About this file

N4008518R87160009.pdf

View the file

Other files

File Type Posted
Attachment_F_AMD23.pdf PDF
N4008518R87160023.pdf PDF
N4008518R87160022.pdf PDF
N4008518R87160021.pdf PDF
N4008518R87160020.pdf PDF
N4008518R87160019.pdf PDF
N4008518R87160018.pdf PDF
N4008518R87160017.pdf PDF
N4008518R87160016.pdf PDF
P293_RUBBER_COMPOUNDING_area.dwg DWG drawing
Attachment_F.pdf PDF
N4008518R87160015.pdf PDF
N4008518R87160014.pdf PDF
N4008518R87160013.pdf PDF
N4008518R87160012.pdf PDF
N4008518R87160011.pdf PDF
N4008518R87160010.pdf PDF
N4008518R87160008.pdf PDF
N4008518R87160007.pdf PDF
Site_Visit_Log.pdf PDF
N4008518R87160006.pdf PDF
N4008518R87160005.pdf PDF
JAs_Redacted.pdf PDF
N4008518R87160004.pdf PDF
N4008518R87160003.pdf PDF
Amendment_0002.pdf PDF
SECNAV_5512_DBIDS_Individual.pdf PDF
Amendment_0001.pdf PDF
Local_Visitor_Request_Form.pdf PDF
Attachment_B.pdf PDF
Attachment_C.xls XLS spreadsheet
Attachment_A.docx DOCX document
N4008518R8716.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

P-293 Paint, Blast and Rubber Consolidation Facility, Portsmouth Naval Shipyard, Kittery, ME

The purpose of this amendment is to provide responses to Pre-Proposal Inquiries. The proposal due date of 13 November 2018 remains unchanged. See attached PPI responses.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 2

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 19-Oct-2018

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N4008518R8716

X 9B. DATED (SEE ITEM 11)

31-Aug-2018

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

19-Oct-2018

CODE

NAVFAC MID ATLANTIC

ACQUISITION CORE

9324 VIRGINIA AVENUE

NORFOLK VA 23511-3095

N40085 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

N4008518R8716

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

(End of Summary of Changes)

SOLICITATION NO. N40085‐18‐R‐8716

PROJECT TITLE/LOCATION: P293 Paint, Blast and Rubber Consolidation Facility PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

10/4/2018

11.50.0

1.1

"work cart to run on elevated rails", there is NO pit, so the reclaim floor will be approximately 12‐14 inches above the concrete floor. Elevated rails are to run approximately 12 inches off the floor and support what loads?

The temporary blast booth rail and work cart will all be supported by the the concrete floor in Building 96. The blast booth structural integrity is by the blast booth manufacturer.

10/4/2018

11.50.0

1.1

Work cart to be of the same style and weight and capacity as building 285?

Style is the same capacity is listed in 115002 pg 7 Parag. 3.

10/4/2018

11.50.0

1.1

Only one cart can be loaded at a time, as one cart has to be in the opposite booth to load and unload?

Concur. 9

10/4/2018

11.50.0

1.1

Work carts are to be loaded perpendicular to the elevated rails?

The work will primarily be loaded from the north side of the high bay.

REFERENCE

QUESTION GOVERNMENT RESPONSEDate Received

Posted on Amend No.

July 2011

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

1.1

"Blast booth will have an integrated dust collector on the back wall", is that a stand alone dust collector with vent piping to a cartridge type collector?

This choice is up to the manufacturer.

A cartridge type dust collector could be use or a integrated dust collector on the the back of the booth.

10/4/2018

11.50.0

1.1

"There will be space for a vacuum system if the design requires additional handling", what exactly does that mean, is a vacuum required?

If a cartridge type dust collector is used it will have to fit within the alloted space depicted on Buildding 96, drawing Q‐101, with out impedding workflow to the north.

10/4/2018

11.50.0

2.1.1.2

"wall and ceiling panels ……galvanized steel", These are 3 year lease booths, is it necessary to be galvanized steel? ‐ the interior is lined with rubber, the exterior is clad with sound proofing andexterior skin.

No, painted panel would be acceptable.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

2.1.1.2

"wall and ceiling panels……. 36" x 120" increments", the booth walls are 20 ft. tall and the roof is 25 ft. wide. Can panels be full length and widths to be determined by the manufacturer?

Yes. 9

10/4/2018 11.50.0 2 2.1.1.2

"skin cover with 11 gauge outer skin" can these be painted sheet metal?

