2020-1001 Electrical Set - Copy.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25821B0012
About this file
This solicitation is for construction services to fully renovate approximately 1,200 square feet of an existing Nuclear Medicine department to prepare the space for installation of a new PET CT scanner. The scope of work includes renovations in accordance with provided specifications, drawings, and statement of work. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The solicitation number is 36C25821B0012 and is titled "Y1DA--CONSTRUCTION 664-CSI-115 4W Nuclear Medicine PET CT II."
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-001
ELECTRICAL GEN. NOTES, LEGEND &
ABBREVIATION
10/02/20 RO GA
SINGLE LINE
CONDUIT ONLY
CIRCUIT BREAKER
AMP SWITCH
COMMUNICATION
CABINET
AMPERE
MOUNTED
MINIMUM
MECHANICAL
MAIN CIRCUIT BREAKER
LABORATORY INFORMATION
MANAGEMENT SYSTEM
FEET OR FOOT
FIXTURE
DEMOLITION/DEMOLISH
ELECTRICAL
NATIONAL ELECTRICAL
HEATING, VENTILATING &
DISCONNECT
DRAWING
GROUND FAULT CIRCUIT INTERRUPTER
KILOVOLT AMPERE
NATIONAL ELECTRICAL
MAIN LUGS ONLY
INTERMEDIATE METAL CONDUIT
AMERICAN WIRE GAUGE
CATALOG/CATEGORY
AMPERE INTERRUPTING CAPACITY
ARC FAULT, AMP FUSE
ABOVE FINISHED FLOOR
SHORT CIRCUIT AMPERES
INCH(ES)
NEMA
EMT
EM
FF
HP
GND
FT
IMC
HVAC
EQUIP
FIXT
GFCI
MAX.
MIN.
ISC
IN
KVA
MLO
NEC
NECA
KW
LIMS
MCB
MECH.
MTD
EQUIPMENT
EMERGENCY
ELECTRICAL METALLIC TUBING
GROUND
FINISHED FLOOR
NATIONAL ELECTRICAL CODE
MAXIMUM
KILOWATT
DWG
AIC
AS
AFF
C/B
COMM
CAB
AF
CAT
CKT
CLG
CU
AWG
CO, EC
C
A
ELECT.
(D)
EA
DISC.
CIRCUIT
COPPER
CEILING
CONDUIT
EACH
BLDG BUILDING
(E), EXIST EXISTING
KCMIL,MCM THOUSAND CIRCULAR MILS
NORMALLY CLOSEDNC
FLEXIBLE METALLIC CONDUIT (STEEL)FLEX
JUNCTION BOXJB,J-BOX
LEDFLUOR
DOWNDN
BC BARE COPPER
INTERNATIONAL RESIDENTIAL CODE
INTERNATIONAL BUILDING CODE
IBC
NOT IN CONTRACT
PANEL
POWER
RECEPTACLE
REQUIRED
SECTION
QUANTITY
NEVADA POWER COMPANY
NORMALLY OPEN
NOT TO SCALE
SCHEDULE
OVERCURRENT PROTECTION
NATIONAL FIRE CODE
NEUTRAL
NIC
NEUT
NFC
NL
PH
NPCO
SPEC
SP
OCP
SECT
SCHED
REQ'D
RECEP
PWR
PNL
NTS
QTY
NO
NIGHT LIGHT
SINGLE POLE
SPECIFICATION
PHASE
POLEP
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCH GEAR
SYS SYSTEM
TEMP TEMPORARY
TELE TELEPHONE
XFMR TRANSFORMER
UBC UNIFORM BUILDING CODE
UL UNLESS NOTED OTHERWISE
V VOLT OR VOLTAGE
VP VAPOR PROOF
TYP. TYPICAL
W WATT, WIRE
WP UL LISTED WEATHERPROOF,
NON-FUSIBLENF
POLYVINYL CHLORIDEPVC
VD VOLTAGE DROP
VA VOLT AMPERE
MANUFACTURERS ASSOCIATION
CONTRACTOR'S ASSOCIATION
28. ALL PENETRATIONS OF FIRE RATED FLOOR OR WALL ASSEMBLIES SHALL BE PROTECTED
BY MATERIALS AND INSTALLATION DIAGRAMS THAT CONFORM TO UL LISTING FOR
"THROUGH-PENETRATION FIRE STOP SYSTEMS".FIRESTOPPING SHALL MATCH F, T, W, AND L
RATINGS OF FLOOR AND WALL ASSEMBLIES.
29. CONTRACTOR SHALL ENGAGE THE SERVICES FOR A STATE LICENSED FIRE ALARM
MANUFACTURER/INSTALLER TO PREPARE ALL DESIGN DRAWINGS AND CALCULATIONS
REQUIRED FOR SYSTEM APPROVAL BY THE AUTHORITY HAVING JURISDICTION.
SUBMIT ALL PLANS AND PROVIDE ALL PERMITS REQUIRED FOR A COMPLETE AND
OPERABLE APPROVED LIFE SAFETY SYSTEM.
30. ALL FIRE ALARM DEVICE WIRING SHALL BE CLASSIFIED PER NFPA 72. FIRE ALARM DEVICE WIRING
SHALL BE MINIMUM #14 AWG COPPER OR PER SYSTEM MANUFACTURER REQUIREMENTS.
PROVIDE MINIMUM 3/4" SEPARATE RACEWAY SYSTEM OR AS REQUIRED FOR LIFE SAFETY SYSTEM
WIRING CONFIGURATION.
31. UPON COMPLETION OF THE INSTALLATION OF LIFE SAFETY SYSTEM WIRING AND
DEVICES, A PERFORMANCE TEST OF THE ENTIRE LIFE SAFETY SHALL BE
PERFORMED TO THE SATISFACTION OF THE AUTHORITY HAVING JURISDICTION.
32. ALL EQUIPMENT ELECTRICAL TERMINATIONS TO UNDERGO A TORQUE TEST.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MANUFACTURER'S RECOMMENDED
TORQUE DOCUMENTATION AND TOOLS TO PERFORM TORQUE TEST. CONTRACTOR SHALL APPLY
UL TABLE 486A-B WHERE THE MANUFACTURER DOES NOT PROVIDE TORQUE
RECOMMENDATIONS.
33. ALL UNDERGROUND SERVICE CONDUITS SHALL BE SEALED PER NEC ARTICLE 230-8.
34. FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE MOUNTED ON A 4" HIGH
CONCRETE PAD.
35. INSTALL TRANSFORMER FOLLOWING MANUFACTURER'S RECOMMENDATIONS FOR
VENTILATION CLEARANCES.
36. PRIOR TO WORK COORDINATE ELECTRICAL REQUIREMENTS FOR ALL PLUMBING AND MECHANICAL
EQUIPMENT WITH FINAL CONTRACTOR SELECTION. THE CONTRACTOR SHALL SIZE
DISCONNECTS BASED UPON CIRCUIT BREAKER RATINGS AND PROVIDE FUSING AS
REQUIRED PER EQUIPMENT MANUFACTURER RECOMMENDATIONS AND U.L. LISTING
REQUIREMENTS.
37. PROVIDE #10 AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS LONGER
THAN 75' AND #8 AWG CONDUCTORS FOR 20 AMPERE, 120V BRANCH CIRCUITS
LONGER THAN 120'. PROVIDE #10 AWG CONDUCTORS FOR 20 AMPERE, 277V
BRANCH CIRCUITS LONGER THAN 200'.
UNDERGROUND PULL SECTIONUGPS
AIR CONDITIONING
NEMA 3R
TELEVISION OUTLET
TELEPHONE/COMPUTER OUTLET-MOUNTED 450MM (18")AFF
UNLESS OTHERWISE NOTED
ELECTRICAL STRIP MOLD-NEMA 5-20R
RECEPTACLES AT 600MM(2'-0")INTERVALS
SERVICE CABLE TERMINATION
CIRCUIT BREAKER
FUSE
FUSED DISCONNECT SWITCH
SWITCH
SURGE SUPPRESSOR
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
GROUNDING ELECTRODE
POWER METER
MOTOR
GENERATOR
SHUNT TRIP
GROUND FAULT INTERRUPT
TRANSFER SWITCH
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP
MOUNTED 450MM (18")AFF UNLESS OTHERWISE NOTED
CONTACT (NORMALLY OPEN)
CONTACT (NORMALLY CLOSED)
TIME SWITCH
CONTROL SWITCH
PUSH BUTTON
DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP
MOUNTED ABOVE COUNTER TOP
UNDERWRITERS LABORATORYU.N.O.
