Attachment 17_230700_THERMAL INSULATION FOR MECHANICAL SYSTEMS 2025-04-03.pdf
PDF 874 KB Posted
- Attached to
- Offutt AFB Multiple Award Construction Contract (MACC) Federal contract opportunity
- Solicitation number
- FA4600-25-R-0002
About this file
This document is a technical specification section (Section 23 07 00) for Thermal Insulation for Mechanical Systems at Offutt Air Force Base, specifically for HVAC repair project B1226. The specification provides comprehensive technical requirements for insulating mechanical systems, including pipes, ducts, and associated equipment, with detailed guidelines on:
Insulation materials include cellular glass, mineral fiber, flexible elastomeric, and phenolic foam, with specific requirements for different temperature ranges and applications. The document specifies minimum insulation thicknesses, installation methods, vapor barrier requirements, and jacket specifications for various piping systems (chilled water, hot water, domestic water, steam) and duct systems. Key installation instructions cover attachment methods, sealing techniques, handling of fittings and accessories, and requirements for exposed and concealed insulation. The specification ensures compliance with ASHRAE 90.1 energy standards and includes provisions for recycled materials, indoor air quality, and specific application techniques for different mechanical system components.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OFFUTT AFB HVAC REPAIR, B1226 B1226
SECTION 23 07 00
THERMAL INSULATION FOR MECHANICAL SYSTEMS
02/13, CHG 7: 05/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. At the discretion of the Government, the manufacturer of any material supplied will be required to furnish test reports pertaining to any of the tests necessary to assure compliance with the standard or standards referenced in this specification.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 90.1 - SI (2019; Errata 1-4 2020; Addenda BY-CP 2020; Addenda AF-DB 2020; Addenda A-G 2020; Addenda F-Y 2021; Errata 5-7 2021;
Interpretation 1-4 2020; Interpretation 5-8 2021; Addenda AU-CM 2022) Energy Standard for Buildings Except Low-Rise Residential Buildings
ASTM INTERNATIONAL (ASTM)
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A240/A240M (2020a) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM A580/A580M (2018) Standard Specification for Stainless Steel Wire
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM C195 (2007; R 2013) Standard Specification for Mineral Fiber Thermal Insulating Cement
ASTM C450 (2008) Standard Practice for Fabrication of Thermal Insulating Fitting Covers for NPS Piping, and Vessel Lagging
ASTM C533 (2017) Standard Specification for Calcium Silicate Block and Pipe Thermal Insulation
ASTM C534/C534M (2020a) Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular
SECTION 23 07 00 Page 1
FA4600-25-R-0002
Attachment 17
Form
ASTM C547 (2022) Standard Specification for Mineral Fiber Pipe Insulation
ASTM C552 (2022) Standard Specification for Cellular Glass Thermal Insulation
ASTM C591 (2021) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C610 (2015) Standard Specification for Molded Expanded Perlite Block and Pipe Thermal Insulation
ASTM C647 (2008; R 2013) Properties and Tests of Mastics and Coating Finishes for Thermal Insulation
ASTM C755 (2019b) Standard Practice for Selection of Water Vapor Retarders for Thermal Insulation
ASTM C795 (2008; R 2018) Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel
ASTM C916 (2020) Standard Specification for Adhesives for Duct Thermal Insulation
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM C921 (2010; R 2015) Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation
ASTM C1126 (2018) Standard Specification for Faced or Unfaced Rigid Cellular Phenolic Thermal Insulation
ASTM C1136 (2021) Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation
ASTM C1710 (2011) Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form
ASTM D882 (2012) Tensile Properties of Thin Plastic Sheeting
ASTM D2863 (2019) Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM D5590 (2000; R 2010; E 2012) Standard Test
SECTION 23 07 00 Page 2
FA4600-25-R-0002
Method for Determining the Resistance of Paint Films and Related Coatings to Fungal Defacement by Accelerated Four-Week Agar Plate Assay
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E96/E96M (2022) Standard Test Methods for Gravimetric Determination ofWater Vapor Transmission Rate of Materials
ASTM E2231 (2021) Standard Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning Characteristics
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-58 (2018) Pipe Hangers and Supports - Materials, Design and Manufacture, Selection, Application, and Installation
MIDWEST INSULATION CONTRACTORS ASSOCIATION (MICA)
MICA Insulation Stds (8th Ed) National Commercial & Industrial Insulation Standards
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 90A (2021) Standard for the Installation of Air Conditioning and Ventilating Systems
NFPA 90B (2021) Standard for the Installation of Warm Air Heating and Air Conditioning Systems
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SECTION 23 07 00 Page 3
FA4600-25-R-0002
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
TECHNICAL ASSOCIATION OF THE PULP AND PAPER INDUSTRY (TAPPI)
TAPPI T403 OM (2015) Bursting Strength of Paper
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-A-3316 (1987; Rev C; Am 2 1990) Adhesives, Fire-Resistant, Thermal Insulation
MIL-A-24179 (1969; Rev A; Am 2 1980; Notice 1 1987;
Notice 2 2020) Adhesive, Flexible Unicellular-Plastic Thermal Insulation
MIL-PRF-19565 (1988; Rev C) Coating Compounds, Thermal Insulation, Fire- and Water-Resistant, Vapor-Barrier
UNDERWRITERS LABORATORIES (UL)
UL 94 (2013; Reprint Apr 2022) UL Standard for Safety Tests for Flammability of Plastic Materials for Parts in Devices and Appliances
UL 723 (2018) UL Standard for Safety Test for Surface Burning Characteristics of Building Materials
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SYSTEM DESCRIPTION
1.2.1 General
Provide field-applied insulation and accessories on mechanical systems as specified herein; factory-applied insulation is specified under the piping, duct or equipment to be insulated. Provide insulation of heat distribution systems and chilled water systems outside of buildings as specified in Section 33 61 13 PRE-ENGINEERED UNDERGROUND HEAT DISTRIBUTION SYSTEM, Section 33 63 13.19 CONCRETE TRENCH HYDRONIC AND STEAM ENERGY DISTRIBUTION, Section 33 60 02 ABOVEGROUND HEAT DISTRIBUTION SYSTEM, and Section 33 61 13.13 PREFABRICATED UNDERGROUND HYDRONIC ENERGY DISTRIBUTION. Furnish and install field applied insulation materials required for use on Government-furnished items as listed in the SPECIAL
CONTRACT REQUIREMENTS.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
SECTION 23 07 00 Page 4
FA4600-25-R-0002
PROCEDURES:
Submit the three SD types, SD-02 Shop Drawings, SD-03 Product Data, and SD-08 Manufacturer's Instructions at the same time for each system.
