EXHIBIT_U-Inspection_MFD-2023-0000511-1.pdf
PDF 192 KB Posted
- Attached to
- Excess Liability Insurance
- Solicitation number
- 2024-316
- Issued by
- Collin County, Texas
About this file
The document is a McKinney Fire Department Inspection Report for the Collin County Justice Center located at 4300 Community Ave in McKinney, Texas. The inspection was conducted by Fire Inspector Morrell Blissett on December 8, 2023, with an inspection number of MFD-2023-0000511-1. The inspection was classified as a High Risk Inspection and resulted in no violations, though several items were noted for resolution, including extension cord usage, fire-rated assemblies, exit lights, sprinkler system, and kitchen hood system.
Specific items addressed in the inspection included instructions to not interconnect power strips in booking areas, replace missing or damaged ceiling tiles, repair exit lights at the back dock, connect a hose in pod 1C, and tag the kitchen hood system. The report also recommended permitting and adding a BDA (Bi-Directional Amplifier) system. The next inspection is tentatively scheduled for on or after October 26, 2024. The report was signed by Rick Monk from Facilities/Maintenance and Fire Inspector Morrell Blissett, emphasizing the facility's commitment to maintaining fire and life safety code compliance.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
McKinney Fire Department Inspection Report
(No Violations)
Fire Prevention - High Risk Inspection Result Inspection Status Inspected by Completed at Inspection Number
Completed Morrell Blissett 12/08/2023 10:09:01 MFD-2023-0000511-1
Address Suite City State Zip
4300 COMMUNITY
AVE
-- MCKINNEY TX 75071
Business Name Building Type
Collin County Justice Center Unknown
General:
Resolved
ITEM: Extension cords/multiplug adapters use per code
Do not interconnect power strips in booking.
CODE: IFC - 603.6 - Extension cords. - Extension cords shall not be a substitute for permanent wiring and shall be listed and labeled in accordance with UL 817. Extension cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Extension cords marked for indoor use shall not be used outdoors.
Resolved
ITEM: Extension cords/multiplug adapters use per code 2nd Instance
You cannot use extension cords in place of permanent wiring......warehouses
CODE: IFC - 603.6 - Extension cords. - Extension cords shall not be a substitute for permanent wiring and shall be listed and labeled in accordance with UL 817. Extension cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with
1 / 4
Inspection #MFD-2023-0000511-1
EXHIBIT U
portable appliances. Extension cords marked for indoor use shall not be used outdoors.
Resolved
ITEM: Fire rated assemblies intact
Replace the missing or damaged ceiling tiles.
CODE: IFC - 701.2 - Fire-resistance-rated construction. - The fire-resistance rating of the following fire-resistance-rated construction shall be maintained: 1.Structural members. 2.Exterior walls. 3.Fire walls, fire barriers, fire partitions. 4.Horizontal assemblies. 5.Shaft enclosures.
B0158
Exits:
Resolved
ITEM: Exit lights illuminated and signs posted in approved location
Repair the exit lights at the back dock.
CODE: IFC - 1013.6.3 - Power source. - Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 603. Group I-2, Condition 2 exit sign illumination shall not be provided by unit equipment batteries only. Exception: Approved exit sign illumination types that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system.
2 / 4
Back dock
Fire Protection Equipment :
Resolved
ITEM: Sprinkler system in service and annually inspected
Connect the hose in pod 1C.
CODE: IFC - 901.6.1 - Standards. - Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 901.6.1.
1C
Resolved
ITEM: Kitchen hood system in-service and inspected
Need to tag the kitchen hood system.
CODE: IFC - 606.3.4 - Extinguishing system service. - Automatic fire-extinguishing systems protecting commercial cooking systems shall be serviced as required in Section 904.13.5.
Ad-hoc violations:
Resolved
ITEM: Recommend permitting and adding a BDA system.
Next inspection is tentatively scheduled to be conducted on or after 10/26/2024.
Thank you for maintaining fire and life safety code compliance!
No violations were noted on this inspections.