VA
3 3 3 3 3
A A
F1
NH 2 3
3 3 3
NH00 NH00 NH00
NK1
DISCONNECTING WEB F1
NH 2 3
3 3 3
NH00 NH00 NH00
NK6
DISCONNECTING WEBF1
NH 2 3
F2
F1
NH 2 3
3 3 3
F3
NH00
F4
NH00 NH00
NK1
L1,L2,L3,PEN 230/400V, 400A, 50Hz, 0.5kA
DISCONNECTING WEB F1
NH 2 3
R E
S E
R V
E
F2
F1
NH 2 3
3 3 3
F3
NH00
F4
NH00 NH00
NK1
DISCONNECTING WEB F1
NH 2 3
AS SHOWN
DIRK KELLAR, SAFETY DIRECTOR, JMTC
BULBOACA TRAINING AREA
MOLDOVA ARMY TRAINING AREA
CONCEPT DESIGN: 25.06.2013
25. JUNE 2013
V
A
A
A
A
A
A
A
R e s e r v e
R e s e r v e
N Y
M J x q m m
N Y
M J x q m m
150/5A
160A
R e s e r v e
3 3 3 3
25-40
AAA
40-63
8kVar
16-25 A
N H
A
FI 25/0.03A
40-63 A
NH00
16A
N K
T A
R G
E T
R Y
N E
W
R A
N G
E
T O
W E
R
N K
NK3
NK4 NYY 5x10 qmm
NK5 NYY 5x16 qmm
P1-1 - P1-10
P2-1 - P2-10
P3-1 - P3-10
NYY 5x10 qmm
F2 F3 F4
NOT TO SCALE
302 302 302 302
N Y x q m m
N Y
M J x q m m
80-125
NYY 5x95 qmm NYY 5x70 qmm
LVPP1
LVPP2 LVPP3
LVPP4
DATA OUT (IF REQUIRED)
DATA IN
CJB SIDE VIEW
BOLT M5 x 30
HINGE
CJB TOP VIEW
SEPARATION TERMINALS
NOTES / ANMERKUNGEN :
2. SECURE GROUND WIRE TO BOX UNDER AT EXTERIOR BOLT, M8.
4. ALL CABLE LEAD-IN TO BE WATER TIGHT, IN STEEL.
6. THE INSTALLATION CARRIER MUST BE EQUPPED WITH FOUR BOLTS M5 X 30MM FOR LATER
STEEL SUPPORTS, WIDTH 40MM, WITH HOLE FOR MOUNTING TO GROUND
SLOPE OF THE BOX APPR. 1:10
CABLE AT THE POINT OF ENTRANCE.
1. ENCLOSURE SHALL BE HIGH-GRADE STEEL, DIMENSIONS: 500mm x 4OOmm x 210mm.
7. MOUNTING OF THE BOX AT CONCRETE BASE - BOX EQUIPPED WITH FOUR HIGH GRADE
ALL OPENINGS WITHOUT CABLES MUST BE CLOSED WITH PLASTIC BLIND STOPPER
TO BE WATER TIGHT.
OF THE CARRIER TO ALLOW THE INSTALLATION OF THE TREADED BOLTS M5 X 30MM (PARAGRAPH 6).
8. DATACABLES MUST BE GROUNDED AT THE CJB CASING
9. ALL CABLE PIGTAILS WILL BE TAGGED WITH PERMANENT TAGS ATTACHED TO THE
IP 66, NEMA 4X
3. DOOR HINGES MOUNTED LEFT, RESPECTIVELY RIGHT SIDE, DEPENDING ON THE LOCATION OF THE BOX AT
THE TARGET EMPLACEMENT
5. INSTALLATION CARRIER MUST BE INSTALLED AT BOLTS AND EQUIPPED WITH 20 SEPARATION
MOUNTING AT CONCRETE WALL AT NEW SAT AND MIT TARGETS
TERMINALS, MOUNTED AT A CARRIER RAIL. NOTICE MINIMUM SIZE
INSTALLATION OF AN ADDITIONAL CARRIER FOR ELECTRONIC EQUIPMENT.
CONTROL CABLE TO TARGET
DATA
DATEN
SCALE 1 : 10
BOLT M8
BOLT M8
CABLE JUNCTION BOX - NEW PERSONNEL TARGETS
FIELD 01
L1, L2, L3, PEN, 10 kV, 50 Hz
10A
100kVA
400V
NYY 5x16 qmm
NYY 5x95 qmm
NYY 5x16 qmm
TRANSFORMER STATION 1 (TR1), NEW
TYPICAL DETAIL CABLE TRENCH
SCALE 1 : 10
L1/L2/L3/N/PE, 230/400V, 50 Hz
L1/L2/L3/N/PE
TM 100/10 kV
PT 100/0,4 kV
A
200/5A
TK-20
L1/L1/L3/PEN
250 A
BH 250-32
Wh Warh
3 NH2 200A
N Y
Y x q m
LEA 10 kV, PDC
CUT-OUT OPN - 10
NYY 5x70 qmm
L1,L2,L3,N,PE 230/400V, 400A, 50Hz, 0.5kAL1,L2,L3,N,PE 230/400V, 400A, 50Hz, 0.5kA
F2
NH00
F3 F4 F5
L1,L2,L3,N,PE 230/400V, 400A, 50Hz, 0.5kA
NYY 5x16 qmmNK6
NK7
NK8
NYY 5x10 qmm
NYY 5x10 qmm
NK12
NK10
NK11
V6
NK9
NK13
MAST SECTOR 112/88-112/92
Cimiseni 35/10kV, F-10, CONNECTION POINT: LEA-10kV, SE-49
FROM THE CONNECTING MAST ON WHITCH THE CUT-OUT SEPERATOR WILL BE MOUNTED
TYPE AND CROSS SECTION ACCORDING TO SPECIFICATION,
OR LES 10kV: DESIGN A DERIVATIVE TO THE TRANSFORMER POINT BY AN UNDERGROUND CABLE, WIRES (AC) WITH A CROSS SECTION NOT SMALLER THAN 70mm;
HIGH VOLTAGE SF-20 PORCELAIN INSULATORS;
LEA 10 kV: SHOULD FORESEEN REINFORCED CONCRETE MAST WITH A SIMPLE CIRCUIT;
PRE FINAL DESIGN: 30.08.2013
C16A
1 2 3
T
400/230V, 50Hz, 3P/N/PE
400/230V
C16A C16A
N Y
M J q
N
M J q
UV TARGET NO.X
40/0,03A
GROUND FAULT CURRENT SWITCH
F1 F2 F3
TARGET PITS AND LIMIT MARKERS
LOW VOLTAGE POWER PANEL FOR
SCHEMATIC LOW VOLTAGE DISTRIBUTION LVPP1-4
CONNECTING TRANSFORMER STATION
SINGLE WIRE ELECTRICAL DRAWING
CONNECTION POINT FOR NEW SHOOTING RANGE
LV TR1
WARNING RIBBON
GROUNDING STRAP
SAND
HIGH VOLTAGE CABLES
EMTY CONDUIT SYSTEM FOR FIBER OPTIC
DETAIL NR. 2
DETAIL NR. 1
DATA CABLE
SAND
LOW VOLTAGE CABLE
EMTY CONDUIT SYSTEM FOR FIBER OPTIC
WARNING RIBBON
CABLE PROTECTION
CABLE PROTECTION
V4 + V5
P5-1 - P5-4
P6-1 - P6-5
25 A 25 25 A 25 A 25 A 25 A 25 A 25 A 25 A 25 A 25 A 25 A 25 A
P7-1 - P7-6, M1 - M5, LM1
P4.6 - P4.10, M6-M9, LM2
FINAL DESIGN: 03.12.2013
NYY 5x16 qmm
NYY 5x16 qmm
LM3
V1-V3, LM4
R E
S E
R V
E
R E
S E
R V
E
DISTRIBUTION LV TR1
SCHEMATIC LOW VOLTAGE
GRAVELL-SHAPE, CONCRETE
GRAVEL
TIMBER 25/15
SCALE 1 : 10
LVPP1 - LVPP4
PROTECTION AGAINST DIRECT FIRE FOR LOW VOLTAGE POWER PANEL
LOW VOLTAGE POWER PANEL
SIDE VIEW
TOP VIEW
UPGRADE MULTI PURPOSE RANGE
RANGE 3
Electrical Connections, Transformer Station and Power Panels, 900 m
13. Feb 20141 DELETION OF ELECTRICAL SYSTEM 300 M RANGE HELMUT SCHWINDL