This solicitation requests proposals for repairs and renovations to Building 488 at Naval Submarine Base New London in Connecticut. Work includes whole building repairs, construction of a new sidewalk, site work, and interior upgrades to fire protection, finishes, mechanical and plumbing systems. The scope also involves exterior enclosure repairs to restore quality to the 188-bed enlisted housing facility. The solicitation was issued by the Naval Facilities Engineering Command on behalf of the Department of the Navy. The deadline for proposals was January 28, 2020.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION GENERAL NOTES:
1. THE FIRE PROTECTION SYSTEM SHALL BE DESIGNED TO COMPLY WITH THE
DEPARTMENT OF DEFENSE (DOD) UNIFIED FACILITIES CRITERIA (UFC), UNITED
FACILITIES GUIDE SPECIFICATIONS (UFGS) AND NFPA 13 REQUIREMENTS:
FINAL DESIGN SHALL BE BASED ON THIS CRITERIA.
2. EXAMINE CONTRACT DOCUMENTS FOR ALL TRADES. THE FIRE
PROTECTION CONTRACTOR SHALL COORDINATE ELECTRICAL, PLUMBING &
HVAC REQUIREMENTS WITH EACH CONTRACTOR.
3. DRAWINGS ARE DIAGRAMMATIC ONLY, FINAL ROUTING OF PIPING AND
EQUIPMENT LOCATIONS SHALL BE DETERMINED IN THE FIELD. ADDITIONAL
OFFSETS, ELBOWS, ETC., SHALL BE PROVIDED AND INSTALLED WITHOUT
ADDITIONAL COST TO THE OWNER.
4. VERIFY THE INTEGRITY, CONDITION AND LOCATION OF EXISTING PIPING WHICH
IS TO BE REUSED. IF PIPING CANNOT BE REUSED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT/ENGINEER TO DETERMINE EXTENT OF REPLACEMENT.
5. VERIFY IN FIELD EXACT LOCATIONS, PIPE ELEVATIONS AND PIPE SIZES OF
EXISTING SPRINKLER PIPING (BRANCH AND MAIN) AND SPRINKLER HEADS
PRIOR TO ANY WORK.
6. TAKE CARE AND PROTECT EXISTING SPRINKLER HEADS AND PIPING TO
REMAIN DURING DEMOLITION AND CONSTRUCTION.
7. COORDINATE ALL ELECTRICAL, PLUMBING & HVAC REQUIREMENTS WITH THE
ELECTRICAL, PLUMBING AND HVAC CONTRACTORS.
8. FURNISH AND INSTALL ALL INCIDENTAL ACCESSORIES/SUPPLEMENTAL STEEL
NECESSARY TO MAKE THE FIRE PROTECTION WORK COMPLETE AND READY
FOR OPERATION.
9. COORDINATE WITH NAVFAC CONSTRUCTION MANAGER OR THEIR
REPRESENTATIVE ALL SYSTEM SHUTDOWNS. THE NAVFAC CONSTRUCTION
MANAGER OR THEIR REPRESETATIVE SHALL BE INFORMED OF ANY
INTERRUPTIONS AT LEAST 72 HOURS IN ADVANCE, AND GRANT PERMISSION OF
EACH SHUT-DOWN. PROVIDE FIRE WATCH OR TEMPORARY SERVICE
REQUIRED BY FIRE DEPARTMENT TO REDUCE OR ELIMINATE
UNPROTECTED AREAS AT ANY TIME DURING DEMOLISHED CONSTRUCTION.
PROVIDE AN IMPAIRMENT PLAN PRIOR TO INSTALLATION.
10. INFORM THE OWNER WELL IN ADVANCE OF ANY WORK TO BE UNDERTAKEN IN
OCCUPIED AREAS OF THE BUILDING ASSOCIATED WITH THIS PROJECT. THE
FIRE PROTECTION CONTRACTOR SHALL CONFORM TO THE OWNER'S CRITERIA
FOR WORK HOURS, ENVIRONMENTAL ISOLATION, AND NOISE LIMITS IN THE
PORTIONS OF THE BUILDING WHICH REMAIN OCCUPIED DURING
CONSTRUCTION.
11. PROVIDE COORDINATED AND FULLY DESIGNED SPRINKLER FABRICATION
DRAWINGS TO THE ARCHITECT/ENGINEER FOR REVIEW PRIOR TO ANY
WORK, FABRICATION, OR ORDERING OF ANY MATERIALS. INCLUDED IN THIS
SUBMISSION SHALL BE STAMPED AND SIGNED DRAWINGS OF THE ENTIRE
FACILITY, AS WELL AS SEISMIC RESTRAINT LOCATIONS AND DESIGN. THIS
SHALL ALL BE PROVIDED AFTER COORDINATION DRAWINGS ARE SUBMITTED
AND APPROVED FOR LAYOUT.
12. PROVIDE COORDINATION DRAWINGS FOR REVIEW BY ARCHITECT AND
ENGINEER PRIOR TO FABRICATION OR INSTALLATION. COORDINATE THE WORK
OF THE FIRE PROTECTION CONTRACT WITH THE WORK OF THE MECHANICAL,
PLUMBING, ELECTRICAL, AND TELE/DATA CONTRACTS. RESOLVE LOCATION
AND DIMENSION CONFLICTS PRIOR TO FABRICATION AND INSTALLATION.
13. ALL SYSTEM PIPING, FITTINGS, DEVICES, VALVES, AND SPRINKLERS SHALL BE
UL LISTED OR FM APPROVED FOR THE SERVICE AND USE INTENDED.
14. FLOW AND TAMPER SWITCHES WILL BE PROVIDED BY FIRE PROTECTION
CONTRACTOR, HOWEVER, ALL ELECTRICAL WIRING IS BY OTHERS. FIRE
PROTECTION CONTRACTOR WILL BE RESPONSIBLE TO COORDINATE WITH THE
APPROPRIATE SUBCONTRACTOR.
