This document provides details for a federal contract opportunity to design and construct a new community living center. The solicitation number is 36C77623R0156 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It seeks proposals to build a new community living center at the Montrose VA medical center to provide housing and support services for veterans. Offerors should submit proposals by the response date listed in the solicitation document. The opportunity type is for design/build construction services with an expected award date in 2023 upon completion of evaluations. The related file is technical drawings for the electrical systems of the proposed new building.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE
SERVER ROOM 214, FIBER A
NOT TO SCALE
BLDG2 TO BLDG3
SERVER ROOM FIBER
NOT TO SCALE
B16 SERVER ROOM
ELECTRONICS FIBER
RACK BLDG2
NOT TO SCALE
SERVER ROOM 214, FIBER
NOT TO SCALE
NOT TO SCALE
BUILDING #20 FACP
NOT TO SCALE
BUILDING #19 FACP
NOT TO SCALE
TELE CLOSET 1B
- BUILDING 3
EMH #24
EMH #12
EMH #11
EMH #9
EMH #8
EMH #7
EMH #1
EMH #2
EMH #3
(TYP)
BUILDING 7
BUILDING 6
BUILDING 19
BUILDING 20
A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT
ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,
ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO
COMMENCING ANY WORK ON THIS SITE.
B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW
VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION
LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS
PRIOR TO COMMENCING ANY WORK ON THIS SITE.
C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY
UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING
ON THIS SITE.
D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
STRUCTURAL ENGINEER FOR CONDUIT OPENING IN STRUCTURAL
SUPPORT.
E. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE
RATED NEMA 3R.
GENERAL NOTES
A. FROM EXISTING TELECOMMUNICATION MANHOLE - EMH #3, PULL
NEW FIBER USING EXISTING SPARE CONDUIT STUBBED UP IN
TELEPHONE CLOSET 1B.
B. CORE DRILL AT THE FOLLOWING LOCATION:
1. FIRST FLOOR SLAB IN CLOSET 1A THROUGH CLOSET 101A.
2. SECOND FLOOR SLAB IN CLOSET 101A THROUGH CLOSET 201.
C. PULL NEW FIBER FROM TELEPHONE CLOSET 1B THROUGH NEWLY
CREATED CORE DRILLS UP TO SECOND FLOOR CLOSET 201.
D. RUN NEW FIBER THROUGH CORRIDORS 2467 AND 247Z TO
TERMINATION LOCATION, SECOND FLOOR SERVER ROOM, ROOM
214.
BUILDING 3 GENERAL NOTES
A. CONTRACTOR SHALL PROVIDE A NEW STAND ALONE FIRE ALARM
CONTROL PANEL.
B. PROVIDE NEW (2) ANNUNCIATOR PANELS; (1) IN BUILDING #19 AND
(1) IN BUILDING #20. CONTRACTOR IS RESPONSIBLE FOR ALL
ELECTRICAL CONNECTIONS, FIRE ALARM CONNECTION TIE IN,
TESTING AND CERIFICATION FOR BOTH LOCATIONS.
1. BUILDING #19 - LOCATE ADJACENT TO EXISTING FACP ON
GROUND LEVEL. COORDINATE WITH COR PRIOR TO
INSTALLATION.
2. BUILDING #20 - LOCATE ADJACENT TO EXISTING FACP ON
GROUND LEVEL. PROVIDE TROUBLE ALARM AND MONITOR
MODULE. COORDINATE WITH COR PRIOR TO INSTALLATION.
CLC'S FIRE ALARM REQUIREMENTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:3
A M
EY100
SPECIAL SYSTEMS RENOVATION OVERALL SITE
PLAN
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
SPECIAL SYSTEMS RENOVATION OVERALL SITE PLAN
Revisions: Date:
KEYNOTES
1. NEW CLC BUILDING.
2. APPROXIMATE LOCATION OF IT CLOSET 105. SEE SHEET EY102A
FOR ADDITIONAL INFORMATION.
3. NEW CONCRETE ENCASED DUCTBANK WITH 100 PAIR
TELEPHONE CABLE, 48 STRAND SINGLE MODE FIBER FOR IT, 48
STRAND SINGLE MODE FIBER FOR ELECTRONICS AND PULL
STRINGS TO EXISTING MANHOLE, EMH#24.
4. EXISTING MANHOLE, EMH.
5. RUN NEW 100 PAIR TELEPHONE CABLE FIBER AND PULL STRINGS
IN EXISTING CONCRETE ENCASED DUCTBANK TO TELEPHONE
SWITCHGEAR ROOM 14 LOCATED IN BUILDING 2. PULL AND
TERMINATE TO FIBER RACK.
6. APPROXIMATE LOCATION OF EXISTING TELEPHONE SWITCHGEAR
IN BUILDING 2, ROOM 14.
7. NEW CLC'S FIRE ALARM SYSTEM SHALL TIE INTO EXISTING FIRE
ALARM LOOP SYSTEM VIA SPARE FIBER LOCATED IN BUILDING 6.
COORDINATE EXACT LOCATION WITH VA COR PRIOR TO
INSTALLATION. PULL NEW MULTIMODE FIBER IN 2" CONDUIT FOR
CLC'S FIRE ALARM SYSTEM TO BUILDING 6 THROUGH
CONNECTING CORRIDOR. CONTRACTOR SHALL HIRE ONE OF THE
FOLLOWING FIRE ALARM VENDORS TO PERFORM ALL
NECESSARY FIRE ALARM DESIGNS, INSTALLATION,
PROGRAMMING, TESTING AND CERTIFICATION:
1) SIRINA FIRE PROTECTION (516) 942-0400
2) AFA PROTECTIVE SYSTEMS (914) 347-5481
3) HURTVET SUBCONTRACTING (251) 648-3210
8. RUN NEW 48 STRAND SINGLE MODE FIBER WITH PULL STRINGS IN
EXISTING CONCRETE ENCASED DUCT BANK TO SECOND FLOOR
SERVER ROOM IN BUILDING 3. ENSURE A MINIMUM OF 200 L.F. OF
FIBER IS PROVIDED FROM ENTRY POINT OF BUILDING TO SERVER
ROOM LOCATION.
9. BUILDING #19 - FIRE DEPARTMENT. PROVIDE ANNUNCIATOR
PANEL PROGRAMMED FOR ALARM AND TROUBLE SIGNALS. IT IS
THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE
ANNUNCIATORS PANEL RECIEVE POWER BY TYING
CIRCUIT TO EXISTING BUILDING'S FACP CIRCUIT; PROVIDE NAC
PANEL AS REQUIRED. SEE "CLC FIRE ALARM REQUIREMENTS"
FOR ADDITIONAL INFORMATION.
10. BUILDING #20 - BOILER PLANT. PROVIDE ANNUNCIATOR PANEL
PROGRAMMED FOR TROUBLE SIGNALS. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THE
ANNUNCIATORS PANEL RECIEVE POWER BY TYING CIRCUIT TO
EXISTING BUILDING'S FACP CIRCUIT; PROVIDE NAC PANEL AS
REQUIRED. SEE "CLC FIRE ALARM REQUIREMENTS" FOR
ADDITIONAL INFORMATION.
