Attachment 14_SGBP 22-0041 Repair HVAC B1226_Cut Sheets.pdf
PDF 7 MB Posted
- Attached to
- Offutt AFB Multiple Award Construction Contract (MACC) Federal contract opportunity
- Solicitation number
- FA4600-25-R-0002
About this file
This is a collection of technical specification sheets and submittals for HVAC equipment and components related to project FA4600-25-R-0002 for repair work in Building 1226 at Offutt Air Force Base. The documents include detailed specifications for multiple HVAC units including: console geothermal heat pumps ranging from 0.75 to 1.5 tons, SmartSource compact single-stage units from 1-6 tons, circulation pumps, expansion tanks, air eliminators, dirt separators, and a Knight XL commercial condensing boiler.
The specifications cover comprehensive technical data such as cooling/heating capacities, electrical requirements, physical dimensions, operating parameters, materials of construction, and standard features for each piece of equipment. Major components include Daikin Applied heat pumps, Bell & Gossett pumps and expansion tanks, Spirotherm air/dirt separators, and a Lochinvar boiler rated at 97% thermal efficiency. The submittal package provides detailed performance data, installation requirements, and dimensional drawings that would be needed for construction and installation of the HVAC system upgrades.
View the file
Other files for this federal contract opportunity
Show all 27
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Job Information Technical Data Sheet
Job Name Offutt B1226
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag CHP-0.75
Unit Overview
Model Number
Voltage V/Hz/Pha se
Air Flow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WMHW200
208- 230/60/1
345 2.40 9430 16.10 14.24 7365 3.20 3.73
Unit
Model Number: WMHW2009
Unit Type: Console Geothermal Range
Unit Construction: Standard Fiberglass Insulation
Approval: None
Refrigerant Type Refrigerant Weight
R-410A 21.0 oz
Unit Performance
Air & Water Flow
Airflow Fluid Flow Fluid Type Glycol Concentration Fluid Pressure Drop
345 CFM 2.40 gpm / 3.20 gpm/ton Propylene Glycol 30.0 % 3.91
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
designEntering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
85.0 95.1 80.0 67.0 61.7 58.1 9430 6709 11623 14.24
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption Btu/hr
COP @ design
Entering Leaving Entering Leaving Total Btu/hrDry Bulb Dry Bulb
40.0 35.2 70.0 89.8 7365 5465 3.73
Electrical
Unit Voltage Minimum Voltage Total Unit MCA Total Unit Full Load Current
208-230/60/1 187 V 4.9 A 4.0 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
3.60 A 21.0 A 0.4 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
CHP‐0.75 Technical Data Sheet
OM143U Offutt B1226 4 6/21/2024
FA460025R0002
Attachment 14
Physical
Unit
Length Height Width Weight Connections
Shipping Operating Water, OD Condensate, ID
46.0 in 25.0 in 10.8 in 164 lb 144 lb 0.625 in 0.75 in
Cabinet
Construction Type Cabinet Type
Standard Fiberglass Insulation Flat Top
Piping Hand Cabinet Height Discharge Grille
Left Hand High Sill - 25" Standard 1-piece Steel
Color
Cabinet Subbase Grille
Antique Ivory Oxford Brown Oxford Brown
Fan Controls
Type Motor Drive Type
Type Horsepower Type
Tangential Standard PSC 0.033 HP Direct Microtech III Unit
Controller - Standalone
(1) 29.25 in x 9.75 in x 0.5 in
Options
Heating
Heat Exchanger: Copper
Drain Pan Material
Primary: Plastic
Controls
Thermostat Mounting: Remote - Wall Mounted Thermostat
Thermostat Type: Programmable
Control Transformer: 50VA Control Transformer
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada.
CHP‐0.75 Technical Data Sheet
OM143U Offutt B1226 5 6/21/2024
FA460025R0002
Indoor Air Quality (IAQ) Non-Fibrous Insulation - Closed-cell type (Rubatex)
Controls MicroTech III Unit Controller - Standalone operation L ® Communication Module BACnet® Communication Module
Warranty Ext. 4-Yr. Parts (Compressor Only) Ext. 4-Yr. Parts (Refrigerant Circuit)
2-Way Motorized Valve Packages (Option)
Extended End Pocket (Option)
Multi-Directional Grilles (Option) degrees for added control of discharge air direction.
