This document is an attachment that provides standards and specifications for building and utility construction materials for Goodfellow Air Force Base (AFB) in Texas.
The key details include:
- The Chief of the Engineering Flight (17 CES/CEN) is responsible for implementing the standardization policy on all Goodfellow AFB projects.
- Requirements are provided for architectural, civil/structural, mechanical, electrical, and fire protection systems and components. Specific products, materials, and manufacturers are identified as the base standards.
- The document includes several attachments with additional details on existing materials/equipment, pipe and fitting materials, approved landscape plants, exterior glass details, and Wi-Q locking and management requirements.
- This standardization policy establishes uniformity in construction materials and systems across the base to ensure compatibility and maintainability.
View the file
Other files for this federal contract opportunity
Show all 49
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BASE STANDARDIZATION
OF
BUILDING/UTILITY DISTRIBUTION SYSTEMS
FOR
GOODFELLOW AFB
June 2024
PREPARED BY: 17 CES/CEN
17TH CIVIL ENGINEER SQUADRON (AETC)
460 KEARNEY BOULEVARD
GOODFELLOW AFB, TX 76908-4104
FOREWARD
This policy letter establishes uniformity in the materials of building construction and utility distribution systems for Goodfellow AFB, TX.
(1) Responsibility: The Chief of the Engineering Flight (17 CES/CEN) is assigned primary responsibility for implementing this policy letter on all Goodfellow AFB project designs and all applicable contract work. Normally, the base project manager will ensure that the standard building materials as stated in this regulation are used on Goodfellow AFB construction projects and that this information is incorporated in all Military Construction Project (MCP) and Architectural Engineering (A/E) and in-house designed projects. The Chief of Operations Flight must assure materials ordered and contract works executed by Operation & Maintenance (O&M) comply with this standardization policy.
(2) Procedures: The following items and policies shall provide for the standardization of building and utility construction materials on Goodfellow AFB.
These items shall be in conjunction with the standardization of systems as defined by Air Force Engineering Technical Letters (AFETL), Unified Facilities Codes (UFC) and Unified Facilities Guide Specifications (UFGS). Refer to Whole Building Design Guide www.wbdg.org for additional information. Base Indefinite Delivery Indefinite Quantity (IDIQ) contracts include Demolition, Flooring, Pavements, Landscaping, Utilities and Roofing. Although these IDIQs may be contractually inactive, they remain as building construction standards with AutoCADD drawings and detailed specifications.
AUTHORIZED BY:
Mr. Lance Overstreet Engineering Flight Chief (17 CEN)
INDEX
FOREWARD
A. ARCHITECTURAL
General
Doors
Windows & Walls
Floors & Ceilings
Landscaping
Roofing
Other
B. CIVIL/STRUCTURAL
C. MECHANICAL
HEATING, VENTILATION & AIR CONDITIONING (HVAC)
PLUMBING/GAS
ENERGY MANAGEMENT CONTROL SYSTEMS (EMCS)
D. ELECTRICAL
INTERIOR
LIGHTING
EXTERIOR ELECTRICAL
LIGHTNING PROTECTION
E. FIRE PROTECTION
ATTATCHMENT I: GOODFELLOW’S EXISTING MATERIALS/EQUIPMENT
ATTATCHMENT II: PIPE & FITTING MATERIALS
ATTATCHMENT III: LANDSCAPE PLANTS LIST
ATTATCHMENT IV: EXTERIOR GLASS DETAIL
ATTATCHMENT V: WI-Q LOCKING AND MANAGEMENT REQUIREMENTS
17 CES Instruction 98-1 1 February 1998
Revised June 2024
DEPARTMENT OF THE AIR FORCE
17th Civil Engineer Squadron (AETC) Goodfellow AFB, Texas 76908-4104
Civil Engineering-General
BASE STANDARDIZATION OF BUILDING/UTILITY DISTRIBUTION
SYSTEMS
A. ARCHITECTURAL
(Refer to Attachment I for additional information)
General:
(1) All architectural work shall comply with the latest edition of the International Building Code as described in UFC 1-200-01.
(2) All exterior architectural finishes shall be chosen to match/be compatible with the Base Architectural Compatibility Guide (ACG). All facility finishes shall be coordinated through the Base CE Project Managers.
(3) To achieve architectural compatibility throughout the base, designers shall use the, AETC Guide to Installation Excellence, Base Color schemes, and the AFPAM 32- 1097 as design guidelines. All design elements, interior and exterior, will strictly adhere to the AETC Guide to Installation Excellence; SID/CID presentation shall comply with Air Force Interior Design Guide: Chapter 12 Presentation Format [Ref:
www.afcee.brooks.af.mil]. All color board submittals shall be organized in a 3-ring binder with an adequate product description and proposed facility location.
Doors:
(4) ELECTRONIC CARD ACCESS LOCKING SYSTEM (ECALS): The Base standard lock system is ECALS, unless otherwise wavered. All ECALS shall be equal to, and software must be 100% compatible to and interface with the existing ECALS, BEST Corp. manufacturer equipment and software currently used on Goodfellow
AFB.
a. BEST WIRELESS ACCESS MANAGEMENT (WI-Q): Includes electronic locking device, card reader, door position switch, request to exit device, door control module, and portal gateway. Connects wirelessly to remote and no wiring or terminations needed.
(See ATTATCHMENT V for further requirements regarding the WI-Q locking system.)
(APPLICABLE ONLY IF ECALS HAS BEEN WAVERED)
(5) Locking: Lock cores shall be removable type keyed in sets or subsets as scheduled. Lock cores shall be seven (7) pins. Cores shall be pinned for an A-4 (.018 differential) type system. Lock cores shall be keyed to existing base master keying system in sets or subsets in accordance with the approved schedule. Locks shall be furnished with the manufacturer’s standard construction cores and key system.
