EXHIBIT_P_-_ELECTRICAL_AND_COMMUNICATIONS.pdf
PDF 29 MB Posted
- Attached to
- Jack Mountain Multi-Use (JMMU) Range Upgrades, Rep Federal contract opportunity
- Solicitation number
- 140D0426R0084
About this file
This is an electrical and communications design exhibit for a Stationary Infantry Target installation at Fort Hood, Texas, part of the Jack Mountain Multi-Use (JMMU) Range Upgrades project. The exhibit provides detailed specifications and installation requirements for the electrical infrastructure serving target systems within the range.
The design specifies installation of a wall-mounted NEMA 3R loadcenter (13"H x 12"W x 6"D maximum) with a 125-amp main, single-phase 240/120V service fed from an existing transformer (TRSF-XX). Key electrical components include a Target Power Receptacle (TPR) rated 120/240V, 20A with NEMA L14-20R twist-lock connector; an Auxiliary Power Receptacle (APR) rated 120V, 20A with NEMA L5-20R connector; a GFCI-protected Maintenance Receptacle (MR); and a Data Power Receptacle (DPR) inside the Master Target Data Panel (MTDP). All equipment must be mounted no higher than 2 inches from the top of the emplacement wall. The design requires reuse of existing cables and conduits, installation of new conduit hubs with cable seal fittings, and NEMA 4-rated enclosure penetrations using Myers-type hubs. All outlet boxes must have perpendicular conduit runs to loadcenter and MTDP enclosures, with no bends or offsets acceptable. Critical requirements include #6 AWG bare copper grounding conductors, NEMA 3R wet-location covers for all outlets, permanent labeling coordination with Fort Hood Range Operations, and mandatory Range Training and Land Program Huntsville Center approval for any deviations to equipment sizes, numbers, or cable entry methods.
View the file
Other files for this federal contract opportunity
Show all 50
Jack Mountain Multi-Use (JMMU) Range Upgrades, Rep has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT P - ELECTRICAL AND COMMUNICATIONS
G
F
E
D
C
B
A
2 3
#6 BARE COPPER
CONDUCTOR
ISOMETRIC ELEVATION
STATIONARY INFANTRY TARGET
NOTTO SCALE
NOTES:
1. RE-USE EXISTING CABLES CONDUITS WITH POWER AND
DATA CABLES ENTERING EMPLACEMENT.
2. INSTALL NEW CONDUIT HUB WITH CABLE SEAL FITTING IN
NEW MTDP. SEE DETAIL ON E-07.
3. PROTECT POWER AND DATA CABLES DURING
REMOVAUDEMOLITION OF EXISTING DATA ENCLOSURE
LOADCENTER. RE-TERMINATE DATA CABLES IN NEW
MTDP ENCLOSURE AND POWER CABLES IN NEW
LOADCENTER.
4. EQUIPMENT SHALL NOT BE MOUNTED HIGHER THAN 2"
FROM TOP OF EMPLACEMENT WALL.
5. POWER TO DATA PANEL RECEPTACLE IN MTDP SHALL BE
ROUTED THROUGH SINGLE POLE SINGLE THROW SWITCH.
6. OUTLET BOXES SHALL BE MOUNTED SO THAT CONDUIT
RUNNING FROM OUTLETS TO LOADCENTER AND MTDP
ENCLOSURES ARE PERPENDICULAR. BENDS AND
CONDUIT OFFSETS TO ENTER ENCLOSURES ARE
UNACCPETBLE.
7. TPR, APR AND DPR SHALL NOT BE GFCI PROTECTED.
8. PERMANENTLY LABEL THE EMPLACEMENT ACCORDING TO
EXISTING LABELING SCHEME. COORDINATE LABELING
WITH FT HOOD RANGE OPERATIONS.
9. PROVIDE SEAL FITTINGS AS SHOWN IN DETAILS ON SHEET
E-07 FOR ALL CABLE ENTRANCES INTO NEMA 4 RATED
ENCLOSURES.
PANEL BOARD: SIT LOCATI ON: XXXX
125 AM P MAIN MAIN LUGS ONLY
VOLTAG E: 240/120 PHASE: 1 WIRE: 3
VAi PHASE
LOAD SERVED
NO. TRIP WIRE
A B
CKT
POLES AM PS SIZE NO.
SURGE ARRESTOR 2 ---- --- 1
SUB FEED THRU LUGS 2 ---- --- 5
0 0
TOTAL VA PHASE A: 444
TOTAL VA PHASE B: 394
SUPPLIED FROM: TRSF-XX
10. INSTALL MYERS TYPE HUBS ON ALL CONDUIT
PENETRATIONS TO SIDE OF ENCLOSURE.
11. ALL DIMENSIONS SHOWN IN INCHES UNLESS OTHERWISE
NOTED.
12. PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA 3R
WET LOCATION COVERS MAKING OUTLETS SUITABLE FOR
USE IN WET LOCATIONS. SEE DETAIL SHEET E-07 FOR WET
LOCATION COVER. IN USE COVERS WITH COVERS
INTENDED TO CLOSE OVER THE INSERTED CORD ARE NOT
ACCEPTABLE AS THESE COVERS WILL NOT CLOSE OVER
TARGET OR AUXILIARY CORDS.
13. DEVIATIONS TO THE EQUIPMENT SIZES, EQUIPMENT
NUMBERS, RECEPTACLE COVERS, OR CABLE ENTRY
METHODS INTO ENCLOSURES WILL REQUIRE RANGE
TRAINING AND LAND PROGRAM HUNTSVILLE CENTER
MANDATORY CENTER OF EXPERTISE APPROVAL.
14. SEE SHEET E-08 FOR ADDITIONAL INFORMATION ON
MASTER TARGET DATA PANELS.
MOUNTED: SURFACE FEED: BOTTOM
ASYM A. I. C MIN. : 10,000
RATING: NEMA 3R
VAi PHASE
CKT
A B
WIRE TRIP NO.
LOAD SERVED NO. SIZE AM PS POLES
394 SIT (NEMA L 14-20R &
2 12 20 2 NEMA L5-20R) 394
6 50 12 20 1 TDP AND MR
8 --- --- 20 1 SPARE
444 394
TOTAL CONNECTED WATTAGE: 838
TOTAL DEMAND AM PS: 3
5 6
LATCHED TYPE REMOVABLE LID.
CONTINUOUS HINGE WITH
REMOVABLE PIN. NEMA 4
ENCLOSURE. SEE NOTE 14.
CONDUIT WITH FIBER OPTIC
DATA CABLES. SEE
NOTE 1-3, & 9.
#6 AWG BARE COPPER
CONDUCTOR. SEE NOTE 9.
CABLE SEAL FITTING.
SEE NOTE 9. TYPICAL
SINGLE GANG 2 5/8" DEEP WEATHERPROOF
BOX WITH WEATHERPROOF BLANK COVER
FOR USE BY TARGET VENDOR.
8 9 10
GFCI MAINTENANCE RECEPTACLE (MR)
AND SINGLE POLE, SINGLE THROW 120V
SWITCH IN WEATHERPROOF ENCLOSURE
WITH COVER. SEE NOTE 4 & 5.
TARGET POWER RECEPTACLE (TPR)
120/240V, 20A, 4 WIRE. TWIST LOCK
(NEMA L 14-20R) WITH WEATHERPROOF
ENCLOSURE WITH WET LOCATION
COVERS. SEE NOTES 4, 7, & 12.
SEE NOTE 8
POWER CABLE IN CONDUIT TO
NEXT/PREVIOUS TARGET PIT.
SEE NOTES 1-3.
AUXILIARY POWER RECEPTACLE (APR) 120V, 20A,
3 WIRE, TWIST LOCK (NEMA L5-20R) WITH WET
LOCATION COVER IN WEATHERPROOF
ENCLOSURE. SEE NOTE 7 & 12.
FRONT ELEVATION
STATIONARY INFANTRY TARGET
DATA POWER RECEPTACLE (DPR) LOCATED
INSIDE PANEL. SEE NOTES 14. RECEPTACLE
SHOWN ON MTDP DETAIL.
NOTTO SCALE
TOP ELEVATION
STATIONARY INFANTRY TARGET
NOTTO SCALE
WALL MOUNTED NEMA 3R
LOADCENTER
13"H X 12"W X 6"D MAX
#6 AWG BARE COPPER
CONDUCTOR, 6' COILED
ABOVE GROUND FOR
BONDING TO FUTURE
TARGET
US Army Corps of Engineers® u 0:
a.
f-:,; :,;
<( e. w
0: CD
(9 ~ ~
Cf) Ct'.
Ou, z <{
8:~~ _J f-
~ >-OU(.') Ct'.
'.'izffi ~ w f-a, ;;: 0 z (.')a,<( _J <{ ~5g: <{ lJ._
~U w (.) ~ <ocn ir >-~g~ f- Ct'.
0 :,:0: (.) <{
~~~ w z _J 0 UJQ>- w
(.') u_J f'= z :, 0: -;j_ Cf) ci i5
SHEET ID
E-01
F
E
D
C
B
A
WALL MOUNTED NEMA 3R
LOADCENTER. SEE NOTE 4
POWER CABLE FROM 120/240V
POWER SOURCE IN CONDUIT.