SD-02 Shop Drawings
MICA Plates; G
Pipe Insulation Systems and Associated Accessories
Duct Insulation Systems and Associated Accessories
Recycled content for insulation materials; S
SD-03 Product Data
Pipe Insulation Systems; G
Duct Insulation Systems; G
SD-04 Samples
Thermal Insulation; G
Display Samples; G
SD-07 Certificates
Indoor air quality for adhesives; S
SD-08 Manufacturer's Instructions
Pipe Insulation Systems; G
Duct Insulation Systems; G
1.4 CERTIFICATIONS
1.4.1 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
SECTION 23 07 00 Page 5
FA4600-25-R-0002
1.5 QUALITY ASSURANCE
1.5.1 Installer Qualification
Qualified installers will have successfully completed three or more similar type jobs within the last 5 years.
1.6 DELIVERY, STORAGE, AND HANDLING
Deliver materials in the manufacturer's unopened containers. Protect materials delivered and placed in storage from weather, humidity, dirt, dust and other contaminants. The Contracting Officer may reject insulation material and supplies that become dirty, dusty, wet, or contaminated by some other means. Attach manufacturer's stamp or label giving the name of the manufacturer and brand, and a description of the material, date codes, and approximate shelf life (if applicable) to packages or standard containers of insulation, jacket material, cements, adhesives, and coatings delivered for use, and samples required for approval. Insulation packages and containers must be asbestos free.
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
Provide materials which are the standard products of manufacturers regularly engaged in the manufacture of such products and that essentially duplicate items that have been in satisfactory use for at least 2 years prior to bid opening. Submit a complete list of materials, including manufacturer's descriptive technical literature, performance data, catalog cuts, and installation instructions. Include the product number, k-value, thickness and furnished accessories including adhesives, sealants and jackets for each mechanical system requiring insulation. The product data must be copyrighted, have an identifying or publication number, and have been published prior to the issuance date of this solicitation. Submit materials furnished under this section together in a booklet.
2.1.1 Insulation System
Provide insulation systems in accordance with the approved MICA National Insulation Standards plates as supplemented by this specification.
Provide field-applied insulation for heating, ventilating, and cooling (HVAC) air distribution systems and piping systems that are located within, on, under, and adjacent to buildings; and for plumbing systems.
Provide CFC and HCFC free insulation.
2.1.2 Surface Burning Characteristics
Unless otherwise specified, insulation must have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Determine flame spread, and smoke developed indexes, by ASTM E84 or UL 723 . Test insulation in the same density and installed thickness as the material to be used in the actual construction. Prepare and mount test specimens according to ASTM E2231.
2.2 MATERIALS
Provide insulation that meets or exceed the requirements of ASHRAE 90.1.
Ensure insulation exterior is cleanable, grease resistant, non-flaking and non-peeling. Provide compatible materials that do not contribute to
SECTION 23 07 00 Page 6
FA4600-25-R-0002
corrosion, soften, or otherwise attack surfaces to which applied in either wet or dry state. Use materials on stainless steel surfaces meeting ASTM C795 requirements. Do not use calcium silicate on chilled or cold water systems. Use asbestos free materials. Provide product recognized under UL 94 (if containing plastic) and listed in FM APP GUIDE.
2.2.1 Adhesives
Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 (HVAC duct sealants must meet limit requirements of "Other" category within SCAQMD Rule 1168 sealants table).
Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for adhesives.
2.2.1.1 Acoustical Lining Insulation Adhesive
Provide a nonflammable, fire-resistant adhesive conforming to ASTM C916, Type I.
2.2.1.2 Mineral Fiber Insulation Cement
Provide cement in accordance with ASTM C195.
2.2.1.3 Lagging Adhesive
Lagging is the material used for thermal insulation, especially around a cylindrical object. This may include the insulation as well as the cloth/material covering the insulation. To resist mold/mildew, use lagging adhesive meeting ASTM D5590 with 0 growth rating. Provide nonflammable and fire-resistant lagging adhesives that have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Ensure adhesive is MIL-A-3316 , Class 1, pigmented white and suitable for bonding fibrous glass cloth to faced and unfaced fibrous glass insulation board; for bonding cotton brattice cloth to faced and unfaced fibrous glass insulation board; for sealing edges of and bonding glass tape to joints of fibrous glass board; for bonding lagging cloth to thermal insulation; or Class 2 for attaching fibrous glass insulation to metal surfaces. Apply lagging adhesives in strict accordance with the manufacturer's recommendations for pipe and duct insulation.
2.2.1.4 Contact Adhesive
Adhesives may be any of, but not limited to, the neoprene based, rubber based, or elastomeric type that have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Ensure adhesive does not adversely affect, initially or in service, the insulation to which it is applied, nor cause any corrosive effect on metal to which it is applied. Ensure that any solvent dispersing medium or volatile component of the adhesive has no objectionable odor and does not contain any benzene or carbon tetrachloride. Ensure dried adhesive does not emit nauseous, irritating, or toxic volatile matters or aerosols when the adhesive is heated to any
SECTION 23 07 00 Page 7
FA4600-25-R-0002
temperature up to 212 degrees F. The dried adhesive must be nonflammable and fire resistant. Flexible Elastomeric Adhesive: Comply with MIL-A-24179 , Type II, Class I. Provide product listed in FM APP GUIDE.