05/09/2022
F
F
SD
SD
SD
SDSD
SD
SD
SD
SD
S
S
SD
S
SS
S
S
S
S S
S
S
B
B
B
B B B
B
B
B
B
B
B
B
B
S
S
S
S
S
S
S
SSS
S
S
S
S
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
SD
S
C R F
CR
CR C
R
C R
C R
C R
CR
DH
DH
ES
E S
D C
DC
D C
D C
DC
E S
E S
ES
ES DC
E S
D C
FS
TS
D E
S
CR
ES DC
E S
D C
C R
ES
DC
C R
CR
CR
ES DC ES DC
CR CR
C R
S
FS
TS
R L
D C
E S
DC ES
RL
RL
RL R
L
R L
R L
R L
RL
RL
RL
RLRL
D C
E S
R L
D E
R L
WAP
WAP
WAP
SD
S
S
S
S
S
PIV
DC
DCES
ES RL
RL CR
C R
A
PORCH-A
LIVING ROOM
DINING
PANTRY
125A
ELEC
RESIDENT 6
SITTING ALCOVE
4/5/6/7A
CORRIDOR
120C
MEDS
STERILE SUPPLY
STORAGE
HALLWAY
209C
SOILED
CRASH CART
IT CLOSET
TLT 6
119A
TLT 5
118A
RESIDENT 5
RESIDENT 4
TLT 4
117A
LN
TLT 3
115A
SITTING ALCOVE
2/3A
RESIDENT 3
RESIDENT 2
RESIDENT 1
TLT 2
114A
LN
TLT 1
110A
SALON
102 LOBBY
FOYER
ACTIVITY
CENTRAL KITCHEN
FAMILY TOILET
WHEELCHAIR/
STRETCHER STRG
MECHANICAL
CLC WALKWAY
PT/KT
MAIN PORCH
RESIDENT 14
RESIDENT 13
SITTING ALCOVE
13/14A
LN
TLT 14
134ASITTING ALCOVE
11/12A
LN
TLT 13
133A
TLT 12
131A
RESIDENT 12
RESIDENT 11
RESIDENT 10
TLT 10
128A
TLT 11
130A
LN
RESIDENT 9
TLT 9
127A
TLT 8
126A
RESIDENT 8
SITTING ALCOVE
8/9/10A
1(TYP)
1 (TYP)
STORAGE
STORAGE
CLEAN
PUBLIC TOILET
HAC
CHARGING A
M A
T C
H
LI
N E
S
E : 1
/E Y
1B
TLT 7
120A
RESIDENT 7
(BARIATRIC)
CORRIDOR 1A
SITTING ALCOVE
1A
CORRIDOR
122C
WP
4K
WP
4K
WP
WP
WP
SCREENING
VESTIBULE
CORR
STAIRS
144B
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
DEDUCT #814
A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF
ALL RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED
RATING ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND
MATERIALS SHALL MEET THE UL RATING OF THE RATED WALLS,
CEILINGS AND SLABS ASSEMBLY. CONTRACTOR SHALL PROVIDE
AN ASSEMBLY INSTALLED IN ACCORDANCE WITH THE RATED
APPLICATION.
B. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL
CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO
ORDERING/INSTALLATION.
C. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE
MECHANCIAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE
THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN
THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE
ELECTRICAL CONTRACTOR.
D. ALL LOW VOLTAGE WIRING SHALL BE ROUTED BACK TO IT ROOM.
NO CAT6 CABLE DEVICES SHALL EXCEED 295' IN LENGTH.
E. VOICE EVACUATION SHALL BE PART OF THE FIRE ALARM SYSTEM.
COORDINATE ALL REQUIREMENTS WITH VA PRIOR TO
INSTALLATION.
F. ALL TELEVISION COMMUNICATION OUTLETS SHALL BE MOUNTED
60" AFF UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL
ELEVATION PLANS FOR ADDITIONAL INFORMATION.
G. CONTRACTOR SHALL PROVIDE PILLOW SPEAKER AT EACH
RESIDENTIAL BED. PILLOW SPEAKER SHALL ALSO CONTROL TV.
PROVIDE WIRE AS REQUIRED. INSTALL PER MANUFACTURER'S
INSTALLATION MANUAL.
GENERAL NOTES
FIRE ALARM LEGEND
MANUAL PULL STATION (46" AFF)F
S
S
SPEAKER (80" AFF)
STROBE LIGHT (80" AFF)
S SPEAKER/STROBE (80" AFF)
SMOKE DETECTOR - CEILING MOUNTEDSD
TS
FS
DH
TAMPER SWITCH
FLOW SWITCH
MAGNETIC DOOR HOLDER (72" AFF)
DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING
TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON
END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6
PORTS, CAT6A, RJ45
WIRELESS ACCESS POINT - GC PROVIDE/INSTALL
CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);
PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE
CEILING. PROVIDE INSULATED NYLON BUSHING ON END
OF CONDUIT FOR PROTECTION OF WIRE
CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE
DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER
RING, 3/4" CONDUIT WITH PULL STRING TO DOOR
CONTROLLER
DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
ELECTRIC STRIKE, FAIL SECURE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
CCTV CAMERA FIXED - PROVIDE DOUBLE GANG BACK
BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT
WITH PULL STRING TO ACCESSIBLE CEILING
CR
DC
ES
N NURSE STATION (46" AFF)
BED NURSE CALL WITH PILLOW
SPEAKER JACK (46" AFF)
TOILET NURSE CALL (46" AFF)
ND
WP - WEATHERPROOF SHOWER NURSE
CALL (46" AFF)
NURSE CALL DUTY STATION (46" AFF)
NURSE CALL MASTER
B
T
S
CCTV CAMERA 360 DEGREES - PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;
WP = WEATHERPROOF
WP
4K
CARD ACCESS LEGEND
NURSE CALL LEGEND
COMMUNICATION LEGEND
SURVEILLENCE LEGEND
CARD READER RELAY; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
RL
WAP
SPEAKER (PUBLIC ADDRESS)S
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
B6 WALKWAY
(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE
EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED
DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER
SHEET GI000.
DEDUCT ALTNERATIVE #4 : ELIMINATE WORK AT B6 CORRIDOR
DEDUCT ALTNERATIVE #8 : ELIMINATE NETWORK VIDEO RECORDER
(NVR) SECURITY
DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH
DEDUCT ALTNERATIVE #10 : ELIMINATE SMALL PORCH-A
DEDUCT ALTERNATIVE NOTES
N
KEY PLAN
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:4
A M
EY101A
SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA
A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
SPECIAL SYSTEMS - LEVEL 1 - AREA A
KEYNOTES
1 FIRE ALARM ZONE.
2 PUSH PLATE FOR DOUBLE SWING DOORS.
3 DELAY-EGRESS DOOR. CONTRACTOR SHALL PROVIDE FIRE ALARM
RELAY FOR DELAY EGRESS LOCK. CARD READER SHALL BE INSTALLED
TO BYPASS DELAY-EGRESS DOOR.
4 CARD READER AND PUSH BUTTON PEDESTAL. VERIFY EXACT LOCATION
WITH VA PRIOR TO INSTALLATION.
5 2"Dx4"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
6 2"Dx12"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
7 2"Dx22"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
8 2"Dx6"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
9 PROVIDE (6) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE
RATED WALLS/HARD CEILING.
10 PROVIDE (1) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE
RATED WALLS/HARD CEILING.
11 FLOOR MOUNTED DATA SERVICING SECURITY SCREEN EQUIPMENT.
COORDINATE EXACT LOCATION AND REQUIREMENTS WITH VA PRIOR
TO INSTALLATION.
12 PROVIDE (4) CAT6E CABLES FROM IT CLOSET TO THIS LOCATION FOR
WAP, WIRELESS ACCESS POINT. WAP SHALL BE INSTALLED BY VA'S IT
CONTRACTOR AT A LATER DATE.
13 CONTRACTOR SHALL PROVIDE SERVER RACK AND PATCH PANELS
LOCATED IN IT CLOSET. VERIFY MAKE/MODEL/QUANTITY WITH VA.
CONTRACTOR SHALL ENSURE ALL SYSTEMS ARE FULLY FUNCTIONING
PRIOR TO TURN OVER. SEE SERVER RACK ELEVATIONS FOR
ADDITIONAL INFORMATION.
