2020-1001 Mechanical Set.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25821B0012
About this file
This solicitation seeks proposals for a construction project to renovate approximately 1,200 square feet of space within the Nuclear Medicine Department at a Veterans Affairs medical center, in order to install a new PET CT scanner. The scope of work includes fully renovating the space in accordance with provided specifications and drawings. Proposals are due by a specified date. The project is valued between $500,000 and $1,000,000. The soliciting agency is the Veterans Health Administration within the Department of Veterans Affairs.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL SHEET ABBREVIATIONS
DUCT MOUNTED COIL
DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)
SUPPLY
RETURN45°
RETURN, NO SPLITTER (45° TAP)
STANDARD BRANCH SUPPLY OR
MANUAL SPLITTER DAMPER
45°
N
2 1 POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
1/24 IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
STAINLESS STEEL DUCT
(ELECTRIC)
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
//FIRE//SMOKE// DAMPER
(VA DOES NOT ALLOW COMBINATION
FIRE/SMOKE
DAMPERS.)
//F//S// DPR
BACK DRAFT DAMPER
BDD
SECTION.)
FC
10x8
FLEXIBLE CONNECTION, EQUIPMENT,
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
FIRE DAMPER
FD
VD
DUCT WITH SOUND LINING
FLEXIBLE DUCTWORK (INSULATED)
MANUAL VOLUME DAMPER
EXISTING DUCT TO BE REMOVED
VIBRATION, OR SEISMIC
DUCTWORK SYMBOLS
LIMIT OF DEMOLITION
(WALL TYPE)
(WALL TYPE)
DN
DN
UP
UP
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER OR TOP GRILLE
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
D
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
R
DNUP RETURN DUCT (UP & DOWN)
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SQUARE 1-WAY CEILING DIFFUSERS
TERMINAL UNIT SYMBOLS
2'x4' RADIANT CEILING PANEL
2'x2' RADIANT CEILING PANEL
AIR CURTAIN
A PTAC
A TWU
THRU WALL AIR CONDITIONING UNIT.
UNIT. LETTER INDICATES UNIT SIZE.
WINDOW TYPE AIR CONDITIONING
LETTER INDICATES UNIT SIZE.
UNIT HEATER (VERTICAL)
UNIT HEATER (HORIZONTAL)
CONVECTOR OR RADIATOR (RECESSED)
LETTER INDICATES UNIT SIZE.
FLOOR MOUNTED VERTICAL CABINET FAN COIL UNIT.
FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.
LETTER INDICATES UNIT SIZE.
CONVECTOR OR RADIATOR (WALL HUNG)
A
FCU
FCU
A
INDICATES UNIT SIZE.
FLOOR MOUNTED HEAT PUMP. LETTER
PTACA
AIR TERMINAL SYMBOLS
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
MB
DOUBLE DUCT MIXING BOX.
TERMINAL UNIT WITH REHEAT COIL
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SW SOFTWATER
SWHX STEAM TO WATER HEAT EXCHANGER
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
WAG WASTE ANETHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
KG KILOGRAM
KG/HR KILOGRAM PER HOUR
kPa KILOPASCAL
KW KILOWATT
KWH KILOWATT HOUR
L LITER
L/h LITERS PER HOUR (or LITERS/HOUR)
L/m LITERS PER MINUTE (or LITERS/MINUTE)
L/s LITERS PER SECOND (or LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUEFIED PETROLEUM GAS
LPR LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/S METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1,000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
Nm NEWTON METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTDOOR AIR DAMPER
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
P PUMP
Pa PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH– ABSOLUTE
PSIG POUNDS PER SQUARE INCH– GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD RETURN AIR DAMPER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RELAD RELIEF AIR DAMPER
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J INTENTIALLY LEFT BLANK
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,
TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
AQST AQUASTAT
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO
COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM
COOLING TOWER)
D DAMPER - AUTOMATIC
Db DRY-BULB TEMPERATURE
DB DECIBELS
DCW DOMESTIC COLD WATER
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
DRAWING SYMBOLS
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
SECTION LETTER
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
EQUIPMENT ABBREVIATION (SUPPLY FAN)
SUPPLY FAN NO. 3 IN BUILDING NO. 26
TYPICAL UNIT NO.
26 - SF 3
BUILDING NO. WHERE EQUIPMENT IS LOCATED
ITEM (TERMINAL UNIT SHOWN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
SERVED BY AIR HANDLER UNIT NO. 1
26-TU-1-1
RHWR REHEAT WATER RETURN
RHWS REHEAT WATER SUPPLY
PHWS PREHEAT HEATING WATER SUPPLY
PHWR PREHEAT HEATING WATER RETURN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:1
P
M
MH-001
MECHANICAL GENERAL NOTES, LEGEND &
ABBREVIATIONS
10/02/2020 EG SS
SHEET NUMBER SHEET NAME
MH-001 MECHANICAL GENERAL NOTES, LEGEND & ABBREVIATIONS
MH-002 MECHANICAL GENERAL NOTES, LEGENDS
MH-003 MECHANICAL SCHEDULES
MH-100 LEVEL 4 - HVAC ZONING
MH-101 LEVEL 4 - MECHANICAL DEMO PLAN
MH-102 LEVEL 4 - MECHANICAL REMODEL
MH-102I-A LEVEL 4 INTERSTITIAL - MECHANICAL REMODEL
MH-102I-B LEVEL 4 INTERSTITIAL - MECHANICAL REMODEL
MH-103 MECHANICAL PLAN REMODEL
MH-104 LEVEL 4 INTERSTITIAL - MECHANICAL PIPING
MH-105 AIRHANDLING UNIT 420 - PATH OF TRAVEL
MH-201 MECHANICAL SECTION
MH-501 SIEMENS EQUIPMENT DETAILS
MH-502 MECHANICAL DETAILS
MH-503 MECHANICAL DETAILS
MH-504 MECHANICAL DETAILS
MH-505 MECHANICAL DETAILS
MH-601 CONTROL DIAGRAMS
MH-602 CONTROL DIAGRAMS
Revisions: Date:
ISSUED FOR 35% C.D. 2019-02-06
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
ISSUED FOR 65% C.D. 2020-09-02
ISSUED FOR 100% C.D. 2020-10-02
1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE HARD SUSPENDED CEILING, OR ACOUSTICAL CEILING.
2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR
INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.
3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES,
TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS SHALL BE
FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.
COORDINATE LOCATION WITH MECHANICAL INSTALLATION AND DEMONSTRATE
ACCESS TO EQUIPMENT SERVED.
4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,
TERMINAL UNITS, FILTERS, COILS, ETC. LOSS FOR FILTERS SHALL BE FOR FILTERS AT
50% LOADING.
5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE
STANDARD EQUIPMENT DETAILS.
6. DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
8. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF
CEILING DIFFUSERS, REGISTERS, AND GRILLES.