Console Water Source Heat Pump – Flat Top Unit, High Sill, Left Hand Models MHC/MHW – Unit Size 009
Options (Factory Installed)
Physical Data Unit Size 009 Fan Wheel - D x W (In.)
Fan Motor Horsepower 1/30
Coil Face Area (Sq. Ft.)
Coil Rows
Refrigerant Charge (Oz.)
Filter, (Qty.) Size (Nominal)
Water Connections (In.) 5/8 O.D.
Condensate Connections (In.) 3/4 I.D.
Weight, Operating (Lbs.) 144
Weight, Shipping (Lbs.) 164
Cabinets
Compressor
™ Fan – User selectable, multi-speed tangential fan system
LED Annunciator – LED status lights display fault conditions to the left or right end panel to the control enclosure.
Filter
Hinged Control Box
MicroTech® III Unit Controller – expansion module can be used to control electric heat and multiple fan speeds. A separate L ® or BACnet® communication module can be easily snapped onto the board to accommodate the building automation system of your choice.
Double-Sloped Drain Pan
Air Dampers (Field-installed Accessory)
Unit Flexibility
MHC-MHW-FT-HS-L-009
Specs
The Water Source Heat Pump product represented on this document will conform to the drawings and may be made to this document without the prior, express, written authorization of the manufacturer.
Group: WSHP Type:
Date:
CHP‐0.75 MHC‐W_009_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 6 6/21/2024
FA460025R0002
Flat Top Unit, High Sill, Left Hand Piping – Size 009 Left and right hand piping determined by facing the front of the unit.
Top View
Left End View Front View
Dimensions
Note: Dimensions are approximate
Unit Size A B C D E F G H J K L M
46 16 0.6 1/5
N P Q R S T V Y
4 10 13/5 5 4
Extended End Pocket (Option) – Dimensions
CHP‐0.75 MHC‐W_009_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 7 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.0
13600 Industrial Park Blvd. Minneapolis, MN 55441 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV012 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 8 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.5 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV019 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 9 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.5 low www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV019 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 10 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-2.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV024 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 11 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-2.0 low www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV024 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 12 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-3.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV036 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 13 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-3.5 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV042 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 14 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-4.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV048 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 15 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-4.0 low www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV048 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 16 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-5.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV060 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 17 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-6.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV070 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 18 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-8.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WLVW1096 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 19 6/21/2024
FA460025R0002
www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WLVW1096 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
CHP‐0.75 Smart Source Drawings
OM143U Offutt B1226 20 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag CHP-1.0
Unit Overview
Model Number
Voltage V/Hz/Pha se
Air Flow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WMHW201
208- 230/60/1
360 2.90 11165 15.30 13.56 9719 3.20 3.51
Unit
Model Number: WMHW2012
Unit Type: Console Geothermal Range
Unit Construction: Standard Fiberglass Insulation
Approval: None
Refrigerant Type Refrigerant Weight
R-410A 21.5 oz
Unit Performance
Air & Water Flow
Airflow Fluid Flow Fluid Type Glycol Concentration Fluid Pressure Drop
360 CFM 2.90 gpm / 2.90 gpm/ton Propylene Glycol 30.0 % 5.61
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
designEntering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
85.0 95.0 80.0 67.0 58.8 56.8 11165 8092 13891 13.56
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption Btu/hr
COP @ design
Entering Leaving Entering Leaving Total Btu/hrDry Bulb Dry Bulb
40.0 34.9 70.0 95.0 9719 7055 3.51
Electrical
Unit Voltage Minimum Voltage Total Unit MCA Total Unit Full Load Current
208-230/60/1 187 V 6.0 A 4.9 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
4.40 A 30.0 A 0.5 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
CHP‐1.0 Technical Data Sheet
OM143U Offutt B1226 21 6/21/2024
FA460025R0002
Length Height Width Weight Connections
Shipping Operating Water, OD Condensate, ID
46.0 in 25.0 in 10.8 in 166 lb 146 lb 0.625 in 0.75 in
Cabinet
Construction Type Cabinet Type
Standard Fiberglass Insulation Flat Top
Piping Hand Cabinet Height Discharge Grille
Left Hand High Sill - 25" Standard 1-piece Steel
Color
Cabinet Subbase Grille
Antique Ivory Oxford Brown Oxford Brown
Fan Controls
Type Motor Drive Type
Type Horsepower Type
Tangential Standard PSC 0.033 HP Direct Microtech III Unit
Controller - Standalone
(1) 29.25 in x 9.75 in x 0.5 in
Options
Heating
Heat Exchanger: Copper
Drain Pan Material
Primary: Plastic
Controls
Thermostat Mounting: Remote - Wall Mounted Thermostat
Thermostat Type: Programmable
Control Transformer: 50VA Control Transformer
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada.