SEE NOTES 1-3
POWER CABLE TO NEXT TARGET
EMPLACEMENT IN CONDUIT.
SEE NOTES 1-3.
2 3 4 5 6 7
SAT TAR GET ELEVATION
EQUIPMENT MOUNTED ON 1.625" DEEP
UNISTRUT. SEE NOTE 6.
NOTTO SCALE
TARGET POWER RECEPTACLE (TPR) 120/240V, 20A,
4 WIRE, TWIST LOCK (NEMA L 14-20R) WITH WET
LOCATION COVER IN WEATHERPROOF ENCLOSURE
SEE NOTES 4, 8, & 13.
GFCI MAINTENANCE RECEPTACLE (MR)
AND SINGLE POLE, SINGLE THROW, 120V
SWITCH IN WEATHERPROOF ENCLOSURE
WITH COVER. SEE NOTES 4 & 5.
RIGID METAL CONDUIT.
TYPICAL.
SINGLE GANG 2 5/8" DEEP WEATHERPROOF
BOX WITH WEATHERPROOF BLANK COVER
FOR USE BY TARGET VENDOR.
AUXILIARY POWER RECEPTACLE (APR), 120V, 20A,
3 WIRE, TWIST LOCK (NEMA L5-20R) IN
WEATHERPROOF ENCLOSURE WITH COVER. SEE
NOTES 4, 8, & 13.
CABLE SEAL FITTING
SEE NOTE 10
#6 AWG BARE COPPER
CONDUCTOR
#6 BARE COPPER CONDUCTOR
SEE NOTE 10
#6 AWG BARE COPPER CONDUCTOR, 10' COILED
ABOVE GROUND FOR BONDING TO FUTURE TARGET.
SEE NOTE 7.
LATCHED TYPE REMOVABLE LID.
CONTINUOUS HINGE WITH
RE MOVEABLE PIN. NEMA 4 TYPE
ENCLOSURE. SEE NOTES 4.
CONDUIT/CABLE SEAL FITTING.
SEE NOTE 18
EXISTING FIBER OPTIC CABLE
ENCLOSURE. SEE NOTE 19.
PANEL BOARD: SAT
XXXX MAIN
VOLTAGE: 240/120
LOAD SERVED
NO.
POLES
SURGE ARRESTOR 2
SPARE 1
SPACE
SPACE
SPACE
TOTAL VA PHASE A: 1375
TOTAL VA PHASE B: 1325
SAT TARGET ENLARGED ELECTRICAL EQUIPMENT ELEVATION SUPPLIED FROM: TRSF-XX
NOTTO SCALE
TRIP
AMPS
8 9 10
NOTES:
1. RE-USE EXISTING CABLES CONDUITS WITH POWER AND
DATA CABLES ENTERING EMPLACEMENT.
2. INSTALL NEW CONDUIT HUB WITH CABLE SEAL FITTING IN
NEW MTDP. SEE DETAIL ON E-07.
3. PROTECT POWER AND DATA CABLES DURING
REMOVAL/DEMOLITION OF EXISTING DATA ENCLOSURE
LOADCENTER. RE-TERMINATE DATA CABLES IN NEW
MTDP ENCLOSURE AND POWER CABLES IN NEW
LOADCENTER.
4. EQUIPMENT SHALL NOT BE MOUNTED HIGHER THAN 2"
FROM TOP OF EMPLACEMENT WALL.
5. POWER TO DATA PANEL RECEPTACLE IN MTDP SHALL BE
ROUTED THROUGH SINGLE POLE, SINGLE THROW SWITCH.
6. ALL EQUIPMENT SHALL BE MOUNTED ON 1.625" DEEP
UNISTRUT. NO EQUIPMENT SHALL BE PERMITTED TO BE
INSTALLED DIRECTLY TO CONCRETE WALL.
7. FOR FLANK TYPE SAT TARGET INCREASE THE LENGTH OF
GROUND CABLE TO 18 FT.
8. TPR, APR AND DPR SHALL NOT BE GFCI PROTECTED.
9. PERMANENTLY LABEL THE EMPLACEMENT ACCORDING TO
THE CIVIL AND ELECTRICAL DESIGNATIONS.
10. PROVIDE SEAL FITTINGS AS SHOWN IN DETAIL ON SHEET
E-07 FOR ALL CABLE PENETRATIONS TO NEMA 4, 4X, OR 6P
RATED ENCLOSURES.
11 . INSTALL MYERS TYPE HUBS ON ALL CONDUIT
PENETRATIONS TO SIDE OF ENCLOSURE.
12. ALL DIMENSIONS SHOWN IN INCHES UNLESS OTHERWISE
NOTED.
13. PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA
3R WET LOCATION COVERS MAKING OUTLETS SUITABLE
FOR USE IN WET LOCATIONS. SEE DETAIL SHEET E-07
FOR WET LOCATION COVER. IN USE COVERS WITH
COVERS INTENDED TO CLOSE OVER THE INSERTED CORD
ARE NOT ACCEPTABLE AS THESE COVERS WILL NOT
CLOSE OVER THE TARGET POWER OR AUXILIARY CORDS.
14. DEVIATIONS TO THE EQUIPMENT SIZES, EQUIPMENT
NUMBERS, RECEPTACLE COVERS, OR CABLE ENTRY
METHODS INTO ENCLOSURES WILL REQUIRE RANGE
TRAINING AND LAND PROGRAM HUNTSVILLE CENTER
MANDATORY CENTER OF EXPERTISE APPROVAL.
15. NOT USED.
16. SEE SHEET E-09 FOR ADDITIONAL INFORMATION ON
MASTER TARGET DATA PANELS.
17. MOUNT EQUIPMENT AS LOW AS POSSIBLE ON THE FRONT
WALL OF THE EMPLACEMENT. NO ELECTRICAL
EQUIPMENT SHALL BE INSTALLED WITHIN 2" OF THE TOP
OF THE EMPLACEMENT WALL.
18. CONDUIT/CABLE SEAL FITTING CONNECTION TO THE
MTDP. SEE CONDUIT/CABLE SEAL FITTING DETAIL ON
SHEET E-07.
19. EXISTING FIBER OPTIC CABLE ENCLOSURE. RE-USE
EXISTING ENCLOSURE. SEAL ALL OPENINGS WITH NEMA 4
RATED PLUGS. PROVIDE NEW CONDUIT INTO NEW MTDP
FOR TERMINATION OF EXISTING FIBER OPTIC CABLES
INSIDE NEW MTDP.
LOCATI ON: XXXXXXX MOUNTED: SURFACE FEED: BOTTOM
MAIN LUGS ONLY ASYM A.I.C MIN.: xxxxx
PHASE: 1 WIRE: 3 RATI NG: NEMA 3R
VA/ PHASE VA/ PHASE
WIRE
A B
CKT CKT
A B
WIRE TRIP NO.
LOAD SERVED SIZE NO. NO. SIZE AM PS POLES
--- 1325 SAT (NEMA L 14-20R, --- 1 2 12 20 2 2-NEMA L5-20R) --- 1325
--- --- 5 6 50 12 20 1 TDP AND MR
7 8 --- --- 20 1 SPARE
9 10 1 SPACE
11 12 1 SPACE
0 0 1375 1325
TOTAL CONNECTED WATTAGE: 2,700
TOTAL DEMAND AM PS: 11
US Army Corps of Engineers® u 0:
a.
f-<( e. w 0:
(9 ~ ~
Ou, z Cf) et:
8:~~ _J <{
~ f- OU(.') et:
'.'izffi ~ w 0 a, ;;: 0 ::;;
(.')a,<( _J et: ~5g: <{ <{ ~U w (.)
>-<ocn ir ~g~ f- et:
0 :,:0: (.) z ~~~ w 0 _J
UJQ>- w f'.= (.') u_J
~ z :, <(:,; Cf) 0: -;j_ ci i5
E-02
E
D
C
B
A
2 3
TARGET POWER RECEPTACLE (TPR) 120/240V,
20A, 4 WIRE, TWIST LOCK (NEMA L 14-20R) IN
WEATHERPROOF ENCLOSURE WITH WET
LOCATION COVERS. SEE NOTES 4, 7, & 14.
WALL MOUNTED NEMA 3R LOAD
CENTER. SEE NOTE 4.
RIGID METAL CONDUIT
TYPICAL
EMPLACEMENT WALL
POWER CABLE FROM
120/240V POWER
SOURCE IN CONDUIT.
SEE NOTES 1-3.
2"
MIN
5"
MIN
POWER CABLE IN
CONDUIT TO NEXT
TARGET PIT.
SEE NOTES 1-3.
SEE NOTE 8
4 5
GFCI MAINTENANCE RECEPTACLE (MR)
AND SINGLE POLE, SINGLE THROW, 120V
SWITCH IN WEATHERPROOF ENCLOSURE
WITH COVER. SEE NOTE 5.
EQUIPMENT MOUNTED ON 1.625" DEEP
UNISTRUT. SEE NOTE 6.