(Permanent cores and keys including a typewritten key codes/biting schedule shall be sent by the lock manufacturer directly to Goodfellow Air Force Base by registered mail or other approved means.) The addresses are as follows:
Base Projects Military Construction Projects 17CONS/LGCA Base Civil Engineer Office Attn: Contracting Officer Attn: Locksmith 210 Scherz Blvd 460 East Kearney Blvd Goodfellow AFB TX 76908-4122 Goodfellow AFB TX 76908-412
a. Keys for the locks shall be stamped with change number and the inscription “U.S. Property – Do Not Duplicate”. Goodfellow uses an “M1” type keyway.
Keys shall be supplied as follows:
Locks: 2 change keys each lock Master Keyed Sets: 2 keys each set Construction Keys 6 total Blank Keys 1 per lock set provided
b. Keying Schedule: All keying schedules must be approved by the Base
Locksmith. The base locksmith shall be contacted (address above) to secure existing key codes if necessary to successfully master key new work.
c. Lock Sets and Latch Sets: Lock sets and latch sets shall meet ANSI/BHMA A156.2, series 4000, grade 1, bored type with levers. Lock sets and latch sets shall be capable of accepting “Best” removable cores.
ANSI/BHMA A156.2, Series 4000, Grade 1 with levers. Lockset shall be or equivalent to Stanley Best EZ Series Heavy Duty Keypad Locks, Part Number 93KZ7DV15KPSTK
626 MX8COR.
(6) Exterior doors and frames shall consist of 18 gauge, galvanized, 1 ¾” thick, hollow metal doors with 16 gauge, galvanized, 2”x5 ¾” throat depth, hollow metal frames with a minimum of three hinges per door and door R value minimum 5. A minimum of three jamb anchors per jamb and a minimum of three rubber silencers per strike jamb.
(7) Interior openings requiring fire rated doors [i.e. Communication, Mechanical and/or Electrical Rooms] shall consist of 18 gauge, 1 ¾” thick hollow metal doors with 16 gauge, 2”x5 ¾” throat depth, hollow metal frames with three hinges per door, minimum. A minimum of three jamb anchors per jamb and a minimum of three rubber silencers per strike jamb.
(8) Interior Doors: Where provided, provide either Solid Core Wood doors [SCW] or Structural Composite Lumber Core (SCLC) type doors. Wood doors shall be 1 ¾” thick, solid core, 5-ply construction (fire-rated, as required); conforming to NWWDA I.S.-1A [the one-year acclimatization requirement shall not apply] and conforming to WDMA TM-7, 8 & 10. Stiles shall be 1 3/8” hardwood minimum [same species as face veneer], with no visible joints and rails. Joints and rails shall be 1 1/8” solid wood, minimum. Cores shall be NWWDA I.S.-1 glued block with faces, stiles and rails bonded to the cores and suitable for transparent finish. Veneers shall be rotary cut hardwood with final finish as determined by 17CES. Particleboard core type doors are prohibited.
(9) Where interior hollow metal doors are used, use 16 ga frame and 18 ga door as listed under Steel Door Institute SDI-100. Fire rated doors and frames shall bear the fire rated label. Hollow metal door frames shall be 2”x5 ¾” throat depth, to the greatest extent possible. A minimum of three jamb anchors per jamb and a minimum of three rubber silencers per strike jamb.
(10) Aluminum store front doors shall be dark bronze anodized medium commercial grade with medium (min 3") stiles storefront. Storefront glazing shall be IAW paragraph (12) below. Provide chair rail height mulls at all aluminum storefronts.
Public-access storefront doors and frames shall be anodized dark bronze aluminum with laminated thermal pane glazing.
(11) All interior door hardware shall consist of Leveler handles to meet 2010 ADA Standards for Accessible Design, Section 404.2.7.
Windows & Walls:
(12) Windows shall be fixed-pane, blast-resistant. Glazing shall be fixed pane anodized bronze aluminum with laminated thermal pane. Exterior glass pane shall be Type I annealed flat glass, Class 2-tinted, Quality q3-glazing select, color bronze with Low-E anti-reflective low-emissivity coating on the number 2 surface (interior surface of exterior pane). Interior glass pane shall be clear laminated glass consisting of two layers of Type I transparent float glass bonded together with 0.030-inch thick PVB interlayer under pressure. Class 1-clear Quality q3-glazing select. All window glazing must qualify for the National Fenestration Rating Council (NFRC), Energy Star label (southern-central region) and have a U Factor of 0.35 or below, and a Solar Heat Gain Coefficient (SHGC) rating of 0.30 or below. Solar screens (min. absorb and dissipate 80% with detachable bronze frames) shall be included with all exterior glass/window glazing.
(Please refer to “ATTATCHMENT IV: Exterior Glass Detail” for appropriate dimensions and thickness.)
(13) Exterior Finishes: Brick and split-faced CMU are preferred to the greatest extent possible; stucco and External Insulating Finishing System (EIFS) are to be used only in special circumstances with the prior approval of the Base Civil Engineer Office (Engineering Flight Chief). Face brick shall be modular in size. Face brick for additions and/or new facilities shall match the prevailing brick of facilities in the immediate vicinity and be in conformance with the recommendations of the Base Architectural Compatibility Guide. All new brick west of Kearney Blvd. shall be ACME Tulsa Blend 2, Garnet Velour, Modular. All new brick east of Kearney Blvd.
shall be Acme Denton Blend #136 Quorum. All split faced block shall be Acme Featherlite Limestone, dimensions: 7 5/8”T x15 5/8”L x 3 5/8”D, applied in a running bond pattern, unless substitute is approved. All face brick shall be sealed with a water repellant equal to, or better than the existing brick sealant/repellant currently used on Goodfellow AFB.
(14) Interior Base: Rubber base shall be continuous roll, 1/8"x6” thick base. Vinyl base is not allowed under any circumstances.
(15) Use cement backer board behind all ceramic tile on walls. Specify mildew resistant grout for all tile surfaces exposed to moisture.
(16) For new construction only, all utility/transformer/dumpster enclosures/screening shall have masonry enclosures that match the new facility.
Floors & Ceilings:
(17) To the greatest extent possible ACM floor covering and mastic shall be removed prior to carpet installation. Carpeting and floor tile shall be chosen in accordance with guidelines set forth by UFCs, Base Flooring IDIQ and the Goodfellow base wide color schemes where applicable. All carpet/flooring shall comply with Base Flooring IDIQ specifications and design drawings.