DUPLEX RECEPTACLE WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED ABOVE COUNTER TOP
WEATHERPROOF DUPLEX RECEPTACLE WITH GFI, NEMA
5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
QUADRAPLEX OUTLET, NEMA 5-20R-20AMP-MOUNTED
450MM (18")AFF OR QUADRAPLEX OUTLET, NEMA
5-20R-20AMP-PEDESTAL-MOUNTED
QUADRAPLEX OUTLET, NEMA 5-20R-20AMP-MOUNTED
ABOVE COUNTER TOP
QUADRAPLEX OUTLET WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED 450MM (18")AFF UNLESS
OTHERWISE NOTED
QUADRAPLEX OUTLET WITH GROUND FAULT INTERRUPTER,
NEMA 5-20R-20AMP-MOUNTED ABOVE COUNTER TOP
DUPLEX RECEPTACLE, NEMA 5-20R-20AMP-EMERGENCY
POWER-MOUNTED 450MM (18")AFF UNLESS OTHERWISE
NOTED
QUADRAPLEX RECEPTACLE, NEMA
5-20R-20AMP-EMERGENCY POWER
SPECIAL RECEPTACLE
WALL MOUNTED TELEPHONE/COMPUTER OUTLET-
MOUNTED AT 1200MM (48")AFF UNLESS OTHERWISE NOTED
SPEAKER-CEILING MOUNTED
INTERCOM OUTLET
NURSE CALL DOME LIGHT-CEILING MOUNTED
NURSE CALL DOME LIGHT-WALL MOUNTED
NURSE CALL DUTY STATION
EMERGENCY NURSE CALL
NURSE CALL STAFF STATION
VOLUME CONTROL-WALL MOUNTED
JUNCTION BOX-PURPOSE AND LOCATION AS NOTED
SINGLE POLE SWITCH
SINGLE POLE SWITCH-SUFFIX OF a,b OR c INDICATES
SEPARATE CONTROL OR FIXTURES WITH SAME DESIGNATION
DIMMER SWITCH
THREE WAY SWITCH
DOOR SWITCH
FUSED OR UNFUSED DISCONNECT SWITCH
2'x2' LED FIXTURE
1'x4' LINEAR LED FIXTURE
2'x4' FLUORESCENT FIXTURE
WALL MOUNTED FLUORESCENT FIXTURE
2'x2' LED FIXTURE-EMERGENCY POWER
2'x4' FLUORESCENT FIXTURE-EMERGENCY POWER
WALL MOUNTED FLUORESCENT FIXTURE-EMERGENCY
POWER
WALL MOUNTED LIGHT FIXTURE-TYPE AS NOTED
LIGHT FIXTURE-TYPE AS NOTED
LIGHT FIXTURE-TYPE AS NOTED EMERGENCY POWER
CIRCUIT BREAKER
BATTERY POWERED CLOCK
EMERGENCY BATTERY UNIT WITH HEADS
DUAL TECHNOLOGY OCCUPANCY SENSOR - CEILING
DUAL TECHNOLOGY OCCUPANCY SENSOR - WALL
A
GFI
GFI-A
WP
A
GFI
GFI-A
w
D
E
S a
D os
NOTES NOTES (CONT'D.)
ST
TVSS
G
M
GFI
S
I
N
N
N
N
N
V
J
DS
CB
C
POWER
LIGHTING SIGNAL
STANDARD ABBREVIATIONS
GENERAL ELECTRICAL NOTES SHEET NUMBER SHEET NAME
EP-001 ELECTRICAL GEN. NOTES, LEGEND & ABBREVIATION
EP-002 SINGLE LINE DIAGRAM
EP-003 ELECTRICAL PANEL SCHEDULES
EP-004 VOLTAGE DROP CALCULATIONS & LOAD SUMMARY
EP-005 TITLE 24 COMPLIANCE DOCUMENTS
EP-100 ELECTRICAL 4TH FLOOR - OVERALL
EP-101 ELECTRICAL 4TH INTERSTITIAL - ENLARGED PLANS
EP-102 ELECTRICAL 4TH FLOOR - AREA OF WORK DEMOLITION
EP-103 4TH FLOOR-AREA OF WORK REMODEL- LIGHTING
EP-104 4TH FLOOR-AREA OF WORK REMODEL-POWER
EP-105 ELECTRICAL ENLARGED PLAN - INTERSTITIAL
EP-106 ELECTRICAL ENLARGED PLAN - EXTERIOR
EP-300 ELECTRICAL LIGHTING CONTROL
EP-301 ELECTRICAL LIGHTING CONTROL SINGLE LINE DIAGRAM
EP-501 PET/CT SCANNER
EP-502 PET/CT SCANNER
EP-503 PET/CT SCANNER
EP-504 PET/CT SCANNER
EP-505 PET/CT SCANNER
EP-600 LIGHTING DETAILS
EP-601 POWER DETAILS
EP-602 POWER DETAILS
EP-603 TELECOM DETAILS
EP-701 4TH FLR- AREA OF WORK REMODEL - PHOTOMETRICS
EP-702 4TH FLR- AREA OF WORK REMODEL - EGRESS PHOTOMETRICS
ISSUED FOR 100% C.D. 2020-10-02
TV
CB CODE BLUE INITIATION STATION
LIGHTINGLTG
PANELBOARD - SURFACE MOUNT
NOT FOR CONSTRUCTION
REVISION SYMBOL
SCHEDULED EQUIPMENT
KEYNOTE SYMBOL
EQUIPMENT TAG
DIAGRAM TAG
WIRELESS APPLICATION PROTOCOL
SWITCH BANK
XX
SHEET
UNIT
X
WAP
MISCELLANEOUS
SB
SINGLE POLE THERMAL RATED MOTOR STARTER SWITCH
M
DOUBLE POLE THERMAL RATED MOTOR STARTER SWITCH
38. FUSES SHALL BE PROVIDED WITH REJECTION TYPE FUSE HOLDERS.
NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALL BE PERMITTED
TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THE ELECTRICAL EQUIPMENT.
CONTRACTOR SHALL PROVIDE DIMENSIONED SHOP DRAWINGS FOR ALL ELECTRICAL
EQUIPMENT.
CONTRACTOR SHALL COORDINATE WITH ALL DICIPLINES AND PROVIDE DIMENSIONED
SUBMITTAL DRAWINGS FOR ALL CONDUIT, PIPE AND WALL DUCTWORK, SUBMITTAL DRAWINGS
SHALL INCLUDE SIZES, DIMESSIONS AND ELEVATIONS FROM BUILDING WALLS, FLOORS AND
DECKS.
CONTRACTOR SHALL COORDIANTE WITH ALL DISCIPLINES AND ROUTE ELECTRICAL BRANCH
CIRCUIT CONDUITS WITH MECHANICAL PIPING WHERE POSSIBLE.
EMERGENCY POWER OFF (EPO) PUSH BUTTON
EXIT SIGN - CEILING MOUNTED
LINEAR LED STRIP FIXTURE
LINEAR LED STRIP FIXTURE - EMERGENCY POWER
TELEPHONE BACKBOARD
OS
TRANSFORMER
T
FUSE (> 600V)
DOOR SWITCHDS
EMERGENCY POWER OFF PUSH BUTTON
(HEIGHT NOTED ON PLANS)
EPO
39.
40.
41.
CONDUIT CAP-OFF
HOMERUN TO PANELBOARD 1/2"C W/3#12
CONDUCTORS UNO
RACEWAY TURNED DOWN
RACEWAY TURNED UP
RACEWAY W/#12 CONDUCTORS UNO
CONDUIT ROUTED UNDERFLOOR / UNDERGROUND
CONDUIT WITH TICKS FOR NUMBER & SIZE OF
CONDUCTOR#10
WIRING
1. ELECTRICAL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN ACCORDANCE WITH
THE NECA INSTALLATION STANDARDS TO THE SATISFACTION OF THE ARCHITECT AND
ENGINEER.
2. ALL WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE CURRENTLY ACCEPTED
EDITION OF ALL APPLICABLE NATIONAL, STATE AND CITY CODES AND ORDINANCES.
3. ALL ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR NATIONALLY
RECOGNIZED TESTING FACILITY AS ALLOWED BY AUTHORITY HAVING JURISDICTION.
4. WHERE AN APPARENT DISCREPANCY EXISTS BETWEEN THE REQUIREMENTS OF THE GENERAL
NOTES AND/OR INFORMATION PORTRAYED IN THE ELECTRICAL DRAWINGS, THE CONTRACTOR
SHALL INCLUDE IN HIS BID THE COST OF THE GREATER QUALITY OR QUALITY.
5. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID AND VERIFY EXISTING CONDITIONS.
CONTRACTOR SHALL INCLUDE IN BASE BID ALL COSTS REQUIRED FOR PERMITS AND
INSPECTIONS.
6. CONTRACTOR SHALL VERIFY, WITH OWNER'S REPRESENTATIVE PRIOR TO SUBMITTING BID,
ALLOWABLE WORKING HOURS, EMPLOYEE PARKING AREAS, MATERIAL DELIVERY, STORAGE
REQUIREMENTS, DEMOLITION AND REMOVAL OF CONSTRUCTION DEBRIS, AS WELL AS DAILY
CLEAN UP REQUIREMENTS. INCLUDE ALL COSTS IN BID FOR DUST BARRIERS, INFECTION
CONTROL, DUMPSTERS ETC. AS REQUIRED FOR THE DURATION OF THE PROJECT. PERFORM
WORK AS DIRECTED BY OWNER'S REPRESENTATIVE AND ARCHITECT.
7. ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT
WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE ALL NECESSARY CORRECTIONS AT NO
ADDITIONAL COST TO OWNER.
8. CONTRACTOR SHALL GUARANTEE WORK AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP
WHICH MAY OCCUR UNDER NORMAL USE FOR A PERIOD OF ONE YEAR AFTER OWNER'S
ACCEPTANCE. DEFECTS SHALL BE PROMPTLY CORRECTED BY CONTRACTOR WITHOUT
ADDITIONAL CHARGE TO OWNER.
