2020-1001 FP set.pdf

PDF 543 KB Posted

Attached to
Y1DA--CONSTRUCTION 664-CSI-115 4W Nuclear Medicine PET CT II
Solicitation number
36C25821B0012
Issued by

About this file

This document package includes construction drawings and notes for a fire protection system upgrade project, along with details of a related federal contract opportunity. The construction drawings depict design criteria and layout for upgrading an existing wet pipe sprinkler system at a Department of Veterans Affairs nuclear medicine facility, in accordance with NFPA 13 and local codes. Key project elements include installing new quick response sprinkler heads, 1-inch piping, and ancillary equipment. General contractor responsibilities encompass supplying all labor, materials, permits and engineering required for a fully functioning fire protection system. The solicitation seeks bids for a construction contract valued around $1.2 million to fully renovate 1,200 square feet of space and install a new PET CT scanner at the VA facility, in compliance with specifications, drawings and a statement of work. The opportunity was posted by the VA Veterans Health Administration VISN 22.

View the file

Other files

File Type Posted
RFIs 1-68 Amendment 0007.docx DOCX document
36C25821B0012 0007.docx DOCX document
36C25821B0012 0006.docx DOCX document
RFIs 1-67 Amendment 0006.docx DOCX document
RFIs 1-63 Amendment 0005.docx DOCX document
36C25821B0012 0005.docx DOCX document
VASD Siemens PET CT 2 Rm 4503 Final2 Shield Design.pdf PDF
270526 Grounding and Bonding for Comm Systems.pdf PDF
270533 Raceways and Boxes for Communications Systems.pdf PDF
271000 Control Comm and Cable Wiring.pdf PDF
271500 Communications Structured Cabling.pdf PDF
270511 Requirements for Comm Installations.pdf PDF
Wage Determination CA20210001 June 25 2021.pdf PDF
36C25821B0012 0004.docx DOCX document
RFIs 1-60 Amendment 0004 14 Jul 2021.docx DOCX document
2020-1106 Siemens Set.pdf PDF
Hazardous Materials Inspection Report 01-2015Part-3.pdf PDF
RFIs 1-60 13 Jul 2021 Amendment 0003.docx DOCX document
Hazardous Materials Inspection Report 01-2015Part-4.pdf PDF
36C25821B0012 0003.docx DOCX document
Hazardous Materials Inspection Report 01-2015Part-6.pdf PDF
Hazardous Materials Inspection Report 01-2015Part-1.pdf PDF
Hazardous Materials Inspection Report 01-2015Part-5.pdf PDF
Hazardous Materials Inspection Report 01-2015Part-2.pdf PDF
Site Walk Sign-In Sheet.pdf PDF
Questions Asked by Potential Bidder.docx DOCX document
36C25821B0012 0002.docx DOCX document
VASD Siemens PET_CT_2 Rm 4503.Final2 Shield Design.pdf PDF
datasheet_gh3_us.pdf PDF
Questions and Responses from Bidders.docx DOCX document
RFIs.docx DOCX document
2020-1001 Electrical Set - Copy.pdf PDF
36C25821B0012 0001.docx DOCX document
2020-1001 Plumbing set.pdf PDF
2020-1001 Mechanical Set.pdf PDF
FINAL20201204 Plumbing Set.pdf PDF
Wage Determination June 10 2021.docx DOCX document
FINAL20201204 Architectural Set.pdf PDF
FINAL20201204 Mechanical Set.pdf PDF
FINAL20201204 Structural Set.pdf PDF
36C25821B0012.docx DOCX document
Final IFC Specification Manual.pdf PDF
Final17X001 Elec 20201203.pdf PDF
Atch 1 Self Performance Calculations.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE PROTECTION SHEET INDEX

1 NOTES, LEGEND AND ABBREVIATIONS

S.No. SHEET TITLE

P-001

FIRE PROTECTION FLOOR PLAN

SHEET

NUMBER

2 FP-102

FD FLOOR DRAIN

ABBREVIATION

FVC

BFP

AFF

FDC

ELEV

GV

AVG

SYMBOL

FIRE VALVE CABINET

DOUBLE CHECK BACKFLOW PREVENTER

ABOVE FINISHED FLOOR

FIRE DEPARTMENT CONNECTION

ELEVATION

GATE VALVE

AVERAGE

SYSTEM RISER

DESCRIPTION

LEGEND

UP UP PIPING

DOWN DOWN PIPING

GPM GALLON PER MINUTE

AHJ AUTHORITY HAVING JURISDICTION

FHV FIRE HOSE VALVE

1. WORK TO BE ACCOMPLISHED ON THESE DRAWINGS INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY FOR THE PROPER COMPLETE INSTALLATION OF WET PIPE ALL FIRE SPRINKLERS TENANT SYSTEM, IN ACCORDANCE WITH CBC 2019 AND NFPA 13 2016

EDITION WORK.

2. BEFORE SUBMITTING A PROPOSAL ON THE WORK CONTEMPLATED ON THESE DRAWINGS, EACH BIDDER SHALL EXAMINE THE SITE, CHECK AS TO THE MEANS OF MAKING CONNECTIONS AND SHALL BECOME FAMILIAR WITH ALL THE EXISTING CONDITIONS AND LIMITATIONS. NO EXTRAS WILL BE ALLOWED BECAUSE CONDITIONS WHICH MAY AFFECT THE WORK. ANY APPARENT VARIANCE OF THE PLANS FROM EXISTING CONDITIONS AT THE SITE SHALL BE CALLED TO THE ATTENTION OF THE ENGINEER DURING

THE BID PERIOD, SO CLARIFICATION CAN BE MADE BY ADDENDUM.

3. REQUIRED FEES, PERMITS, AND INSPECTIONS SHALL BE OBTAINED AND/OR ARRANGED BY THE

CONTRACTOR.

4. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL CURRENT AND APPLICABLE CODES,

ORDINANCES, LAWS, REGULATIONS AND INDUSTRY STANDARDS.

5. SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE REQUIREMENTS OF THE APPLICABLE BUILDING CODES, STATE LAWS, LOCAL ORDINANCES OR INDUSTRY STANDARDS, THE CONTRACTOR SHALL BEAR ALL COST ARISING TO CORRECT THE DEFICIENCIES.

6. CONTRACTOR SHALL INITIATE, MAINTAIN, AND SUPERVISE ALL SAFETY PRE-CAUTIONS REQUIRED FOR HIS WORK, INCLUDING REGULATIONS OF THE OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

(OSHA).

7. DRAWINGS ARE TO SCALE AS NOTED, BUT THE CONTRACTOR SHALL REFER TO ARCHITECTURAL AND/OR STRUCTURAL DRAWINGS FOR EXACT LOCATION OF PARTITIONS, WALLS, BEAMS, SHAFTS, EQUIPMENT, ETC.

8. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF BUILDING AND SHALL BE FOLLOWED AS CLOSELY

AS ACTUAL BUILDING CONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT.

9. MATERIALS AND EQUIPMENT SHALL BE STORED IN SUCH A PLACE AND IN SUCH A MANNER THAT A MINIMUM OF CONGESTION WILL RESULT. THE PLACING OF SUCH MATERIALS AND EQUIPMENT SHALL BE

SUBJECT TO THE APPROVAL OF THE OWNER.

10. CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES.

11. CONTRACTOR SHALL SOLVE ALL CONFLICTS WITH OTHER TRADES AMONG THEMSELVES WHEN

POSSIBLE. GENERAL CONTRACTOR WILL ARBITRATE WHEN NECESSARY, AND HIS JUDGEMENT SHALL

STAND, WITH NO ADDITIONAL COST TO THE OWNER.

12. CONTRACTOR SHALL BEAR THE EXPENSE OF ALL CUTTING, PATCHING, REPAIRING OR REPLACING OF THE WORK OF OTHER TRADES REQUIRED BECAUSE OF HIS FAULT, ERROR OR TARDINESS BECAUSE OF

ANY DAMAGED DONE BY HIM.

13. CONTRACTOR SHALL PERIODICALLY CLEAR AWAY ALL DEBRIS, SURPLUS MATERIALS, ETC., RESULTING

FROM HIS WORK, LEAVING THE JOB AND THE EQUIPMENT FURNISHED IN A CLEAN CONDITION.

14. PLANS DO NOT INCLUDE ALL OFFSETS FOR COORDINATION WITH DUCT, LIGHTING AND STRUCTURE.

PROVIDE ALLOWANCES FOR REQUIRED OFFSETS.

15. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL A

COMPLETE AND OPERABLE SPRINKLER SYSTEM TO ACCOMMODATE THE PROPOSED WORK AS

INDICATED ON THE DRAWINGS AND AS REQUIRED BY CODE.

16. PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AROUND

OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

17. FIRE CAULK ALL FLOOR PENETRATIONS AND WHERE PIPING PENETRATES RATED WALLS.

1) THIS SUBMITTAL IS FOR A PROPOSED FIRE SPRINKLERS WORK.

2) BUILDING OCCUPANCY AND CLASSIFICATION IS LIGHT HAZARD.

3) BUILDING IS FULLY SPRINKLED.

4) NEW SPRINKLER HEADS SHALL BE OF THE QUICK RESPONSE TYPE.

5) MATERIALS SHALL BE NEW AND U.L. LISTED FOR FIRE SPRINKLER INSTALLATION.

6) NEW OVERHEAD PIPING SHALL BE AS FOLLOWS:

-1"- 1¼" - BLACK STEEL PIPE SCHEDULE 40 WITH THREADED FITTINGS.

7) ALL SYSTEM PIPING SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR TWO HOURS OR

50 PSI ABOVE THE SYSTEM OPERATING PRESSURE, WHICHEVER IS GREATER.

8) ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN INDICATING ITS FUNCTION.

9) IT IS THE RESPONSIBILITY OF THE OWNER TO MAINTAIN THE INTEGRITY OF THE FIRE

SPRINKLER SYSTEM.

10) THREADED PIPE AND FITTINGS SHALL HAVE THREADS CUT TO ANSI/ASME B1.20.1.

11) HYDRAULICALLY CALCULATE THE WET PIPE SPRINKLER SYSTEMS PER NFPA 13, AND UFC

3-600-01 DENSITY AND SPACING LISTED IN THE SPRINKLER DESIGN CRITERIA BELOW. FIELD

VERIFY SYSTEM DESIGN AND LAYOUT PRIOR TO FABRICATION OR INSTALLATION.

12) PROVIDE PIPE HANGERS AND SWAY BRACING ON ALL FIRE SPRINKLER SYSTEM PIPING AND

EQUIPMENT PER NFPA 13 AS REQUIRED BY UFC 3-600-01.

13) SEE ARCHITECTURAL DRAWINGS FOR ROOM FINISH SCHEDULE AND ROOM USE. SEE

ARCHITECTURAL, ELECTRICAL, MECHANICAL, AND TELECOMMUNICATION PLANS FOR THE

LOCATION OF THE CEILING-MOUNTED DEVICES, FIELD VERIFY AND COORDINATE THE

LOCATIONS OF ALL SYSTEM COMPONENTS INCLUDING PIPING, ALARMS, DRAINS, TEST

POINTS, ETC. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL

EQUIPMENT WITHIN THE BUILDING.

14) PROVIDE AUXILIARY DRAINAGE WITH A DRAIN VALVE AND PLUG FOR ALL TRAPPED SECTION

OF PIPE, AS REQUIRED BY NFPA 13.

15) THESE DOCUMENT DEPICT PERFORMANCE LEVEL ENGINEERING DESIGN CRITERIA TO BE

UTILIZED AS GUIDANCE FOR THE PLANNING OF THE FIRE SPRINKLER SYSTEM BY THE

CONTRACTOR, PROVED COMPLETE DOCUMENTS FOR REVIEW AND APPROVAL FROM THE

ENGINEER OF RECORD AND AHJ PRIOR TO INSTALLATION. INCLUDE IN THE SHOP

DRAWINGS AND CALCULATION ANY ADDITIONAL EQUIPMENT NECESSARY TO PROVIDE A

COMPLETE INSTALLATION.

16) PIPE MAIN DRAIN TO OUTSIDE OF BUILDING.

GENERAL NOTES

GENERAL NOTES

2018 INTERNATIONAL PLUMBING CODE (IPC)

2018 INTERNATIONAL MECHANICAL CODE (IMC)

2019 NFPA 13

2018 INTERNATIONAL BUILDING CODE (IBC)

REFERECNE CODES

VALVE IN RISE

VALVE IN DROP

STRAINER

CHECK VALVE

GATE VALVE

PRESSURE CONTROL VALVE

RELIEF VALVE

PRESSURE GAUGE

TEST PORT

GALS GALLON

NC NONCOMBUSTIBLE

OS&Y

NIC

SQFT

OUTSIDE SCREW & YOKE

NOT IN CONTRACT

SQUARE FEET

SOV SOLENOID VALVE

NP NOT PERMITTED

PSIG POUNDS PER SQUARE INCH GAUGE

MIN MINIMUM

VLV VALVE

UH UNIT HEATER

SPRINKLER DESIGN CRITERIA

GENERAL ROOM/AREA

CLASSIFICATION

HAZARD

CLASSIFICATION

DENSITY

REQUIREMENTS

DURATION

OF SUPPLY

MAXIMUM

SPRINKLER

PROTECTION AREA

SPRINKLER

TEMPERATURE

HOSE

ALLOWANCE

LIGHT 0.10 GPS/SQFT OVER

MOST REMOTE 1500 SQFT.

60 MIN. 225 SQFT. ORDINARY 100 GPM

2019 INTERNATIONAL FIRE CODE (IFC)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

664-CSI-1154W NUCLEAR MEDICINE PET- CT 2

SAN DIEGO, CA

IDS GROUP INC.

1 PETERS CANYON RD. STE. 130

IRVINE, CA 92606

949.387.8500

NOT FOR CONSTRUCTION

C :\U se rs

\M ar ilo u.

fra nc is co

\D oc um en ts \V

A S

D -N uc -M ed _A

R C

H -C en tra l_ R

TV

_m ar ilo u.

fra nc is co .rv t 9/

/2

3:

:0

P M

10/02/20Revisions: Date:

ISSUED FOR 100% C.D. 2020-10-02 FP-001

FIRE PROTECTION NOTES, LEGEND

AND ABBREVIATIONS

H H

J J

J.1 J.1

J.5 J.5

J.4 J.4

9'- 1"

2'-9 1/2" 8'-0"

5'-

1/ 2"

1'-6 1/2"

4.2

4.2

4.3

4.3

4.1

4.1

4'-1 1/2" 4'-0"

3.2

3.2

5.1

5.1

5.2

5.2

5.3

5.3

2'-3 1/2" 1'-8 1/2"

'-4

/2

7'-

0" 4'-

0"

1/

2" 3'-

/2

1'-8" 2'-9" 2'-11 1/2"

4'-

1/ 2"

3'- 6"

3'- 6"

4'-0"

4'-9"

'-2

6'-10"

1'-5"

3'- 2"

4'-0" 9'-4"

2'- 2"

1'- 8"

2'- 1"

1'-

2'-

5"

7'- 1"

3'- 9"

6'-1" 3'-2"

1'-

SCAN

EXAM RM

COMPUTER RM

EQUIPMENT

RM

CONTROL

SCAN

DESIGN / INSTALLATION / MODIFICATION OF

EXISTING WET PIPE SPRINKLER SYSTEM

SHALL BE PER NFPA13 2019 EDITION AND

SPECIFICATION 211313 WET PIPE SPRINKLER

SYSTEM. DESIGN CLASSIFICATION SHALL BE

LIGHT HAZARD WITH MINIMUM DESIGN

DENSITY OF 0.15/1500 SQ.FT.

FD-204

FP-204

LEVEL 4 - FIRE PROTECTION FLOOR

PLAN

10/02/20

N

1/4" = 1'-0"LEVEL 4 - AREA OF WORK - DEMO RCP 1

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

664-CSI-1154W NUCLEAR MEDICINE PET- CT 2

SAN DIEGO, CA

IDS GROUP INC.

1 PETERS CANYON RD. STE. 130

IRVINE, CA 92606

949.387.8500

NOT FOR CONSTRUCTION

C :\U se rs

\M ar ilo u.

fra nc is co

\D oc um en ts \V

A S

D -N uc -M ed _A

R C

H -C en tra l_ R

TV

_m ar ilo u.

fra nc is co .rv t 9/

/2

3:

:0

P M

10/02/20Revisions: Date:

ISSUED FOR 100% C.D. 2020-10-02

LEGEND

NEW SPRINKLER HEAD.

EXISTING SPRINKLER HEAD

Sheets and Views
17x001.03_FP-001_notes-FP-001
17x002.03_FP-LEVEL 4 - FIRE PLAN-FP-204

File details come from the government source that posted it. Updated .