2" MIN
SEE NOTE 11 SEE NOTE 9
SINGLE GANG 2 5/8" DEEP WEATHERPROOF
BOX WiTH WEATHERPROOF BLANK COVER
FOR USE BY TARGET VENDOR.
AUXILIARY POWER RECEPTACLE (APR)
120V, 20A, 3 WIRE, TWIST LOCK (NEMA L5-20R)
WITH WET LOCATION COVER IN WEATHERPROOF
#6 AWG BARE ENCLOSUl'tE. SEE NOTES 4, 7, & 14.
COPPER CONDUCTOR ~-----------------~
#6 AWG BARE COPPER CONDUCTOR.
SEE NOTE 18.
#6 AWG BARE COPPER CONDUCTOR
10' COILED ABOVE GROUND FOR
BONDING TO FUTURE TARGET
CONDUIT WITH DATA CABLES
AS SHOWN ON THE RISER DIAGRAM.
SEE NOTES 1-3, 9, & 16.
ELEVATION
6 7
DATA POWER RECEPTACLE (DPR)
LOCATED INSIDE ENCLOSURE.
SEE NOTE 7. RECEPTACLE NOT
SHOWN FOR CLARITY.
78" MAX. SEE NOTE 10.
AREA FOR ELECTRICAL
EQUIPMENT
5"
MIN
LATCHED TYPE REMOVABLE
LID. CONTINUOUS HINGE WITH
REMOVABLE PIN. NEMA 4.
SEE NOTES 4 & 6.
CONDUIT/CABLE SEAL FITTING.
SEE NOTE 13
ELECTRICAL BLOCKOUT TYPICAL OF 2.
SEE CIVIL DETAILS FOR EXACT PLACEMENT.
MOVING INFANTRY TARGET
NOTTO SCALE
NOTES:
1. CONDUIT TO EXTEND 5 FEET BEYOND EMPLACEMENT. 12.
2. CABLES/CONDUITS ARE ROUTED FROM SIDE OF BERM TO
PREVENT CABLE DAMAGE DURING MAINTENANCE OF 13.
PANEL BOARD: MIT LOCATI ON: XXXXXXX MOUNTED: SURFACE FEED: BOTTOM
BERM.
3. ROUTE UNDER SLAB. POWER AND DATA INSTALLED IN
125 MAIN MAIN LUGS ONLY ASYM A.I.C MIN .. 10,000 SAME TRENCH. 14.
VOLTAGE: 2401120 PHASE: 1 WIRE: 3 RATI NG: NEMA3R 4. EQUIPMENT SHALL NOT BE MOUNTED HIGHER THAN 2" VAi PHASE VAi PHASE FROM TOP OF EMPLACEMENT WALL.
LOAD SERVED
NO. TRIP WIRE
A B
CKT CKT
A B
WIRE TRIP NO.
LOAD SERVED POLES AM PS SIZE NO. NO. SIZE AM PS POLES 5. POWER TO DATA PANEL RECEPTACLE IN MTDP SHALL BE
ROUTED THROUGH SINGLE POLE SINGLE THROW SWITCH.
SURGE ARRESTOR
--- 1000 MIT (NEMA L 14-20R &
2 ---- --- 1 2 12 20 2 NEMA L5-20R) --- 1000 6. ALL EQUIPMENT SHALL BE MOUNTED ON 1.625" DEEP 15.
UNISTRUT. NO EQUIPMENT SHALL BE PERMITTED TO BE
SPARE 1 20 --- --- 5 6 50 12 20 1 TDP AND MR INSTALLED DIRECTLY TO CONCRETE WALL.
SPACE 7 8 --- --- 20 1 SPARE
SPACE 9 10 1 SPACE
7. TPR, APR AND DPR SHALL NOT BE GFCI PROTECTED.
SPACE 11 12 1 SPACE
0 0 1050 1000
8. PERMANENTLY LABEL THE EMPLACEMENT ACCORDING TO 16.
THE CIVIL AND ELECTRICAL DESIGNATIONS.
TOTAL VA PHASE A: 1050 9. PROVIDE SEAL FITTINGS AS SHOWN IN DETAIL ON SHEET 17.
TOTAL VA PHASE B: 1000
TOTAL CONNECTED WATTAG E: 2,050
E-07 FOR ALL CABLE PENETRATIONS TO NEMA 4, 4X, OR 6P
RATED ENCLOSURES.
18.
- 10. INSTALL POWER AND DATA ON THE FIRST 78" OF THE
SUPPLIED FROM : TRSF-XX TOTAL DEMAND AM PS: 9
- FRONT WALL CLOSEST TO THE DIRECTION OF FIRE.
11. INSTALL MYERS TYPE HUBS ON ALL CONDUIT
PENETRATIONS INTO THE SIDE OF THE DATA ENCLOSURE.
8 9
ALL DIMENSIONS SHOWN IN INCHES UNLESS OTHERWISE
NOTED.
CONDUIT/CABLE SEAL FITTING CONNECTION TO THE
MTDP. SEE CONDUIT/CABLE SEAL FITTING DETAIL ON
SHEET E-07.
PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA
3R WET LOCATION COVERS MAKING OUTLETS SUITABLE
FOR USE IN WET LOCATIONS. SEE DETAIL SHEET E-07
FOR WET LOCATION COVER. IN USE COVERS WITH
COVERS INTENDED TO CLOSE OVER THE INSERTED CORD
ARE NOT ACCEPTABLE AS THESE COVERS WILL NOT
CLOSE OVER THE TARGET POWER OR AUXILIARY CORDS.
DEVIATIONS TO THE EQUIPMENT SIZES, EQUIPMENT
NUMBERS, RECEPTACLE COVERS, OR CABLE ENTRY
METHODS INTO ENCLOSURES WILL REQUIRE RANGE
TRAINING LAND PROGRAM, HUNTSVILLE CENTER
MANDA TORY CENTER OF EXPERTISE APPROVAL.
STUB UP CONDUIT AS CLOSE AS PRACTICAL TO CABLE
FITTING.
SEE SHEET E-09 FOR ADDITIONAL INFORMATION ON
MASTER TARGET DATA PANELS.
PROVIDE GROUNDING IN ACCORDANCE WITH
EMPLACEMENT GROUNDING DETAIL ON SHEET E-07.
US Army Corps of Engineers® u 0:
a.
<( e. f- 0: w w "' "'"' (!) Cf) Ow z
8:~~ a:: _J
O<.lc,i ~ ~ '.'izffi ~ >- w a, ;;: a:: Cl C)a,<( f- _J
~5g: z ~ ~U w ~ (.)
<ocn u. ir ~g~ ~ f- 0 :,:0: (!) (.)
~~~ z w > _J
WQ>- w C) u_J 0 z :, :,; <(:,;
0: 'ii.
ci i5
E-03
E
D
C
B
A
2 3 4
SEEN 19
PARTIAL MAT TARGET ELEVATION
NOTTO SCALE
NOTES:
1. CONDUIT TO EXTEND 5 FEET BEYOND EMPLACEMENT.
2. CABLES/CONDUITS ARE ROUTED FROM SIDE OF BERM TO
PREVENT CABLE DAMAGE DURING MAINTENANCE OF
BERM.
3. ROUTE UNDER SLAB. POWER AND DATA INSTALLED IN
SAME TRENCH.
4. EQUIPMENT SHALL NOT BE MOUNTED HIGHER THAN 2"
FROM TOP OF EMPLACEMENT WALL.
5. POWER TO DATA PANEL RECEPTACLE IN MTDP SHALL BE
ROUTED THROUGH SIGN LE POLE, SINGLE THROW
SWITCH.
6. ALL EQUIPMENT SHALL BE MOUNTED ON 1.625" DEEP
UNISTRUT. NO EQUIPMENT SHALL BE PERMITTED TO BE
INSTALLED DIRECTLY TO THE CONCRETE WALL.
7. NOTUSED.
8. TPR, APR AND DPR SHALL NOT BE GFCI PROTECTED.
9. PERMANENTLY LABEL THE EMPLACEMENT ACCORDING TO
THE CIVIL AND ELECTRICAL DESIGNATIONS.
10. PROVIDE SEAL FITTINGS AS SHOWN IN DETAIL ON SHEET
E-07 FOR ALL CABLE PENETRATIONS TO NEMA 4, 4X, OR 6P
RATED ENCLOSURES.
11 . INSTALL MYERS TYPE HUBS ON ALL CONDUIT
PENETRATIONS TO SIDE OF ENCLOSURE.
12. ALL DIMENSIONS SHOWN IN INCHES UNLESS OTHERWISE
NOTED.
13. IF TARGET IS BATTERY OPERATED WITH NO AC POWER
PROVIDED, THE TARGET GROUND ROD SHALL BE
INSTALLED WITH A 15' COILED #1 /0 AWG BARE COPPER
GROUND CABLE FOR FUTURE BONDING TO THE TARGET
MECHANISM.
14. PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA
3R WET LOCATION COVERS MAKING OUTLETS SUITABLE
FOR USE IN WET LOCATIONS. SEE DETAIL SHEET E-07
FOR WET LOCATION COVER. IN USE COVERS WITH
COVERS INTENDED TO CLOSE OVER THE INSERTED CORD
ARE NOT ACCEPTABLE AS THESE COVERS WILL NOT
CLOSE OVER THE TARGET POWER OR AUXILIARY CORDS.