CHP‐1.0 Technical Data Sheet
OM143U Offutt B1226 22 6/21/2024
FA460025R0002
Controls MicroTech III Unit Controller - Standalone operation L ® Communication Module BACnet® Communication Module
Warranty Ext. 4-Yr. Parts (Compressor Only) Ext. 4-Yr. Parts (Refrigerant Circuit)
2-Way Motorized Valve Packages (Option)
Extended End Pocket (Option)
Multi-Directional Grilles (Option) degrees for added control of discharge air direction.
Console Water Source Heat Pump – Flat Top Unit, High Sill, Left Hand Models MHC/MHW – Unit Size 012
Options (Factory Installed)
Physical Data Unit Size 012 Fan Wheel - D x W (In.)
Fan Motor Horsepower 1/30
Coil Face Area (Sq. Ft.)
Coil Rows 3 Refrigerant Charge (Oz.)
Filter, (Qty.) Size (Nominal)
Water Connections (In.) 5/8 O.D.
Condensate Connections (In.) 3/4 I.D.
Weight, Operating (Lbs.) 146
Weight, Shipping (Lbs.) 166
LED Annunciator – LED status lights display fault conditions to the left or right end panel to the control enclosure.
Filter
Hinged Control Box
MicroTech® III Unit Controller – expansion module can be used to control electric heat and multiple fan speeds. A separate L ® or BACnet® communication module can be easily snapped onto the board to accommodate the
MHC-MHW-FT-HS-L-012
Specs may be made to this document without the prior, express, written authorization of the manufacturer.
Group: WSHP Type:
Date:
CHP‐1.0 MHC‐W_012_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 23 6/21/2024
FA460025R0002
N P Q R S T V Y
4 10 13/5 5 4
Flat Top Unit, High Sill, Left Hand Piping – Size 012
Note: Dimensions are approximate
Unit Size A B C D E F G H J K L M
46 16 0.6 1/5
Extended End Pocket (Option) – Dimensions
CHP‐1.0 MHC‐W_012_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 24 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag CHP-1.25
Unit Overview
Model Number
Voltage V/Hz/Pha se
Air Flow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WMHW201
208- 230/60/1
525 3.70 13820 17.30 16.58 12062 3.40 3.60
Unit
Model Number: WMHW2015
Unit Type: Console Geothermal Range
Unit Construction: Standard Fiberglass Insulation
Approval: None
Refrigerant Type Refrigerant Weight
R-410A 30.0 oz
Unit Performance
Air & Water Flow
Airflow Fluid Flow Fluid Type Glycol Concentration Fluid Pressure Drop
525 CFM 3.70 gpm / 2.96 gpm/ton Propylene Glycol 30.0 % 3.03
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
designEntering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
85.0 94.3 80.0 67.0 64.5 58.4 13820 8625 16578 16.58
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption Btu/hr
COP @ design
Entering Leaving Entering Leaving Total Btu/hrDry Bulb Dry Bulb
40.0 35.0 70.0 91.3 12062 8836 3.60
Electrical
Unit Voltage Minimum Voltage Total Unit MCA Total Unit Full Load Current
208-230/60/1 187 V 6.7 A 5.5 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
5.00 A 30.0 A 0.5 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
CHP‐1.25 Technical Data Sheet
OM143U Offutt B1226 25 6/21/2024
FA460025R0002
Length Height Width Weight Connections
Shipping Operating Water, OD Condensate, ID
54.0 in 25.0 in 10.8 in 196 lb 166 lb 0.625 in 0.75 in
Cabinet
Construction Type Cabinet Type
Standard Fiberglass Insulation Flat Top
Piping Hand Cabinet Height Discharge Grille
Left Hand High Sill - 25" Standard 1-piece Steel
Color
Cabinet Subbase Grille
Antique Ivory Oxford Brown Oxford Brown
Fan Controls
Type Motor Drive Type
Type Horsepower Type
Tangential Standard PSC 0.056 HP Direct Microtech III Unit
Controller - Standalone
(1) 37.25 in x 9.75 in x 0.5 in
Options
Heating
Heat Exchanger: Copper
Drain Pan Material
Primary: Plastic
Controls
Thermostat Mounting: Remote - Wall Mounted Thermostat
Thermostat Type: Programmable
Control Transformer: 50VA Control Transformer
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada.