9. SEISMIC PROVISIONS // REQUIRED - SEE SPECS // NOT REQUIRED //
ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED
GENERAL NOTES
PIPING SYMBOLS
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HOT WATER HEATING SUPPLY
HOT WATER HEATING RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
CONDENSER WATER SUPPLY (FROM TOWER)
CONDENSER WATER RETURN (TO TOWER)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
MAKE-UP WATER
DRAIN LINE
VENT LINE
EXISTING PIPE TO BE REMOVED
CHEMICAL FEED
OVERFLOW
COMPRESSED AIR
NATURAL GAS MAIN FUEL
COLD WATER (CITY WATER)
SOFTENED WATER
HOT WATER
ROLLER-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
CLEVIS-TYPE HANGER
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT TO
TRAPEZE EXCEPT WHERE RH ARE INDICATED)
FLOOR-SUPPORTED PIPE STAND
RISER CLAMP (TYPE 42)*
WALL BRACKET (TYPE 31, 32, 33)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
SLIDING SUPPORTS (TYPE 35)*
S-60
CR-60
S-30
CR-30
S-15
CR-15
PC
HWS
HWR
RL
RS
RHG
CWS
CWR
CHS
CHR
MW
D
V
X
CF
OFL
A
G
CW
SW
HW
RH
SH
SCH
TH
PS
RC
WB
CSH
SS
GENERAL PIPING SYMBOLS
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
INVERTED BUCKET TRAP SET INCLUDING PIPING
ACCESSORIES SEE DETAIL
FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING
ACCESSORIES SEE DETAIL
THERMOSTATIC TRAP SET INCLUDING PIPING ACCESSORIES
SEE DETAIL
THERMOMETER
PRESSURE GAGE
VENTURI FLOW METER
REFRIGERANT SIGHT GLASS
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
MANUAL AIR VENT
QUICK-COUPLE HOSE CONNECTOR
VALVE SYMBOLS
GATE VALVE - THREADED/FLANGED
GLOBE VALVE - THREADED/FLANGED
GATE VALVE WITH 3/4" HOSE ADAPTER
CHECK VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE
HOSE CONNECTOR
FLEXIBLE CONNECTION
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
MODULATING CONTROL VALVE
MODULATING CONTROL BUTTERFLY VALVE
TWO POSITION CONTROL VALVE
THREE-WAY MODULATING CONTROL VALVE
THREE-WAY TWO POSITION CONTROL VALVE
PRESSURE REGULATING VALVE
PRESSURE SAFETY VALVE
AUTOMATIC BALANCING CONTROL VALVE
WATER BALANCE DEVICE
CIRCUIT SETTER VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
PRESSURE REDUCING VALVE (PRV)
WATER LEVEL CONTROLLER
FLOW METERM
LC
CONTROL SYMBOLS
ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL MOUNT
TEMPERATURE TRANSMITTER
TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
MOISTURE (HUMIDITY) TRANSMITTER
PRESSURE TRANSMITTER
STATIC PRESSURE SENSOR
FLOW TRANSMITTER
CURRENT TRANSMITTER
CONDUCTIVITY TRANSMITTER
SMOKE DETECTOR
PRESSURE DIFFERENTIAL TRANSMITTER
PRESSURE DIFFERENTIAL SWITCH
HAND SWITCH (HAND-OFF-AUTO SWITCH)
VALVE OR DAMPER POSITION CONTROLLER
LOCAL RECORDING TIME CLOCK (RUNTIME)
TEMPERATURE SWITCH, LOW (FREEZESTAT)
TEMPERATURE SWITCH, HIGH (FREEZESTAT)
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SWITCH HIGH
PRESSURE SWITCH LOW
ELECTRONIC TO PNEUMATIC TRANSDUCER
CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
OCCUPANCY SENSOR
LOCAL TEMPERATURE CONTROL PANEL
HVAC CONTROL PANEL
VARIABLE SPEED MOTOR CONTROLLER
INTEGRATE CONTROL POINT ON REMOTE GRAPHICS WORKSTATION
AT ENERGY CONTROL CENTER
TEMPERATURE CONTROLLER. SEE SEQUENCE OF OPERATION
PRESSURE CONTROLLER. SEE SEQUENCE OF OPERATION
SPEED CONTROLLER. SEE SEQUENCE OF OPERATION
FLOW CONTROLLER. SEE SEQUENCE OF OPERATION
FLOW SWITCH HIGH
FLOW SWITCH LOW
TIME CLOCK CONTROLLING EQUIPMENT ON A SCHEDULE
TEMPERATURE SENSING ELEMENT FOR TRANSMITTING
TEMPERATURE TO EMCS (PROVIDE 12 INCHES [200mm] MINIMUM
LENGTH IN DUCT WHEN SPACE PERMITS.)
SENSOR WITH AVERAGING ELEMENT TO TRANSMIT TEMPERATURE
TO EMCS
MOTOR STARTER
ELECTRIC OPERATED CONTROL DAMPER/OR VALVE
T
M
TT
TT
MT
PT
SPS
FT
IT
CT
SD
PDT
PDS
HS
ZC
KR
TSL
TSH
LC
LT
PSH
PSL
EPT
AT
AT
AT
LTCP
HVAC
VSMC
ECC
TC
PC
SC
FC
FSH
FSL
KC
CO2
CO
OC
M
A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:1
P
M
MH-002
MECHANICAL GENERAL NOTES, LEGENDS
10/02/2020 EG SSRevisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
AC
CAV
4-1
GX
AIR HANDLING UNIT SCHEDULE (CHILLED WATER)
SYMBOL
TYPE
TOTAL
CFM
SUPPLY FAN (QTY 2)
TOTAL
E.S.P.
(IN.W.G.)
DESCRIPTION
LVG. AIR (°F)
D.B.
ENT. AIR (°F)
W.B.D.B. W.B.
FACE
AREA
(SQ.FT.)
MIN.
NO. OF
ROWS
MAX.
AIR P.D.
(IN.W.G.)
G.P.M.
ENT.
WATER
(°F)
LVG.
WATER
(°F)
WATER
P.D.(FT.)
MERV 8-2"COOLING COIL
RPM
EA.
BHP
EA.
VOLT PHASE
INITIAL
P.D.
(IN.)
FINAL
P.D.
(IN.)
H.P.
EA.
ENERGY LABS
MODEL C3672-FC-L
PLENUM
FAN 3,200 2.6 2514 3.48 7.5 460 3 8 8 76 67.0 51.0151.03 0.50.1112.657.045.026.11.0
AREA SERVED
SCAN 4505 & 4503
CONTROL 4504, COMP.
4502, EXAM 4501
F.P.M.
MERV 13- 4"
INITIAL
P.D.
(IN.)
FINAL
P.D.
(IN.)
0.50.25
CAV BOX SCHEDULE
CFM MBH
EAT
(°F)
HOT WATER REHEAT COIL
DESCRIPTIONSYMBOL
TITUS DESV 1750 1750 1750 94.5 40 9016"Ø
SIZE
MAX MIN
CFM
INLET DOWN
STATIC PRESSURE
0.21
MIN
RAD
DIS
NC LEVELS
0.2 9.5 200 180 0.4 2-RH 12
INLET
(IN)
AREA SERVED
PET/CT SCAN RM 4503
LAT
(°F)
APd
(WG)
GPM
EWT
(°F)
LWT
(°F)
WPd
(FT.)
ROWS FPI
EXHAUST FAN SCHEDULE
3,425
DESCRIPTIONSYMBOL
GREENHECK
SQ-160-VG
0.5 " WC DIRECT 1312 2 208 1 160
CFM E.S.P. DRIVE RPM
H.P. VOLT PHASE
OPER
WT. (LBS.)
MOTOR
AREA SERVED
15.1
INLET
SONES
MOUNTING
DETAIL
MOUNTING
DETAIL
MOUNTING
DETAIL
AIR DISTRIBUTION SCHEDULE (UNLESS OTHERWISE NOTED ON PLANS)
FACE
SIZE
MANUFACTURER &
MODEL NO.
