Drawings 15 of 15 ELECTRICAL 2.pdf

PDF 15 MB Posted

Attached to
Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334
Solicitation number
36C77623R0156
Issued by

About this file

This document provides details for a federal contract opportunity to design and construct a new community living center. The solicitation number is 36C77623R0156 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It seeks proposals to build a new community living center at the Montrose VA medical center to provide housing and support services for veterans. Offerors should submit proposals by the response date listed in the solicitation document. The opportunity type is for design/build construction services with an expected award date in 2023 upon completion of evaluations. The related file is technical drawings for the electrical systems of the proposed new building.

View the file

Other files

File Type Posted
620-334-Responses to Tech Questions - 1-30-24.pdf PDF
36C77623R0156 0003.pdf PDF
620-334-Pre Bid Presentation20240109.pdf PDF
36C77623R0156 0002.pdf PDF
620-334-Responses to Tech Questions - 1-25-24.pdf PDF
Site Visit Sign-In Sheet - 01-09-24.pdf PDF
36C77623R0156 0001.pdf PDF
DBA Wage Rates - Westchester County - 01-05-24.pdf PDF
Drawings 8 of 15 ARCHITECTURAL 3.pdf PDF
Site Visit Campus Map.pdf PDF
Drawings 14 of 15 ELECTRICAL 1.pdf PDF
Specifications 10-30-23.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
Drawings 5 of 15 STRUCTURAL.pdf PDF
RFP 36C77623R0156 - 12-20-23.pdf PDF
Drawings 12 of 15 PLUMBING.pdf PDF
Drawings 1 of 15 GENERAL.pdf PDF
Drawings 4 of 15 LANDSCAPE.pdf PDF
Drawings 6 of 15 ARCHITECTURAL 1.pdf PDF
Drawings 2 of 15 CIVIL 1.pdf PDF
Drawings 7 of 15 ARCHITECTURAL 2.pdf PDF
Drawings 10 of 15 ARCH SIGN-EQUIP.pdf PDF
Drawings 13 of 15 MECHANICAL.pdf PDF
DBA Wage Rates - Westchester County - 11-17-23.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Brand Name J_A - Montrose.pdf PDF
Site Visit Instructions.pdf PDF
Drawings 11 of 15 FIRE PROTECTION.pdf PDF
Drawings 9 of 15 ARCHITECTURAL 4.pdf PDF
Drawings 3 of 15 CIVIL 2.pdf PDF
Construction Cost Breakdown.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE

SERVER ROOM 214, FIBER A

NOT TO SCALE

BLDG2 TO BLDG3

SERVER ROOM FIBER

NOT TO SCALE

B16 SERVER ROOM

ELECTRONICS FIBER

RACK BLDG2

NOT TO SCALE

SERVER ROOM 214, FIBER

NOT TO SCALE

NOT TO SCALE

BUILDING #20 FACP

NOT TO SCALE

BUILDING #19 FACP

NOT TO SCALE

TELE CLOSET 1B

- BUILDING 3

EMH #24

EMH #12

EMH #11

EMH #9

EMH #8

EMH #7

EMH #1

EMH #2

EMH #3

(TYP)

BUILDING 7

BUILDING 6

BUILDING 19

BUILDING 20

A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT

ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,

ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO

COMMENCING ANY WORK ON THIS SITE.

B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW

VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION

LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS

PRIOR TO COMMENCING ANY WORK ON THIS SITE.

C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY

UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING

ON THIS SITE.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH

STRUCTURAL ENGINEER FOR CONDUIT OPENING IN STRUCTURAL

SUPPORT.

E. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE

RATED NEMA 3R.

GENERAL NOTES

A. FROM EXISTING TELECOMMUNICATION MANHOLE - EMH #3, PULL

NEW FIBER USING EXISTING SPARE CONDUIT STUBBED UP IN

TELEPHONE CLOSET 1B.

B. CORE DRILL AT THE FOLLOWING LOCATION:

1. FIRST FLOOR SLAB IN CLOSET 1A THROUGH CLOSET 101A.

2. SECOND FLOOR SLAB IN CLOSET 101A THROUGH CLOSET 201.

C. PULL NEW FIBER FROM TELEPHONE CLOSET 1B THROUGH NEWLY

CREATED CORE DRILLS UP TO SECOND FLOOR CLOSET 201.

D. RUN NEW FIBER THROUGH CORRIDORS 2467 AND 247Z TO

TERMINATION LOCATION, SECOND FLOOR SERVER ROOM, ROOM

214.

BUILDING 3 GENERAL NOTES

A. CONTRACTOR SHALL PROVIDE A NEW STAND ALONE FIRE ALARM

CONTROL PANEL.

B. PROVIDE NEW (2) ANNUNCIATOR PANELS; (1) IN BUILDING #19 AND

(1) IN BUILDING #20. CONTRACTOR IS RESPONSIBLE FOR ALL

ELECTRICAL CONNECTIONS, FIRE ALARM CONNECTION TIE IN,

TESTING AND CERIFICATION FOR BOTH LOCATIONS.

1. BUILDING #19 - LOCATE ADJACENT TO EXISTING FACP ON

GROUND LEVEL. COORDINATE WITH COR PRIOR TO

INSTALLATION.

2. BUILDING #20 - LOCATE ADJACENT TO EXISTING FACP ON

GROUND LEVEL. PROVIDE TROUBLE ALARM AND MONITOR

MODULE. COORDINATE WITH COR PRIOR TO INSTALLATION.

CLC'S FIRE ALARM REQUIREMENTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:3

A M

EY100

SPECIAL SYSTEMS RENOVATION OVERALL SITE

PLAN

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

SPECIAL SYSTEMS RENOVATION OVERALL SITE PLAN

Revisions: Date:

KEYNOTES

1. NEW CLC BUILDING.

2. APPROXIMATE LOCATION OF IT CLOSET 105. SEE SHEET EY102A

FOR ADDITIONAL INFORMATION.

3. NEW CONCRETE ENCASED DUCTBANK WITH 100 PAIR

TELEPHONE CABLE, 48 STRAND SINGLE MODE FIBER FOR IT, 48

STRAND SINGLE MODE FIBER FOR ELECTRONICS AND PULL

STRINGS TO EXISTING MANHOLE, EMH#24.

4. EXISTING MANHOLE, EMH.

5. RUN NEW 100 PAIR TELEPHONE CABLE FIBER AND PULL STRINGS

IN EXISTING CONCRETE ENCASED DUCTBANK TO TELEPHONE

SWITCHGEAR ROOM 14 LOCATED IN BUILDING 2. PULL AND

TERMINATE TO FIBER RACK.

6. APPROXIMATE LOCATION OF EXISTING TELEPHONE SWITCHGEAR

IN BUILDING 2, ROOM 14.

7. NEW CLC'S FIRE ALARM SYSTEM SHALL TIE INTO EXISTING FIRE

ALARM LOOP SYSTEM VIA SPARE FIBER LOCATED IN BUILDING 6.

COORDINATE EXACT LOCATION WITH VA COR PRIOR TO

INSTALLATION. PULL NEW MULTIMODE FIBER IN 2" CONDUIT FOR

CLC'S FIRE ALARM SYSTEM TO BUILDING 6 THROUGH

CONNECTING CORRIDOR. CONTRACTOR SHALL HIRE ONE OF THE

FOLLOWING FIRE ALARM VENDORS TO PERFORM ALL

NECESSARY FIRE ALARM DESIGNS, INSTALLATION,

PROGRAMMING, TESTING AND CERTIFICATION:

1) SIRINA FIRE PROTECTION (516) 942-0400

2) AFA PROTECTIVE SYSTEMS (914) 347-5481

3) HURTVET SUBCONTRACTING (251) 648-3210

8. RUN NEW 48 STRAND SINGLE MODE FIBER WITH PULL STRINGS IN

EXISTING CONCRETE ENCASED DUCT BANK TO SECOND FLOOR

SERVER ROOM IN BUILDING 3. ENSURE A MINIMUM OF 200 L.F. OF

FIBER IS PROVIDED FROM ENTRY POINT OF BUILDING TO SERVER

ROOM LOCATION.