9. AS PART OF THE CLOSE-OUT FOR THE PROJECT, THE CONTRACTOR SHALL PROVIDE AS-BUILT
DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ACCURATE CONDUIT AND DEVICE
LOCATIONS DIMENSIONED FROM PERMANENT LANDMARKS SUCH AS BUILDING WALLS.
10. DO NOT SCALE ELECTRICAL DRAWINGS. VERIFY EXACT LOCATION OF ALL DEVICES, JUNCTION BOXES, LIGHTING FIXTURES WITH ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO
INSTALLATION. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF MECHANICAL
EQUIPMENT AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ROUGH-
IN. EVERY OUTLET HEIGHT SHALL BE VERIFIED ON EACH WALL WITH THE INTERIOR PLANNING
AND DESIGN DRAWINGS. COORDINATE WITH CABINET SHOP DRAWINGS TO ENSURE PROPER
HEIGHT AND LOCATION WITH RESPECT TO MILLWORK, EQUIPMENT.
11. THESE DRAWINGS INDICATE THE FINISHED REQUIREMENTS FOR THE ELECTRICAL SYSTEMS, EQUIPMENT, LIGHTING FIXTURES, OUTLETS AND DEVICES. DUE TO STRUCTURAL CONDITIONS, MECHANICAL DUCT, PIPING CONFLICTS, OR OTHER LEGITIMATE REASONS, THE CONTRACTOR
MAY DESIRE TO INSTALL THE WORK INDICATED IN A MANNER DIFFERENT FROM THAT SHOWN.
SUCH CHANGES SHALL BE PRESENTED TO THE OWNER'S REPRESENTATIVE FOR REVIEW AND
APPROVAL PRIOR TO PROCEEDING. UPON APPROVAL, THE WORK SHALL BE PERFORMED AND
THE AS-BUILT DRAWINGS SHALL BE REVISED TO ACCURATELY REFLECT THE WORK AS
ACTUALLY INSTALLED.
12. RACEWAY SYSTEMS ARE SHOWN DIAGRAMMATICALLY. ACTUAL LOCATION AND ROUTING OF
ALL, SHALL BE DETERMINED BY CONTRACTOR TO SUIT FILED CONDITIONS
13. PROVIDE DEDICATED NEUTRAL FOR EACH NEW CIRCUIT PER NEC 210.4. SHARED NEUTRALS
SHALL NOT BE ALLOWED ETWEEN LOADS FROM SEPERATE OVERCURRENT DEVICES.
HANDLETIES SHALL NOT BE ALLOWED AS A METHOD OF COMPLIANCE WITH NEC 210.4 BETWEEN
SEPERATE DEVICES. HOME RUN CONDUCTORS MAY BE COMBINED INTO ONE CONDUIT WITH
SEPARATE NEUTRALS FOR EACH CIRCUIT. NO RACEWAY OR CABLE SHALL CONTAIN MORE THAN
NINE (9) CURRENT CARRYING CONDUCTORS. NEUTRAL CONDUCTORS SHALL BE CONSIDERED
CURRENT CARRYING CONDUCTORS. WHERE MULTIPLE CONDUCTORS IN EXCESS OF THREE (3)
ARE INDICATED ON THESE DRAWINGS, THEY SHALL BE DERATED AS REQUIRED BY NEC ARTICLE
310 REQUIREMENTS.
14. RACEWAYS SHALL BE INSTALLED CONCEALED (IN CMU OR OTHER WALL) WHENEVER POSSIBLE.
RACEWAYS INSTALLED EXPOSED SHALL BE ROUTED OUT OF PUBLIC VIEW AS MUCH AS
POSSIBLE. RACEWAYS SHALL BE RUN PARALLEL WITH, OR AT RIGHT ANGLE TO WALLS.
15. PROVIDE APPROVED EXPANSION FITTINGS WHERE RACEWAYS CROSS BUILDING EXPANSION
JOINTS. PROVIDE BONDING JUMPER(S) SIZED PER CODE WHERE REQUIRED. PROVIDE FITTINGS
REQUIRED FOR A COMPLETE INSTALLATION. REFER TO ARCHITECTURAL DRAWINGS FOR
EXPANSION JOINT LOCATION(S).
16. MINIMUM RACEWAY SIZE SHALL BE 3/4". MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG U.N.O.
TYPICAL FOR ALL INTERIOR. MINIMUM CONDUCTOR SIZE FOR EXTERIOR SHALL BE #10 AWG
U.N.O. ALL POWER RELATED CONDUITS SHALL HAVE A GROUND WIRE INSTALLED IN EACH RUN
PER NEC 250.66.
17. CONTRACTOR SHALL PROVIDE PULL CORDS IN SPARE CONDUITS. WHERE MORE THAN ONE
CONDUIT TERMINATES IN A JUNCTION BOX, THE CONTRACTOR SHALL IDENTIFY EACH CONDUIT
AND JUNCTION BOX IN A MANNER ALLOWING IDENTIFICATION AFTER ALL WALL FINISHES HAVE
BEEN APPLIED.
18. CONTRACTOR SHALL PROVIDE ALL RACEWAY SYSTEMS INDICATED ON THE DRAWING PER NEC
REQUIREMENTS AND GENERAL NOTES. ANY DEVIATION FROM THE WIRING METHODS
INDICATED SHALL BE ALLOWED ONLY BY SPECIFIC WRITTEN APPROVAL FROM EITHER THE
ARCHITECT, ENGINEER OR OWNER. CONTRACTOR'S BID SHALL INCLUDE ALL COSTS FOR
RACEWAY SYSTEMS AS SPECIFIED UNLESS SPECIFIC WRITTEN APPROVAL FOR AN
ALTERNATIVE WIRING METHOD IS OBTAINED FROM EITHER THE ARCHITECT, ENGINEER OR
OWNER AND IS SUBMITTED AS PART OF CONTRACTOR'S FORMAL BID PROPOSAL.
19. CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECT SIZE AND INSTALLATION OF OUTLET,
PULL AND JUNCTION BOXES IN ACCORDANCE WITH NEC 314-16. BOXES SHALL BE MINIMUM 4"
SQUARE BY 1-1/2" DEEP OR AS INDICATED ON THE DRAWINGS. BOXES SHALL BE RECESSED
WITH COVER PLATE TO SUIT THE INTENDED APPLICATION.
20. PRIOR TO INSTALLATION, CONTRACTOR SHALL REVIEW THE COMPLETE SET OF CONSTRUCTION
DOCUMENTS FOR CONFLICTS WITH OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE TO
COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT DURING INSTALLATION.
CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS IN EQUIPMENT LOCATION AND ROUTING AS
NECESSARY AT NO ADDITIONAL COST TO THEOWNER.
21. CONTRACTOR SHALL BE RESPONSIBLE TO PROPERLY CUT AND PATCH EXISTING
CONSTRUCTION AS REQUIRED TO INSTALL NEW ELECTRICAL WORK. ALL PATCHING SHALL BE
OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS THE EXISTING WORK AND SHALL
ACCURATELY MATCH ALL SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT.
22. ALL ELECTRICAL EQUIPMENT SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO
ACCOMMODATE QUANTITY AND SIZE OF CONDUCTORS REQUIRED. CONTRACTORS SHALL
PROVIDE EQUIPMENT WITH OVERSIZED ENCLOSURES WHERE REQUIRED.
23. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE TYPE WRITTEN UPDATED PANEL
DIRECTORY WITH DATE AND INCLUDING ROOM NUMBER FOR ALL NEW EXISTING LOADS PER
NEC 408.4 TO BE MOUNTED ON INSIDE OF ALL PANEL DOOR COVERS. DIRECTORY SHALL
REFLECT ALL ADDITIONS OR MODIFICATIONS TO EXISTING PANELS AND SHALL REFLECT ACTUAL
"AS-BUILT" CONDITIONS. HANDWRITTEN DIRECTORIES OR MODIFICATIONS TO DIRECTORIES
ARE NOT ACCEPTABLE. LOAD DESCRIPTION SHALL NOT INCLUDE "EXISTING" OR "EXISTING
LOAD". ALL LOADS SHALL BE VERIFIED BY THE CONTRACTOR. PROVIDE DIRECTORIES AS A
CLOSE-OUT SUBMITTAL PER SPEICIFICATION SECTION 26 24 16 PANELBOARDS.
24. VERIFY DEVICE COLOR AND MOUNTING ORIENTATION (VERTICAL OR HORIZONTAL) WITH
ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO ORDERING ANY EQUIPMENT AND
PROVIDE DEVICES AS REQUIRED. UNLESS NOTED OTHERWISE, DEVICES AND DEVICE PLATES
SHALL BE WHITE IN COLOR.
25. WHERE MOTORS ARE INSTALLED IN SUSPENDED CEILINGS, CONTRACTOR SHALL PROVIDE
DISCONNECT SWITCH IN SUSPENDED CEILING WITHIN REACH FROM ACCESS POINT.
26. CONTRACTOR SHALL VERIFY ACTUAL MOTOR AND APPLIANCE RATING AND LOADS.
CONTRACTOR TO PROVIDE MOTOR OVERLOAD ELECTRICAL COMPONENTS BASED ON
NAMEPLATE RATING. REFLECT ANY CHANGES IN THE AS-BUILT DRAWINGS.
27. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ARCHITECT FOR REVIEW OF THE
FOLLOWING EQUIPMENT:
A. ELECTRICAL SWITCHGEAR: SWITCHBOARDS, PANELS, MOTOR CONTROL CENTERS AND
SAFETY SWITCH
B. TIME/CURRENT TRIP CURVES
C. LIGHTING FIXTURES: INDOOR/OUTDOOR AS PSECIFIED, PHOTOMETRIC PERFORMANCE
DATA AND LAMPS
D. DEVICES: SWITCHES, RECEPTACLES, MOTOR CONTROLLERS AND DEVICE PLATES
INCLUDING SHOP DRAWINGS FOR ALL LIGHTING CONTROLS.
E. LIFE SAFETY /FIRE ALARM SYSTEMS: CONTROL PANEL, ANNUNCIATOR PANEL,INITIATION
AND NOTIFICATION DEVICES / APPLIANCES, SYSTEM WIRING REQUIREMENTS AND
DIAGRAMS, SYSTEM LOCA CALCULATIONS, STAND-BY BATTERY CALCULATIONS, AND
AUXILIARY POWER SUPPLY
LIGHTING FIXTURE SCHEDULE
Type Mark Description Lamp Mounting Volts Manufacturer Model Wattage Notes
F1 2'X2' LED FIXTURE WITH 0-10V
DIMMING
LED RECESSED 120V DAYBRITE 2LTG27L840-2-21-UNV-D
IM-BAC
46 W
F1E 2'X2' LED FIXTURE WITH 0-10V
DIMMING
LED RECESSED 120V DAYBRITE 2LTG27L840-2-21-UNV-D
IM-BAC
46 W CONNECTED TO LIFE SAFETY
CIRCUIT
F2 6" LED DOWNLIGHT WITH 0-10V
DIMMING
LED RECESSED 120V LIGHTOLIER C6RN-BAC /
C6L25840WZ10U-BAC /
C6RDLCL-BAC
0 W
F2E 6" LED DOWNLIGHT WITH 0-10V
DIMMING
LED RECESSED 120V LIGHTOLIER C6RN-BAC /
C6L25840WZ10U-BAC /
C6RDLCL-BAC
0 W
F3 4' LINEAR LED STRIP FIXTURE WITH
0-10V DIMMING
LED SURFACE 120V DAYBRITE FSS440L840-UNV-DIM-B
AC
31 W
F3E 4' LINEAR LED STRIP FIXTURE WIRH
0-10V DIMMING
LED SURFACE 120V DAYBRITE FSS440L840-UNV-DIM-B
AC
31 W
X1 SINGLE FACE COMPACT EXIT SIGN GREEN SURFACE 120V CHLORIDE CLXNGW2C PROVIDE UNIVERSAL
MOUNTING KIT FOR SIDE,
END, TOP AND FACE
MOUNTING.
X-RAY X-RAY IN USE WARNING SIGN LED RECESSED 120V CHLORIDE AMS-120-GW-"X-RAY IN
USE"-CMB
COORDINATE REQUIRED
MOUNTING BRACKET FOR
SIDE OR CEILING MOUNT
Revisions: Date:
CEM1
H 11
5CE
L 8
PP4D
J5 5
4A
J3 4.2
4XC
E2 9.3
4XE
4CEXA
J5 5
225 A
150 AT
EMG SWITCH GEAR
800 A
800 AT
ATS 5
NE
800 A
70 AF
EDB1
800 A
800 AT
800 A
800 AT
1200A
1200AT
A B
100 A
70 AT
400 A
400 AT
100 A
100 AT
1200A TIE BREAKER
H 11
2CE
C D
1600 A
1200AT
225 A
150 AT
1200A TIE BREAKER
SWBD. B
225 A
150 AT
100 A
100 AT
100 A
70 AT
800 A
800 AT
SWBD. D
800 A
800 AT
225 A
200 AT
150 A
200 AF
J5 4.2
4XB
L 5.1
4XAA
L 5.1
4XA
D4A
N5 9.5
4D
60 A
60 AF
60 A
100 AF
L8
J5 4.2
4XCA
O1 9.5
4XQ
N 8
4XR
J3 5.1
4XD
150 A
200 AF
150 A
200 AF
150 A
200 AF
D4XA
L8
D4AA
N5 9.5
60 AF
60 A
4CCD
RM 4054
150 KVA
J5 14.1
150 A
200 AF
112.5 KVA
T16
T
D2 9.5D2 9.3
4XG
4XF
E2 10
4XH
200 A
200 AF
D4XB
H11
T17
4XK
J5 9.5
4XS
K 14.1
4XL
J5 13.3
4XM
J 13.3
4XJ
100 A
100 AF
175 A
200 AF
150 A
200 AF
T
800 A
800 AT800 AT
800 A 800 A
800 AT
100 AF
800 A
100 AF
800 A
CEM2-603
600 AF 250A400 AF
800 A
800 AF
800 A
600 AF 800 AF 100A225A
4CEXD
100 AF
100 A
H11
200 AF
150 A
200 AF
150 A
200 AF
175 A
100 AF
100 A
D4CEXA-234
T
4CEXB
E2 9.5
4CEXC
J5 13.3 O 9.5
T15-449
112.5 KVA
E N ATS 12
J5 5
4CEXA1
J5 5
4CEXAA
600 AF
800 A
BASEMENT
2ND INT'STIT.
1ST INT'STIT.
3RD INT'STIT.
4TH INT'STIT.
5TH INT'STIT.
4CEXE
9 N
ISC = 3,682A
ISC = 3,621A
ISC = 2,806A
ISC = 2,909 A
ISC = 5,408 A
ISC = 11,040A
ISC = 10,083AISC = 2,423A
NORMAL POWERCRITICAL POWER
SIEMENS
EQUIPMENT
PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-002
SINGLE LINE DIAGRAM
10/02/20 RO GA
1. AS REQUIRED ALL OVERSIZED FEEDERS THAT WERE ADJUSTED IN SIZE TO COMPENSATE FOR VOLTAGE DROP SHALL BE PROVIDED WITH ADAPTER LUGS OR SPLICE BOX. ADAPTER LUGS SHALL BE PROVIDED IF SIZE IS AVAILABLE, OTHERWISE PROVIDE CABLE SPLICES IN THE SPLICE BOX TO
REDUCE CABLES TO THE MAXIMUM SIZE THAT THE BREAKER LUGS CAN ACCOMMODATE.
2. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED FOR FINAL INSPECTIONS.
3. ALL CONDUCTORS SHALL BE 600V. RATED WITH THHN/THWN INSULATION AT 75° CELSIUS.
4. ALL CIRCUIT BREAKER TERMINALS IN SWITCHBOARDS AND PANEL BOARDS SHALL BE U.L LISTED
AND APPROVED FOR USE COPPER 75° CELSIUS CONDUCTORS.
5. ALL FINAL TERMINATION'S OF CONDUCTORS TO ELECTRICAL EQUIPMENT AND DEVICES SHALL BE
TORQUE WRENCH TIGHTENED TO THE MANUFACTURER'S RECOMMENDED SPECIFICATION, NO
EXCEPTION.
6. MINIMUM AIC SHALL BE 10,000 FOR 208/120-VOLT EQUIPMENT UNLESS NOTED.
AFFECTED BY SCOPE OF WORK.
REPLACE EXISTING 400AT/800AF/3P TO 600AT/800AF/3P. CIRCUIT BREAKER SHALL BE SAME
MANUFACTURER AS EXISTING AND SHALL HAVE A MINIMUM AIC RATING OF EQUIPMENT'S
AIC RATING.
PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR SIZED PER NEC 250.122 AS
REQUIRED PER NEC 517.14 AND BOND ALL PANELBOARDS SERVING PATIENT CARE AREAS.
PROVIDE 3#3/0, 1#6 GND., 2"C.
NOT FOR CONSTRUCTION
GENERAL NOTES
KEYNOTES
NO SCALEPARTIAL SINGLE LINE DIAGRAM 1
1 1
(TYP)
(TYP)
(TYP)
ISSUED FOR 100% C.D. 2020-10-02
CRITICAL NORMAL NORMAL
CRITICAL
NORMAL
NORMAL
NORMAL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-003
ELECTRICAL PANEL SCHEDULES
10/02/20 RO GA
CONTRACTOR SHALL TRACE, LOCATE AND VERIFY LOADS. REVISE DIRECTORY CARD WITH
DESCRIPTION OF LOAD AND INCLUDE ROOM NUMBER PER NEC 408.4.
PROVIDE NEW CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH
EXISTING IN MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD
INFORMATION.
DISCONNECT AND REMOVE EXISTING CONDUIT AND CONDUCTORS COMPLETELY. THERE
SHALL BE NO ABANDONED CONDUITS. LEAVE BREAKER AS SPARE, AND UPDATE PANEL CARD
INFORMATION.
REMOVE EXISTING CIRCUIT BREAKER 30A/2P AN RETURN TO THE OWNER. PROVIDE NEW
CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH EXISTING IN
MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD INFORMATION.
REMOVE EXISTING CIRCUIT BREAKERS 20A/1P AN RETURN TO THE OWNER. PROVIDE NEW
CIRCUIT BREAKER SIZE AND TYPE INDICATED. CIRCUIT BREAKER SHALL MATCH EXISTING IN
MANUFACTURER, TYPE, STYLE AND AIC RATING, AND UPDATE PANEL CARD INFORMATION.
