This document provides details for a federal contract solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The solicitation number is 36C25821B0012 and seeks construction services to fully renovate approximately 1200 square feet of an existing Nuclear Medicine department to prepare the space for a new PET CT scanner. The renovation is to be completed according to the provided Statement of Work, Specifications, and Drawings. The opportunity type is listed as a solicitation and no further information is provided regarding response dates, award dates, pricing terms, or set asides.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-001
ELECTRICAL GEN. NOTES, LEGEND &
ABBREVIATION
11/06/20 RO GA
SINGLE LINE
CONDUIT ONLY
CIRCUIT BREAKER
AMP SWITCH
COMMUNICATION
CABINET
AMPERE
MOUNTED
MINIMUM
MECHANICAL
MAIN CIRCUIT BREAKER
LABORATORY INFORMATION
MANAGEMENT SYSTEM
FEET OR FOOT
FIXTURE
DEMOLITION/DEMOLISH
ELECTRICAL
NATIONAL ELECTRICAL
HEATING, VENTILATING &
DISCONNECT
DRAWING
GROUND FAULT CIRCUIT INTERRUPTER
KILOVOLT AMPERE
NATIONAL ELECTRICAL
MAIN LUGS ONLY
INTERMEDIATE METAL CONDUIT
AMERICAN WIRE GAUGE
CATALOG/CATEGORY
AMPERE INTERRUPTING CAPACITY
ARC FAULT, AMP FUSE
ABOVE FINISHED FLOOR
SHORT CIRCUIT AMPERES
INCH(ES)
NEMA
EMT
EM
FF
HP
GND
FT
IMC
HVAC
EQUIP
FIXT
GFCI
MAX.
MIN.
ISC
IN
KVA
MLO
NEC
NECA
KW
LIMS
MCB
MECH.
MTD
EQUIPMENT
EMERGENCY
ELECTRICAL METALLIC TUBING
GROUND
FINISHED FLOOR
NATIONAL ELECTRICAL CODE
MAXIMUM
KILOWATT
DWG
AIC
AS
AFF
C/B
COMM
CAB
AF
CAT
CKT
CLG
CU
AWG
CO, EC
C
A
ELECT.
(D)
EA
DISC.
CIRCUIT
COPPER
CEILING
CONDUIT
EACH
BLDG BUILDING
(E), EXIST EXISTING
KCMIL,MCM THOUSAND CIRCULAR MILS
NORMALLY CLOSEDNC
FLEXIBLE METALLIC CONDUIT (STEEL)FLEX
JUNCTION BOXJB,J-BOX
LEDFLUOR
DOWNDN
BC BARE COPPER
INTERNATIONAL RESIDENTIAL CODE
INTERNATIONAL BUILDING CODE
IBC
NOT IN CONTRACT
PANEL
POWER
RECEPTACLE
REQUIRED
SECTION
QUANTITY
NEVADA POWER COMPANY
NORMALLY OPEN
NOT TO SCALE
SCHEDULE
OVERCURRENT PROTECTION
NATIONAL FIRE CODE
NEUTRAL
NIC
NEUT
NFC
NL
PH
NPCO
SPEC
SP
OCP
SECT
SCHED
REQ'D
RECEP
PWR
PNL
NTS
QTY
NO
NIGHT LIGHT
SINGLE POLE
SPECIFICATION
PHASE
POLEP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCH GEAR
SYS SYSTEM
TEMP TEMPORARY
TELE TELEPHONE
XFMR TRANSFORMER
UBC UNIFORM BUILDING CODE
UL UNLESS NOTED OTHERWISE
V VOLT OR VOLTAGE
VP VAPOR PROOF
TYP. TYPICAL
W WATT, WIRE
WP UL LISTED WEATHERPROOF,
NON-FUSIBLENF
POLYVINYL CHLORIDEPVC
VD VOLTAGE DROP
VA VOLT AMPERE
MANUFACTURERS ASSOCIATION
CONTRACTOR'S ASSOCIATION
28. ALL PENETRATIONS OF FIRE RATED FLOOR OR WALL ASSEMBLIES SHALL BE PROTECTED
BY MATERIALS AND INSTALLATION DIAGRAMS THAT CONFORM TO UL LISTING FOR
"THROUGH-PENETRATION FIRE STOP SYSTEMS".FIRESTOPPING SHALL MATCH F, T, W, AND L
RATINGS OF FLOOR AND WALL ASSEMBLIES.
29. CONTRACTOR SHALL ENGAGE THE SERVICES FOR A STATE LICENSED FIRE ALARM
MANUFACTURER/INSTALLER TO PREPARE ALL DESIGN DRAWINGS AND CALCULATIONS
REQUIRED FOR SYSTEM APPROVAL BY THE AUTHORITY HAVING JURISDICTION.
SUBMIT ALL PLANS AND PROVIDE ALL PERMITS REQUIRED FOR A COMPLETE AND
OPERABLE APPROVED LIFE SAFETY SYSTEM.
30. ALL FIRE ALARM DEVICE WIRING SHALL BE CLASSIFIED PER NFPA 72. FIRE ALARM DEVICE WIRING
SHALL BE MINIMUM #14 AWG COPPER OR PER SYSTEM MANUFACTURER REQUIREMENTS.
PROVIDE MINIMUM 3/4" SEPARATE RACEWAY SYSTEM OR AS REQUIRED FOR LIFE SAFETY SYSTEM
WIRING CONFIGURATION.
31. UPON COMPLETION OF THE INSTALLATION OF LIFE SAFETY SYSTEM WIRING AND
DEVICES, A PERFORMANCE TEST OF THE ENTIRE LIFE SAFETY SHALL BE
PERFORMED TO THE SATISFACTION OF THE AUTHORITY HAVING JURISDICTION.
32. ALL EQUIPMENT ELECTRICAL TERMINATIONS TO UNDERGO A TORQUE TEST.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MANUFACTURER'S RECOMMENDED
TORQUE DOCUMENTATION AND TOOLS TO PERFORM TORQUE TEST. CONTRACTOR SHALL APPLY
UL TABLE 486A-B WHERE THE MANUFACTURER DOES NOT PROVIDE TORQUE
RECOMMENDATIONS.
33. ALL UNDERGROUND SERVICE CONDUITS SHALL BE SEALED PER NEC ARTICLE 230-8.
34. FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE MOUNTED ON A 4" HIGH
CONCRETE PAD.
35. INSTALL TRANSFORMER FOLLOWING MANUFACTURER'S RECOMMENDATIONS FOR
VENTILATION CLEARANCES.
36. PRIOR TO WORK COORDINATE ELECTRICAL REQUIREMENTS FOR ALL PLUMBING AND MECHANICAL
EQUIPMENT WITH FINAL CONTRACTOR SELECTION. THE CONTRACTOR SHALL SIZE
DISCONNECTS BASED UPON CIRCUIT BREAKER RATINGS AND PROVIDE FUSING AS
REQUIRED PER EQUIPMENT MANUFACTURER RECOMMENDATIONS AND U.L. LISTING
REQUIREMENTS.
37. PROVIDE #10 AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER
THAN 75' AND #8 AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS
LONGER THAN 120'. PROVIDE #10 AWG CONDUCTORS FOR 20 AMPERE, 277V
BRANCH CIRCUITS LONGER THAN 200'.
UNDERGROUND PULL SECTIONUGPS
AIR CONDITIONING
NEMA 3R
TELEVISION OUTLET
TELEPHONE/COMPUTER OUTLET-MOUNTED 450MM (18")AFF
UNLESS OTHERWISE NOTED
ELECTRICAL STRIP MOLD-NEMA 5-20R
RECEPTACLES AT 600MM(2'-0")INTERVALS
SERVICE CABLE TERMINATION
CIRCUIT BREAKER
FUSE
FUSED DISCONNECT SWITCH
SWITCH
SURGE SUPPRESSOR
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
GROUNDING ELECTRODE
POWER METER
MOTOR
GENERATOR
SHUNT TRIP
GROUND FAULT INTERRUPT
TRANSFER SWITCH
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP
MOUNTED 450MM (18")AFF UNLESS OTHERWISE NOTED
CONTACT (NORMALLY OPEN)
CONTACT (NORMALLY CLOSED)
TIME SWITCH
CONTROL SWITCH
PUSH BUTTON
DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP
MOUNTED ABOVE COUNTER TOP
UNDERWRITERS LABORATORYU.N.O.
DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED ABOVE COUNTER TOP
WEATHERPROOF DUPLEX RECEPTACLE WITH GFI, NEMA
5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
QUADRAPLEX OUTLET, NEMA 5-20R-20AMP-MOUNTED
450MM (18")AFF OR QUADRAPLEX OUTLET, NEMA
5-20R-20AMP-PEDESTAL-MOUNTED
QUADRAPLEX OUTLET, NEMA 5-20R-20AMP-MOUNTED
ABOVE COUNTER TOP
QUADRAPLEX OUTLET WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
QUADRAPLEX OUTLET WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED ABOVE COUNTER TOP
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP-EMERGENCY
POWER-MOUNTED 450MM (18")AFF UNLESS OTHERWISE
NOTED
QUADRAPLEX RECEPTACLE, NEMA
5-20R-20AMP-EMERGENCY POWER
SPECIAL RECEPTACLE
WALL MOUNTED TELEPHONE/COMPUTER OUTLET-
MOUNTED AT 1200MM (48")AFF UNLESS OTHERWISE NOTED
SPEAKER-CEILING MOUNTED
INTERCOM OUTLET
NURSE CALL DOME LIGHT-CEILING MOUNTED
NURSE CALL DOME LIGHT-WALL MOUNTED
NURSE CALL DUTY STATION
EMERGENCY NURSE CALL
NURSE CALL STAFF STATION
VOLUME CONTROL-WALL MOUNTED
JUNCTION BOX-PURPOSE AND LOCATION AS NOTED
SINGLE POLE SWITCH
SINGLE POLE SWITCH-SUFFIX OF a,b OR c INDICATES
SEPARATE CONTROL OR FIXTURES WITH SAME DESIGNATION
DIMMER SWITCH
THREE WAY SWITCH
DOOR SWITCH
FUSED OR UNFUSED DISCONNECT SWITCH
2'x2' LED FIXTURE
1'x4' LINEAR LED FIXTURE
2'x4' FLUORESCENT FIXTURE
WALL MOUNTED FLUORESCENT FIXTURE
2'x2' LED FIXTURE-EMERGENCY POWER
2'x4' FLUORESCENT FIXTURE-EMERGENCY POWER
WALL MOUNTED FLUORESCENT FIXTURE-EMERGENCY
POWER
WALL MOUNTED LIGHT FIXTURE-TYPE AS NOTED
LIGHT FIXTURE-TYPE AS NOTED
LIGHT FIXTURE-TYPE AS NOTED EMERGENCY POWER
CIRCUIT BREAKER
BATTERY POWERED CLOCK
EMERGENCY BATTERY UNIT WITH HEADS
DUAL TECHNOLOGY OCCUPANCY SENSOR - CEILING
DUAL TECHNOLOGY OCCUPANCY SENSOR - WALL
A
GFCI
GFIC-A
WP
A
GFCI
GFCI-A
w
D
E
S a
D os
NOTES NOTES (CONT'D.)
ST
TVSS
G
M
GFI
S
I
N
N
N
N
N
V
J
DS
CB
C
POWER
LIGHTING SIGNAL
STANDARD ABBREVIATIONS
GENERAL ELECTRICAL NOTES SHEET
NUMBER SHEET NAME
E-00.10 ELECTRICAL GENERAL NOTES, SYMBOLS & ABBREVIATIONS
E-001 ELECTRICAL GEN. NOTES, LEGEND & ABBREVIATION
E-002 SINGLE LINE DIAGRAM
E-003 ELECTRICAL PANEL SCHEDULES
E-004 ELECTRICAL PANEL SCHEDULES
E-005 VOLTAGE DROP CALCULATIONS & LOAD SUMMARY
E-006 ELECTRICAL PHOTOGRAPHS
E-007 TITLE 24 COMPLIANCE DOCUMENTS
E-100 ELECTRICAL 4TH FLOOR - OVERALL
ED-100 ELECTRICAL 4TH FLOOR - AREA OF WORK DEMOLITION
EL-101 4TH FLOOR-AREA OF WORK REMODEL- LIGHTING
EL-102 ELECTRICAL LIGHTING CONTROL
EL-103 ELECTRICAL LIGHTING CONTROL DIAGRAMS
EL-104 LIGHTING DETAILS
EL-201 4TH FLR- AREA OF WORK REMODEL - PHOTOMETRICS
EL-202 4TH FLR- AREA OF WORK REMODEL - EGRESS PHOTOMETRICS
EP-101 4TH FLOOR-AREA OF WORK REMODEL-POWER
EP-102 ELECTRICAL 4TH INTERSTITIAL - ENLARGED PLANS
EP-103 ELECTRICAL ENLARGED PLAN - INTERSTITIAL
EP-104 ELECTRICAL ENLARGED PLAN - EXTERIOR
EP-105 POWER DETAILS
EP-106 POWER DETAILS
EY-101 4TH FLOOR-AREA OF WORK REMODEL-TELECOM
EY-201 TELECOM DETAILS
EY-202 FIRE ALARM DETAILS
TV
CB CODE BLUE INITIATION STATION
LIGHTINGLTG
PANELBOARD - SURFACE MOUNT
REVISION SYMBOL
SCHEDULED EQUIPMENT
KEYNOTE SYMBOL
EQUIPMENT TAG
DIAGRAM TAG
WIRELESS APPLICATION PROTOCOL
SWITCH BANK
XX
SHEET
UNIT
X
WAP
MISCELLANEOUS
SB
SINGLE POLE THERMAL RATED MOTOR STARTER SWITCH
M
DOUBLE POLE THERMAL RATED MOTOR STARTER SWITCH
38. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS.
NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED
TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
CONTRACTOR SHALL PROVIDE DIMENSIONED SHOP DRAWINGS FOR ALL ELECTRICAL
EQUIPMENT.
CONTRACTOR SHALL COORDINATE WITH ALL DICIPLINES AND PROVIDE DIMENSIONED
SUBMITTAL DRAWINGS FOR ALL CONDUIT, PIPE AND WALL DUCTWORK, SUBMITTAL DRAWINGS
SHALL INCLUDE SIZES, DIMESSIONS AND ELEVATIONS FROM BUILDING WALLS, FLOORS AND
DECKS.
CONTRACTOR SHALL COORDIANTE WITH ALL DISCIPLINES AND ROUTE ELECTRICAL BRANCH
CIRCUIT CONDUITS WITH MECHANICAL PIPING WHERE POSSIBLE.
EMERGENCY POWER OFF (EPO) PUSH BUTTON
EXIT SIGN - CEILING MOUNTED
LINEAR LED STRIP FIXTURE
LINEAR LED STRIP FIXTURE - EMERGENCY POWER
TELEPHONE BACKBOARD
OS
TRANSFORMER
T
FUSE (> 600V)
DOOR SWITCHDS
EMERGENCY POWER OFF PUSH BUTTON
(HEIGHT NOTED ON PLANS)
EPO
39.
40.
41.
CONDUIT CAP-OFF
HOMERUN TO PANELBOARD 1/2"C W/3#12
CONDUCTORS UNO
RACEWAY TURNED DOWN
RACEWAY TURNED UP
RACEWAY W/#12 CONDUCTORS UNO
CONDUIT ROUTED UNDERFLOOR / UNDERGROUND
CONDUIT WITH TICKS FOR NUMBER & SIZE OF
CONDUCTOR#10
WIRING
1. ELECTRICAL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH
THE NECA INSTALLATION STANDARDS TO THE SATISFACTION OF THE ARCHITECT AND
ENGINEER.
2. ALL WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE CURRENTLY ACCEPTED
EDITION OF ALL APPLICABLE NATIONAL, STATE AND CITY CODES AND ORDINANCES.
3. ALL ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR NATIONALLY
RECOGNIZED TESTING FACILITY AS ALLOWED BY AUTHORITY HAVING JURISDICTION.
4. WHERE AN APPARENT DISCREPANCY EXISTS BETWEEN THE REQUIREMENTS OF THE GENERAL
NOTES AND/OR INFORMATION PORTRAYED IN THE ELECTRICAL DRAWINGS, THE CONTRACTOR
SHALL INCLUDE IN HIS BID THE COST OF THE GREATER QUALITY OR QUALITY.
5. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID AND VERIFY EXISTING CONDITIONS.
CONTRACTOR SHALL INCLUDE IN BASE BID ALL COSTS REQUIRED FOR PERMITS AND
INSPECTIONS.
