J-1502000-18 Uniformat Classification.pdf

PDF 256 KB Posted

Attached to
HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) Maintenance and Repair Services and Direct Digital Controls (DDC)
Solicitation number
N4008520R2502
Issued by

View the file

Other files

File Type Posted
N4008520R250200003.pdf PDF
N4008520R25020002.pdf PDF
J-0200000-04 Invoice Form.pdf PDF
N4008520R25010001.pdf PDF
J-1502000-12A NAVSUBASE NLON FY14 UPV CERT CARDS.pdf PDF
J-1502000-08B BOILER INVENTORY REVISED 2.xls XLS spreadsheet
J-0200000-02D CBA Sup 30OCT19.pdf PDF
J-0200000-02C CBA.pdf PDF
N4008520R2502.pdf PDF
J-0200000-09 - CHARACTERISTIC METER READING INFORMATION v2 - 2016-09-30.xlsx XLSX spreadsheet
HVAC 1502000 WBS Facility Investment.pdf PDF
HVAC 1502000 SECTION J.pdf PDF
J-1502000-20 Service Order Summary Report.xls XLS spreadsheet
J-1502000-16 Navy Sub Systems Water Testing.xlsx XLSX spreadsheet
J-0200000-05F On site Labor Summary Report reviewed.xls XLS spreadsheet
J-1502000-05A HVAC-CALLS 1-1-15 to 12-31-15.xls XLS spreadsheet
J-0200000-15 ACM HISTORICAL DATA.xls XLS spreadsheet
J-1502000-21 Monthly Preventative Maintenance Summary Report.xls XLS spreadsheet
J-0200000-02B SCA 2015-4111.pdf PDF
J-0200000-16 UEM Contractor Outage Process 20141120.pdf PDF
J-1502000-09 BUILDING INVENTORY FOR BAS.xlsx XLSX spreadsheet
0200000 F Management and Administration.pdf PDF
J-1502000-8A Unfired Pressure Vessels NEWLON.xlsx XLSX spreadsheet
J-0200000-07 - ASSET INFORMATION v2 - 2017-04-26.xlsx XLSX spreadsheet
J-1502000-24 Asset Condition Report 2018.xlsx XLSX spreadsheet
J-0200000-06 - SERVICE PROVIDER INFORMATION v1 - 2013-07-07.xlsx XLSX spreadsheet
J-0200000-05E Quality Inspection and Surveillance report reviewed.xls XLS spreadsheet
HVAC 1502000 SECTION F.pdf PDF
J-1502000-19 Direct Condition Rating Guidance.pdf PDF
J-0200000-12 Installation Spill Control Plan.pdf PDF
0200000 C Management and Administration.pdf PDF
0200000 J Management and Administration.pdf PDF
J-0200000-05D contractor incident report system.pdf PDF
J-1502000-10A Refrigerant Appliance Disposal.pdf PDF
J-1502000-05B HVAC-CALLS 1-1-16 to 12-31-16.xls XLS spreadsheet
J-1502000-06 PROPERTY ASSET INVENTORY revised.xls XLS spreadsheet
J-1502000-5D HVAC 2018 Call Log.xlsx XLSX spreadsheet
J-1502000-12B NAVSUBASE NLON FY14 BOILER CERT CARDS.pdf PDF
J-1502000-25 Hot and Cold Closed Loop HVAC.pdf PDF
J-1502000-17 HVAC Systems Seasonal Start-Up and Shutodwn.xlsx XLSX spreadsheet
J-1502000-03 BUILDING INVENTORY.xls XLS spreadsheet
J-1502000-22 Prescriptive Maintenance Summary Report.xls XLS spreadsheet
J-1502000-5C HVAC 2017 Call Log.xlsx XLSX spreadsheet
0100000 C General Information.pdf PDF
J-1502000-10B Refrigerant Appliance Installation.pdf PDF
HVAC BID SCHEDULE.xls XLS spreadsheet
J-0200000-08 - ASSET SPECIFICATION v1 - 2016-01-20.xlsx XLSX spreadsheet
J-1502000-23 MP-217_D_00_SB.pdf PDF
J-0200000-02A DBA WD CT20190024.pdf PDF
HVAC 1502000 SECTION C.pdf PDF
Show 40 more

Latest 50 of 53 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT J-1502000-18

UNIFORMAT CLASSIFICATION

METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE

D3020130 - Boiler, Cast Iron, Hot Water, Gas Meter & Description Direct Condition Rating Guidance Condition CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly AMBER: Controls need calibrating RED: Controls are damaged and/or not operational

CR-5365 - Record the condition of the Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes RED: Firebox has significant damage or corrosion, cracks or holes may be present

CR-5370 - Record the condition of the Flue

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired

CR-5380 - Record the condition of the Fuel System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired

CR-5530 - Record the

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

CR-5540 - Record the condition of the Pressure Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured

CR-5690 - Record the

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3020134 - Boiler, Cast Iron, Steam, Gas

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

CR-5520 - Record the

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3020138 - Boiler, Cast Iron, Steam, Gas/Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

CR-5345 - Record the condition of the Feed Water System

GREEN: Feed Water System has no damage or leaks, fully operational AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3020901 - Boiler, Cast Iron, HW, Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

System

GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3020902 - Boiler, Cast Iron, Steam, Oil

CR-5060 - Record the condition of the Burner Assembly

GREEN: Burners have minimal damage or corrosion, but is fully operational AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound

GREEN: Controls function properly

Firebox/Fire Tubes

GREEN: Firebox has minimal damage or corrosion AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Vessel

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030130 - Chiller, Reciprocating, Water Cooled

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional RED: Unacceptable Noise, Vibration, or overheating from compressor, significant damage, and/or operationally impaired

CR-5155 - Record the

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired

GREEN: Controls function properly

CR-5295 - Record the

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing

CR-5305 - Record the

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5565 - Record the condition of the Receiver Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030135 - Chiller, Reciprocating, Air Cooled

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5175 - Record the

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3030140 - Chiller, Centrifugal, Water Cooled

CR-5110 - Record the condition of the Centrifugal Motor

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

CR-5140 - Record the

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5210 - Record the

Controls/Sensors

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Tank

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030145 - Chiller, Gas Absorption, Water Cooled

CR-5000 - Record the condition of the Absorber

GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5430 - Record the condition of the Heat Generator

GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, operationally impaired

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5555 - Record the

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030150 - Chiller, Steam Absorption, Water Cooled

CR-5000 - Record the condition of the Absorber

GREEN: Absorber has minimal damage and corrosion, but no leaks AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Evaporator

GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

CR-5430 - Record the condition of the Heat Generator

GREEN: Heating Element has little to no damage or corrosion, and is fully operational AMBER: Heating Element has noticeable damage or corrosion, but still operational RED: Heating Element has significant damage or corrosion, operationally

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5555 - Record the

GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure

D3030310 - Cooling Tower, Galvanized

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking RED: Sump has significant damage or corrosion, and noticeable leaking, CR-5280 - Record the

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional RED: Conductivity Electrodes have significant damage and corrosion, loose or missing connections, operationally impaired

CR-5325 - Record the condition of the Fan Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational RED: Fans blades are out of balance, significantly bent or corroded, or fan is operationally impaired

CR-5350 - Record the condition of the Fill Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow RED: Air Filter clogged with dirt and debris, or shows signs of damage such as, punctures, tears, rips

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030320 - Cooling Tower, Fiberglass

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional

Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030330 - Cooling Tower, Stainless Steel

CR-5025 - Record the condition of the Basin/Sump

GREEN: Sump has minimal damage or corrosion, no leaking AMBER: Sump has noticeable damage or corrosion, but no leaking

Electrodes

GREEN: Conductivity Electrodes have minimal damage and corrosion, secure connections and fully functional AMBER: Conductivity Electrodes have noticeable damage and corrosion, some loose connections but still functional

Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Material

GREEN: Filter has minimal to no dirt and debris, free of damage AMBER: Filter shows noticeable signs of debris, but little to no damage allowing unobstructed flow

Pipes/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3030902 - Condenser, DX, Evaporative

CR-5325 - Record the condition of the Fan Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

CR-5495 - Record the condition of the Louvers

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational RED: Louvers have significant damage and corrosion, may be loose, missing, and/or operationally impaired

CR-5515 - Record the condition of the Nozzles

GREEN: Nozzles show no signs of damage, corrosion, or clogging, fully operational AMBER: Nozzles have some damage, corrosion, or clogs, noticeable obstruction of flow, but operational RED: Nozzles have significant damage and corrosion, severely obstructed flow, operationally impaired

CR-5615 - Record the condition of the Sump Pump

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3030903 - Packaged DX Refrigerant System

CR-5140 - Record the condition of the Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

CR-5185 - Record the

Condensing Coils

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

GREEN: Controls function properly

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040106 - Air Handling Unit, Field Fabricated

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

CR-5125 - Record the condition of the Coils (Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

CR-5145 - Record the

Condensate Piping

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Controls/Sensors

GREEN: Controls function properly

CR-5235 - Record the condition of the Dampers

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational RED: Damper has significant damage and corrosion, noticeably loose, CR-5260 - Record the condition of the Drain Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5330 - Record the

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040110 - Air Handling Unit, Central Station

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5340 - Record the condition of the Fan(s) Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040114 - Air Handling Unit, Rooftop

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

CR-5340 - Record the condition of the Fan(s) Assembly

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

GREEN: Louvers have minimal damage and corrosion, fully secured AMBER: Louvers have noticeable damage and corrosion, may be loose but still operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3040220 - Fan System, Centrifugal In-Line

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040230 - Fan System, Utility Set

CR-5330 - Record the condition of the Fan Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

CR-5630 - Record the condition of the Switches Controls

GREEN: Switches function properly AMBER: None RED: Switches do not function properly

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040240 - Fan System, Roof Exhaust

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

GREEN: Damper has minimal damage, is secured and aligned properly, and fully operational AMBER: Damper has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3040330 - Circulating Pump, End Suction

CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally

D3040340 - Circulating Pump, Double Suction

CR-5045 - Record the condition of the Booster Pump, w/ Oil Reservoir

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally

D3040610 - Heat Exchanger, Plate Type

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

CR-5375 - Record the

Frame/Supports

GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured

CR-5465 - Record the

Insulation

GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5570 - Record the condition of the Relief Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration RED: Valve has significant damage or corrosion, is operationally

CR-5590 - Record the condition of the Steam Modulating Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration

D3040620 - Heat Exchanger, Shell Tube

CR-5200 - Record the condition of the Controls

GREEN: Controls function properly

CR-5375 - Record the

Frame/Supports

GREEN: Supports have minimal damage and corrosion, are fully stable and secure AMBER: Supports have noticeable damage and corrosion, but still structurally stable and secure RED: Supports have significant damage and corrosion, and/or unstable or not secured

CR-5465 - Record the

Insulation

GREEN: Insulation has minimal deterioration, and is mostly in place where necessary AMBER: Insulation has noticeable deterioration, portions may be loose or displaced, but mostly intact RED: Insulation is significantly damaged, or large portions are displaced or missing

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

CR-5570 - Record the condition of the Relief Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration

CR-5590 - Record the condition of the Steam Modulating Valve

GREEN: Valve has little to no damage or corrosion, is fully operational AMBER: Valve shows some damage or corrosion, valve functions but may require calibration

D3050170 - Split Systems With Air Cooled Condensing Units

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

RED: Coils are clogged, show some signs of damage, or significant scaling and deterioration.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks RED: Drain Pan has significant damage or corrosion, and noticeable leaks

CR-5460 - Record the condition of the Indoor Fan Motor Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding RED: Wiring is significantly deteriorated or frayed, connection are loose, or risk of unintentional grounding

D3050185 - Computer Room Cooling Units

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

CR-5150 - Record the

Condensate Pump

GREEN: Pump has minimal damage or corrosion, no unusual noise/vibration, no leaks, and is fully operational AMBER: Pump has noticeable damage or corrosion, slight leaking, unusual noise/vibration, but still operational RED: Pump has significant damage or corrosion, excessive noise/vibration, noticeable leaking, and/or is operationally impaired

Controls/Sensors

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

CR-5450 - Record the

Humidifier

GREEN: Pan has minimal damage or corrosion AMBER: Pan has noticeable damage or corrosion, but no leaks RED: Pan has significant damage or corrosion, and noticeable leaks

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

D3050201 - Packaged A/C, Air Cooled, Elec Heat

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

CR-5275 - Record the condition of the Duct Connectors

GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

D3050201 - Packaged A/C, Air Cooled, Elec Heat

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3050203 - Packaged A/C, Air Cooled, HW Heat

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

Condenser Fan(s) Assembly

GREEN: Motor operates properly, free of excessive noise/vibration, or overheating AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

CR-5275 - Record the condition of the Duct Connectors

GREEN: Ductwork has little to no damage or corrosion, insulation is intact and there are no holes, leaks, or blockages AMBER: Ductwork has noticeable damage or corrosion, but minimal leaks or blockages RED: Ductwork has significant damage or corrosion, holes, punctures, leaks, or blockages. Operation is severely impaired

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

D3050203 - Packaged A/C, Air Cooled, HW Heat

CR-5530 - Record the condition of the Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

DIRECT CONDITION RATING GUIDANCE BY METER GROUP AND UNIFORMAT

D3050210 - Packaged A/C, Water Cooled, Elec Heat

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3050220 - Packaged A/C, Water Cooled, HW Heat

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the condenser/coils, no damage AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational

GREEN: Controls function properly

Pan

GREEN: Drain Pan has minimal damage or corrosion AMBER: Drain Pan has noticeable damage or corrosion, but no leaks

Enclosure

GREEN: Minimal damage and corrosion on Enclosure, fully secured AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose or displaced

Assy

GREEN: Fan blades are in balance and free of damage or corrosion AMBER: Excessive Noise/Vibration, but blades not bent or corroded, fully operational

Piping/Fittings/Valves

GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking

Wiring/Connections

GREEN: Wiring is protected/insulated and connections are secure AMBER: Wiring is may be frayed but not exposed, connection are generally secure, no noticeable risk of unintentional grounding

D3050255 - Thru-Wall A/C Unit

CR-5120 - Record the condition of the Coils (Cooling)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

(Heating)

GREEN: Coils have minimal scaling and free of debris.

AMBER: Coils are clogged, or show significant scaling and deterioration, but minimal damage.

Compressor

GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational AMBER: Excessive Noise, Vibration, or overheating noticeable from compressor, but compressor is still functional

Condenser

GREEN: Minimal corrosion or fouling of the…