Report 1457 PH B112 Fire Alarm PM 6-30-20.pdf
PDF 680 KB Posted
- Solicitation number
- FA255024R0003
About this file
This document contains a report on an annual fire alarm inspection and test at a U.S. Navy facility, along with a related federal contract opportunity notice for base operations support services at the facility.
The fire alarm inspection report details the inspection of an alarm panel and devices at a Navy building, finding everything in proper working order. The related federal contract opportunity is a pre-solicitation notice for base operations support at the Prospect Harbor Space Force Station in Maine. Services will include facility operations, maintenance, security, logistics and other support functions. The planned solicitation release date is January 2024 and the requirement is set aside for small businesses. The contract will transition the facility's operations from Navy to Space Force responsibility in October 2024.
View the file
Other files
Show 40 more
Latest 50 of 292 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
x
D002AM 1457
Barry Prescott #135
200000030930Inspection Ref:
Conducted by:
Report of Inspection/Test
Property Owner/Agent
526 Western Ave.
Augusta, ME 04430
CCI Group, LLCUS Navy - Prospect Harbor -
Bldg 112 (admin)
Light House Point Road
Prospect Harbor, ME
Annual Alarm
Derek McCaslin
(207)620-7172 x111 Print Date: 7/31/2020
06/30/2020
Signatures
Inspector - Printed Date CompletedInspector - Signature
Barry Prescott 6/30/20
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Equipment Summary
Site
Description
Inspected Unable to
Inspect
Serviced
Repaired Failed
%Qty%Qty%Qty%QtyQty
Alarm Alarm Panel 2
1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Battery
Sealed Lead Acid 1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Panel Information
Panel Manufacturer Model Serial No. Location
Silent Night 5208
Overcurrent Protect Type Overcurrent Size (Amps) Primary Supply Disconnect Location / Panel # / Breaker #
Battery Test
Location Type Manufacturer
Model
R e p la ce m e n t
D a te
Q u a n tit iy
C o n d iti o n
L e a ks o r
C o rr o si o n
C o n n e ct io n s
V o lt a g e N o
L a d
M e a su re d
C a p a ci ty A
-H r
R a te d C a p a ci ty
A -H r O k?
V o lta g e W ith h a rg e r
V o lt a g e N
L a d
M e a su re d a p a ci ty A
-H r
Ok OkOk Ok 2 Sealed Lead Acid 15 13.24 1413.24
Device Summary
Device Qty Manufacturer Model Quantity
Failed
% of Total
Tested
Quantity
Tested
Initiating Devices
Pull Station 2 2 0100%
Smoke PE 6 6 0100%
Heat Detector 5 ror 5 0100%
Indicating Devices
Horn/Strobe 2 2 0100%
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software
Report of Inspection/Test
US Navy - Prospect Harbor - Bldg 112 (admin)Property:
Owner: CCI Group, LLC 200000030930Inspection Ref:
Annual Alarm
06/30/2020
System Function Summary & Test
Function Description Test Result
Alarm Functions
Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass
Alarm Panel Supervisory Functions
Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass
Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass
Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass
Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass
Ground Faults Detected Ground faults in alarm circuits are detected Pass
Panel Inspection
Yes Panel and surrounding equipment, conduit and wiring well secured and in good condition
YesSystem was in operation upon arrival?
Yes Primary power supply operates properly under full load ?
YesAre all lamps and displays operating correctly?
Yes Have all fuses been checked for rating and supervision ?
YesTransient suppressors visually inspected?
Yes Are operating instructions posted or available at the panel?
YesAre drawings and wiring diagrams available at the panel?
Yes Are zones labeled and identified?
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software