15. ALL SPRINKLER PIPING SHALL BE AT LEAST 1" SIZE.
16. NEW SPRINKLERS SHALL MATCH THE THERMAL SENSITIVITY, RESPONSE
TIME, PROTECTION AREA, SPACING, AND MANUFACTURER OF THE EXISTING
SPRINKLERS THAT ARE TO REMAIN WITHIN THE SAME COMPARTMENT.
17. ALL THREADED PIPE SHALL BE BLACK STEEL, SCHEDULE-40 OR EQUAL (2" AND
SMALLER).
18. ALL GROOVED PIPE SHALL BE BLACK STEEL, SCHEDULE-10 OR EQUAL (2-1/2"
AND LARGER).
19. ALL PIPING USED FOR EXTERIOR APPLICATIONS SHALL BE GALVANIZED.
20. FITTINGS SHALL BE CLASS 125 THREADED CAST IRON ANSI B16.4.
21. ALL PIPING SHALL BE EARTHQUAKE BRACED AS OUTLINED IN NFPA 13.
22. ALL HANGER COMPONENTS AND INSTALLATION METHODS SHALL BE IN
ACCORDANCE WITH NFPA 13.
23. ALL NEW PIPING SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR A
PERIOD OF TIME THAT IS NOT LESS THAN TWO HOURS.
24. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING
PERMITS WITH THE BASE ENVIORNMENTAL DEPARTMENT FOR DISCHARGE OF
WATER TO THE STORMWATER DRAINAGE SYSTEM.
SYMBOLS:
DOUBLE CHECK VALVE ASSEMBLY WITH TAMPER SWITCHES
WATER MOTOR GONG
CHECK VALVE
CONTROL VALVE WITH TAMPER SWITCH
PRESSURE GAUGE
PIPE DROP OR RISE
FLOOR CONTROL VALVE ASSEMBLY
PUMP TEST HEADER
HOSE VALVE CONNECTION
ALARM CHECK VALVE
DRY ALARM VALVE
FIRE DEPARTMENT CONNECTION
PENDENT/RECESSED SPRINKLER
EXISTING ABOVEGROUND PIPING
NEW ABOVEGROUND PIPING
CONNECT TO EXISTING
POST INDICATOR VALVE
UPRIGHT ABOVE AND PENDENT BELOW
UPRIGHT SPRINKLER
SPRINKLER WITH GUARD (SEE TYPE)
PIPE CONTINUATION
JPC JOCKEY PUMP CONTROLLER
FPC FIRE PUMP CONTROLLER
JP
AB
UNDERGROUND PIPING
FLOW METER
JOCKEY PUMP
ROOF MANIFOLD
DS DRY SIDEWALL SPRINKLER
FP FIRE PUMP
PRESSURE SWITCH
WATERFLOW SWITCH
TEST AND DRAIN VALVE
FIRE PROTECTION SCOPE OF WORK:
THE FIRE PROTECTION WORK INCLUDES, BUT IS NOT LIMITED TO
COMPLETING THE FOLLOWING TASKS:
1. THE WORK INCLUDES RELOCATION OF SPRINKLERS IN THE
GAMEROOM, TV ROOM, ENTRANCE LOBBY, VENDING ROOM,
OFFICE, JANITORS CLOSET, BATHROOM, AND CORRIDOR. WHEN
THE EXISTING SPRINKLERS ARE RELOCATED THEY SHALL BE
REPLACED WITH NEW SPRINKLERS.
2. THE WORK INCLUDES INSTALLATION OF NEW SPRINKLERS IN THE
LOUNGE, LAUNDRY ROOMS, AND MECHANICAL ROOMS.
3. THE WORK INCLUDES INSTALLATION OF CHECK VALVES AND
PRESSURE RELIEF VALVES AT EACH ZONE CONTROL ASSEMBLY.
4. THE WORK INCLUDES THE INSTALLATION OF CONTROL VALVES
AND FLOW SWITCHES FOR EACH STANDPIPE RISER ASSEMBLY.
5. THE WORK INCLUDES THE INSTALLATION OF A NITROGEN
GENERATOR FOR THE EXISTING DRY-PIPE SPRINKLER SYSTEM.
6. THE WORK INCLUDES REPACKING OF THE EXISTING FIRE PUMP.
7. THE WORK INCLUDES THE INSTALLATION OF A FLOW METER
INLINE WITH THE FIRE PUMP TEST HEADER.
8. THE WORK INCLUDES INSTALLATION OF NEW PIPING AND VALVES
FOR RECIRCULATION OF WATER THROUGH THE FIRE PUMP.
9. THE WORK INCLUDES THE RECONFIGURATION OF THE SENSING
LINES FOR THE FIRE PUMP AND THE JOCKEY PUMP CONTROLLERS.
10. THE WORK INCLUDES THE INSTALLATION OF FIRE DEPARTMENT
HOSE VALVE MANIFOLDS ON THE ROOF OF THE BUILDING.
11. THE WORK INCLUDES THE TEMPORARY REMOVAL AND
REINSTALLATION OF SPRINKLER ESCUTCHEONS IN THE
EXISTING BERTHING UNITS AND THE CORRIDORS TO FACILITATE
REMOVAL AND REINSTALLATION OF THE CEILINGS. THE
CONTRACTOR SHALL PROVIDE PROTECTIVE COVERS FOR
SPRINKLERS WITHIN THE WORK AREAS. THE WORK ALSO
INCLUDES DE-ENERGIZING AND RE-ENERGIZING THE SPRINKLER
SYSTEM ON A DAILY BASIS WHILE THIS WORK IS COMPLETED.
12. THE WORK INCLUDES THE INSTALLATION OF A DRY SIDEWALL
SPRINKLER IN VESTIBULE C-119. THE CONTRACTOR SHALL
REMOVE THE EXISTING PENDENT SPRINKLER, ASSOCIATED PIPING,
AND HEAT TRACE FROM THE ENTRY VESTIBULE.
