This solicitation requests proposals for a Multiple Award Construction Contract at McConnell Air Force Base. The government intends to award up to six firm-fixed price indefinite-delivery/indefinite-quantity contracts for a total not-to-exceed amount of $75 million over six years. Task orders will be issued on a competitive basis for individual construction projects ranging from $2,000 to $10 million. Work includes design-build, renovation, new construction, and repair of facilities, roadways, and airfields integrating multiple trades. Successful offerors must have the capability to provide full project design from concept or performance work statement. Responses are due by November 2021 and will be evaluated based on a best value tradeoff between past performance, which is significantly more important than price. A pre-proposal conference will be held on November 17, 2021.
View the file
Other files for this federal contract opportunity
Show all 31
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
iSi Environmental (iSi) F:\DATA\Krehbiel Architecture\2010015 NESHAP Survey Bldg 852\1-Cover Letter.docx
Wichita, Kansas Atlanta, Georgia Tulsa, Oklahoma Phone: (888) 264-7050 www.iSiEnvironmental.com
November 13, 2020
Ed Knox
Krehbiel Architecture
1300 East Lewis
Wichita, Kansas 67211
Re: Asbestos Survey – Building 852 McConnell AFB
Dear Mr. Knox:
iSi Environmental (iSi) has completed the asbestos survey of the areas to be impacted by renovation activities at Bldg. 852 MAFB. This survey is required for identification of asbestos-containing materials (ACM) which were accessible. After laboratory analysis of the samples, the following ACM were identified:
No Asbestos Detected
This survey was performed by an EPA-accredited inspector and sample analysis was performed by a National Voluntary Laboratory Accreditation Program (NVLAP) and American Industrial
Hygiene Association (AIHA) accredited laboratory. iSi cannot guarantee all ACM were identified since the possibility exists there may be ACM hidden from sight by non-ACM or be located in inaccessible locations.
If asbestos is discovered it is recommended the Owner employ a licensed asbestos abatement contractor for abatement of any ACM required to be removed prior to renovation or demolition activities. Before asbestos abatement is undertaken, an asbestos abatement plan and notification should be prepared by the asbestos abatement contractor.
This report has been prepared for the exclusive use of our client, in accordance with generally accepted asbestos survey practices within the constraints of the client’s directives. No warranties, either expressed or implied, are intended or made. Conclusions drawn by others from the results of this survey, as described within this report, should recognize the limitations of the survey methods.
iSi Environmental (iSi) F:\DATA\Krehbiel Architecture\2010015 NESHAP Survey Bldg 852\1-Cover Letter.docx
If you have any questions or require additional services, please contact me at (316) 265-0012 or raunquoe@isienvironmental.com.
Sincerely, Ron Aunquoe
Inspector
Certificate #6970226
Attachments: Sample Data Summary
Bulk Sample Analysis & Chain of Custody
Sample Location Map
Credentials cc: iSi Project Number 2010015
Asbestos Survey of
Building 852
McConnell AFB
Wichita, Kansas prepared for
Krebiel Architecture
1300 East Lewis
Wichita, Kansas 67211
November 13, 2020
SAMPLE DATA SUMMARY
Building:
SAMPLE DATA SUMMARY
Building 852 MAFB Wichita, Kansas
Inspection Date: October 29, 2020
Inspector: Ron Aunquoe- #687620
Asbestos-Containing Sample Data
Sample Description Sample Number Location
#01VG Vibration Gasket Boiler Rom
#02WM White Mastic (MJF) Boiler Room
#03FT White/Gray 12" Floor Tile & Mastic South Entrance
#04FT White/Gray 12" Floor Tile & Mastic Power Room
#05FT White/Gray 12" Floor Tile & Mastic Room 112
#06SR White Sheetrock & Compound Room 123
#07SR White Sheetrock & Compound Room 114
#08CP White/Gray 2x2 Ceiling Panel Power Room
#09CP White/Gray 2x4 Ceiling Panel Room 126
#10CP White/Gray 2x4 Ceiling Panel Room 125
#11CP White/Gray 2x2 Ceiling Panel Room 129
#12CP White/Gray 2x2 Ceiling Panel Break Room
#13CP White/Gray 2x4 Ceiling Panel Room 112
NAD = No Asbestos Detected
%Asbestos Friable or
· Non-Friable
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
NAD
BULK SAMPLE ANALYSIS & CHAIN OF
CUSTODY
Date Received: 11/03/2020
Project: Asbestos Survey
QuanTEM Lab No. 328514
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: McConnel AFB Wichita, KS - Building #852 West
Project Number: 2010015
Account Number: B263
Received By: Chloe Collins
Date Analyzed: 11/05/2020
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: ISI Environmental Services
Allen Sill
215 S. Laura
Wichita, KS 67211
Non Fibrous
001 #01VG Homogeneous BinderAsbestos Not Present 40Cellulose
Gasket
Gray/White
002 #02WM Layered CaCO3
Binder
Asbestos Not Present NA
Mastic
White
002a Layered Foil
Binder
Asbestos Not Present 30
Cellulose
Glass FiberWrap
White
002b Layered Asbestos Not Present 100Glass Fiber
Insulation
Gray
003 #03FT Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White/Gray
003a Layered TarAsbestos Not Present NA
Mastic
Black
004 #04FT Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White/Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.
QuanTEM Lab No. 328514
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: McConnel AFB Wichita, KS - Building #852 West
Project Number: 2010015
Account Number: B263
Received By: Chloe Collins
Date Analyzed: 11/05/2020
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: ISI Environmental Services
Allen Sill
215 S. Laura
Wichita, KS 67211
Non Fibrous
004a Layered TarAsbestos Not Present NA
Mastic
Black
005 #05FT Layered GlueAsbestos Not Present NA
Mastic
Yellow
005a Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White/Gray
005b Layered TarAsbestos Not Present NA
Mastic
Black
006 #06SR Layered CaCO3
Paint
Asbestos Not Present NA
Texture
White
006a Layered CaCO3Asbestos Not Present NA
Joint Compound
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 328514
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: McConnel AFB Wichita, KS - Building #852 West
Project Number: 2010015
Account Number: B263
Received By: Chloe Collins
Date Analyzed: 11/05/2020
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: ISI Environmental Services
Allen Sill
215 S. Laura
Wichita, KS 67211
Non Fibrous
006b Layered GypsumAsbestos Not Present 10
Cellulose
Glass FiberSheetrock
White
007 #07SR Layered CaCO3
Paint
Asbestos Not Present NA
Texture
White
007a Layered CaCO3Asbestos Not Present NA
Joint Compound
White
007b Layered GypsumAsbestos Not Present 10
Cellulose
Glass FiberSheetrock
White
008 #08CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
009 #09CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
010 #10CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 328514
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: McConnel AFB Wichita, KS - Building #852 West
Project Number: 2010015
Account Number: B263
Received By: Chloe Collins
Date Analyzed: 11/05/2020
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: ISI Environmental Services
Allen Sill
215 S. Laura
Wichita, KS 67211
Non Fibrous
011 #11CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
012 #12CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
013 #13CP Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White/Gray
Date of Report
11/5/2020
Cassie Sanborn, Laboratory Analyst
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
iSi> Environmental
215 S. Laura • Wichita, Kansas 67211 • Phone: (316) 265-0012
CHAIN OF CUSTODY
DATE 10-29-20
CLIENT Krebiel Architecture
ADDRESS 1300 E. Lewis VVICnlla,K.S bl£11
PO # Ed Knox
PAGE OF
PROJECT Asbestos Survey
ADDRESS McConnel AFB Wichita,Ks
BLDG # Building #852 West
JOB # 2010015
PHONE : ___________ _
FAX : ed.knox@krebielarchitecture.com
TEST FOR:
ASBESTOS X
LEAD --
OTHER _____ __ _
T d 3 d urnaroun : ,.. 'd.-4
SAMPLE TYPE OF
TYPE OF ANALYSIS :
PLM;..:.X..:.___
TEM
ATO~SORPTION
TCLP ---
OTBE"""R--
DESCRIPTION OF
NUMBER CONTAI NER MATERIAL
#01VG Plastic Bag Gray/White Vibration Gasket (Boiler Room)
#02WM \ White Mastic on MJF (Boiler Room)
#03FT \ White/Gray 12" Floor Tile & Mastic (South Entr)
#04FT
\ White/Gray 12" Floor Tile & Mastic (Power Room)
#05FT White/Gray 12" Floor Tile & Mastic (Room 112)
#06SR I White Sheetrock & Compound (Room 123)
#07SR I White Sheetrock & Compound (Room 114)
#08CP White/Gray 2X2 Ceiling Panel (Power Room)
#09CP White/Gray 2X4 Ceiling Panel (Room 126)
#10CP White/Gray 2X4 Ceiling Panel (Room 125)
#11CP \ White/Gray 2X2 Ceiling Panel (Room 129)
#12CP \ White/Gray 2X2 Ceiling Panel (Break Room)
#13CP J White/Gray 2X4 Ceiling Panel (Room 11 2)
I NSPECTOR/SAMPLER Ron Aunquoe
DATE RECEIVED BY DATE
1-2- - 2.C)
I
Black
Black
Black
T-1
T-2
T-3
T-4
T-5
T-6
SAMPLE LOCATION MAP
PROJECT: . Asbestos Survey Sample Location Sheet
LOCATION: Building 852 MAFB Wichita, Ks
CLIENT: Krehbiel Architecture
#11CP
®i l
®b
#09CP ' . ®i~
DATE 10-29-2020
BY Ron Aunquoe
JOB NO.
#OSFT
__,_--H-#13CP
01VG
01WM
10CP
SHEET NO.
OF
l I i I I I
I J i I l i
I I i
I I
CREDENTIALS
Expiration: 10/9/2021 Certificate Number: 6970226
1~ Precision Environmental
215 S. Laura :J Wichita, KS 67211 :J Phone: (316) 264-7050 :J Email: training@isienvironmental.com
Ron Aunquoe has successfully completed a course in and passed the final written exam with a score of at least 70% for EPA and Missouri Approved
AHERA Asbestos Inspector Refresher Training EPA/AHERA Accreditation for under 40 CFR Part 763, Subpart E, Appendix C, Section 206 of the Toxic Substances Control Act (TSCA Title II), 15 U.S.C. 2646. Missouri Training Provider MO #126
. ·' /. "-..._, _j-·· "-==-<. / · .•. ::... . ...-:,. ·~ ;···,.._.~ ··:.- -~-<---
'---- l