14 NETWORK VIDEO RECORDER (NVR) SECURITY LOCATED IN IT CLOSET.
REMOVE AS REQUIRED UNDER DEDUCT #8.
1/8" = 1'-0"
SPECIAL SYSTEMS FLOOR PLAN - COVERED WALKWAY
DEDUCT #10
DEDUCT #9
MATCHLINE
SEE: 2/EY101A
MATCHLINE
SEE: 1/EY101A
DEDUCT #4
Revisions: Date:
DEDUCT #8
SD
SD
SD
SD
SD
SDSD
S
S
FS
S
S
S
S
S
S
S
S
B
B
B
B
B
B
B
B
B
B
B
B
B
B
S
S
S
S
S
S
S
S
S
S
S
SS
S
T
T
T
T
T
T
T
T
T
T
T
T
T
T
SD
SD
C R
C R
CR
CR
C R
DH
DH
SD
E S
ESD
C
DC
E S
ES
DC
D C
D C
C R
E S
ES
CR
DC
E S
D C
C R
R L
R L
R L
RL
RL
RL
CR CRDCDC
ES
RL
R L
D C
E S
R L
D E
D E
N D
WAP
WAP
WAP
SD
S
S
S
S S
S
RL
ES
ES
CORRIDOR
164C
STAFF LOUNGE
STAFF TOILET/
SHOWER
HOTELING
ADMIN HALL-B
OFFICE
OFFICE
OFFICE
HALLWAY
192C
CLEAN
SOILED
MEDS
CRASH CART B
ELEC
DINING
CHARGING B
PANTRY
168A
LN
TLT 14
183A
TLT 13
181A
SITTING ALCOVE
12/13B
SITTING ALCOVE
10/11B
SITTING ALCOVE
6/7/8/9B
RESIDENT 7
RESIDENT 14
RESIDENT 13
RESIDENT 12
TLT 12
180A
TLT 11
178A
LN
LN
TLT 10
175A
TLT 9
173A
RESIDENT 11
RESIDENT 10
RESIDENT 9
RESIDENT 8
TLT 7
171A
TLT 8
172A
LIVING ROOM
PORCH B
RESIDENT 5
SITTING ALCOVE
3/4/5B
TLT 5
164A
TLT 4
163A
RESIDENT 4
RESIDENT 3
RESIDENT 2
RESIDENT 1
SITTING ALCOVE
1/2B
LN
TLT 3
162A
TLT 2
160A
TLT 1
159A
LN
EXAM RM
EMERGENCY
POWER
POWER
CONFERENCE
MAIN PORCH
DP
ITFACP EQ1
LS
B
1 (TYP)
1 (TYP)
RESIDENT 6
(BARIATRIC)
TLT 6
170A
HAC
GAS
SITTING ALCOVE
14B
M A
T C
H
LI
N
E : 1
/E Y
1A
CORRIDOR
163C
WP
4K
WP
4K
WP
ATS-LS
LCP
NCT
EQ
150A
ENCLOSED
CKT BKR
1000A
ENCLOSED
CKT BKR
WP
ATS-DP
ATS-EQ
400A
ENCLOSED
CKT BKR
MDP
NL
PT/KT
7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
8.6
AA
FIRE ALARM LEGEND
MANUAL PULL STATION (46" AFF)F
S
S
SPEAKER (80" AFF)
STROBE LIGHT (80" AFF)
S SPEAKER/STROBE (80" AFF)
SMOKE DETECTOR - CEILING MOUNTEDSD
TS
FS
DH
TAMPER SWITCH
FLOW SWITCH
MAGNETIC DOOR HOLDER (72" AFF)
DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING
TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON
END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6
PORTS, CAT6A, RJ45
WIRELESS ACCESS POINT - GC PROVIDE/INSTALL
CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);
PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE
CEILING. PROVIDE INSULATED NYLON BUSHING ON END
OF CONDUIT FOR PROTECTION OF WIRE
CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE
DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER
RING, 3/4" CONDUIT WITH PULL STRING TO DOOR
CONTROLLER
DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
ELECTRIC STRIKE, FAIL SECURE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
CCTV CAMERA FIXED - PROVIDE DOUBLE GANG BACK
BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT
WITH PULL STRING TO ACCESSIBLE CEILING
CR
DC
ES
N NURSE STATION (46" AFF)
BED NURSE CALL WITH PILLOW
SPEAKER JACK (46" AFF)
TOILET NURSE CALL (46" AFF)
ND
WP - WEATHERPROOF SHOWER NURSE
CALL (46" AFF)
NURSE CALL DUTY STATION (46" AFF)
NURSE CALL MASTER
B
T
S
CCTV CAMERA 360 DEGREES - PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;
WP = WEATHERPROOF
WP
4K
CARD ACCESS LEGEND
NURSE CALL LEGEND
COMMUNICATION LEGEND
SURVEILLENCE LEGEND
CARD READER RELAY; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
RL
WAP
SPEAKER (PUBLIC ADDRESS)S
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
A. CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFICATION OF
ALL RATED WALLS, CEILINGS AND SLABS AND THEIR SPECIFIED
RATING ON THE ARCHITECTURAL DRAWINGS. ALL DEVICES AND
MATERIALS SHALL MEET THE UL RATING OF THE RATED WALLS,
CEILINGS AND SLABS ASSEMBLY. CONTRACTOR SHALL PROVIDE
AN ASSEMBLY INSTALLED IN ACCORDANCE WITH THE RATED
APPLICATION.
B. ELECTRICAL CONTRACTOR SHALL COORDINATE ELECTRICAL
CHARACTERISTICS AND REQUIREMENTS OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO
ORDERING/INSTALLATION.
C. ALL CONTROL WIRING SHALL BE INCLUDED AS PART OF THE
MECHANCIAL WORK. MECHANICAL CONTRACTOR SHALL ENSURE
THAT ELECTRICAL INTERFACE DEVICES THAT ARE NECESSARY IN
THE ELECTRICAL COMPONENT ARE COORDINATED WITH THE
ELECTRICAL CONTRACTOR.
D. ALL LOW VOLTAGE WIRING SHALL BE ROUTED BACK TO IT ROOM.
NO CAT6 CABLE DEVICES SHALL EXCEED 295' IN LENGTH.
E. VOICE EVACUATION SHALL BE PART OF THE FIRE ALARM SYSTEM.
COORDINATE ALL REQUIREMENTS WITH VA PRIOR TO
INSTALLATION.
F. ALL TELEVISION COMMUNICATION OUTLETS SHALL BE MOUNTED
60" AFF UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL
ELEVATION PLANS FOR ADDITIONAL INFORMATION.
G. CONTRACTOR SHALL PROVIDE PILLOW SPEAKER AT EACH
RESIDENTIAL BED. PILLOW SPEAKER SHALL ALSO CONTROL TV.
PROVIDE WIRE AS REQUIRED. INSTALL PER MANUFACTURER'S
INSTALLATION MANUAL.
GENERAL NOTES
(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE
EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED
DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER
SHEET GI000.
DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH
DEDUCT ALTNERATIVE #11 : ELIMINATE SMALL PORCH-B
DEDUCT ALTERNATIVE NOTES
N
KEY PLAN
AREA B
(EAST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:5
A M
EY101B
SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA
B
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA B
KEYNOTES
1 FIRE ALARM ZONE.
2 DELAY-EGRESS DOOR. CONTRACTOR SHALL PROVIDE FIRE ALARM
RELAY FOR DELAY EGRESS LOCK. CARD READER SHALL BE INSTALLED
TO BYPASS DELAY-EGRESS DOOR.
3 2"Dx6"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
4 2"Dx4"W LADDER TYPE CABLE TRAY. COORDINATE MOUNTING AND
ROUTING WITH ABOVE CEILING UTILITIES.