6. CONTRACTOR SHALL VERIFY, WITH OWNER'S REPRESENTATIVE PRIOR TO SUBMITTING BID,
ALLOWABLE WORKING HOURS, EMPLOYEE PARKING AREAS, MATERIAL DELIVERY, STORAGE
REQUIREMENTS, DEMOLITION AND REMOVAL OF CONSTRUCTION DEBRIS, AS WELL AS DAILY
CLEAN UP REQUIREMENTS. INCLUDE ALL COSTS IN BID FOR DUST BARRIERS, INFECTION
CONTROL, DUMPSTERS ETC. AS REQUIRED FOR THE DURATION OF THE PROJECT. PERFORM
WORK AS DIRECTED BY OWNER'S REPRESENTATIVE AND ARCHITECT.
7. ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT
WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE ALL NECESSARY CORRECTIONS AT NO
ADDITIONAL COST TO OWNER.
8. CONTRACTOR SHALL GUARANTEE WORK AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP
WHICH MAY OCCUR UNDER NORMAL USE FOR A PERIOD OF ONE YEAR AFTER OWNER'S
ACCEPTANCE. DEFECTS SHALL BE PROMPTLY CORRECTED BY CONTRACTOR WITHOUT
ADDITIONAL CHARGE TO OWNER.
9. AS PART OF THE CLOSE-OUT FOR THE PROJECT, THE CONTRACTOR SHALL PROVIDE AS-BUILT
DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ACCURATE CONDUIT AND DEVICE
LOCATIONS DIMENSIONED FROM PERMANENT LANDMARKS SUCH AS BUILDING WALLS.
10. DO NOT SCALE ELECTRICAL DRAWINGS. VERIFY EXACT LOCATION OF ALL DEVICES, JUNCTION BOXES, LIGHTING FIXTURES WITH ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO
INSTALLATION. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF MECHANICAL
EQUIPMENT AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ROUGH-
IN. EVERY OUTLET HEIGHT SHALL BE VERIFIED ON EACH WALL WITH THE INTERIOR PLANNING
AND DESIGN DRAWINGS. COORDINATE WITH CABINET SHOP DRAWINGS TO ENSURE PROPER
HEIGHT AND LOCATION WITH RESPECT TO MILLWORK, EQUIPMENT.
11. THESE DRAWINGS INDICATE THE FINISHED REQUIREMENTS FOR THE ELECTRICAL SYSTEMS, EQUIPMENT, LIGHTING FIXTURES, OUTLETS AND DEVICES. DUE TO STRUCTURAL CONDITIONS, MECHANICAL DUCT, PIPING CONFLICTS, OR OTHER LEGITIMATE REASONS, THE CONTRACTOR
MAY DESIRE TO INSTALL THE WORK INDICATED IN A MANNER DIFFERENT FROM THAT SHOWN.
SUCH CHANGES SHALL BE PRESENTED TO THE OWNER'S REPRESENTATIVE FOR REVIEW AND
APPROVAL PRIOR TO PROCEEDING. UPON APPROVAL, THE WORK SHALL BE PERFORMED AND
THE AS-BUILT DRAWINGS SHALL BE REVISED TO ACCURATELY REFLECT THE WORK AS
ACTUALLY INSTALLED.
12. RACEWAY SYSTEMS ARE SHOWN DIAGRAMMATICALLY. ACTUAL LOCATION AND ROUTING OF
ALL, SHALL BE DETERMINED BY CONTRACTOR TO SUIT FILED CONDITIONS
13. PROVIDE DEDICATED NEUTRAL FOR EACH NEW CIRCUIT PER NEC 210.4. SHARED NEUTRALS
SHALL NOT BE ALLOWED ETWEEN LOADS FROM SEPERATE OVERCURRENT DEVICES.
HANDLETIES SHALL NOT BE ALLOWED AS A METHOD OF COMPLIANCE WITH NEC 210.4 BETWEEN
SEPERATE DEVICES. HOME RUN CONDUCTORS MAY BE COMBINED INTO ONE CONDUIT WITH
SEPARATE NEUTRALS FOR EACH CIRCUIT. NO RACEWAY OR CABLE SHALL CONTAIN MORE THAN
NINE (9) CURRENT CARRYING CONDUCTORS. NEUTRAL CONDUCTORS SHALL BE CONSIDERED
CURRENT CARRYING CONDUCTORS. WHERE MULTIPLE CONDUCTORS IN EXCESS OF THREE (3)
ARE INDICATED ON THESE DRAWINGS, THEY SHALL BE DERATED AS REQUIRED BY NEC ARTICLE
310 REQUIREMENTS.
14. RACEWAYS SHALL BE INSTALLED CONCEALED (IN CMU OR OTHER WALL) WHENEVER POSSIBLE.
RACEWAYS INSTALLED EXPOSED SHALL BE ROUTED OUT OF PUBLIC VIEW AS MUCH AS
POSSIBLE. RACEWAYS SHALL BE RUN PARALLEL WITH, OR AT RIGHT ANGLE TO WALLS.
15. PROVIDE APPROVED EXPANSION FITTINGS WHERE RACEWAYS CROSS BUILDING EXPANSION
JOINTS. PROVIDE BONDING JUMPER(S) SIZED PER CODE WHERE REQUIRED. PROVIDE FITTINGS
REQUIRED FOR A COMPLETE INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR
EXPANSION JOINT LOCATION(S).
16. MINIMUM RACEWAY SIZE SHALL BE 3/4". MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG U.N.O.
TYPICAL FOR ALL INTERIOR. MINIMUM CONDUCTOR SIZE FOR EXTERIOR SHALL BE #10 AWG
U.N.O. ALL POWER RELATED CONDUITS SHALL HAVE A GROUND WIRE INSTALLED IN EACH RUN
PER NEC 250.66.
17. CONTRACTOR SHALL PROVIDE PULL CORDS IN SPARE CONDUITS. WHERE MORE THAN ONE
CONDUIT TERMINATES IN A JUNCTION BOX, THE CONTRACTOR SHALL IDENTIFY EACH CONDUIT
AND JUNCTION BOX IN A MANNER ALLOWING IDENTIFICATION AFTER ALL WALL FINISHES HAVE
BEEN APPLIED.
18. CONTRACTOR SHALL PROVIDE ALL RACEWAY SYSTEMS INDICATED ON THE DRAWING PER NEC
REQUIREMENTS AND GENERAL NOTES. ANY DEVIATION FROM THE WIRING METHODS
INDICATED SHALL BE ALLOWED ONLY BY SPECIFIC WRITTEN APPROVAL FROM EITHER THE
ARCHITECT, ENGINEER OR OWNER. CONTRACTOR'S BID SHALL INCLUDE ALL COSTS FOR
RACEWAY SYSTEMS AS SPECIFIED UNLESS SPECIFIC WRITTEN APPROVAL FOR AN
ALTERNATIVE WIRING METHOD IS OBTAINED FROM EITHER THE ARCHITECT, ENGINEER OR
OWNER AND IS SUBMITTED AS PART OF CONTRACTOR'S FORMAL BID PROPOSAL.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECT SIZE AND INSTALLATION OF OUTLET,
PULL AND JUNCTION BOXES IN ACCORDANCE WITH NEC 314-16. BOXES SHALL BE MINIMUM 4"
SQUARE BY 1-1/2" DEEP OR AS INDICATED ON THE DRAWINGS. BOXES SHALL BE RECESSED
WITH COVER PLATE TO SUIT THE INTENDED APPLICATION.
20. PRIOR TO INSTALLATION, CONTRACTOR SHALL REVIEW THE COMPLETE SET OF CONSTRUCTION
DOCUMENTS FOR CONFLICTS WITH OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE TO
COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT DURING INSTALLATION.
CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS IN EQUIPMENT LOCATION AND ROUTING AS
NECESSARY AT NO ADDITIONAL COST TO THEOWNER.
21. CONTRACTOR SHALL BE RESPONSIBLE TO PROPERLY CUT AND PATCH EXISTING
CONSTRUCTION AS REQUIRED TO INSTALL NEW ELECTRICAL WORK. ALL PATCHING SHALL BE
OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS THE EXISTING WORK AND SHALL
ACCURATELY MATCH ALL SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT.
22. ALL ELECTRICAL EQUIPMENT SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO
ACCOMMODATE QUANTITY AND SIZE OF CONDUCTORS REQUIRED. CONTRACTORS SHALL
PROVIDE EQUIPMENT WITH OVERSIZED ENCLOSURES WHERE REQUIRED.
23. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE TYPE WRITTEN UPDATED PANEL
DIRECTORY WITH DATE AND INCLUDING ROOM NUMBER FOR ALL NEW EXISTING LOADS PER
NEC 408.4 TO BE MOUNTED ON INSIDE OF ALL PANEL DOOR COVERS. DIRECTORY SHALL
REFLECT ALL ADDITIONS OR MODIFICATIONS TO EXISTING PANELS AND SHALL REFLECT ACTUAL
"AS-BUILT" CONDITIONS. HANDWRITTEN DIRECTORIES OR MODIFICATIONS TO DIRECTORIES
ARE NOT ACCEPTABLE. LOAD DESCRIPTION SHALL NOT INCLUDE "EXISTING" OR "EXISTING
LOAD". ALL LOADS SHALL BE VERIFIED BY THE CONTRACTOR. PROVIDE DIRECTORIES AS A
CLOSE-OUT SUBMITTAL PER SPEICIFICATION SECTION 26 24 16 PANELBOARDS.
24. VERIFY DEVICE COLOR AND MOUNTING ORIENTATION (VERTICAL OR HORIZONTAL) WITH
ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO ORDERING ANY EQUIPMENT AND
PROVIDE DEVICES AS REQUIRED. UNLESS NOTED OTHERWISE, DEVICES AND DEVICE PLATES
SHALL BE WHITE IN COLOR.
25. WHERE MOTORS ARE INSTALLED IN SUSPENDED CEILINGS, CONTRACTOR SHALL PROVIDE
DISCONNECT SWITCH IN SUSPENDED CEILING WITHIN REACH FROM ACCESS POINT.
26. CONTRACTOR SHALL VERIFY ACTUAL MOTOR AND APPLIANCE RATING AND LOADS.
CONTRACTOR TO PROVIDE MOTOR OVERLOAD ELECTRICAL COMPONENTS BASED ON
NAMEPLATE RATING. REFLECT ANY CHANGES IN THE AS-BUILT DRAWINGS.
27. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ARCHITECT FOR REVIEW OF THE
FOLLOWING EQUIPMENT:
A. ELECTRICAL SWITCHGEAR: SWITCHBOARDS, PANELS, MOTOR CONTROL CENTERS AND
SAFETY SWITCH
B. TIME/CURRENT TRIP CURVES
C. LIGHTING FIXTURES: INDOOR/OUTDOOR AS PSECIFIED, PHOTOMETRIC PERFORMANCE
DATA AND LAMPS
D. DEVICES: SWITCHES, RECEPTACLES, MOTOR CONTROLLERS AND DEVICE PLATES
INCLUDING SHOP DRAWINGS FOR ALL LIGHTING CONTROLS.
E. LIFE SAFETY /FIRE ALARM SYSTEMS: CONTROL PANEL, ANNUNCIATOR PANEL,INITIATION
AND NOTIFICATION DEVICES / APPLIANCES, SYSTEM WIRING REQUIREMENTS AND
DIAGRAMS, SYSTEM LOCA CALCULATIONS, STAND-BY BATTERY CALCULATIONS, AND
AUXILIARY POWER SUPPLY
LIGHTING FIXTURE SCHEDULE
Type Mark Description Lamp Mounting Volts Manufacturer Model Wattage Notes
F1 2'X2' LED FIXTURE WITH 0-10V
DIMMING
LED RECESSED 120V DAYBRITE 2LTG27L840-2-21-UNV-D
IM-BAC
46 W
F1E 2'X2' LED FIXTURE WITH 0-10V
DIMMING
LED RECESSED 120V DAYBRITE 2LTG27L840-2-21-UNV-D
IM-BAC
46 W PROVIDE WITH 90 MINUTE
BATTERY PACK
F2 6" LED DOWNLIGHT WITH 0-10V
DIMMING
LED RECESSED 120V LIGHTOLIER C6RN-BAC /
C6L25840WZ10U-BAC /
C6RDLCL-BAC
21 W
F2E 6" LED DOWNLIGHT WITH 0-10V
DIMMING
LED RECESSED 120V LIGHTOLIER C6RN-BAC /
C6L25840WZ10U-BAC /
C6RDLCL-BAC
21 W PROVIDE WITH 90 MINUTE
BATTERY PACK
F3 4' LINEAR LED STRIP FIXTURE WITH
0-10V DIMMING
LED SURFACE 120V DAYBRITE FSS440L840-UNV-DIM-B
AC
29 W
F3E 4' LINEAR LED STRIP FIXTURE WIRH
0-10V DIMMING
LED SURFACE 120V DAYBRITE FSS440L840-UNV-DIM-B
AC
29 W PROVIDE WITH 90 MINUTE
BATTERY PACK
X1 SINGLE FACE COMPACT EXIT SIGN GREEN SURFACE 120V CHLORIDE CLXNGW2C PROVIDE UNIVERSAL
MOUNTING KIT FOR SIDE,
END, TOP AND FACE
MOUNTING. PROVIDE WITH 90
MINUTE BATTERY PACK.
X-RAY X-RAY IN USE WARNING SIGN LED CHLORIDE AMS-120-GW-"X-RAY IN
USE"-CMB
INTERLOCK WITH SIEMENS
EQUIPMENT
FIRE ALARM
SD SMOKE DETECTOR
FIRE ALARM STROBE
HD HEAT DETECTOR
FIRE ALARM SYMBOLS ARE INDICATED ON THE PLANS FOR COORDINATION AND BIDDING PURPOSES ONLY.
COMPLETE FIRE ALARM CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE CONTRACTOR AS A
DEFERRED SUBMITTAL AND SHALL INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
1. A COMPLETE DESCRIPTION OF THE SCOPE OF FIRE ALARM WORK.
2. PRODUCT DATA.
3. CONDUCTOR SCHEDULE.
4. SEQUENCE OF OPERATION.
CLOCK OUTLET
NURSE CALL
N NURSE CALL STATION
NURSE CALL INDICATOR
NURSE CALL SYMBOLS ARE INDICATED ON THE PLANS FOR COORDINATION AND BIDDING PURPOSES ONLY.
COMPLETE NURSE CALL CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE CONTRACTOR AS A
DEFERRED SUBMITTAL AND SHALL INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING:
1. A COMPLETE DESCRIPTION OF THE SCOPE OF NURSE CALL WORK.
2. PRODUCT DATA
3. CONDUIT AND CONDUCTORS.
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
ISSUED FOR CONSTRUCTION 2020-11-06
ISSUED FOR CONSTRUCTION 2020-12-04
CEM1
H 11
5CE
L 8
PP4D
J5 5
4A
J3 4.2
4XC
E2 9.3
4XE
4CEXA
J5 5
225 A
150 AT
EMG SWITCH GEAR
800 A
800 AT
ATS 5
NE
800 A
70 AF
EDB1
800 A
800 AT
800 A
800 AT
1200A
1200AT
A B
100 A
70 AT
400 A
400 AT
100 A
100 AT
1200A TIE BREAKER
H 11
2CE
C D
1200AT
225 A
150 AT
1200A TIE BREAKER
SWBD. B
225 A
150 AT
100 A
100 AT
100 A
70 AT
800 A
800 AT
SWBD. D
800 A
800 AT
225 A
200 AT
150 A
200 AF
J5 4.2
4XB
L 5.1
4XAA
L 5.1
4XA
D4A
N5 9.5
4D
60 A
60 AF
60 A
100 AF
L8
J5 4.2
4XCA
O1 9.5
4XQ
N 8
4XR
J3 5.1
4XD
150 A
200 AF
150 A
200 AF
150 A
200 AF
D4XA
L8
D4AA
N5 9.5
60 AF
60 A
4CCD
RM 4054
150 KVA
J5 14.1
150 A
200 AF
112.5 KVA
T16
T
D2 9.5D2 9.3
4XG
4XF
E2 10
4XH
200 A
200 AF
D4XB
H11
T17
4XK
J5 9.5
4XS
K 14.1
4XL
J5 13.3
4XM
J 13.3
4XJ
100 A
100 AF
175 A
200 AF
150 A
200 AF
T
800 A
800 AT800 AT
800 A 800 A
800 AT
100 AF
800 A
100 AF
800 A
CEM2-603
600 AF 250A400 AF
800 A
800 AF
800 A
600 AF 800 AF 100A225A
4CEXD
100 AF
100 A
H11
200 AF
150 A
200 AF
150 A
200 AF
175 A
100 AF
100 A
D4CEXA-234
T
4CEXB
E2 9.5
4CEXC
J5 13.3 O 9.5
T15-449
112.5 KVA
E N
ATS 12
800A/4P
J5 5
4CEXA1
J5 5
4CEXAA
400 AF
400 A
BASEMENT
2ND INT'STIT.
1ST INT'STIT.
3RD INT'STIT.
4TH INT'STIT.
5TH INT'STIT.
4CEXE
9 N
ISC = 3,682A
ISC = 3,621A
ISC = 2,806A
ISC = 2,909 A
ISC = 5,408 A
ISC = 11,040A
ISC = 10,083AISC = 2,423A
NORMAL POWERCRITICAL POWER
SIEMENS
EQUIPMENT
PANEL "MP"
EDB1
800 AT
800 A
800 AT
800 A
PANEL A
RM 4503
SCAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-002
SINGLE LINE DIAGRAM
11/06/20 RO GA
1. AS REQUIRED ALL OVERSIZED FEEDERS THAT WERE ADJUSTED IN SIZE TO COMPENSATE FOR VOLTAGE DROP SHALL BE PROVIDED WITH ADAPTER LUGS OR SPLICE BOX. ADAPTER LUGS SHALL BE PROVIDED IF SIZE IS AVAILABLE, OTHERWISE PROVIDE CABLE SPLICES IN THE SPLICE BOX TO
REDUCE CABLES TO THE MAXIMUM SIZE THAT THE BREAKER LUGS CAN ACCOMMODATE.
2. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED FOR FINAL INSPECTIONS.
3. ALL CONDUCTORS SHALL BE 600V. RATED WITH THHN/THWN INSULATION AT 75° CELSIUS.
4. ALL CIRCUIT BREAKER TERMINALS IN SWITCHBOARDS AND PANELBOARDS SHALL BE U.L LISTED
AND APPROVED FOR USE COPPER 75° CELSIUS CONDUCTORS.
5. ALL FINAL TERMINATIONS OF CONDUCTORS TO ELECTRICAL EQUIPMENT AND DEVICES SHALL BE
TIGHTENED TO THE MANUFACTURER'S RECOMMENDED SPECIFICATION OR PER UL 486A/B, NO
EXCEPTION.
6. MINIMUM AIC SHALL BE 10,000 FOR 208/120-VOLT EQUIPMENT UNLESS NOTED.
7. ALL PANELBOARDS, SWITCHBOARDS, AND FEEDERS INDICATED ON THE SINGLE LINE DIAGRAM ARE
EXISTING TO REMAIN UNLESS NOTED OTHERWISE.
AFFECTED BY SCOPE OF WORK.
PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR SIZED PER NEC 250.122 AS
REQUIRED PER NEC 517.14 AND BOND ALL PANELBOARDS SERVING PATIENT CARE AREAS.
PROVIDE 3#3/0, 1#6 GND., 2"C.
COORDINATE WITH SIEMENS EQUIPMENT PROVIDER FOR LOCATION AND INSTALLATION OF
EQUIPMENT.
GENERAL NOTES
KEYNOTES
NO SCALEPARTIAL SINGLE LINE DIAGRAM 1
1 1
(TYP)
(TYP)
(TYP)
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-003
ELECTRICAL PANEL SCHEDULES
11/06/20 RO GA
CONTRACTOR SHALL TRACE, LOCATE AND VERIFY LOADS. REVISE DIRECTORY CARD WITH
DESCRIPTION OF LOAD AND INCLUDE ROOM NUMBER PER NEC 408.4.
PROVIDE NEW CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH
EXISTING IN MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD
INFORMATION.
DISCONNECT AND REMOVE EXISTING CONDUIT AND CONDUCTORS COMPLETELY. THERE
SHALL BE NO ABANDONED CONDUITS. LEAVE BREAKER AS SPARE, AND UPDATE PANEL CARD
INFORMATION.
REMOVE EXISTING CIRCUIT BREAKER 30A/2P AN RETURN TO THE OWNER. PROVIDE NEW
CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH EXISTING IN
MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD INFORMATION.
REMOVE EXISTING CIRCUIT BREAKERS 20A/1P AN RETURN TO THE OWNER. PROVIDE NEW
CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH EXISTING IN
MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD INFORMATION.
1. ALL PANELS ARE EXISTING TO REMAIN. MODIFY AS INDICATED.
GENERAL NOTES
KEYNOTES
PANEL 4CEXA PANEL 4XCA
PANEL 4A PANEL 4XE
PANEL 4XC
PANEL PP4D
1. EXISTING BREAKER, EXISTING LOAD
Notes:
Total Est. Demand Current: 7 A
Total Conn. Current: 7 A
Total Est. Demand: 6000 VA
Total Conn. Load: 6000 VA
Lighting 6000 VA 100.00% 6000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 7 A 7 A 7 A
Total Load: 2000 VA 2000 VA 2000 VA
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 LITES RM 4052 20 A 1 500 VA 500 VA 1 20 A LITES RM 4003,4007,4006,4008,4009,4010 12
9 LITES RM 4041,42,43,44,45,48,52 20 A 1 500 VA 500 VA 1 20 A LITES RM 4002,04,05,12,14,15,16,17 10
7 LITES RM... 20 A 1 500 VA 500 VA 1 20 A LITES RM 402340,24,4025,4079,4080,4081,4086 8
5 LITES RM 4000,4000C,4001,4019,4088 20 A 1 500 VA 500 VA 1 20 A LITES RM 4026,4027,4027A,4029,4033,4034,4038 6
3 LITES RM 4000 20 A 1 500 VA 500 VA 1 20 A LITES RM 4077,4085 4
1 LITES RM 4020,4022,4037,4039,4053,4077 20 A 1 500 VA 500 VA 1 20 A LITES RM 4078,4082,4083,4084 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: D4A Phases: 3 Mains Type: MCB
Location: INTERSTITIAL Volts: 480/277 Wye A.I.C. Rating: 10,000
Branch Panel: 4A
1. EXISTING BREAKER TO REMAIN (EXISTING LOAD) 2. EXISTING BREAKER, NEW LOAD 3. PROVIDE CIRCUIT BREAKER AS INDICATED TO MATCH EXISTING WITH NEW LOAD
Notes:
Total Est. Demand Current: 140 A
Total Conn. Current: 149 A
Receptacle 16120 VA 81.02% 13060 VA Total Est. Demand: 50553 VA
Power 6602 VA 100.00% 6602 VA Total Conn. Load: 53613 VA
Lighting 30891 VA 100.00% 30891 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 153 A 150 A 146 A
Total Load: 18246 VA 17906 VA 17461 VA
29 BIO HOOD RM 4062 20 A 1 500 VA 3120... -- -- -- 30
27 Spare 20 A 1 0 VA 3200... -- -- -- 28
25 Spare 20 A 1 0 VA 2850... 3 100 A PANEL FEED RM 4503 26
23 OUTLET RM 4502 20 A 1 500 VA 540 VA 1 20 A OUTLET N WALL RM 4520 24
21 OUTLET RM 4506 30 A 1 500 VA 540 VA 1 20 A OUTLET RM 4072 22
19 OUTLET N WALL RM 4072 30 A 1 500 VA 540 VA 1 20 A OUTLET RM 4506 20
17 CATWALK STRIP LTG 20 A 1 96 VA 720 VA 1 20 A OUTLET RM 4070 18
15 SCAN ROOM 4505 DOOR OPERATOR 20 A 1 400 VA 900 VA 1 20 A OUTLET RM 4070 16
13 CONTROL 4504 20 A 1 500 VA 1240... -- -- -- 14
11 MEDRAD WORKSTATION PWR 20 A 1 1000... 850 VA 2 50 A PANEL FEED 4CEXAA RM 4503 12
9 -- -- -- 1976... 250 VA 1 20 A HVAC CONTROL PANEL (AC/420) 10
7 HP/4520 (4TH FLOOR EXTERIOR) 30 A 2 1976... 500 VA 1 20 A SCAN 4503 OVERHEAD LIFT PWR 8
5 -- -- -- 9600... 540 VA 1 20 A RM 4016A REC (E) 6
3 -- -- -- 9600... 540 VA 1 20 A RM 4016A REC (E) 4
1 PANEL FEED 4CEXA1 100 A 3 9600... 540 VA 1 20 A RM 4016A REC (E) 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: D4CEXA Phases: 3 Mains Type: MLO
Location: INTERSTITIAL Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: 4CEXA
1. EXISTING BREAKER, EXISTING LOAD 2. EXISTING BREAKER, NEW LOAD
Notes:
Total Est. Demand Current: 43 A
Receptacle 5760 VA 100.00% 5760 VA Total Conn. Current: 43 A
Power 7000 VA 100.00% 7000 VA Total Est. Demand: 15410 VA
Motor 1450 VA 100.00% 1450 VA Total Conn. Load: 15410 VA
Lighting 1200 VA 100.00% 1200 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 34 A 49 A 48 A
Total Load: 4127 VA 5697 VA 5587 VA
41 OUTLET RM 4511 20 A 1 500 VA 0 VA -- -- -- 42
39 OUTLET RM 4509 20 A 1 500 VA 920 VA 2 20 A GX-45 40
37 OUTLET RM 4509 20 A 1 500 VA 0 VA 1 20 A Spare 38
35 OUTLET RM 4501 20 A 1 500 VA 0 VA 1 30 A Spare 36
33 -- -- -- 1000... 250 VA -- -- -- 34
31 CAV 4-1,4-2,4-3,4-4,4-5 20 A 2 1030... 250 VA 2 50 A EXH HOOD RM 32
29 OUTLET RM 4501 20 A 1 500 VA 250 VA -- -- -- 30
27 OUTLET RM 4504, 4505 20 A 1 500 VA 250 VA 2 50 A CENTRIFUGE RM 28
25 -- -- -- 0 VA 500 VA 1 20 A OUTLET RM 4513 26
23 Spare 40 A 2 0 VA 720 VA 1 20 A EXAM RM 4501 REC 24
21 OUTLET RM 4510 20 A 1 500 VA 180 VA 1 20 A OUTLET RM 4520 22
19 Spare 20 A 1 0 VA 0 VA 1 30 A Spare 20
17 OUTLET RM 4518 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4507 18
15 REC AC-420 LVL 4 INTERSTITIAL 20 A 1 180 VA 0 VA 1 20 A Spare 16
13 -- -- -- 250 VA 180 VA 1 20 A Receptacle 14
11 OUTLET RM 4504 20 A 2 250 VA 500 VA 1 20 A OUTLET RM 4507 12
9 FUME HOOD RM 4504 20 A 1 500 VA 167 VA -- -- -- 10
7 OUTLET RM 4504 20 A 1 500 VA 167 VA -- -- -- 8
5 PET SCAN COVE LIGHTS 20 A 1 1200... 167 VA 3 20 A ZEBRA DISK RM 4070 6
3 OUTLET RRM 4505 20 A 1 500 VA 250 VA -- -- -- 4
1 OUTLET RM 4516 20 A 1 500 VA 250 VA 2 30 A OUTLET S WALL RM 4503 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: 4XC Phases: 3 Mains Type: MCB
Location: INTERSTITIAL Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: 4XCA
1. EXISTING BREAKER, EXISTING LOAD
Notes:
Total Est. Demand Current: 18 A
Receptacle 500 VA 100.00% 500 VA Total Conn. Current: 18 A
Power 2000 VA 100.00% 2000 VA Total Est. Demand: 6319 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 6319 VA
Lighting 3822 VA 100.00% 3822 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 22 A 20 A 13 A
Total Load: 2500 VA 2328 VA 1500 VA
29 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 30
27 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 28
25 -- -- -- 0 VA 0 VA 1 20 A Spare 26
23 Spare 30 A 2 0 VA 0 VA -- -- -- 24
21 Spare 20 A 1 0 VA 0 VA 2 30 A Spare 22
19 Spare 20 A 1 0 VA 0 VA -- -- -- 20
17 -- -- -- 0 VA 0 VA 2 20 A Spare 18
15 Spare 20 A 2 0 VA 20 VA 1 20 A X-RAY SIGNS 16
13 -- -- -- 0 VA 500 VA 1 20 A SCAN 4503 MEDRAD BOOM PWR 14
11 Spare 20 A 2 0 VA 500 VA 1 20 A SCAN 4503 MEDRAD BOOM PWR 12
9 EXAM 4501/COMPUTER 4502/SCAN 4503 LTG 20 A 1 835 VA 500 VA 1 20 A SCAN 4503 MEDRAD BOOM PWR 10
7 LITES CORRIDOR RM 4505 20 A 1 500 VA 500 VA 1 20 A SCAN 4503 MEDRAD BOOM PWR 8
5 OUTLET RM 4501,4510,4518,4519 20 A 1 500 VA 500 VA 1 20 A LITES RM 4040A,4041A,4045A,B,C 6
3 LITES RM 4503, 4504 20 A 1 500 VA 500 VA 1 20 A LITES RM 4520 4
1 LITES RM 4513,4514,4515,4516,4517 20 A 1 500 VA 500 VA 1 20 A LITES RM 4506,4507,4511 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: 4XD Phases: 3 Mains Type: MLO
Location: INTERSTITIAL Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: 4XC
1. EXISTING BREAKER, EXISTING LOAD 2. EXISTING BREAKER, NEW LOAD
Notes:
Total Est. Demand Current: 61 A
Total Conn. Current: 63 A
Total Est. Demand: 21902 VA
Receptacle 11500 VA 93.48% 10750 VA Total Conn. Load: 22652 VA
Power 11152 VA 100.00% 11152 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 63 A 62 A 65 A
Total Load: 7546 VA 7386 VA 7720 VA
41 OUTLET RM 4100 20 A 1 500 VA 250 VA -- -- -- 42
39 OUTLET RM 4092 20 A 1 500 VA 250 VA 2 50 A TEMP BOX 40
37 -- -- -- 250 VA 500 VA 1 20 A OUTLET RM 4092 38
35 DRYER ROOM 4095A 30 A 2 250 VA 500 VA 1 20 A HOIST RM 4111 36
33 -- -- -- 250 VA 250 VA -- -- -- 34
31 J BOX RM 4112 40 A 2 250 VA 250 VA 2 30 A OUTLET RM 4089 32
29 J BOX RM 4112 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4089 30
27 OUTLET RM 4111,4112,4113,4114 20 A 1 500 VA 500 VA 1 20 A OUTLET RM A-4012, TELE BD 28
25 OUTLET RM 4112,4113,4114 20 A 1 500 VA 180 VA 1 20 A HP 4068 REC (6TH FLOOR EXTERIOR) 26
23 HANDS FREE SINK AND DISPENSER 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4091,4092 24
21 CONTROL 4504 REC 20 A 1 1080... 500 VA 1 20 A OUTLET RM 4091,4092 22
19 CONTROL 4504 REC 20 A 1 1080... 500 VA 1 20 A OUTLET RM 4091,4092 20
17 COMPUTER 4502/EXAM 4501 REC 20 A 1 1760... 0 VA 1 20 A Spare 18
15 EXAM RM 4501 REC 20 A 1 360 VA 0 VA 1 20 A Spare 16
13 OUTLET RM 4092 20 A 1 500 VA 300 VA 1 20 A SCAN 4503 LUMINOUS VIRTUAL WINDOW 14
11 OUTLET RM 4096,4100 20 A 1 500 VA 400 VA 1 20 A HANDS FREE DOOR OPERATOR 12
9 OUTLET RM 4098,4100 20 A 1 500 VA 1976... -- -- -- 10
7 SCAN 4503 REC 20 A 1 540 VA 1976... 2 30 A HP 4068 (6TH FLOOR EXTERIOR) 8
5 CONTROL 4504BLANKET WARMER 20 A 1 840 VA 720 VA 1 20 A COMPUTER RM 4502 REC 6
3 720 VA 1 20 A COMPUTER RM 4502 REC 4
1 720 VA 1 20 A COMPUTER RM 4502 REC 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: D4XB Phases: 3 Mains Type:
Location: INTERSTITIAL Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: 4XE
NORMALCRITICAL NORMAL
NORMAL
NORMAL
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-004
ELECTRICAL PANEL SCHEDULES
11/06/20 Checker Author
1. EXISTING BREAKER, EXISTING LOAD 2. EXISTING BREAKER, NEW LOAD
Notes:
Total Est. Demand Current: 37 A
Total Conn. Current: 47 A
Total Est. Demand: 13500 VA
Total Conn. Load: 17000 VA
Receptacle 17000 VA 79.41% 13500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 50 A 46 A 46 A
Total Load: 6000 VA 5500 VA 5500 VA
41 -- -- -- 250 VA 250 VA -- -- -- 42
39 RECEPTACLE ROOM 4040 30 A 2 250 VA 250 VA 2 30 A RECEPTACLE ROOM 4506 40
37 EMG LITE RM 4506 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4049B 38
35 Spare 20 A 1 0 VA 500 VA 1 20 A OUTLET RM 4049B 36
33 Spare 20 A 1 0 VA 250 VA -- -- -- 34
31 Spare 20 A 1 0 VA 250 VA 2 30 A OUTLET RM 4049 32
29 Spare 20 A 1 0 VA 500 VA 1 20 A OUTLET RM 4045A,B,C 30
27 OUTLET RM 4020,4039 20 A 1 500 VA 250 VA -- -- -- 28
25 OUTLET RM 4020,4039 20 A 1 500 VA 250 VA 2 30 A OUTLET RM 4045 26
23 OUTLET RM 4049 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4045A,B,C 24
21 OUTLET RM 4049 20 A 1 500 VA 500 VA 1 20 A OUTLET RM A-4016, TELE BD 22
19 OUTLET RM 4049 20 A 1 500 VA 500 VA 1 20 A LITE RM A-4016, SEQ 5 20
17 OUTLET RM 4047 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4046 18
15 OUTLET RM 4047 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4046 16
13 OUTLET RM 4048,4052 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4046 14
11 OUTLET RM 4048,4052 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4042,4043 12
9 OUTLET RM 4045,4047,4048,4049 30 A 1 500 VA 500 VA 1 20 A OUTLET RM 4042,4042,4044 10
7 OUTLET RM 4045,4048,4049 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4043,4044,4045 8
5 OUTLET RM 4044,4045 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4040,4041 6
3 OUTLET RM 4044,4045 20 A 1 500 VA 500 VA 1 20 A OUTLET RM 4040,4041 4
1 LITES RM 4046, 4047, 4048, 4049 20 A 1 500 VA 500 VA 1 30 A OUTLET RM 4511 2
N O T E CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
N O T E
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: 4XAA Phases: 3 Mains Type: MLO
Location: INTERSTITIAL Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: 4XB
PANEL 4XBSWBD PP4D
NORMAL
Notes:
Total Est. Demand Current: 208 A
Total Conn. Current: 208 A
Total Est. Demand: 172854 VA
Total Conn. Load: 172854 VA
Power 172854 VA 100.00% 172854 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 208 A
Total Conn. Load: 172854 VA
1 SWITCHBOARD SMP 3 400 A 20 A 172854 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: Type 1 MCB Rating: 400 A
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: CEM1 Phases: 3 Mains Type: MLO
Location: Electrical Room A4018 Volts: 480/277 Wye A.I.C. Rating:
Switchboard: PP4D
Notes:
Total Est. Demand Current: 208 A
Total Conn. Current: 208 A
Total Est. Demand: 172854 VA
Total Conn. Load: 172854 VA
Power 172854 VA 100.00% 172854 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 208 A
Total Conn. Load: 172854 VA
3 AC-420 3 400 A 40 A 22854 VA
2 PT SCANNER SCAN ROOM 4503 3 400 A 20 A 150000 VA
1 HEAT EXCHANGER EQUIPMENT ROOM 4068 3 400 A 20 A 0 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating:
Supply From: PP4D Phases: 3 Mains Type:
Location: EQUIPMENT ROOM 4520 Volts: 480/277 Wye A.I.C. Rating:
Switchboard: SIEMENS EQUIPMENT PANEL "MP"
CRITICAL
CRITICAL (SIEMENS)
SWBD SMP
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-005
VOLTAGE DROP CALCULATIONS &
LOAD SUMMARY
11/06/20 RO GA
NOT SCALEVOLTAGE DROP CALCULATION 2
NO SCALEFAULT CURRENT CALCULATIONS 3
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
EXISTING
PANEL 4A
EXISTING
PANEL 4CEXA
EXISTING LOW
VOLTAGE PANEL
EXISTING LOW
VOLTAGE PANELEXISTING CABLE TRAY
TO BE DEMOLISHED
EXISTING PANEL
EXISTING
PANELEXISTING CABLE TRAY
TO BE DEMOLISHED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-006
ELECTRICAL PHOTOGRAPHS
11/06/20 RO GA
12" = 1'-0"1
CATWALK ELECTRICAL PHOTO 1
12" = 1'-0"2
CATWALK ELECTRICAL PHOTO 2
12" = 1'-0"3
CATWALK ELECTRICAL PHOTO 3
12" = 1'-0"4
CATWALK ELECTRICAL PHOTO 4
12" = 1'-0"5
CATWALK ELECTRICAL PHOTO 5
12" = 1'-0"6
CATWALK ELECTRICAL PHOTO 6
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:2
P
M
E-007
TITLE 24 COMPLIANCE DOCUMENTS
11/06/20 RO GARevisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
UPDNUPDN
CAB DESK
1 2 2.1 3 3.1 3.2 4 4.2 5 6 7 7.1 8 9 9.1 9.5 9.4 10 11 11.1 12 13 13.3 14 14.1 15 15.1 15.3 16 16.116.3 17 18
B
B.1
C
D
D.2
D.4
E
E.2
E.3
F
G
G.1
H
J
J.1
J.5
J.4
K
L
L.1
M
N
N.2
N.4
N.5
N.6
N.7
O
O.1
P
Q
Q.1
R
S
EP-102
EP-102
FOURTH FLOOR
ELECTRICAL
ROOM
EL-101
EP-103
5.34.3 5.1 5.24.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:3
P
M
E-100
ELECTRICAL 4TH FLOOR - OVERALL
11/06/20 RO GA
1" = 20'-0"LEVEL 4 - OVERALL REFERENCE PLAN 1
N
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS. THE CONTRACTOR SHALL VERIFY AND CONFIRM ALL
WORK PRIOR TO ROUGH-IN.
2. PRIOR TO ANY WORK, THE CONTRACTOR SHALL VERIFY AND CONFIRM ALL EXISTING
CIRCUITS AND LOADS PRIOR TO DISCONNECTING POWER,OUTAGES, OR THE LIKE OF. THE
CONTRACTOR SHALL VERIFY AND CONFIRM LOCATIONS AND REQUIREMENTS OF EXISTING TO
REMAIN DEVICES AND EQUIPMENT IN BOTH AREAS OF WORK AND AREAS OUTSIDE OF AREA
OF WORK. PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS, PERFORM SPLICES, AND
EXTEND CIRCUITS AS NECESSARY TO MAINTAIN THE CONTINUITY OF CIRCUIT TO EXISTING TO
REMAIN DEVICES AND EQUIPMENT.
GENERAL NOTES
KEYPLAN - LEVEL 4 INTERSTITIAL
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
G F
C I
J
JJ
J
J
J
SCAN
EXAM RM
NUCMED ALCOVE
EQUIPMENT RM
CORRIDOR
TOILET
4070B
LAB
4070D
EXAM RM
4070A
LAB
4070C
RECEPTION
CORRIDOR
HAC
GAMMA WELL
COUNTER
4500A
LAB
SCAN
EXAM RM
CLEAN UTILITY
TOILET
OFFICE
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
(E)POWER OUTLETS
COMPUTER RM
(E) RESTROOM
(E)
(E) (E)
(E)
(E)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)(D)
(D)(D)
(D)
(D)
(D) (D)(D)(D)
SCAN
(E)
(E)
EPO
S
(D)
(E)(D)
(E)
(E)
(E)
(D)
(D)
(D) (D)
(E)
(E)
(E) (E) (D)
S
S
S
(E)
EPO
SD
(E)
(E)(E)
(E)
(E)
(D)
(D)
(D)
(D)
(E)
(E)
(D)
(D)
(D) (D)
(D)(D)
(D) (D) (D)
(D)(D)
(D)
(D)
(D)(D)(D)(D)
(D)
(D)
(D)
(D)
(D)
(D) (D)
(D)
(D)
ED-100
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:3
P
M
ED-100
ELECTRICAL 4TH FLOOR - AREA OF
WORK DEMOLITION
11/06/20 RO GA
1/4" = 1'-0"LEVEL 4 - AREA OF WORK DEMOLITION 1
COORDINATE WITH FACILITY AND COR TO MAINTAIN OPERATIONS AT EXISTING SCAN ROOM 4505
DURING NORMAL OPERATING HOURS. CONTRACTOR SHALL PROVIDE BARRIERS AND
TEMPORARY CONSTRUCTION WALLS AS NECESSARY TO MAINTAIN SCAN OPERATING AND
MONITORING EQUIPMENT IN PLACE DURING CONSTRUCTION.
MAINTAIN CONTINUITY OF CIRCUIT TO EXISTING TO REMAIN RECEPTACLES AND SURFACE
MOUNTED RACEWAY FOR OPERATION OF SCAN OPERATING AND MONITORING EQUIPMENT
DURING CONSTRUCTION IN SCAN ROOM 4505.
PROTECT EXISTING TO REMAIN SAFETY DISCONNECT SWITCH IN PLACE.
COORDINATE SCOPE OF DEMOLITION FOR OVERHEAD LIFT ASSIST AND ASSOCAITED
APPURTANCES. CONTRACTOR SHALL REMOVE ALL ELECTRICAL DEVICES, BACKBOXES,
CONDUIT, AND CONDCUTORS COMPLETELY TO SOURCE.
EXISTING LOCATION TO REMAIN. REMOVE EXISTING DUPLEX RECEPTACLE AND SAFE OFF
EXISTING BRANCH CIRCUIT CONDUCTORS. SEE POWER PLAN EP-101.
DISCONNECT AND REMOVE EXISTING SPEAKER SYSTEMS THROUGHOUT THE AREA OF WORK.
SAFELY STORE AND PROTECT EXISTING SPEAKER CABLING FOR DURATION OF WORK.
DISCONNECT AND REMOVE EXISTING MANAGEMENT SYSTEMS THROUGHOUT THE AREA OF
WORK. SAFELY STORE AND PROTECT EXISTING SPEAKER CABLING FOR DURATION OF WORK.
DISCONNECT AND REMOVE CLOCK OUTLET, BACKBOX, CONDUIT AND CONDCUTORS
COMPLETELY TO SOURCE.
MAINTAIN EXISTING ILLUMINATED EXIT SIGN AND PROTECT IN PLACE.
N
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK. ANY
UNFORSEEN CONDITIONS SHALL BE IDENTIFIED PRIOR TO BEGINNING ANY WORK AND
BROUGHT TO THE ATTENTION OF THE COR.
3. CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF CIRCUIT TO ALL DEVICES AND EQUIPMENT
OUTSIDE THE AREA OF WORK. WHERE THE SCOPE OF THIS PROJECT REQUIRES THE
INTERRUPTION OF EXISTING TO REMAIN CIRCUITS WITHIN AND OUTSIDE THE AREA OF WORK,
THE CONTRACTOR SHALL NOTIFY THE COR IMMEDIATELY.
4. CONTRACTOR SHALL PROVIDE ADDITIONAL JUNCTION BOXES, CONDUIT, AND CONDUCTORS
FOR SPLICES IN ORDER TO MAINTAIN CONTINUITY OF CIRCUIT TO EXISTING TO REMAIN
DEVICES AND EQUIPMENT.
5. ALL DEVICES, EQUIPMENT, CONDUIT, AND CONDUCTORS SHALL REMAIN THE PROPERTY OF
VANMCSD. COORDINATE WITH THE COR FOR THE SCHEDULE OF RECYCLABLE MATERIALS AND
DISPOSAL.
GENERAL NOTES
KEY NOTES
KEYPLAN - LEVEL 4
N
5 5
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
D
D D
J
J
D
OS
OS
OS
OSOS
J
J
OS
OS
D
D
EL-101
2 2.1 3 3.1 3.2 4 4.2 5
J
J.1
J.5
J.4
SCOPE OF WORK.
SCOPE OF WORK
c c
F3
(E) RESTROOM
4054TOILET
4070B
GAMMA WELL
COUNTER
4500ALAB
NUCMED ALCOVE
CORRIDOR
RECEPTION
OFFICE (S)
OFFICE (S)
OFFICE
TOILET
OFFICE (S)
OFFICE (S)
CORRIDOR
BREAK
CLEAN UTILITY
EXAM RM
CONFERENCE
TOILET
SCAN
CORRIDOR
SCAN
EXAM RM
COMPUTER RM
EQUIPMENT RM
F3E
PDC
X1
X1
EQUIPMENT RM
SCAN
CONTROL
SCAN
X-RAY
F1
F1
F1E
F1
F2 F2E
F2E F2 F2
F2
F1 F1E
F1 F1
F2
F2
F2
F2E
F2
F1E
F1
F2E
F2
F1
F1E
4XC - 9
a a a b b b ab
9 c 9c b b b b b b
F2E
4XC - 9
4XE - 14
(TYP.
OF 3)
X-RAY
F2
9b
(E)
EXISTING
DISCONNECT
SWITCH
4XC - 16
4XC - 16
a,b,c d,e e e d d a a
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts \1
X
.0
-V
A S
D -N u c -M e d
E le c
R T
V a le ja n d ro
.a g u ila r9
G N
F T
.r v t
/3 /2
:0
:3
P
M
EL-101
4TH FLOOR-AREA OF WORK
REMODEL- LIGHTING
11/06/20 RO GA
RE-CONNECT NEW LIGHTS TO EXISTING CIRCUIT J-BOX (277V) IN CEILING SPACE. VERIFY CIRCUIT
NUMBER IN FIELD.
PROVIDE (2)-#10 & (1)-#10 GND IN EXISTING 3/4"C.
PROVIDE ENGRAVED CONTROL STATION WITH SEPARATE ON/OFF/DIM 0-10V CONTROLS FOR
GENERAL LIGHTING AND FOR DOWNLIGHTING . LOCATE AT SCAN ENTRANCE AND CONTROL
ROOM FOR CONTROL FROM BOTH LOCATIONS.
PROVIDE WARNING LIGHT WITH WORDING "X-RAY IN USE, DO NOT ENTER". PROVIDE INTERFACE
WITH CT CONTROLLER VIA INTERFACE RELAY. WARNING LIGHT TO BE PROVIDED BY OTHERS.
INTERCEPT EXISTING BRANCH CIRCUIT AND EXTEND AS INDICATED.
PROVIDE (2)-#12 & (1)-#12 GND IN 3/4"C. FOR LOW VOLTAGE TRANSFORMER. COORDINATE
LOCATION WITH OWNER PRIOR TO ROUGH-IN.
PROVIDE NURSE CALL LIGHT. INSTALL 2" ABOVE DOOR JAMB AND CENTERED ON DOOR.
COORDINATE REQUIREMENTS WITH EXISTING NURSE CALL SYSTEM.
PROVIDE 120V TO WALL MOUNTED LIGHT PANELS MANUFACTURER SKY FACTORY SERIES #ALS-
BL-TWIN-2240-4IV. COORDINATE WITH ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND
INSTALLATION REQUIREMENTS.
PROVIDE 120V TO LUMINOUS VIRTUAL WINDOW. COORDINATE CONNECTION REQUIREMENTS
WITH VENDOR PRIOR TO ROUGH-IN. COORDINATE WITH ARCHITECT FOR LOCATIONS AND
MOUNTING HEIGHTS.
INTERCEPT EXISTING BRANCH CIRCUIT FROM THE CORRIDOR EXIT SIGN AND EXTEND TO EXIT
SIGN AS INDICATED.
N
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE SURVEYS
AND AS-BUILT DRAWINGS.
2. MULTIPLE HOME RUNS MAYBE SHOWN ON THESE PLANS FOR CLARITY. E.C. IS TO COMBINE HOME RUN CONDUIT AND WIRES SO AS TO OBSERVE ALL REQUIREMENTS FOR N.E.C.110.14. IT IS NOT THE
INTENTION OF THIS DESIGN TO ALLOW MULTIPLE TAPPED CIRCUIT BREAKERS.
3. CONTRACTOR TO VERIFY ALL CONDITIONS, LOCATIONS, AND CONNECTIONS TO EQUIPMENT WITH
OWNER AND/OR ARCHITECT PRIOR TO BID AND INCLUDE ALL COST IN BID.
4. PROVIDE SHIELDING BEHIND ALL BOXES AND OTHER PENETRATIONS IN SHIELDED SCANNING
ROOM SURFACES.
(TYP)
GENERAL NOTES
KEY NOTES
KEYPLAN - LEVEL 4
1/4" = 1'-0"LEVEL 4 - AREA OF WORK - REMODEL LIGHTING 1
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
D
D D
D
OS
OS
OS
OSOS
OS
PP
EPC
PP
EPC
EPC
EPC
EPC
EPC
EPC
PP
PP
PP
EPC
EPC
EPC
D
D
3.2 4 4.2 5
J
J.1
J.5
J.4
EXAM RM
COMPUTER RM
EQUIPMENT RM
SCAN
CONTROL
EQUIPMENT RM
c c a a a c c b b b b…