2.2.2 Caulking
ASTM C920, Type S, Grade NS, Class 25, Use A.
2.2.3 Corner Angles
Nominal 0.016 inch aluminum 1 by 1 inch with factory applied kraft backing. Aluminum must be ASTM B209, Alloy 3003, 3105, or 5005.
2.2.4 Fittings
Fabricated Fittings are the prefabricated fittings for flexible elastomeric pipe insulation systems in accordance with ASTM C1710.
Together with the flexible elastomeric tubes, they provide complete system integrity for retarding heat gain and controlling condensation drip from chilled-water and refrigeration systems. Flexible elastomeric, fabricated fittings provide thermal protection (0.25 k) and condensation resistance (0.05 Water Vapor Transmission factor). For satisfactory performance, use properly installed protective vapor retarder/barriers and vapor stops on high relative humidity and below ambient temperature applications to reduce movement of moisture through or around the insulation to the colder interior surface.
2.2.5 Finishing Cement
ASTM C450: Mineral fiber hydraulic-setting thermal insulating and finishing cement. All cements that may come in contact with Austenitic stainless steel must comply with ASTM C795.
2.2.6 Fibrous Glass Cloth and Glass Tape
Provide fibrous glass cloth, with 20X20 maximum mesh size, and glass tape with maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Provide tape consisting of 4 inch wide rolls. Provide Class 3 tape that is 4.5 ounces/square yard.
Elastomeric Foam Tape: Black vapor-retarder foam tape with acrylic adhesive containing an anti-microbial additive.
2.2.7 Staples
Outward clinching type monel .
2.2.8 Jackets
2.2.8.1 Aluminum Jackets
Provide aluminum jackets consisting of corrugated, embossed or smooth sheet, 0.016 inch nominal thickness; ASTM B209, Temper H14, Temper H16, Alloy 3003, 5005, or 3105. Do not use corrugated aluminum jacket outdoors. Aluminum jacket securing bands must be Type 304 stainless steel, 0.015 inch thick, 1/2 inch wide for pipe under 12 inch diameter and 3/4 inch wide for pipe over 12 inch and larger diameter . Aluminum jacket circumferential seam bands must be 2 by 0.016 inch aluminum matching jacket material. Ensure bands for insulation below ground are 3/4 by 0.020 inch thick stainless steel, or fiberglass reinforced tape.
SECTION 23 07 00 Page 8
FA4600-25-R-0002
The jacket may, at the option of the Contractor, be provided with a factory fabricated Pittsburgh or "Z" type longitudinal joint. When the "Z" joint is used, use bands at the circumferential joints that are designed by the manufacturer to seal the joints and hold the jacket in place.
2.2.8.2 Polyvinyl Chloride (PVC) Jackets
Polyvinyl chloride (PVC) jacket and fitting covers must have high impact strength, ultraviolet (UV) resistant rating or treatment and moderate chemical resistance with minimum thickness 0.030 inch.
2.2.8.3 Vapor Barrier/Weatherproofing Jacket
Provide laminated self-adhesive vapor barrier/weatherproofing jacket, greater than 3 plies standard grade, silver, white, black and embossed or greater than 8 ply (minimum 2.9 mils adhesive); with 0.0000 permeability when tested in accordance with ASTM E96/E96M, using the water transmission rate test method; heavy duty, white or natural; and UV resistant.
Flexible Elastomeric exterior foam with factory applied, UV Jacket made with a cold weather acrylic adhesive. Construction of laminate designed to provide UV resistance, high puncture, tear resistance and excellent Water Vapor Transmission (WVT) rate.
2.2.8.4 Vapor Barrier/Vapor Retarder
Apply the following criteria to determine which system is required.
a. On ducts, equip piping and equipment operating below 65 degrees F or located outside with a vapor barrier.
b. Install ducts, pipes and equipment that are located inside and that always operate above 65 degrees F with a vapor retarder where required as stated in paragraph VAPOR RETARDER REQUIRED.
2.2.9 Vapor Retarder Required
ASTM C921, Type I, minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork, where a minimum puncture resistance of 25 Beach units is acceptable. Minimum tensile strength, 35 pounds/inch width. ASTM C921, Type II, minimum puncture resistance 25 Beach units, tensile strength minimum 20 pounds/inch width. Use jackets on insulation exposed in finished areas that have white finish suitable for painting without sizing. Based on the application, insulation materials that require manufacturer or fabricator applied pipe insulation jackets are cellular glass, when all joints are sealed with a vapor barrier mastic, and mineral fiber. Ensure all non-metallic jackets have a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Flexible elastomerics require (in addition to vapor barrier skin) vapor retarder jacketing for high relative humidity and below ambient temperature applications.
2.2.9.1 White Vapor Retarder All Service Jacket (ASJ)
ASJ is for use on hot/cold pipes, ducts, or equipment indoors or outdoors if covered by a suitable protective jacket. Provide product which meets all physical property and performance requirements of ASTM C1136, Type I, except a minimum burst strength of 85 psi. ASTM D2863 Limited Oxygen Index (LOI) is a minimum of 31.
SECTION 23 07 00 Page 9
FA4600-25-R-0002
In addition, do not use paper or other moisture-sensitive material for the outer exposed surface or the inner-most surface contacting the insulation. Ensure the outer exposed surface is white and has an emittance no less than 0.80. Ensure the outer exposed surface is paintable.
2.2.9.2 Vapor Retarder/Vapor Barrier Mastic Coatings
2.2.9.2.1 Vapor Barrier
The vapor barrier must be self adhesive (minimum 2 mils adhesive, 3 mils embossed) greater than 3 plies standard grade, silver, white, black and embossed white jacket for use on hot/cold pipes. Ensure permeability is less than 0.02 when tested in accordance with ASTM E96/E96M. Provide products meeting UL 723 or ASTM E84 flame and smoke requirements and that are UV resistant.