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
NTS
:3 :4
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-001
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
N O T E S
A N D
S Y M B O L S
L E G E N D
F P
12807016
PSM PSM CMA
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
2 0
6 66
2 2 2
STAIRWELL 6
SECOND FLOOR
NORTH BUILDING
NORTH BUILDING
THIRD FLOOR
NORTH BUILDING
FOURTH FLOOR
NORTH BUILDING
FIFTH FLOOR
NORTH BUILDING
FIRST FLOOR
ROOF LEVEL
NORTH BUILDING
SECOND FLOOR
SOUTH BUILDING
THIRD FLOOR
SOUTH BUILDING
FOURTH FLOOR
SOUTH BUILDING
ROOF LEVEL
SOUTH BUILDING
STAIRWELL 4STAIRWELL 5
SOUTH BUILDING
NORTH BUILDING
STAIRWELL 3 STAIRWELL 1
GROUND LEVEL
SOUTH BUILDING
STAIRWELL 2
SOUTH BUILDING
NEW CHECK VALVE AND RELIEF VALVE FOR ZONE CONTROL ASSEMBLY
NEW CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER
NEW FLOW METER INLINE WITH FIRE PUMP TEST HEADER
NEW HOSE MANIFOLD ON THE ROOF OF THE BUILDING
NEW NITROGEN GENERATOR FOR EXISTING DRY-PIPE SYSTEM
NEW CONTROL VALVE FOR FLOW METER INSTALLATION
NEW PIPING FOR WATER RECIRCULATION THROUGH PUMP
REPLACE THE PACKING FOR THE EXISTING FIRE PUMP ASSEMBLY
CONCEPTUAL FIRE PROTECTION RISER DIAGRAM
KEY NOTES
CHECK VALVE
ELECTRIC FIRE PUMP
(400GPM @ 50psi)
FIRE PUMP TEST HEADER
FIRE PUMP
BYPASS
THIRD FLOOR
SPRINKLERS
SECOND FLOOR
SPRINKLERS
D R
A
IN
R
IS
E R
FDC 3'-0" A.F.G.
EXISTING 8"
FIRE SERVICE
PIV
FLOW METER
4"
4"
4"
WATER MOTOR GONG
6"
FOURTH FLOOR
SPRINKLERS
THIRD FLOOR
SPRINKLERS
SECOND FLOOR
SPRINKLERS
D R
A
IN
R
IS
E R
4"
4"
4"
FOURTH FLOOR
SPRINKLERS
NORTH TOWER
ELEVATOR PENTHOUSE
SPRINKLERS
4" FIFTH FLOOR
SPRINKLERS
4" FIFTH FLOOR
SPRINKLERS
FIRST FLOOR
SPRINKLERS
4"
6" 6"
6"
THIRD FLOOR
SPRINKLERS
SECOND FLOOR
SPRINKLERS
D R
A
IN
R
IS
E R
4"
4"
4"
FOURTH FLOOR
SPRINKLERS
FIRST FLOOR
SPRINKLERS
4"
SOUTH TOWER ELEVATOR
PENTHOUSE SPRINKLERS
THIRD FLOOR
SPRINKLERS
SECOND FLOOR
SPRINKLERS
D R
A
IN
R
IS
E R
4"
4"
4"
FOURTH FLOOR
SPRINKLERS
FIRST FLOOR
SPRINKLERS
4"
6" 6" 6"6"
GROUND LEVEL
SPRINKLERS
6"6"
PIV
PIV
JP
FP
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
:3 :4
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-002
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
C O N C E P T U A L
R
IS
E R
D
IA
G R A M
F P
12807017
PSM PSM CMA
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
WD
D
D D
D D
D D
W W
W W
W W
W
15 16 17 18
FFEEDDCCBB
BB
AA
AA
M M
L L
F F
G G
H H
K K
J J
ELEVATOR
P-1
UTILITY
N-135
ELEVATOR
LOBBY
N-134
STAIR
LOUNGE
C-108
STAIR
C-108B
VESTIBULE
C-123
RECEPTION
DESK
C-108A
VENDING
C-115
JAN. CLO
C-117
CORRIDOR
C-116
W.C.
C-114
OFFICE
C-120
VESTIBULE
C-119
CORRIDOR
C-122
STAIR
SWITCH
GEAR ROOM
N-101
MECHANICAL
ROOM
N-101.1
MECHANICAL
ROOM
N-102
UTILITY
N-108
BB
BB
AA
AA
B
C C
D D
E E
F F
G G
H H
J J
CORRIDOR
C-122
STAIR
BERTHING
UNIT
S-101
BERTHING
UNIT
S-103
BERTHING
UNIT
S-105
BERTHING
UNIT
S-107
BAG
STORAGE
S-108
LAUNDRY
ROOM
S-106
JAN. CLO
S-106A
BERTHING
UNIT
S-104
BERTHING
UNIT
S-102
CORRIDOR
S-137
VESTIBULE
C-124
STAIR
ELEVATOR
LOBBY
S-134
ELEVATOR
P-2
UTILITY
S-135
BERTHING
UNIT
S-110
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
A
B
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :5
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-101A&B
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IR
S T
F L O O R
P L A N
P A R T
A
B
F P A B
12807018
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIRST FLOOR PLAN - PART A
A1 SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIRST FLOOR PLAN - PART B
A3
1 INSTALL TWO (2) NEW SPRINKLERS UNDER STAIRS (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
3 INSTALL ONE (1) NEW SPRINKLER UNDER LOWER CEILING (SEE DETAIL FP-201)
4 INSTALL TWO (2) NEW SPRINKLERS UNDER SOFFIT (SEE DETAIL FP-201)
5 INSTALL CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER (SEE DETAIL FP-201)
6 INSTALL NITROGEN GENERATOR FOR DRY-PIPE SYSTEM (SEE DETAIL FP-201)
7 RELOCATE SPRINKLERS IN NEW CEILINGS FOR WATER CLOSET C-114, VENDING C-115,
CORRIDOR C-116, AND JAINTORS CLOSET C-117 (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
D D
D D
D D
W W
W W
W W
W W
CC
CC
BB
BB
AA
AA
M M
L L
G G
H H
K K
J J
JP
C
FP
C
FP
BERTHING
UNIT
N-119
BERTHING
UNIT
N-117
BERTHING
UNIT
N-115
BERTHING
UNIT
N-113
LAUNDRY
ROOM
N-111
FIRE PUMP
N-109
ELEVATOR
P-1
UTILITY
N-135
ELEVATOR
LOBBY
N-134
STAIR
BERTHING
UNIT