5 PROVIDE (1) 4" CONDUITS FOR LOW VOLTAGE WIRING THROUGH FIRE
RATED WALLS/HARD CEILING.
6 CARD READER AND PUSH BUTTON PEDESTAL. VERIFY EXACT LOCATION
WITH VA PRIOR TO INSTALLATION.
7 PROVIDE (4) CAT6E CABLES FROM IT CLOSET TO THIS LOCATION FOR
WAP, WIRELESS ACCESS POINT. WAP SHALL BE INSTALLED BY VA'S IT
CONTRACTOR AT A LATER DATE.
DEDUCT #9
DEDUCT #11
Revisions: Date:
PRIMARY SWITCH COMPARTMENT
CONCRETE PAD
GRADE
PAD LOCKABLE
DOOR HANDLE
WEATHERPROOF STAINLESS
STEEL ENCLOSURE
SECONDARY SWITCH
COMPARTMENT
SWITCH COMPARTMENT
3/4" x 10' COPPER CLAD
GROUND ROD, TYP OF
4, ONE AT EACH
CORNER OF PAD.
COMPARTMENT GROUND
DUAL-PURPOSE BARRIER
SPRING LATCH
HOLDER
SWITCH
GROUND STUDS
UP FRONT FOR
CLEAR ACCESS
SWITCH
TERMINALS
SURGE
ARRESTERS
SWITCH-SIDE
REMOVABLE
INTERPHASE
BARRIER
PRIMARY COMPARTMENT
CONCRETE PAD
GRADE
PRIMARY SERVICE
CONCRETE ENCASED
CONDUITS
SECONDARY SERVICE
CONCRETE ENCASED
CONDUITS
SECONDARY COMPARTMENT
SECTION A-A
A
A
GROUNDING DETAIL
GROUND
BAR
NEUTRAL
BAR
CATV FA SEC
ELEC
METER
GROUND
BAR
NEUTRAL
BAR
GENERATOR GROUNDING AND NEUTRAL DETAILB
N
N
G
GEN
N
LOAD
208/120V, 3-PH, 4W
1. TRANSFER SWITCH CONTACTS SHALL BE OF
THE OPEN TYPE AND SHALL BE ACCESSIBLE
FOR INSPECTION AND REPLACEMENT.
MAIN
EQUIPMENT
GROUNDING
CONDUCTOR
EQUIPMENT
GROUNDING
CONDUCTOR 4-POLE
AUTOMATIC
TRANSFER
SWITCH
NEUTRAL-GROUND BOND IN MDP
N
GND
LUG
GENERATOR NOT A
SEPARATELY
DERIVED SYSTEM
MAIN PANEL
NOTE:
SERVICE EQUIPMENT
EQUIPMENT
GROUNDING
CONDUCTOR OR
SUPPLY-SIDE
BONDING JUMPER
A N.T.S.
N.T.S.
TWO HOLE STRAP OR
CADWELD CONNECTION TYPE
''LK'', TYPICAL
MOUNTING BRACKETS
FIBERGLASS INSULATORS
4"
MIN.
NOTES:
1. PREDRILLED BOLT HOLE SIZE AND SPACING AS REQUIRED FOR INDICATED TERMINATIONS .
2. PROVIDE LENGTH SUFFICIENT FOR ALL INDICATED TERMINATIONS AND 20% SPARE MOUNTING
SPACE. CONNECTIONS SHALL UTILIZE TWO HOLE COMPRESSIONS CONNECTOR.
3. GROUND BAR SHALL BE MOUNTED MINIMUM 2" OFF WALL AND 12" AFF.
4. FIBERGLASS INSULATORS SHALL HAVE A MINIMUM DIELECTRIC STRENGTH OF 15kV.
INSULATED COPPER
GROUND CONDUCTOR TO
BUILDING GROUNDING
ELECTRODE CONDUCTOR
C GROUND BUS DETAIL NTS
E 6-WAY DUCTBANK 4" CONDUIT DETAIL NTS
NOTES:
1. TYPICAL FOR WOOD AND METAL STUD ROUGH-IN.
2. PLASTER RINGS NOT SHOW.
3. LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND
MECHANICAL DRAWINGS, AND WITH ALL APPLICABLE SHOP DRAWINGS.
4. IN ACCORDANCE WITH UBC 4304 OUTLETS ON OPPOSITE SIDES OF WALLS OR
PARTITIONS IN THE SAME STUD SPACE MUST BE SEPARATED BY A MIN. OF 24"
HORIZONTAL DISTANCE.
5. TOENAILING OF OUTLET BOXES DIRECTLY TO THE STUDS WILL NOT BE
ACCEPTED.
6. OUTLETS SHOWN TOGETHER ON PLAN SHALL BE INSTALLED TOGETHER.
TYPICAL
WALL
OUTLETS
PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE WITH NEC. SPACING
REQUIREMENTS FOR TYPE OF RACEWAY
REQUIRED.
AS REQUIRED FOR TYPE
OF CONSTRUCTION.
BOX
SUPPORT
TYPICAL
OUTLET
BOX.
D TYPICAL ROUGH-IN NTS
G NTS
61_
MIN.
DEDICATED
ELECTRICAL
SPACES
PERMITTED
LUMINARIE
PERMITTED
PERMITTED
STRUCTURAL
CEILING
SUSPENDED
CEILING
SIDE VIEW FRONT
6' OR
LESS
DEDICATED EQUIPMENT SPACE NOTES:
1. THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE EQUIPMENT AND EXTENDING
FROM THE FLOOR TO A HEIGHT OF 6'-0" ABOVE THE EQUIPMENT OR TO THE
STRUCTURAL CEILING, WHICHEVER IS LOWER, SHALL BE DEDICATED TO THE
ELECTRICAL INSTALLATION. NO PIPING, DUCTS, LEAK PROTECTION APPARATUS OR
OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL INSTALLATION SHALL BE
LOCATED IN THIS ZONE.
2. THE AREA ABOVE THE DEDICATED SPACE SHALL BE PERMITTED TO CONTAIN
FOREIGN SYSTEMS, PROVIDED PROTECTION IS INSTALLED TO AVOID DAMAGE TO
THE ELECTRICAL EQUIPMENT FROM CONDENSATION, LEAKS, OR BREAKS IN SUCH
FOREIGN SYSTEMS.
3. SPRINKLER PROTECTION SHALL BE PERMITTED FOR THE DEDICATED SPACE WHERE
THE PIPING COMPLIES WITH THESE NOTES.
4. A DROPPED, SUSPENDED, OR SIMILAR CEILING THAT DOES NOT ADD STRENGTH TO
THE BUILDING STRUCTURE SHALL NOT BE CONSIDERED A STRUCTURAL CEILING.
DEDICATED ELECTRICAL SPACES
H GENERATOR SYSTEM REQUIREMENTS NTS
F NTSELECTRICAL EQUIPMENT NAMEPLATE
GENERATOR SYSTEM REQUIREMENTS:
NFPA 110 LEVEL---------------------------------------------------------------------- 1
NFPA 110 TYPE------------------------------------------------------------------------ 10
NFPA CLASS----------------------------------------------------------------------------96 (HRS)
GENERATOR SET MODEL--------------------------------------------------------- 350REOZJC
KW @ 130C RISE---------------------------------------------------------------------- 350 KW
KVA @ 0.8 PF--------------------------------------------------------------------------- 438 KVA
VOLTAGE-------------------------------------------------------------------------------- 208/120 VOLTS, 3 PHASE, 60HZ
PEAK MOTOR STARTING KVA @ 35% MAXIMUM
INSTANTANEOUS VOLTAGE DIP------------------------------------------------ 1314 KVA
ALTERNATOR-------------------------------------------------------------------------- 4M4019
FREQUENCY REGULATION------------------------------------------------------- ±0.25%
CONTROLLER MODEL-------------------------------------------------------------- APM603
MUFFLER-------------------------------------------------------------------------------- CRITICAL GRADE MUFFLER
ENCLOSURE---------------------------------------------------------------------------- LEVEL 2 ACOUSTIC ENCLOSURE
ENGINE HP@ 1800 RPM------------------------------------------------------------ 401 kWm
FREQUENCY / SPEED REGULATION------------------------------------------ ISOCHRONOUS
CIRCUIT BREAKER #1 AMPS----------------------------------------------------- 1200A
CIRCUIT BREAKER #2 AMPS----------------------------------------------------- N/A
SHUNT TRIP---------------------------------------------------------------------------- NO
GFI INDICATION----------------------------------------------------------------------- YES
MANUFACTURER/MODEL TANK------------------------------------------------- HIGHLAND TANK PETRO HOPPER HT-1032
TANK SIZE (GAL)---------------------------------------------------------------------- 1,000
ATS MODEL ATS-L-LS-------------------------------------------------------------- KBP-DCVA-0150S
AMPERAGE---------------------------------------------------------------------------- 150A
VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ
NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1
SERVICE ENTRANCE RATED---------------------------------------------------- NO
INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO
ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT
ATS MODEL ATS-L-EQ-------------------------------------------------------------- KBP-DCVA-1000S
AMPERAGE---------------------------------------------------------------------------- 1000A
VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ
NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1
SERVICE ENTRANCE RATED---------------------------------------------------- NO
INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO
ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT
ATS MODEL ATS-L-DP-------------------------------------------------------------- KBP-DCVA-0400S
AMPERAGE---------------------------------------------------------------------------- 400A
VOLTAGE------------------------------------------------------------------------------- 208 /120 VOLTS, 3 PHASE, 60HZ
NEMA TYPE ENCLOSURE--------------------------------------------------------- TYPE 1
SERVICE ENTRANCE RATED---------------------------------------------------- NO
INTEGRAL CIRCUIT BREAKER-------------------------------------------------- NO
ACCESSORIES----------------------------------------------------------------------- (6) PROGRAMMABLE INPUT/OUTPUT
*EQUIPMENT LISTED IS MANUFACTURED BY KOHLER, INC. OF KOHLER, WISCONSIN, FOR THE PURPOSE OF
ESTABLISHING A MINIMUM STANDARD. SUBSTITUTIONS BY GENERAC, CUMMINS/ONAN OR CATEPILLAR AND
ALL EQUIPMENT FURNISHED SHALL BE EQUAL IN EVERY RESPECT TO KOHLER, INCLUDING QUALITY, SPECIFICATIONS, OPERATION, AND FUNCTION TO BE CONSIDERED. THE EQUIPMENT SPACING, ELECTRICAL WIRING, EQUIPMENT MECHANICAL, FUEL AND EXHAUST COMPONENTS, HAVE ALL BEEN SIZED
AND DESIGNED AROUND KOHLER EQUIPMENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY
CHANGE IN BUILDING WORK MADE NECESSARY FOR THE PROPER INSTALLATION AND OPERATION OF ANY
EQUIPMENT OTHER THAN KOHLER WITH OUT ADDITIONAL COST TO THE VA.
FUEL TYPE------------------------------------------------------------------------------ DIESEL
I SECTIONAL SWITCHGEAR BLOCK ENCLOSURE (EXTERIOR)NTS
J SECTIONAL SWITCHGEAR BLOCK ENCLOSURE (INTERIOR) NTS
K CONCRETE PAD WITH CONDUIT PENETRATION NTS
NOTES:
1. AIR ENTRAINED CONCRETE - 4000 PSI AFTER 28 DAYS, MAX AGGREGATE 3/4".
2. STEEL FLOAT FINISH.
3. REINFORCEMENT: TYPE A-305 NEW BILLET STOCK A.S.T.M. GRADE 60.
4. ALL REINFORCING SHALL BE #4 BAR 12" O.C. EACH WAY. WIRE TIE ALL CROSSINGS.
5. IF THE ANTICIPATED FORECAST TEMPERATURE IS 35 DEGREES OR LESS, THE PAD
SHALL BE INSULATED WITH EITHER BLANKETS OR POLY AND STRAW FOR A MINIMUM
OF 3 DAYS.
6. ALL MEMBRANE CURING COMPOUND, MEETING A.S.T.M. C-309, AT MANUFACTURERS
PRESCRIBED RATE AFTER REMOVAL OF FORMS.
7. EDGE TROWEL WITH CHAMFERED OUTSIDE EDGES.
8. A SAFE OPERATING CLEARANCE OF A MINIMUM OF 10'-0" (UNOBSTRUCTED) IS
REQUIRED IN FRONT OF THE EQUIPMENT DOOR. THE DOOR(S) CAN FACE ANY
DIRECTION EXCEPT TOWARDS THE BUILDING.
9. IF NECESSARY, ELECTRICAL CONTRACTOR MAY REMOVE TOP LIP OF FIBERGLASS
GROUND SLEEVE IN THE LOW VOLTAGE SECTION.
10. PRIMARY CONDUIT (WHERE REQUIRED) IS PROVIDED BY CONTRACTOR AND
INSTALLED BY CONTRACTOR.
NOTE: CONTRACTOR TO OBTAIN ALL REQUIRED PERMITTING AND REGISTRATION FOR GENERATOR AND FUEL
TANK AS REQUIRED BY THE LOCAL, STATE, AND GOVERNMENT AGENCIES (NYSDEC, USEPA).
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance
Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in. (102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in.
(610 mm) OC. Additional studs installed to completely frame the opening.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 mm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition
Design. Max area of opening is 352 sq in. (2271 sq cm) with max dimension of 22 in. (559 mm) wide.
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Cable Tray* — Max 18 in. (457 mm) wide by max 6 in. (152 mm) deep open-ladder or solid-back cable tray with channel-shaped side rails formed of 0.065 in. (1.65 mm) thick aluminum or 0.060 in. (1.52 mm) thick steel and with 1-1/2 in. (38 mm) wide by 1 in.
(25 mm) channel shape rungs spaced 9 in. (229 mm) OC or a 0.029 in. (0.74 mm) thick steel solid back, respectively. One cable tray to be installed in the opening. The max annular space between the cable tray and the periphery of the opening shall be min 1
in. (25 mm) to max 7 in. (178 mm) Cable tray to be rigidly supported on both sides of floor or wall assembly.
3. Cables — Aggregate cross-sectional area of cables in cable tray to be max 30 percent of the cross-sectional area of the cable tray. Any combination of the following types and sizes of copper conductor cables may be used:
A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and PVC jacket.
B. 100 pair - No. 24 AWG cable with PVC insulation and jacket.
C. 1/C, 750 kcmil (or smaller) with PVC insulation and jacket.
4. Through-Penetrants — One or more pipe or tube to be installed within the opening. The total number of through-penetrants is dependent on the size of the opening and types and sizes of the penetrants. Any combination of the penetrants described below may be used provided that the following parameters relative to the annular spaces and the spacings between the pipes are maintained. The space between the pipe or tube and the periphery of the opening shall be min 1-1/2 in. (38 mm) to max 9-1/4 in.
(235 mm). Pipe or tube to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of non-metallic or metallic pipes, or tubes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Max 3 in. (76 mm) diam Schedule 40 solid core PVC pipe (or smaller) for use in closed
(process or supply) or vented (drain, waste or vent) piping system.
B. Steel Pipe — Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe.
C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) diam steel conduit.
D. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
E. Copper Tube — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.
4A. Pipe Covering — (Not Shown) Nom 1-1/2 in. (38 mm) thick hollow cylindrical heavy density (min 3.5 pcf) (56kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product.