2.2.9.2.2 Vapor Retarder
Provide fire and water resistant vapor retarder coating appropriately selected for either outdoor or indoor service. Color must be white.
Ensure the water vapor permeance of the compound is in accordance with ASTM C755, Section 7.2.2, Table 2, for insulation type and service conditions. Provide nonflammable, fire resistant coating. To resist mold/mildew, provide coating meeting ASTM D5590 with 0 growth rating.
Ensure coating meets MIL-PRF-19565 Type II (if selected for indoor service) and is Qualified Products Database listed. Determine all other application and service properties pursuant to ASTM C647.
2.2.9.3 Laminated Film Vapor Retarder
ASTM C1136, Type I, maximum moisture vapor transmission 0.02 perms, minimum puncture resistance 50 Beach units on all surfaces except concealed ductwork; where Type II, maximum moisture vapor transmission
0.02 perms, a minimum puncture resistance of 25 Beach units is acceptable. Provide vapor retarder with a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Flexible Elastomeric exterior foam with factory applied UV Jacket. Construction of laminate designed to provide UV resistance, high puncture, tear resistance and an excellent WVT rate.
2.2.9.4 Polyvinylidene Chloride (PVDC) Film Vapor Retarder
Provide PVDC film vapor retarder with a maximum moisture vapor transmission of 0.02 perms, minimum puncture resistance of 150 Beach units, a minimum tensile strength in any direction of 30 lb/inch when tested in accordance with ASTM D882, and a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84.
2.2.9.5 Polyvinylidene Chloride Vapor Retarder Adhesive Tape
Requirements must meet the same as specified for Laminated Film Vapor Retarder above.
2.2.9.6 Vapor Barrier/Weather Barrier
Ensure the vapor barrier is greater than 3 ply self adhesive laminate
SECTION 23 07 00 Page 10
FA4600-25-R-0002
-white vapor barrier jacket- superior performance (less than 0.0000 permeability when tested in accordance with ASTM E96/E96M). Provide vapor barrier meeting UL 723 or ASTM E84 25 flame and 50 smoke requirements; and UV resistant. Minimum burst strength 185 psi in accordance with TAPPI T403 OM . Tensile strength 68 lb/inch width (PSTC-1000). Provide tape as specified for laminated film vapor barrier above.
2.2.10 Vapor Retarder Not Required
ASTM C921, Type II, Class D, minimum puncture resistance 50 Beach units on all surfaces except ductwork, where Type IV, maximum moisture vapor transmission 0.10, a minimum puncture resistance of 25 Beach units is acceptable. Provide jacket with a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84.
2.2.11 Wire
Soft annealed ASTM A580/A580M Type 302, 304 or 316 stainless steel, 16 or 18 gauge.
2.2.12 Insulation Bands
Provide 1/2 inch wide; 26 gauge stainless steel insulation bands.
2.2.13 Sealants
Choose sealants from the butyl polymer type, the styrene-butadiene rubber type, or the butyl type of sealants. Provide sealants with a maximum permeance of 0.02 perms based on Procedure B for ASTM E96/E96M, and a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84.
2.3 PIPE INSULATION SYSTEMS
Conform insulation materials to Table 1 and minimum insulation thickness as listed in Table 2 and meet or exceed the requirements of ASHRAE 90.1 - SI . Limit pipe insulation materials to those listed herein and meeting the following requirements:
2.3.1 Recycled Materials
Provide insulation materials containing the following minimum percentage of recycled material content by weight:
Rock Wool: 75 percent slag of weight Fiberglass: 20 percent glass cullet Rigid Foam: 9 percent recovered material Phenolic Rigid Foam: 9 percent recovered material
Provide data identifying percentage of recycled content for insulation materials.
2.3.2 Aboveground Cold Pipeline ( -30 to 60 deg. F)
Provide insulation for outdoor, indoor, exposed or concealed applications, as follows:
SECTION 23 07 00 Page 11
FA4600-25-R-0002
2.3.2.1 Cellular Glass
ASTM C552, Type II, and Type III. Supply the insulation from the fabricator with (paragraph WHITE VAPOR RETARDER ALL SERVICE JACKET (ASJ)) ASJ vapor retarder and installed with all longitudinal overlaps sealed and all circumferential joints ASJ taped or supply the insulation unfaced from the fabricator and install with all longitudinal and circumferential joints sealed with vapor barrier mastic.
2.3.2.2 Flexible Elastomeric Cellular Insulation
Closed-cell, foam- or expanded-rubber materials containing anti-microbial additive, complying with ASTM C534/C534M, Grade 1, Type I or II. Type I, Grade 1 for tubular materials. Type II, Grade 1, for sheet materials.
Ensure Type I and II have vapor retarder/vapor barrier skin on one or both sides of the insulation, and require an additional exterior vapor retarder covering for high relative humidity and below ambient temperature applications.
2.3.2.3 Mineral Fiber Insulation with Integral Wicking Material (MFIWM)
ASTM C547. Install in accordance with manufacturer's instructions. Do not use in applications exposed to outdoor ambient conditions in climatic zones 1 through 4.
2.3.2.4 Polyisocyanurate Insulation
ASTM C591, Type I. Supply the insulation with a factory applied vapor retarder/barrier that complies with Section 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS. The insulation and all covering must pass the flame spread index of 25 and the smoke developed index of 50 when tested in accordance with ASTM E84.
2.3.3 Aboveground Hot Pipeline (Above 60 deg. F)
Provide insulation for outdoor, indoor, exposed or concealed applications meeting the following requirements. Supply the insulation with manufacturer's recommended factory-applied jacket/vapor barrier.
2.3.3.1 Mineral Fiber
ASTM C547, Types I, II or III, supply the insulation with manufacturer's recommended factory-applied jacket.
