The file is an Excel spreadsheet (Exhibit M-Tank Schedule) for Collin County, Texas, detailing storage tank information across three county facilities: Farmersville Service Center, Collin County Juvenile Justice Center, and Collin County Service Center. The document provides a comprehensive inventory of eight storage tanks, including their installation dates (ranging from 1988 to 2004), capacities (from 1,000 to 20,000 gallons), and contents such as unleaded gasoline, diesel, asphalt emulsion, and waste oil. The tanks vary in construction types, including double-walled and single-walled designs, with materials like steel, concrete, and fiberglass reinforced plastic (FRP).
The accompanying contract opportunity is for Excess Liability Insurance, seeking a three-year contract with two potential one-year extensions. Collin County, currently self-insured for general liability, is requesting proposals for excess liability coverage in multiple areas including commercial crime, professional liability, public officials' errors and omissions, employment practices, law enforcement liability, and pollution coverage. The county is seeking coverage options with self-insured retentions (SIR) of $1,000,000 or $2,000,000, with coverage limits of $3,000,000 or $5,000,000. The insurance proposal aims to provide comprehensive protection for various county operational risks beyond the existing self-insurance threshold.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Locations
| EXHIBIT M | ||||
| Location Number | Name | Address | Facility Type | Own/Lease |
| 1 | Farmersville Service Center | 1269 S State Hwy 78, Farmersville, TX 75442 | Local Government Center | Own |
| 2 | Collin County Juvenile Justice Center | 4600 Community Ave McKinney, TX 75071 | Generator Fueling Facility | Own |
| 3 | Collin County Service Center | 700 A Wilmeth Road McKinney, TX 75069 | Local Government Center | Own |
Tank Info
| EXHIBIT L | |||||||||
| Location | 1 - Farmersville Service Center | 1- Farmersville Service Center | 1- Farmersville Service Center | 2- Collin County Justice Center | 3 - Collin County Service Center | 3 - Collin County Service Center | 3 - Collin County Service Center | 3 - Collin County Service Center | NOTE: Storage Tank #4 is currently not being used due to a leak in the pipe (the leak was not from the tank itself). The tank still has fuel in it. |
| Tank # | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |
| Underground/Aboveground | AST | AST | AST | UST | UST | UST | AST | AST | |
| Install Date Year | 1996 | 2004 | 2004 | 1993 | 1988 | 1988 | 2000 | 2004 | |
| Capacity (Gallons) | 6,000 | 9,600 | 9,600 | 20,000 | 6,000 | 12,000 | 1,000 | 9,600 | |
| Contents | Split Product Tank: Unleaded Gasoline- 1,000 Diesel- 5,000 | Asphalt Emulsion | Asphalt Emulsion | Diesel | Unleaded Gasoline | Diesel | Waste Oil | Asphalt Emulsion | |
| Tank Construction Double Walled (DW)/ Single Walled (SW) | DW | SW | SW | SW | SW | SW | DW | SW | |
| Tank Construction Material (DWDM-Double Wall/Double Material) | Steel, Concrete, DWDM | Steel | Steel | FRP (Fiberglass Reinforced Plastic) | FRP (Fiberglass Reinforced Plastic) | FRP (Fiberglass Reinforced Plastic) | Steel, Concrete, DWDM | Steel | |
| Overfill/Spill Protection | Spill Containment Bucket, Level Gauges- High Level Alarms | None | None | Tight Fill, Level Gauges- High Level Alarms, Spill Containment Bucket, Flow shut-off | Tight Fill, Level Gauges- High Level Alarms, Spill Containment Bucket, Flow shut-off | Tight Fill, Level Gauges- High Level Alarms, Spill Containment Bucket, Flow shut-off | Level Gauges- High Level Alarms | None | |
| Tank Leak Detection | Automatic Tank Gauging System | Visual Inspection of AST systems | Visual Inspection of AST systems | Automatic Tank Gauging Systems, Groundwater Monitoring Wells, Tight Fill | Automatic Tank Gauging Systems, Groundwater Monitoring Wells, Tight Fill | Automatic Tank Gauging Systems, Groundwater Monitoring Wells, Tight Fill | Automatic Tank Gauging Systems, Visual Inspection of AST systems | Visual Inspection of AST systems | |
| AST Diking and Base Construction | None | Asphalt Dike | Asphalt Dike | N/A | N/A | N/A | None | Asphalt Dike | |
| Piping Construction (DW or SW) | SW | SW | SW | SW | SW | SW | SW | SW | |
| Piping Construction Material | Steel | Steel | Steel | FRP | FRP | FRP | Steel | Steel | |
| Piping Leak Detection | Visual | Visual | Visual | Interstitial Monitoring in containment pipe | Mechanical Line Leak Detector | Mechanical Line Leak Detector | Visual | Visual |