1. ALL PANELS ARE EXISTING TO REMAIN. MODIFY AS INDICATED.
NOT FOR CONSTRUCTION
GENERAL NOTES
KEYNOTES
PANEL 4CEXA
PANEL 4XCA
PANEL 4A
PANEL 4XB
PANEL 4XE
PANEL 5CE
PANEL 4XC
PANEL PP4D
ISSUED FOR 100% C.D. 2020-10-02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-004
VOLTAGE DROP CALCULATIONS &
LOAD SUMMARY
10/02/20 RO GA
NOT FOR CONSTRUCTION
NOT SCALEVOLTAGE DROP CALCULATION 2
NOT SCALELOAD SUMMARY 1NO SCALEFAULT CURRENT CALCULATIONS 3
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-005
TITLE 24 COMPLIANCE DOCUMENTS
10/02/20 RO GA
UPDNUPDN
CAB DESK
1 2 2.1 3 3.1 3.2 4 4.2 5 5.1 6 7 7.1 8 9 9.1 9.5 9.4 10 11 11.1 12 13 13.3 14 14.1 15 15.1 15.3 16 16.116.3 17 18
B
B.1
C
D
D.2
D.4
E
E.2
E.3
F
G
G.1
H
J
J.1
J.5
J.4
K
L
L.1
M
N
N.2
N.4
N.5
N.6
N.7
O
O.1
P
Q
Q.1
R
S
EP-101
EP-101
FOURTH FLOOR
ELECTRICAL
ROOM
EP-103
EP-105
MH-102IA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-100
ELECTRICAL 4TH FLOOR - OVERALL
10/02/20 RO GA
1" = 20'-0"LEVEL 4 - OVERALL REFERENCE PLAN 1
N
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS. THE CONTRACTOR SHALL VERIFY AND CONFIRM ALL
WORK PRIOR TO ROUGH-IN.
2. PRIOR TO ANY WORK, THE CONTRACTOR SHALL VERIFY AND CONFIRM ALL EXISTING
CIRCUITS AND LOADS PRIOR TO DISCONNECTING POWER,OUTAGES, OR THE LIKE OF. THE
CONTRACTOR SHALL VERIFY AND CONFIRM LOCATIONS AND REQUIREMENTS OF EXISTING TO
REMAIN DEVICES AND EQUIPMENT IN BOTH AREAS OF WORK AND AREAS OUTSIDE OF AREA
OF WORK. PROVIDE ADDITIONAL CONDUIT AND CONDUCTORS, PERFORM SPLICES, AND
EXTEND CIRCUITS AS NECESSARY TO MAINTAIN THE CONTINUITY OF CIRCUIT TO EXISTING TO
REMAIN DEVICES AND EQUIPMENT.
NOT FOR CONSTRUCTION
GENERAL NOTES
KEYPLAN - LEVEL 4 INTERSTITIAL
A4012
CORRIDOR
A4021.4
CORRIDOR
A4018.1
CORRIDOR
A4018.4
CORRIDOR
A4018.2
A4018
STAIR
NO 9
CORRIDOR
A4018.3
A4012
CORRI DOR
A4021.4
CORRI DOR
A4018.1
CORRI DOR
A4018.4
CORRI DOR
A4018.2
A4018
STAIR
NO 9
CORRI DOR
A4018.3
9.1
9.1
E.2 E.2
E.3 E.3
F F
(E)4XE
120/208V
225A BUS
3PH, 4W
7 7.1 8 9
K
L
L.1
(E) PANEL PP4C
120/208V
400A BUS 3PH, 4W
(E) PANEL PP4A
277/480V
400A BUS 3PH, 4W
(E) PANEL PP4AA
277/480V
225A BUS 3PH, 4W
(E) PANEL D4XA
120/208V
400A BUS 3PH, 4W
(E) PANEL PP4D
277/480V
400A BUS3PH, 4W
(E)TELEPHONE
BACKBOARD
(E)TELEPHONE
BACKBOARD
(E) PANEL D4A
277/480V
225A BUS 3PH, 4W
(E) T16 480-208/120V
112.5 KVA
3PH, 4W
(E) T4 480-208/120V
75 KVA
3PH, 4W
4.2 5
J.5
(E) PANEL 4CEXA
120/208V
225A BUS 3PH, 4W
(E)4XB
120/208V
225A BUS
3PH, 4W
(E)4XCA
120/208V
225A BUS
3PH, 4W
(E)4XC
120/208V
225A BUS
3PH, 4W
(E) PANEL 4A
277/480V
225A BUS 3PH, 4W
(E) PANEL A
120/208V
225A BUS 3PH, 4W
(E) PANEL UPS
120/208V
100A BUS 3PH, 4W
CONTRACTOR SHALL COMPLETELY
REMOVE EXISTING ABANDONED CABLE
TRAY, ASSOCIATED SUPPORTS,
SEISMIC BRACING, ANCHORS, AND
APPURTENANCES. PATCH AND REPAIR
SURFACES.
(E) LOW VOLTAGE PANELS
MH-102IA
EP-101
EP-101
EP-101
EP-101
5 5.1
G.1
H
J
CONTRACTOR SHALL
COMPLETELY REMOVE EXISTING
ABANDONED CABLE TRAY,
ASSOCIATED SUPPORTS, SEISMIC
BRACING, ANCHORS, AND
APPURTENANCES. PATCH AND
REPAIR SURFACES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:4
P
M
EP-101
ELECTRICAL 4TH INTERSTITIAL -
ENLARGED PLANS
10/02/20 RO GA
AFFECTED BY SCOPE OF WORK. REFER TO PANEL SCHEDULE ON EP-003
REFER TO PHOTO
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS.
1/4" = 1'-0"LEVEL 4 - INTERSTITIAL - PANEL LOCATION 1 3 1/4" = 1'-0"LEVEL 4 - INTERSTITIAL ELECT. RM. A4018 1
1/4" = 1'-0"LEVEL 4 - INTERSTITIAL - PANEL LOCATION 2 2
N N
N
NOT FOR CONSTRUCTION
GENERAL NOTES
KEYNOTES
KEYPLAN - LEVEL 4 INTERSTITIAL
1 1
ISSUED FOR 100% C.D. 2020-10-02
1/4" = 1'-0"LEVEL 4 - INTERSTITIAL - PLATFORM AREA 4
J
J
SCAN
EXAM RM
NUCMED ALCOVE
EQUIPMENT RM
CORRIDOR
TOILET
4070B
LAB
4070D
EXAM RM
4070A
LAB
4070C
RECEPTION
CORRIDOR
HAC
GAMMA WELL
COUNTER
4500A
LAB
SCAN
EXAM RM
CLEAN UTILITY
TOILET
OFFICE
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
SCOPE OF WORK
(E)POWER OUTLETS
COMPUTER RM
(E) RESTROOM
(E)
(E) (E)
(E)
(E)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)
(D)(D)(D)(D)(D)
(D)
(D)
(D) (D)(D)(D)
SCAN
(E)
EP-102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:5
P
M
EP-102
ELECTRICAL 4TH FLOOR - AREA OF
WORK DEMOLITION
10/02/20 RO GA
1/4" = 1'-0"LEVEL 4 - AREA OF WORK DEMOLITION 1
DISCONNECT AND REMOVE EXISTING COMMUNICATION DEVICE, PLATE AND DEVICE BOX.
REMOVE CABLING AND ALL FITTINGS, BACK TO THE SERVICE POINT.
DISCONNECT AND REMOVE EXISTING DISCONNECT SWITCH. REMOVE EXISTING WIRE AND
CONDUIT, BACK TO THE SERVICE POINT. REMOVE ALL FITTING, ATTACHING HARDWARE,
BRACKETS, SUPPORTS AND APPLICABLE APPURTENANCES.
REMOVE EXISTING SWITCH DEVICE, PLATE AND DEVICE BOX. REMOVE EXISTING WIRING AND
ALL EXPOSED CONDUIT.
DISCONNECT AND REMOVE ALL LIGHTING FIXTURES. JUNCTION BOXES, RECEPTACLES.
COMPLETELY REMOVE ALL EXPOSED ATTACHING HARDWARE, BRACKETS, SUPPORT,
PROTRUDING BOLTS AND SLEEVES. MAINTAIN CONTINUITY OF CIRCUIT TO BE USED ON NEW
LIGHT CIRCUITS. REFER TO NEW CONSTRUCTION PLAN FOR MORE INFORMATION.
DISCONNECT AND REMOVE EXISTING EQUIPMENT, SALVAGE AND RETURN TO THE OWNER.
DISCONNECT AND RELOCATE EXISTING UPS PANEL. COORDINATE LOCATION WITH OWNER
PRIOR TO ROUGH-IN.
DISCONNECT AND RELOCATE EXISTING OUTLETS. ACCOMMODATE ELECTRICAL DEVICES,
FOLLOWING THE NEW ROOM DISTRIBUTION. MAINTAIN CONTINUITY OF CIRCUIT TO BE USED ON
NEW POWER CIRCUITS. REFER TO NEW CONSTRUCTION PLAN FOR MORE INFORMATION.
DISCONNECT AND RELOCATE EXISTING LIGHTING FIXTURES. ACCOMMODATE LIGHTING
FIXTURES, FOLLOWING THE NEW ROOM DISTRIBUTION. MAINTAIN CONTINUITY OF CIRCUIT TO
BE USED ON THE NEW LIGHTING FIXTURE LOCATION. REFER TO NEW CONSTRUCTION PLAN FOR
MORE INFORMATION.