See Pipe and Equipment Covering and Materials (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a
Flame Spread Index of 25 or less and a Smoke Developed Index of 50 may be used.
5. Cables — Max 1-1/2 in. (38 mm) diam tight bundle of cables installed within the opening and rigidly supported on both surfaces of wall. The space between the cables and periphery of the opening shall range from 1-3/16 in. (30.2 mm) min to a max of 1-1/2
in. (38 mm). Any combination of the following types and sizes of cables may be used:
A. 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. 25 pair — No. 24 AWG cable with PVC insulation and jacket.
C. Type R GU/59 coaxial cable with PVC outer jacket.
D. 24 fiber optic cable with PVC sub unit and outer jacket.
6. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* — Fire Blocks For walls incorporating max 3-5/8 in. (92 mm) steel studs or max 2 (51 mm) by 4
in. (102 mm) wood studs, fire block installed with 5 in. (127 mm) dimension projecting through and centered in opening. For walls constructed of larger steel or wood studs, fire block installed with long dimension passing through and centered in opening. Blocks may or may not be cut flush with both surfaces of wall. When multiple layers of gypsum board are used, blocks may be recessed 1/2 in. (13 mm) from surface of wall. Blocks to be firmly packed in opening. Either one or a combination of the block types specified below may be used.
B. Fill, Void or Cavity Material* — Sealant or Putty - Fill material to be forced into interstices of cables, between cables and cable trays, around each penetrant and where obvious voids are observed to max extent possible on both surfaces of the penetration.
L PENETRATIONS THROUGH RATED WALLS NTS
GROUNDING DETAIL KEYNOTES
1. GROUND BUS BAR LOCATED IN MAIN ELECTRICAL ROOM OR WITHIN
SERVICE ENTRANCE MAIN. 0.25" X 4" X 12" WITH 18 HOLES MINIMUM FOR
EXTERNAL INSTALLATION.
2. GROUNDING TRIAD, 3-3/4" X 10'-0" COPPERCLAD GROUND RODS DRIVEN
INTO GROUND AT LEAST 1 ROD'S LENGTH APART. PROVIDE WITH
INSPECTION TEST WELL.
3. COPPER GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC TABLE
250.66, MINIMUM SIZE #8.
4. SERVICE ENTRANCE MAIN BONDING JUMPER SIZED PER NEC TABLE
250.66. NEUTRAL SHALL ONLY BE BONDED AT SERVICE ENTRANCE, ALL
OTHER NEUTRALS SHALL BE CONSIDERED FLOATING.
5. CONNECTIONS TO BUILDING STEEL SHALL BE BY EXOTHERMIC WELD.
6. CONNECTIONS TO REBAR ENCASED IN CONCRETE SHALL BE BY
EXOTHERMIC WELD.
7. BOND METALLIC COLD WATER PIPE WITHIN 5' - 0" OF ENTERING
BUILDING. CONNECTION SHALL BE MADE WITH NON-CORROSIVE
MATERIAL GROUNDING ELECTRODE CLAMP.
8. SERVICE ENTRANCE NEUTRAL CONDUCTOR.
9. ALL EQUIPMENT ENCLOSURES AND METAL RACEWAYS SHALL BE
GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR SIZED PER
NEC TABLE 250.122.
10. EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122.
11. NEUTRAL CONDUCTOR WITH INSULATED EQUIPMENT GROUNDING
CONDUCTOR TO BRANCH CIRCUIT PANELS/EQUIPMENT.
X
SERVICE ENTRANCE MAIN
BRANCH CIRCUIT PANEL
GRADE
3 3 3
HEM
120/208V, 3PH, 4W
FED FROM MSB BKR. 11
SCA 36,921A 01/03/12
LETTER (FILL) COLOR
EMERGENCY = WHITE
NORMAL - WHITE
INDICATED
VOLTAGE,
NO. OF PHASES,
NO OF WIRES
INDICATES WHERE
THIS EQUIPMENT IS
FED FROM
(TRANSFER
SWITCHES WILL HAVE
TWO LINES.)
CALCULATED
AVAILABLE FAULT
CURRENT
ATTACH
NAMEPLATE
WITH 2 SCREWS
NAMEPLATE COLOR
LIFE SAFETY - YELLOW
CRITICAL - ORANGE
EQUIPMENT - GREEN
NORMAL - BLACK
EMERGENCY - RED
LETTERING
SHALL BE
1/4" HIGH
MASONRY LEVELING
BLOCKS AT BASE SPACERS
#4 REBAR (TYPICAL)
#4 REBAR (TYPICAL)
1'-6" ON CENTER
3" MINIMUM CLEARANCE
FINISHED GRADE
3'-6" MINIMUM
DUCTBANK
MARKING TAPE
3000 P.S.I CONCRETE
4" P.V.C CONDUIT
(TYPICAL)
BASE AND INTERMEDIATE
SPACERS 4'-0" ON CENTER
7 1/2" TO MINIMUM
SEPARATION
LCL C
REFER TO CIVIL PLANS
DETAIL C5 ON SHEET CG506
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:1
A M
E-501
ELECTRICAL DETAILS
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
Revisions: Date:
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION
Fix.
Qty
Lamp Type
VOLTS MOUNTING REMARKS
INPUT
WATTS
A USAI
P4RDF 15L2 27KS M WH NC UNV
D22
4.5" DOWNLIGHT, 1575 LUMENS, 50,000 HOUR L70
RATED LIFE, 5 YEAR WARRANTY, DIMMABLE
323 LED 120 RECESSED
RESIDENT, 0-10V
DIMMING
B BROWNLEE 5853 BN G30 BAC 26" VANITY, (3) 10W GU24LED LAMPS 31 LED 120 SURFACE VANITY 30
C BROWNLEE 2612 36 CC3 NT C49 XXX 35K BAC
36" DIAMETER DRUM PENDANT, COLOR BY ARCHITECT,
5877 LUMENS, 50,000 HOUR L70 RATED LIFE, 5 YEAR
WARRANTY
2 LED 120 PENDANT LIVING ROOM 49
D LITHONIA
2BLT4 48L ADP 120 GZ10 LP835
USPOM
2X4 TROFFER, CURVED LENS, 4800 LUMENS, 60,000 L80
RATED LIFE, 5 YEAR WARRANTY, DIMMABLE
49 LED 120 RECESSED GENERAL 44
F LITHONIA
LDN8CYL 35/80 L0AR LD 120
GZ10 PM DWHG
8" CYLINDER, 8000 LUMENS, 60,000 L70 RATED LIFE, 5
YEAR WARRANTY
35 LED 120 PENDANT CORRIDOR 93
G LITHONIA
CLX L48 5000LM SEF FDL 120
GZ10 35K 80CRI WH USPOM
HC36 WGCLX48
4' STRIP, FLAT DIFFUSE LENS WITH 48" WIREGAURD,
5,000 LUMENS, 100,000 HOUR L70 RATED LIFE, 5 YEAR
WARRANTY
37 LED 120 SURFACE UTILITY 36
H AUBERGE
AU RE R15W 35 9 RE7W14H XX
XX
RECTANGULAR ADA WALL SCONCE, WASHABLE
ACRYLIC RESIN, 100,000 HOUR L70 RATED LIFE, 10
YEAR WARRANTY, DIMMABLE
48 LED 120 SURFACE GENERAL 15
K FOCAL POINT
FSM2LS FL 750LF 35K 1C UNV
LD1 C24 WH
LINEAR SUSPENDED, DIRECT, 750 LUMENS/FT, 61,000
HOUR L70 RATED LIFE, 5 YEAR WARRANTY, DIMMABLE
20 LED 120 SUSPENDED DINING 28
M LITHONIA
CLX L48 5000LM SEF FDL 120
GZ10 35K 80CRI WH USPOM
HC36 WGCLX48 MSDPDT7
4' STRIP, FLAT DIFFUSE LENS WITH 48" WIREGAURD,
5,000 LUMENS, 100,000 HOUR L70 RATED LIFE, 5 YEAR
WARRANTY, DUAL TECHNOLOGY OCCUPANCY SENSOR
37 LED 120 SURFACE STAIRS 36
N TECH LIGHTING GAMBIT 19-LIGHT CHANDELIER FULLY DIMMABLE, LED 3278 LUMENS, 90 CRI, 2700K 1 LED 120 PENDANT SALON 38
P BIG ASS FANS
FR127A S0 F1 0-3H03 02 258
654P010
52" HAIKU OUTDOOR CEILING FAN, COCOA
WOODGRAIN, UNIVERSAL MOUNTING WITH OUTDOOR
LIGHT KIT
4 LED 120 CEILING OUTDOOR 22
Q VODE LIGHTING LED WING RAIL
ART WALL LIGHTING, WALL ARM MOUNTED, 2700K
COLOR TEMPERATURE
6 LED 120 WALL ART LIGHTING 6.14
R ANP LIGHTING LA213 1 P117LD4 D T3 W 40K PC
DARK SKY FRIENDLY, TYPE 3 DISTRIBUTION, 4000K IN
COLOR TEMPERATURE, PHOTOCELL, WHITE
8 LED 120 POLE SITE LIGHTING 117
ANP LIGHTING CB1206 4S15.188 44
15FT, 4" DIAMETER WHITE POLE, SEE SHEET CG503
DETAILS "B5" AND SHEET S202 DETAILS "W" FOR
ADDITIONAL INFORMATION
8 POLE
S LITHONIA
LDN6 35/50 L06AR LSS MVOLT
GZ10 USPOM
6" DOWNLIGHT, 3500K COLOR TEMPERATURE, 5000
LUMENS, SEMI-SPECULAR, 0-10 DRIVER DIMS TO 10% 5
YEAR WARRANTY
14 LED 120 RECESSED EXTERIOR 10
T BROWNLEE CEILING WALL ARM
WALL PACK, 4000K COLOR TEMPERATURE, WITH
PHOTOCELL
13 LED 120 WALL EXTERIOR 45
U KIM LIGHTING ELL271 FLOOD LIGHT BY LANDSCAPE 5 LED 120 GRADE EXTERIOR 7
V KIM LIGHTING B30 LED BOLLARD BY LANDSCAPE 17 LED 120 GRADE EXTERIOR 25
W KIM LIGHTING EL807 WALL LIGHT BY LANDSCAPE 16 LED 120 GRADE EXTERIOR 11
X LITHONIA LQM S W 3 R 120/277 AC
EXIT SIGN, WHITE THERMOPLASTIC HOUSING, RED
LETTER, AC ONLY
19 LED 120 WALL GENERAL 4
LIGHTING SCHEDULE NOTES:
1. ALL LAMPS SHALL BE 80+ CRI AND 3500K UNLESS NOTED OTHERWISE
LIGHTING CONTROL DEVICES SCHEDULE
TAG MANUFACTURER CATALOG NUMBER DESCRIPTION QTY
CONTROL
WIRING
MOUNTING
ACUITY WSX PDT WALL SWITCH OCCUPANCY/VACANCY SENSOR AS REQ
120V LINE
VOLTAGE
ELECTRICAL
BOX
ACUITY WSX PDT 2P DUAL RELAY WALL SWITCH OCCUPANCY SENSOR AS REQ
120V LINE
VOLTAGE
ELECTRICAL
BOX
ACUITY nCM PDT 9 CEILING MOUNT, DUAL TECH SENSOR AS REQ CAT5 CEILING
ACUITY nCM 6 CEILING MOUNT PIR HIGH MOUNT AS REQ CAT5
ELECTRICAL
BOX
ACUITY nPODM nLIGHT PUSH-BUTTON SWITCH, 1 CHANNEL AS REQ CAT5
ELECTRICAL
BOX
ACUITY nPODM 4SB nLIGHT PUSH-BUTTON SCENE SWITCH, 4 CHANNEL AS REQ CAT5
ELECTRICAL
BOX
ACUITY nPODM DX nLIGHT DIMMER SWITCH, 1 CHANNEL AS REQ CAT5
ELECTRICAL
BOX
LIGHTING CONTROLS SCHEDULE NOTES:
1. The equipment used for the basis of design is Acuity Brands Controls.
2. Other equipment may be submitted for approval up to 10 working days prior to bid date, to allow for proper evaluation. Submissions within 10 working days prior to bid date will not be evaluated. Equipment is approved through addendum only.
DS
S
S
S
LIGHTING CONTROL DEVICES SCHEDULE
TAG MANUFACTURER CATALOG NUMBER DESCRIPTION QTY
CONTROL
WIRING
MOUNTING
ACUITY nPP16 D
ROOM CONTROLLER, 1-CIRCUIT, 0-10V DIMMING,
16A MAX
AS REQ
120V LINE
VOLTAGE
ELECTRICAL
BOX
ACUITY nCM ADCX SINGLE ZONE, PHOTO SENSOR, CEILING MOUNT AS REQ CAT5
ELECTRICAL
BOX
ACUITY
ARP INTENC16
NLT-16SPR-MVOLT-SC-FM
ARPA PC
nLIGHT LIGHTING CONTROL PANEL, 16-RELAYS, 0-10V DIMMING, FLUSH MOUNTED, EXTERIOR
PHOTOCELL ACCESSORY
120V LINE
VOLTAGE
SURFACE
ACUITY nPP16 D ER
EMERGENCY LIGHTING CONTROLLER, 1-CIRCUIT,
0-10V DIMMING, 16A MAX
AS REQ CAT5
ELECTRICAL
BOX
LIGHTING CONTROLS SCHEDULE NOTES:
1. The equipment used for the basis of design is Acuity Brands Controls.
2. Other equipment may be submitted for approval up to 10 working days prior to bid date, to allow for proper evaluation. Submissions within 10 working days prior to bid date will not be evaluated. Equipment is approved through addendum only.
RC1
LCP
ER
OS
OS
P
D
LV
MS#
XS2
XS
NOT TO SCALEA
TYPE "A" - RECESSED
DOWNLIGHT
NOT TO SCALEB
TYPE "B" - 24 INCH VANITY
NOT TO SCALEF D
TYPE "D" - 2X4
RECESSED TROFFER
NOT TO SCALEC
TYPE "C" - 36 INCH DRUM
PENDANT
TYPE "F" - 8 INCH
CYLINDER PEDANT
G
NOT TO SCALE
H
NOT TO SCALE
TYPE "H" - RECTANGULAR
WALL SCONCE
TYPE "G" - 4 FT STRIP
WITH WIREGUARD
K
NOT TO SCALE
TYPE "K" - 4 FT LINEAR
SUSPENDEDN
NOT TO SCALE
TYPE "N" - 19 LIGHT
CHANDELIER
T
NOT TO SCALE
TYPE "T" - WALL PACK
X
NOT TO SCALE
TYPE "X" - LED EXIT
LIGHT WALL MOUNTED
P
NOT TO SCALE
TYPE "P" - CEILING FAN
Q
NOT TO SCALE
TYPE "Q" - LED WING RAIL
CEILING WALL ARMS
NOT TO SCALE
TYPE "S" - LED
RECESSED MOUNTED
R
NOT TO SCALE
TYPE "R" - POST TOP
SITE LIGHTING M
NOT TO SCALE
TYPE "M" - STAIRS
1. 4" DOWNLIGHT.
2. FIXTURE SHALL PROVIDE 1575 LUMENS.\
3. 2700K COLOR TEMPERATURE.
4. 5 - YEAR LIMITED WARRANTY.
5. MADE IN THE USA.
NOT TO SCALE
1. 26" VANITY FIXTURE.
2. BRUSHED NICKEL FINISH.
3. 3000K COLOR TEMPERATURE.
4. (3) LAMP, 10WATT PER LAMP.
5. 5 - YEAR LIMITED WARRANTY.
6. MADE IN THE USA.
1. 36" DIAMETER DRUM PENDANT.
2. COLOR BY ARCHITECT.
3. FIXTURE SHALL PROVIDE 5877 LUMENS.
4. 3500K COLOR TEMPERATURE.
5. 5 - YEAR LIMITED WARRANTY.
6. MADE IN THE USA.
1. 2X4 TROFFER WITH CURVED LENS.
2. FIXTURE SHALL PROVIDE 4800 LUMENS.
3. FIXTURE SHALL BE DIMMABLE.
4. 5 - YEAR LIMITED WARRANTY.
5. MADE IN THE USA.
1. 3500K COLOR TEMPRETURE.
2. FIXTURE SHALL PROVIDE 5,000 LUMENS.
3. 8" CYLINDER DOWNLIGHT.
4. CLEAR TRIM COLOR
5. SEMI- SPECULAR FINISH.
6. 5 - YEAR LIMITED WARRANTY.
7. MADE IN THE USA.
1. FULLY DIMMABLE.
2. FIXTURE SHALL PROVIDE 3278 LUMENS.
3. 2700K COLOR TEMPERATURE.
4. 5 - YEAR LIMITED WARRANTY.
5. MADE IN THE USA.
1. LINEAR SUSPENDED FIXTURE.
2. FIXTURE SHALL PROVIDE 750 LUMEN/FT.
3. 3500K COLOR TEMPERATURE.
4. 5 - YEAR LIMITED WARRANTY.
5. MADE IN THE USA.
1. RECTANGULAR ADA SCONCE.
2. WASHABLE ACRYLIC RESIN.
3. 3500K COLOR TEMPERATURE.
4. FIXTURE SHALL BE DIMMABLE.
5. 5 - YEAR LIMITED WARRANTY
6. MADE IN THE USA.
1. 4' STRIP LED.
2. FLAT DIFFUSE LENS WITH 48" WIREGAURD.
3. FIXTURE SHALL PROVIDE 5,000 LUMENS.
4. 3500K COLOR TEMPERATURE.
5. 5 - YEAR LIMITED WARRANTY.
6. MADE IN THE USA.
1. 4000K COLOR TEMPERATURE.
2. FIXTURE SHALL HAVE INTEGRAL PHOTOCELL.
3. 5 - YEAR LIMITED WARRANTY.
4. MADE IN THE USA.
5. WEATHERPROOF.
1. EXIT SIGN.
2. MULTI-VOLT.
3. WHITE THERMOPLASTIC HOUSING.
4. RED LETTER, AC ONLY.
5. WEATHERPROOF.
6. 5- YEAR LIMITED WARRANTY.
7. MADE IN THE USA.
1. 52" HAIK OUTDOOR CEILING FAN.
2. COCOA WOODGRAIN.
3. UNIVERSAL MOUNTING.
4. OUTDOOR LIGHT KIT.
5. 5 - YEAR LIMITED WARRANTY.
6. MADE IN THE USA.
1. SINGLE RAIL
2. RAIL LENGTH OF 48"
3. WALL ARM MOUNTED
4. ARM LENGTH OF 6"
5. 2700K COLOR TEMPERATURE.
6. 5 - YEAR LIMITED WARRANTY.
7. MADE IN THE USA.
1. 6" ROUND DOWNLIGHT
2. FIXTURE SHALL PROVIDE 5000 LUMENS.
3. SEMI-SPECULAR FINISH.
4. MULTI-VOLT OPTION.
5. 3500K COLOR TEMPERATURE.
6. 5 - YEAR LIMITED WARRANTY.
7. MADE IN THE USA.
1. DARK SKY FRIENDLY
2. FIXTURE SHALL PROVIDE 3100 LUMENS.
3. TYPE III DISTRIBUTION.
4. 120-277-VOLT OPTION.
5. 4000K COLOR TEMPERATURE.
6. PHOTOCELL.
7. 5 - YEAR LIMITED WARRANTY.
8. MADE IN THE USA.
1. 4' STRIP LED.
2. FLAT DIFFUSE LENS WITH 48" WIREGAURD.
3. FIXTURE SHALL PROVIDE 5,000 LUMENS.
4. 3500K COLOR TEMPERATURE.
5. 5 - YEAR LIMITED WARRANTY.
6. MADE IN THE USA.
7. DUAL TECHNOLOGY OCCUPANCY SENSOR.
LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTSLUMINAIRE REQUIREMENTS
LUMINAIRE REQUIREMENTS LUMINAIRE REQUIREMENTS
(DEDUCTIVE ALTERNATIVES ARE CASCADING AND MUST BE
EXCERCISED IN THE ORDER PRESENTED) FOR A DETAILED
DESCRIPTION OF EACH DEDUCTIVE ALTERNATE REFER TO COVER
SHEET GI000.
DEDUCT ALTNERATIVE #6 : ELIMINATE LANDSCAPE
DEDUCT ALTNERATIVE #9 : ELIMINATE LARGE PORCH
DEDUCT ALTNERATIVE #10 : ELIMINATE SMALL PORCH-A
DEDUCT ALTNERATIVE #11 : ELIMINATE SMALL PORCH-B
DEDUCT ALTERNATIVE NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:2
A M
E-502
ELECTRICAL DETAILS
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
DEDUCT #6 AND #9-11
Revisions: Date:
FS TS
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
NEXTSPEED ASCENT 10G
2625 2827 3029 363332 3534 3837 4039 45434241 44 484746
721 3 4 5 6 1298 10 11 1413 15 16 211917 18 20 2422 23
B ST
F
S
SD
COMMUNICATIONS SYSTEM RISER KEYNOTES
1. SEE SPECIAL SYSTEMS FLOOR PLAN FOR NUMBER OF DEVICES, TYPICAL. PROVIDE RJ45
DATA JACK. FOR RESIDENTIAL UNITS EACH DATA DROP SHALL HAVE 6 ACTIVE PORTS; FOR
ALL OTHER AREAS EACH DATA DROP SHALL HAVE 6 ACTIVE PORTS WITH THE FOLLOWING
CRITERIA:
A) BLUE TOP LEFT (FOR TELEPHONE)
B) GREEN TOP RIGHT (FOR TELEPHONE)
C) RED MIDDLE LEFT (DATA BACK TO PATCH PANELS)
D) YELLOW MIDDLE RIGHT (DATA BACK TO PATCH PANELS)
E) BLANKED-OFF BOTTOM LEFT
F) GREY BOTTOM RIGHT (DATA BACK TO PATCH PANELS).
2. 1-1/2" EMT CONDUIT TO CABLE TRAY, PROVIDE CAT6A CABLE FROM OUTLET BOX TO IT
CLOSET 105, TYPICAL. FOR ALL CONDUIT TO CABLE TRAY TRANSITIONS, SEE SHEET B2/A721.
3. IT RACK IN IT CLOSET 105.
4. PROVIDE NETWORK RJ45, 48 PORT, CAT6A, PATCH PANELS AS REQUIRED IN RACK.
5. LADDER TYPE CABLE TRAY INSTALLED IN ACCESSIBLE CEILING. PROVIDE SEPARATE CABLE
TRAY FOR FIRE ALARM AND NURSE CALL SYSTEM TO DIVIDE LIFE SAFETY LOW VOLTAGE
EQUIPMENT. SEE SPECIAL SYSTEMS FLOOR PLAN FOR MORE INFORMATION, TYPICAL.
6. PROVIDE EMT CONDUIT SLEEVES, HILTI CP653 4" SPEED SLEEVE…