N-110
BERTHING
UNIT
N-112
BERTHING
UNIT
N-114
BERTHING
UNIT
N-116
BERTHING
UNIT
N-118
BERTHING
UNIT
N-120
CORRIDOR
N-133
LOUNGE
C-108
STAIR
C-108B
VESTIBULE
C-123
RECEPTION
DESK
C-108A
FIRE SERVICE
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :5
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-101C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IR
S T
F L O O R
P L A N
P A R T
C
F P C
12807019
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIRST FLOOR PLAN - PART C
A1
1 INSTALL TWO (2) NEW SPRINKLERS UNDER SOFFIT (SEE DETAIL FP-201)
2 INSTALL CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER (SEE DETAIL FP-201)
3 INSTALL NEW FLOW METER INLINE WITH TEST HEADER (SEE DETAIL FP-201)
4 REPLACE EXISTING FIRE PUMP PACKING (SEE DETAIL FP-200)
5 RECONFIGURE SENSING LINES FOR FIRE PUMP AND JOCKEY PUMP (SEE DETAIL FP-200)
6 INSTALL NEW CONTROL VALVE FOR FLOW METER INSTALLATION (SEE DETAIL FP-200)
7 INSTALL NEW PIPING FOR WATER RECIRCULATION THROUGH PUMP (SEE DETAIL FP-200)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
W W
W W
W W
W W
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
B
C C
D D
E E
F F
G G
H H
J J
OFFICE
C-120
VESTIBULE
C-119
CORRIDOR
C-122
BERTHING
UNIT
S-105
BERTHING
UNIT
S-107
BAG
STORAGE
S-108
LAUNDRY
ROOM
S-106
JAN. CLO
S-106A
VESTIBULE
C-124
STAIR
ELEVATOR
LOBBY
S-134
ELEVATOR
P-2
UTILITY
S-135
BERTHING
UNIT
S-110
BERTHING
UNIT
S-112
BERTHING
UNIT
S-114
BERTHING
UNIT
S-116
BERTHING
UNIT
S-118
BERTHING
UNIT
S-120
BERTHING
UNIT
S-122
BERTHING
UNIT
S-128
BERTHING
UNIT
S-126
BERTHING
UNIT
S-124
BERTHING
UNIT
S-127
BERTHING
UNIT
S-125
BERTHING
UNIT
S-123
BERTHING
UNIT
S-121
BERTHING
UNIT
S-119
BERTHING
UNIT
S-117
BERTHING
UNIT
S-115
BERTHING
UNIT
S-113
CORRIDOR
S-133
STAIR
DS 3
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :5
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-101D
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IR
S T
F L O O R
P L A N
P A R T
D
F P D
12807020
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIRST FLOOR PLAN - PART D
A1
1 INSTALL CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
3 INSTALL DRY SIDEWALL SPRINKLER IN VESTIBULE (SEE DETAIL FP-201)
4 RELOCATE SPRINKLERS IN NEW CEILING FOR OFFICE C-120 (SEE DETAIL FP-201) IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
M M
L L
F F
G G
H H
K K
J J
ELEVATOR
P-1
ELEVATOR
LOBBY
N-234
UTILITY
N-235
CORRIDOR
N-237
LOUNGE
C-108
STAIR
C-108B
BERTHING
UNIT
N-207
BERTHING
UNIT
N-205
BERTHING
UNIT
N-206
BERTHING
UNIT
N-208
STAIR
LOUNGE
C-203
CORRIDOR
C-202
ABABAB
ABABAB
BB
BB
AA
AA
B B
C C
D D
E E
F F
G G
H H
J J
STAIR
BERTHING
UNIT
S-201
BERTHING
UNIT
S-203
BERTHING
UNIT
S-205
BERTHING
UNIT
S-207
CORRIDOR
S-237
BERTHING
UNIT
S-202
BERTHING
UNIT
S-204
BERTHING
UNIT
S-206
BERTHING
UNIT
S-208
STAIR
ELEVATOR
P-2
ELEVATOR
LOBBY
S-234
UTILITY
S-235
STUDY
S-210
BERTHING
UNIT
S-209
CORRIDOR
C-202
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
A
B
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :5
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-102A&B
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
S E C O N D
F L O O R
P L A N
P A R T
A
B
F P A B
12807021
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION SECOND FLOOR PLAN - PART A
A1 SCALE: 1/8" = 1'-0"
FIRE PROTECTION SECOND FLOOR PLAN - PART B
A3
1 RELOCATE SIX (6) SPRINKLERS IN THE CEILING OF LOUNGE C-108 (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
3 RELOCATE SIX (6) SPRINKLERS IN THE GAMEROOM (SEE DETAIL FP-201)
4 INSTALL SIX (6) SPRINKLERS IN THE NEW CLOUD CEILINGS (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
CC
CC
BB
BB
AA
AA
M M
L L
G G
H H
K K
J J
STAIR
BERTHING
UNIT
N-227
BERTHING
UNIT
N-225
BERTHING
UNIT
N-223
BERTHING
UNIT
N-221
BERTHING
UNIT
N-219
BERTHING
UNIT
N-217
BERTHING
UNIT
N-215
BERTHING
UNIT
N-213
BERTHING
UNIT
N-211
BERTHING
UNIT
N-209
BERTHING
UNIT
N-210
BERTHING
UNIT
N-214
BERTHING
UNIT
N-218
BERTHING
UNIT
N-212
BERTHING
UNIT
N-216
BERTHING
UNIT
N-220
BERTHING
UNIT
N-222
BERTHING
UNIT
N-224
BERTHING
UNIT
N-226
BERTHING
UNIT
N-228
CORRIDOR
N-233
ELEVATOR
P-1
ELEVATOR
LOBBY
N-234
UTILITY
N-235
STAIR
LOUNGE
C-108
STAIR
C-108B
CORRIDOR
C-202
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :0
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-102C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