EXISTING DUPLEX RECEPTACLE AND FACEPLATE TO BE REMOVED. SAFE-OFF EXISTING BRANCH
CIRCUIT AND CONDUCTORS. MAINTAIN EXISTING BACKBOX AND CONDUIT. SEE EP-104 FOR NEW
WORK.
DISCONNECT CEILING OUTLETS AND PROTECT IN PLACE. MAINTAIN CONTINUITY OF CIRCUIT
FOR BEEN RECONNECTED AFTER DEMOLITION IS COMPLETED. REFER TO NEW CONSTRUCTION
PLAN FOR MORE INFORMATION. COORDINATE WITH ELECTRICAL CONTRACTOR FOR
RECONNECTION.
N
1 2 3 4
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS.
NOT FOR CONSTRUCTION
GENERAL NOTES
KEY NOTES
KEYPLAN - LEVEL 4
N
9 9
D
D D
J
J
OS
OS
OS
OS
OSOS
J
JJJJ
EP-103
2 2.1 3 3.1 3.2 4 4.2 5 5.1
J
J.1
J.5
J.4
SCOPE OF WORK.
(TYP)
SCOPE OF WORK
a a
F3
(E) RESTROOM
4054TOILET
4070B
GAMMA WELL
COUNTER
4500ALAB
NUCMED ALCOVE
CORRIDOR
RECEPTION
OFFICE (S)
OFFICE (S)
OFFICE
TOILET
OFFICE (S)
OFFICE (S)
CORRIDOR
BREAK
CLEAN UTILITY
EXAM RM
CONFERENCE
TOILET
SCAN
CORRIDOR
SCAN
EXAM RM
COMPUTER RM
EQUIPMENT RM
F3E
PDC
X1
X1
EQUIPMENT RM
SCAN
CONTROL
SCAN
X-RAY
F1
F1
F1E
F1 F2
F2E
F2E F2 F2
F2
F1 F1E
F1 F1
F2
F2 F2
F2E
F2
F1E
F1
F2E
F2E
F1
F1E
5CE - 1
a a a b b b ab
1 a 1 a b b bb b b
F2E
5CE - 1
4XE - 14
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:5
P
M
EP-103
4TH FLOOR-AREA OF WORK
REMODEL- LIGHTING
10/02/20 RO GA
RE-CONNECT NEW LIGHTS TO EXISTING CIRCUIT J-BOX (277V) IN CEILING SPACE. VERIFY CIRCUIT
NUMBER IN FIELD.
PROVIDE (2)-#10 & (1)-#10 GND IN EXISTING 3/4"C.
PROVIDE ENGRAVED SWITCH WITH SEPARATE ON/OFF/DIM 0-10V CONTROLS FOR GENERAL
LIGHTING AND FOR DOWNLIGHTING . LOCATE AT SCAN ENTRANCE AND CONTROL ROOM FOR
CONTROL FROM BOTH LOCAITONS.
PROVIDE WARNING LIGHT WITH WORDING "X-RAY IN USE, DO NOT ENTER". PROVIDE INTERFACE
WITH CT CONTROLLER VIA INTERFACE RELAY. WARNING LIGHT TO BE PROVIDED BY OTHERS.
INTERCEPT EXISTING BRANCH CIRCUIT AND EXTEND AS INDICATED.
PROVIDE (2)-#12 & (1)-#12 GND IN 3/4"C. FOR LOW VOLTAGE TRANSFORMER. COORDINATE
LOCATION WITH OWNER PRIOR TO ROUGH-IN.
PROVIDE NURSE CALL LIGHT. INSTALL 2" ABOVE DOOR JAMB AND CENTERED ON DOOR.
PROVIDE 120V TO WALL MOUNTED LIGHT PANELS MANUFACTURER SKY FACTORY SERIES #ALS-
BL-TWIN-2240-4IV. COORDINATE WITH ARCHITECTURAL PLANS FOR EXACT LOCATIONS AND
INSTALLATION REQUIREMENTS.
PROVIDE 120V TO LUMINOUS VIRTUAL WINDOW. COORDINATE CONNECTION REQUIREMENTS
WITH VENDOR PRIOR TO ROUGH-IN.
N
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE SURVEYS
AND AS-BUILT DRAWINGS.
2. MULTIPLE HOME RUNS MAYBE SHOWN ON THESE PLANS FOR CLARITY. E.C. IS TO COMBINE HOME RUN CONDUIT AND WIRES SO AS TO OBSERVE ALL REQUIREMENTS FOR N.E.C.110.14. IT IS NOT THE
INTENTION OF THIS DESIGN TO ALLOW MULTIPLE TAPPED CIRCUIT BREAKERS.
3. CONTRACTOR TO VERIFY ALL CONDITIONS, LOCATIONS, AND CONNECTIONS TO EQUIPMENT WITH
OWNER AND/OR ARCHITECT PRIOR TO BID AND INCLUDE ALL COST IN BID.
4. PROVIDE SHIELDING BEHIND ALL BOXES AND OTHER PENETRATIONS IN SHIELDED SCANNING
ROOM SURFACES.
(TYP)
NOT FOR CONSTRUCTION
GENERAL NOTES
KEY NOTES
KEYPLAN - LEVEL 4
1/4" = 1'-0"LEVEL 4 - AREA OF WORK - REMODEL LIGHTING 1
ISSUED FOR 100% C.D. 2020-10-02
T T
T
T
T T
T
G F
C I
G F
C I
G F
C I
GFCI
J
J
J
J
J
JJ
J
J
J
2.1 3 3.1 3.2 4 4.2 5 5.1
H
J
J.1
J.5
J.4
SCAN
EXAM RM
NUCMED ALCOVE
EQUIPMENT RM
CORRIDOR
TOILET
4070B
LAB
4070D
EXAM RM
4070A
LAB
4070C
RECEPTION
CORRIDOR
HAC
GAMMA WELL
COUNTER
4500A
LAB
SCAN
EXAM RM
CLEAN UTILITY
TOILET
OFFICE
BREAK
TOILET
CONFERENCE
OFFICE (S)
OFFICE (S)
OFFICE (S)
OFFICE (S)
COMPUTER RM
SCOPE OF WORK.
19 19 19
21 21
SCOPE OF WORK
(E) RESTROOM
LAB
4070C
AC
VOLTAGE LOAD
AC
4XE - 19
4XE - 21
4XCA - 22
EQUIPMENT RM
4XCA - 24
4XCA - 2424
CORRIDOR
PP4D - 18,20,22
(N)HEAT EXCHANGER CABINET
PP4D - 7,9,11
PP4D - 2,4,6
EPO
4XE - 1,3
4XE - 1,3
4XE - 5
BLANKET
WARMER
4XCA - 24
+48"
+48"
+48"
PDC
cPDC
4XE - 15
4XE - 17
4CEXA - 8
+48"
4CEXA - 11
4CEXA - 13
EPO
+48"
DS
(E)
(E) (E)
(E)
(E)
EPO
CONTROL
COMMON POWER
DISTRIBUTION UNIT
POWER DISTRIBUTION
CABINET (PDC) AND UPS
LEAD
PIG
IMAGE
RECONSTRUCTION
SYSTEM
PATIENT TABLE
SCAN
KEYBOARD
& CONTROL
BOX
MEDRAD
WORKSTATION
& BASE UNIT
GATING LAPTOP
COMPUTER & DECK PORT
HEAT EXCHANGER
WATER/AIR SPLIT (ID#11)
4XE - 2,4,6
4XE - 17
4XE - 7,15,8
(E)
4CEXA -
12,14,16,18
4CEXA - 1
+48"
EPO 5
4CEXA - 3
EP-104
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:5
P
M
EP-104
4TH FLOOR-AREA OF WORK
REMODEL-POWER
10/02/20 RO GA
1/4" = 1'-0"LEVEL 4 - AREA OF WORK - REMODEL POWER 1
N
NOT FOR CONSTRUCTION
PROVIDE POWER CONNECTION ABOVE CEILING TO MODULAR SERVICE COLUMN.
EXISTING OUTLET TO REMAIN.
PROVIDE EMERGENCY POWER OFF PUSH BUTTON STATION A22EL-M-12A-11-B, WITH ELECTRIC
GUARD, METAL FRAME AND A TEXT ABOVE WHICH READS "EMERGENCY SHUT OFF". CONNECT
TO SHUNT TRIP AT MAIN DISCONNECT.
COORDINATE WITH VENDOR FOR EXACT LOCATION OF CONDUIT ENTRY WINDOW IN SLAB.
PROVIDE 1" CONDUIT AND FLOOR BOX ROUTED IN INTERSTITIAL SPACE BELOW. ROUTE FROM
PDC UNIT AT EQUIPMENT ROOM 4520 TO LOCATION OF PATIENT TABLE. CONDUIT SHALL BE
ROUTED WITHIN 12" BELOW UNDERSIDE OF SLAB BELOW. CONDUITS BELOW 12" SHALL NOT BE
ALLOWED WITHOUT THE CONTRACTOR PROVIDING ADDITIONAL SEISMIC BRACING OF CONDUIT
FOR SEISMIC ZONE 4.
PROVIDE (4)-#1/0 & (1)-#6 GND IN 2"C.
PROVIDE DOOR SWITCH PER DETAIL X/E-XX FOR SAFETY CONTROL OF CT SYSTEM. POWER TO
THE CT EQUIPMENT SHALL BE INTERRUPTED IF DOOR IS OPENED VIA SHUNT TRIP DEVICE.