9. BUILDING #19 - FIRE DEPARTMENT. PROVIDE ANNUNCIATOR

PANEL PROGRAMMED FOR ALARM AND TROUBLE SIGNALS. IT IS

THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE

ANNUNCIATORS PANEL RECIEVE POWER BY TYING

CIRCUIT TO EXISTING BUILDING'S FACP CIRCUIT; PROVIDE NAC

PANEL AS REQUIRED. SEE "CLC FIRE ALARM REQUIREMENTS"

FOR ADDITIONAL INFORMATION.

10. BUILDING #20 - BOILER PLANT. PROVIDE ANNUNCIATOR PANEL

PROGRAMMED FOR TROUBLE SIGNALS. IT IS THE

RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE

ANNUNCIATORS PANEL RECIEVE POWER BY TYING CIRCUIT TO

EXISTING BUILDING'S FACP CIRCUIT; PROVIDE NAC PANEL AS

REQUIRED. SEE "CLC FIRE ALARM REQUIREMENTS" FOR

ADDITIONAL INFORMATION.

05/09/2022

F

F

SD

SD

SD

SDSD

SD

SD

SD

SD

S

S

SD

S

SS

S

S

S

S S

S

S

B

B

B

B B B

B

B

B

B

B

B

B

B

S

S

S

S

S

S

S

SSS

S

S

S

S

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

SD

S

C R F

CR

CR C

R

C R

C R

C R

CR

DH

DH

ES

E S

D C

DC

D C

D C

DC

E S

E S

ES

ES DC

E S

D C

FS

TS

D E

S

CR

ES DC

E S

D C

C R

ES

DC

C R

CR

CR

ES DC ES DC

CR CR

C R

S

FS

TS

R L

D C

E S

DC ES

RL

RL

RL R

L

R L

R L

R L

RL

RL

RL

RLRL

D C

E S

R L

D E

R L

WAP

WAP

WAP

SD

S

S

S

S

S

PIV

DC

DCES

ES RL

RL CR

C R

A

PORCH-A

LIVING ROOM

DINING

PANTRY

125A

ELEC

RESIDENT 6

SITTING ALCOVE

4/5/6/7A

CORRIDOR

120C

MEDS

STERILE SUPPLY

STORAGE

HALLWAY

209C

SOILED

CRASH CART

IT CLOSET

TLT 6

119A

TLT 5

118A

RESIDENT 5

RESIDENT 4

TLT 4

117A

LN

TLT 3

115A

SITTING ALCOVE

2/3A

RESIDENT 3

RESIDENT 2

RESIDENT 1

TLT 2

114A

LN

TLT 1

110A

SALON

102 LOBBY

FOYER

ACTIVITY

CENTRAL KITCHEN

FAMILY TOILET

WHEELCHAIR/

STRETCHER STRG

MECHANICAL

CLC WALKWAY

PT/KT

MAIN PORCH

RESIDENT 14

RESIDENT 13

SITTING ALCOVE

13/14A

LN

TLT 14

134ASITTING ALCOVE

11/12A

LN

TLT 13

133A

TLT 12

131A

RESIDENT 12

RESIDENT 11

RESIDENT 10

TLT 10

128A

TLT 11

130A

LN

RESIDENT 9

TLT 9

127A

TLT 8

126A

RESIDENT 8

SITTING ALCOVE

8/9/10A

1(TYP)

1 (TYP)

STORAGE

STORAGE

CLEAN

PUBLIC TOILET

HAC

CHARGING A

M A

T C

H

LI

N E

S

E : 1

/E Y

1B

TLT 7

120A

RESIDENT 7

(BARIATRIC)

CORRIDOR 1A

SITTING ALCOVE

1A

CORRIDOR

122C

WP

4K

WP

4K

WP

WP

WP

SCREENING

VESTIBULE

CORR

STAIRS

144B

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

DEDUCT #814

A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF

ALL RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED

RATING ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND

MATERIALS SHALL MEET THE UL RATING OF THE RATED WALLS,

CEILINGS AND SLABS ASSEMBLY. CONTRACTOR SHALL PROVIDE

AN ASSEMBLY INSTALLED IN ACCORDANCE WITH THE RATED

APPLICATION.

B. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING/INSTALLATION.

C. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANCIAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

D. ALL LOW VOLTAGE WIRING SHALL BE ROUTED BACK TO IT ROOM.

NO CAT6 CABLE DEVICES SHALL EXCEED 295' IN LENGTH.

E. VOICE EVACUATION SHALL BE PART OF THE FIRE ALARM SYSTEM.

COORDINATE ALL REQUIREMENTS WITH VA PRIOR TO

INSTALLATION.

F. ALL TELEVISION COMMUNICATION OUTLETS SHALL BE MOUNTED

60" AFF UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL

ELEVATION PLANS FOR ADDITIONAL INFORMATION.

G. CONTRACTOR SHALL PROVIDE PILLOW SPEAKER AT EACH

RESIDENTIAL BED. PILLOW SPEAKER SHALL ALSO CONTROL TV.

PROVIDE WIRE AS REQUIRED. INSTALL PER MANUFACTURER'S

INSTALLATION MANUAL.

GENERAL NOTES

FIRE ALARM LEGEND

MANUAL PULL STATION (46" AFF)F

S

S

SPEAKER (80" AFF)

STROBE LIGHT (80" AFF)

S SPEAKER/STROBE (80" AFF)

SMOKE DETECTOR - CEILING MOUNTEDSD

TS

FS

DH

TAMPER SWITCH

FLOW SWITCH

MAGNETIC DOOR HOLDER (72" AFF)

DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING

TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON

END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6

PORTS, CAT6A, RJ45

WIRELESS ACCESS POINT - GC PROVIDE/INSTALL

CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);

PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE

CEILING. PROVIDE INSULATED NYLON BUSHING ON END

OF CONDUIT FOR PROTECTION OF WIRE

CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER

RING, 3/4" CONDUIT WITH PULL STRING TO DOOR

CONTROLLER

DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

ELECTRIC STRIKE, FAIL SECURE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

CCTV CAMERA FIXED - PROVIDE DOUBLE GANG BACK

BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT

WITH PULL STRING TO ACCESSIBLE CEILING

CR

DC

ES

N NURSE STATION (46" AFF)

BED NURSE CALL WITH PILLOW

SPEAKER JACK (46" AFF)

TOILET NURSE CALL (46" AFF)

ND

WP - WEATHERPROOF SHOWER NURSE

CALL (46" AFF)

NURSE CALL DUTY STATION (46" AFF)

NURSE CALL MASTER

B

T

S

CCTV CAMERA 360 DEGREES - PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;

WP = WEATHERPROOF

WP

4K

CARD ACCESS LEGEND

NURSE CALL LEGEND

COMMUNICATION LEGEND

SURVEILLENCE LEGEND

CARD READER RELAY; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

RL

WAP

SPEAKER (PUBLIC ADDRESS)S

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

B6 WALKWAY

(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE

EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED

DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER

SHEET GI000.