CHP‐1.25 Technical Data Sheet
OM143U Offutt B1226 26 6/21/2024
FA460025R0002
Controls MicroTech III Unit Controller - Standalone operation L ® Communication Module BACnet® Communication Module
Warranty Ext. 4-Yr. Parts (Compressor Only) Ext. 4-Yr. Parts (Refrigerant Circuit)
2-Way Motorized Valve Packages (Option)
Extended End Pocket (Option)
Multi-Directional Grilles (Option) degrees for added control of discharge air direction.
Console Water Source Heat Pump – Flat Top Unit, High Sill, Left Hand Models MHC/MHW – Unit Size 015
Options (Factory Installed)
Physical Data Unit Size 015 Fan Wheel - D x W (In.) 7/16
Fan Motor Horsepower 1/18
Coil Face Area (Sq. Ft.) 2.22 Coil Rows 2 Refrigerant Charge (Oz.) 29.9 Filter, (Qty.) Size (Nominal)
Water Connections (In.)
Condensate Connections (In.)
Weight, Operating (Lbs.) 166
Weight, Shipping (Lbs.) 196
LED Annunciator – LED status lights display fault conditions to the left or right end panel to the control enclosure.
Filter
Hinged Control Box
MicroTech® III Unit Controller – expansion module can be used to control electric heat and multiple fan speeds. A separate L ® or BACnet® communication module can be easily snapped onto the board to accommodate the
MHC-MHW-FT-HS-L-015
Specs may be made to this document without the prior, express, written authorization of the manufacturer.
Group: WSHP Type:
Date:
CHP‐1.25 MHC‐W_015_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 27 6/21/2024
FA460025R0002
Flat Top Unit, High Sill, Left Hand Piping – Size 015
Unit Size A B C D E F G H J K L M
015 20½ 12½ 7 0.6 1/
N P Q R S T V Y
4 10 1 / 7½ 4
Extended End Pocket (Option) – Dimensions
CHP‐1.25 MHC‐W_015_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 28 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag CHP-1.5
Unit Overview
Model Number
Voltage V/Hz/Pha se
Air Flow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WMHW201
208- 230/60/1
475 4.60 16332 15.30 16.13 14074 3.40 3.75
Unit
Model Number: WMHW2018
Unit Type: Console Geothermal Range
Unit Construction: Standard Fiberglass Insulation
Approval: None
Refrigerant Type Refrigerant Weight
R-410A 33.0 oz
Unit Performance
Air & Water Flow
Airflow Fluid Flow Fluid Type Glycol Concentration Fluid Pressure Drop
475 CFM 4.60 gpm / 3.07 gpm/ton Propylene Glycol 30.0 % 4.31
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
designEntering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
85.0 93.9 80.0 67.0 60.4 55.5 16332 9886 19684 16.13
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption Btu/hr
COP @ design
Entering Leaving Entering Leaving Total Btu/hrDry Bulb Dry Bulb
40.0 35.2 70.0 97.5 14074 10465 3.75
Electrical
Unit Voltage Minimum Voltage Total Unit MCA Total Unit Full Load Current
208-230/60/1 187 V 8.2 A 6.7 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
6.20 A 32.0 A 0.5 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
CHP‐1.5 Technical Data Sheet
OM143U Offutt B1226 29 6/21/2024
FA460025R0002
Length Height Width Weight Connections
Shipping Operating Water, OD Condensate, ID
54.0 in 25.0 in 10.8 in 201 lb 171 lb 0.625 in 0.75 in
Cabinet
Construction Type Cabinet Type
Standard Fiberglass Insulation Flat Top
Piping Hand Cabinet Height Discharge Grille
Left Hand High Sill - 25" Standard 1-piece Steel
Color
Cabinet Subbase Grille
Antique Ivory Oxford Brown Oxford Brown
Fan Controls
Type Motor Drive Type
Type Horsepower Type
Tangential Standard PSC 0.056 HP Direct Microtech III Unit
Controller - Standalone
(1) 37.25 in x 9.75 in x 0.5 in
Options
Heating
Heat Exchanger: Copper
Drain Pan Material
Primary: Plastic
Controls
Thermostat Mounting: Remote - Wall Mounted Thermostat
Thermostat Type: Programmable
Control Transformer: 50VA Control Transformer
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada.