PROVIDE (3)-#10 & (1)-#10 GND IN 3/4"C.
PROVIDE 200AS/200AF/3P STAINLESS STEEL FUSED DISCONNECT AND LIQUIDTIGHT FLEXIBLE
METAL CONDUIT OR LFMC FOR POWER CONNECTION TO UNIT. PROVIDE FUSE SIZE PER
MANUFACTURER'S RECOMMENDATION.
PROVIDE 200AS/150AF/3P STAINLESS STEEL FUSED DISCONNECT AND LIQUIDTIGHT FLEXIBLE
METAL CONDUIT OR LFMC FOR POWER CONNECTION TO UNIT. PROVIDE FUSE SIZE PER
MANUFACTURER'S RECOMMENDATION. COORDINATE EXACT LOCATION WITH SIEMENS AND
ARCHITECT PRIOR ROUGH-IN.
PROVIDE 30AS/30AF/3P STAINLESS STEEL FUSED DISCONNECT AND LIQUIDTIGHT FLEXIBLE
METAL CONDUIT OR LFMC FOR POWER CONNECTION TO UNIT. PROVIDE FUSE SIZE PER
MANUFACTURER'S RECOMMENDATION.
PROVIDE RECESSED CEILING MOUNT DUPLEX CONVENIENCE OUTLET 125V, 20A TYPE 5-20R FOR
OVERHEAD LIFT SYSTEM. COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN.
PROVIDE DOUBLE POLE THERMAL RATED MOTOR STARTER SWITCH.
PROVIDE POWER TO AED. COORDINATE EXACT LOCATION WITH OWNER PRIOR ROUGH-IN.
RE-CONNECT CEILING OUTLET TO NEW OVERHEAD LIFT SYSTEM AS INDICATED. COORDINATE
EXACT LOCATION PRIOR TO ROUGH-IN.
RE-CONNECT WALL OUTLET AS INDICATED.
PROVIDE SURFACE MOUNTED 10"X3-1/2" METALLIC DUCT AT THE FLOOR LINE FOR ENTIRE
LENGTH OF DESK. DUCT SHALL HAVE THREE SEPARATE DIVIDED SECTIONS. COORDINATE WITH
SIEMENS VENDOR.
PROVIDE (4) 120V DEDICATED CIRCUITS TO THE MEDRAD BOOM PER DETAIL 2/EP-601.
PROVIDE (4) CAT5E ETHERNET CONNECTIONS PER DETAIL 2/EP-601.
1. RECEPTACLES ON COMMON WALLS SHALL BE SEPARATE BOXES AND OFFSET 12" MINIMUM. FIRE RATED WALLS SHALL HAVE AN OFFSET OF 24" MINIMUM. COORDINATE w/ ARCH'L FIRE RATED WALL
DETAILS
2. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROTECTED FROM THE SPREAD OF FIRE W/ AN APPROVED FIRESTOP SYSTEM EQUAL OR GREATER THAN THE FIRE RATING OF THE WALL.
3. PROVIDE 1-1/2" C.O. FROM EACH TELE/DATA OUTLET AND STUB 6" INTO ACCESIBLE CEILING SPACE, U.N.O. SEE DETAIL 3/EP-601 FOR FURTHER REQUIREMENTS.
4. REFER TO ARCHITECTURAL PLAN FOR ELECTRICAL DEVICE HEIGHTS AND EXACT LOCATION.
5. PROVIDE SHIELDING FOR ALL BOXES, CONDUITS AND OTHER PENETRATIONS IN SHIELDED
SCANNING ROOM SURFACES. REFER TO SHIELDING REQUIREMENTS AND DETAILS ON
ARCHITECTURAL SHEET AE-608.
6. PROVIDE 3/4" C.O. FOR EACH THERMOSTAT BACK TO EACH CORRESPONDING HVAC UNIT AND
BETWEEN MECHANICAL UNITS AS NEEDED FOR CONTROLS. REFER TO MECHANICAL DRAWINGS
FOR EXACT QUANTITY AND LOCATION.
GENERAL NOTES
KEY NOTES
KEYPLAN - LEVEL 4
15 15
ISSUED FOR 100% C.D. 2020-10-02
Revisions: Date:
J
J
J
J
J
J
J
EP-105
2.1 3 3.1 3.2 4 4.2 5 5.1
G
G.1
H
J
J.1
J.5
CAV
4-5
CAV
4-2
CAV
4-1
CAV
4-4
GX
AC
AV
(E)
0.40
AV
(E)
0.30
DV
(E)
2.23
AV
(E)
0.30
BV
(E)
0.55
AV
(E)
0.30
AV
(E)
0.30
AV
(E)
0.30
AC
(E)
PP4D - 1,3,5
4XCA - 15
4XCA - 31,33
31,33 31,33
31,33
31,33
31,33
4XCA - 40,42
GX
(E)
AC
DV
(E)
1.30
BV
(E)
0.63
AV
(E)
0.27
BV
(E) 0.55
VAV
E
4-5
VAV
E
VAV
E
VAV
E
VAV
E
VAV
E
AV
(E)
0.29
CAV
(E)
4-3
BV
(E)
0.55
BV
(E)
0.65
F3
F3
F3E
+6'-6" A.F.F.
+6'-6" A.F.F.
+6'-6" A.F.F.
4CEXA - 10
4CEXA - 17
TO RH SENSOR
RH SENSOR
AND AIR FLOW
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:5
P
M
EP-105
ELECTRICAL ENLARGED PLAN -
INTERSTITIAL
10/02/20 RO GA
PROVIDE (2)-#12 & (1)-#12 GND IN 3/4"C.
PROVIDE 60AS/40AF/3P STAINLESS STEEL FUSED DISCONNECT AND LIQUIDTIGHT FLEXIBLE
METAL CONDUIT OR LFMC FOR POWER CONNECTION TO UNIT. PROVIDE FUSE SIZE PER
MANUFACTURER'S RECOMMENDATION. COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR
ROUGH-IN.
PROVIDE (3)-#8 & (1)-#10 GND IN 1"C.
PROVIDE GROUND-FAULT PROTECTED DUPLEX CONVENIENCE OUTLET 125V, 20A TYPE 5-20R IN
WEATHERPROOF BOX WITH WEATHERPROOF COVER. COORDINATE EXACT LOCATION PRIOR TO
ROUGH-IN.
PROVIDE 1"C.O. FOR LOW VOLTAGE HVAC CONTROLS.
PROVIDE (2) 1"C.O. FOR LOW VOLTAGE HVAC CONTROLS AND F.P. LIFE SAFETY INTERLOCK.
PROVIDE 1"C.O. AND CAT5E ETHERNET CONNECTION TO IDF ROOM.
GENERAL NOTES
KEY NOTES
1. ALL EXISTING ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED ON VISUAL SITE
SURVEYS AND AS-BUILT DRAWINGS.
2. THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT ALL CONDUIT AND PIPING
ROUTING THROUGH THE INTERSTITIAL SPACE, CONDUIT CHASE, ABOVE CEILING AREAS NOT
ACCESSIBLE AT THE INTERSTITIAL SPACE, AND PROVIDE A CONDUIT ROUTING PLAN FOR
REVIEW AND APPROVAL BY THE AOR AND COR PRIOR TO ROUGH-IN.
NOT FOR CONSTRUCTION
N
KEYPLAN - LEVEL 4 INTERSTITIAL
1/4" = 1'-0"LEVEL 4 INTERSTITIAL - AREA A 1
ISSUED FOR 100% C.D. 2020-10-02
T
W P
WP
J
4.2 5
J.4
K
L
TRANSFER
CENTER
RECEPTION
CORRIDOR
HP
4CEXA - 7,9
4XCA - 24 WP
SCAN
5 5.1
G
G.1
H
J
OFFICE (S)
6083B
HP
WP
4XE - 8,10
4XE - 26
EP-106
1LEVEL 4
EP-106
LEVEL 6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:0
P
M
EP-106
ELECTRICAL ENLARGED PLAN -
EXTERIOR
10/02/20 RO GA
N
NOT FOR CONSTRUCTION
1. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE PROTECTED FROM THE SPREAD OF FIRE W/ AN APPROVED FIRESTOP SYSTEM EQUAL OR GREATER THAN THE FIRE RATING OF THE WALL.
2. REFER TO ARCHITECTURAL PLAN FOR ELECTRICAL DEVICE HEIGHTS AND EXACT LOCATION.
3. COORDINATE WITH MECHANICAL CONTRACTOR AND ROUTE BRANCH CIRCUIT CONDUITS WITH
PRIMARY COOLING CIRCUIT PIPES. VERIFY ROUTE IN PIPE CHASE PRIOR TO WORK.
GENERAL NOTES
KEYPLAN - LEVEL 4
1/4" = 1'-0"LEVEL 4 - AREA OF WORK REMODEL 1
PROVIDE (2)-#12 & (1)-#12 GND IN 3/4"C.
PROVIDE WEATHER PROOF DOUBLE POLE THERMAL RATED MOTOR STARTER SWITCH.
PROVIDE GROUND-FAULT PROTECTED DUPLEX CONVENIENCE OUTLET 125V, 20A TYPE
5-20R IN WEATHERPROOF BOX WITH WEATHER PROOF COVER.COORDINATE EXACT
LOCATION PRIOR TO ROUGH-IN.