15. DEVIATIONS TO THE EQUIPMENT SIZES, EQUIPMENT
NUMBERS, RECEPTACLE COVERS, OR CABLE ENTRY
METHODS INTO ENCLOSURES WILL REQUIRE RANGE
TRAINING AND LAND PROGRAM HUNTSVILLE CENTER
MANDATORY CENTER OF EXPERTISE APPROVAL.
16. CONDUIT STUBBED UP AS CLOSE TO CABLE SEAL FITTING
AS POSSIBLE.
17. EQUIPMENT IS SHOWN AT THE PREFERRED MOUNTING
HEIGHT. UNDER NO CIRCUMSTANCE SHOULD ANY
EQUIPMENT BE INSTALLED SUCH THAT THE TOP OF THE
EQUIPMENT IS LESS THAN 2" FROM THE TOP OF THE
EMPLACEMENT WALL.
18. SEE SHEET E-09 FOR ADDITIONAL INFORMATION ON
MASTER TARGET DATA PANELS.
19. INSTALL NEW TARGET EQUIPMENT APPROXIMATELY 20 FT
FROM EXISTING MAT EQUIPMENT AND POWER CENTER
EQUIPMENT. EXTEND POWER AND DATA FROM POWER
CENTER DISTRIBUTION PANEL AND FIBER PATCH PANEL IN
PVC CONDUIT.
5 6 7
PANEL BOARD: MAT
235 MAIN
VOLTAGE: 240/120
LOAD SERVED
NO.
POLES
SURGE ARRESTOR 2
SPARE 1
SPACE
SPACE
SPACE
TOTAL VA PHASE A: 1950
TOTAL VA PHASE B: 1900
SUPPLIED FROM : TRSF-XX
#6 AWG BARE COPPER
CONDUCTOR
#1 /0 AWG BARE COPPER
CONDUCTOR EXOTHERMIC
WELD TO GROUND ROD
TARGET GROUND ROD
8 9 10
LOCATION: XXXXXXX MOUNTED: SURFACE FEED: BOTTOM
MAIN LUGS ONLY ASYM A. I.C MIN .. 10,000
PHASE: 1 WIRE: 3 RATING: NEMA3R
VA/ PHASE VA/ PHASE
TRIP WIRE
A B
CKT CKT
A B
WIRE TRIP NO.
LOAD SERVED AMPS SIZE NO. NO. SIZE AMPS POLES
--- 1900 MAT (NEMA L 14-20R,
---- --- 1 2 12 20 2 2-NEMA L5-20R) --- 1900
20 --- --- 5 6 50 12 20 1 TDPAND MR
7 8 --- --- 20 1 SPARE
9 10 1 SPACE
11 12 1 SPACE
0 0 1950 1900
TOTAL CONNECTED WATTAG E: 3,850
TOTAL DEMAND AMPS: 16
NEMA 3R
LOADCENTER
NEMA 4 MTDP / TDP
#1 /0 AWG BARE COPPER
CONDUCTOR, 15' COILED
ABOVE GROUND FOR
BONDING TO FUTURE
TARGET TRACK
PROVIDE CABLE SEAL FITTING FOR
GROUND CABLE PENETRATION
INTO DATA ENCLOSURE
GROUND ROD FOR TARGET TRACK
INSTALL 30 FT FROM MTDP.
#1/0 AWG BARE COPPER CONDUCTOR.
SEE EMPLACEMENT GROUNDING DETAIL.
EMPLACEMENT GROUNDING DETAIL
EQUIPMENT MOUNTED ON 1.625"
DEEP UNISTRUT. SEE NOTE 6.
NOTTO SCALE
TARGET POWER RECEPTACLE (TPR) 120/240V, 20A,
~tc!~fi'ci~b~v~ic~N<~i~~~~t~i~o111~~7}suRE.
AUXILIARY POWER RECEPTACLE (APR) 120V, 20A, 3 WIRE,
TWIST LOCK (NEMA L5-20R) WITH WET LOCATION COVER
IN WEATHERPROOF ENCLOSURE. SEE NOTES 4 & 14.
SEE NOTES 4 & 14.
SEE NOTE 9
SINGLE POLE, SINGLE THROW, 120V
SWITCH IN WEATHERPROOF ENCLOSURE
WITH COVER. SEE NOTES 4 & 5
SINGLE GANG 2 5/8" DEEP WEATHERPROOF
RIGID METAL CONDUIT ~g~ t1'~1HB'¢'t!W,ilf~i?N°cioiLANK covER
(TYPICAL)
GFCI MAINTENANCE RECEPTACLE (MR) IN
WEATHERPROOF ENCLOSURE WITH COVER
WALL MOUNTED NEMA 34
LOADCENTER. SEE NOTE 4.
#6 BARE COPPER
CONDUCTOR
#6 BARE COPPER CONDUCTOR
SEE NOTE 10
CONDUIT WITH ARMORED DATA CABLES.
SEE NOTES 1-3, 10, & 16
DATA POWER RECEPTACLE (DPR) LOCATED
INSIDE PANEL. SEE NOTE 9. RECEPTACLE
NOT SHOWN FOR CLARITY.
MAT TARGET ENLARGED ELECTRICAL EQUIPMENT ELEVATION
NOTTO SCALE
US Army Corps of Engineers® u 0:
a.
<( e.
0: f- (9 ~ ~
Cf) w Ou,z
8:~~ _J <:)
ll'.
OU(.') j::
'.'izffi~ w a,;;: 0 ll'.
(.')a,<( _J 0 ~5g: -,: :,;
~Uw (.) ll'.
<ocn ir -,:
~g~ f- <:)
0:,:0: (.) z ~~~ w > _J
UJQ>- w 0 (.')u_J :,; z :, 0: 'ii.
ci i5
E-04
E
D
C
B
A
2 3
SIT CLUSTER DATA OUTLETS.
SEE NOTE 15.
SINGLE POLE, SINGLE THROW, 120V
SWITCH IN WEATHERPROOF ENCLOSURE
WITH COVER. SEE NOTES 4 & 5.
GFCI MAINTENANCE RECEPTACLE (MR) IN
WEATHERPROOF ENCLOSURE WITH COVER
EQUIPMENT MOUNTED ON 1.625" DEEP
UNISTRUT. SEE NOTE 6.
WALL MOUNTED NEMA 3R
LOADCENTER. SEE NOTE 4
POWER CABLE FROM 120/240V
POWER SOURCE IN CONDUIT.
SEE NOTES 1-3
SAT EMPLACEMENT
POWER AND DATA
OUTLETS.
SEE NOTE 15.
SIT CLUSTER POWER OUTLETS.
SEE NOTE 15.
SAT EMPLACEMENT
ELECTRICAL EQUIPMENT
STATIONARY ARMOR TARGET ELEVATION
RIGID METAL CONDUIT.
TYPICAL
NOTTO SCALE
TARGET DATA PANEL (TDP) 2" CONDUIT
6 7
SIT CLUSTER POWER OUTLETS.
SEE NOTE 15.
SIT CLUSTER DA TA OUTLETS.
SEE NOTE 15.
MASTER TARGET DATA PANEL (MTDP)
LATCHED TYPE REMOVABLE LID.
CONTINUOUS HINGE WITH
RE MOVEABLE PIN. NEMA 4 TYPE
ENCLOSURE. SEE NOTES 4.
DATA POWER RECEPTACLE (DPR) LOCATED
INSIDE PANEL. RECEPTACL~
NOT SHOWN FOR CLARITY.
CONDUIT/CABLE SEAL FITTING.
SEE NOTE 18
8 9 10
NOTES:
1. RE-USE EXISTING CABLES CONDUITS WITH POWER AND
DATA CABLES ENTERING EMPLACEMENT.
2. INSTALL NEW CONDUIT HUB WITH CABLE SEAL FITTING IN
NEW MTDP. SEE DETAIL ON E-07.
3. PROTECT POWER AND DATA CABLES DURING
REMOVAL/DEMOLITION OF EXISTING DATA ENCLOSURE
LOADCENTER. RE-TERMINATE DATA CABLES IN NEW
MTDP ENCLOSURE AND POWER CABLES IN NEW
LOADCENTER.
4. EQUIPMENT SHALL NOT BE MOUNTED HIGHER THAN 2"
FROM TOP OF EMPLACEMENT WALL.
5. POWER TO DATA PANEL RECEPTACLE IN MTDP SHALL BE
ROUTED THROUGH SINGLE POLE, SINGLE THROW SWITCH.
6. ALL EQUIPMENT SHALL BE MOUNTED ON 1.625" DEEP
UNISTRUT. NO EQUIPMENT SHALL BE PERMITTED TO BE
INSTALLED DIRECTLY TO CONCRETE WALL.
7. FOR FLANK TYPE SAT TARGET INCREASE THE LENGTH OF
GROUND CABLE TO 18 FT.
8. TPR, APR AND DPR SHALL NOT BE GFCI PROTECTED.
9. PERMANENTLY LABEL THE EMPLACEMENT ACCORDING TO
THE CIVIL AND ELECTRICAL DESIGNATIONS.
10. PROVIDE SEAL FITTINGS AS SHOWN IN DETAIL ON SHEET
E-07 FOR ALL CABLE PENETRATIONS TO NEMA 4, 4X, OR 6P
RATED ENCLOSURES.
11 . INSTALL MYERS TYPE HUBS ON ALL CONDUIT
PENETRATIONS TO SIDE OF ENCLOSURE.
12. ALL DIMENSIONS SHOWN IN INCHES UNLESS OTHERWISE
NOTED.
13. PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA
3R WET LOCATION COVERS MAKING OUTLETS SUITABLE
FOR USE IN WET LOCATIONS. SEE DETAIL SHEET E-07
FOR WET LOCATION COVER. IN USE COVERS WITH
COVERS INTENDED TO CLOSE OVER THE INSERTED CORD
ARE NOT ACCEPTABLE AS THESE COVERS WILL NOT
CLOSE OVER THE TARGET POWER OR AUXILIARY CORDS.
14. DEVIATIONS TO THE EQUIPMENT SIZES, EQUIPMENT
NUMBERS, RECEPTACLE COVERS, OR CABLE ENTRY
METHODS INTO ENCLOSURES WILL REQUIRE RANGE
TRAINING AND LAND PROGRAM HUNTSVILLE CENTER
MANDATORY CENTER OF EXPERTISE APPROVAL.
15. SEE SHEET E-06 FOR DETAILS ON SAT POWER AND DATA
OUTLETS, SIT POWER OUTLETS, AND SIT DATA OUTLETS.
16. SEE SHEET E-09 FOR ADDITIONAL INFORMATION ON
MASTER TARGET DATA PANELS.
17. MOUNT EQUIPMENT AS LOW AS POSSIBLE ON THE FRONT
WALL OF THE EMPLACEMENT. NO ELECTRICAL
EQUIPMENT SHALL BE INSTALLED WITHIN 2" OF THE TOP
OF THE EMPLACEMENT WALL.
18. CONDUIT/CABLE SEAL FITTING CONNECTION TO THE
MTDP. SEE CONDUIT/CABLE SEAL FITTING DETAIL ON
SHEET E-07.
19. EXISTING FIBER OPTIC CABLE ENCLOSURE. RE-USE
EXISTING ENCLOSURE. SEAL ALL OPENINGS WITH NEMA 4
RATED PLUGS. PROVIDE NEW CONDUIT INTO NEW MTDP
FOR TERMINATION OF EXISTING FIBER OPTIC CABLES
INSIDE NEW MTDP.
CONDUIT/CABLE SEAL FITTING.
SEE NOTE 18 PANEL BOARD: SAT-SIT CLUSTERLOCATI ON: XXXXXXX MOUNTED: SURFACE FEED: BOTTOM
POWER CABLE TO NEXT TARGET
EMPLACEMENT IN CONDUIT.
SEE NOTES 1-3.
WIRE GUTTER, SIZE PER NUMBER AND
SIZE OF CONDUCTORS IN EACH EMPLACEMENT
#6 AWG BARE COPPER CONDUCTOR, 1 O' COILED
ABOVE GROUND FOR BONDING TO FUTURE TARGET.
SEE NOTE 7.
CONDUIT FOR POWER TO LOAD
CENTER
CONDUIT FOR POWER TO EMPLACEMENT
POWER OUTLETS
#6 BARE COPPER CONDUCTOR
SEE NOTE 10
STATIONARY ARMOR TARGET
ELECTRICAL EQUIPMENT ELEVATION
NOTTO SCALE
CABLE SEAL FITTING.
SEE NOTE 10
#6 BARE COPPER CONDUCTOR
SEE NOTE 10
EXISTING FIBER OPTIC CABLE
ENCLOSURE. SEE NOTE 19.
125 MAIN
VOLTAGE: 240/120
LOAD SERVED
NO.
POLES
SURGE ARRESTOR 2
2-SITS(2-NEMA L 14-20R,
2-NEMA L5-20R) 2
2-SITS(2-NEMA L 14-20R,
2-NEMA L5-20R) 2
TOTAL VA PHASE A: 2951
TOTAL VA PHASE B: 2901
SUPPLIED FROM: TRSF-XX
MAIN LUGS ONLY
PHASE: 1 WIRE: 3
VA/ PHASE
TRIP WIRE
A B
CKT
AM PS SIZE NO.
---- --- 1 ...
20 12 788 5
788 7 788 9
20 12 788 11
1576 1576
ASYM A.I.C MIN. : 10,000
RATI NG: NEMA3R
VA/ PHASE
CKT
A B
WIRE TRIP NO.
LOAD SERVED NO. SIZE AM PS POLES
1325 SAT (NEMA L 14-20R,
2 12 20 2 2-NEMA L5-20R) 1325
6 50 12 20 1 TDPAND MR
8 ... ... 20 1 SPARE
10 ... ... 20 1 SPARE
12 1 SPAC E
1375 1325
TOTAL CONNECTED WATTAGE: 5,852
TOTAL DEMAND AM PS: 24
US Army Corps of Engineers® a::
lJ.J f-u (/)
0: I-' (l_ f- 0 :,; :,;
~ t;; <( e.
0:
(9 ~ ~ Cl) tij (9 Ou, z ..J(!)a::
8:~~ ;;: a::;::
OU(.') f- <( >- '.'izffi ~ lJ.J f- a::
a, ;;: 0 a:: f- (.')a,<( -'OZ ~5g: <( ::;; <( ~ U w Ua::u..
<ocn ii' <(~ ~g~ f- >- >- 0 :,:0: U a::a::
UJQ>- woo (.') u_J z :, i= i= <(:,;
0: -;j_ ;:: ;::
ci z i5 <(
E-05
F
E
D
C
B
A
I 2
FOR USE BY TARGET VENDOR. SEE NOTE 1. ..,
SINGLE GANG 2 5/8" DEEP WEATHERPROOF ~
BOX WITH WEATHERPROOF BLANK COVER
I 3 I 4 I 5
AUXILIARY POWER RECEPTACLE (APR), 120V, 20A, ~
3 WIRE, TWIST LOCK (NEMA L5-20R) IN '.
WEATHERPROOF ENCLOSURE WITH COVER. SEE
NOTES 2, 3, AND 4.
TARGET POWER RECEPTACLE (TPR\ 120/240V, 20A,
4 WIRE, TWIST LOCK (NEMA L 14-20R WITH WET
LOCATION COVER IN WEATHERPROOF ENCLOSURE
SEE NOTES 2, 3, AND 4 .
I 6
STATIONARY INFANTRY TARGET
CLUSTER DATA OUTLETS ELEVATION
STATIONARY INFANTRY TARGET
CLUSTER POWER OUTLETS ELEVATION
NOTTO SCALE
PROVIDED THIS CONTRACT + PROVIDED BY TARGET CONTRACT
,-= ____ ;__ __ ,-::::::~:c---;;~ 0 0 • ----Q)
SINGLE GANG, DEEP,
WEATHERPROOF
OUTLET BOX
Q)
L----
SEALING GASKET WEATHERPROOF AMPHENOL AMPHENOL
COVER JE18 RJF21G
GASKET ETHERNET
NOTES:
CONNECTOR
1. CONSTRUCTION CONTRACTOR TO PROVIDE BLANK
WEATHERPROOF COVER. ALL OPENINGS IN COVER FOR
WEAHTERPROOF DATA CONNECTOR WILL BE DONE BY
THE TARGET VENDOR DURING THE TARGET
INSTALLATION.
DATA OUTLET RESPONSIBILITY
REFERENCE DETAIL
NOTTO SCALE
AMPHENOL
RJFC6G
OUTLET CAP
NOTTO SCALE
I 7 I 8 I 9 I 10
FOR USE BY TARGET VENDOR. SEE NOTE 1. ..,
SINGLE GANG 2 5/8" DEEP WEATHERPROOF ~
BOX WITH WEATHERPROOF BLANK COVER
i • r AUXILIARY POWER RECEPTACLE (APR), 120V, 20A, 3 WIRE, TWIST LOCK (NEMA L5-20R) IN
WEATHERPROOF ENCLOSURE WITH COVER. SEE
NOTES 2, 3, AND 4.
TARGET POWER RECEPTACLE (TPR) 120/240V, 20A,
4 WIRE, TWIST LOCK (NEMA L 14-20R) WITH WET
LOCATION COVER IN WEATHERPROOF ENCLOSURE
SEE NOTES 2, 3, AND 4.
STATIONARY ARMOR TARGET
POWER AND DATA OUTLETS ELEVATION
NOTTO SCALE
NOTES:
1.
2.
TARGET DATA OUTLET SHALL HAVE 6" -12" OF CAT 6
CABLE COILED AND TERMINATED WITH A MAIL RJ-45
CONNECTOR. INSTALL SEALING GASKET AND
WEATHERPROOF COVER. ALL OTHER DATA OUTLET
RQUIREMENTS WILL BE INSTALLED BY TARGET VENDOR
UNDER A SEPER.ATE COTRACT. SEE DATA OUTLET
RESPONSIBILITY REFERENCE DETAIL FOR MORE
INFORMATION ON HOW DATA OUTLET WILL BE INSTALLED.
ALL OUTLETS SHALL BE MOUNTED ON THE EMPLACEMENT
WALL AS LOW AS POSSIBLE. UNDER NO CIRCUMSTANCE
SHALL THE OUTLETS BE INSTALLED WITHIN 2" FROM THE
TOP OF THE EMPLACEMENT WALL.
3. TARGET POWER OUTLETS AND AUXILIARY POWER
OUTLETS SHALL NOT BE GFCI PROTECTED.
4. PROVIDE TARGET AND AUXILIARY OUTLETS WITH NEMA 3R
WET LOCATION COVERS MAKING OUTLETS SUITABLE FOR
USE IN WET LOCATIONS. SEE DETAIL SHEET E-07 FOR
WET LOCATION COVER. IN USE COVERS WITH COVERS
INTENDED TO CLOSE OVER THE INSERTED CORD ARE NOT
ACCEPTABLE AS THESE COVERS WILL NOT CLOSE OVER
THE TARGET POWER OR AUXILIARY CORDS.
US Army Corps of Engineers®
<I)"' "'w w >w z z w
- u ~ b:
0 Q.
<I) <I) Q.
"'°" 8 <!)
:, "' "'w <I) 0 u 0:
Q.
< e.
0:
(9 ~ ~ Owz
8:~~
OU<!)
'.'izffi~ a,,::
"'"'" ~5g:
~Uw «o<ll ~g~ 0:,:0:
WQ>-
<!Ju.J z ::, 0: -;j_ i5
-w N U) a::
lJ.J f-
I -' f- 0
~t;;
Cl) tij (9 _J (!) a::
;;:a::;::
f- <( >-lJ.J f- a::
0 a:: f- -'Oz <( ::;; <( Ua::u._ ii'<(~ f- >- >-Ua::a::
~~~ woo i= i= ;::;::
z
E-06
E
D
C
B
A
WEATHERPROOF EXTERIOR
ENCLOSURE
2 3
LID SPRINGS CLOSED
WHEN PLUG NOT
INSERTED
RUBBER GASKET
NOTE:
WEATHERPROOF, IN-USE WET LOCATION COVERS SHALL BE PROVIDED
WITH ETHYLENE PROPYLENE RUBBER GASKETS AROUND THE FACE OF
THE RECEPTACLE TO PREVENT THE ENTRANCE OF MOISTURE AND DIRT
WITH COVER OPEN AND PLUG INSERTED. COVER SHALL ACCEPT MALE
PLUG WITH DIAMETER OF 1.8" - 1.95".
WET LOCATION RECEPTACLE COVER
NOTTO SCALE
NEMA3R
LOADCENTER
NEMA 4 MTDP / TDP
LOCKNUT
BOTTOM OF
DATA ENCLOSURE
CABLE SEAL FITTING
MAIN BODY
NEOPRENE BUSHING
CABLE SEAL FITTING
GLAND NUT
CONDUIT
PROVIDE CABLE SEAL FITTING
#6 AWG BARE COPPER
CONDUCTOR EXOTHERMIC
WELD TO GROUND ROD
TARGET GROUND ROD
NOTE:
FOR GROUND CABLE PENETRATION
INTO DATA ENCLOSURE
#6 AWG BARE COPPER CONDUCTOR,
10' (FOR MITS AND SATS)AND 6' (FOR
SITS) COILED ABOVE GROUND FOR
BONDING TO FUTURE TARGET
THIS DETAIL DEPICTS GROUNDING REQUIREMENTS FOR SITS, SATS,
AND MITS. SEE SHEET E-4 FOR MAT GROUNDING DETAIL.
EMPLACEMENT GROUNDING DETAIL
NOTTO SCALE
5 6 7
CABLE SEAL FITTING DETAIL
NOTTO SCALE
8 9 10
EXISTING FIBER OPTIC CABLE
CABLE SEAL FITTING
GLAND NUT
NEOPRENE BUSHING
CABLE SEAL FITTING
MAIN BODY
BOTTOM OF DATA ENCLOSURE
THREADED REDUCING BUSHING AS
NEEDED TO REDUCE CONDUIT SIZE
TO CABLE SEAL FITTING SIZE
(NOT SHOWN)
RIGID COUPLING
EXISTING CONDUIT
CONDUIT/ CABLE SEAL FITTING DETAIL
NOTTO SCALE
US Army Corps of Engineers® u 0:
a. f-:,; :,; z
<( e. w 0:
(9 ~ ~
Ou,z w Cf)
8:~~ (.) _J
<{ ~ OU(.') _J
'.'izffi~ CL w a,;;:
:;; Cl (.')a,<( w _J
~5g: f- <{ ~Uw w (.)
<ocn (!) ir ~g~ a:: f- 0:,:0: ~ (.)
~~~ w _J _J
UJQ>- <{ w (.')u_J (.)
z :, a: <(:,;
0: "ii. >-f-ci i5
E-07
E
D
C
B
A
2 3 4 5 6
TYPICAL MASTER TARGET DATA PANEL (MTDP) DETAIL AT TARGET EMPLACEMENT
NOTTO SCALE
KEYED NOTES REPRESENTED WITH@:
1. ENCLOSURE SHALL BE 16 GAUGE MINIMUM GALVANIZED STEEL SHEET METAL WITH
WALL MOUNT BRACKETS. ENCLOSURE SHALL CARRY A NEMA 4 RATING AND BE
TESTED BY UL OR OTHER APPROVED TESTING AGENCY.
2. PROVIDE ENCLOSURE WITH FAST OPERATING CLAMP ASSEMBLY. BOLT TYPE CLAMPS
ARE NOT ACCEPTABLE.
3. INJECTION-MOLDED PLASTIC CONNECTOR 12 PORT PATCH PANEL.
4. METAL BACK PLATE TO SECURE COMPONENTS INSIDE ENCLOSURE.
5. 6-STRAND ARMORED TYPE FIBER OPTIC CABLE(S) WITH CENTRAL STRENGTH
MEMBER. SECURE FIBER OPTIC CABLE CENTRAL MEMBER INSIDE MTDP ENCLOSURE.
6. METALLIC CABLE SHEATH GROUNDING CLAMP AND GROUNDING CONNECTOR, BOND
CABLE ARMOR/SHIELD TO MTDP BACK PLATE GROUNDING BAR. ALL GROUND CABLES
NOT SHOWN FOR CLARITY.
7. CENTRAL MEMBER STRAIN-RELIEF BRACKET.
8. GROUND BAR - SECURE TO METAL BACK PLATE.
9. #6 AWG BARE COPPER GROUNDING CONDUCTOR.
10. DATA PANEL RECEPTACLE (DPR)- 20 AMP, 125 VOLT, 2 POLE, 3 WIRE GROUNDING
TYPE IN A STANDARD SINGLE-GANG METAL BOX AND GALVANIZED STEEL DEVICE
PLATE. CONNECT DPR AHEAD OF GFCI MAINTENANCE RECEPTACLE TO AVOID
NUISANCE TRIPPING.
11. 2/C #12 WITH GROUND CORD IN CONDUIT FROM CIRCUIT BREAKER LOADCENTER FOR
120 VOLT, 1-PHASE SERVICE TO DUPLEX RECEPTACLE. RECEPTACLE SHALL NOT BE
FED FROM ANY GROUND FAULT INTERRUPTING DEVICE.
12. FIELD INSTALLABLE "SC" CONNECTORS WITH BEND PROTECTOR. ALL CONNECTORS
NOT SHOWN FOR CLARITY.
13. FIBER OPTIC CABLE BUFFER TUBES WITH 6-STRANDS OF FIBER, EACH. PROVIDE 2'
SLACK EACH END.
14. NOT USED.
15. WALL MOUNTED SINGLE PANEL HOUSING FOR FIBER OPTIC CABLE TERMINATIONS.
FIBER OPTIC BUFFER TUBE SLACK AND FAN OUT KIT SHALL BE CONTAINED WITHIN
HOUSING. HOUSING SHALL BE COMPATIBLE WITH 12 PORT PATCH PANEL.
16. NOT USED.
17. PROVIDE MYERS HUB TYPE FITTING AT CONDUIT PENETRATION.
18. MTDP SHALL HAVE A ROLLED FLANGE AROUND PERIMETER OF OPENING.
19. PROVIDE ONE CABLE SEAL FITTING FOR EACH CABLE. SEE TYPICAL CABLE SEAL
FITTING DETAIL ON SHEET E-07.
20. EXISTING CONDUIT FOR FIBER OPTIC CABLES.
21 . CONDUIT/CABLE SEAL FITTING CONNECTION TO THE MTDP. SEE CONDUIT/CABLE
SEAL FITTING DETAIL ON SHEET E-07.
22. HINGED COVER WITH CORROSION - RESISTANT STAINLESS STEEL CAPTIVE CLAMPS.
HINGE MUST HAVE REMOVABLE PIN. PROVIDE A SEAMLESS FOAM-IN-PLACE GASKET
FOR A WATERTIGHT AND DUST TIGHT SEAL.
23. FIBER OPTIC FAN-OUT KIT OR SPLICE KIT WITH PIGTAILS.
24. PROVIDE 14" X 10" SPACE FOR INSTALLATION OF TARGET COMMUNICATIONS
EQUIPMENT. POWER OUTLET AND GROUND LUG ARE ONLY COMPONENTS INSTALLED
IN THIS SPACE THAT IS NOT BY THE TARGET VENDOR. AREA MEASURED FROM SIDE
OF ENCLOSURE NOT EDGE OF BACKPLATE.
7 8 9
MASTER TARGET DATA PANEL
(MTDP)
- - - - - - - - - - - - - - - - - - - - - - - - - .£""® -I
, MTDP BACKPLATE
~~-----------7 ~@~ ' I ~~ I
~-c=J ___ _
-c::J ,-~J
~i- ---------- _I tj ETHERNET
I SWITCH
GROUND
LUGS
mm d I d I
1-d L ___ _
L .. - .. - .. - .. - .. - .. - . --1- -_-.: :.-.: :.--= :...-J -
MTDP DATA WIRING SCHEMATIC
PROVIDED BY MCA CONTRACTOR
• - - - - - - - - PROVIDED BY OPA CONTRACTOR
GENERAL NOTES:
1. THIS DETAIL ONLY APPLIES FOR THE STATIONARY TARGET EMPLACEMENTS (SIT).
2. TERMINATE ALL FIBER OPTIC CABLES ENTERING OR LEAVING WITH "SC" CONNECTORS. ALL 6
STRANDS OF FIBER ARE REQUIRED TO BE TERMINATED AT EACH EMPLACEMENT.
3. PROVIDE CABLE IDENTIFICATION DIRECTORY ON INSIDE OF COVER.
4. LABEL ALL CABLES WITH ADHESIVE POLYETHYLENE WRAP AROUND LASER PRINTED LABELS
INDICATING CABLE DESTINATION AND CABLE TYPE.
5. MASTER TARGET DATA PANEL (MTDP) SHALL BE 24"W X 12"H X 6"D.
ml US Army Corps of Engineers® w N U) iii u Ir al z z iii
U) ...
z w u :;;;
w
0: () a. <( :,; " _J <( e. Q_ 0: :;;;
(9 ~ ~ Ou,z U) w 8:~~ _J ...
OU<!) ~ ci5 '.'izffi~ w _.:, a,;;: 0 w <!)a,<( _J z ~5g: <( <( ~Uw () Q_ <ocn ir <( ~g~ ...
~ 0:,:0: ()
~~~ w 0 _J ... UJQ>- w w <!Ju.J z :, ('.)
<(" ~ 0: 'ii. <( 0 ~ i5 w ...
U)
E-08
E
D
C
B
A
2 3 4 5 6
TYPICAL MASTER TARGET DATA PANEL (MTDP) DETAIL AT TARGET EMPLACEMENT
NOTTO SCALE
KEYED NOTES REPRESENTED WITH@:
1. ENCLOSURE SHALL BE 16 GAUGE MINIMUM GALVANIZED STEEL SHEET METAL WITH
WALL MOUNT BRACKETS. ENCLOSURE SHALL CARRY A NEMA 4 RATING AND BE
TESTED BY UL OR OTHER APPROVED TESTING AGENCY.
2. PROVIDE ENCLOSURE WITH FAST OPERATING CLAMP ASSEMBLY. BOLT TYPE CLAMPS
ARE NOT ACCEPTABLE.
3. INJECTION-MOLDED PLASTIC CONNECTOR 12 PORT PATCH PANEL.
4. METAL BACK PLATE TO SECURE COMPONENTS INSIDE ENCLOSURE.
5. 6-STRAND ARMORED TYPE FIBER OPTIC CABLE(S) WITH CENTRAL STRENGTH
MEMBER. SECURE FIBER OPTIC CABLE CENTRAL MEMBER INSIDE MTDP ENCLOSURE.
6. METALLIC CABLE SHEATH GROUNDING CLAMP AND GROUNDING CONNECTOR, BOND
CABLE ARMOR/SHIELD TO MTDP BACK PLATE GROUNDING BAR. ALL GROUND CABLES
NOT SHOWN FOR CLARITY.
7. CENTRAL MEMBER STRAIN-RELIEF BRACKET.
8. GROUND BAR - SECURE TO METAL BACK PLATE.
9. #6 AWG BARE COPPER GROUNDING CONDUCTOR.
10. DATA PANEL RECEPTACLE (DPR)- 20 AMP, 125 VOLT, 2 POLE, 3 WIRE GROUNDING
TYPE IN A STANDARD SINGLE-GANG METAL BOX AND GALVANIZED STEEL DEVICE
PLATE. CONNECT DPR AHEAD OF GFCI MAINTENANCE RECEPTACLE TO AVOID
NUISANCE TRIPPING.
11. 2/C #12 WITH GROUND CORD IN CONDUIT FROM CIRCUIT BREAKER LOADCENTER FOR
120 VOLT, 1-PHASE SERVICE TO DUPLEX RECEPTACLE. RECEPTACLE SHALL NOT BE
FED FROM ANY GROUND FAULT INTERRUPTING DEVICE.
12. FIELD INSTALLABLE "SC" CONNECTORS WITH BEND PROTECTOR. ALL CONNECTORS
NOT SHOWN FOR CLARITY.
13. FIBER OPTIC CABLE BUFFER TUBES WITH 6-STRANDS OF FIBER, EACH. PROVIDE 2'
SLACK EACH END.
14. NOT USED.
15. WALL MOUNTED SINGLE PANEL HOUSING FOR FIBER OPTIC CABLE TERMINATIONS.
FIBER OPTIC BUFFER TUBE SLACK AND FAN OUT KIT SHALL BE CONTAINED WITHIN
HOUSING. HOUSING SHALL BE COMPATIBLE WITH 12 PORT PATCH PANEL.
16. NOT USED.
17. PROVIDE MYERS HUB TYPE FITTING AT CONDUIT PENETRATION.
18. MTDP SHALL HAVE A ROLLED FLANGE AROUND PERIMETER OF OPENING.
19. PROVIDE ONE CABLE SEAL FITTING FOR EACH CABLE. SEE TYPICAL CABLE SEAL
FITTING DETAIL ON SHEET E-07.
20. CONDUIT FOR FIBER OPTIC CABLES.
21 . NOTUSED
22. HINGED COVER WITH CORROSION - RESISTANT STAINLESS STEEL CAPTIVE CLAMPS.
HINGE MUST HAVE REMOVABLE PIN . PROVIDE A SEAMLESS FOAM-IN-PLACE GASKET
FOR A WATERTIGHT AND DUST TIGHT SEAL.
23. FIBER OPTIC FAN-OUT KIT OR SPLICE KIT WITH PIGTAILS.
24. PROVIDE 14" X 10" SPACE FOR INSTALLATION OF TARGET COMMUNICATIONS
EQUIPMENT. POWER OUTLET AND GROUND LUG ARE ONLY COMPONENTS INSTALLED
IN THIS SPACE THAT IS NOT BY THE TARGET VENDOR. AREA MEASURED FROM SIDE
OF ENCLOSURE NOT EDGE OF BACKPLATE.
8 9
MASTER TARGET DATA PANEL
(MTDP)
-~--------------------------1
MTDP BACKPLATE ,
~@~ i-----------1c
- - - -1~-j :- - - - - - - - - - -~
I :1 [;:=i- - _J
I ETHERNET p
SWITCH I
b I b I b-1 ____ _j
GROUND
LUGS
mm _ l-_: :...-_: :...-_::...-_:·I- •• - •• - •• - •• - •• - •• - •• .J
MTDP DATA WIRING SCHEMATIC
PROVIDED BY MCA CONTRACTOR
• - - - - - - - - PROVIDED BY OPA CONTRACTOR
GENERAL NOTES:
1. TERMINATE ALL FIBER OPTIC CABLES ENTERING OR LEAVING WITH "SC" CONNECTORS. ALL 6
STRANDS OF FIBER ARE REQUIRED TO BE TERMINATED AT EACH EMPLACEMENT.
2. PROVIDE CABLE IDENTIFICATION DIRECTORY ON INSIDE OF COVER.
3. LABEL ALL CABLES WITH ADHESIVE POLYETHYLENE WRAP AROUND LASER PRINTED LABELS
INDICATING CABLE DESTINATION AND CABLE TYPE.
4. MASTER TARGET DATA PANEL (MTDP) SHALL BE 24"W X 12"H X 6"D.
5. ALL COMPONENTS INSTALLED INSIDE MTDP ENCLOSURES SHALL BE SECURED BY
MECHANICAL MEANS. ADHESIVES ARE NOT ALLOWED FOR SECURING COMPONENTS INSIDE
MTDP ENCLOSURES.
US Army Corps of Engineers® w N U) iii u Ir al z z iii
U) w _J al u (.)
0: (.)
a. f'.C :,; " <( e. Q_
0: 0 (9 ~ ~
U) c,:
Ou,z w 8:~~ _J al
OU<!) u::
'.'izffi~ w _.'., a,;;: 0 <!)a,<( _J w ~5g: <{ z
~Uw (.)
Q_ <ocn ir ~g~ f- <{
0:,:0: (.) ~ ~~~ w 0 _J
UJQ>- w f- <!Ju.J w z :, (!)
0: 'ii.
c,:
>- f- 0 c,:
i5 w f- U)
E-09
E
D
C
B
A
2 3 4 5 6
TYPICAL FACADE/CLUSTER MASTER TARGET DATA PANEL (MTDP) DETAIL AT TARGET EMPLACEMENT
NOTTO SCALE
KEYED NOTES REPRESENTED WITH@:
1.
2.
3.
4.
5.
ENCLOSURE SHALL BE 16 GAUGE MINIMUM GALVANIZED STEEL SHEET METAL WITH
WALL MOUNT BRACKETS. ENCLOSURE SHALL CARRY A NEMA 4 RATING AND BE
TESTED BY UL OR OTHER APPROVED TESTING AGENCY.
PROVIDE ENCLOSURE WITH FAST OPERATING CLAMP ASSEMBLY. BOLT TYPE
CLAMPS ARE NOT ACCEPTABLE. TYPICAL FOR BOTH ENCLOSURES.
INJECTION-MOLDED PLASTIC CONNECTOR 12 PORT PATCH PANEL WITH SUPPORT
BRACKETS FOR FIELD INSTALLABLE SC CONNECTORS.
METAL BACK PLATE TO SECURE COMPONENTS INSIDE ENCLOSURE.
~li:~~D tr~1?tn1JJ~'b~~~~~~[f cii,~irn~i~~~~JJ\~~ ~lllPNmtLOSURE
6. METALLIC CABLE SHEATH GROUNDING CLAMP AND GROUNDING CONNECTOR, BOND
CABLE ARMOR/SHIELD TO MTDP BACK PLATE GROUNDING BAR. ALL GROUND
CABLES NOT SHOWN FOR CLARITY.
7. CENTRAL MEMBER STRAIN-RELIEF BRACKET.
8. GROUND BAR - SECURE TO METAL BACK PLATE. BOND ALL GROUND BARS
TOGETHER WITH A #6 AWG COPPER GROUND CONDUCTOR. GROUND CONDUCTOR
NOT SHOW IN THIS DETAIL.
9. #6 AWG BARE COPPER GROUNDING CONDUCTOR.
10. DATA PANEL RECEPTACLE (DPR)- 20 AMP, 125 VOLT, 2 POLE, 3 WIRE GROUNDING
TYPE IN A STANDARD SINGLE-GANG METAL BOX AND GALVANIZED STEEL DEVICE
PLATE. CONNECT DPR AHEAD OF GFCI MAINTENANCE RECEPTACLE TO AVOID
NUISANCE TRIPPING.
11. 2/C #12 WITH GROUND CORD IN CONDUIT FROM SINGLE POLE SINGLE THROW
SWITCH FOR 120 VOLT, 1-PHASE SERVICE TO DUPLEX RECEPTACLE. SEE TARGET
EMPLACEMENT ELECTRICAL DETAIL FOR SWITCH LOCATIONS.
12. FIELD INSTALLABLE "SC" CONNECTORS WITH BEND PROTECTOR. ALL CONNECTORS
NOT SHOWN FOR CLARITY.
13. FIBER OPTIC CABLE BUFFER TUBES WITH 6-STRANDS OF FIBER, EACH. PROVIDE 2'
SLACK EACH END, COIL AROUND RADIUS CONTROL GUIDES.
14. INDOOR/OUTDOOR RATED CATEGORY 6 CABLES TO TARGET DATA OUTLETS. COIL 3'
SLACK IN MTDP. COIL 6"-12" OF CABLE IN TARGET OUTLET AND TERMINATE CABLE
WITH MALE RJ-45 CONNECTOR. SAT-SIT CLUSTER EMPLACEMENTS MAY HAVE AS
MANY AS 5 CAT 6 DATA CABLES SERVING TARGET MECHANISMS. ONLY ONE CABLE
SHOWN ON THIS DETAIL FOR CLARITY.
15. WALL MOUNTED SINGLE PANEL HOUSING FOR FIBER OPTIC CABLE TERMINATIONS.
FIBER OPTIC BUFFER TUBE SLACK AND FAN OUT KIT SHALL BE CONTAINED WITHIN
HOUSING. HOUSING SHALL BE COMPATIBLE WITH 12 PORT PATCH PANEL.
16. PROVIDE MODULAR JACK WITH 110 BLOCKS ON LINE SIDE AND RJ45 OUTLETS ON
EQUIPMENT SIDE TO TERMINATE CAT 6 CABLES ENTERING OR EXITING ENCLOSURE.
17. 2" CONDUIT WITH MYERS HUBS WHERE CONDUIT PENETRATES EACH ENCLOSURE.
CONDUIT USE BY TARGET INSTALLER.
18. MTDP SHALL HAVE A ROLLED FLANGE AROUND PERIMETER OF OPENING.
19. PROVIDE ONE CABLE SEAL FITTING FOR EACH CABLE. SEE "TYPICAL CABLE SEAL
FITTING DETAIL," SHEET E-07.
20. NOT USED.
21. CONDUIT WITH CAT 6 CABLES, SEE TARGET EMPLACEMENT PLAN AND ELEVATION.
22. HINGED COVER WITH CORROSION-RESISTANT STAINLESS STEEL CAPTIVE CLAMPS.
HINGE MUST HAVE REMOVABLE PIN . PROVIDE A SEAMLESS FOAM-IN-PLACE GASKET
FOR A WATERTIGHT AND DUST TIGHT SEAL.
23. FIBER OPTIC FAN-OUT KIT OR SPLICE KIT WITH PIGTAILS.
24. PROVIDE MYERS HUB FITTING AT CONDUIT PENETRATION.
25. CONDUIT/CABLE SEAL FITTING CONNECTION TO THE MTDP. SEE CONDUIT/CABLE
SEAL FITTING DETAIL ON SHEET E-07.
7 8 9 10
TARGET DATA PANEL (MASTER) TARGET DATA PANEL
SEE GENERAL NOTE 4 SEE GENERAL NOTE 4
TYPICAL
r- - - -1~ --------- -1 I -------f~ - - - - - - - - - _,-,-_-__ -_-_-_
-c:: = = = = = = = = = = = ,--L..c::
t ------ I 1 r=--=--=--= b------C ~--'II I L ____ _J I I
I -::-..=-..=-..=-..=-~ I p------c! ~---· I L ____ _J b-1 ____ _J
I I I
TO LOCAL 1
TARGET - - _J
MECHANISM
..=- ..=- ..=- 7 -1 I --7 I I I
I I I I I I I I I I I
I
MTDP DATA WIRING SCHEMATIC
PROVIDED BY MCA CONTRACTOR
• - - - - - - - - PROVIDED BY OPA CONTRACTOR
GENERAL NOTES:
1. TERMINATE ALL FIBER OPTIC CABLES ENTERING OR LEAVING WITH "SC" CONNECTORS. ALL 6
STRANDS OF FIBER ARE REQUIRED TO BE TERMINATED AT EACH EMPLACEMENT.
2. PROVIDE CABLE IDENTIFICATION DIRECTORY ON INSIDE OF COVER.
3. LABEL ALL CABLES WITH ADHESIVE POLYETHYLENE WRAP AROUND LASER PRINTED LABELS
INDICATING CABLE DESTINATION AND CABLE TYPE.
4. TARGET DATA PANEL ENCLOSURES SHALL BE 16"W X 12"H X 6"D. MATER TARGET DATA PANEL
ENCLOSURES SHALL BE 24"W X 12"H X 6"D.
5. ALL COMPONENTS INSTALLED INSIDE MTDP ENCLOSURES SHALL BE SECURED BY
MECHANICAL MEANS. ADHESIVES ARE NOT ALLOWED FOR SECURING COMPONENTS INSIDE
MTDP ENCLOSURES.
US Army Corps of Engineers®
_J w z u <(
0..
0: <( a.
<( e. <( 0: 0 (9 ~ ~ (/) >- (/) Ou, z
8:~~ _J w w ;;: (.') _, OU(.') >- D:'. Ol
'.'izffi ~ w <( <( a, ;;: 0 >- (.)
(.')a,<( _JD:'.(.)
~5g: ~~~ ~Uw <ocn D:'. <( 0 ~g~ >- :a D:'.
0 :,:0: Uo::w ~~~ ~ w £Q UJQ>- w >- lJ._ (.') u_J (/) z :, ::::, <(:,; _J 0: 'ii. ~ >-ci 0 i5 <( lJ._
E-10
| E-01 SIT (2021) |
| E-02 SAT (2021) |
| E-03 MIT (2021) |
| E-04 MAT (2021) |
| E-05 SAT Cluster (2021) |
| E-06 SAT Cluster Details (2021) |
| E-07 Details (2021) |
| E-08 SIT MTDP (2021) |
| E-09 MTDP (2021) |
| E-10 Cluster MTDP (2021) |
File details come from the government source that posted it. Updated .