO / LPO

1EC5

CORR

1EC4

CORR

1E14

TLT

1E21

RN MNGR

1E23

CHIEF (SMO)

1G15

COMM

x094

MALE TLT

x093

PERIO SUPV

x092

ORAL SURG

x091

SCRUB

x090

SURG SPRT

x089

CSR SOIL

x072

CONFERENCE

x088

CORR

x073

SUPPLY ADMIN

x074

STOR

x075

BRANCH DIR

x088

CORR

x088

CORR

x087

PROS LAB

x085

CERAMICS

x086

CASTING

x084

SUPPLY

x076

ADMIN

x095

CORR

x095

CORR

x102

FEMALE TLT

1A02

LOBBY

x109

CORR

x109

CORR

x110

CORR

x108

OFFICE

x110

CORR

x107

ORAL DIAG

x101

PERIO

x100

PERIO

x106

ORAL DIAG

x105

XRAY

x099

FEMALE LCKR

x098

TLT

x097

SURGERY SUPV

x096

FEMALE LCKR

x103

ENDO SUPV

x104

X-RAY ADMIN

x111

ENDO

x112

ENDO

x113

ORAL HYGIENE

x118

HOUSEKEEPING

x119

ORAL DIAG

x120

ORAL DIAG

x126

FEMALE STAFF

x124

VEST

x146

PROS

x128

COMM

x129

PROS SUPV

x145

PROS

x144

GEN DTR

x142

CORR

x142

CORR

x141

SUB-WAIT

x139

GEN DTR

x138

GEN DTR

x137

CONSULT

x136

TEAM DTR

x135

GEN DTR

x134

TEAM DTR

x133

GEN DTR

x132

CONSULT

x131

GEN DTR

x130

GEN DTR

x150

COURTYARD

x125

CORR

x125

CORR

x122

GEN DTR

x121

SICK CALL

x114

ORAL HYGIENE

x115

ORAL DIAG SUPV

x117

CONTROL / RECORDS

x080

MALE STAFF

x078

LPO

x077

LCPO

1A06

TLT FEMALE

1D03

EXAM / CONSULT

1D01

RECEPTION

1G17

TLT

1E18

MCMH TEAM LEAD

1E16

EXAM

1E32

LACTATION

1E06

TEAM COLLABORATION

1F04

EQUIPMENT

1F02

REHAB

1F01

PHYSICAL THERAPY

1E01

RECEPTION

1EC3

CORR

1EC2

CORR 1E43

TLT

1EC1

CORR

1D21

AUDIOBOOTH

1D18

MCMH TEAM LEAD

1D21

AUDIOBOOTH

1D19

EXAM

1D15

TLT

1D23

EXAM

1G07

TRASH / RECYC

1G03

DENTAL LOUNGE

1G01

ELEC

1G02

JAN

1G04

RMW

1D24

EXAM

1D12

EXAM

1DC5

CORR

1D27A

TLT, ISO

1D27

EXAM, ISO

1DC1

CORR

1D29

TLT

1G08

LOGISTICS

1GC3

CORR

1D07

EXAM

1D09

EXAM

1D11

EXAM

1DC2A

MEASURES

1DC3

CORR

1CC6

CORR

1AC4

CORR

1AC3

CORR

B5

FX501

1DC2

CORR

1G10

MAIN COMM

1G19

ELEC

1E33

DERM STORAGE

XPXP

XNXN

XMXM

XL.6XL.6

XLXL

XK.4XK.4

XJXJ

XFXF

XH.5XH.5

XGXG

XEXE

XC.3XC.3

XRXR

X1X1

X2X2 X3X3 X4X4 X5X5 X6X6 X7X7 X8X8 X9X9 X10X10 X11X11

X12X12

X4.5X4.5 X6.6X6.6 X7.2X7.2 X9.5X9.5 X9.8X9.8

X2.4X2.4 X3.2X3.2 X3.4X3.4 X3.5X3.5 X3.8X3.8 X4.3X4.3 X4.8X4.8 X6.2X6.2 X6.3X6.3 X6.5X6.5 X6.9X6.9 X7.3X7.3

X7.6X7.6 X7.7X7.7 X8.3X8.3 X8.4X8.4 X8.6X8.6 X8.8X8.8 X9.2X9.2 X9.4X9.4 X9.6X9.6

XC.6XC.6

XB.4XB.4

XBXB

XAXA

F

F

F

EH

OH OH

1H01

MAIN ELEC

OH

OH

OH

OH

OH

6BFP

FP1

1G06

MECH

x070

MECHANICAL

OH

OH

OHOH

OH

OH

OH

OH

F

OH

EF

RT

I

N N

N O

L.

