Report 1455 PH B103 Fire Alarm PM 6-30-20.pdf
PDF 679 KB Posted
- Solicitation number
- FA255024R0003
About this file
This document contains a report on the annual inspection of the fire alarm system at the Prospect Harbor Space Force Station in Maine, as well as a notice regarding an upcoming solicitation for base operations support services at that location.
The fire alarm inspection report documents the testing and status of the system's components, including the alarm panel, pull stations, smoke detectors, horns, strobes, and backup battery. All equipment was found to be in working order. The base operations support solicitation is expected to be released in January 2024 seeking services to manage, operate, maintain, and provide logistical and security support for the station under a GOCO contract. The requirement is set aside for small businesses and will utilize a best value tradeoff source selection process. Offerors are advised to register for the Procurement Integrated Enterprise Environment to submit proposals electronically.
View the file
Other files
Show 40 more
Latest 50 of 292 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
x
D002AM #1455
Barry Prescott #135
200000030927Inspection Ref:
Conducted by:
Report of Inspection/Test
Property US Navy - Prospect Harbor -
Bldg 103
Light House Point Road
Prospect Harbor, ME
Annual Alarm
Print Date: 7/31/2020
06/30/2020
Signatures
Inspector - Printed Date CompletedInspector - Signature
Barry Prescott 6/30/20
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Equipment Summary
Site
Description
Inspected Unable to
Inspect
Serviced
Repaired Failed
%Qty%Qty%Qty%QtyQty
Alarm Alarm Panel 2
1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Battery
Sealed Lead Acid 1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Panel Information
Panel Manufacturer Model Serial No. Location
Simplex 4010ES
Software Rev Software Updated
Overcurrent Protect Type Overcurrent Size (Amps) Primary Supply Disconnect Location / Panel # / Breaker #
Battery Test
Location Type Manufacturer
Model
R e p la ce m e n t
D a te
Q u a n tit iy
C o n d iti o n
L e a ks o r
C o rr o si o n
C o n n e ct io n s
V o lta g e N o
L a d
M e a su re d
C a p a ci ty A
-H r
R a te d C a p a ci ty
A -H r O k?
V o lta g e W ith h a rg e r
V o lta g e N
L a d
M e a su re d a p a ci ty A
-H r
Ok OkOk Ok 12-182 Sealed Lead Acid 14 13.8 2013.06
Device Summary
Device Qty Manufacturer Model Quantity
Failed
% of Total
Tested
Quantity
Tested
Initiating Devices
Pull Station 2 2 0100%
Smoke PE 11 11 0100%
Indicating Devices
Horn/Strobe 4 4 0100%
Strobe 1 1 0100%
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software
Report of Inspection/Test
US Navy - Prospect Harbor - Bldg 103Property:
200000030927Inspection Ref:
Annual Alarm
06/30/2020
System Function Summary & Test
Function Description Test Result
Alarm Functions
Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass
Alarm Panel Supervisory Functions
Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass
Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass
Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass
Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass
Ground Faults Detected Ground faults in alarm circuits are detected Pass
Panel Inspection
Yes Panel and surrounding equipment, conduit and wiring well secured and in good condition
YesSystem was in operation upon arrival?
Yes Primary power supply operates properly under full load ?
YesAre all lamps and displays operating correctly?
Yes Have all fuses been checked for rating and supervision ?
YesTransient suppressors visually inspected?
Yes Are operating instructions posted or available at the panel?
YesAre drawings and wiring diagrams available at the panel?
Yes Are zones labeled and identified?
Central Station Test
Yes Operator spoke toAlarm, Trouble and Supervisory indication tested and verified with the central station?
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software