TAG REMARKS
24x24
DESCRIPTION
CEILING DIFFUSER
MOUNTING
DETAIL
REMARKS
REMARKS
REMARKS
CAV
4-2
450 450 24.38"Ø 1 0.25 0.16 14 25 0.15 2.5 0.9 10CONTROL RM 4504
CAV
4-3
150 150 8.16"Ø 1 0.06 - 18 0.04 0.8 0.08 10
EXAM, READING, &
CORRIDOR 4502
TITUS DESV
TITUS DESV
TITUS PAS SUPPLY AIR
GRILLE
1 2
6 / MH-502
SD-2
SD-1
AC
SPLIT SYSTEM AC UNIT/HEAT PUMP SCHEDULE (USE COOLING MODE ONLY)
DESCRIPTIONSYMBOL AREA LOCATED MOUNTING
DETAIL
HP
AC
8 / MH-502
HP
MITSUBISHI PKA-A24KA7
WALL MOUNTED INDOOR UNIT
EQUIPMENT ROOM
LEVEL 4 ADJACENT TO
ROOM 4040
EQUIPMENT ROOM. 4068
MITSUBISHI PUZ-A24NHA7-BS
OUTDOOR HEAT PUMP UNIT
1 208 1
CFM
SUPPLY FAN
MCA
AMPS
MAX
W
VOLT PHASE
Hz
19 ----
CAPACITY (MBH)
TOTAL OAT
COOLING MODE @ 95 F OAT
9524.0
80 67
ENT. AIR (°F)
W.B.D.B.
FILTERS
ANTI ALLERGY
MAC-408FT-E
TYPE
OPER.
WT. (LBS)
CEILING DIFFUSER
MOUNTING MATERIAL
24x24
LAY-IN
SURFACE
MOUNTED
STEEL
TITUS PAR EXHAUST
AIR GRILLE
EG-1 CEILING DIFFUSER 24x24 LAY-IN
TITUS PAS SUPPLY AIR
GRILLE
FINISH
MATCH
EXISTING
MATCH
EXISTING
MATCH
EXISTING
STEEL
STEEL
NOISE LEVEL SHOULD NOT EXCEED 30 DB.1 COORDINATE GRILLES AND DIFFUSERS LOCATION WITH ARCHITECTURAL PLANS.2
1 2
1 2
1 2
TITUS PAR RETURN
AIR GRILLE
EG-2 CEILING DIFFUSER 24x24
MATCH
EXISTING
STEEL 1 2
SURFACE
MOUNTED
0.25
0.25 1. ALL CONTROLS SHALL BE INTERFACED WITH THE EXISTING BUILDING AUTOMATION SYSTEM (BAC)
JOHNSON METASYS CONTROLS, EXISTING DIRECT DIGITAL CONTROLS (DDC) AND NETWORK .
2. PROVIDE WALL MOUNTED WIRED THERMOSTAT.
3. PROVIDE HOT WATER REHEAT COIL.
ELECTRICAL
56 60
208 1 60
FLA
AMPS
0.36
7.4
SEER
21.40
MERV 14-12"
INITIAL
P.D.
(IN.)
FINAL
P.D.
(IN.)
0.50.2
ELECTRICAL
FLA
27.3
MCA
30.3
MOCP
4-5
600 600 32.410"Ø 1 0.25 0.14 15 24 0.13 3.24 0.28 10PET/CT SCAN RM 4505
CAV
4-4
150 150 8.16"Ø 1 0.06 - 18 0.04 0.8 0.08 10NUC MED EXAM RM 4501
TITUS DESV
TITUS DESV 0.25
CAV
SCAN 4505 & 4503
CONTROL 4504, COMP.
4502, EXAM 4501
9 / MH-502
MOCP
AMPS
LEVEL 6 ADJACENT TO
ROOM 6083B
OUTLET
(IN)
24x18
12x10
12x8
12x8
14x12.5
40 90
40 90
40 90
40 90
2-RH
2-RH
2-RH
2-RH
PRE-FILTER MERV 8, MOISTURE ELIMINATOR .
UNIT TO BE HUNG FROM 5TH FLOOR SLAB. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
INFORMATION.
AIR-HANDLING UNITS SHALL BE CONSTRUCTED IN MODULAR, HORIZONTAL, AND DRAW-THROUGH
CONFIGURATION. . USE OF BLOW-THROUGH AIR-HANDLING UNITS IS NOT PERMITTED.
THE AHU CASING SHALL BE SOLID DOUBLE-WALL WITHOUT PERFORATIONS.
SINGLE POINT CONNECTION FOR ELECTRICAL
THE INTERIOR LINING MUST BE SS AND EXTERIOR CASINGS SHALL BE TREATED WITH A
CORROSION RESISTANT COATING. ALL INTERIOR COMPONENTS EXPOSED TO THE AIR STREAM
SUCH AS FAN SCROLL, FILTER RACKS, ETC. SHALL ALSO BE PROTECTED.
PROVIDE AN INSULATED, STAINLESS STEEL, DOUBLE-WALL, AND DOUBLE SLOPING DRAIN PAN FOR
REMOVING COOLING COIL CONDENSATE FROM THE PAN.
CHILLED WATER COOLING AND PRE-HEAT COIL SUPPORT FRAME SHALL BE STAINLESS
STEEL. LIMIT COOLING AND PRE-HEAT COIL FACE VELOCITY TO 450 FPM OR BELOW.
ALL COILS SHALL BE COPPER TUBE COPPER FINS (CU/CU)
3 4 5 6 7 8 9
INDOOR UNIT CONTROLS - WALL MOUNTED, WIRED T-STAT (NOT WIRELESS REMOTE)
INDOOR UNIT POWERED BY OUTDOOR UNIT.
PROVIDE CONDENSATE PUMP FOR INDOOR UNIT.
OUTDOOR UNIT SHALL BE RATED FOR A CORROSIVE COASTAL ENVIRONMENT.
OUTDOOR UNIT SHALL BE MOUNTED ON NEOPRENE ISOLATION PADS.
OUTDOOR UNIT DISCONNECT PROVIDED BY MECHANICAL CONTRACTOR AND WIRED BY
ELECTRICAL CONTRACTOR
INDOOR UNIT PROVIDED WITH MAINTENANCE TOGGLE TYPE DISCONNECT SWITCH
H
HUMIDIFIER SCHEDULE
3,200
DESCRIPTIONSYMBOL
VAPOR MIST-30 24"x16" 156
CFM
DUCT
DIMENSION
OPER
WT. (LBS.)
AREA SERVED
DIMENSIONS
HxWxL
REMARKS
SCAN 4505 & 4503
CONTROL 4504, COMP.
4502, EXAM 4501
24"X18"X16"
ELECTRODE
STEAM
HUMIDIFIER
TYPE
ULTRA-SORB
MP-1.5"
DISPERSION
MODEL
KW
36.1
FLA
FUSE
460 / 3
VOLT/PH
1. AIR PRESSURE SENSING SWITCH AFS-222-112 TO INTERLOCK WITH HUMIDIFIER.
2. VAPOR LOGIC CONTROLLER.
3. DRISTEAM KHR-2-DS SPACE RELATIVE HUMIDITY TRANSMITTER
4. DUCT RELATIVE HUMIDITY TRANSMITTER KHD-2-DSB FOR. CONNECT TO HUMIDIFIER CONTROL PANEL
5. INSTALL WITH DRISTEAM DRANE-KOOLER. DRANE-KOOLER OPERATION WEIGHT=15 LB.
6. 2" STEAM HOSE OR PIPE.
7. DISPERSION UNIT ULTRA-SORB 1.5" WEIGHT 37LBS. UNIT INSTALLED ON DUCT. CONNECT DRAIN TO DRANE COOLER DESCRIBED ABOVE.
8. CONNECT WITH NEW RO UNIT. SEE PLUMBING DRAWINGS FOR DETAILS
9. BACnet COMPATIBILITY FOR CONNECTION TO BMS
OPER.
WEIGHT
LBS
4,690
UV LIGHT AT COIL SECTION
VFD'S FOR SUPPLY FANS PROVIDED AND INSTALLED BY MANUFACTURER
ALL CONTROL'S PROVIDED BY MECHANICAL CONTRACTOR.
LVG. AIR (°F)
D.B.
ENT. AIR (°F)
W.B.D.B. W.B.