2.3.3.2 Calcium Silicate
ASTM C533, Type I indoor only, or outdoors above 250 degrees F pipe temperature. Supply insulation with the manufacturer's recommended factory-applied jacket/vapor barrier.
2.3.3.3 Cellular Glass
ASTM C552, Type II and Type III. Supply the insulation with manufacturer's recommended factory-applied jacket.
2.3.3.4 Flexible Elastomeric Cellular Insulation
Closed-cell, foam- or expanded-rubber materials containing anti-microbial additive, complying with ASTM C534/C534M, Grade 1, Type I or II to 220
SECTION 23 07 00 Page 12
FA4600-25-R-0002
degrees F service. Type I for tubular materials. Type II for sheet materials.
2.3.3.5 Phenolic Insulation
ASTM C1126 Type III to 250 degrees F service must comply with ASTM C795.
Supply the insulation with manufacturer's recommended factory-applied jacket/vapor barrier.
2.3.3.6 Perlite Insulation
ASTM C610
2.3.3.7 Polyisocyanurate Insulation
ASTM C591, Type I. Supply the insulation with a factory applied vapor retarder/barrier that complies with Section 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS. The insulation and all covering must pass the flame spread index of 25 and the smoke developed index of 50 when tested in accordance with ASTM E84.
2.3.4 Aboveground Dual Temperature Pipeline
Select insulation for use over a dual temperature pipeline system (Outdoor, Indoor - Exposed or Concealed) in accordance with the most limiting/restrictive case. Find an allowable material from paragraph PIPE INSULATION MATERIALS and determine the required thickness from the most restrictive case. Use the thickness listed in paragraphs INSULATION THICKNESS for cold & hot pipe applications.
2.3.5 Below-ground Pipeline Insulation
For below-ground pipeline insulation, use cellular glass, ASTM C552, type
II.
2.4 DUCT INSULATION SYSTEMS
2.4.1 Factory Applied Insulation
Provide factory-applied ASTM C552, cellular glass thermal insulation according to manufacturer's recommendations for insulation with insulation manufacturer's standard reinforced fire-retardant vapor barrier, with identification of installed thermal resistance (R) value and out-of-package R value.
2.4.1.1 Rigid Insulation
Calculate the minimum thickness in accordance with ASHRAE 90.1.
2.4.1.2 Blanket Insulation
Calculate minimum thickness in accordance with ASHRAE 90.1.
2.4.2 Acoustical Duct Lining
2.4.2.1 General
For ductwork indicated or specified in Section 23 30 00 HVAC AIR DISTRIBUTION to be acoustically lined, provide external insulation in
SECTION 23 07 00 Page 13
FA4600-25-R-0002
accordance with this specification section and in addition to the acoustical duct lining. Do not use acoustical lining in place of duct wrap or rigid board insulation (insulation on the exterior of the duct).
2.4.2.2 Duct Liner
Flexible Elastomeric Acoustical and Conformable Duct Liner Materials:
Flexible Elastomeric Thermal, Acoustical and Conformable Insulation Compliance with ASTM C534/C534M Grade 1, Type II; and NFPA 90A or NFPA 90B as applicable.
2.4.3 Duct Insulation Jackets
2.4.3.1 All-Purpose Jacket
Provide insulation with insulation manufacturer's standard reinforced fire-retardant jacket with or without integral vapor barrier as required by the service. In exposed locations, provide jacket with a white surface suitable for field painting.
2.4.3.2 Metal Jackets
2.4.3.2.1 Aluminum Jackets
ASTM B209, Temper H14, minimum thickness of 27 gauge ( 0.016 inch), with factory-applied polyethylene and kraft paper moisture barrier on inside surface. Provide smooth surface jackets for jacket outside dimension 8 inches and larger. Provide corrugated surface jackets for jacket outside dimension 8 inches and larger. Provide stainless steel bands, minimum width of 1/2 inch.
2.4.3.2.2 Stainless Steel Jackets
ASTM A167 or ASTM A240/A240M ; Type 304, minimum thickness of 33 gauge (
0.010 inch), smooth surface with factory-applied polyethylene and kraft paper moisture barrier on inside surface. Provide stainless steel bands, minimum width of 1/2 inch.
2.4.3.3 Vapor Barrier/Weatherproofing Jacket
Provide vapor barrier/weatherproofing jacket that is laminated self-adhesive (minimum 2 mils adhesive, 3 mils embossed) less than 0.0000 permeability, (greater than 3 ply, standard grade, silver, white, black and embossed or greater than 8 ply (minimum 2.9 mils adhesive), heavy duty white or natural).
PART 3 EXECUTION
3.1 APPLICATION - GENERAL
Apply insulation to unheated and uncooled piping and equipment. Do not compress flexible elastomeric cellular insulation at joists, studs, columns, ducts, and hangers. The insulation must not pull apart after a one hour period; replace any insulation found to pull apart after one hour.
3.1.1 Display Samples
Submit and display, after approval of materials, actual sections of installed systems, properly insulated in accordance with the specification
SECTION 23 07 00 Page 14
FA4600-25-R-0002
requirements. Such actual sections must remain accessible to inspection throughout the job and will be reviewed from time to time for controlling the quality of the work throughout the construction site. Identify each material used by indicating on an attached sheet the specification requirement for the material and the material by each manufacturer intended to meet the requirement. The Contracting Officer will inspect display sample sections at the jobsite. Keep approved display sample sections on display at the jobsite during the construction period. Upon completion of construction, the display sample sections will be closed and sealed.
3.1.1.1 Pipe Insulation Display Sections
Include as a minimum an elbow or tee, a valve, dielectric waterways and flanges, a hanger with protection shield and insulation insert, or dowel as required, at support point, method of fastening and sealing insulation at longitudinal lap, circumferential lap, butt joints at fittings and on pipe runs, and terminating points for each type of pipe insulation used on the job, and for hot pipelines and cold pipelines, both interior and exterior, even when the same type of insulation is used for these services.
