This package includes construction documents for a plumbing renovation project at a Veterans Affairs nuclear medicine facility. The documents provide specifications, drawings, notes and details for replacing an existing PET CT system and renovating approximately 1,200 square feet of space. Work includes demolishing old plumbing systems, installing new domestic water, sanitary waste and vent piping, and connecting to existing medical gas systems. The project will also update interstitial plumbing in pipe chases and connect a new steam dispersion unit. Construction must follow all noted code requirements and firestopping details.
The related federal contract opportunity is a solicitation from the VA Veterans Health Administration VISN 22 to fully renovate the nuclear medicine space per the provided scope of work, specifications and drawings. Offerors are to price the required plumbing construction and systems installation.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES PLUMBING LEGEND PLUMBING SHEET INDEX
1. CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO SUBMITTAL OF BID, FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND DETAILS OF THE WORK, VERIFY DIMENSIONS IN THE FIELD AND ADVISE THE ARCHITECT AND ENGINEER OF ANY DISCREPANCY. SUBMITTAL OF BID WILL VERIFY THAT THE CONTRACTOR
HAS VISITED THE SITE.
2. BEFORE COMMENCEMENT OF WORK, THE CONTRACTOR SHALL VERIFY EXACT LOCATIONS, ELEVATIONS, DEPTH, CHARACTERISTICS, AND SIZE OF ALL PIPING
TO WHICH CONNECTIONS ARE REQUIRED AT CONTRACTOR'S EXPENSE. CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER OF ANY DISCREPANCIES.
FINAL CONNECTIONS TO EXISTING UTILITIES SHALL BE BY THIS CONTRACTOR.
3. PLUMBING QUALITY AND WEIGHTS OF MATERIALS, AND ALTERNATE METHODS OF CONSTRUCTION SHALL CONFORM TO INTERNATIONAL PLUMBING CODE.
4. CONTRACTOR SHALL COORDINATE ALL WORK SHOWN ON THESE DRAWINGS AND SPECIFICATIONS WITH ALL DISCIPLINES AND TRADES PRIOR TO SUBMITTAL OF
BID AND INSTALLATION OF SYSTEM. PLUMBING WORK SHALL AVOID INTERFERENCE WITH OTHER TRADE.
5. ANY DEVIATIONS FROM THE DRAWINGS OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER PRIOR TO
INSTALLATION.
6. ALL PLUMBING FIXTURE LOCATIONS (WATER CLOSETS, LAVATORIES ETC.) ARE DIAGRAMMATIC AND CONTRACTOR SHALL REFER TO ARCHITECTURAL
DRAWINGS FOR HANDICAP FIXTURES, EXACT LOCATIONS, MOUNTING HEIGHTS, AND COLOR.
7. TRAP PRIMERS FOR FLOOR DRAINS AND FLOOR SINKS AND WATER HAMMER ARRESTORS TO BE INSTALLED AS PER THE 2016 IPC AND THE LATEST EDITION OF
THE AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE 1010) SIZING AND INSTALLATION REQUIREMENTS.
8. CONTRACTOR TO REFER TO PLUMBING FIXTURE SCHEDULE FOR INDIVIDUAL ROUGH-IN CONNECTIONS AT EACH PLUMBING FIXTURE.
9. STEEL PLATE SUPPORTS FOR ALL WALL FIXTURES: SUPPORT WITH 3/8" THICK x 8" HIGH STEEL PLATES RECESSED AND BOLTED TO STUDS AND TAPPED FOR
FIXTURE BOLTS. LENGTH OF PLATE AT LEAST ON STUD BEYOND FIXTURE, UNLESS CARRIERS ARE SPECIFIED.
10. ALL INDIRECT WASTE PIPING ON ROOF SHALL BE SUPPORTED BY 14 GAGE GALVANIZED CHANNEL WITH PIPE CLAMPS ATTACHED TO 100% RECYCLED RUBBER
TIRE, UV RESISTANT. PIPING SHALL BE SLOPED TO AND TERMINATED AT AN APPROVED RECEPTOR. CONDENSATE PIPING SHALL SLOPE OF NOT LESS THAN 1%.
11. ALL CLEANOUTS SHALL BE INSTALLED WHERE READILY ACCESSIBLE AND LOCATED AS PER CODE REQUIREMENTS. THE CONTRACTOR SHALL COORDINATE ALL
CLEAN OUT LOCATIONS WITH EQUIPMENT, CABINETS, ETC., AND THE ARCHITECT PRIOR TO ANY INSTALLATION. PROVIDE WALL CLEANOUT ON ALL VENT FROM
BELOW GRADE, AND FOR ALL SINKS AND URINALS.
12. ALL PLUMBING FIXTURE VENTS TO TERMINATE A MINIMUM OF 12 INCHES FROM ANY VERTICAL SURFACE AND 10 FEET FROM ANY OUTSIDE AIR INTAKES.
13. ALL PIPING DISCHARGING INTO SERVICE SINKS AND/OR FLOOR SINKS TO HAVE A MINIMUM AIRGAP AS REQUIRED BY 2019 IPC.
14. ALL VALVES, UNIONS, ETC. TO BE SAME SIZE AS PIPE SIZE UNLESS OTHERWISE INDICATED ON DRAWINGS.
15. UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH SCREW-TYPE VALVE AND PRIOR TO EQUIPMENT CONNECTIONS.
16. ALL EQUIPMENT SHALL BE LATERALLY SUPPORTED IN ALL DIRECTIONS TO RESIST HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION.