Yes. 9

10/4/2018

11.50.0

2.1.1.2A

Should doors be outfitted with E stop outside door? Door shall be fitted with interlocks, see 115002 pg. 7, 2 A.

10/4/2018

11.50.0

2.1.1.2D

Inlet air plenums to be located on the front side walls and exhaust plenums shall be located on the rear wall?

Yes, the the flow through the booth is required to be crossflow at a minimum of 60 fpm.

10/4/2018 11.50.0 2 2.1.1.3

"The cart will travel …….and fully extend feet outside" How many feet outside?

See Building 96, Q‐101. 9

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

2.1.1.5A

"The mechanical or pneumatic conveying system…" Pneumatic reclaim floors are not dependable and are very high maintenance. There are both lease units, with the mfg required to support the equipment with parts and service. Can both the steel and aluminum oxide booths be mechanical reclaim booths?

Yes, mechanical is ok for both booths. 9

10/4/2018

11.50.0

2.1.1.5C

"Elevated equipment shall be accessed…." The air wash separator is a critical component / process for the abrasive and abrasive reclaim system. The air wash requires constant adjustments to achieve proper abrasive cleaning. We suggest the air wash separator to be ground mounted for ease of operator and maintenance personnel. Would the customer consider a ground mounted air wash separator? (a second short bucket elevator would be required ‐ see attached ACM)

Contractor should refer to Q‐101 to determine to space available for media recovery systems. The plan north of the blast booth is reserved for auxiliary equipment. The space between the rails and to the south must be kept clear for product work flow. The contractor can provide alternative systems. The media recovery , filtration, dust collection system must be functional and reliable.

10/4/2018

11.50.0

2.1.1.5F

"transfer the material from the floor to a bucket elevator…", Bucket elevator to have ZERO SPEED indicator attached to the shaft to insure system shuts down when the elevator either stops or jams?

It is the equipment manufacturer's responsibility to ensure the equipment operates safely and with high reliability.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

2.1.1.7

"and explosion hazards…" Dust Kst values have been determined and appropriate prescription of explosion vents, rotary valves, filter selections have been defined?

Yes, the blast booth were not found to have explosive kst values.

10/4/2018

11.50.0

2.1.1.7B

"with cartridge type filters…", Filters to be horizontal or vertical? (Vertical cleans better ‐ horizontal accumulates dust on the top side of dust collector cartridge)

The equipment has to fit in the alotted space shown on Q‐101.

Orientation of filters is up to the manufactuer.

10/4/2018

11.50.0

2.1.1.7B

What is the dust collector air to cloth ratio? The air cloth ratio should be determined by the the blast booth designer. This is dependent on the technology the manufacturer uses.

10/4/2018

11.50.0

2.1.1.7B

30,000 cfm @ what inches of static? The static pressure is within the design of the blast booth and must be determined by the the blast booth designer.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

2.1.1.7B

Diaphragm values to be 1 1/2" with 110 volt solenoids? 9

10/4/2018

11.50.0

2.1.1.7D

"provided with HEPA filters…", HEPA filters to be a separate plenum / module that bolts to thee exhaust of the dust collector blower?

The primary dust collector will discharge to a HEPA filter and then exhaust back to the space.

10/4/2018

11.50.0

2.4.1

"blast system to have 90 degrees cones…", Is this a typo? Normally minimum 60 degrees cones are required.

The 90 degree cones can be thought of as two 45 degree angles. A 60 degree cone would be acceptable as well.

10/4/2018

11.50.0

2.4.1

"1/2" diameter silicon nitride ….nozzle" 2.4.3 indicates 7/16" nozzle. Which is the correct nozzle size?

The 7/16" nozzle is correct. 9

10/4/2018

11.50.0

2.4.4

What is the height of the blast curtains? The curtains are in place to protect wall from ricochet and should cover entire wall.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

2.4.4

What is the durometer of the blast curtains? This is up to blast booth manufacturer recommendations.

10/4/2018

11.50.0

2.4.4

What is the thickness of the blast curtains? This is up to blast booth manufacturer recommendations. Current thickness is 1/2".

10/4/2018

11.50.0

3.3.1

Field NRTL shall be required after equipment has been installed but prior to acceptance testing and training?

Yes. 9

10/4/2018

11.50.0

3.3.1

"start up shall confirm…" Add in feed current to main control panel, no load AMPs of all motors, full load AMPS of all motors, setting fo motor overload limits for each motor?