T E

N A

040804

E N G

R

NI E E R

OL

V

SEAL

S

A

SFO

R P

E

H C

I A

L

OI N

OR

L

T

J E

KEY NOTES 00

NOTES:

0 10'

1/16" = 1'-0" GRAPHIC SCALE

20' 40' 60'

NPROJECT

NORTH

KEYPLAN

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m jt\

D oc um en ts \4

0-

B

LD

G -1

-F

_r

_m jt@ rlf ae

.c om

.rv t

/3

0/

:1 2:

A

M

1/16" = 1'-0"

F

IR

E S

U P

P R

E S

S

IO

N R

E N

O V

A T

IO

N

P

LA

N

FX110

MJT JAK BEF

12760644

11/18/20

SCALE: 1/16" = 1'-0" A3

FIRE SUPPRESSION RENOVATION PLAN

1 PROVIDE SPRINKLER PROTECTION THIS AREA.

2 HYDRAULICALLY MOST REMOTE AREA.

3 THIS AREA FULLY SPRINKLERED - NO WORK REQUIRED.

4 EXISTING FIRE SUPPRESSION TO REMAIN. PROTECT

SPRINKLERS DURING CONSTRUCTION.

5 BACKFLOW PREVENTER TEST HEADER. MOUNT TEST

HEADER AT 36" ABOVE FINISHED GRADE. COORDINATE

MOUNTING HEIGHT WITH FDC MOUNTING HEIGHT. ADJUST

MOUNTING HEIGHT AS REQUIRED TO BE LINEAR WITH FDC.

6 WALL MOUNTED FDC - 5"STORZ TYPE CONNECTION. MOUNT

FDC AT 36" ABOVE FINISHED GRADE. COORDINATE MOUNTING

HEIGHT WITH BACKFLOW PREVENTER TEST HEADER

MOUNTING HEIGHT. ADJUST MOUNTING HEIGHT AS REQUIRED

TO BE LINEAR WITH BACKFLOW PREVENTER TEST HEADER.

7 EXTEND SPRINKLER SYSTEM TO EXISTING PIPING.

8 PROVIDE SPRINKLERS THIS AREA WITH SAME FINISH AS

EXISTING SPRINKLERS.

9 PROVIDE AUDIOMETRIC BOOTH WITH SPRINKLER PROTECTION.

COORDINATE SPRINKLER LOCATION(S) WITH AUDIOMETRIC

BOOTH MANUFACTURER. AUDIOMETRIC BOOTH MANUFACTURER

SHALL PROVIDE SPRINKLER PENETRATIONS. CONTRACTOR

INSTALLED SPRINKLER PENETRATIONS ARE NOT ACCEPTABLE.

REFER TO DETAIL A3/FX501.

DSN

mec

REMOVE EXISTING 4" FIRE

MAIN CONNECTION TO POINT

INDICATED

CHECK VALVE

PRESSURE GAUGE

2" MAIN DRAIN WITH

SHUTOFF VALVE.

EXISTING SHUTOFF

VALVE WITH TAMPER

SWITCH

TO EXISTING FDC

(REMOVE EXISTING

FDC)

EXISTING 3" DOMESTIC

WATER SUPPLY

EXISTING 6" COMBINATION

DOMESTIC WATER AND FIRE

WATER SERVICE

REMOVE EXISTING 4" FIRE

MAIN CONNECTION TO POINT

INDICATED

FLOOR

EXISTING 3" DOMESTIC

WATER SUPPLY

CONNECT 4" FIRE MAIN TO

EXISTING 4" FIRE MAIN

EXISTING SHUTOFF

VALVE WITH TAMPER

SWITCH

CONNECT 4" FIRE MAIN TO

EXISTING 4" FIRE MAIN

FLOOR

FLOOR MOUNTED ANGLE

SUPPORT BRACKETS

PIPE BACKFLOW PREVENTER

DRAIN TO BUILDING EXTERIOR

PIPE STAND (TYPICAL)

AIR GAP FITTING

4" TO FDC. PROVIDE 5"

STORZ CONNECTION.

4" FIRE MAIN

BUTTERFLY VALVE

WITH TAMPER SWITCH

2" MAIN DRAIN WITH

SHUTOFF VALVE. PIPE

MAIN DRAIN TO BUILDING

EXTERIOR. PROVIDE

SPLASHBLOCK AT

DISCHARGE POINT.

WATERFLOW SWITCH

TO BFP TEST HEADER

SHUTOFF VALVE WITH

TAMPER SWITCH

CHECK VALVE WITH

AUTOMATIC BALL DRIP

EXISTING 6" COMBINATION

DOMESTIC WATER AND FIRE

WATER SERVICE

AUDIOMETRIC

BOOTH ROOF

PANEL

1 3/8" HOLE (BY AUDIOMETRIC

BOOTH MANUFACTURER)

NON-CONDUCTIVE

DIELECTRIC

ISOLATOR

RF GASKET

HEX NUT

TO SPRINKLER

BRANCH/MAIN

AUDIOMETRIC BOOTH EXTERIOR

NOTES:

1. A NON-CONDUCTIVE DIELECTRIC ISOLATOR MUST BE INSTALLED IMMEDIATELY ON THE EXTERIOR OF

THE AUDIOMETRIC BOOTH.

2. FIELD INSTALLATION OF SPRINKLER PENETRATIONS BY THE CONTRACTOR ARE NOT PERMITTED. ALL

SPRINKLER PENETRATIONS TO BE MADE BY THE AUDIOMETRIC BOOTH MANUFACTURER.

5" HOLE (BY AUDIOMETRIC

BOOTH MANUFACTURER)

ESCUTCHEON (FIELD INSTALLED BY

AUDIOMETRIC BOOTH MANUFACTURER)

CONCEALED SPRINKLER

AUDIOMETRIC BOOTH INTERIOR

1" X 6" LONG FULLY

THREADED BRASS PIPE

ESCUTCHEON (FIELD INSTALLED BY

AUDIOMETRIC BOOTH MANUFACTURER)

POP RIVET

CONCEALED

SPRINKLER

COVER PLATE

8" DIA.

CONCEALED SPRINKLER

COVER PLATE

EF

RT

I

N N

N O

L.

T E

N A

040804

E N G

R

NI E E R

OL

V

SEAL

S

A

SFO

R P

E

H C

I A

L

OI N

OR

L

T

J E

1 2 3 4 5

1 2 3 4 5

D

C

B

A

D

C

B

A

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.:

SCALE:

D E

P A

R T

M E

N T

O F

T H

E N

A V

Y

F R

E N

C H

C R

E E

K A

M B

U

LA

T O

R Y

C A

R E

C

LI

N

IC

A D

D

IT

IO

N

A

LT

E

R A

T

V

IR

G

IN

IA

A V

E N

U E

JA

C

K S

O N

V

IL

LE

, N

C

N O

R F

O

LK

, V

IR

G

IN

IA

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

N D

, A T

LA

N

T

IC

N A

V A

L F

A C

IL

IT

IE

S

E N

G

IN

E E

R

IN

G C

O M

M A

R

IN

E C

O R

P S

B A

S E

C A

M P

L E

JE

U

N E

FP ENGINEER

CHIEF ENG/ARCH

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

S Y

M D

E S

C R

IP

T

IO

N

D A

T E

A P

P R

1430035

DRAWFORM REVISION: 10 MARCH 2009

NOTE:

IF THIS DRAWING IS LESS THAN 34" X 22"

IT IS A REDUCED SIZE DRAWING

FOR OFFICIAL USE ONLY

4750 New Broad Street

Orlando, Florida 32814 www.rlfae.com

LICENSE #AA C000564 #EB 0000629

TBD

JGG / RSF

EJA

Approved by JOANNE KRAUSE, Director of Medical Facilities

Program Office, via Email

C :\U se rs

\m jt\

D oc um en ts \4

0-

B

LD

G -1

-F

_r

_m jt@ rlf ae

.c om

.rv t

/3

0/

:1 2:

A

M

12" = 1'-0"

F

IR

E S

U P

P R

E S

S

IO

N D

E T

A

IL

S

FX501

MJT JAK BEF

12760645

11/18/20

SCALE: NOT TO SCALE B2

FIRE PROTECTION RISER DEMOLITION DETAIL

SCALE: NOT TO SCALE B5

FIRE PROTECTION BACKFLOW PREVENTER RENOVATION DETAIL

SCALE: NOT TO SCALE A3

AUDIOMETRIC BOOTH CONCEALED SPRINKLER DETAIL

DSN

mec

FX001 - FIRE SUPPRESSION SYMBOLS AND ABBREVIATIONS
FD110 - FIRE SUPPRESSION DEMOLITION PLAN
FX110 - FIRE SUPPRESSION RENOVATION PLAN
FX501 - FIRE SUPPRESSION DETAILS
2019-12-26T10:49:20-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2019-12-26T10:50:12-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2019-12-26T10:50:13-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2019-12-26T10:50:14-0500
Jennifer L. Lovett
I, Jennifer L. Lovett, am signing to approve this document.
2021-01-16T18:57:45-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:58:24-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:58:29-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:58:30-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:58:45-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:59:07-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:59:08-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.
2021-01-16T18:59:08-0500
James E. Donahue, R.A.
I, James E. Donahue, R.A., am signing this document to confirm that it has been reviewed.

File details come from the government source that posted it. Updated .