3.1.1.2 Duct Insulation Display Sections
Display sample sections for rigid and flexible duct insulation used on the job. Use a temporary covering to enclose and protect display sections for duct insulation exposed to weather
3.1.2 Installation
Except as otherwise specified, install material in accordance with the manufacturer's written instructions. Do not apply insulation materials until tests specified in other sections of this specification are completed. Remove material such as rust, scale, dirt and moisture from surfaces to receive insulation. Keep insulaton clean and dry. Do not remove insulation from its shipping containers until the day it is ready to use and return to like containers or equally protect from dirt and moisture at the end of each workday. Thoroughly clean insulation that becomes dirty prior to use. If insulation becomes wet or if cleaning does not restore the surfaces to like new condition, reject the insulation, and immediately remove from the jobsite. Stagger joints on multi layer insulation. Mix mineral fiber thermal insulating cement with demineralized water when used on stainless steel surfaces. Install insulation, jacketing and accessories in accordance with MICA Insulation Stds plates except where modified herein or on the drawings.
3.1.3 Firestopping
Where pipes and ducts pass through fire walls, fire partitions, above grade floors, and fire rated chase walls, seal the penetration with fire stopping materials as specified in Section 07 84 00 FIRESTOPPING. The protection of ducts at point of passage through firewalls must be in accordance with NFPA 90A and/or NFPA 90B. All other penetrations, such as piping, conduit, and wiring, through firewalls must be protected with a material or system of the same hourly rating that is listed by UL, FM, or a NRTL.
SECTION 23 07 00 Page 15
FA4600-25-R-0002
3.1.4 Painting and Finishing
Paint as specified in Section 09 90 00 PAINTS AND COATINGS.
3.1.5 Installation of Flexible Elastomeric Cellular Insulation
Install flexible elastomeric cellular insulation with seams and joints sealed with rubberized contact adhesive. Do not use flexible elastomeric cellular insulation on surfaces greater than 220 degrees F. Stagger seams when applying multiple layers of insulation. Protect insulation exposed to weather and not shown to have vapor barrier weatherproof jacketing with two coats of UV resistant finish or PVC or metal jacketing as recommended by the manufacturer after the adhesive is dry and cured.
3.1.5.1 Adhesive Application
Apply a brush coating of adhesive to both butt ends to be joined and to both slit surfaces to be sealed. Allow the adhesive to set until dry to touch but tacky under slight pressure before joining the surfaces. Ensure insulation seals at seams and joints are not capable of being pulled apart one hour after application. Replace insulation that can be pulled apart one hour after installation.
3.1.5.2 Adhesive Safety Precautions
Use natural cross-ventilation, local (mechanical) pickup, and/or general area (mechanical) ventilation to prevent an accumulation of solvent vapors, keeping in mind the ventilation pattern must remove any heavier-than-air solvent vapors from lower levels of the workspaces.
Gloves and spectacle-type safety glasses are recommended in accordance with safe installation practices.
3.1.6 Welding
Welding is not permitted on piping, duct without written approval of the Contracting Officer. The capacitor discharge welding process may be used for securing metal fasteners to duct .
3.1.7 Pipes/ Ducts/ That Require Insulation
Insulation is required on all pipes, ducts, except for omitted items as specified.
3.2 PIPE INSULATION SYSTEMS INSTALLATION
3.2.1 Pipe Insulation
3.2.1.1 General
Install pipe insulation on aboveground hot and cold pipeline systems as specified below to form a continuous thermal retarder/barrier, including straight runs, fittings and appurtenances unless specified otherwise.
Install full length units of insulation using a single cut piece to complete a run. Do not use cut pieces or scraps abutting each other.
Omit pipe insulation on the following:
a. Pipe used solely for fire protection.
SECTION 23 07 00 Page 16
FA4600-25-R-0002
b. Chromium plated pipe to plumbing fixtures. However, for fixtures used by the physically handicapped, insulate the hot water supply and drain, including the trap, where exposed.
c. Sanitary drain lines.
d. Air chambers.
e. Adjacent insulation.
f. ASME stamps.
g. Access plates of fan housings.
h. Cleanouts or handholes.
3.2.1.2 Pipes Passing Through Walls, Roofs, and Floors
Provide continuous pipe insulation through the sleeve.
Provide an aluminum jacket or vapor barrier/weatherproofing self adhesive jacket (minimum 2 mils adhesive, 3 mils embossed) less than 0.0000 permeability, greater than 3 ply standard grade, silver, white, black and embossed with factory applied moisture retarder over the insulation wherever penetrations require sealing.
3.2.1.2.1 Penetrate Interior Walls
Provide aluminum jacket or vapor barrier/weatherproofing - self adhesive jacket (minimum 2 mils adhesive, 3 mils embossed) less than 0.0000 permeability, greater than 3 plies standard grade, silver, white, black and embossed which extends 2 inches beyond either side of the wall and secure on each end with a band.
3.2.1.2.2 Penetrating Floors
Extend the aluminum jacket from a point below the backup material to a point 10 inches above the floor with one band at the floor and one not more than 1 inch from the end of the aluminum jacket.
3.2.1.2.3 Penetrating Waterproofed Floors
Extend the aluminum jacket rom below the backup material to a point 2 inches above the flashing with a band 1 inch from the end of the aluminum jacket.
3.2.1.2.4 Penetrating Exterior Walls
Continue the aluminum jacket required for pipe exposed to weather through the sleeve to a point 2 inches beyond the interior surface of the wall.
3.2.1.2.5 Penetrating Roofs
Insulate pipe as required for interior service to a point flush with the top of the flashing and sealed with flashing sealant. Tightly butt the insulation for exterior application to the top of flashing and interior insulation. Extend the exterior aluminum jacket 2 inches down beyond the end of the insulation to form a counter flashing. Seal the flashing and counter flashing underneath with metal jacketing/flashing sealant.