DEDUCT ALTNERATIVE #4 : ELIMINATE WORK AT B6 CORRIDOR

DEDUCT ALTNERATIVE #8 : ELIMINATE NETWORK VIDEO RECORDER

(NVR) SECURITY

DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH

DEDUCT ALTNERATIVE #10 : ELIMINATE SMALL PORCH-A

DEDUCT ALTERNATIVE NOTES

N

KEY PLAN

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:4

A M

EY101A

SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA

A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

SPECIAL SYSTEMS - LEVEL 1 - AREA A

KEYNOTES

1 FIRE ALARM ZONE.

2 PUSH PLATE FOR DOUBLE SWING DOORS.

3 DELAY-EGRESS DOOR. CONTRACTOR SHALL PROVIDE FIRE ALARM

RELAY FOR DELAY EGRESS LOCK. CARD READER SHALL BE INSTALLED

TO BYPASS DELAY-EGRESS DOOR.

4 CARD READER AND PUSH BUTTON PEDESTAL. VERIFY EXACT LOCATION

WITH VA PRIOR TO INSTALLATION.

5 2"Dx4"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

6 2"Dx12"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

7 2"Dx22"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

8 2"Dx6"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

9 PROVIDE (6) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE

RATED WALLS/HARD CEILING.

10 PROVIDE (1) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE

RATED WALLS/HARD CEILING.

11 FLOOR MOUNTED DATA SERVICING SECURITY SCREEN EQUIPMENT.

COORDINATE EXACT LOCATION AND REQUIREMENTS WITH VA PRIOR

TO INSTALLATION.

12 PROVIDE (4) CAT6E CABLES FROM IT CLOSET TO THIS LOCATION FOR

WAP, WIRELESS ACCESS POINT. WAP SHALL BE INSTALLED BY VA'S IT

CONTRACTOR AT A LATER DATE.

13 CONTRACTOR SHALL PROVIDE SERVER RACK AND PATCH PANELS

LOCATED IN IT CLOSET. VERIFY MAKE/MODEL/QUANTITY WITH VA.

CONTRACTOR SHALL ENSURE ALL SYSTEMS ARE FULLY FUNCTIONING

PRIOR TO TURN OVER. SEE SERVER RACK ELEVATIONS FOR

ADDITIONAL INFORMATION.

14 NETWORK VIDEO RECORDER (NVR) SECURITY LOCATED IN IT CLOSET.

REMOVE AS REQUIRED UNDER DEDUCT #8.

1/8" = 1'-0"

SPECIAL SYSTEMS FLOOR PLAN - COVERED WALKWAY

DEDUCT #10

DEDUCT #9

MATCHLINE

SEE: 2/EY101A

MATCHLINE

SEE: 1/EY101A

DEDUCT #4

Revisions: Date:

DEDUCT #8

SD

SD

SD

SD

SD

SDSD

S

S

FS

S

S

S

S

S

S

S

S

B

B

B

B

B

B

B

B

B

B

B

B

B

B

S

S

S

S

S

S

S

S

S

S

S

SS

S

T

T

T

T

T

T

T

T

T

T

T

T

T

T

SD

SD

C R

C R

CR

CR

C R

DH

DH

SD

E S

ESD

C

DC

E S

ES

DC

D C

D C

C R

E S

ES

CR

DC

E S

D C

C R

R L

R L

R L

RL

RL

RL

CR CRDCDC

ES

RL

R L

D C

E S

R L

D E

D E

N D

WAP

WAP

WAP

SD

S

S

S

S S

S

RL

ES

ES

CORRIDOR

164C

STAFF LOUNGE

STAFF TOILET/

SHOWER

HOTELING

ADMIN HALL-B

OFFICE

OFFICE

OFFICE

HALLWAY

192C

CLEAN

SOILED

MEDS

CRASH CART B

ELEC

DINING

CHARGING B

PANTRY

168A

LN

TLT 14

183A

TLT 13

181A

SITTING ALCOVE

12/13B

SITTING ALCOVE

10/11B

SITTING ALCOVE

6/7/8/9B

RESIDENT 7

RESIDENT 14

RESIDENT 13

RESIDENT 12

TLT 12

180A

TLT 11

178A

LN

LN

TLT 10

175A

TLT 9

173A

RESIDENT 11

RESIDENT 10

RESIDENT 9

RESIDENT 8

TLT 7

171A

TLT 8

172A

LIVING ROOM

PORCH B

RESIDENT 5

SITTING ALCOVE

3/4/5B

TLT 5

164A

TLT 4

163A

RESIDENT 4

RESIDENT 3

RESIDENT 2

RESIDENT 1

SITTING ALCOVE

1/2B

LN

TLT 3

162A

TLT 2

160A

TLT 1

159A

LN

EXAM RM

EMERGENCY

POWER

POWER

CONFERENCE

MAIN PORCH

DP

ITFACP EQ1

LS

B

1 (TYP)

1 (TYP)

RESIDENT 6

(BARIATRIC)

TLT 6

170A

HAC

GAS

SITTING ALCOVE

14B

M A

T C

H

LI

N

E : 1

/E Y

1A

CORRIDOR

163C

WP

4K

WP

4K

WP

ATS-LS

LCP

NCT

EQ

150A

ENCLOSED

CKT BKR

1000A

ENCLOSED

CKT BKR

WP

ATS-DP

ATS-EQ

400A

ENCLOSED

CKT BKR

MDP

NL

PT/KT

7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

8.6

AA

FIRE ALARM LEGEND

MANUAL PULL STATION (46" AFF)F

S

S

SPEAKER (80" AFF)

STROBE LIGHT (80" AFF)

S SPEAKER/STROBE (80" AFF)

SMOKE DETECTOR - CEILING MOUNTEDSD

TS

FS

DH

TAMPER SWITCH

FLOW SWITCH

MAGNETIC DOOR HOLDER (72" AFF)

DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING

TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON

END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6

PORTS, CAT6A, RJ45

WIRELESS ACCESS POINT - GC PROVIDE/INSTALL

CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);

PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE

CEILING. PROVIDE INSULATED NYLON BUSHING ON END

OF CONDUIT FOR PROTECTION OF WIRE

CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER

RING, 3/4" CONDUIT WITH PULL STRING TO DOOR

CONTROLLER

DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

ELECTRIC STRIKE, FAIL SECURE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

CCTV CAMERA FIXED - PROVIDE DOUBLE GANG BACK

BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT

WITH PULL STRING TO ACCESSIBLE CEILING

CR

DC

ES

N NURSE STATION (46" AFF)

BED NURSE CALL WITH PILLOW

SPEAKER JACK (46" AFF)

TOILET NURSE CALL (46" AFF)

ND

WP - WEATHERPROOF SHOWER NURSE

CALL (46" AFF)

NURSE CALL DUTY STATION (46" AFF)

NURSE CALL MASTER

B

T

S

CCTV CAMERA 360 DEGREES - PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;

WP = WEATHERPROOF

WP

4K

CARD ACCESS LEGEND

NURSE CALL LEGEND

COMMUNICATION LEGEND

SURVEILLENCE LEGEND

CARD READER RELAY; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

RL

WAP

SPEAKER (PUBLIC ADDRESS)S

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF

ALL RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED

RATING ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND

MATERIALS SHALL MEET THE UL RATING OF THE RATED WALLS,

CEILINGS AND SLABS ASSEMBLY. CONTRACTOR SHALL PROVIDE

AN ASSEMBLY INSTALLED IN ACCORDANCE WITH THE RATED

APPLICATION.

B. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL

CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL

EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO

ORDERING/INSTALLATION.

C. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE

MECHANCIAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE

THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN

THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE

ELECTRICAL CONTRACTOR.

D. ALL LOW VOLTAGE WIRING SHALL BE ROUTED BACK TO IT ROOM.

NO CAT6 CABLE DEVICES SHALL EXCEED 295' IN LENGTH.

E. VOICE EVACUATION SHALL BE PART OF THE FIRE ALARM SYSTEM.

COORDINATE ALL REQUIREMENTS WITH VA PRIOR TO

INSTALLATION.