CHP‐1.5 Technical Data Sheet
OM143U Offutt B1226 30 6/21/2024
FA460025R0002
Controls MicroTech III Unit Controller - Standalone operation L ® Communication Module BACnet® Communication Module
Warranty Ext. 4-Yr. Parts (Compressor Only) Ext. 4-Yr. Parts (Refrigerant Circuit)
2-Way Motorized Valve Packages (Option)
Extended End Pocket (Option)
Multi-Directional Grilles (Option) degrees for added control of discharge air direction.
Console Water Source Heat Pump – Flat Top Unit, High Sill, Left Hand Models MHC/MHW – Unit Size 018
Options (Factory Installed)
Physical Data Unit Size 018 Fan Wheel - D x W (In.) 7/16
Fan Motor Horsepower 1/18
Coil Face Area (Sq. Ft.) 2.22 Coil Rows
Refrigerant Charge (Oz.)
Filter, (Qty.) Size (Nominal)
Water Connections (In.)
Condensate Connections (In.)
Weight, Operating (Lbs.) 171
Weight, Shipping (Lbs.) 201
LED Annunciator – LED status lights display fault conditions to the left or right end panel to the control enclosure.
Filter
Hinged Control Box
MicroTech® III Unit Controller – expansion module can be used to control electric heat and multiple fan speeds. A separate L ® or BACnet® communication module can be easily snapped onto the board to accommodate the
MHC-MHW-FT-HS-L-018
Specs
MHC-MHW-FT-HS-L-018 Specs / Page 1 of 2
The Water Source Heat Pump product represented on this document will conform to the drawings and may be made to this document without the prior, express, written authorization of the manufacturer.
Group: WSHP Type:
Date:
CHP‐1.5 MHC‐W_018_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 31 6/21/2024
FA460025R0002
Flat Top Unit, High Sill, Left Hand Piping – Size 018
Unit Size A B C D E F G H J K L M
018 20½ 12½ 7 0.6 1/
N P Q R S T V Y
4 10 1 / 7½ 4
Extended End Pocket (Option) – Dimensions
MHC-MHW-FT-HS-L-018 Specs / Page 2 of 2
CHP‐1.5 MHC‐W_018_HS_F_L_Features‐Dim‐Phys_Data_Drawin
OM143U Offutt B1226 32 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-1.0
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV012
208-
230/60/1 347 3.00 9477 15.1 10.2 9240 3.4 3.1
Unit
Model Number: WGCV012
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 21.5 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
347 CFM 0.70 3.00 gpm / 3.00 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 98.9 75.0 63.0 55.3 53.4 9477 7400 12657 10.2 10.00
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 35.6 70.0 94.5 9240 6282 3.1 11.13
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/1 197 V 5.5 A 6.7 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
4.6 A 27.9 A 0.9 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
19.0 in 24.0 in 19.0 in 133 lb 105 lb 0.50 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant Torque 0.10 hp
HP‐1.0 Technical Data Sheet
OM143U Offutt B1226 33 6/21/2024
FA460025R0002
Unit Options
Controls
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 12 in x 16 in x 1 in
Insulation
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐1.0 Technical Data Sheet
OM143U Offutt B1226 34 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV012 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐1.0 Smart Source Drawings
OM143U Offutt B1226 35 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-1.5
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV019
208-
230/60/1 600 4.00 15214 16.7 11.2 13940 3.5 3.5
Unit
Model Number: WGCV019
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 29.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
600 CFM 0.75 4.00 gpm / 2.53 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 100.4 75.0 63.0 57.2 54.1 15214 11589 19861 11.2 10.24
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 34.8 70.0 91.4 13940 9970 3.5 11.40
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/1 197 V 9.2 A 10.8 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
6.2 A 31.5 A 3.0 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
21.5 in 32.0 in 21.5 in 174 lb 146 lb 0.50 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.17 hp
HP‐1.5 Technical Data Sheet
OM143U Offutt B1226 36 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 16 in x 20 in x 1 in
Insulation
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐1.5 Technical Data Sheet
OM143U Offutt B1226 37 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.5 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV019 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐1.5 Smart Source Drawings
OM143U Offutt B1226 38 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-1.5 low
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV019