17. NO PIPING SHALL BE DIRECTLY EMBEDDED IN CONCRETE OR MASONRY WALLS OR FOOTING.
18. ALL WASTE AND VENT PIPING SHALL SLOPE TO UNIFORM GRADE OF NOT LESS THAN 2%.
19. ALL VALVES, TRAP PRIMERS, WATER HAMMER ARRESTORS OR OTHER EQUIPMENT SHOWN IN WALLS OR ABOVE NON-ACCESSIBLE CEILINGS SHALL BE
INSTALLED BEHIND AN ACCESS PANEL.
20. ALL HORIZONTAL PIPING LINES EXTENDED AND CONNECTED TO EQUIPMENT SHALL RUN AT THE HIGHEST POSSIBLE ELEVATIONS AND NOT LESS THAN 6" ABOVE
THE FLOOR TO PROVIDE CLEARANCE FOR CLEANING. AT WALL OR COLUMN LOCATIONS, PIPING ROUGH-IN SHALL BE STUBBED IN WALLS WHENEVER POSSIBLE.
21. CONNECTION BETWEEN INCOMPATIBLE PIPE MATERIALS ABOVE GRADE AND INSIDE BUILDING SHALL BE MADE WITH (2) DIELECTRIC UNIONS SEPARATED BY A
TWELVE INCH (12") LONG SECTION OF RED BRASS PIPE.
22. CONTRACTOR SHALL PROVIDE THE OWNER WITH ALL THE LITERATURE AND INSTRUCTIONS PROVIDED BY THE MANUFACTURER DESCRIBING OPERATIONS AND
MAINTENANCE OF ANY EQUIPMENT AND DEVICES INSTALLED.
23. PIPING THROUGH FIRE RATED WALLS SHALL BE PER U.L. FIRE RESISTANCE SYSTEM. SEE ARCHITECTURAL PLANS FOR ALL WALL LOCATIONS.
24.
PENETRATIONS OF PIPES, CONDUITS, ETC. IN WALLS, FLOORS OR CEILING ASSEMBLIES REQUIRING PROTECTED OPENINGS SHALL BE A TESTED ASSEMBLY.25.
MOUNTING HEIGHTS FOR HANDICAPPED FIXTURES TO COMPLY WITH ADA REQUIREMENTS.26.
PROVIDE CLEANOUTS AT END OF ALL HORIZONTAL RUNS, CHANGE OF DIRECTION EXCEEDING 45 DEGREES AND NEAR THE BASE OF EACH VERTICAL WASTE OR
SOIL STACK.
27.
CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER SUPPLIED APPLIANCES.28.
ALL REQUIRED CLEANOUTS SHALL BE INSTALLED PER CHAPTER 7 OF THE INTERNATIONAL PLUMBING CODE.29.
WATER PIPE AND FITTING WITH A LEAD CONTENT WHICH EXCEEDS 8% SHALL BE PROHIBITED IN SYSTEMS CONVEYING POTABLE WATER.30.
THE PRESSURE REGULATING VALVE (PRV) SHALL BE INSTALLED ABOVE GRADE OR FINISHED FLOOR. THE PRV SHALL NOT BE INSTALLED IN A PIT WHERE IT CAN
BECOME SUBMERGED IN WATER.
31.
THE REDUCED PRESSURE BACK FLOW DEVICE (BFP) SHALL BE INSTALLED AT LEAST 12 INCHES ABOVE GRADE OR FINISHED FLOOR. THE BFB SHALL NOT BE
INSTALLED IN A PIT WHERE IT CAN BECOME SUBMERGED IN WATER.
32.
THE CLEANOUTS FOR HORIZONTAL BUILDING STORM DRAINS SHALL COMPLY WITH THE REQUIREMENT OF SECTION 708 OF THE CURRENT INTERNATIONAL
PLUMBING CODE.
33.
NEW OR REPAIRED POTABLE WATER SYSTEMS ARE REQUIRED TO BE DISINFECTED BY CHLORINATION. 2019 IPC SECTION 610.
35. BACTERIOLOGICAL TESTING OF POTABLE WATER SYSTEM REQUIRED TO BE PERFORMED BY AN INDEPENDENT THIRD PARTY TESTING LABORATORY, 2019 IPC
SEC. 610(4).