S E C O N D
F L O O R
P L A N
P A R T
C
F P C
12807022
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION SECOND FLOOR PLAN - PART C
A1
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
B B
C C
D D
E E
F F
G G
H H
J J
LOUNGE
C-204
BERTHING
UNIT
S-205
BERTHING
UNIT
S-207
BERTHING
UNIT
S-206
BERTHING
UNIT
S-208
STAIR
ELEVATOR
P-2
ELEVATOR
LOBBY
S-234
UTILITY
S-235
STUDY
S-210
BERTHING
UNIT
S-212
BERTHING
UNIT
S-214
BERTHING
UNIT
S-216
BERTHING
UNIT
S-218
BERTHING
UNIT
S-220
BERTHING
UNIT
S-222
BERTHING
UNIT
S-224
BERTHING
UNIT
S-226
BERTHING
UNIT
S-228
BERTHING
UNIT
S-227
BERTHING
UNIT
S-225
BERTHING
UNIT
S-223
BERTHING
UNIT
S-221
BERTHING
UNIT
S-219
BERTHING
UNIT
S-217
BERTHING
UNIT
S-215
BERTHING
UNIT
S-213
BERTHING
UNIT
S-211
BERTHING
UNIT
S-209
CORRIDOR
S-233
STAIR
CORRIDOR
C-202
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :0
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-102D
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
S E C O N D
F L O O R
P L A N
P A R T
D
F P D
12807023
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION SECOND FLOOR PLAN - PART D
A1
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
2 RELOCATE FOUR (4) SPRINKLERS IN THE TV ROOM (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
M M
L L
F F
G G
H H
K K
J J
ELEVATOR
P-1
ELEVATOR
LOBBY
N-334
UTILITY
N-335
JAN. CLO
N-336
BERTHING
UNIT
N-307
BERTHING
UNIT
N-305
BERTHING
UNIT
N-303
BERTHING
UNIT
N-301
BERTHING
UNIT
N-302
BERTHING
UNIT
N-304
CORRIDOR
N-337
LOUNGE
C-108
BB
BB
AA
AA
B B
C C
D D
E E
F F
G G
H H
J J
STAIR
BERTHING
UNIT
S-301
BERTHING
UNIT
S-303
BERTHING
UNIT
S-305
BERTHING
UNIT
S-307
BERTHING
UNIT
S-308
BERTHING
UNIT
S-306
BERTHING
UNIT
S-304
BERTHING
UNIT
S-302
CORRIDOR
S-337
STAIR
JAN. CLO
S-336
ELEVATOR
P-2
ELEVATOR
LOBBY
S-334
UTILITY
S-335
BERTHING
UNIT
S-309
BERTHING
UNIT
S-310
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
A
B
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :0
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-103A&B
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
T H
IR
D
F L O O R
P L A N
P A R T
A
B
F P A B
12807024
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION THIRD FLOOR PLAN - PART A
A1 SCALE: 1/8" = 1'-0"
FIRE PROTECTION THIRD FLOOR PLAN - PART B
A3
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
CC
CC
BB
BB
AA
AA
M M
L L
G G
H H
K K
J J
STAIR
BERTHING
UNIT
N-327
BERTHING
UNIT
N-325
BERTHING
UNIT
N-323
BERTHING
UNIT
N-321
BERTHING
UNIT
N-319
BERTHING
UNIT
N-317
BERTHING
UNIT
N-315
BERTHING
UNIT
N-313
BERTHING
UNIT
N-311
BERTHING
UNIT
N-309
BERTHING
UNIT
N-328
BERTHING
UNIT
N-326
BERTHING
UNIT
N-324
BERTHING
UNIT
N-322
BERTHING
UNIT
N-320
BERTHING
UNIT
N-318
BERTHING
UNIT
N-316
BERTHING
UNIT
N-314
BERTHING
UNIT
N-312
LOUNGE
N-310
ELEVATOR
P-1
ELEVATOR
LOBBY
N-334
UTILITY
N-335
STAIR
JAN. CLO
N-336
BERTHING
UNIT
N-307
BERTHING
UNIT
N-305
CORRIDOR
N-337
CORRIDOR
N-333
LOUNGE
C-108
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :1
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-103C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
T H
IR
D
F L O O R
P L A N
P A R T
C
F P C
12807025
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION THIRD FLOOR PLAN - PART C
A1
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
B B
C C
D D
E E
F F
G G
H H
J J
BERTHING
UNIT
S-305
BERTHING
UNIT
S-307
BERTHING
UNIT
S-308
BERTHING
UNIT
S-306
STAIR
JAN. CLO
S-336
ELEVATOR
P-2
ELEVATOR
LOBBY
S-334
UTILITY
S-335
BERTHING
UNIT
S-309
BERTHING
UNIT
S-311
BERTHING
UNIT
S-313
BERTHING
UNIT
S-315
BERTHING
UNIT
S-317
BERTHING
UNIT
S-319
BERTHING
UNIT
S-321
BERTHING
UNIT
S-323
BERTHING
UNIT
S-325
BERTHING
UNIT
S-327
BERTHING
UNIT
S-328
BERTHING
UNIT
S-326
BERTHING
UNIT
S-324
BERTHING
UNIT
S-322
BERTHING
UNIT
S-320
BERTHING
UNIT
S-318
BERTHING
UNIT
S-316
BERTHING
UNIT
S-314
BERTHING
UNIT
S-312
BERTHING
UNIT
S-310
STAIR
CORRIDOR
S-333
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :1
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-103D
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
T H
IR
D
F L O O R
P L A N
P A R T
D
F P D
12807026
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION THIRD FLOOR PLAN - PART D
A1
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
M M
L L
F F
G G
H H
K K
J J
ELEVATOR
P-1
ELEVATOR
LOBBY
N-434
UTILITY
N-435
STAIR
JAN. CLO
N-436
BERTHING
UNIT
N-407
BERTHING
UNIT
N-405
BERTHING
UNIT
N-403
BERTHING
UNIT
N-401
BERTHING
UNIT
N-402
BERTHING
UNIT
N-404
BERTHING
UNIT
N-406
BERTHING
UNIT
N-408
CORRIDOR
N-437
STAIR
BB
BB
AA
AA
B
C
D D
E E
F F
G G
H H
J J
STAIR
BERTHING
UNIT
S-401
BERTHING
UNIT
S-403
BERTHING
UNIT
S-405
BERTHING
UNIT
S-407
BERTHING
UNIT
S-402
BERTHING
UNIT
S-404
BERTHING
UNIT
S-406
BERTHING
UNIT
S-408
CORRIDOR
S-437
UTILITY
S-438
STAIR
BERTHING
UNIT
S-409
JAN. CLO
S-436
ELEVATOR
P-2
ELEVATOR
LOBBY
S-434
UTILITY
S-435
LOUNGE
S-410
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
A
B
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :2
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-104A&B
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F O U R T H
F L O O R
P L A N
P A R T
A
B
F P A B
12807027
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FOURTH FLOOR PLAN - PART A
A1 SCALE: 1/8" = 1'-0"
FIRE PROTECTION FOURTH FLOOR PLAN - PART B
A3
1 INSTALL CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
3 INSTALL TWO (2) NEW SPRINKLERS UNDER DUCTWORK (SEE DETAIL FP-201)
4 EXTEND EXISTING STANDPIPE FOR NEW ROOF MANIFOLD (SEE DETAIL FP-201) IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
CC
CC
BB
BB
AA
AA
M M
L L
G G
H H
K K
J J
STAIR
BERTHING
UNIT
N-427
BERTHING
UNIT
N-425
BERTHING
UNIT
N-423
BERTHING
UNIT
N-421
BERTHING
UNIT
N-419
BERTHING
UNIT
N-417
BERTHING
UNIT
N-415
BERTHING
UNIT
N-413
BERTHING
UNIT
N-411
BERTHING
UNIT
N-409
BERTHING
UNIT
N-410
BERTHING
UNIT
N-412
BERTHING
UNIT
N-414
BERTHING
UNIT
N-416
BERTHING
UNIT
N-418
BERTHING
UNIT
N-420
BERTHING
UNIT
N-422
BERTHING
UNIT
N-424
BERTHING
UNIT
N-426
BERTHING
UNIT
N-428
ELEVATOR
P-1
ELEVATOR
LOBBY
N-434
UTILITY
N-435
STAIR
JAN. CLO
N-436
BERTHING
UNIT
N-407
BERTHING
UNIT
N-405
BERTHING
UNIT
N-406
BERTHING
UNIT
N-408
CORRIDOR
N-437
CORRIDOR
N-433
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :2
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-104C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F O U R T H
F L O O R
P L A N
P A R T
C
F P C
12807028
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FOURTH FLOOR PLAN - PART C
A1
1 INSTALL CONTROL VALVE AND FLOW SWITCH FOR STANDPIPE RISER (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
B
C
D D
E E
F F
G G
H H
J J
BERTHING
UNIT
S-405
BERTHING
UNIT
S-407
BERTHING
UNIT
S-406
BERTHING
UNIT
S-408
STAIR
BERTHING
UNIT
S-409
JAN. CLO
S-436
ELEVATOR
P-2
ELEVATOR
LOBBY
S-434
UTILITY
S-435
BERTHING
UNIT
S-411
BERTHING
UNIT
S-413
BERTHING
UNIT
S-415
BERTHING
UNIT
S-417
BERTHING
UNIT
S-419
BERTHING
UNIT
S-421
BERTHING
UNIT
S-423
BERTHING
UNIT
S-425
BERTHING
UNIT
S-427
BERTHING
UNIT
S-428
BERTHING
UNIT
S-426
BERTHING
UNIT
S-424
BERTHING
UNIT
S-422
BERTHING
UNIT
S-420
BERTHING
UNIT
S-418
BERTHING
UNIT
S-416
BERTHING
UNIT
S-414
BERTHING
UNIT
S-412
LOUNGE
S-410
CORRIDOR
S-433
STAIR
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
D
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :2
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-104D
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F O U R T H
F L O O R
P L A N
P A R T
D
F P D
12807029
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FOURTH FLOOR PLAN - PART D
A1
1 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
FF
FF
EE
EE
DD
DD
CC
CC
BB
BB
AA
AA
M M
L L
F F
G G
H H
K K
J J
ELEVATOR
P-1
ELEVATOR
LOBBY
N-534
UTILITY
N-535
STAIR
JAN. CLO
N-536
UTILITY
N-538
BERTHING
UNIT
N-507
BERTHING
UNIT
N-505
BERTHING
UNIT
N-503
BERTHING
UNIT
N-501
BERTHING
UNIT
N-502
BERTHING
UNIT
N-504
BERTHING
UNIT
N-506
RADIO ROOM
N-508
CORRIDOR
N-537
STAIR
BB
BB
AA
AA
B
C
D D
E E
F F
G G
H H
J J
ELEVATOR
P-2
UTILITY
S-435
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTH
A
B
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :2
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-105A&B
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IF
T H
F L O O R
P L A N
P A R T
A
B
F P A B
12807030
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIFTH FLOOR PLAN - PART A
A1
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIFTH FLOOR PLAN - PART B
A3
1 INSTALL HOSE MANIFOLD ON THE ROOF OF THE BUILDING (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
CC
CC
BB
BB
AA
AA
M
L
G G
H H
K K
J J
STAIR
BERTHING
UNIT
N-527
BERTHING
UNIT
N-525
BERTHING
UNIT
N-523
BERTHING
UNIT
N-521
BERTHING
UNIT
N-519
BERTHING
UNIT
N-517
BERTHING
UNIT
N-515
BERTHING
UNIT
N-513
BERTHING
UNIT
N-511
BERTHING
UNIT
N-509
BERTHING
UNIT
N-528
BERTHING
UNIT
N-526
BERTHING
UNIT
N-524
BERTHING
UNIT
N-522
BERTHING
UNIT
N-520
BERTHING
UNIT
N-518
BERTHING
UNIT
N-516
BERTHING
UNIT
N-514
BERTHING
UNIT
N-512
LOUNGE
N-510
CORRIDOR
N-533
ELEVATOR
P-1
ELEVATOR
LOBBY
N-534
UTILITY
N-535
STAIR
JAN. CLO
N-536
UTILITY
N-538
BERTHING
UNIT
N-507
BERTHING
UNIT
N-505
BERTHING
UNIT
N-506
RADIO ROOM
N-508
CORRIDOR
N-537
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :3
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-105C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IF
T H
F L O O R
P L A N
P A R T
C
F P C
12807031
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION FIFTH FLOOR PLAN - PART C
A1
1 INSTALL TWO (2) NEW SPRINKLERS UNDER DUCTWORK (SEE DETAIL FP-201)
2 INSTALL CHECK VALVE FOR ZONE CONTROL ASSEMBLY (SEE DETAIL FP-201)
3 EXTEND EXISTING STANDPIPE FOR NEW ROOF MANIFOLD (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
CC
CC
BB
BB
AA
AA
M
L
G G
H H
K K
J J
ELEVATOR
P-1
UTILITY
N-535
FIRE PROTECTION DRAWING KEYNOTES:
0' 1' 2' 4'
SCALE: 1/2" = 1'
0' 2' 4' 8'
SCALE: 1/4" = 1'
0' 16' 32' 64'
SCALE: 1/32" = 1'
0' 8' 16' 32'
SCALE: 1/16" = 1'
0' 4' 8' 16'
SCALE: 1/8" = 1'
NORTHC
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
KEY PLAN
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
As indicated
:3 :3
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-106C
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
R O O F
P L A N
P A R T
C
F P C
12807032
PSM PSM CMA
SCALE: 1/8" = 1'-0"
FIRE PROTECTION ROOF PLAN - PART C
A1
1 PROVIDE HOSE MANIFOLD ON THE ROOF OF THE BUILDING (SEE DETAIL FP-201)
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
12 22
NORTH BUILDING
FIRST FLOOR
1-1/4" OS&Y WITH
TAMPER SWITCH
1-1/4" CHECK VALVE
1/2" BRASS SENSING LINES W/ 3/32" ORIFICE
UNIONS W/ 5'-0 MINIMUM SEPARATION
CONNECT PER NFPA 20
SUCTION LINE
JOCKEY PUMP
PSI RELIEF VALVE
JOCKEY PUMP
CONTROLLER
FIRE PUMP CONTROLLER
1/2" PETCOCK W/ 1/2" PLUG
CONNECT PER NFPA 20 TO
PUMP DISCHARGE CHECK VALVE
1/2" BRASS SENSING LINES W/ 3/32" ORIFICE
UNIONS W/ 5'-0 MINIMUM SEPARATION
PSI GAUGE
1/2" PETCOCK W/ 1/2" PLUG
NEW FLOW METER INLINE WITH FIRE PUMP TEST HEADER
NEW CONTROL VALVE FOR FLOW METER INSTALLATION
NEW PIPING FOR WATER RECIRCULATION THROUGH PUMP
RECONFIGURE SENSING LINES FOR FIRE PUMP AND JOCKEY PUMP
REPLACE THE PACKING FOR THE EXISTING FIRE PUMP ASSEMBLY
EXISTING FIRE PUMP INFORMATION
MANUFACTURER: PATTERSON
MODEL: 5" x 3" VERTICAL INLINE PUMP
RATING: 400 GPM AND 50 PSI
SERIAL NUMBER: FP-C045031
C3
A3A1
KEY NOTES
CONCEPTUAL FIRE PUMP ASSEMBLY DETAIL
N.T.S.SCALE:
FIRE PUMP CONTROLLER SENSING LINE DETAIL
N.T.S.SCALE:
JOCKEY PUMP CONTROLLER SENSING LINE DETAIL
N.T.S.SCALE:
FIRE PUMP TEST HEADER
FDC 3'-0" A.F.G.
EXISTING 8"
FIRE SERVICE
PIV
WATER MOTOR GONG
CHECK VALVE
FIRE PUMP
BYPASS
FLOW METER
6"
6"
6"
4"
6"
4"4"
RECONFIGURE THE EXISTING*
FIRE PUMP SENSING LINES
RECONFIGURE THE EXISTING*
JOCKEY PUMP SENSING LINES
6"
4"
JP
FP
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
:3 :3
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-200
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
F
IR
E
P U M P
R O O M
P L A N
F P
12807033
PSM PSM CMA
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
SCALE:SCALE:
SCALE: SCALE:
SCALE:
SCALE:
SCALE:
TYPICAL ZONE CONTROL VALVE ASSEMBLY DETAIL
NOT TO SCALE
TYPICAL HORIZONTAL DRY SIDEWALL SPRINKLER DETAIL
NOT TO SCALE
B4B2
C2
TYPICAL UPRIGHT SPRINKLER INSTALLATION DETAIL
NOT TO SCALE
TYPICAL PENDENT SPRINKLER INSTALLATION DETAIL
NOT TO SCALE
C1 C4
TYPICAL PENDENT SPRINKLER RETURN BEND DETAIL
NOT TO SCALESCALE:
SCALE:
A2
TYPICAL DRY-PIPE SYSTEM NITROGEN GENERATOR DETAIL
NOT TO SCALE
TYPICAL ROOF MANIFOLD INSTALLATION DETAIL
NOT TO SCALE
A1 TYPICAL CONTROL VALVE FOR STANDPIPE RISER DETAIL
NOT TO SCALE
A4
TYPICAL UPRIGHT AND PENDENT SPRINKLER DETAIL
NOT TO SCALE
B1
BRANCHLINE
SUSPENDED CEILING
1" NIPPLE
RECESSED PENDENT SPRINKLER
1" X 1/2" R.C.
1" 90 EL.
1" X DROP
(SEE PLAN)
1" X ARMOVER
UPRIGHT SPRINKLER
BRANCHLINE
PENDENT SPRINKLER
BRANCHLINE
6" MAXIMUM
CEILING
WALL
THREADED TEE
DRY SIDEWALL SPRINKLER
NEW UPRIGHT
SPRINKLER
EXISTING STRUCTURE
BRANCHLINE
SUSPENDED CEILING
1" NIPPLE
NEW PENDENT SPRINKLER
1" X 1/2" R.C.
1" 90 EL.
1" X DROP
(SEE PLAN)
1" X ARMOVER
1" - 12"
EXISTING DRAIN RISER
EXISTING CONTROL VALVE
WITH TAMPER SWITCH
NEW CHECK VALVE AND RELIEF VALVE FOR EACH
EXISTING FLOW SWITCH
EXISTING TEST AND DRAIN
EXISTING FIRE
DEPARTMENT VALVE
TO SYSTEM
ZONE CONTROL VALVE ASSEMBLY
PROVIDE NEW CHECK VALVE
NEW RELIEF VALVE
PIPED TO EXISTING DRAIN
FROM FIRST FLOOR
SPRINKLER SYSTEM
TO DRY-PIPE SYSTEM
IN MECH ROOM S-008
GENERATOR FOR THE
EXISTING DRY-PIPE SYSTEM
PROVIDE NEW NITROGEN
(300 GALLON CAPACITY).
EXISTING DRY-PIPE VALVE
WITH TRIM ASSEMBLY
ROOF
NEW WATER
PRESSURE GUAGE
NEW 4" X 2-1/2" X 2-1/2"
ROUGH BRASS ROOF
MANIFOLD WITH (2)
2-1/2" HOSE VALVES
WITH CAPS AND CHAIN
STANDPIPE EXPOSED
WILL BE GALVANIZED 2
M
IN
NEW CONTROL VALVE
WITH PIV STEM
EXTEND EXISTING
STANDPIPE RISER
TO PROVIDE NEW ROOF MANIFOLD
EXTEND EXISTING STANDPIPE RISER
EXISTING FEED FOR
STANDPIPE RISER
EXISTING STANDPIPE RISER
NEW CONTROL VALVE
WITH TAMPER SWITCH
NEW FLOW SWITCH
AND FLOW SWITCH FOR EACH
EXISTING STANDPIPE RISER
INSTALL NEW CONTROL VALVE
NITROGEN GENERATOR SHALL
HAVE AN AIR SUPPLY CAPACITY
CAPABLE OF RESTORING
NORMAL AIR PRESSURE IN THE
SYSTEM WITHIN 30 MINUTES.
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
SATISFACTORY TO
APPROVED
ACTIVITY
DATE
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
UNCLASSIFIED
U N C
LA
S S
IF
IE
D
UNCLASSIFIED
D E P A R T M E N T
O F
T H E
N A V Y
N A V A L
F A C
IL
IT
IE
S
E N G
IN
E E R
IN
G
C O M M A N D
S Y M
D E S C R
IP
TI
O N
D
AT
E
AP
P R
DRAWFORM REVISION: 12 APRIL 2018
SYMMES MAINI & McKEE
ASSOCIATES
1000 Massachusetts Avenue Cambridge, Massachusetts 02138 P: 617.547.5400 F: 617.648.4920
F
IL
E
N A M E
L A Y O U T
N A M E
P L O T T E D
U S E R
OF 342
01/10/2020
APPROVED BY
JOHNATHAN JOHNS PM&EB Supervisor with NAVAL BASE, New London, CT
MRI/LEJ
EA
R C M A
P ro je c ts C M A
N A V S U B A S E
N e w
L o n d o n
C T
B ld g
T a s k
D e ta il e d
D e s ig n R E V
IT
D e s ig n F in a l D e s ig n
M o d e l\ C e n tr a l_ F P p m o tt o la .r v t
:3 :3
P M
P R
O
JE
C T
R M
-1
R
E P
A
IR
F A
IL
IN
G
S U
B M
A R
IN
E
A S
C H
O O
L B
Q
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G C
O M
M A
N D
M
ID
A
T L A
N T
IC
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
Y B
AS
E
N E W
LO
N D O N
N E W
LO
N D O N C T
N
AV
S U B
AS
E
P U B
LI
C
W O R K S
D E P
AR
TM
E N T
1600393
FP-201
N40085-20-R-0034
F
IR
E
P R O T E C T
IO
N
D E T A
IL
S
P L A N
F P
12807034
PSM PSM CMA
IS
SU
E
FO
R
C O N
ST
RU
C
TI
O N
| FIRE PROTECTION |
| FP-001 - FIRE PROTECTION NOTES AND SYMBOLS LEGEND |
| FP-002 - FIRE PROTECTION CONCEPTUAL RISER DIAGRAM |
| FP-101A&B - FIRE PROTECTION FIRST FLOOR PLAN -PART A & B |
| FP-101C - FIRE PROTECTION FIRST FLOOR PLAN -PART C |
| FP-101D - FIRE PROTECTION FIRST FLOOR PLAN -PART D |
| FP-102A&B - FIRE PROTECTION SECOND FLOOR PLAN -PART A & B |
| FP-102C - FIRE PROTECTION SECOND FLOOR PLAN -PART C |
| FP-102D - FIRE PROTECTION SECOND FLOOR PLAN -PART D |
| FP-103A&B - FIRE PROTECTION THIRD FLOOR PLAN -PART A & B |
| FP-103C - FIRE PROTECTION THIRD FLOOR PLAN -PART C |
| FP-103D - FIRE PROTECTION THIRD FLOOR PLAN -PART D |
| FP-104A&B - FIRE PROTECTION FOURTH FLOOR PLAN -PART A & B |
| FP-104C - FIRE PROTECTION FOURTH FLOOR PLAN -PART C |
| FP-104D - FIRE PROTECTION FOURTH FLOOR PLAN -PART D |
| FP-105A&B - FIRE PROTECTION FIFTH FLOOR PLAN -PART A & B |
| FP-105C - FIRE PROTECTION FIFTH FLOOR PLAN -PART C |
| FP-106C - FIRE PROTECTION ROOF PLAN -PART C |
| FP-200 - FIRE PROTECTION FIRE PUMP ROOM PLAN |
| FP-201 - FIRE PROTECTION DETAILS PLAN |
2020-02-12T16:23:04-0500
2020-02-12T16:23:20-0500
2020-02-12T16:23:22-0500
20…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .