Report 1846 PH B103 Fire Alarm PM 4-5-21.pdf
PDF 426 KB Posted
- Solicitation number
- FA255024R0003
About this file
This document contains a fire alarm system inspection report and related federal contract opportunity notice. The inspection report details the annual testing and maintenance of fire alarm equipment at a U.S. Navy facility in Prospect Harbor, Maine. All fire alarm panels, detectors, and notification devices were inspected and tested with no failures noted. The related federal contract opportunity is a pre-solicitation notice for base operations support services at the Prospect Harbor Space Force Station, including physical security, facilities maintenance, communications, logistics, and environmental compliance. The solicitation is expected to be released in January 2024 as a 100% small business set-aside with a best value source selection. The notice provides registration details for the Procurement Integrated Enterprise Environment solicitation module which will host proposal submissions.
View the file
Other files
Show 40 more
Latest 50 of 292 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(ATTACH ADDITIONAL SHEETS IF NECESSARY)
YES NO
YES NO
YES NO
MATERIALS USED
MAINTENACE & INSPECTION REPORT
(ONE FOR EACH PIECE OF EQUIPMENT)
WILL MATERIALS NEED TO BE ORDERED? HOW LONG IS THE LEED TIME?
EXPLAIN BELOW
HAVE NOT BEEN MET
(BELOW) FOR ADMINISTRATION USE ONLY
DATE IT WILL BE RECEIVED :
PROPER PPE BEING WORN
YES
CONTRACTOR: TECHNICIANS NAME:
LOCATION WEATHERBUILDING NAME or #
CONTRACTOR/SIGNATURE CCI/ SIGNATURE SITE INSPECTOR/SIGNATURE
CONTRACT # ELIN # REPORT NO.
HAVE BEEN MET
DATE:
General Direct Condition Rating
TYPE OF EQUIPMENT MAKE MODEL
WORK DESCRIPTION & PROBLEMS FOUNDS
TIME TO COMPLETE TASK
IS INSPECTION CHECK LIST ATTACHED?
SAFETY REQUIREMENTS
WAS WORK COMPLETED?
IF NO EXPLAIN BELOW
General Direct Condition Rating Notes ( Explain Conditions found for the Rating given above)
N40085-17-D-7201
NO
HOUSE KEEPING COMPLETE
YES
NO
MAXIMO # Work Order #
4/5/2021
Fire alarm system Simplex 4010ES 2 Dean & Allyn, Inc. Barry Prescott
Prospect harbor #103 Cool/drizzle Green +
Performed annual fire alarm test
1846E002AM
x
Barry Prescott #135
200000044214Inspection Ref:
Conducted by:
Report of Inspection/Test
Property US Navy - Prospect Harbor -
Bldg 103
Light House Point Road
Prospect Harbor, ME
Annual Alarm
Print Date: 5/3/2021
April 5, 2021
Equipment Summary
Site
Description
Inspected Unable to
Inspect Serviced
Repaired Failed
%Qty%Qty%Qty%QtyQty
Alarm Alarm Panel 2
1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Battery
Sealed Lead Acid 1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Panel Information
Panel Manufacturer Model Serial No. Location
Simplex 4010ES
Overcurrent Protect Type Overcurrent Size (Amps) Primary Supply Disconnect Location / Panel # / Breaker #
Battery Test
Location Type Manufacturer
Model
R e p la ce m e n t
D a te
Q u a n tit iy
C o n d iti o n
L e a ks o r
C o rr o si o n
C o n n e ct io n s
V o lta g e N o
L a d
M e a su re d
C a p a ci ty A
-H r
R a te d C a p a ci ty
A -H r O k?
V o lta g e W ith h a rg e r
V o lta g e N
L a d
M e a su re d a p a ci ty A
-H r Ok OkOk Ok12-172 Sealed Lead Acid 17 13.08 1913.06
Device Summary
Device Qty Manufacturer Model Quantity
Failed
% of Total
Tested
Quantity
Tested
Indicating Devices
Horn/Strobe 3 3 0100%
Initiating Devices
Pull Station 3 3 0100%
Smoke PE 11 smoke & combination smoke/CO2 det. 11 0100%
Indicating Devices
Strobe 1 1 0100%
System Function Summary & Test
Function Description Test Result
Alarm Functions
Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass
Print Date: 5/3/2021 Copyright 2002-2018 Life Safety Inspector, OnSite Software
Report of Inspection/Test
US Navy - Prospect Harbor - Bldg 103Property:
200000044214Inspection Ref:
Annual Alarm
April 5, 2021
System Function Summary & Test
Function Description Test Result
Alarm Panel Supervisory Functions
Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass
Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass
Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass
Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass
Ground Faults Detected Ground faults in alarm circuits are detected Pass
Panel Inspection (Alarm Panel 2)
Yes Panel and surrounding equipment, conduit and wiring well secured and in good condition
YesSystem was in operation upon arrival?
Yes Primary power supply operates properly under full load
YesAre all lamps and displays operating correctly?
Yes Have all fuses been checked for rating and supervision
YesTransient suppressors visually inspected?
Yes Are operating instructions posted or available at the panel?
YesAre drawings and wiring diagrams available at the panel?
Yes Are zones labeled and identified?
Central Station Test (Central Station Test)
Alarm, Trouble and Supervisory indication tested and verified with the central station?
YesType Transmission
Operator spoke to
Inspector's Suggestions (Recommendations)
None In addition to the problems noted in this report the inspector suggests the following system changes/improvements, however, these suggestions are not the result of an engineering survey.
Print Date: 5/3/2021 Copyright 2002-2018 Life Safety Inspector, OnSite Software