I.E. INVERT ELEVATION
AMERICANS WITH DISABILITIES ACT
DN
UP
SOV
ADA
BALL VALVE
PIPE DOWN
PIPE RISE
FCO
WCO
POC
V
FLOOR CLEANOUT
WALL CLEANOUT
POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK
SANITARY VENT
(E)
SYMBOL
HOT WATER RETURN
HW
HWR
(E)
CW
ABBREVIATION
HOT WATER
DESCRIPTION
COLD WATER
EXISTING
HB HOSE BIBB
PL-001 GENERAL NOTES, LEGEND, SCHEDULES & ABBREVIATIONS
SHEET NUMBER SHEET NAME
FOURTH FLOOR DEMO. PLAN - PLUMBING
MA
O
MV
MA
MV MEDICAL VACUUM
MEDICAL AIR
PL-101
PL-301 LEVEL 4 INTERSTITIAL - ENLARGED REMODEL B
LPS
MPS
LPS
MPS
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
S OR W
SOIL OR WASTE BELOW FLOOR OR GRADE
SOIL OR WASTE ABOVE FLOOR
S OR W
LPR
MPR
LPR
MPR
LOW PRESS STEAM RETURN
MEDIUM PRESS STEAM RETURN
TP
CD
TP
CD
TRAP PRIMER
CONDENSATE DRAIN
ICW ICW INDUSTRIAL COLD WATER
CA CA COMPRESSED AIR
FOURTH FLOOR PLAN - PLUMBING PART 1PL-102
POD LIMIT OF DEMOLITION
TYP. TYPICAL
O OXYGEN
FOURTH INTERSTITIAL - PLUMBING REMODELPL-102-2
PL-501 PLUMBING DETAILS
MGA MEDICAL GAS ALARM
MGO MEDICAL GAS OUTLET
ZV ZONE VALVE
STOP VALVES SHALL BE PROVIDED AT ALL FIXTURES TO ENABLE REGULATION OF FLOW AND SHUT-DOWN OF SUPPLY TO FIXTURE.
34.
FOURTH FLOOR PLAN - PLUMBING PART 2PL-102.1
MATERIAL SCHEDULE
PLUMBING FIXTURE AND EQUIPMENT SCHEDULE
TP
FS
SERVICE MATERIALS
CAST IRON SOIL PIPE WITH NO-HUB FITTINGS ABOVE GRADE AND BELOW GRADE.
PROVIDE HEAVY DUTY 4-BAND STAINLESS STEEL COUPLING FOR ALL ABOVE AND
BELOW GRADE PIPING.
TYPE "L" HARD DRAWN COPPER TUBING ASTM B88, WITH WROUGHT COPPER SWEAT
FITTINGS ANSI B16.22. LEAD FREE SOLDER.
SEAMLESS COPPER TUBE TYPE "L" HARD DRAWN CONFORMS TO ASTM B819 "OXYGEN
CLEANED" WITH BRAZED JOINTS AND FITTINGS
BLACK STEEL SCHEDULE 80 PIPE & FITTINGSSTEAM AND CONDENSATE
RETURN
MEDICAL GASES
SOIL, WASTE AND VENT
DOMESTIC WATER
TRAP
PRIMER
PRECISION PLUMBING PRODUCT MODEL PR-500 PROVIDE WITH 1/2" COPPER PIPE PRIMER CONNECTION TO FLOOR SINK.1/2"- - - -
FLOOR
SINK
ZURN NO.Z1901-NH-2-P, 12"x12" WITH 8"SUMP DEPTH, CAST IRON, COMPLETE WITH ACID-RESISTING ENAMELED INSIDE, NICKEL BRONZE HEELPROOF HALF GRATE WITH 1/4" SQUARE OPENINGS, ALUMINUM DOME STRAINER, TRAP PRIMER CONNECTION AND P-TRAP-3" 2" -
W A
T E
R
V E
N T
C O
LD
T R
A P
W A
S T
E
DESCRIPTION
ROUGH-IN CONNECTIONS
FIXTUREITEM
S O
IL
O
R
H O
T
S
SINK 2" - 1-1/2" 1/2" 1/2"
JUST COUNTER-MOUNTED STAINLESS STEEL HAND SINK MODEL No. SL-ADA-17519-A-GR, 18 GAUGE STAINLESS STEEL, POLISHED WITH STANDARD BRUSH FINISH. ADA COMPLIANT. PROVIDE WITH JUST JSGN-6-B, BATTERY OPERATED SENSOR FAUCET WITH LAMINAR FLOW CONTROL, JTMLF-47 THERMOSTATIC MIXING VALVE, LOW LEAD CERTIFIED PROVIDE J-ADA-115-FS FLAT GRID DRAIN WITH OVERFLOW, JT-125 CAST BRASS P-TRAP. DRAIN PUNCHED FOR JUST J-ADA-115-FS LAVATORY DRAIN. THE FAUCET IS EQUIPPED WITH CONTROL CIRCUIT SOLENOID, BATTERY SOLENOID VALVE, WALL MOUNTED CONTROL BOX WITH (4) AA ALKALINE BATTERIES
W A
T E
R
HB
HOSE
BIBB
3/4"- - - - ACORN MODEL 8126-LF WITH INTEGRAL VACUUM BREAKER
1/2"
ZV
ZONE
VALVE
BOX
-- - - - 3/4"
MGA
MEDICAL
GAS
ALARM
MGO
MEDICAL
GAS
OUTLET
-- - - - 3/4"
A
IR
M E
D
IC
A L
M E
D
IC
A L
V A
C U
U M
O X
Y G
E N
1/2"
1/2"
1/2" 1/2"
BEACON MEDAES TOTAL ALERT INFINITY T3-A10-OAX MEDICAL GAS NOTIFICATION SYSTEM, PROVIDES AREA ALARM SIGNAL AS REQUIRED BY LATEST EDITION OF NFPA 99, ALARM IS U.L. LISTED TO UL 1069 AND CSA C22.2 NO.205 SIGNAL
EQUIPMENT 120V/60HZ/1PH. MATCH EXISTING MED. GAS ALARM MANUFACTURER.
MEDICAL GAS CEILING COLUMN AMICO ALERT-1, MODEL # C-COL-RIGID-36-ADV, AIR, OXYGEN VACUUM, RIGID COLUMN, 12"x12" SQ.
COLUMN WITH STAINLESS STEEL SHROUD, 16 GAUGE TYPE 304 SS. UNIT COMPLY WITH NFPA 99 CURRENT EDITION, NEC, CSA & CEC.
OPTG WT. 125 lbs.
BEACON MEDAES SERIES ZVB3-AAB-ENG 4107219445 VALVES SHALL BE FULL PORT, DOUBLE SEAL, BALL TYPE WITH 3-PIECE BRONZE/BRASS BODY AND CHROME PLATED BRASS BALL VALVE. PROVIDE WITH 4107655177, (VAC), 4107655178 (A, 02) GAUGES AND 4107401625 SENSOR. PROVIDE KIT FOR ZONE VALVE BOX SENSOR ASSX 410740167562, 4107401677(A), 4107401678(V).
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:2
P
M
PL-001
GENERAL NOTES, LEGEND, SCHEDULES &
ABBREVIATIONS
12/04/2020 RPM JPRevisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
ISSUED FOR CONSTRUCTION 2020-11-06
ISSUED FOR CONSTRUCTION 2020-12-04
SCAN
EXAM RM
NUCMED
ALCOVE
CORRIDOR
TOILET
4070B
RECEPTION
GAMMA
WELL
COUNTER
4500A
SCAN
EXAM RM
CLEAN UTILITY
TOILET
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
SHOWER
COMPUTER
RM
CORRIDOR
RECEPTION
TRANSFER
CENTER
CORRIDOR
(E)
RESTROOM
OFFICE
CORRIDOR
SCAN
NURSING
EDUCATION MULTI
OFF.
OFFICE
2.1 3 3.1 3.2 4 4.2 5 5.1
J J
J.1 J.1
J.5 J.5
J.4 J.4
K K
PRIMARY
AREA OF WORK
PRIMARY
AREA OF WORK
(E) CO
(E
2" W
(E) 2" HW
(E) 1-1/2" HW
(E) 2" CW
(E) 2" HW
(E) 2-1/2" CW
(E) 1-1/4" HW
(E) 2" HW
(E) 2-1/2" CW
(E) 1-1/4" HW
(E) 2" HW
(E) 1-1/2" HW
(E) 2" CW
(E) 2" HW
(E) 1-1/2" HW
(E) 2" CW
(E
2" W
(E) 4" W
(E) CO
(E) CO
(E) 1-1/4" HW
(E) 2-1/2"V (E) 2"V (E) 2"V (E) 1-1/2"V
(E) 3/4" HW
(E) 1-1/2" CW
(E) 3/4" HW
(E) 3/4" CW
(E
4" W
(E) CO
(E) CO
(E) CO
(E
1- 1/
4" H
W
(E
1- 1/
2" H
W (E
2"
C W
(E) 4" W
(E) 4" W
(E
4"
W PRIMARY
AREA OF
WORK
(E) 2" CW
(E) FD
3 3
(E) 2" V
(E) 2" W
(E) 2" V(E) 2-1/2" V
(E
2- 1/
2" V
(E) O
(E) MA
(E) MV
(E
1- 1/
4" H
W
(E
1- 1/
2" H
W (E
2"
C W
(E) O, (E) MA & (E) MV
(E) O, (E) MA & (E) MV
(E) O, (E) MA & (E) MV
(E) O
(E) MA
(E) MV
(E) O
(E) MA
(E) MV
(E
O (E
M
A (E
M
V
KEY PLAN AREA OF WORK
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:2
P
M
PL-101
FOURTH FLOOR DEMO. PLAN - PLUMBING
12/04/2020 RPM JP
1/4" = 1'-0"1
FOURTH FLOOR WEST - PLUMB. - DEMOLITION
SHEET NOTES:
REMOVE EXISTING SHOWER. ALL EXISTING DOMESTIC WATER SUPPLY TO BE DEMOLISHED SHALL BE
CAPPED AT THE BRANCH MAIN ABOVE CEILING
REMOVE EXISTING FLOOR DRAIN.
EXISTING 4"W BELOW FLOOR FIELD VERIFY EXACT LOCATION.
EXISTING 2"CW, 1-1/4"HW ABOVE CEILING. FIELD VERIFY EXACT LOCATION.
EXISTING UTILITY PIPING ABOVE CORRIDOR. FIELD VERIFY LOCATION.
EXISTING 2" VENT. FIELD VERIFY EXACT LOCATION.
REMOVE EXISTING SINK. ALL EXISTING DOMESTIC WATER SUPPLY TO BE DEMOLISHED SHALL BE CAPPED
AT THE BRANCH MAIN ABOVE CEILING
REMOVE EXISTING MEDICAL GAS WALL OUTLETS CAP EXISTING MEDICAL GAS AT BRANCH MAIN.
CONTRACTOR TO VERIFY FIELD EXISTING CONDITIONS PRIOR TO DEMOLITION AND START OF
CONSTRUCTION. CAP EXISTING PIPE AT BRANCH MAIN.
EXISTING MEDICAL GASES IN FOURTH FLOOR INTERSTITIAL SPACE. CONTRACTOR TO VERIFY FIELD EXISTING CONDITIONS PRIOR TO DEMOLITION AND START OF CONSTRUCTION. CAP EXISTING PIPE AT
BRANCH MAIN.
GENERAL NOTES:
1. ALL DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO START OF
CONSTRUCTION.
N
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
T T
T T
T
T
2.1
2.1
3.1
3.1
3.2
3.2
4.2
4.2
5.1
5.1
J J
J.1 J.1
J.5 J.5
SCAN
EXAM RM
NUCMED ALCOVE
EQUIPMENT RM
CORRIDOR
TOILET
4070B
RECEPTION
CORRIDOR
GAMMA WELL COUNTER
4500A
LAB
SCAN
EXAM RM
CLEAN UTILITY
4508TOILET
OFFICE
BREAK
TOILET
CONFERENCE
4513OFFICE (S)
OFFICE (S)
OFFICE (S)
COMPUTER RM
CORRIDOR
LAB
4070C
HX
CAV-4-1
CAV-4-2
CAV-4-5
S
FS
PRIMARY
AREA OF WORK
(E ) 1
-1 /4
" H W
R
(E ) 1
-1 /2
" H W
(E ) 2
-1 /2
" C W
(E ) 2
" W
(E) 2" HWR
(E) 1-1/2" HW (E) 2" CW
(E) 2" HW
(E) 2-1/2" CW
(E) 1-1/4" HW
(E) 2" HW
(E) 2-1/2" HW
(E) 1-1/4" HWR
(E) 3/4" CW
(E
2- 1/
2" V
(E) 2-1/2"V
(E) 2"V (E) 2"V
(E ) 4
" W
(E) CO
(E) CO
(E) CO
(E ) 1
-1 /4
" H W
(E ) 1
-1 /2
" H W
(E ) 2
" C W
(E) 4" W
(E ) 4
" W
PRIMARY
AREA OF
WORK
TP
(E) CO
(E) 2" W
(E) 2" V(E) 2-1/2" V
(E ) 2
-1 /2
" V
(E) 1-1/4" HW
(E) 1-1/2"V
(E ) 3
/4 " H
W
(E ) 1
-1 /2
" C W
(E) 3/4" HW
(E) 3/4" CW
(E) 4" W
(E) 2" CW
3"W
2% SLOPE
HB
(E) 3/4" CW
ZV
MGA
3/4" MV
1/2" MA
1/2" O
MGO
AC
AC
(E)
(E)
(E)
4.1
4.1
4.3
4.3
4 22
3/4" MV
1/2" MA
1/2" O
/4
M
V /2
M
A
/2
O
/4
C
D
2" V
/2
C W
1 1/2"V
PL-501
PL-501
(E) RESTROOM
LAB
4070D
FOR CONTINUATION
SEE SHEET 1/PL-102.3
(E)
3/4" MV
1/2" MA
1/2" O
(E) O
(E) MA
(E) MV
(E ) O
(E ) M
A
(E ) M
V
KEY PLAN AREA OF WORK
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:2
P
M
PL-102
FOURTH FLOOR PLAN - PLUMBING PART 1
12/04/2020 RPM JP
N
KEY NOTES:
MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.
NEW MEDICAL GAS SUPPLY PIPING SEE 1/PL-102.1 FOR CONTINUATION.
POC NEW 3" W TO (E) 4" W.
PIPING BELOW FLOOR.
POC NEW 1-1/2" V TO (E) 2" V.
EXISTING MEDICAL GAS PIPING IN INTERSTITIAL SPACE TO REMAIN. PIPING ABOVE CEILING.
POC NEW 1/2" HW TO (E)1-1/4" HW.
POC NEW 1/2" CW TO (E)2-1/2" CW.
POC NEW 2" W TO (E) 4" W.
POC NEW 2" V TO (E) 2" V.
EXISTING 4"W BELOW FLOOR FIELD VERIFY EXACT LOCATION.
EXISTING 2" VENT. FIELD VERIFY EXACT LOCATION.
3/4"CD DOWN IN WALL CONNECT TO TAIL PIECE OF (N) FIXTURE.
3/4"CW DOWN IN WALL. ROUGH-IN & CONNECT 3/4"CW TO HB.
POC NEW 3/4" CW TO (E)3/4" CW.
ROUGH-IN AND CONNECT 1/2"02 , 1/2"MA, 3/4"MV TO MEDICAL GAS OUTLLET COLUMN.
ROUGH-IN AND CONNECT 1/2"HW, 1/2"CW, 2"W & 1 1/2"V.
1 1/2"CD TO TERMINATE TO EXISTING RECEPTOR AT EXISTING AC UNIT.
3/4"CD TO TERMINATE TO SINK TAILPIECE.
3/4"CD TO TERMINATE TO FS-1.
3/4" CONDENSATE DRAIN.
3/8" HOSE (PROVIDED BY SIEMENS INSTALLED BY CONTRACTOR) TERMINATE TO SINK TAILPIECE.
SEE DETAIL F9/PL-501.
1/4" = 1'-0"1
FOURTH FLOOR WEST - PLUMBING PART 1
GENERAL NOTES:
1. ALL DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO START OF
CONSTRUCTION.
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
FEC
5.1
5.1
7.1
7.1
H H
J J
J.1 J.1
J.5 J.5
5.2
5.2
5.3
5.3
AV(E)
0.20
AV(E)
0.20
NOT IN SCOPE OF WORK
OFFICE
4024A
OFFICE
OFFICE
CONFERENCE
OFFICE
NURSING EDUCATION MULTI
OFF.
CORR
EXAM RM
4085D
OFFICE(S)
EMPLOYEE EDUCATION
CENTER
EDUCATION TRAINING
CORR
CORR
3/4" MV
1/2" MA
1/2" O
3/4" MV
1/2" MA
1/2" O
OFFICE
OFFICE
4024B
OFFICE
4086A
TAND L
EXAM RM
4085A
OFFICE(S)
EXAM RM
4085B
OFFICE(S)
EXAM RM
4085C
(E ) V
(E ) O
(E
) M A
(E)
(E)
(E) HW
(E) CW
(E) HW
(E) HW
(E) CW
(E) HW
(E) CW
(E) HW
(E) O
(E) MA
(E) MV
(E) O
(E) MA
(E) MV
(E) HW
KEY PLAN AREA OF WORK
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:2
P
M
PL-102.1
FOURTH FLOOR PLAN - PLUMBING PART 2
12/04/2020 RPM JP
1/4" = 1'-0"1
FOURTH FLOOR WEST - PLUMBING PART 2
KEY NOTES:
PIPING ABOVE CEILING.
EXISTING MEDICAL GAS SUPPLY UPSTREAM OF EXISTING ZONE VALVE.
EXISTING ZONE VALVE. FIELD VERIFY EXACT LOCATION.
CONNECT NEW 3/4"MV, 1/2"MA AND TO EXISTING MEDICAL GAS PIPE UPSTREAM OF EXISTING
MEDICAL GAS SUPPLY TO EXISTING ZONE VALVE.
MEDICAL GAS PIPING SEE PL-102 DRAWING FOR CONTINUATION.
GENERAL NOTES:
1. ALL DIMENSIONS ARE APPROXIMATE. CONTRACTOR TO VERIFY FIELD CONDITIONS PRIOR TO START OF
CONSTRUCTION.
Revisions: Date:
4.2
4.2
5.1
5.1
G G
G.1 G.1
H H
J J
(E
A C
(E) GX- 109
PL-301
3/ 4"
D
3/4"D
1/2" CW1/2" CW
2 1
FOR CONTINUATION
SEE SHEET 1/PL-102
1 1/2" CW(N)
(N
(N) (N)
3" W
W
3" W
C.O
2" V 2" V
V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:3
P
M
PL-102.2
LEVEL 4 INTERSTITIAL - PLUMBING REMODEL
12/04/2020 RPM JP
1/4" = 1'-0"1
LEVEL 4 INTERSTITIAL - PLUMBING REMODEL B
PIPING AT INTERSTITIAL SPACE.
EXISTING 1 1/2"CW FEILD VERIFY EXACT LOCATION.
1/2"CW W/SOV TO DRANE KOOLER MAKE-UP.
EXISTING CATWALK.
NEW CATWALK.
STEAM DISPERSION UNIT. SEE MECHANICAL DRAWING.
DRAIN FROM STEAM DISPERSION UNIT TO "DRANE KOOLER".
EXISTING 6" WASTE PIPE RISER IN SHAFT. FIELD VERIFY
EXACT PIPE LOCATION.
WASTE PIPING AT 4th. LEVEL INTERSTITIAL SPACE.
CONNECT NEW 3" WASTE TO EXISTING WASTE RISER.
2" VENT UP TO VTR.
SHEET NOTES:
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
G.1 G.1
H H
SEE DRAWING PL-102.2
FOR CONTINUATION
/4
D
/4
D
/2
C
W
/2
C
W
1/2" CW1/2" CW
1/2" RO
SEE DRAWING PL-102.2
FOR CONTINUATION
H-1
W
1" CD
C D
C D
SEE DRAWING PL-102.2
FOR CONTINUATION
2" V 2" V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:3
P
M
PL-301
LEVEL 4 INTERSTITIAL - ENLARGED
REMODEL B
12/04/2020 RPM JP
1" = 1'-0"1
LEVEL 4 INTERSTITIAL - ENLARGED REMODEL B
SHEET NOTES:
RO WATER FILTER UNIT CULLIGAN MATRIX GI SERIES.
PROVIDE 1/2" RO WATER TO HUMIDIFIER.
2" DRANE KOOLER DRAIN. TERMINATE TO FLOOR SINK.
DRANE KOOLER WATER TEMPERING UNIT BY DRI-STEEM.
3/4" HUMIDIFIER DRAIN TO DRANE KOOLER.
1/2" RO TO HUMIDIFIER.
3/4" DRAIN FROM DISPERSION UNIT. TERMINATE TO DRANE
KOOLER
1/2"CW W/SOV TO DRANE KOOLER MAKE-UP.
1"CD TERMINATE TO FS-1, PROVIDE 2" AIRGAP.
Revisions: Date:
ISSUED FOR 100% C.D. 2020-10-02
ALTERNATE WATER SEAL
SHOWN (BY INSTALLER)
SERVICE UNION
VACUUM BREAKER
VALVE
COLD WATER ENTERS HERE
TEMPERATURE SENSON
FLOOR SINK
1" AIR GAP (25 mm)
ADJUSTABLE
TEMPERATURE-ACTUATED
FLOOR STAND
TEMPERED WATER
DISCHARGED HERE
DRANE-KOOLER 304
STAINLESS STEEL
MIXING CHAMBER
HOT WATER
ENTERS HERE
NEW CATWALK
55 55 19
VACUUMMEDICAL AIROXYGEN
ICU NW ZONE 1 ICU NW ZONE 1 ICU NW ZONE 1
PSIG PSIG PSIG
NORMAL ICU NW PANEL
BBBBEACONEACONEACONEACONMMMMEDAESEDAESEDAESEDAES
13.50 in
0.80in 2.88in
(TYP)
1.05in
2.13in
2.49in
3.38in 1.75in
PLUGGED
KNOCKOUTS
14.00in
.4 in
0.82in
2.13in
6.00in 6.00in
WALL THICKNESS
1/2" TO 1 1/2"
.0 in
0.58in 4.13in
FINISHED WALL
FRONT PANEL
HINGED FOR
INTERNET
ZV
ZV
ZV
14-1/2" 4" 3"3"4"3"3"
22-9/16"
PRESSURE/VACUUM
GANGES (TYP)
FULL PORT DOUBLE SEAL BALL
TYPE WITH 3 PIECE BRONZE/BRASS
BODY AND A CHROME PLATED
BRASS BALL VALVE
1/8"BRASS NPT PORT FOR
INSTALLATION OF SENSOR
FRONT VIEW
4"
16"
CORRIDOR SCAN
SIDE ROOM
NYLON 6/6 INSULATED
GROMMETS (TYP)
MOUNTING
BRACKET (TYP)
CORRIDOR
WALL
±6"
SIDE VIEW
MOUNTING BRACKET (TYP)
FRONT VIEW
LOCK WASHER & NUT, TYP
HILTI 1/2"Ø KB-TZ (ICC-ESR1917) EFFECTIVE EMBED
2-1/4" W/ UNISTRU HRCN COUPING NUT, FOR
CONCRETE CEILING STRUCTURE OR WELD
ON STRUCTURAL STEEL. SEE STRUCTURAL
DRAWING
PIPE
ADJUSTABLE STEEL YOKE
PIPE ROLL B-LINE B3110 SERIES
1/2" ROD FOR PIPE DIA.
2-1/2" TO 3" AND 5/8" ROD
FOR 4" & 5" PIPE DIA.
STRUCTURE
PIPE
PIPE COVERING
PUTTY: MINIMUM 1-1/2"
THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULUS ON
TOP SURFACE OF FLOOR.
PACKING MATERIAL:
MINIMUM 4PCF MINERAL
WOOL BATT INSULATION
U.L. SYSTEM No. C-AJ-5054
PENETRATING ITEM:
COPPER TUBING 1-1/2"
DIA (OR SMALLER)
TYPE ''L'' OR ''K''
PIPE COVERING
PIPE
WALL ASSEMBLY
(WOOD OR STEEL
CHANNEL STUDS WITH
GYPSUM WALLBOARD)
WALL ASSEMBLY
(WOOD OR STEEL
CHANNEL STUDS WITH
GYPSUM WALLBOARD)
PENETRATING ITEM: COPPER
TUBING 6 INCH DIA. OR SMALLER
TYPE ''L'' OR ''K''
CAULK FILL MATERIAL INSTALLED TO COMPLETELY
FILL ANNULAR SPACE BETWEEN PIPE AND GYPSUM
WALL BOARD AND WITH A MINIMUM 1/4INCH DIA.
BEAD OF CAULK APPLIED TO PERIMETER OF PIPE AT
ITS EGRESS FROM THE WALL.U.L. SYSTEM No. W-L-1001
5/16''DIA x 2''LG. STEEL WALL
ANCHOR EQUALLY SPACED
(TOTAL OF 6)
PENETRATING ITEM: COPPER
TUBING 6 INCH DIA. OR SMALLER
TYPE ''L'' OR ''K''
PUTTY: MINIMUM 5-INCH
OF FILL MATERIAL
APPLIED WITHIN THE
ANNULUS ON BOTH
SURFACES OF THE WALL
GALV. SHEET METAL
SLEEVE W/ TABS TO
RETAIN PUTTY
TRIM RING
U.L. SYSTEM No. W-L-5001
NOTES:
1. PENETRATIONS OF PIPES, CONDUITS, ETC., IN WALLS, FLOORS OR CEILING
ASSEMBLIES REQUIRING PROTECTED OPENINGS SHALL BE FIRE STOPPED. FIRE
STOP MATERIAL SHALL BE A TESTED ASSEMBLY AS PRESCRIBED IN U.B.C.
STANDARD 7-5 AND AS APPROVED BY THE OSHPD FIRE MARSHALL
(C.B.C.714).
2. COMPLY WITH CBC 712.3, CPC 301, 701.1.2.2.
CONCRETE FLOOR
PIPE
TECHNICAL DATA
-22°F TO 122°F
MAXIMUM
TEMPERATURE
RANGE OF WATER
PRIMARY COOLING
CIRCUIT
SECONDARY COOLING
CIRCUIT
39°F TO 54°F
N/A
TEMPERATURE
GRADIENT OF WATER
K/MINUTE
NOMINAL
OPERATING
PRESSURE
29 TO 73 PSI
AT OUTPUT OF
THE PUMP
58 PSI TO 73 PSI
AFTER FILLING
PROCEDURE
1. WATER QUALITY
POTABLE WATER QUALITY FOR BOTH THE PRIMARY AND SECONDARY CIRCUIT.
2. OPERATION WITHOUT WATER WILL DESTROY THE PUMP IN THE COOLING
SYSTEM. FOR THIS REASON, THE PUMP OF THE SECONDARY
REASON, THE PUMP OF THE SECONDARY COOLING CIRCUIT CAN BE OPERATED
ONLY WHEN FILLED ACCORDINGLY.
FILLING PRESSURE
(STATIC)
29 PSI ± 2.9PSI
AFTER FILLING
PROCEDURE
29 PSI ± 3 PSI
AFTER FILLING
PROCEDURE
0% TO
100%
HEAT
DISSIPATION
20% TO 75%
WITH DewPoint
BETWEEN 63°F
20 GALLONS
WITHOUT HOSE
EXTENSION
FILLING
VOLUME
13.2 GALLONS
WITHOUT HOSE
EXTENSION
RELATIVE
HUMIDITY
119,425 BTU/HR
MAXIMUM TO THE
AIR EXHAUST
6,824 BTU/HR
TO ROOM AIR
54,594 BTU/HR
TO WATER
BAROMETRIC
PRESSURE
10.2 PSI TO
15.3 PSI
N/A
AMBIENT AIR
TEMPERATURE RANGE
(AIR INTAKE)
-22°F TO 122°F
MAXIMUM
41°F TO 104°F
3. ANTIFREEZE (GLYKOSOL-N)
ANITFREEZE (GLYKOSOL-N) MAY BE ADDED TO PRIMARY COOLING CIRCUIT ONLY,
BY THE TECHNICIAN WHO WILL START THE SYSTEM. THE PERMITTED MIXING
RATION IS 40:60 (GLYCOL:WATER) FOR TEMPERATURE RANGE -22° TO 122° F.
26.4 GALLONS OF ANTIFREEZE (GLYKOSOL-N) IS INCLUDED IN DELIVERY AND
ADDITIONAL CAN BE ORDERED THROUGH SIEMENS LCAL SERVICE. WATER
CANNOT BE ADDED TO THIS MIXTURE.
4. ANTIFREEZE (GLYKOSOL-N) IS NOT PERMITTED ON THE SECONDARY CIRCUIT
FOR THE BIOGRAPH VISION COOLING CIRCUIT.
SINK DRAIN
FLOOR DRAIN
1. A WATER DRAIN IS REQUIRED TO BE
SUPPLIED AND INSTALLED BY THE
CUSTOMER/CONTRACTOR TO DRAIN
CONDENSED WATER FROM THE GANTRY. THE
DRAIN MUST BE WITHIN 32'-9" OF THE
GANTRY. THE HOSE MAY BE EXTENDED
ON-SITE UP TO 65'-7" BY THE
CUSTOMER/CONTRACTOR. BELOW ARE SOME
EXAMPLES OF POSSIBLE WATER DRAINS. THE
MECHANICAL CONTRACTOR IS RESPONSIBLE
FOR DETERMINING WHICH DRAIN TYPE TO USE
AND FOR SPECIFYING, SUPPLYING AND
INSTALLING THE PLUMBING FIXTURES
NECESSARY TO CONNECT THE SIEMENS WATER
HOSE TO THE SELECTED DRAIN.
2. THE MAX. FLOW RATE OF THE CONDENSED
WATER IS 0.53 GALLONS/HR AT 75% RELATIVE
HUMIDITY.
1/2"∅ DRAIN HOLE
TO BE LOCATED ON THE RIGHT SIDE OF THE
GANTRY (WHEN VIEWED FROM THE
FRONT). MIN. 4" FLOOR DRAIN AS REQUIRED PER
LOCAL CODE. PROVIDE SURFACE MOUNTED PULL
BOX OR SURFACE DUCT AS REQUIRED.
GANTRY (TOP VIEW FACING
FRONT OF THE GANTRY)
GANTRY (BACK
SIDE)
WALL
SINK
SIEMENS CONDENSATION WATER
HOSE (LENGTH: 32'-9",OUTSIDE
DIA. 3/8"). MAX. BENDING RADIUS
1 3/16".
WATER
DRAIN
HOSE
OUTLET
EX. CABLE
DUCT
H E
IG
H
T A
.F .F
MV MA 02 02 MA MV
MV MA 02 02 MA MV
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C U s e rs \J u lia n .P in e d a \D o c u m e n ts
\1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T ju lia n
.p in e d a .r v t
/3 /2
:5
:3
P
M
PL-501
PLUMBING DETAILS
12/04/2020 RPM JP
NO SCALE4
TYPICAL PIPE SUPPORT DETAIL
NO SCALE3
TYPICAL PIPING PENETRATION FIRE RATED WALL DETAIL
NO SCALE2
TECHNICAL DATA TABLE DETAIL
NO SCALE1
CONDENSATE WATER DRAIN DETAIL
NO SCALE5
DRANE-KOOLER DETAIL
NO SCALE6
MEDICAL GAS ALARM PANEL DETAIL
NO SCALE7
ZONE VALVE BOX DETAIL
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
| Sheets |
| PL-001 - GENERAL NOTES, LEGEND, SCHEDULES & ABBREVIATIONS |
| PL-101 - FOURTH FLOOR DEMO. PLAN - PLUMBING |
| PL-102 - FOURTH FLOOR PLAN - PLUMBING PART 1 |
| PL-102.1 - FOURTH FLOOR PLAN - PLUMBING PART 2 |
| PL-102.2 - LEVEL 4 INTERSTITIAL - PLUMBING REMODEL |
| PL-301 - LEVEL 4 INTERSTITIAL - ENLARGED REMODEL B |
| PL-501 - PLUMBING DETAILS |