SECTION 23 07 00 Page 17
FA4600-25-R-0002
3.2.1.2.6 Hot Water Pipes Supplying Lavatories or Other Similar Heated Service
Terminate the insulation on the backside of the finished wall. Protect the insulation termination with two coats of vapor barrier coating with a minimum total thickness of 1/16 inch applied with glass tape embedded between coats (if applicable). Extend the coating out onto the insulation 2 inches and seal the end of the insulation. Overlap glass tape seams 1 inch. Caulk the annular space between the pipe and wall penetration with approved fire stop material. Cover the pipe and wall penetration with a properly sized (well fitting) escutcheon plate. Ensure the escutcheon plate overlaps the wall penetration at least 3/8 inches.
3.2.1.2.7 Domestic Cold Water Pipes Supplying Lavatories or Other Similar Cooling Service
Terminate the insulation on the finished side of the wall (i.e., insulation must cover the pipe throughout the wall penetration). Protect the insulation with two coats of weather barrier mastic (breather emulsion type weatherproof mastic impermeable to water and permeable to air) with a minimum total thickness of 1/16 inch. Extend the mastic out onto the insulation 2 inches and seal the end of the insulation. The annular space between the outer surface of the pipe insulation and caulk the wall penetration with an approved fire stop material having vapor retarder properties. Cover the pipe and wall penetration with a properly sized (well fitting) escutcheon plate. Ensure the escutcheon plate overlaps the wall penetration by at least 3/8 inches.
3.2.1.3 Pipes Passing Through Hangers
Ensure insulation, whether hot or cold application, is continuous through hangers. Support all horizontal pipes 2 inches and smaller on hangers with the addition of a Type 40 protection shield to protect the insulation in accordance with MSS SP-58 . Whenever insulation shows signs of being compressed, or when the insulation or jacket shows visible signs of distortion at or near the support shield, install insulation inserts as specified below for piping larger than 2 inches, or factory insulated hangers (designed with a load bearing core) can be used.
3.2.1.3.1 Horizontal Pipes Larger Than 2 Inches at 60 Degrees F and Above
Supported on hangers in accordance with MSS SP-58 , and Section 22 00 00
PLUMBING, GENERAL PURPOSE.
3.2.1.3.2 Horizontal Pipes Larger Than 2 Inches and Below 60 Degrees F
Supported on hangers with the addition of a Type 40 protection shield in accordance with MSS SP-58 . Install an insulation insert of cellular glass, prefabricated insulation pipe hangers, or perlite above 80 degrees F above each shield. Ensure insert covers no less than the bottom 180-degree arc of the pipe. Provide inserts that are the same thickness as the insulation, and extend 2 inches on each end beyond the protection shield. When insulation inserts are required in accordance with the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the weight of the pipe from crushing the insulation, as an option to installing insulation inserts. Ensure the insulation jacket is continuous over the wooden dowel, wooden block, or insulation insert.
SECTION 23 07 00 Page 18
FA4600-25-R-0002
3.2.1.3.3 Vertical Pipes
Supported with either Type 8 or Type 42 riser clamps with the addition of two Type 40 protection shields in accordance with MSS SP-58 covering the 360-degree arc of the insulation. Install an insulation insert of cellular glass or calcium silicate between each shield and the pipe.
Ensure the insert covers the 360-degree arc of the pipe. Provide inserts that are the same thickness as the insulation, and extend 2 inches on each end beyond the protection shield. When insulation inserts are required in accordance with the above, and the insulation thickness is less than 1 inch, wooden or cork dowels or blocks may be installed between the pipe and the shield to prevent the hanger from crushing the insulation, as an option instead of installing insulation inserts. Ensure the insulation jacket is continuous over the wooden dowel, wooden block, or insulation insert.
Support the vertical weight of the pipe with hangers located in a horizontal section of the pipe. When the pipe riser is longer than 30 feet, support the weight of the pipe additionally with hangers in the vertical run of the pipe that are directly clamped to the pipe, penetrating the pipe insulation. Use insulated hangers and seal the insulation jacket as indicated herein for anchors in a similar service.
3.2.1.3.4 Inserts
Covered with a jacket material of the same appearance and quality as the adjoining pipe insulation jacket, overlap the adjoining pipe jacket 1-1/2 inches, and seal as required for the pipe jacket. Use jacket material to cover inserts in flexible elastomeric cellular insulation conforming to ASTM C1136, Type 1, and is allowed to be of a different material than the adjoining insulation material.
3.2.1.4 Flexible Elastomeric Cellular Pipe Insulation
Use tubular form flexible elastomeric cellular pipe insulation for pipe sizes 6 inches and less. Grade 1, Do not stretch Type II sheet insulation used on pipes larger than 6 inches around the pipe. On pipes larger than 12 inches, adhere the insulation directly to the pipe on the lower 1/3 of the pipe. Stagger seams when applying multiple layers of insulation.
Insulate sweat fittings with miter-cut pieces the same size as on adjacent piping. Insulate screwed fittings with sleeved fitting covers fabricated from miter-cut pieces and overlap and seal to the adjacent pipe insulation. Type II requires an additional exterior vapor retarder/barrier covering for high relative humidity and below ambient temperature applications.
3.2.1.5 Pipes in high abuse areas.
In high abuse areas such as janitor closets and traffic areas in equipment rooms, kitchens, and mechanical rooms, utilize welded PVC , aluminum or flexible laminate cladding (comprised of elastomeric, plastic or metal foil laminate) laminated self-adhesive (minimum 2 mils adhesive, 3 mils embossed) vapor barrier/weatherproofing jacket, - less than 0.0000 permeability; (greater than 3 ply, standard grade, silver, white, black and embossed) jackets. Protect pipe insulation to the 6 foot level.
3.2.1.6 Pipe Insulation Material and Thickness
Pipe insulation materials must be as listed in Table 1 and must meet or exceed the requirements of ASHRAE 90.1.