F. ALL TELEVISION COMMUNICATION OUTLETS SHALL BE MOUNTED

60" AFF UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL

ELEVATION PLANS FOR ADDITIONAL INFORMATION.

G. CONTRACTOR SHALL PROVIDE PILLOW SPEAKER AT EACH

RESIDENTIAL BED. PILLOW SPEAKER SHALL ALSO CONTROL TV.

PROVIDE WIRE AS REQUIRED. INSTALL PER MANUFACTURER'S

INSTALLATION MANUAL.

GENERAL NOTES

(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE

EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED

DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER

SHEET GI000.

DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH

DEDUCT ALTNERATIVE #11 : ELIMINATE SMALL PORCH-B

DEDUCT ALTERNATIVE NOTES

N

KEY PLAN

AREA B

(EAST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:5

A M

EY101B

SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA

B

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA B

KEYNOTES

1 FIRE ALARM ZONE.

2 DELAY-EGRESS DOOR. CONTRACTOR SHALL PROVIDE FIRE ALARM

RELAY FOR DELAY EGRESS LOCK. CARD READER SHALL BE INSTALLED

TO BYPASS DELAY-EGRESS DOOR.

3 2"Dx6"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

4 2"Dx4"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND

ROUTING WITH ABOVE CEILING UTILITIES.

5 PROVIDE (1) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE

RATED WALLS/HARD CEILING.

6 CARD READER AND PUSH BUTTON PEDESTAL. VERIFY EXACT LOCATION

WITH VA PRIOR TO INSTALLATION.

7 PROVIDE (4) CAT6E CABLES FROM IT CLOSET TO THIS LOCATION FOR

WAP, WIRELESS ACCESS POINT. WAP SHALL BE INSTALLED BY VA'S IT

CONTRACTOR AT A LATER DATE.

DEDUCT #9

DEDUCT #11

Revisions: Date:

PRIMARY SWITCH COMPARTMENT

CONCRETE PAD

GRADE

PAD LOCKABLE

DOOR HANDLE

WEATHERPROOF STAINLESS

STEEL ENCLOSURE

SECONDARY SWITCH

COMPARTMENT

SWITCH COMPARTMENT

3/4" x 10' COPPER CLAD

GROUND ROD, TYP OF

4, ONE AT EACH

CORNER OF PAD.

COMPARTMENT GROUND

DUAL-PURPOSE BARRIER

SPRING LATCH

HOLDER

SWITCH

GROUND STUDS

UP FRONT FOR

CLEAR ACCESS

SWITCH

TERMINALS

SURGE

ARRESTERS

SWITCH-SIDE

REMOVABLE

INTERPHASE

BARRIER

PRIMARY COMPARTMENT

CONCRETE PAD

GRADE

PRIMARY SERVICE

CONCRETE ENCASED

CONDUITS

SECONDARY SERVICE

CONCRETE ENCASED

CONDUITS

SECONDARY COMPARTMENT

SECTION A-A

A

A

GROUNDING DETAIL

GROUND

BAR

NEUTRAL

BAR

CATV FA SEC

ELEC

METER

GROUND

BAR

NEUTRAL

BAR

GENERATOR GROUNDING AND NEUTRAL DETAILB

N

N

G

GEN

N

LOAD

208/120V, 3-PH, 4W

1. TRANSFER SWITCH CONTACTS SHALL BE OF

THE OPEN TYPE AND SHALL BE ACCESSIBLE

FOR INSPECTION AND REPLACEMENT.

MAIN

EQUIPMENT

GROUNDING

CONDUCTOR

EQUIPMENT

GROUNDING

CONDUCTOR 4-POLE

AUTOMATIC

TRANSFER

SWITCH

NEUTRAL-GROUND BOND IN MDP

N

GND

LUG

GENERATOR NOT A

SEPARATELY

DERIVED SYSTEM

MAIN PANEL

NOTE:

SERVICE EQUIPMENT

EQUIPMENT

GROUNDING

CONDUCTOR OR

SUPPLY-SIDE

BONDING JUMPER

A N.T.S.

N.T.S.

TWO HOLE STRAP OR

CADWELD CONNECTION TYPE

''LK'', TYPICAL

MOUNTING BRACKETS

FIBERGLASS INSULATORS

4"

MIN.

NOTES:

1. PREDRILLED BOLT HOLE SIZE AND SPACING AS REQUIRED FOR INDICATED TERMINATIONS .

2. PROVIDE LENGTH SUFFICIENT FOR ALL INDICATED TERMINATIONS AND 20% SPARE MOUNTING

SPACE. CONNECTIONS SHALL UTILIZE TWO HOLE COMPRESSIONS CONNECTOR.

3. GROUND BAR SHALL BE MOUNTED MINIMUM 2" OFF WALL AND 12" AFF.

4. FIBERGLASS INSULATORS SHALL HAVE A MINIMUM DIELECTRIC STRENGTH OF 15kV.

INSULATED COPPER

GROUND CONDUCTOR TO

BUILDING GROUNDING

ELECTRODE CONDUCTOR

C GROUND BUS DETAIL NTS

E 6-WAY DUCTBANK 4" CONDUIT DETAIL NTS

NOTES:

1. TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.

2. PLASTER RINGS NOT SHOW.

3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND

MECHANICAL DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.

4. IN ACCORDANCE WITH UBC 4304 OUTLETS ON OPPOSITE SIDES OF WALLS OR

PARTITIONS IN THE SAME STUD SPACE MUST BE SEPARATED BY A MIN. OF 24"

HORIZONTAL DISTANCE.

5. TOENAILING OF OUTLET BOXES DIRECTLY TO THE STUDS WILL NOT BE

ACCEPTED.

6. OUTLETS SHOWN TOGETHER ON PLAN SHALL BE INSTALLED TOGETHER.

TYPICAL

WALL

OUTLETS

PROVIDE CONDUIT SUPPORTS IN

ACCORDANCE WITH NEC. SPACING

REQUIREMENTS FOR TYPE OF RACEWAY

REQUIRED.

AS REQUIRED FOR TYPE

OF CONSTRUCTION.

BOX

SUPPORT

TYPICAL

OUTLET

BOX.

D TYPICAL ROUGH-IN NTS

G NTS

61_

MIN.

DEDICATED

ELECTRICAL

SPACES

PERMITTED

LUMINARIE

PERMITTED

PERMITTED

STRUCTURAL

CEILING

SUSPENDED

CEILING

SIDE VIEW FRONT

6' OR

LESS

DEDICATED EQUIPMENT SPACE NOTES:

1. THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT AND EXTENDING

FROM THE FLOOR TO A HEIGHT OF 6'-0" ABOVE THE EQUIPMENT OR TO THE

STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED TO THE

ELECTRICAL INSTALLATION. NO PIPING, DUCTS, LEAK PROTECTION APPARATUS OR

OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE

LOCATED IN THIS ZONE.

2. THE AREA ABOVE THE DEDICATED SPACE SHALL BE PERMITTED TO CONTAIN

FOREIGN SYSTEMS, PROVIDED PROTECTION IS INSTALLED TO AVOID DAMAGE TO

THE ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS, OR BREAKS IN SUCH

FOREIGN SYSTEMS.

3. SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE DEDICATED SPACE WHERE

THE PIPING COMPLIES WITH THESE NOTES.

4. A DROPPED, SUSPENDED, OR SIMILAR CEILING THAT DOES NOT ADD STRENGTH TO

THE BUILDING STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL CEILING.

DEDICATED ELECTRICAL SPACES

H GENERATOR SYSTEM REQUIREMENTS NTS

F NTSELECTRICAL EQUIPMENT NAMEPLATE

GENERATOR SYSTEM REQUIREMENTS:

NFPA 110 LEVEL---------------------------------------------------------------------- 1

NFPA 110 TYPE------------------------------------------------------------------------ 10

NFPA CLASS----------------------------------------------------------------------------96 (HRS)

GENERATOR SET MODEL--------------------------------------------------------- 350REOZJC

KW @ 130C RISE---------------------------------------------------------------------- 350 KW

KVA @ 0.8 PF--------------------------------------------------------------------------- 438 KVA

VOLTAGE-------------------------------------------------------------------------------- 208/120 VOLTS, 3 PHASE, 60HZ

PEAK MOTOR STARTING KVA @ 35% MAXIMUM

INSTANTANEOUS VOLTAGE DIP------------------------------------------------ 1314 KVA

ALTERNATOR-------------------------------------------------------------------------- 4M4019

FREQUENCY REGULATION------------------------------------------------------- ±0.25%

CONTROLLER MODEL-------------------------------------------------------------- APM603

MUFFLER-------------------------------------------------------------------------------- CRITICAL GRADE MUFFLER

ENCLOSURE---------------------------------------------------------------------------- LEVEL 2 ACOUSTIC ENCLOSURE

ENGINE HP@ 1800 RPM------------------------------------------------------------ 401 kWm

FREQUENCY / SPEED REGULATION------------------------------------------ ISOCHRONOUS

CIRCUIT BREAKER #1 AMPS----------------------------------------------------- 1200A

CIRCUIT BREAKER #2 AMPS----------------------------------------------------- N/A

SHUNT TRIP---------------------------------------------------------------------------- NO

GFI INDICATION----------------------------------------------------------------------- YES

MANUFACTURER/MODEL TANK------------------------------------------------- HIGHLAND TANK PETRO HOPPER HT-1032

TANK SIZE (GAL)---------------------------------------------------------------------- 1,000

ATS MODEL ATS-L-LS-------------------------------------------------------------- KBP-DCVA-0150S

AMPERAGE---------------------------------------------------------------------------- 150A

VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ

NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1

SERVICE ENTRANCE RATED---------------------------------------------------- NO

INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO

ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT

ATS MODEL ATS-L-EQ-------------------------------------------------------------- KBP-DCVA-1000S

AMPERAGE---------------------------------------------------------------------------- 1000A

VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ

NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1

SERVICE ENTRANCE RATED---------------------------------------------------- NO

INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO

ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT

ATS MODEL ATS-L-DP-------------------------------------------------------------- KBP-DCVA-0400S

AMPERAGE---------------------------------------------------------------------------- 400A

VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ

NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1

SERVICE ENTRANCE RATED---------------------------------------------------- NO

INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO

ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT

*EQUIPMENT LISTED IS MANUFACTURED BY KOHLER, INC. OF KOHLER, WISCONSIN, FOR THE PURPOSE OF

ESTABLISHING A MINIMUM STANDARD. SUBSTITUTIONS BY GENERAC, CUMMINS/ONAN OR CATEPILLAR AND

ALL EQUIPMENT FURNISHED SHALL BE EQUAL IN EVERY RESPECT TO KOHLER, INCLUDING QUALITY, SPECIFICATIONS, OPERATION, AND FUNCTION TO BE CONSIDERED. THE EQUIPMENT SPACING, ELECTRICAL WIRING, EQUIPMENT MECHANICAL, FUEL AND EXHAUST COMPONENTS, HAVE ALL BEEN SIZED

AND DESIGNED AROUND KOHLER EQUIPMENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY

CHANGE IN BUILDING WORK MADE NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF ANY

EQUIPMENT OTHER THAN KOHLER WITH OUT ADDITIONAL COST TO THE VA.

FUEL TYPE------------------------------------------------------------------------------ DIESEL

I SECTIONAL SWITCHGEAR BLOCK ENCLOSURE (EXTERIOR)NTS

J SECTIONAL SWITCHGEAR BLOCK ENCLOSURE (INTERIOR) NTS

K CONCRETE PAD WITH CONDUIT PENETRATION NTS

NOTES:

1. AIR ENTRAINED CONCRETE - 4000 PSI AFTER 28 DAYS, MAX AGGREGATE 3/4".

2. STEEL FLOAT FINISH.

3. REINFORCEMENT: TYPE A-305 NEW BILLET STOCK A.S.T.M. GRADE 60.

4. ALL REINFORCING SHALL BE #4 BAR 12" O.C. EACH WAY. WIRE TIE ALL CROSSINGS.

5. IF THE ANTICIPATED FORECAST TEMPERATURE IS 35 DEGREES OR LESS, THE PAD

SHALL BE INSULATED WITH EITHER BLANKETS OR POLY AND STRAW FOR A MINIMUM

OF 3 DAYS.

6. ALL MEMBRANE CURING COMPOUND, MEETING A.S.T.M. C-309, AT MANUFACTURERS

PRESCRIBED RATE AFTER REMOVAL OF FORMS.

7. EDGE TROWEL WITH CHAMFERED OUTSIDE EDGES.

8. A SAFE OPERATING CLEARANCE OF A MINIMUM OF 10'-0" (UNOBSTRUCTED) IS

REQUIRED IN FRONT OF THE EQUIPMENT DOOR. THE DOOR(S) CAN FACE ANY

DIRECTION EXCEPT TOWARDS THE BUILDING.

9. IF NECESSARY, ELECTRICAL CONTRACTOR MAY REMOVE TOP LIP OF FIBERGLASS

GROUND SLEEVE IN THE LOW VOLTAGE SECTION.

10. PRIMARY CONDUIT (WHERE REQUIRED) IS PROVIDED BY CONTRACTOR AND

INSTALLED BY CONTRACTOR.

NOTE: CONTRACTOR TO OBTAIN ALL REQUIRED PERMITTING AND REGISTRATION FOR GENERATOR AND FUEL

TANK AS REQUIRED BY THE LOCAL, STATE, AND GOVERNMENT AGENCIES (NYSDEC, USEPA).

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance

Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in. (102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in.

(610 mm) OC. Additional studs installed to completely frame the opening.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition

Design. Max area of opening is 352 sq in. (2271 sq cm) with max dimension of 22 in. (559 mm) wide.

The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Cable Tray* — Max 18 in. (457 mm) wide by max 6 in. (152 mm) deep open-ladder or solid-back cable tray with channel-shaped side rails formed of 0.065 in. (1.65 mm) thick aluminum or 0.060 in. (1.52 mm) thick steel and with 1-1/2 in. (38 mm) wide by 1 in.

(25 mm) channel shape rungs spaced 9 in. (229 mm) OC or a 0.029 in. (0.74 mm) thick steel solid back, respectively. One cable tray to be installed in the opening. The max annular space between the cable tray and the periphery of the opening shall be min 1

in. (25 mm) to max 7 in. (178 mm) Cable tray to be rigidly supported on both sides of floor or wall assembly.

3. Cables — Aggregate cross-sectional area of cables in cable tray to be max 30 percent of the cross-sectional area of the cable tray. Any combination of the following types and sizes of copper conductor cables may be used:

A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and PVC jacket.

B. 100 pair - No. 24 AWG cable with PVC insulation and jacket.

C. 1/C, 750 kcmil (or smaller) with PVC insulation and jacket.

4. Through-Penetrants — One or more pipe or tube to be installed within the opening. The total number of through-penetrants is dependent on the size of the opening and types and sizes of the penetrants. Any combination of the penetrants described below may be used provided that the following parameters relative to the annular spaces and the spacings between the pipes are maintained. The space between the pipe or tube and the periphery of the opening shall be min 1-1/2 in. (38 mm) to max 9-1/4 in.

(235 mm). Pipe or tube to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of non-metallic or metallic pipes, or tubes may be used:

A. Polyvinyl Chloride (PVC) Pipe — Max 3 in. (76 mm) diam Schedule 40 solid core PVC pipe (or smaller) for use in closed

(process or supply) or vented (drain, waste or vent) piping system.

B. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe.

C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) diam steel conduit.

D. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.

E. Copper Tube — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.

4A. Pipe Covering — (Not Shown) Nom 1-1/2 in. (38 mm) thick hollow cylindrical heavy density (min 3.5 pcf) (56kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product.

See Pipe and Equipment Covering and Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a

Flame Spread Index of 25 or less and a Smoke Developed Index of 50 may be used.

5. Cables — Max 1-1/2 in. (38 mm) diam tight bundle of cables installed within the opening and rigidly supported on both surfaces of wall. The space between the cables and periphery of the opening shall range from 1-3/16 in. (30.2 mm) min to a max of 1-1/2

in. (38 mm). Any combination of the following types and sizes of cables may be used:

A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

B. 25 pair — No. 24 AWG cable with PVC insulation and jacket.

C. Type R GU/59 coaxial cable with PVC outer jacket.

D. 24 fiber optic cable with PVC sub unit and outer jacket.

6. Firestop System — The firestop system shall consist of the following:

A. Fill, Void or Cavity Material* — Fire Blocks For walls incorporating max 3-5/8 in. (92 mm) steel studs or max 2 (51 mm) by 4

in. (102 mm) wood studs, fire block installed with 5 in. (127 mm) dimension projecting through and centered in opening. For walls constructed of larger steel or wood studs, fire block installed with long dimension passing through and centered in opening. Blocks may or may not be cut flush with both surfaces of wall. When multiple layers of gypsum board are used, blocks may be recessed 1/2 in. (13 mm) from surface of wall. Blocks to be firmly packed in opening. Either one or a combination of the block types specified below may be used.

B. Fill, Void or Cavity Material* — Sealant or Putty - Fill material to be forced into interstices of cables, between cables and cable trays, around each penetrant and where obvious voids are observed to max extent possible on both surfaces of the penetration.

L PENETRATIONS THROUGH RATED WALLS NTS

GROUNDING DETAIL KEYNOTES

1. GROUND BUS BAR LOCATED IN MAIN ELECTRICAL ROOM OR WITHIN

SERVICE ENTRANCE MAIN. 0.25" X 4" X 12" WITH 18 HOLES MINIMUM FOR

EXTERNAL INSTALLATION.

2. GROUNDING TRIAD, 3-3/4" X 10'-0" COPPERCLAD GROUND RODS DRIVEN

INTO GROUND AT LEAST 1 ROD'S LENGTH APART. PROVIDE WITH

INSPECTION TEST WELL.

3. COPPER GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC TABLE

250.66, MINIMUM SIZE #8.

4. SERVICE ENTRANCE MAIN BONDING JUMPER SIZED PER NEC TABLE

250.66. NEUTRAL SHALL ONLY BE BONDED AT SERVICE ENTRANCE, ALL

OTHER NEUTRALS SHALL BE CONSIDERED FLOATING.

5. CONNECTIONS TO BUILDING STEEL SHALL BE BY EXOTHERMIC WELD.

6. CONNECTIONS TO REBAR ENCASED IN CONCRETE SHALL BE BY

EXOTHERMIC WELD.

7. BOND METALLIC COLD WATER PIPE WITHIN 5' - 0" OF ENTERING

BUILDING. CONNECTION SHALL BE MADE WITH NON-CORROSIVE

MATERIAL GROUNDING ELECTRODE CLAMP.

8. SERVICE ENTRANCE NEUTRAL CONDUCTOR.

9. ALL EQUIPMENT ENCLOSURES AND METAL RACEWAYS SHALL BE

GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER

NEC TABLE 250.122.

10. EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122.

11. NEUTRAL CONDUCTOR WITH INSULATED EQUIPMENT GROUNDING

CONDUCTOR TO BRANCH CIRCUIT PANELS/EQUIPMENT.

X

SERVICE ENTRANCE MAIN

BRANCH CIRCUIT PANEL

GRADE

3 3 3

HEM

120/208V, 3PH, 4W

FED FROM MSB BKR. 11

SCA 36,921A 01/03/12

LETTER (FILL) COLOR

EMERGENCY = WHITE

NORMAL - WHITE

INDICATED

VOLTAGE,

NO. OF PHASES,

NO OF WIRES

INDICATES WHERE

THIS EQUIPMENT IS

FED FROM

(TRANSFER

SWITCHES WILL HAVE

TWO LINES.)

CALCULATED

AVAILABLE FAULT

CURRENT

ATTACH

NAMEPLATE

WITH 2 SCREWS

NAMEPLATE COLOR

LIFE SAFETY - YELLOW

CRITICAL - ORANGE

EQUIPMENT - GREEN

NORMAL - BLACK

EMERGENCY - RED

LETTERING

SHALL BE

1/4" HIGH

MASONRY LEVELING

BLOCKS AT BASE SPACERS

#4 REBAR (TYPICAL)

#4 REBAR (TYPICAL)

1'-6" ON CENTER

3" MINIMUM CLEARANCE

FINISHED GRADE

3'-6" MINIMUM

DUCTBANK

MARKING TAPE

3000 P.S.I CONCRETE

4" P.V.C CONDUIT

(TYPICAL)

BASE AND INTERMEDIATE

SPACERS 4'-0" ON CENTER

7 1/2" TO MINIMUM

SEPARATION

LCL C

REFER TO CIVIL PLANS

DETAIL C5 ON SHEET CG506

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:1

A M

E-501

ELECTRICAL DETAILS

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

Revisions: Date:

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION

Fix.