MAX.
AIR P.D.
(IN.W.G.)
G.P.M.
ENT.
WATER
(°F)
LVG.
WATER
(°F)
WATER
P.D.(FT.)
PRE-HEATING COIL
30 - -64 1.11702008.50.06
HEATING
MBH
125.7
MOUNTING
DETAIL
STEAM
LBS/H
REMARKS
PROVIDE FAN WITH FACTORY MOUNTED TRANSFORMER AND
DISCONNECT SWITCH
1 INTERLOCK FAN WITH AHU SUPPLY FAN2
1 2
AREA LOCATED
LEVEL 4
INTERSTITIAL
SPACE
AREA LOCATED
LEVEL 4
INTERSTITIAL
SPACE
AREA LOCATED
LEVEL 4 INTERSTITIAL
SPACE
LEVEL 4 INTERSTITIAL
SPACE
LEVEL 4 INTERSTITIAL
SPACE
LEVEL 4 INTERSTITIAL
SPACE
LEVEL 4 INTERSTITIAL
SPACE
AREA LOCATED
LEVEL 4
INTERSTITIAL
SPACE
1.2
REQUIRED
GPM
1 / SF6
3 / SF6
5 / MH-502
5 / MH-503
5 / MH-503
5 / MH-503
5 / MH-503
5 / MH-503
OPER.
WT. (LBS)
1 / SF8 1, 2, 3, 4, 5, 6, 7, 8, 9
6 / MH-502
6 / MH-502
6 / MH-502
11 12
MIN.
NO. OF
ROWS
COOLING
MBH
156.4
PROVIDE EXTERNAL VIBRATION ISOLATORS. 3
200 180
200 180
200 180
200 180
8 / MH-5021 208 1700
19 ---- 9524.0
80 67
ANTI ALLERGY
MAC-408FT-E
56 60
208 1 60
0.36
7.4 21.40
26 5 / MH-502
MITSUBISHI PKA-A24KA7
WALL MOUNTED INDOOR UNIT
MITSUBISHI PUZ-A24NHA7-BS
OUTDOOR HEAT PUMP UNIT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:1
P
M
MH-003
MECHANICAL SCHEDULES
10/02/2020 EG SSRevisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
UPDNUPDN
1 2 3 4 5
G
G.1
H
J
J.1
J.5
J.4
K
L
SCAN
BREAK
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
LAB
GAMMA WELL COUNTER
4500A
HAC
EQUIPMENT RM
TOILET
4070B
(E) RESTROOM
LAB
4070C
NUCMED ALCOVE
CORRIDOR
LAB
LAB
4064 EXAM RM
TOILET
EXAM RM
PET SCANNER
EQUIPMENT RM
EXAM RM
CORRIDOR
SCAN
CONTROL
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
SCAN
COMPUTER RM
R A
D S
T O
R A
G E
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:1
P
M
MH-100
LEVEL 4 - HVAC ZONING
10/02/2020 EG SS
1/8" = 1'-0"1 Level 4 HVAC Zones
N
MH-100
LEGEND:
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
2.1 3 3.1 3.2 4 4.2 5 5.1
G
G.1
H
J
J.1
J.5
J.4
SCAN
EXAM RM
NUCMED ALCOVE
CORRIDOR
T O
IL
E
T B
LAB
4070D
EXAM RM
4070A
P E
T S
C A
N N
E R
RECEPTION
CORRIDOR
HAC
GAMMA WELL COUNTER
4500A
LAB
E X
A M
R M
E X
A M
R M
SCAN
EXAM RM
CLEAN UTILITY
TOILET
OFFICE
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
LAB
4062 L
A B
S H
O W
E R
EV (E)
2.32
AV(E)
0.26
AV(E)
0.29
AV(E)
0.30
BV(E)
0.65
BV(E)
0.55
AV (E)
0.30
BV (E)
0.55
AV(E)
0.30
DV (E)
2.23
AV (E)
0.30
AV (E)
0.40
DV(E)
1.30
BV (E)
0.55AV (E)
0.27
BV(E)
0.63
EV (E)
2.31
AV (E)
0.27
AV (E)
0.17
AV (E)
0.20
AV(E)
0.20
EC (E)
5.45
DV (E)
2.88
AV (E)
0.25
AV (E)
0.25
AV (E)
0.37
(E) S
280 CFM
(E) R
400 CFM
(E) S
220 CFM
(E) S
200 CFM
(E) S
200 CFM
(E) E
300 CFM
(E
S
C
F M
(E) E
215 CFM
(E) S
300 CFM
(E) S
320 CFM
(E) E
275 CFM
(E) S
125 CFM
(E) E
125 CFM
(E) R
110 CFM
(E) S
650 CFM
PRIMARY
AREA OF WORK
(E)1-1/4" RHWS & R
LAB
4070C
CORRIDOR
COMPUTER RM
LAB
4070C
RESTROOM
SHOWER
32"ø20"ø
20"ø
20"ø
32"ø
24"x20" 16"x20"
24"x20"
"ø
3(TYP.)
AV (E)
0.30
(E) AC- 57
3 3
(E
G X
4.1 4.3 5.2 5.3
R A
D S
T O
R A
G E
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:2
P
M
MH-101
LEVEL 4 - MECHANICAL DEMO PLAN
10/02/2020 EG SS
1/4" = 1'-0"1
LEVEL 4 - MECHANICAL DEMO PLAN
SHEET NOTES:
EXISTING DUCTWORK TO REMAIN AS INDICATED.
DASHED LINE DENOTES CATWALK AT 4TH FLOOR INTERSTITIAL SPACE.
EXISTING DUCTWORK AND CONNECTIONS SURVEYED AS BEST AS POSSIBLE.
CONTRACTOR TO CARRY ALLOWANCE FOR ADDITIONAL DEMOLITION OR
RELOCATION OF EXISTING DUCTWORK, PIPING, OR CONDUIT ABOVE SCOPE OF
WORK AREA THAT MAY BE REQUIRED TO INSTALL NEW WORK.
ABANDONED TRANE AIRHANDLING UNIT. DEMOLISH AS INDICATED AND ASSOCIATED
SUPPLY AND RETURN DUCTWORK. CUT AND CAP EXISTING CHW PIPING.
DEMO EXISTING DUCTWORK AS INDICATED.
DEMO EXISTING ABANDONED FLEXIBLE DUCT.
ABANDONED STAINLESS STEEL DUCT. DEMOLISH AS INDICATED.
MH-101
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
T T
T
T
T T
T
UPDNUPDN
2.1 3 3.1 3.2 4 4.2 5 5.1
G
G.1
H
J
J.1
J.5
J.4
Room
HX
(TYP.4)
(TYP.3)
LAB
4070C(E) RESTROOM
TOILET
4070B
EQUIPMENT RM
SD-2
435 CFM
SCAN
EXAM RM
NUCMED ALCOVE
CORRIDOR
LAB
4070D
EXAM RM
4070A
PET SCANNER
RECEPTION
CORRIDOR
CORRIDOR
HAC
G A
M M
A W
E L L C
O U
N T
E R
A
LAB
E X
A M
R M
EXAM RM
SCAN
EXAM RM
CLEAN UTILITY
TOILET
OFFICE
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
LAB
LAB
SHOWER
COMPUTER RM
TOILET
CORRIDOR
EQUIPMENT RM
AC
SD-2
450 CFM
SD-1
150 CFM
SD-1
150 CFM
EG-1
175 CFM
SD-2
340 CFM
EG-2
800 CFM
(TYP.2)
EG-2
730 CFM
EG-1
125 CFM
RAD STORAGE
AC
SD-2
50 CFM
EG-2
40 CFM
AC 4-5
AC 4-2
AC 4-1
AC 4-3AC 4-4
CONTROL
H
4.1 4.3 5.2 5.3
LIBRARY
QUIET
4078A
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:2
P
M
MH-102
LEVEL 4 - MECHANICAL REMODEL
10/02/2020 EG SS
SHEET NOTES:
NEW SIEMENS HEAT EXCHANGER SUPPLIED BY VA AND INSTALLED BY MECHANICAL
CONTRACTOR.
NEW INDOOR WALL MOUNTED FAN COIL UNIT.
VERIFY THERMOSTAT LOCATIONS WITH ARCHITECT PRIOR TO INSTALLATION.
RELATIVE HUMIDITY TRANSMITER.
REFER TO ARCHITECTURAL DRAWINGS FOR LEAD-LINING OF ANY PIPING, DUCTS, AND
DIFFUSERS LOCATED IN LEAD-LINED WALLS, CEILINGS, AND FLOORS.
1/4" = 1'-0"1
LEVEL 4 - MECHANICAL REMODEL
MH-102
Revisions: Date:
ISSUED FOR 65% C.D. 2019-04-12
ISSUED FOR 65% C.D. 2020-07-10
J
J.1
J.5
J.4
AV(E)
0.30
BV(E)
0.65
BV(E)
0.55
BV (E)
0.55
AV (E)
0.30
AV(E)
0.30
(TYP.3)
"x
12"ø
"ø
"ø
CAV
4-4
24"x16"
"x
10"ø
8"ø
8" ø
CAV
4-3
8"ø
CAV
4-1
"x
10"ø
"ø
CAV
4-5
CAV
4-2
2 2
"ø 12"ø
"ø
12"ø
12"ø
"ø
10"ø
14"ø 16"ø
12"ø
12"ø
"ø
/1 MH-102I-B/1 MH-102I-B
10"ø
"ø
24"x16"
4.1 4.3 5.2 5.3
RHT
AFS
TYP.
5 5
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:2
P
M
MH-102I-A
LEVEL 4 INTERSTITIAL - MECHANICAL
REMODEL
10/02/2020 EG SS
SHEET NOTES:
DASHED LINE DENOTES CATWALK AT 4TH FLOOR INTERSTITIAL SPACE.
PROVIDE NEW CAV BOX AT 4TH FLOOR INTERSTITIAL SPACE. ALL NEW CAV BOXES
TO BE INSTALLED IN CLOSE PROXIMITY TO CATWALKS TO ALLOW FOR FUTURE
MAINTENANCE.
RELATIVE HUMIDITY TRANSMITTER AND AIRFLOW SWITCH. INSTALL 8 TO 12 FEET
DOWNSTREAM FROM DISPERSION UNIT.
ALL NEW SUPPLY DUCTWORK TO BE INSULATED IN IT'S ENTIRETY. REFER TO
SPECIFICATIONS FOR ADDITIONAL DETAILS.
ALL NEW DUCTWORK AND EQUIPMENT TO BE SUPPORT FROM BUILDING STRUCTURE
AND NOT OTHER DUCTWORK, PIPING, OR CONDUITS.
1/4" = 1'-0"1
LEVEL 4 INTERSTITIAL - MECHANICAL REMODEL
MH-102I-A
Revisions: Date:
G
G.1
H
DV (E)
2.23
AV (E)
0.30
AV (E)
0.40
DV(E)
1.30
BV (E)
0.55
AV (E)
0.27
BV(E)
0.63
EV (E)
2.31
O S
A
3175 CFM
3355 CFM
(E) AC-22
(E)AC-22
(E)GX-30
CAP
GX
(E
G X
(E) AC- 57
24"x16"
"x
24"x16"
12"ø
"ø
8" ø
8"ø
6"ø
6"ø
EXHAUST AIR PLENUM CONNECTED TO
44"x24" EXHAUST GRILLE AT SOFFIT.
GRILLE SHALL BE ALUMINUM CONSTRUCTION
WITH EPOXY PAINT FOR COASTAL ENVIRONMENT.
SEE 1 / AE-204A AND 2 / AE-204A FOR DETAIL.
H
/1 MH-102I-A/1 MH-102I-A
4.1 4.3 5.2 5.3
AC
48"x24"7
MH-201
SD
MH-201
CP
AC420
VFD
SF-1
AC
VFD
SF-2
24"x72"
"x
44"x24"
3355 CFM
OSA INTAKE PLENUM CONNECTED TO
72"x24" OSA INTAKE GRILLE AT SOFFIT.
GRILLE SHALL BE ALUMINUM CONSTRUCTION
WITH EPOXY PAINT FOR COASTAL ENVIRONMENT.
SEE 1 / AE-204A AND 2 / AE-204A FOR DETAIL.
3175 CFM
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:3
P
M
MH-102I-B
LEVEL 4 INTERSTITIAL - MECHANICAL
REMODEL
10/02/2020 EG SS
SHEET NOTES:
DASHED LINE DENOTES CATWALK AT 4TH FLOOR INTERSTITIAL SPACE.
PROVIDE NEW AIR HANDLER AT 4TH FLOOR INTERSTITIAL SPACE. SEE EQUIPMENT
SECHEDULE ON SHEET MH-003 AND DETAIL 1 / MH-504.
PROVIDE NEW EXHAUST FAN AT 4TH FLOOR INTERSTITIAL SPACE.
PROVIDE STEAM HUMIDIFIER AT 4TH FLOOR INTERSTITIAL SPACE. SEE SCHEDULE ON
MH-003.
NEW CATWALK FOR AC-420. SEE STRUCTURAL DRAWING 15 / SF6 FOR ADDITIONAL
INFORMATION AND DETAILS.
CLEARANCE FOR COIL SERVICE.
PROVIDE STAINLESS STEEL DUCT FOR OUTSIDE AIR INTAKE.
1/4" = 1'-0"1
LEVEL 4 INTERSTITIAL - MECHANICAL REMODEL
MH-102I-B
Revisions: Date:
4.2 5 5.1
K
L
TRANSFER
CENTER
HP
RS
RL
5 5.1
G
G.1
H
J
OFFICE (S)
6083B
HP
RL
RS
4.2 5 5.1
H
J
J.1
KEYPLAN - LEVEL 6
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:3
P
M
MH-103
MECHANICAL PLAN REMODEL
10/02/2020 EG SS
1/4" = 1'-0"1
LEVEL 4 - MECHANICAL REMODEL PARTIAL PLAN
1/4" = 1'-0"2
LEVEL 6 - MECHANICAL REMODEL PARTIAL PLAN
SHEET NOTES:
EXISTING COOLING UNIT (DRY COOLER) TO REMAIN.
NEW SIEMENS DRYCOOLER SUPPLIED BY VA AND INSTALLED BY MECHANICAL
CONTRACTOR. MECHANICAL CONTRACTOR RESPONSIBLE FOR ALL SUPPLY AND
RETURN PIPING MATERIAL, INSULATION, SUPPORTS, AND ANCHORS, AND
INSTALLATION BETWEEN DRYCOOLER AND INDOOR UNIT. MECHANICAL
CONTRACTOR RESPONSIBLE FOR ANCHORAGE OF DRYCOOLER. SEE STRUCTRUAL
DRAWINGS FOR ADDITIONAL INFORMATION.
INSTALL PRIMARY COOLING CIRCUIT PIPES FROM SIEMENS OUTDOOR UNIT, DOWN
EXISTING SHAFT TO 4TH FLOOR INTERSTITIAL SPACE. CONNECT TO SIEMENS HEAT
EXCHANGER. SEE MH-104 FOR CONTINUATION. PIPING SUPPLIED BY AND INSTALLED
BY MECHANICAL CONTRACTOR.
PROVIDE OUTDOOR HEAT PUMP UNIT AT 6TH FLOOR.
ANCHOR UNIT PER DETAIL 5 / MH-502.
INSTALL REFRIGERANT PIPES FROM HP UNIT TO FAN COIL UNIT AT 4TH FLOOR. RUN
PIPE DOWN THROUGH EXISTING SHAFT. SEE SHEET MH-104 FOR CONTINUATION.
PROVIDE OUTDOOR HEAT PUMP UNIT AT 4TH FLOOR.
ANCHOR PER DETAIL 5 / MH-502.
INSTALL REFRIGERANT PIPES FROM HP UNIT TO FAN COIL UNIT. PIPES AT 4th FLOOR
INTERSTITIAL SPACE. SEE SHEET MH-104 FOR CONTINUATION. FOR SIZES, REFER TO
MANUFACTURER'S RECOMMENDATION.
INSTALL SECONDARY COOLING CIRCUIT PIPES FROM SIEMENS HEAT EXCHANGER
INDOOR UNIT TO SIEMENS GANTRY. SEE PIPING SCHEMATIC ON SHEET MH-501
(2) 1" HIGH PRESSURE WATER HOSES SUPPLIED BY SIEMENS AND INSTALLED BY
MECHANICAL CONTRACTOR AT CEILING OF 3RD FLOOR INTERSTITIAL SPACE.
REFER TO ARCHITECTURAL DRAWINGS FOR LEAD-LINING OF ANY PIPING, DUCTS,
AND DIFFUSERS LOCATED IN LEAD-LINED WALLS, CEILINGS, AND FLOORS.
1/4" = 1'-0"3
LEVEL 3 INTERSTITIAL - MECHANICAL PIPING
MH-103
MH-103
Revisions: Date:
ISSUED FOR 65% C.D. 2020-07-10
2.1 33.1 3.2 4 4.2 5 5.1 6 7 7.1 8 9 9.1 9.5 9.4
G
G.1
H
J
J.1
J.5
J.4
K
L
L.1
M
(N) 1-1/2" CHS & CHR
(N) 1-1/2" CHS & CHR
AV(E)
0.30
BV(E)
0.65
BV(E)
0.55
AV(E)
0.30
DV (E)
1.30
BV (E)
0.55
AV (E)
0.30
DV (E)
2.23
AV (E)
0.30
AV (E)
0.40
BV(E)
0.55
AV (E)
0.27
GX
(E
A C
(E) AC- 22
(E) GX- 109
H
CAV
4-5
CAV
4-2
CAV
4-1
CAV
4-4
CAV
4-3
(E) 4" PHWS & PHWR (RISER #3)
(E) 6" RHWS & RHWR (RISER #3)
(N) 1" PHWS & PHWR
(N) 1" RHWS & RHWR
(E) 6" CHS & CHR (RISER #4)
(N) 1" PHWS & PHWR
(N) 1-1/2" CHS & CHR
(N) 1" RHWS & RHWR
MH-201
MH-201
KEYPLAN- LEVEL 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:4
P
M
MH-104
LEVEL 4 INTERSTITIAL - MECHANICAL PIPING
10/02/2020 EG SS
SHEET NOTES:
PIPES AT 4TH FLOOR INTERSTITIAL SPACE.
ROUTE PIPE IN EXISTING SHAFT AND UP TO 6TH FLOOR. SEE 2 / MH-103 FOR
CONTINUATION
CONNECT REFRIGERANT PIPE TO OUTDOOR HEAT PUMP UNIT AT FOURTH FLOOR.
SEE SHEET 1/MH-103 FOR LOCATION.
CONNECT 3/4" HWS AND HWR PIPES TO RE-HEAT COIL PER DETAIL 4 / MH-504.
CONNECT CHS AND CHR PIPES TO AC UNIT PER DETAIL 5 / MH-504.
(N) AIRHANDLING UNIT AT 4TH FLOOR INTERSTITIAL SPACE.
CONNECT REFRIGERANT PIPE TO WALL MOUNTED INDOOR FAN COIL UNIT AT
FOURTH FLOOR. SEE SHEET MH-102 FOR LOCATION.
DASH LINE DENOTES EXISTING CATWALK.
PROVIDE STEAM HUMIDIFIER. SEE SCHEDULE ON MH-003.
STEAM DISPERSION ASSEMBLY IN SUPPLY AIR DUCT.
INSTALL PRIMARY COOLING CIRCUIT PIPES FROM SIEMENS HEAT EXCHANGER
INDOOR UNIT TO SIEMENS OUTDOOR UNIT AT 6TH FLOOR. SEE PIPING SCHEMATIC
ON SHEET MH-501.
1/8" = 1'-0"1
4TH FLOOR INTERSTITIAL-NEW PIPING
MH-104
Revisions: Date:
ISSUED FOR 65% C.D. 2020-07-10
SCAN
SCAN
ROOM
COMPUTER
ROOM
EXAM
EXAM RM
LINEN
(S)
TOILET
CORR.
SCAN
4286A
RM
EXAM
RM
EXAM
OFFICE(S)
OFFICE(S)
OFFICE(S)
437O
OFFICE(S)
OFFICE
4088B
OFFICE(S)
4088C (S)
OFFICE
4518A
OFFICE(S)
OFFICE(S)
OFFICE(S)
OFFICE(S)
OFFICE(S)
OFFICE(S)
OFFICE(S)
OFFICE(S) 4081
OFFICE(S)
OFFICE(S)
4086A
OFFICE(S)
OFFICE
OFFICE
OFFICE
4025C
OFFICE
4025B
OFFICE
4025A
OFFICE
4024C
OFFICE
4024B
OFFICE
4024A
OFFICE
OFFICE
OFFICE
OFFICE
4085D
EXAM RM
4085C
EXAM RM
4085B
EXAM RM
EXAM RM
4085A
EXAM RM
EXAM RM
RM
EXAM
OFFICE(S)
OFFICE(S)
OFFICE(S)
RM
EXAM
TOILET(S)
4006A
PHYSICIAN
PHYSICIAN
RESIDENT
ONE BED
RESIDENT
ONE BED
BREAK RM LAUNDRY
CORR.
CORR.
4157A
TOI.
PHYSICIAN
CONFERENCE
BREAK
(S)
OFFICE
CONFERENCE 4039
CORR.
SCANNER
PET
LAB
LAB 4064
LAB
TOI.
SHOWER
4070A
RM
EXAM
4070C
LAB
4070D
LAB
CORR.
CORR.
RECEPTION
CORR.
CORR.
MED
NUC
4070B
TOILET
NURSING
EDUCATION
MULTI OFF.
CORR.
4078A
QUIET
4078B
LAB
COMPUTER
LIBRARY
CORR.
CORR.
4027B
STOR.
FILM
PHYSICIAN4027A
HAC
HAC
4027C
CORR.
SW9-4
STAIR
CORR.
4016A
STOR.
GEN.
THERAPY
RESP
LAB
SIM
OFFICE(S)
CORR.4015A
CONTROL
4000B
LOBBY
LOBBY
SW10-4
STAIR
T AND L
4158A
TOI. (M)
4000A
RECEPTION
RESTROOM
(E)
4500A
COUNTER
GAMMA WELL
CORR.
EP LAB
EXAM ROOM
SCRUB RM
ROOM
EQUIPMENT
TRANSFER
CENTER
4039A
OFFICE
RECEPTION
4039A
CORRIDOR
OFFICE(S)
OFFICE(S)
OFFICE
STUDIO
4046B
OFFICE
4046A
STUDIO
STUDIO
ILLUSTRATION
40465A
STUDIO
STUDIO
STUDIO
4049B
STUDIO
40465B
STUDIO
EP LAB
OFFICE
OFFICE(S)
KEYPLAN- LEVEL 4
2.1
2.1
3.1
3.1
3.2
3.2
4.2
4.2
5.1
5.1
7.1
7.1
9.1
9.1
9.5
9.5
9.4
9.4
G
G.1
H
J
J.1
J.5
J.4
K
L
L.1
M
AC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:4
P
M
MH-105
AIRHANDLING UNIT 420 - PATH OF TRAVEL
10/02/2020 EG SS
SHEET NOTES:
LIFT AHU SECTIONS INTO PLACE FROM 4TH FLOOR LIBRARY SPACE AND QUITE ROOM.
REFER TO STRUCTURAL DRAWING 1 / SF4 AND 1 / SF6 FOR TEMPORARY STRUCTURAL
MEMBER REMOVAL INFORMATION. MAXIMUM AHU SECTION SIZE 59”x78”x44”
AHU SECTIONS TO BE TRANSPORTED UP TO 4TH FLOOR VIA THE SERVICE ELEVATOR
PROPOSED PATH OF EQUIPMENT TRAVEL
MH-105
1/8" = 1'-0"1
LEVEL 4 -PATH OF TRAVEL
1. PROTECT FLOOR WHEN TRANSPORTING AHU SECTIONS INCLUDING WITHIN
ELEVATOR
2. TRANSPORT AHU SECTIONS ON ROLLERS TO THEIR FINAL INSTALLATION LOCATION
3. ATTENTION REQUIRED TO ANYTHING THAT EXTENDS BELOW CEILING (EX SIGNAGE
AND EMERGENCY LIGHTING)
4. PROTECT DOORS AND CASES WHEN HAVING TO TURN SECTION IN DIFFERENT
ROOMS
5. COORDINATE WITH HOSPITAL FOR PREVIOUSLY REMOVING ANY OBSTRUCTIONS
TO THE PATH OF TRAVEL
6. ENCLOSE AREA FROM ANY PERSONNEL OR PATIENT COMMUTE.
GENERAL NOTES:
Revisions: Date:
5.1
LEVEL 4
51' - 9"
LEVEL 4
INTERSTITIAL
61' - 9 1/2"
LEVEL 5
69' - 0"
CEILING
60' - 9"
5.2
AC
5' - 10" 6' - 0"
MH-201
GG.1H
LEVEL 4
51' - 9"
LEVEL 4
INTERSTITIAL
61' - 9 1/2"
LEVEL 5
69' - 0"
CEILING
60' - 9"
MH-201
2' - 2" 14' - 8"
" AC
3 1
O S
A
16"x24"
LIBRARY
QUIET
4078A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
C
L o c a l R e v it F ile s \1
X
.0
-V
A S
D -N u c -M e d
M e c h
R
V T
S u h a il-
ID
S .r v t
/2 /2
:0
:4
P
M
MH-201
MECHANICAL SECTION
10/02/2020 EG SS
SHEET NOTES:
EXISTING CATWALK AT 4TH FLOOR INTERSTITIAL SPACE.
NEW AIR HANDLER AT 4TH FLOOR INTERSTITIAL SPACE.
NEW CATWALK FOR AC-420.
CLEARANCE FOR COIL SERVICE.
1/4" = 1'-0"2
AC-420 SECTION B
1/4" = 1'-0"1
AC-420 SECTION A
Revisions: Date:
SINK DRAIN
CONDENSATE DRAIN NOTES:
A WATER DRAIN IS REQUIRED TO BE SUPPLIED AND INSTALLED BY THE
MECHANICAL CONTRACTOR TO DRAIN CONDENSED WATER FROM THE
GANTRY. THE DRAIN MUST BE WITHIN 32'-9" OF THE GANTRY. THE HOSE MAY
BE EXTENDED ON-SITE UP TO 65'-7" BY THE MECHANICAL CONTRACTOR. THE
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR DETERMINING WHICH
DRAIN TYPE TO USE AND FOR SPECIFYING, SUPPLYING AND INSTALLING THE
PLUMBING FIXTURES NECESSARY TO CONNECT THE SIEMENS WATER HOSE
TO THE SELECTED DRAIN.
THE MAX. FLOW RATE OF THE CONDENSED WATER IS 0.53 GALLONS/HR AT
75% RELATIVE HUMIDITY.
GANTRY (BACK
SIDE)
WALL
SINK
SIEMENS CONDENSATION WATER
HOSE (LENGTH: 32'-9",OUTSIDE
DIA. 3/8"). MAX. BENDING RADIUS
1 3/16".
WATER
DRAIN
HOSE
OUTLET
EX. CABLE
DUCT
H E
IG
H
T A
.F .F
THE WATER-AIR SPLIT COOLING SYSTEM IS DELIVERED AS A PRE-INSTALLATION KIT. IT MUST BE
INSTALLED PRIOR TO DELIVERY OF THE SYSTEM BY THE MECHANICAL CONTRACTOR. THE
FOLLOWING IS INCLUDED IN THE PRE-INSTALLATION KIT: OUTDOOR COOLING UNIT, INDOOR HEAT
EXCHANGER CABINET, HOSES AND SYSTEM CABLES, CONNECTION KIT AND CONNECTION
SCHEMATIC.
THE COOLING CIRCUIT BETWEEN THE OUTDOOR UNIT AND THE INDOOR UNIT IS THE PRIMARY
COOLING CIRCUIT. THE COOLING CIRCUIT BETWEEN THE GANTRY AND THE INDOOR COOLING UNIT
IS THE SECONDARY COOLING CIRCUIT. FILLING OF THE PRIMARY COOLING CIRCUIT MUST BE
PERFORMED BY THE MECHANICAL CONTRACTOR LOCAL SPECIALIST FOR THE WATER
INSTALLATIONS (A PLUMBER). THE STATIC FILL PRESSURE MUST BE SET TO 29 PSI ±3 PSI AFTER FILLING. THE PUMP IN THE PRIMARY COOLING CIRCUIT GENERATES AN OPERATING PRESSURE OF 29-73 PSI AT THE PUMP OUTLET. THE PUMP IN THE SECONDARY COOLING CIRCUIT GENERATES AN OPERATING PRESSURE OF 58-73 PSI AT THE PUMP OUTLET. THE WATER VOLUME IN THE PRIMARY
COOLING CIRCUIT IS APPROX. 20 GALLONS. THE WATER VOLUME IN THE SECONDARY COOLING
CIRCUIT IS APPROX. 13.2 GALLONS, NOT INCLUDING ANY HOSE EXTENSIONS. A 3/4" HOSE BIB AND A WATER DRAIN (EX. SINK) MUST BE AVAILABLE IN THE EQUIPMENT ROOM OR IN THE SCAN ROOM
NEAR THE HEAT EXCHANGER FOR FILLING THE COOLING CIRCUITS.
SIEMENS
OUTDOOR UNIT
(FRONT)
SIEMENS
HEAT EXCHANGER
INDOOR UNIT
(FRONT) SIEMENS GANTRY
(BACK SIDE)
HEAT EXCHANGER:
DUE TO THE HIGH NOISE (<60dB), IT IS
RECOMMENDED TO INSTALL THE HEAT
EXCHANGER IN THE EQUIPMENT ROOM. THE
HEAT EXCHANGER MAY BE INSTALLED TO THE
LEFT OR RIGHT OF THE PDC OR INDEPENDENT
OF THE PDC CABINET.
CHILLED WATER HOSES (SECONDARY COOLING
CIRCUIT):
SIEMENS SUPPLIES THE 2 - 1" HIGH PRESSURE
WATER SUPPLY AND WATER RETURN HOSES
WITH 1/2" INSULATION FOR THE BIOGRAPH
VISION THAT TERMINATE INTO THE SUPPLY /
RETURN MANIFOLDS THAT ARE SUPPLIED AND
INSTALLED BY SIEMENS. THE MAXIMUM LENGTH
OF THE WATER SUPPLY HOSE IS 90'-0" AND
WATER RETURN HOSES IS 90'-0". ACCEPTABLE
BENDING RADIUS OF THE HOSES IS 9".
IT IS VERY IMPORTANT TO RUN THE SUPPLY
WATER LINES ON THE LEFT AND THE
RETURN LINES ON THE RIGHT (WHEN THE
GANTRY IS VIEWED FROM THE FRONT). IT IS
RECOMMENDED THAT THE PLUMBING
INSTALLER DESIGNATE THE SUPPLY LINE.
THE SUPPLY/RETURN MANIFOLDS SUPPLIED
AND INSTALLED BY SIEMENS MUST BE
DIRECTED TO THE RIGHT (WHEN THE
GANTRY IS VIEWED FROM THE FRONT).
THE COOLING WATER SUPPLY TO THE
GANTRY, INCLUDING ALL FITTINGS,
PRESSURE REGULATORS AND SITE
CONTROL VALVES, ARE TO BE DESIGNED,
CONSTRUCTED AND TESTED BY THE
MECHANICAL CONTRACTOR.
THE SITE CONTROL VALVES MUST BE
READILY AVAILABLE AND EASILY
ACCESSIBLE FOR SHUTOFF AND SHOULD BE
LOCATED IN THE EQUIPMENT ROOM.
SIEMENS HEAT
EXCHANGER
INDOOR UNIT
(FRONT)
SIEMENS GANTRY
(BACK SIDE)
ADAPTER
1"
DN25 (2) SUPPLIED
BY SIEMENS.
SUPPLY/RETURN
MANIFOLDS
SUPPLY AND
INSTALL BY SIEMENS.
(2) 1" HIGH PRESSURE
WATER HOSES SUPPLIED
BY SIEMENS.
MAX. LENGTH 90'-0".
CHILLED WATER HOSES (PRIMARY LOOP)
THE CHILLED WATER HOSES ARE SUPPLIED IN THE FOLLOWING LENGTH ONLY:
1. 131 FEET. A 1 1/4" ∅ SUPPLY AND RETURN COPPER PIPES CAN BE USED INSTEAD OF THE
SIEMENS WATER HOSES, HOWEVER THE SUPPLIED WATER HOSES MUST BE CUT AND USED TO
CONNECT THE SIEMENS COMPONENTS TO THE COPPER PIPE. THE LENGTH MAY BE EXTENDED
FROM 131 FEET UP TO 196 FEET WITH MECHANICAL CONTRACTOR SUPPLIED 1 1/4" INNER ∅
COPPER PIPE USED WITH SIEMENS WATER HOSES OR FROM 131 FEET UP TO 328 FEET WITH
MECHANICAL CONTRACTOR SUPPLIED 2" INNER ∅ COPPER PIPE USED WITH SIEMENS WATER
HOSES. 20 ELBOW ADAPTERS (90 DEGREES) ARE PERMITTED WITHIN THE TOTAL RUN.
2. MECHANICAL CONTRACTOR TO PROVIDE BLEED VALVES INSTALLED AT THE HIGHEST POINT IN
THE PIPING RUN AND CUT OFF VALVES AT END OF THE SUPPLY AND RETURN. IF REQUIRED.
MECHANICAL CONTRACTOR TO SUPPLY AND INSTALL FITTINGS TO MATCH THE SELECTED PIPE
SIZE.
3. MECHANICAL CONTRACTOR TO INSULATE WITH 1/2" ARMAFLEX INSULATION, INCLUDING FLEX
HOSES.
4. IF THE SIEMENS WATER HOSES ARE EXTENDED (>131 FEET), THE LINE VOLTAGE/CONTROL CABLE
THAT RUNS FROM THE HEAT EXCHANGER CABINET TO THE OUTDOOR UNIT MUST ALSO BE
EXTENDED. THESE EXTENDED CABLES ARE AVAILABLE THROUGH SIEMENS.
SIEMENS
OUTDOOR UNIT
SIEMENS HEAT
EXCHANGER INDOOR
UNIT
(1 1/4" FEMALE NPT
SUPPLIED AND INSTALLED
BY MECHANICAL
CONTRACTOR)
SIEMENS SUPPLIED DN32 WATER HOSE
WITH DN25 ADAPTER CUT TO SUIT OR 1
1/4"∅ COPPER PIPES REQUIRE
1 1/4" NPT FEMALE SUPPLIED AND
INSTALLED BY MECHANICAL CONTRACTOR.
FLEXIBLE WATER HOSES
SUPPLIED WITH DRY
COOLER
FLEXIBLE
WATER
HOSES.
SUPPLIED
WITH
INDOOR
UNIT
MECHANICAL
CONTRACTOR
TO PROVIDE BLEED VALVES .
TOP
VIEW
FRONT
VIEW
WATER INLET FROM
OUTDOOR UNIT (PRIMARY
CIRCUIT)
WATER INLET TO
GANTRY
(SECONDARY
COOLING CIRCUIT)
WATER RETURN FROM
GANTRY (SECONDARY
COOLING CIRCUIT)
WATER RETURN TO
OUTDOOR UNIT (PRIMARY
CIRCUIT)
OPENINGS IN CABINET
BASE FOR ROUTING
HOSES AND CABLES
2 13/16"6 7/8"6 7/8"2 13/16"
4 7/8" 4 1/8"
8 1/2" 7 5/8"
3/
4"
/1 6"
1/
8"
2' -3
/4
.8
1'
-0
/4
1' -0
/4
/8 " 3'-1 5/8"
3'-3 3/8"
COG
6' -5
(E) 5" CONC. SLAB
ANGLE 3x3x1/4x2'-4"
WT. = 911 LBS
COG
ANGLE 3x3x1/4x2'-4"
(4) 1/2"Ø THROUGH BOLTS
(4) 1/2"Ø THROUGH BOLTS
SIDE VIEW
TOP VIEW
FRONT
VIEW
WEATHER
PROTECTION
AIR
INTAKE
CABLE
CONNECTION
BOX
OUTDOOR DRYCOOLER NOTES
1. DRYCOOLER UNIT TO BE INSTALLED BY MECHANICAL CONTRACTOR AND
MUST BE INSTALLED PRIOR TO INSTALLATION OF ASSOCIATED INDOOR
EQUIPMENT.
2. MOUNTING SURFACE FOR DRYCOOLER UNIT MUST BE FLAT AND LEVEL.
3. UNIT MUST BE BOLTED THROUGH THE FLOOR. SEE STRUCTURAL
DRAWINGS FOR ADDITIONAL INFORMATION.
WATER
INLET &
RETURN
WATER
INLET &
RETURN
SEE DETAIL A
(TYP.)
WATER
INLET &
RETURN
8'-4 13/16"
3' -6
/8
3'-11 1/4"2'-3 9/16"
3'-4 1/16"
3'-6 1/8"
6'-8 5/16"
8'-4 13/16"
3' -9
/1
6"
1' -7
1/
M
IN
F
O R
E X
H A
U S
T
MIN. SERVICEMIN. SERVICE
3/8"∅ (SS 316) HILTI KB-TZ W/ 2"
EMBED, 6" MINIMUM
EDGE DISTANCE. INSTALL W/
SPECIAL INSPECTION PER
ICC ESR 1917. (TYP. 4 PLCS.)
DETAIL A
SEE DETAIL A
(TYP.)
1. TESTING THE SITE WATER PUMP CAPACITY:
BEFORE INSTALLING THE BIOGRAPH VISION SCANNER, IT IS IMPORTANT TO HAVE THE SITE CONFIRM THAT THE SITE WATER PUMP IS CAPABLE OF MAINTAINING MINIMUM PRESSURE…