(18) Architectural floor plan numbering of rooms shall match final room numbering sequence for the facility and all door and finish schedules. The designer/(A/E) is responsible for determining the final room numbering sequence. Room numbering shall be coordinated with the Base Civil Engineer Office (Engineering Flight Chief).
(19) Insulation: All ceiling insulation shall have a minimum overall value of R-30 and wall insulation a minimum overall value of R-19.
(20) Suspended Ceilings: All suspended grid ceiling systems shall be as follows for the indicated locations: The suspended grid ceiling system for all wet areas shall be 2’x 2’ ceiling tile equal to Armstrong ½” Gridstone fire resistive, white, stipple finish, aluminum grid and vinyl coated sheetrock in a suspension system equal to Armstrong AL Prelude Plus with 15/16” white tees. The suspended grid ceiling system for all other areas shall be 2’x2’ white ceiling tile equal to Armstrong ¾” Cirrus #577, fire resistive, tegular, beveled, tiles set in a suspension system equal to Armstrong Suprafine 9/16” white tees. Coordinate special sound transmission classification (STC) ratings with project manager for particular project.
(21) Gypsum Ceiling and/or Wall Finish shall be orange-peel textured, Semi-Gloss Latex paint.
Landscaping:
(22) Irrigation: Lawn sprinkler piping and fittings shall be schedule 40 PVC. Use flexible PVC tubing from mains and laterals to all sprinkler heads or swing joints.
Sprinkler heads shall be of the flow type; impact heads are prohibited. Lawn sprinkler systems shall be designed by a Texas Licensed Irrigator. Use the following sprinkler materials/products for controller: Install resilient wedge valve ahead of backflow prevention to allow system isolation. Atmospheric Vacuum breaker shall be 6” above highest head. Pressure Vacuum Breaker for multi system shall be 12” above head.
Reduce pressure zone (RPZ) backflow prevention devices are permitted for use. Valve boxes shall be installed 1”-2” above grade for easy location of valve box.
(23) Plants: Refer to Attachment III and Base Landscape IDIQ for list of acceptable landscape plants, decomposed granite, boulders, multi-colored rock, deco-curbing.
Xeriscaping should be used to the greatest extent possible.
(24) Weed Barrier: All locations that require weed barrier shall be provided with two layers. Each layer shall have min. weight of 1.9oz per square yard.
Roofing:
(25) All applicable new facilities shall employ Standing Seam Metal Roof Systems with a minimum slope of 3 on 12. BUR designs shall be standard 3-ply SBS, refer to Base Roofing IDIQ (specifications and design drawings) for additional information.
All metal fascia panels shall be smooth and metal roofing panels shall striated to mitigate any oil canning effects.
(26) All roof appurtenances (vent stacks, exposed utilities, etc.) shall be painted/or provided with metal sleeves to match the color of the roof.
(27) All roofing covers shall be fully adhered polyvinyl chloride (PVC), thermoplastic polyolefin (TPO), or approved equal. Roofing membrane sheet widths shall be consistent with membrane attachment methods and wind uplift requirements and shall be as large as practical. In order to minimize joints and 3-way overlaps, prefabricated sheets are not accepted.
(28) Roofing shall be high Albedo with a SRI rating of 0.88 or better.
Other:
(29) The use of organic adhesives is prohibited.
(30) Bathroom partitions shall be floor mounted, solid plastic, (High Density Polyethylene (HDPE) resins with homogenous color throughout.
(31) The use of particle board or melamine for any woodwork, millwork, or casework is prohibited. Underlayment for plastic laminate [i.e. counter tops, vanity tops, etc.] shall be ¾” thick Medium Density Fiberboard, only. All other components for Millwork/Casework shall be ¾” thick plywood or hardwood, only. The Millwork/Casework standard shall be ANSI/KCMA A161.1 – Performance and Construction Standards for Kitchen and Vanity Cabinets. All solid surface will be mounted on 3/4" thick medium density fiberboard.
(32) Painting shall conform to the standards contained in the Master Painters Institute (MPI) Architectural Painting Specification Manual, latest edition. Refer to www.paintinfo.com for more information on painting standards. Also, all painting work shall conform to the Base Protective Coatings IDIQ specifications. Note, all handrails shall be stainless steel and under no circumstances shall handrails be painted.
(33) All exterior signage shall be designed in accordance with UFC 3-120-01 (paint backside dark bronze), minimize free standing signs and use anodized aluminum lettering mounted on face of facility.
(34) Handicapped Accessibility: Facilities will accommodate the handicapped in accordance with the latest edition of the Uniform Federal Accessibility Standards, the American Disabilities Act and ANSI 117.1.
B. CIVIL/STRUCTURAL
(Refer to Attachment I for additional information)
(1) All new and/or rehabbed paved surfaces shall include curbing. For all paving refer to Base Pavements IDIQ.
(2) Consider screen pads when appropriate for HVAC equipment. Provide a concrete approach apron at each location. Fence shall be tall enough to conceal equipment and be constructed of masonry for new buildings and bronze ribbed metal panels (both sides) with steel post and framing painted color currently used at Goodfellow AFB for renovation and all other projects. All exterior exposed (not behind a screen) conduit, gas lines, water lines, cable TV boxes, telephone boxes, gas regulators / meters, and exposed electrical panels / breaker boxes and conduit shall be painted to match the color currently used at Goodfellow AFB.
(3) All utility road and driveway crossings shall be bored and sleeved with single schedule 80 PVC or 1/4" wall steel sleeve. Roads and driveways shall not be crossed by open cut unless approved in advance and only under special circumstances. All road cuts on Kearney Blvd. are prohibited.
(4) Mechanical thrust restrainers shall be used on all utilities that require thrust restraint, if concrete thrust blocks are used in conjunction with mechanical restrainers the joint shall be first covered in plastic before pouring of the thrust block. All components of the restrainers, including the gland, bolts, and restraint segments shall be high strength ductile iron, ASTM A536, Grade 65-45-12. Restraining devices shall be UL listed/FM approved on AWWA C 900 PVC pipe and complies with ASTM F 1674. Restraining ring segments shall be actuated by bolts featuring twist off heads to ensure proper installation torque is applied.
(5) Typical minimum utility line burial depths below finished grades shall be as follows:
Minimum
a. Gas mains/service lines 24 inches
b. Electrical secondary 18 inches
c. Water lines 36 inches
d. Communications 36 inches (in conduit) (cable TV/telephone in conduit)
Notes:
a. All buried utilities shall show warning and identification tape minimum 12 inches below grade.
b. All electric utilities shall be in conduit with metallic strip caution tape, and installed per NEC. Concrete over primary ducts shall also have red markings.
Note: primary electric is owned and managed by AEP Texas.
c. For areas requiring vehicle loading provide concrete encasement and/or 4 in.
concrete cap.
d. For additional information refer to UFGS specification 31 23 00, “Backfilling”.
(6) Sidewalks crossing roads shall have handicap ramps and crosswalks that comply with the Americans with Disabilities Act (ADA). New handicap ramps shall be installed to the greatest extent possible.
(7) Troopwalk: A unique architectural feature of Goodfellow is the troopwalk, which traverses the base. Since many of the students do not have auto transportation, this network of walks aids in getting from place to place on-foot and assists in marching/training exercises. Exposed aggregate shall be washed and graded natural river rock 3/8 in. to ¾ in. round (color to match existing troopwalk color) and pavers shall match the pavers currently used on Goodfellow AFB.
(8) All petroleum storage tanks shall be rated Aboveground Storage Tanks (AST) and installed in an approved concrete vault.
(9) All structural design work shall comply with the latest edition of the International Building Code as described in UFC 1-200-01.
(Note, where requirements for Licensed Engineer or Registered Architect are stipulated in the specifications, that stipulation will call for a Professional Engineer (PE) and/or Architect (AIA)).
(10) Poles for all pole mounted signage shall be painted to match the currently used color on Goodfellow. The back of all signs shall be coated.
(11) Removable bollards shall be painted to match the currently used color on Goodfellow.
(12) All traffic signage shall comply with the latest Manual on Uniform Traffic Control Devices (MUTCD).
C. MECHANICAL
(Refer to Attachments I & II for additional information)
HEATING, VENTILATION & AIR CONDITIONING (HVAC):
(1) Chilled water and dual temperature water piping 4” and less shall be rigid copper Type K or L piping, or other by 17 CES approval. Attachment II, Table II lists where to use Type K and L pipe and fitting materials. Type K pipe and fittings shall be used underground and Type L shall be used in above ground applications.
(2) All underground chilled/hot water piping shall be factory pre-insulated with at least a #12 tracer wire.
(3) Hot and chilled water pumps less than 8 hp shall be of the in-line or end suction close-coupled type and shall be of brass construction.
(4) Chilled water systems shall use air cooled chillers for total cooling plant cooling loads of 350 tons or less and for loads greater than 350 tons multiple air cooled chillers shall be used. Also, water cooled chillers should be considered.
All HVAC Chiller will be TRANE, refer to approved J&A.
(5) All air-cooled condensing coils shall be protected from hail by appropriate screens. Screens shall be by the manufacturer of the equipment protected.
(6) All diffusers and registers in humid areas (i.e. bathrooms) shall be constructed of aluminum. Special precautions shall be taken (make-up air, etc.) in providing adequate ventilation.
(7) All outside air control dampers shall be of the low leakage type rated at 5 CFM maximum leakage at 4 inches water gauge static pressure when closed.
(8) All duct work shall be aluminum, stainless steel, or galvanized sheet metal. Duct board to be used only for external insulation purposes. Internally lined/insulated duct shall not be used. Flex duct shall not be used for runs greater than 6 ft.
(9) To the greatest extent possible, include energy recovery systems during the design phase of all building renovations and new construction. Enthalpy wheels are not advised to be use in the energy recovery systems per 17 CES/CEOIH. Plate exchangers are recommended.
(10) All exterior mechanical equipment shall be screened from view. Screen type shall be as directed by AETC Guide to Installation Excellence. Mechanical equipment that cannot be screened from view such as wall mounted exhaust fans and louvers shall be painted to match the color currently used at Goodfellow AFB.
(11) Refer to Base CADD detail for typical chemical feeder. All closed loop systems must include a sock filtration/ chemical feed point. If piping allows, a spin filter is recommended.
(12) All commercial refrigeration, comfort cooling equipment and appliances (any capacity) shall use non ozone depleting refrigerants such as R-454B, R-134A, R-410A or approved EPA compliant substitute. There shall be no ozone depleting refrigerant allowed.
(13) For all large HVAC systems, isolation valves shall be provided to facilitate ease of maintenance without the shutdown of the entire system.
(14) Portable chiller connections shall be installed on all large HVAC systems for maintenance purposes.
(15) Fan powered VAVs are prohibited unless filters are accessible at ceiling height.
(16) All Air cooled Chiller, Evaporator & Condenser barrels shall be required to have “Factory Applied” epoxy coating added to end tube sheet plates and end bells.
(17) No micro channel coils are permitted unless otherwise coordinated with 17
CES/CEN.
PLUMBING/GAS:
(18) Ensure that backflow prevention devices are aboveground with a height not exceeding 4 ft, and are testable.
(19) Pipe and fitting materials for drainage, waste, and vent (DWV) piping and interior rainwater conductor (interior roof drains) systems shall be schedule 40 PVC or
NewAge Epoxy cast iron; recommended by 17 CES/CEOI. Use cast iron pipe for firewall penetrations.
(20) Pipe and fitting materials for pressure piping systems inside the building to a point 5 ft. outside the building: As listed in Attachment II. All interior plumbing piping shall be Viega Pex, Aquapex or copper Type “L”.
(21) No pipe, fitting, or solder shall contain lead.
(22) Water heaters/recirculating potable water boilers with tanks shall be natural gas type, and shall be State or equal, with high recovery. Hot water temperature at lavatories shall not exceed 120°F. Consider A.O. Smith water heaters.
(23) Refer to the Goodfellow Dormitory Domestic Hot Water Heating Study (June 2001) for information on existing dormitory hot water systems and required engineering methodology for calculating hot water requirements to preclude underestimating demand requirements.
(24) Bath shower fixtures shall include bathtub spout, shower head, valves, and diverters. Shower head mounting shall be via a ball joint mount. Where floor and shower drains are provided, provide galvanized body with perforated or slotted type drains conforming to ASME A112.6.3. Where work scope requires new drains and surrounding substrate/flooring areas are affected, wastewater shall positively flow towards drain at a minimum 1% or 1/8” per foot. All shower drain rough-ins shall be at finished concrete floor height. A water proof membrane with smooth concrete substrate, “OATEY” PVC shower pan liner, shall be applied to the shower pan and turned up a minimum of 12 inches and over the shower curb. Where substrate or concrete demo/replacement work is included, shape and screed all areas to ensure proper drainage. Flood areas within scope to ensure drainage to the satisfaction of the Government prior to final acceptance.
(25) Water service lines 3 inches in diameter and less shall be HDPE, PEX or PVC schedule 80.
(26) Water meters: All new water meters shall be turbine type with oval flanged ends complete with companion flanges, gaskets, bolts, and nuts. Water meters shall read in gallons and have a pulse initiator for interface with the base Energy Monitoring Control System (EMCS) and the Advanced Meter Reading System (AMRS). Pulse initiator shall be equipped with one dry switch type pulse output channel in which contact position is detected by a 0 - 10 Vdc wetting voltage supplied by a separate EMCS control panel resulting in a 0.5 mA maximum sense current when the contacts are closed. Pulse output related to water volume (gallons). AMCO Elster T4000 or equal.
(27) All plumbing fixtures (urinals, showerheads, water closets, and lavatories) shall comply with EPA Watersense product requirement for flush valves and flush meters.
Provide 1.28 gpf flush valves on commercial/residential type toilets, and 0.5 gpf flush valves for all urinals. Waterless urinals are prohibited.
(28) All underground water metallic valves and fittings shall be provided with a 32 pound magnesium sacrificial anode connected by an exothermic weld through a No.
12 AWG copper wire. All valves in water mains 2” or larger shall be resilient wedge type.
(29) Exterior underground water distribution or service piping 4 inches through 12 inches shall be PVC elastomeric gasket joint type with a DR of 14, pressure class 200, and conform to AWWA C-900. Piping greater than 12 inches shall be PVC in conformance with AWWA C-905 or concrete encased steel in conformance with AWWA 300, 301, or 303 rated at 150 psi.
(30) Underground gas piping shall be polyethylene, SDR-11, with all welded joints meeting ASTM D3350 and ASTM 2513 with pipe designation 2306, 2406, or 3406.
Socket fusion fittings shall comply with ASTM D2683.
(31) All underground fittings shall be polyethylene, steel fittings are not allowed.
(32) Interior and above grade gas piping shall be black steel with malleable iron or steel fittings in conformance with ANSI B16.3 and ANSI B16.11, respectively.
(33) Gas service: gas service, valves, and meters shall be installed in compliance with local utility company requirements. All gas piping shall be polyethylene SDR-11 for the external part of the building, including isolation valves, (2” nut on main valve or slots on service) with anode less type risers. Refer to Base CADD detail for typical gas meter installation.
(34) All Underground gas piping shall be fitted with an anode less riser when accessing an above ground connection.
(35) Gas meters: Provide meters conforming to AGA B109.2, pipe mounted. Provide meters suitable for accurately measuring and handling gas at pressures, temperatures, and flow rates indicated. Provide meters with a pulse switch initiator (IMAC Systems Pulsimatic Model 300-10P-10 or equal) capable of operating up to speeds of 500 maximum pulses per minute with no false pulses and requiring no field adjustments.
Provide not less than one pulse per 100 cubic feet of gas. The pulse switch initiator shall be equipped with a dry switch type pulse output channel in which contact position is detected by a 5 Vdc wetting voltage supplied by a separate EMCS control panel resulting in a 0.5 mA maximum sense current when the contacts are closed.
Pulse kit must be able to produce a two-wire (Form A) pulse output to deliver data into an Advanced Meter Reading System (AMRS) compatible electric meter or to an accumulator that speaks the Modbus protocol natively and can communicate to AMRS via the Modbus/TCP protocol.
(36) Water Filling Stations: Single and Bi-Level water filling stations equal to
ELKAY.
a. Single – Wall mount: Elkay (Model LZS8WSLP) Bottle Filling Station & Single ADA, filtered, refrigerated cooler. Minimum chilling capacity 8.0 GPH (gallons per hour) of 50 Deg F drinking water, based on 80 deg F inlet water, and 90 deg. F, per ASHRAE 18 testing.
Features shall include antimicrobial materials, automatic filter status reset, energy savings, hands free, laminar flow, real drain system, visual filter monitor, safety bubbler, electronic bottle filler sensor with electronic front and side bubbler push-bar activation. Product shall be Wall Mount (On Wall), for indoor applications, serving as 1 station(s). Unit shall be compliance certified:
ADA & ICC A117.1, ASME A112.19.3/CSA B45.4, Buy American Act, CAN/CSA C22.2 No. 120, Green Spec, NSF/ANSI 42, 53, 61, & 372 (lead free) UL 399
b. Dual – Wall mount Bi- level: Elkay (Model LZSTLG8WSLK) Station shall conform to same capacity, temperature, filtration, and output requirements as “Single-Wall mount” above. Product shall be Wall Mount (On Wall), for indoor applications, serving as 2 station(s). Unit shall be of equal compliance certification as “Single-Wall mount” above.
c. In-Wall – Bottle filling station: Elkay (Model LZWSGRN8K) Station shall conform to same capacity, temperature, filtration, and output requirements as “Single-Wall mount” above. Product shall be Wall Mount (In- Wall frame/plate), for indoor applications, serving as 1 station. Unit shall be of equal compliance certification as “Single-Wall mount” above.
ENERGY MANAGEMENT CONTROL SYSTEMS (EMCS):
(37) Direct Digital Control (DDC) shall be a complete open architecture, open source, and non-proprietary system suitable for the heating, ventilating, and air conditioning (HVAC). DDC shall be 100% fully compatible/integrated with the existing base wide front-end EMCS currently used on Goodfellow AFB.
(38) Microprocessor controls on VAV boxes shall be fully 100% compatible with the Base EMCS construct that is currently utilized for Goodfellow AFB.
(39) Fiber optic transmission lines shall be used for base wide transmission of EMCS data, unless otherwise directed. New fiber optic lines shall be tied into the existing system with a fiber optic to copper interface.
(40) Copper interfaces shall be used to transmit EMCS data to the base local area network.
D. ELECTRICAL
INTERIOR:
(1) Cables: Conductors in cables shall be of copper only. Conductors #12 THHN AWG copper and larger shall be solid. Minimum acceptable size for power cables shall be #12 THHN AWG copper.
Each circuit will have its own grounded conductor with no sharing of grounded conductors. Each circuit will have a grounding conductor wire ran in the conduit with the circuit.
(2) Interior Wiring Conduit: No rigid nonmetallic conduit or electrical nonmetallic tubing shall be allowed unless approved by 17 CES/CEO. Aluminum conduit shall not be embedded in concrete or masonry, buried in earth, or used to penetrate firewalls. If conduit runs penetrate firewalls, steel conduit shall be used a minimum of three feet on each side. Metal-clad (type MC) cable is not acceptable and shall be so stated in the specifications under “wiring methods”. No exposed conduit or piping shall be permitted on exterior of building surface without prior approval from 17 CES/CEO. Exterior disconnect switches shall be installed in accordance with NEC section 404.8(A).
(3) 4” X 4” normal size and smaller cast-metal hub type boxes shall not be used when flush mounted on outside of exterior surfaces.
(Note: For electrical wiring, low voltage refers to voltages less than or equal to 50V whereas high voltage refers to voltages greater than or equal to 120V. Specification to wiring in between 50V and 120V should be cautioned and treated like the latter.
See (20) for further information).
(4) No equipment grounding conductor shall be installed in empty or low voltage conduits.
(5) Raceways and conduits shall not share both low and high voltage wiring.
(6) Low Voltage Dry Type Distribution Transformers: All new low voltage dry type distribution transformers 15 KVA and larger shall comply with NEMA TP-1 2002 standards for energy efficiency.
(7) Panelboards shall have a minimum of 20% of single pole spare spaces and 20% spare power. Panelboards must be near the loads they serve. Panelboards not within sight of the power feed, or in the same room, must be equipped with a main breaker.
(8) Toggle Switches: Where toggle switches are provided, ensure switches are UL 20, cULus rated, and NEMA WD1 rated for use. Provide quiet-type 20A, 120/277 volt unless noted otherwise. Toggle switch bodies shall thermoplastic or thermoset plastic type toggles with current rating and number of poles indicated.
(9) Receptacles: Where receptacles are provided, ensure receptacles are UL 498 general purpose grade, cULus rated , and UL 94 rated for flammability. Provide 20A, 125V tamper resistant receptacles unless noted otherwise. Provide steel housing and mounting strap with thermoplastic face and body.
(10) Device Plates: For plates on finished walls, provide UL listed one piece device cover plates to match color of wiring device. Where high impact is expected, provide cover plates conforming to UL 514C High Impact rating. Provide medium sized covers made of either thermoplastic or nylon with machine-type screws to match final finish of plate. Provide gasketed and UL listed cover plates in designated “wet areas”.
Final finish selection shall be either ivory or white as approved by 17CES.
LIGHTING:
(11) Exit lights: All EXIT lights shall be of the high intensity Light Emitting Diode (LED) type with the following standard features: universal/dual voltage (120/277V);
polymeric diffuser; white face with 6” red high letters; single face or double face and directional arrows as required; 3 watts maximum (for either single or double face version) or match existing signs if applicable.
(12) The emergency features shall include: maintenance-free nickel cadmium battery;
automatic low-voltage disconnect; reverse polarity and short-circuit protection; AC indicator light; push-to-test switch; constant current charger.
(13) The nickel cadmium battery shall carry a minimum of a 5-year full warranty.
Exterior EXIT lights shall be vandal resistant.
(14) LED lighting: All interior and exterior lighting including parking lot lighting shall be LED. Consider 3000 color rendering for Intel training classrooms and consider 4000 for all other interior applications. 5000 is recommended for exterior applications.
(15) LED Fixtures: Lighting for general office areas, classrooms, corridors, conference rooms, and lobbies shall be provided by LED fixtures incorporating an aluminum parabolic louver with 27 cell, low iridescent, specular silver, parabolic louver or match existing lighting in appearance if applicable.
(16) Emergency Lighting: Emergency lighting must be provided IAW the latest Edition NFPA 101, NEC and UFC code requirements. Unit equipment must be circuited to comply with NEC. Emergency battery packs within fluorescent fixtures and/or LED is the preferred method. Emergency ballasts will be connected to the same circuit as the remainder of the same fixture, but ahead of the local switch.
(17) Lighting Levels: General illumination levels shall not exceed the intensities shown in Mil-Hdbk 1190, Chapter 9, Table 9-1 through 9-4 and Illuminating Engineering Society of North America (IESNA) Handbook. Design of rooms (particularly areas with fluorescent troffer lighting) shall include evaluation of multi-level switching to provide user-adjustable levels of lighting, as well as dimming and work area lighting. Design Analysis shall address all options considered to minimize energy consumption while providing effective lighting, and the reasons for choices made shall be documented.
(18) Multi-level switching, using multiple ballasts and separately switched circuits to provide adjustable levels of lighting, is the minimum standard for all facilities. An example is having one tube on a ballast and two tubes on another ballast in a 2’x 4’ troffer, so either one, two or all three bulbs in a 3-bulb system can be selected.
Another design tool is to provide additional switches to sectionalize the room in addition to level control. Other design considerations include task lighting, strategically placed down lights, dimmers, photoelectric controls, occupancy sensors, LED, solar lighting, and day-lighting design, all of which give users flexible control of their workspace lighting and save money.
EXTERIOR ELECTRICAL:
(Note: Goodfellow AFB Electrical Primary Service is a Privatized Electrical Utility System)
(19) AEP Texas is the utility owner and sole provider of the electrical distribution utility system at Goodfellow Air Force Base, Texas. The Construction Contractor is responsible for paying AEP for installation of all temporary power lines.
a. Newly provided system infrastructure and/or modifications or of connections to the existing system infrastructure identified in the specifications and/or drawings must be coordinated with the utility owner prior to the contract start date.
b. To connect facilities, the construction contractor shall request that the utility owner provide the required connecting facilities, up to a point of demarcation which includes all terminations at the transformer.
c. The utility owner responsibilities include:
i. Sizing and providing of all primary conductors, including ditch and conduit.
ii. Sizing and providing of distribution transformer.
iii. Construction of transformer pad.
iv. Providing of secondary cable terminals.
d. All work on the system or facilities expected to connect to the system shall comply with the utility owner's specifications and construction standards.
Under no circumstance shall the construction contractor connect to, or otherwise touch the utility owner's infrastructure without the utility owner's express written permission.
The Utility owner: Contact via:
AEP Texas 930 West 19th Street San Angelo, Texas 76903 Phone: 325-657-2800
Temporary Power Notes:
a. The Construction Contractor shall provide the utility owner with contact names and phone numbers prior to commencement of work for any applicable project.
b. Temporary power pole location to be approved by AEP Texas.
c. Temporary construction power will be supplied to Construction Contractor with power poles located within five feet of an existing pad mounted transformer or within fifty feet of a primary power pole. The Construction Contractor is responsible for all utility connections.
(20) Medium Voltage Cable: Base Electrical Primary Distribution System has been privatized and this work is now the responsibility of AEP Texas.
(21) Lighting Poles shall be 30’ anodized bronze aluminum with flat panel style.
Troopwalk/sidewalk lighting shall be accomplished using LED luminaries equivalent to 70 watt HPS. Bollard fixtures shall not be used unless specifically so stated in project definition. High mast lighting shall be considered for large square parking lots. Where photocell controls are provided, provide utility grade controls with failure mode “on” configurations. Ensure controls are weather protected with UV stabilized polycarbonate with conformally coated electronics. Photocell controls shall conform to ANSI C136.10-2010 Roadway & Area Lighting Equipment ratings and UL773 & CSA TIL A15 (20 year design life).
(22) Transformers: New building service transformer shall be pad mounted served by an underground concrete encased duct bank. Base Electrical Primary Distribution System has been privatized and this work is now the responsibility of AEP Texas.
(23) Manholes: Base Electrical Primary Distribution System has been privatized and this work is now the responsibility of AEP Texas.
(24) Aerial to Underground Medium Voltage Connections: Base Electrical Primary Distribution System has been privatized and this work is now the responsibility of AEP Texas.
(25) Metering: Power meters shall be socket-mount design conforming to base form factor 9S. Meter shall be a Class 20, transformer rated design. Meter shall be capable of connection to the service voltage phases and magnitude being monitored. If the meter is not rated for the service voltage, provide suitable potential transformers (+/- 0.3% accuracy at 60Hz) to send an acceptable voltage to the meter. Meter shall accept independent voltage inputs from each phase. Meter shall be auto-ranging over the full range of input voltages. Meter shall accept independent current inputs from each phase. Current transformers (+/- 0.3% accuracy at 60Hz) shall be installed with a full load rating to meet the application requirements. All meters shall contain a separate indicator for measuring kilowatt-hours and maximum kilowatt demand. Meters shall be installed with shorting blocks or test switches to allow removal of the meter.
Meters shall be compatible and able to communicate with the Advanced Meter Reading System (AMRS) and the Base EMCS system. All electric meters shall meet the most up to date AMRS Meters Specifications provided by AFCEC. Meter shall be equipped with one dry switch type pulse output channel in which contact positions is detected by a 5 Vdc wetting voltage supplied by a separate EMCS control panel resulting in a 0.5 mA maximum sense current when the contacts are closed. Pulse out shall be related to kWh. Meters shall not be mounted on transformer cabinets.
Options for mounting include internal and external wall mounts or external pedestal mounts. Mounting configuration to be confirmed prior to installation. Conduit to be provided for all conductors associated with metering devices.
(26) All secondary and primary service shall be in PVC ducts using type URD cable with concentric neutral compatible with base system. All ductbanks containing voltage over 50 volts shall be concrete encased. Base Electrical Primary Distribution System has been privatized and this work is now the responsibility of AEP Texas.
(27) All exterior lighting shall be controlled by a 7 day electronic astronomic time switch, minimum 24 On/24 Off set points, manual operating bypass mode, battery back up, sunset On and sunrise Off option, and automatic daylight saving time On/Off adjustment.
(28) The Base Intrusion Detection Systems (IDS) is Advantor Systems Corp. No exposed conduits on exterior of buildings unless approved by 17 CES/CEO. For additional information on IDS contact 17 SFS/S5.
LIGHTNING PROTECTION:
(29) Lightning protection should be considered on all new facilities. Rods are preferred on all facilities that are not in remote locations on the base. Where rods are not applicable or allowed trapeze systems will be considered. All work performed on lightning protection systems shall be accomplished by certified Lightning protection specialists.
E. FIRE PROTECTION
(1) Facility construction shall be in accordance with UFC 3-600-01, Fire Protection Engineering for Facilities, NFPA 101, and all applicable National Fire Codes.
Emergency lighting shall be in accordance with NFPA 70 and NFPA-72.
(2) Base Fire department vehicles must have unimpeded access to the building for emergency response, IAW UFC 3-600-01.
(3) Fire alarms shall be audible and/or audiovisual installed in accordance with the latest edition of NFPA 72 and UFC 3-600-01. Fire alarm junction/pull boxes and covers shall be red to identify them as part of the fire protection system. Fire alarm conduit shall be ¾” minimum diameter. UFC 3-600-01 and NFPA will be strictly adhered to this design of the fire alarm system. Refer to Attachment I for additional information on Fire Alarm Control Panels (FACP).
(4) Each floor of multi-story buildings shall be zoned separately for fire alarms and sprinkler systems. See UFC-3-600-01 for applicable zoning.
(5) Fire extinguisher cabinets shall be recessed and installed in accordance with NFPA-10. Fire Extinguishers and cabinets will be contractor provided. Fire extinguishers will be 10 pound, 4A: 60B: C rechargeable.
(6) All fire hydrants shall be painted to match the color scheme currently used on Goodfellow AFB. The top cap painted IAW NFPA 291 marking and color standards for the rated capacity at the time of installation. Fire hydrant colors shall be as follows:
a. (Fire Hydrant Barrel: For all potable water) Tan – B54W101 – Stucco Match Apply reflective/glass beads while paint is still wet.
b. Brown - B54T104 – New Slate Bronze
(Fire Hydrant Barrel: Only applies to non-potable water at the Fire Training School)
c. Green – B54T104 – SW 7420 Equipment Green
(Fire Hydrant Cap Only)
(Note, custom paint colors and identification numbers are based upon the San Angelo Sherwin-Williams store.) For additional information contact:
Sherwin Williams Co. (325) 944-4521 10 N Fillmore San Angelo, TX 76901
(7) Double check or reduced pressure type backflow protection shall be installed as part of the fire protection system. Post Indicator Valves (PIV) shall be installed with an electronic tamper proof switch, physical locks, and a permanently attached 6”x4” brown sign with white text identifying the building or buildings served. OS & Y valves shall have a dual tamper switch located on valves. The PIV shall be painted to match the color currently used on Goodfellow AFB.
(8) Fire protection piping under buildings shall be ductile iron to a point 5 ft. outside the building. Ductile iron fire protection risers and fire hydrant hubs shall be provided with a sacrificial anode to conform to UFC 3-570-06 and MIL HDBK 1136.
(9) Sprinkler Heads: Semi-recessed or fully recessed sprinkler heads shall be used to the greatest extent possible. All sprinkler conduits shall be black steel pipe IAW
NFPA 13.
(10) Heat Detectors: All heat detectors and their installation must comply with UFC and NFPA regulations.
ATTACHMENT I
GOODFELLOW’S EXISTING MATERIAL/EQUIPMENT
PRODUCT MANUFACTURE SPECIFICATION
1. Prime-A-Pell 200 brick sealant/repellant ChemProbe Coating Systems VOLATILE ORGANIC
6.1 lbs/gal
ACTIVE INGREDIENT -
Oligomeric Alkylalkoxy Siloxane/Diffused Quartz Carbide
ACTIVE CONTENT 7%
FLASH POINT - SETA
102°F (39°C)
SOLUBILITY IN WATER
None APPEARANCE Clear liquid
2. Door ECALS, Card reader and other ECALS electrical equipment
Best “B.A.S.I.S. G series”
Best cylindrical 9K Series
93KG7DV15MS-S3-626-
EXBB
Best BASD-MSE Mag-stripe encoder Best BASD-CAB Programming cable Best BAS-SES-G Software Best BASD-PDA Transport device including cable for personal computer connection.
ANSI A156.2, Series 4000, Grade 1 Mortise lock case, meeting or exceeding ANSI A156.13, Series 1000
Goodfellow existing master key system is by “Best”.
3. Aluminum Storefront
Kawneer, Corp.
Kawneer 350 medium duty door, Tri-Fab 451 storefront system (1 ¾” x 4 ½”)
4. Windows
EFCO, Corp.
Kawneer, Corp.
EFCO 5600 System, fixed-pane, blast-resistant
5. Suspended Ceilings
Armstrong, Corp.
Gold Bond Building Products
Wet Areas:
Provide 24” x 24” gypsum core & stapple texture vinyl laminate coated tiles rated for use by WOA in food service and wet areas. Provide fire-resistant tiles where noted.
White finish; Prelude 15/16” ceiling tile grid or equivalent.
All other areas:
Provide 24” x 24” x 5/8” mineral fiber, beveled tegular tile.
Provide Class A fire-resistance with ceiling grid system, White, Armstrong Suprafine 9/16” system or equivalent.
6. Cement backer board
US Gypsum 1/2” Dura-Rock
7. Restroom Partitions
Scranton Products National Toilet
Toilet enclosures shall conform to CID A-A-60003, Type I, Style C, overhead braced. Panels shall be solid polyethylene, Finish 5.
8. Landscape Irrigation equipment
Rain Dial; for fix spray, use Toro; for gears, use Nelson
Capable of covering 10 feet radius at 25 psi with a or Rain Bird; Controllers:
Toro and Rain Bird discharge rate of 2 gpm.
Sprinkler body, nozzle, and screen constructed of heavy-duty, ultra-violet resistant plastic with wiper seal.
Brass nozzle with matched precipitation rate and an adjustable screw capable of regulating the radius and flow.
Controller, NEMA ICS 2 with 120-volt single phase service, operating with indicated station, and grounded chassis. Provide enclosure NEMA ICS 6 Type 3R], with locking hinge cover, wall mounted.
9. Landscape Weed Barrier and Concrete Decorative Curb (no metal edge)
ACF West Geo-Synthetic Products
PolySpun 350: Resist degradation due to ultraviolet exposure and resistant to commonly encountered soil chemicals, mildew and insects, and is non-biodegradable.
10. Standing Seam Metal Roof Systems
AEP Roofing, Corp. (for retrofits flat to sloped)
Berridge (New roofs)
Mueller, Inc.
5-year Warranty for Non- Structural Metal Roofing System, 20-year Manufacturer's Material (finish and rust) and Weathertightness Warranty.
Zinc-coated steel conforming to ASTM A 653/A 653M;
aluminum-zinc alloy coated steel conforming to ASTM A 792/A 792M, AZ 55 coating;
or aluminum-coated steel conforming to ASTM A 463/A 463M, Type 2, coating designation T2 65.
UL…