208-
230/60/1 450 4.00 14456 16.7 10.8 13370 3.5 3.2
Unit
Model Number: WGCV019
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 29.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
450 CFM 0.75 4.00 gpm / 2.53 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 100.0 75.0 63.0 54.9 51.5 14456 9800 19027 10.8 10.24
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 35.2 70.0 97.4 13370 9144 3.2 11.40
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/1 197 V 9.2 A 10.8 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
6.2 A 31.5 A 3.0 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
21.5 in 32.0 in 21.5 in 174 lb 146 lb 0.50 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.17 hp
HP‐1.5 low Technical Data Sheet
OM143U Offutt B1226 39 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 16 in x 20 in x 1 in
Insulation
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐1.5 low Technical Data Sheet
OM143U Offutt B1226 40 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-1.5 low www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV019 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐1.5 low Smart Source Drawings
OM143U Offutt B1226 41 6/21/2024
FA460025R0002
www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV024 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐1.5 low Smart Source Drawings
OM143U Offutt B1226 42 6/21/2024
FA460025R0002
www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV048 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐1.5 low Smart Source Drawings
OM143U Offutt B1226 43 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-2.0
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV024
208-
230/60/3 800 5.00 21109 15.9 10.5 18577 3.4 3.6
Unit
Model Number: WGCV024
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 32.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
800 CFM 0.75 5.00 gpm / 2.50 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 101.8 75.0 63.0 56.7 53.7 21109 15863 27988 10.5 9.07
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 34.3 70.0 91.4 18577 13457 3.6 10.10
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/3 197 V 10.1 A 11.9 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
7.1 A 55.4 A 3.0 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
21.5 in 39.0 in 21.5 in 197 lb 169 lb 0.75 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.33 hp
HP‐2.0 Technical Data Sheet
OM143U Offutt B1226 44 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 20 in x 20 in x 1 in
Insulation
Compressor: Sound Blanket
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐2.0 Technical Data Sheet
OM143U Offutt B1226 45 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-2.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV024 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐2.0 Smart Source Drawings
OM143U Offutt B1226 46 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-2.0 low
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV024
208-
230/60/3 600 5.00 20176 15.9 10.3 18109 3.4 3.5
Unit
Model Number: WGCV024
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 32.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
600 CFM 0.75 5.00 gpm / 2.50 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 101.3 75.0 63.0 54.1 50.9 20176 13613 26887 10.3 9.07
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 34.6 70.0 97.8 18109 12887 3.5 10.10
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/3 197 V 10.1 A 11.9 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
7.1 A 55.4 A 3.0 A 15 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
21.5 in 39.0 in 21.5 in 197 lb 169 lb 0.75 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.33 hp
HP‐2.0 low Technical Data Sheet
OM143U Offutt B1226 47 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 20 in x 20 in x 1 in
Insulation
Compressor: Sound Blanket
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐2.0 low Technical Data Sheet
OM143U Offutt B1226 48 6/21/2024
FA460025R0002
www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV024 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐2.0 low Smart Source Drawings
OM143U Offutt B1226 49 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-3.0
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV036
208-
230/60/3 1200 6.00 32268 15.8 10.4 28558 3.4 3.4
Unit
Model Number: WGCV036
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 48.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
1200 CFM 0.75 6.00 gpm / 2.00 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 105.0 75.0 63.0 56.8 53.5 32268 23758 42818 10.4 7.44
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 33.0 70.0 91.9 28558 20067 3.4 8.29
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/3 197 V 15.4 A 18.0 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
10.4 A 73.0 A 5.0 A 25 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
26.0 in 44.0 in 21.5 in 221 lb 193 lb 0.75 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.33 hp
HP‐3.0 Technical Data Sheet
OM143U Offutt B1226 50 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 24 in x 24 in x 1 in
Insulation
Compressor: Sound Blanket
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐3.0 Technical Data Sheet
OM143U Offutt B1226 51 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-3.0 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV036 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐3.0 Smart Source Drawings
OM143U Offutt B1226 52 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-3.5
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV042
208-
230/60/3 1400 7.00 35754 16.7 10.9 30927 3.4 3.4
Unit
Model Number: WGCV042
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Configuration Refrigerant Type Refrigerant Weight Loop Temperature Range
Vertical R-410A 52.0 oz Ground Loop (Geothermal)
Unit Performance
Air & Fluid Flow
Airflow Total External Static Pressure Fluid Flow Fluid Type Glycol Concentration Altitude
1400 CFM 0.75 7.00 gpm / 2.00 gpm/ton
Propylene Glycol 30.0 % 0 ft
Cooling Performance
Fluid Temperature Air Temperature Capacity Heat of Rejection
Btu/hr
EER @
design
Fluid Pressure
Drop Entering Leaving Entering Leaving Total
Btu/hr Sensible Btu/hrDry Bulb Wet Bulb Dry Bulb Wet Bulb
90.0 104.1 75.0 63.0 57.5 54.0 35754 26611 46919 10.9 10.96
Heating Performance
Fluid Temperature Air Temperature Capacity Heat of Absorption
Btu/hr
COP @ design Fluid Pressure DropEntering Leaving Entering Leaving Total
Btu/hrDry Bulb Dry Bulb
40.0 33.5 70.0 90.3 30927 21736 3.4 12.20
Electrical
Unit Voltage Minimum Voltage Total Unit Full Load Current Total Unit MCA
208-230/60/3 197 V 20.5 A 23.8 A
Compressor RLA Compressor LRA Motor FLA Maximum Recommended Fuse Size / HACR Breaker Size
13.2 A 88.0 A 7.3 A 35 A
*Short-Circuit Current = 5 kA rms symmetrical, 600 V maximum
Physical
Unit
Depth Height Width Weight Connection
Shipping Operating Water Condensate
26.0 in 44.0 in 21.5 in 233 lb 205 lb 0.75 in 0.75 in
Fan
Motor Type Motor Horsepower
ECM Constant CFM 0.50 hp
HP‐3.5 Technical Data Sheet
OM143U Offutt B1226 53 6/21/2024
FA460025R0002
Unit Control: Microtech III
Control Transformer: Standard 50 VA Transformer
Thermostat / Sensor Control: Thermostat Control
Unit Airflow Configuration
Return Air Location: Right Hand
Discharge Air Location: Top
Construction Options
Drain Pan Material
Primary: Stainless Steel
Filters
Filter Rack Type: Standard 1-inch 2-Sided
Filter Type: 1-inch Throwaway (Quantity) Nominal Filter
Dimensions:
(1) 24 in x 24 in x 1 in
Insulation
Compressor: Sound Blanket
Compressor Compartment: 1/2 inch Fiberglass, Skin-faced
Air Compartment: 1/2 inch Fiberglass, Skin-faced
Miscellaneous
Coil Treatment: None
Warranty
Unit Warranty: 4 Yr Refrigerant Circuit Only Extended Parts Warranty, 1st Yr Labor Allowance
AHRI Certification
All equipment is rated and certified in accordance with AHRI / ISO 13256-1 and tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL 60335-2- 40 Version 2 for the United States and CAN/CSA-C22.2 NO. 60335-2-40 Version 2 for Canada.
HP‐3.5 Technical Data Sheet
OM143U Offutt B1226 54 6/21/2024
FA460025R0002
Product Drawing Unit Tag: HP-3.5 www.DaikinApplied.com Software Version: 12.30
Product: Project Name: Offutt B1226 Model: WGCV042 Sales Office: Mechanical Sales, Inc.
Sales Engineer: Mike Nebel June 21, 2024 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25 Dwg Units: (in)
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
HP‐3.5 Smart Source Drawings
OM143U Offutt B1226 55 6/21/2024
FA460025R0002
Date 6/21/2024
Submitted By Mike Nebel
Software Version 12.30
Unit Tag HP-4.0
Unit Overview
Model Number
Voltage V/Hz/Phase
Airflow
CFM
Fluid Flow gpm
Cooling Capacity
Btu/hr
Cooling Efficiency
EER@AHRI
Cooling Efficiency EER@Design
Heating Capacity
Btu/hr
Heating Efficiency
COP@AHRI
Heating Efficiency COP@Design
WGCV048
208-
230/60/3 1600 10.00 39739 16.9 12.5 41447 3.6 3.8
Unit
Model Number: WGCV048
Unit Type: SmartSource Compact - Single Stage
Approval: ETL, CETL, AHRI
Confi…
This is the start of the file's text. The full file is on GovTribe.