Agreed "start up shall confirm…" Add in feed current to main control panel, no load AMPs of all motors, full load AMPS of all motors, setting fo motor overload limits for each motor.

10/4/2018

11.50.0

3.7.2

Customer shall conduct all operator checks and services as well as change required replacement parts / consumables as required?

3.7.2 requires the Contractor to provide preventative maintenance. e) excludes consumables.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.50.0

3.7.2

Equipment shall be available for scheduled preventative maintenance events, contractor to advise customer of shutdown date and time, 2 weeks prior to designated date?

Agree, this is a good sentence to add.

Should be 4 weeks instead of 2 weeks.

10/4/2018

11.50.0

3.7.2

ONLY trained operators and maintenance personnel shall be authorized to operate and/ or work on this equipment?

This sentence can be added. 9

10/4/2018

11.30.0

1.2

NFPA 654 is not listed in the reference NFPA documents. Is it not a requirement for these blast booths?

Blast Booth dust analysis kst values were not explosive.

10/4/2018

11.30.0

2.1

"A 3D model shall be provided…." Is this a physical 3 D model or a digital model? What format if a digital model is required?

The model will be digital compatible with REVIT 2017.

10/4/2018

11.30.0

2.1.1

Testing to be done with both blast nozzles operational with or without abrasive being blasted?

Testing will be done with both blast nozzles operational.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.30.0

2.1.1.2

"skin cover with 11 gauge outer skin" can these be painted sheet metal?

Yes. 9

10/4/2018

11.30.0

2.1.1.2

"sound attenuation insulation" Will rockwool be acceptable sound attenuation / insulation material?

"Rockwool" is specified IAW ASTM C612.

10/4/2018

11.30.0

2.1.1.2B

Should doors be outfitted with E stop outside the door? The safety interlock described in 2.1.1.2B will shut down the blast booth when open. E Stop is not required with the door interlock

10/4/2018

11.30.0

2.1.1.2E

Inlet air plenums to be located on the front side walls and exhaust plenums shall be located on the rear wall?

Yes. 9

10/4/2018

11.30.0 2 2.1.1.3

"The cart will travel…. And fully extend feet outside" How many feet outside?

The cart will extend 24 feet outside the booth.

10/4/2018

11.30.0

2.1.1.5

"grating…with a replaceable perforated steel plate…" Perforated steel plate for steel grit or any grit that is using a mechanical reclaim does not require steel perf if a rotary screen is incorporated into the abrasive reclaim system. This is the most cost effective and operationally efficient means of removing large debris from the abrasive. If rotary screens are included can the perf plate requirement be deleted?

Yes. 9

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.30.0

2.1.1.5B

"The reclaim floor shall be immune of plugging…" All pneumatic reclaim systems plug therefore we highly recommend all reclaim systems to be mechanical for all medias ‐ steel, alox, garnet, plastic. This provides for many advantages. 1. consistent productivity, 2. less maintenance costs, 3. opportunity to standardize every component of the reclaim systems. Standard elevator pulleys, gear drives / motors, shafts, bearings, belts, buckets. Standardize screw drives, / motors, stub shafts, end bearings, hanger bearings. Standardize air wash and rotary screens.

The shop believes pneumatic will work well for plastic bead and AlOx.

10/4/2018

11.3

2.1.1.5F

"transfer the material from the floor to a bucket elevator….." Bucket elevator to have ZERO SPEED indicator attached to shaft to insure system shuts down when elevator either stops or jams?

Manufacturer off the blast booth is responsible to protect the equipment and design equipment that will operate safely and reliably.

10/4/2018

11.30.0

2.1.1.7

"and explosion hazards…" Dust Kst values have been determined and appropriate prescription of explosion vents, rotary valves, filter selections have been defined?

Blast Booth dust analysis kst values were not explosive.

10/4/2018

11.30.0

2.1.1.7B

"with cartridge type filters…", Filters to be horizontal or vertical? (Vertical cleans better ‐ horizontal accumulates dust on the top side of dust collector cartridge)

Design of the the dust collector is the manufacturer responsibility. Vertcal filter arrangement is fine.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.03.0

2.1.1.7B

What is the dust collector air to cloth ratio? The air cloth ratio should be determined by the the blast booth designer. This is dependent on the technology the manufacturer uses.

10/4/2018

11.03.0

2.1.1.7B

30,000 cfm @ what inches of static? Fan pressure required is by the blast booth manufacturer.

10/4/2018

11.03.0

2.1.1.7D

"provided with HEPA filters…", HEPA filters to be a separate plenum / module that bolts to the exhaust of the dust collector blower?

The dust collector discharge will discharge to the the HEPA filter inlet plenum. After the HEPA filter the air will discharge to the high bay area.

10/4/2018

11.03.0

2.1.1.8

"rated for hazardous location…" What is the Class and Div rating for these lights?

The lights must be designed for a industrial environment non rated.

10/4/2018

11.30.0 2 2.1.1.12A

"…dust tight seals…" What is the load rating for these covers?

Electrical Enclosures should be NEMA 4X.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.30.0

2.1.1.12A

"…belt guards…" Are these drives belt or gearboxes / motor drives?

Potentially some belt drives depending on manufacturer selection.

10/4/2018

11.30.0 2 2.1.1.12C

"...take top up…" Is a bottom take up also required?

(Suggested)

Defer to manufactuer's recommendation.

10/4/2018

11.30.0

2.1.1.12C

"…elevator housing…" Will also have a 5 inch vent with slide gate?

Manufacturer should incorporate requirement for a vent in to their design.

10/4/2018

11.30.0

2.1.1.12E

"…cross screw shall be…" The cross screw feeds the elevator, is the elevator and separator / blast pots to be located at the front of the booth?

The location of the media recovery and blast pots are shown towards the rear on Q‐102 and Q‐103.

10/4/2018

11.30.0

2.1.1.12E

Cross screw shall be made into two piece to facilitate easy uninstall and install from inside the blast booth?

Yes. 9

10/4/2018

11.30.0

2.1.2

"VFD to ramp up…" Cartridge filters are considered fully loaded at what static?

The location of the media recovery and blast pots are shown towards the rear on Q‐102 and Q‐103.

10/4/2018

11.30.0

2.2.1

"…painting may be 1AW mfg standard practices…" All fabricated steel shall be either galvanized or blasted, primed with a 2 part marine grade epoxy and top coated with a 2 part marine grade polyurethane?

Yes, meeting 11 30 02 2.2.1. 9

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.30.0

2.4.1

"..blast system to have 90 degree cones…" Is this a typo? Normally minimum 60 degree cones are required.

The 90 degree cones can be thought of as two 45 degree angles. A 60 degree cone would be acceptable as well.

10/4/2018

11.30.0

2.4.1

"…1/2" diameter silicon nitride ….nozzle." 2.4.3 indicates 7/16" nozzle. Which is the correct nozzle size?

7/16" nozzles are correct. 9

10/4/2018

11.30.0 2 2.4.4

What is the height of the blast curtains? Blast curtains should cover as much of thethe wall as possible.

10/4/2018

11.30.0 2 2.4.4

What is the durometer of the blast curtains? This is up to blast booth manufacturer recommendations.

10/4/2018

11.30.0

2.4.4

What is the thickness of the blast curtains? This is up to blast booth manufacturer recommendations. Current thickness is 1/2".

10/4/2018

11.30.0 2 2.5.5

How many sets of PPE shall be required? Specify mfg? PPE for Shipyard emplyees is by the government.

10/4/2018

11.30.0

2.5.5

CO monitor alarm to be remotely located in the blast booth to provide a visual and audible alarm?

No CO monitor is reqired. 9

10/4/2018

11.30.0

3.3.2

"…start up shall confirm.." Add in feed current to maintain control panel, no load AMPs of all motors, full load AMPs of all motors, setting of motor overload limits for each motor?

Agreed "start up shall confirm…" Add in feed current to main control panel, no load AMPs of all motors, full load AMPS of all motors, setting of motor overload limits for each motor.

10/4/2018

11.30.0

3.5.2

Upon conclusion of training with a documented and proven start up, shall the operating and shutdown procedures be laminated and posted on the equipment?

Placard can be posted when system is ready for test.

10/4/2018

11.30.0

1.2

NFPA 654 is not listed in the reference NFPA documents. Is it not a requirement for these blast areas?

Blast Booth dust analysis kst values were not explosive.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11.30.0

2.1

Black Beauty is not considered a recyclable media.

Including this in the new blast system will reduce the life of the dust collector filters and cause filters to load quicker. Is there another media that is an acceptable substitute, i.e. garnet, olivine?

PNS is phasing out the use of Black Beauty , it it may still be used sporatically.

10/4/2018

11.30.0

2.1

"A 3D model shall be provided…." Is this a physical 3D model or a digital model? What format if a digital model is required?

The model must be compatible with

REVIT 2017.

10/4/2018

11.30.0

2.1.1

What are the required safety interlocks and intrinsically safe requirements for operating in the paint mode?

During paint operations the space is Class I Div I and all electrical circuit must be explosion proof.

10/4/2018

11.30.0

2.1.1

Both areas, VLP and Shaft have large floor surface areas. Is there a reason not to include a partial reclaim floor, i.e. "H" or "U" type?

Grating is not acceptable for reclaim. 9

10/4/2018

11.30.0

2.1.1

Vacuum systems are appropriate for spaces that are hard to recover abrasive, ship hulls, tank cars, etc. Using a vacuum as a supplemental system is preferred.

Equally important is to be able to conveniently operate and maintain this vacuum system. Can the vacuum system be ground mounted and discharge into an elevator that will transfer the abrasive to a storage hopper?

We are space limited and the vacuum needs to stay on the equipment platform.

10/4/2018

11.30.0

2.1.1

Can the reclaim systems for both the VLP and Shaft be similar to the other blast booths, with the addition of a vacuum system?

No. Grating is not acceptable. 9

10/4/2018 11.30.0 4 2.1.1

All elevators to be outfitted with electro / mechanical brakes?

Yes. 9

10/4/2018

11.30.0

2.1.1.1e

Would it be beneficial to have a Rotary screen before the air wash separator to extract the large debris?

A rotary screen can be used, provided it fits into the footprint shown on the Q drawing.

10/4/2018

11.30.0

2.1.1.1f

"blast system to have 90 degree cones…" Is this a typo?

Normally a minimum 60 degree cones are required

The 90 degree cones can be thought of as two 45 degree angles. A 60 degree cone would be acceptable as well.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018 11.30.0 4 2.1.1.1f

"blaster….(4) 110 volt twinline". Is that 4 hoses complete per two outlet pots?

Two blast pot with two hoses for a total of 4 blasters.

10/4/2018

11.30.0

2.1.1.1f

"self metering microvalve abrasive metering valves" I thought all metering valves were to be Thompson II?

Metering valves to be Thompson II Valve ® (or equivalent).

10/4/2018

11.30.0 4 2.5

"enter text here…" What is required from the contractor?

Section 2.5 will be deleted, testing is covered under 3.3.

10/4/2018

11.30.0 4 2.5

Equipment to be NRTL certified after installation? NRTL required prior to acceptance testing.

10/4/2018

11.30.0

3.3.1

"start up shall confirm…" Add in feed current to main control panel, no load AMPs of all motors, full load AMPS of all motors, setting fo motor overload limits for each motor?

Agreed "start up shall confirm…" Add in feed current to main control panel, no load AMPs of all motors, full load AMPS of all motors, setting fo motor overload limits for each motor.

10/4/2018

11.30.0

3.5.2

Upon conclusion of training with a documented and proven start up, shall the operating and shutdown procedures be laminated and posted on the equipment?

Placard can be posted when system is ready for test.

10/4/2018

11.50.0

1.9

ONLY new equipment shall be warranted by the contractor, previously mentioned uninstalled and reinstalled equipment has no warranty.

Concur. 9

10/4/2018

11.50.0

1.3.2 all the equipment being moved shall be inspected and tested, a written report of each machine shall be submitted for record. After the equipment has been relocated, a new inspect and test report shall be generated. Equipment must meet the original inspect and test report results. Any items that are not operational or require repair shall be wither noted and / or replaced ‐ repaired?

Any items that are not operational prior to being moved should be noted.

Any items operational prior to the move and not operational after the move shall be repaired.

10/4/2018 11.50.0 3 table 1

Powder Coat Booth electrics ‐ AMPs? See Drawing 12775940 E‐101A for electrical connections.

10/4/2018 11.50.0 3 table 1 glove blaster electrics ‐ AMPs? See Drawing 12775940 E‐101A for electrical connections.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018 11.50.0 3 table 1

All lockers shall be empty? Yes, lockers will be empty. 9

10/4/2018

11.50.0

3.4.e

Certified fire suppression contractor to inspect and test system before uninstalling and inspect and test after relocating to building 96?

No. The Contractor shall disconnect the powder coat booth fire suppression piping system for transport from Building 285 to Building 96. The wet pipe sprinkler system will be reconnected per Building 96 drawing FP‐101.

10/4/2018

11.50.0 3 3.2.1 equipment to be NRTL field certified before testing? Yes. 9

10/4/2018

11.50.0

3.3 contractor to review with operators and maintenance persons complete OEM manuals, spare parts listing as well as generate a SOP for start up, operate and shutdown ‐ processes to be laminated and posted on each machine?

No. "The Contractor working with the government representatives shall perform initial startup and checkout of the Temporary Powder Coat System." This is an existing system, (with the exception of a new curing oven) that will be moved from Building 285 to Building 96. The intent of this is that the contractor will have a electrician and Millwright on hand during startup of the relocated equipment to resolve problems that may arise

10/4/2018

11 40 table1

Tag 187 Max size product shall be 10 ft long booth is 120" , needs to be 6" longer?, max size product shall be 8 ft high booth is 78 needs to be 10 " longer?

Product sizes are nominal , Oven size is correct.

10/4/2018

11 40

JJ

No forklift pockets are required ‐ unit to be moved by lifting under the oven floor?

Equipment should be lifted per manufacturer's recommendations.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/4/2018

11 30 table 1

Propane fuel curing oven to be what size? The fuel has been changed to natural gas supplied by the government, piped up by the contractor.

10/4/2018

11 30 table 1 propane shall be provided by whom? The fuel has been changed to natural gas supplied by the government, piped up by the contractor.

10/4/2018

11 30 cc.b

12' wide x 8ft opening? With two monorails in the oven?

See Q‐103; the cure oven has two rails and the powder coat booth has one.

10/4/2018

11 30 cc.b do monorails extend out of the oven? What is the distance between monorails?

Yes, refer to drawing Q‐103 for representation of powder manual shuttle system rails.

10/4/2018 Drawing E‐503 building 60, Communication Riser states to reroute fiber optic cable to new telco room 116. It is unclear if there is sufficient cable to make the transition can this cable be spliced to add the needed length if not we would need to replace the cable back to source. Can this cable be spliced?

Existing cable has sufficient length to reach new telcom room without splicing.

10/4/2018 Referencing Drawing “Volume 3, EP‐101 North Area First Floor Power Plan” Please provide specifications on Bus Duct and Bus Duct Plugs.

See spec section 26 20 00 of Amendment 6 dated 10/1/2018 for spec on bus duct.

10/4/2018 FROM PAINT BOOTH SUPPLIER: RE: Section 11‐20‐04, Tag # 17 & 18. This piece of equipment is called a sanding, grinding and paint booth. We are concerned and need to be sure that the grinding mode will not cause sparks. If there would be still wet paint or primer in the filters and then a spark was introduced to this filter media, and explosion and fire would be imminent.

Please confirm there will be zero chance of sparks created in these booths.

Sanding and painting will not take place at the same time. The sanding is for fiberglass parts. There should be no metal grinding in the fiberglass booth.

PNSY, Kittery, ME

PREAWARD INQUIRY FORM (TEMPLATE)

Page Section Para.

QUESTION GOVERNMENT RESPONSEDate Received

10/5/2018 23 00

Per B404b drawing number 12776225 page M‐720 and dwg# 12776203 page M‐602, please confirm if AHU‐5 and AHU‐6 cabinets are to be explosion proof construction, not just the fans and motors.

The air handler cabinets (5 and 6) are not required to have explosion proof construction. Electrical components such as actuators would be mounted in explosion proof boxes. Lighting, wiring and any control devices such as transmitters and switches would be wired according to Class 1 Division 1 requirements.

10/5/2018 23 00

Per B404b drawing number 12776225 page M‐720 and dwg# 12776203 page M‐602, please clarify AHU curb design requirements and which AHUs are to have curbs.

AHU‐5 and AHU‐6 are located on a raised platform with no roof curb. All other air handlers shall have 18 inch high roof curbs.

10/5/2018 23 00

Per B404b drawing number 12776225 page M‐720 and dwg# 12776203 page M‐602, AHU‐4 specifies a seismic and wind rated curb, are other curbs expected to meet the same requirements?

All roof curbs are expected to meet the wind rating. No roof curbs are required to meet the seismic rating.

10/8/2018 Drawing EP‐101 in the areas marked as Class 1 Division 1 Explosion proof there are receptacles and they are not noted as XP. Are these to be Explosion proof receptacles in these areas? If so is there a specification for these devices?

Per note 4 of Electrical Code Reference Plans E‐101 thru E‐103 all equipment and devices installed in classified areas shall be rated for the space. See spec 26 20 00 "HAZARDOUS LOCATIONS" paragraph for requirements.

Amendment 0009 Text