COORDINATE WITH VA FACILITY FOR ACCESS INTO THE PIPE CHASE. ONLY QUALIFIED AND
TRAINED PERSONNEL SHALL HAVE ACCESS INTO THE PIPE CHASE.
COORDINATE ALL PIPING AND BRANCH CIRCUIT CONDUITS ORIGINATING FROM LEVEL D6 WITH
WORK IN THIS AREA AND PROVIDE SINGLE ROUTE AND RACK.
PROVIDE (2) 3" CONDUITS TO HEAT EXCHANGER COORDINATE WITH SIEMENS VENDOR.
PLAN NOTES
1/4" = 1'-0"LEVEL 6 - AREA OF WORK REMODEL 2
N
ISSUED FOR 100% C.D. 2020-10-02
PROVIDE (2)-#12 & (1)-#12 GND IN 3/4"C.
PROVIDE WEATHER PROOF DOUBLE POLE THERMAL RATED MOTOR STARTER SWITCH.
PROVIDE GROUND-FAULT PROTECTED DUPLEX CONVENIENCE OUTLET 125V, 20A TYPE
5-20R IN WEATHERPROOF BOX WITH WEATHER PROOF COVER.COORDINATE EXACT
LOCATION PRIOR TO ROUGH-IN.
COORDINATE WITH VA FACILITY FOR ACCESS INTO THE PIPE CHASE. ONLY QUALIFIED AND
TRAINED PERSONNEL SHALL HAVE ACCESS INTO THE PIPE CHASE.
COORDINATE ALL PIPING AND BRANCH CIRCUIT CONDUITS ORIGINATING FROM LEVEL D6 WITH
WORK IN THIS AREA AND PROVIDE SINGLE ROUTE AND RACK.
PROVIDE (2) 3" CONDUITS TO HEAT EXCHANGER COORDINATE WITH SIEMENS VENDOR.
PROVIDE (2) 3" C.O. TO THE LOCATION OF THE HEAT EXCHANGER CABONET PER THE
REQUIREMENTS OF SEIMENS EQUIPMENT SUPPLIER.
PLAN NOTES
Revisions: Date:
nPODM
DX
nP D nPD
ER
nP D nPD
ER
1nPODM
DX
nP D nPD
ER
nPD
ER
nPODM
2P DX
nPD
ER
nPODM
DX
nPODM
2P DX
nPODM
DX
nP D nPD
ER
nP D
J
3.2 4 4.2 5 5.1
J
J.1
J.5
J.4
EXAM RM
COMPUTER RM
EQUIPMENT RM
SCAN
CONTROL
EP-102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:0
P
M
EP-300
ELECTRICAL LIGHTING CONTROL
10/02/20 RO GA
CONTROLS LINETYPE LEGEND
SECONDARY DAYLIT ZONE BOUNDARY
SKYLIGHT DAYLIT ZONE BOUNDARY
nLIGHT AIR GROUP PAIRING
SYA CABLE A4
LOW VOLTAGE WIRING - SEE DRAWINGS FOR WIRING DETAILS
DMX512 - WIRING MUST FOLLOW THE DMX512-A/RDM STANDARD - ANSI E1.1
FRESCO NETWORK - CAT5, CAT5E OR CAT6; TERMINATED AS RJ45 TIA/EIA-568B
nLIGHT NETWORK - CAT5, CAT5E OR CAT6; TERMINATED AS RJ45 TIA/EIA-568B
PRIMARY DAYLIT ZONE BOUNDARY
DAYLIGHT LINETYPE LEGEND
CONTROL NOTES
THE LIGHTING CONTROL DESIGN IS SUBJECT TO CHANGE BASED ON ADDITIONAL
PROJECT SPECIFIC INFORMATION.
• THIS IS A STAND ALONE NLIGHT DESIGN- TIME CLOCK AND ADR EQUIPMENT NOT INCLUDED
• PLUG LOAD CONTROLLERS NOT INCLUDED IN THIS DESIGN
• ASSUMING 0-10V DIMMING ON ALL FIXTURES
0-10V CONTINUOUS DIMMING PROVIDED IN LIEU OF A/B SWITCHING
SYMBOLS LIST
nPODM
2P DX
nPODM 2P DX [COLOR] 2 Channel On/Off Toggle With Dimming nPODM
DX
nPODM DX [COLOR] 1 Channel On/Off Toggle With Dimming nPP16 D Power/Relay Pack: 16A 120/277 VAC w/ 0-10VDC Dimming nP D nPP16 D ER Relay Pack: 16A 120/277 VAC UL-924 Emergency Relay Pack w/ 0-10VDC Dimming nPD
ER
NOT FOR CONSTRUCTION
N a ae a a ae a ae a/ae/ce a ae ce ce ce cece cece ae a a ae ae ae a/ae/ce b/be ae b be b be a a
1/4" = 1'-0"LEVEL 4 - AREA OF WORK - REMODEL LIGHTING AND CONTROL 1
a
KEYPLAN - LEVEL 4
ISSUED FOR 100% C.D. 2020-10-02
a a ae aea a aa
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION DOCUMENTSOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
664-CSI-1154W NUCLEAR MEDICINE PET- CT 2
SAN DIEGO, CA
IDS GROUP INC.
1 PETERS CANYON RD. STE. 130
IRVINE, CA 92606
949.387.8500
FULLY SPRINKLERED
C U s e rs \A le ja n d ro .A g u ila r\ D o c u m e n ts
\1 X
.0
-V
A S
D -N u c -M e d
E le c R
T V ra m i.
e lh a s s a n id s g i.
c o m .r v t
/2 /2
:5
:0
P
M
EP-301
ELECTRICAL LIGHTING CONTROL
SINGLE LINE DIAGRAM
10/02/20 RO GA
1. nPODM DX SWITCH PROVIDES MANUAL OVERRIDE OF THE LIGHTS: ON/OFF/RAISE/LOWER.
2. nPP16 D PROVIDES RELAY AND 0-10V DIMMING CONTROL OF NORMAL POWERED GENERAL LIGHTING
3. nPP16 D ER PROVIDES RELAY AND 0-10V DIMMING CONTROL OF EMERGENCY CIRCUIT POWERED LIGHTING WITH INTEGRAL UL924 SHUNT. 1. nPODM DX SWITCH PROVIDES MANUAL OVERRIDE OF THE LIGHTS: ON/OFF/RAISE/LOWER.
2. nPODM 2P DX SWITCH PROVIDES 2 ZONES OF MANUAL OVERRIDE OF THE LIGHTS: ON/OFF/RAISE/LOWER.
3. nPP16 D PROVIDES RELAY AND 0-10V DIMMING CONTROL OF NORMAL POWERED GENERAL LIGHTING
4. nPP16 D ER PROVIDES RELAY AND 0-10V DIMMING CONTROL OF EMERGENCY CIRCUIT POWERED LIGHTING WITH INTEGRAL UL924 SHUNT.
BILL OF MATERIAL
nPP16 D
PRODUCT # DESCRIPTION
16 AMP RELAY PACK WITH 0-10V DIMMING CONTROL;
CHASE NIPPLE MOUNTING
nPODM DX WH SINGLE CHANNEL ON/OFF TOGGLE WITH DIMMING
QUANTITY OF nLIGHT DEVICES MAY VARY BASED ON LIGHTING FLOOR PLAN nPP16 D ER
16 AMP RELAY PACK WITH 0-10V DIMMING CONTROL;
EMERGENCY CIRCUIT CONTROL; INTEGRAL UL924
SHUNT; CHASE NIPPLE MOUNTING
BILL OF MATERIAL
nPP16 D
PRODUCT # DESCRIPTION
16 AMP RELAY PACK WITH 0-10V DIMMING CONTROL;
CHASE NIPPLE MOUNTING
nPODM 2P DX WH 2 CHANNEL ON/OFF TOGGLE WITH DIMMING
QUANTITY OF nLIGHT DEVICES MAY VARY BASED ON LIGHTING FLOOR PLAN nPODM DX WH
SINGLE CHANNEL ON/OFF TOGGLE WITH
DIMMING
nPP16 D ER
16 AMP RELAY PACK WITH 0-10V DIMMING CONTROL;
EMERGENCY CIRCUIT CONTROL; INTEGRAL UL924
SHUNT; CHASE NIPPLE MOUNTING
BLUE
W /R
Y E
L /R
E D
RJ45 PORTS
nPP16 D ER
HN
W H
T
B L K
EHEN
B L U
E
EN
VIOLET
GRAY
YEL- 120V/ RED- 277V
NORMAL (sense only)
G R
N
OPTION FOR
NETWORKED
SYSTEM
NOTE 1
BLK - 120VAC
ORN - 277VAC
RJ45
PORTS
+40mA nPP16 D
VIOLET
GRAY
GRN
BLUE
HN
W H
T
B L K
/O R
N1
B L U
E
N277/120VAC 0-10V DIMMING
GENERAL LIGHTING
R J
R J nPODM DX WH
277/120VAC 0-10V DIMMING
EMERGENCY
CIRCUIT LIGHTING
NOTE 1
BLK - 120VAC
ORN - 277VAC
nPODM 2P DX WH
R J
R J
R J
R J nPODM DX WH
RJ45
PORTS
+40mA nPP16 D
VIOLET
GRAY
GRN
BLUE
HN
W H
T
B L K
/O R
N1
B…
This is the start of the file's text. The full file is on GovTribe.