Qty

Lamp Type

VOLTS MOUNTING REMARKS

INPUT

WATTS

A USAI

P4RDF 15L2 27KS M WH NC UNV

D22

4.5" DOWNLIGHT, 1575 LUMENS, 50,000 HOUR L70

RATED LIFE, 5 YEAR WARRANTY, DIMMABLE

323 LED 120 RECESSED

RESIDENT, 0-10V

DIMMING

B BROWNLEE 5853 BN G30 BAC 26" VANITY, (3) 10W GU24LED LAMPS 31 LED 120 SURFACE VANITY 30

C BROWNLEE 2612 36 CC3 NT C49 XXX 35K BAC

36" DIAMETER DRUM PENDANT, COLOR BY ARCHITECT,

5877 LUMENS, 50,000 HOUR L70 RATED LIFE, 5 YEAR

WARRANTY

2 LED 120 PENDANT LIVING ROOM 49

D LITHONIA

2BLT4 48L ADP 120 GZ10 LP835

USPOM

2X4 TROFFER, CURVED LENS, 4800 LUMENS, 60,000 L80

RATED LIFE, 5 YEAR WARRANTY, DIMMABLE

49 LED 120 RECESSED GENERAL 44

F LITHONIA

LDN8CYL 35/80 L0AR LD 120

GZ10 PM DWHG

8" CYLINDER, 8000 LUMENS, 60,000 L70 RATED LIFE, 5

YEAR WARRANTY

35 LED 120 PENDANT CORRIDOR 93

G LITHONIA

CLX L48 5000LM SEF FDL 120

GZ10 35K 80CRI WH USPOM

HC36 WGCLX48

4' STRIP, FLAT DIFFUSE LENS WITH 48" WIREGAURD,

5,000 LUMENS, 100,000 HOUR L70 RATED LIFE, 5 YEAR

WARRANTY

37 LED 120 SURFACE UTILITY 36

H AUBERGE

AU RE R15W 35 9 RE7W14H XX

XX

RECTANGULAR ADA WALL SCONCE, WASHABLE

ACRYLIC RESIN, 100,000 HOUR L70 RATED LIFE, 10

YEAR WARRANTY, DIMMABLE

48 LED 120 SURFACE GENERAL 15

K FOCAL POINT

FSM2LS FL 750LF 35K 1C UNV

LD1 C24 WH

LINEAR SUSPENDED, DIRECT, 750 LUMENS/FT, 61,000

HOUR L70 RATED LIFE, 5 YEAR WARRANTY, DIMMABLE

20 LED 120 SUSPENDED DINING 28

M LITHONIA

CLX L48 5000LM SEF FDL 120

GZ10 35K 80CRI WH USPOM

HC36 WGCLX48 MSDPDT7

4' STRIP, FLAT DIFFUSE LENS WITH 48" WIREGAURD,

5,000 LUMENS, 100,000 HOUR L70 RATED LIFE, 5 YEAR

WARRANTY, DUAL TECHNOLOGY OCCUPANCY SENSOR

37 LED 120 SURFACE STAIRS 36

N TECH LIGHTING GAMBIT 19-LIGHT CHANDELIER FULLY DIMMABLE, LED 3278 LUMENS, 90 CRI, 2700K 1 LED 120 PENDANT SALON 38

P BIG ASS FANS

FR127A S0 F1 0-3H03 02 258

654P010

52" HAIKU OUTDOOR CEILING FAN, COCOA

WOODGRAIN, UNIVERSAL MOUNTING WITH OUTDOOR

LIGHT KIT

4 LED 120 CEILING OUTDOOR 22

Q VODE LIGHTING LED WING RAIL

ART WALL LIGHTING, WALL ARM MOUNTED, 2700K

COLOR TEMPERATURE

6 LED 120 WALL ART LIGHTING 6.14

R ANP LIGHTING LA213 1 P117LD4 D T3 W 40K PC

DARK SKY FRIENDLY, TYPE 3 DISTRIBUTION, 4000K IN

COLOR TEMPERATURE, PHOTOCELL, WHITE

8 LED 120 POLE SITE LIGHTING 117

ANP LIGHTING CB1206 4S15.188 44

15FT, 4" DIAMETER WHITE POLE, SEE SHEET CG503

DETAILS "B5" AND SHEET S202 DETAILS "W" FOR

ADDITIONAL INFORMATION

8 POLE

S LITHONIA

LDN6 35/50 L06AR LSS MVOLT

GZ10 USPOM

6" DOWNLIGHT, 3500K COLOR TEMPERATURE, 5000

LUMENS, SEMI-SPECULAR, 0-10 DRIVER DIMS TO 10% 5

YEAR WARRANTY

14 LED 120 RECESSED EXTERIOR 10

T BROWNLEE CEILING WALL ARM

WALL PACK, 4000K COLOR TEMPERATURE, WITH

PHOTOCELL

13 LED 120 WALL EXTERIOR 45

U KIM LIGHTING ELL271 FLOOD LIGHT BY LANDSCAPE 5 LED 120 GRADE EXTERIOR 7

V KIM LIGHTING B30 LED BOLLARD BY LANDSCAPE 17 LED 120 GRADE EXTERIOR 25

W KIM LIGHTING EL807 WALL LIGHT BY LANDSCAPE 16 LED 120 GRADE EXTERIOR 11

X LITHONIA LQM S W 3 R 120/277 AC

EXIT SIGN, WHITE THERMOPLASTIC HOUSING, RED

LETTER, AC ONLY

19 LED 120 WALL GENERAL 4

LIGHTING SCHEDULE NOTES:

1. ALL LAMPS SHALL BE 80+ CRI AND 3500K UNLESS NOTED OTHERWISE

LIGHTING CONTROL DEVICES SCHEDULE

TAG MANUFACTURER CATALOG NUMBER DESCRIPTION QTY

CONTROL

WIRING

MOUNTING

ACUITY WSX PDT WALL SWITCH OCCUPANCY/VACANCY SENSOR AS REQ

120V LINE

VOLTAGE

ELECTRICAL

BOX

ACUITY WSX PDT 2P DUAL RELAY WALL SWITCH OCCUPANCY SENSOR AS REQ

120V LINE

VOLTAGE

ELECTRICAL

BOX

ACUITY nCM PDT 9 CEILING MOUNT, DUAL TECH SENSOR AS REQ CAT5 CEILING

ACUITY nCM 6 CEILING MOUNT PIR HIGH MOUNT AS REQ CAT5

ELECTRICAL

BOX

ACUITY nPODM nLIGHT PUSH-BUTTON SWITCH, 1 CHANNEL AS REQ CAT5

ELECTRICAL

BOX

ACUITY nPODM 4SB nLIGHT PUSH-BUTTON SCENE SWITCH, 4 CHANNEL AS REQ CAT5

ELECTRICAL

BOX

ACUITY nPODM DX nLIGHT DIMMER SWITCH, 1 CHANNEL AS REQ CAT5

ELECTRICAL

BOX

LIGHTING CONTROLS SCHEDULE NOTES:

1. The equipment used for the basis of design is Acuity Brands Controls.

2. Other equipment may be submitted for approval up to 10 working days prior to bid date, to allow for proper evaluation. Submissions within 10 working days prior to bid date will not be evaluated. Equipment is approved through addendum only.

DS

S

S

S

LIGHTING CONTROL DEVICES SCHEDULE

TAG MANUFACTURER CATALOG NUMBER DESCRIPTION QTY

CONTROL

WIRING

MOUNTING

ACUITY nPP16 D

ROOM CONTROLLER, 1-CIRCUIT, 0-10V DIMMING,

16A MAX

AS REQ

120V LINE

VOLTAGE

ELECTRICAL

BOX

ACUITY nCM ADCX SINGLE ZONE, PHOTO SENSOR, CEILING MOUNT AS REQ CAT5

ELECTRICAL

BOX

ACUITY

ARP INTENC16

NLT-16SPR-MVOLT-SC-FM

ARPA PC

nLIGHT LIGHTING CONTROL PANEL, 16-RELAYS, 0-10V DIMMING, FLUSH MOUNTED, EXTERIOR

PHOTOCELL ACCESSORY

120V LINE

VOLTAGE

SURFACE

ACUITY nPP16 D ER

EMERGENCY LIGHTING CONTROLLER, 1-CIRCUIT,

0-10V DIMMING, 16A MAX

AS REQ CAT5

ELECTRICAL

BOX

LIGHTING CONTROLS SCHEDULE NOTES:

1. The equipment used for the basis of design is Acuity Brands Controls.

2. Other equipment may be submitted for approval up to 10 working days prior to bid date, to allow for proper evaluation. Submissions within 10 working days prior to bid date will not be evaluated. Equipment is approved through addendum only.

RC1

LCP

ER

OS

OS

P

D

LV

MS#

XS2

XS

NOT TO SCALEA

TYPE "A" - RECESSED

DOWNLIGHT

NOT TO SCALEB

TYPE "B" - 24 INCH VANITY

NOT TO SCALEF D

TYPE "D" - 2X4

RECESSED TROFFER

NOT TO SCALEC

TYPE "C" - 36 INCH DRUM

PENDANT

TYPE "F" - 8 INCH

CYLINDER PEDANT

G

NOT TO SCALE

H

NOT TO SCALE

TYPE "H" - RECTANGULAR

WALL SCONCE

TYPE "G" - 4 FT STRIP

WITH WIREGUARD

K

NOT TO SCALE

TYPE "K" - 4 FT LINEAR

SUSPENDEDN

NOT TO SCALE

TYPE "N" - 19 LIGHT

CHANDELIER

T

NOT TO SCALE

TYPE "T" - WALL PACK

X

NOT TO SCALE

TYPE "X" - LED EXIT

LIGHT WALL MOUNTED

P

NOT TO SCALE

TYPE "P" - CEILING FAN

Q

NOT TO SCALE

TYPE "Q" - LED WING RAIL

CEILING WALL ARMS

NOT TO SCALE

TYPE "S" - LED

RECESSED MOUNTED

R

NOT TO SCALE

TYPE "R" - POST TOP

SITE LIGHTING M

NOT TO SCALE

TYPE "M" - STAIRS

1. 4" DOWNLIGHT.

2. FIXTURE SHALL PROVIDE 1575 LUMENS.\

3. 2700K COLOR TEMPERATURE.

4. 5 - YEAR LIMITED WARRANTY.

5. MADE IN THE USA.

NOT TO SCALE

1. 26" VANITY FIXTURE.

2. BRUSHED NICKEL FINISH.

3. 3000K COLOR TEMPERATURE.

4. (3) LAMP, 10WATT PER LAMP.

5. 5 - YEAR LIMITED WARRANTY.

6. MADE IN THE USA.

1. 36" DIAMETER DRUM PENDANT.

2. COLOR BY ARCHITECT.

3. FIXTURE SHALL PROVIDE 5877 LUMENS.

4. 3500K COLOR TEMPERATURE.

5. 5 - YEAR LIMITED WARRANTY.

6. MADE IN THE USA.

1. 2X4 TROFFER WITH CURVED LENS.

2. FIXTURE SHALL PROVIDE 4800 LUMENS.

3. FIXTURE SHALL BE DIMMABLE.

4. 5 - YEAR LIMITED WARRANTY.

5. MADE IN THE USA.

1. 3500K COLOR TEMPRETURE.

2. FIXTURE SHALL PROVIDE 5,000 LUMENS.

3. 8" CYLINDER DOWNLIGHT.

4. CLEAR TRIM COLOR

5. SEMI- SPECULAR FINISH.

6. 5 - YEAR LIMITED WARRANTY.

7. MADE IN THE USA.

1. FULLY DIMMABLE.

2. FIXTURE SHALL PROVIDE 3278 LUMENS.

3. 2700K COLOR TEMPERATURE.

4. 5 - YEAR LIMITED WARRANTY.

5. MADE IN THE USA.

1. LINEAR SUSPENDED FIXTURE.

2. FIXTURE SHALL PROVIDE 750 LUMEN/FT.

3. 3500K COLOR TEMPERATURE.

4. 5 - YEAR LIMITED WARRANTY.

5. MADE IN THE USA.

1. RECTANGULAR ADA SCONCE.

2. WASHABLE ACRYLIC RESIN.

3. 3500K COLOR TEMPERATURE.

4. FIXTURE SHALL BE DIMMABLE.

5. 5 - YEAR LIMITED WARRANTY

6. MADE IN THE USA.

1. 4' STRIP LED.

2. FLAT DIFFUSE LENS WITH 48" WIREGAURD.

3. FIXTURE SHALL PROVIDE 5,000 LUMENS.

4. 3500K COLOR TEMPERATURE.

5. 5 - YEAR LIMITED WARRANTY.

6. MADE IN THE USA.

1. 4000K COLOR TEMPERATURE.

2. FIXTURE SHALL HAVE INTEGRAL PHOTOCELL.

3. 5 - YEAR LIMITED WARRANTY.

4. MADE IN THE USA.

5. WEATHERPROOF.

1. EXIT SIGN.

2. MULTI-VOLT.

3. WHITE THERMOPLASTIC HOUSING.

4. RED LETTER, AC ONLY.

5. WEATHERPROOF.

6. 5- YEAR LIMITED WARRANTY.

7. MADE IN THE USA.

1. 52" HAIK OUTDOOR CEILING FAN.

2. COCOA WOODGRAIN.

3. UNIVERSAL MOUNTING.

4. OUTDOOR LIGHT KIT.

5. 5 - YEAR LIMITED WARRANTY.

6. MADE IN THE USA.

1. SINGLE RAIL

2. RAIL LENGTH OF 48"

3. WALL ARM MOUNTED

4. ARM LENGTH OF 6"

5. 2700K COLOR TEMPERATURE.

6. 5 - YEAR LIMITED WARRANTY.

7. MADE IN THE USA.

1. 6" ROUND DOWNLIGHT

2. FIXTURE SHALL PROVIDE 5000 LUMENS.

3. SEMI-SPECULAR FINISH.

4. MULTI-VOLT OPTION.

5. 3500K COLOR TEMPERATURE.

6. 5 - YEAR LIMITED WARRANTY.

7. MADE IN THE USA.

1. DARK SKY FRIENDLY

2. FIXTURE SHALL PROVIDE 3100 LUMENS.

3. TYPE III DISTRIBUTION.

4. 120-277-VOLT OPTION.

5. 4000K COLOR TEMPERATURE.

6. PHOTOCELL.

7. 5 - YEAR LIMITED WARRANTY.

8. MADE IN THE USA.

1. 4' STRIP LED.

2. FLAT DIFFUSE LENS WITH 48" WIREGAURD.

3. FIXTURE SHALL PROVIDE 5,000 LUMENS.

4. 3500K COLOR TEMPERATURE.

5. 5 - YEAR LIMITED WARRANTY.

6. MADE IN THE USA.

7. DUAL TECHNOLOGY OCCUPANCY SENSOR.

LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS

LUMINAIRE REQUIREMENTS LUMINAIRE REQUIREMENTS

(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE

EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED

DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER

SHEET GI000.

DEDUCT ALTNERATIVE #6 : ELIMINATE LANDSCAPE

DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH

DEDUCT ALTNERATIVE #10 : ELIMINATE SMALL PORCH-A

DEDUCT ALTNERATIVE #11 : ELIMINATE SMALL PORCH-B

DEDUCT ALTERNATIVE NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:2

A M

E-502

ELECTRICAL DETAILS

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

DEDUCT #6 AND #9-11

Revisions: Date:

FS TS

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

NEXTSPEED ASCENT 10G

2625 2827 3029 363332 3534 3837 4039 45434241 44 484746

721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23

B ST

F

S

SD

COMMUNICATIONS SYSTEM RISER KEYNOTES

1. SEE SPECIAL SYSTEMS FLOOR PLAN FOR NUMBER OF DEVICES, TYPICAL. PROVIDE RJ45

DATA JACK. FOR RESIDENTIAL UNITS EACH DATA DROP SHALL HAVE 6 ACTIVE PORTS; FOR

ALL OTHER AREAS EACH DATA DROP SHALL HAVE 6 ACTIVE PORTS WITH THE FOLLOWING

CRITERIA:

A) BLUE TOP LEFT (FOR TELEPHONE)

B) GREEN TOP RIGHT (FOR TELEPHONE)

C) RED MIDDLE LEFT (DATA BACK TO PATCH PANELS)

D) YELLOW MIDDLE RIGHT (DATA BACK TO PATCH PANELS)

E) BLANKED-OFF BOTTOM LEFT

F) GREY BOTTOM RIGHT (DATA BACK TO PATCH PANELS).

2. 1-1/2" EMT CONDUIT TO CABLE TRAY, PROVIDE CAT6A CABLE FROM OUTLET BOX TO IT

CLOSET 105, TYPICAL. FOR ALL CONDUIT TO CABLE TRAY TRANSITIONS, SEE SHEET B2/A721.

3. IT RACK IN IT CLOSET 105.

4. PROVIDE NETWORK RJ45, 48 PORT, CAT6A, PATCH PANELS AS REQUIRED IN RACK.

5. LADDER TYPE CABLE TRAY INSTALLED IN ACCESSIBLE CEILING. PROVIDE SEPARATE CABLE

TRAY FOR FIRE ALARM AND NURSE CALL SYSTEM TO DIVIDE LIFE SAFETY LOW VOLTAGE

EQUIPMENT. SEE SPECIAL SYSTEMS FLOOR PLAN FOR MORE INFORMATION, TYPICAL.

6. PROVIDE EMT CONDUIT SLEEVES, HILTI CP653 4" SPEED SLEEVE…