SECTION 23 07 00 Page 19
FA4600-25-R-0002
TABLE 1
Insulation Material for Piping
Service
Material Specification Type Class VR/VB Req'd
Chilled Water (Supply & Return, Dual Temperature Piping, 40 F nominal)
Cellular Glass ASTM C552 II 2 Yes
Flexible Elastomeric Cellular ASTM C534/C534M I Yes
Mineral Fiber with Wicking Material
ASTM C547 I Yes
Heating Hot Water Supply & Return, Heated Oil (Max 250 F)
Mineral Fiber ASTM C547 I 1 No
Calcium Silicate ASTM C533 I No
Cellular Glass ASTM C552 II 2 No
Faced Phenolic Foam ASTM C1126 III Yes
Perlite ASTM C610 No
Flexible Elastomeric Cellular ASTM C534/C534M I 2 No
Cold Domestic Water Piping, Makeup Water & Drinking Fountain Drain Piping
Cellular Glass ASTM C552 II 2 No Flexible Elastomeric Cellular ASTM C534/C534M I No
Hot Domestic Water Supply & Recirculating Piping (Max 200 F)
Mineral Fiber ASTM C547 I 1 No
Cellular Glass ASTM C552 II 2 No
Flexible Elastomeric Cellular ASTM C534/C534M I No
Faced Phenolic Foam ASTM C1126 III Yes
Refrigerant Suction Piping (35 degrees F nominal)
Flexible Elastomeric Cellular ASTM C534/C534M I No
Cellular Glass ASTM C552 II 1 Yes
Compressed Air Discharge, Steam and Condensate Return (201 to 250 Degrees F
Cellular Glass ASTM C552 II No
Mineral Fiber ASTM C547 I 1 No
SECTION 23 07 00 Page 20
FA4600-25-R-0002
Insulation Material for Piping
Service
Material Specification Type Class VR/VB Req'd
Calcium Silicate ASTM C533 I No
Faced Phenolic Foam ASTM C1126 III Yes
Perlite ASTM C610 No
Flexible Elastomeric Cellular ASTM C534/C534M I 2 No
Exposed Lavatory Drains, Exposed Domestic Water Piping & Drains to Areas for Handicapped Personnel
Flexible Elastomeric Cellular ASTM C534/C534M I No
Horizontal Roof Drain Leaders (Including Underside of Roof Drain Fittings)
Flexible Elastomeric Cellular ASTM C534/C534M I No
Faced Phenolic Foam ASTM C1126 III Yes
Cellular Glass ASTM C552 III Yes
Condensate Drain Located Inside Building
Cellular Glass ASTM C552 II 2 No Flexible Elastomeric Cellular ASTM C534/C534M I No
Medium Temperature Hot Water, Steam and Condensate (251 to 350 Degrees F)
Mineral Fiber ASTM C547 I 1 No
Calcium Silicate ASTM C533 I No
Cellular Glass ASTM C552 I or II No
Perlite ASTM C610 No
Flexible Elastomeric Cellular ASTM C534/C534M I 2 No
High Temperature Hot Water & Steam (351 to 700 Degrees F)
Mineral Fiber ASTM C547 I 2 No
Calcium Silicate ASTM C533 I No Perlite ASTM C610 No
Cellular Glass ASTM C552 No
Brine Systems Cryogenics (-30 to 0 Degrees F)
Cellular Glass ASTM C552 II 2 No
Flexible Elastomeric Cellular ASTM C534/C534M I No
SECTION 23 07 00 Page 21
FA4600-25-R-0002
Insulation Material for Piping
Service
Material Specification Type Class VR/VB Req'd
Brine Systems Cryogenics (0 to 34 Degrees F)
Cellular Glass ASTM C552 II 2 No
Flexible Elastomeric Cellular ASTM C534/C534M I No
Note: VR/VB = Vapor Retarder/Vapor Barrier
TABLE 2
Piping Insulation Thickness (inch) Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.
Service
Material Tube And Pipe Size (inch)
<1 1-<1.5 1.5-<4 4-<8 > or = >8
Chilled Water (Supply & Return, Dual Temperature Piping, 40 Degrees F nominal)
Cellular Glass 1.5 2 2 2.5 3
Mineral Fiber with Wicking Material
1 1.5 1.5 2 2
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Cellular Glass 1.5 1.5 1.5 1.5 2
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Mineral Fiber with Wicking Material
1 1.5 1.5 2 2
Heating Hot Water Supply & Return, Heated Oil (Max 250 F)
Mineral Fiber 1.5 1.5 2 2 2
SECTION 23 07 00 Page 22
FA4600-25-R-0002
TABLE 2
Piping Insulation Thickness (inch) Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.
Service
Material Tube And Pipe Size (inch)
<1 1-<1.5 1.5-<4 4-<8 > or = >8
Calcium Silicate 2.5 2.5 3 3 3
Cellular Glass 2 2.5 3 3 3
Perlite 2.5 2.5 3 3 3
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Cold Domestic Water Piping, Makeup Water & Drinking Fountain Drain Piping
Cellular Glass 1.5 1.5 1.5 1.5 1.5
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Hot Domestic Water Supply & Recirculating Piping (Max 200 F)
Mineral Fiber 1 1 1 1.5 1.5
Cellular Glass 1.5 1.5 1.5 2 2
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Refrigerant Suction Piping (35 degrees F nominal)
Flexible Elastomeric Cellular 1 1 1 N/A N/A
Cellular Glass 1.5 1.5 1.5 1.5 1.5
Compressed Air Discharge, Steam and Condensate Return (201 to 250 Degrees F
Mineral Fiber 1.5 1.5 2 2 2
1.5* 2* 2.5* 3* 3.5*
Calcium Silicate 2.5 3 4 4 4.5
Cellular Glass 2 2.5 3 3 3
Perlite 2.5 3 4 4 4.5
SECTION 23 07 00 Page 23
FA4600-25-R-0002
Piping Insulation Thickness (inch) Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.
Service
Material…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .