Drawings 14 of 15 ELECTRICAL 1.pdf

PDF 11 MB Posted

Attached to
Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334
Solicitation number
36C77623R0156
Issued by

About this file

This document contains a government file related to a federal contract opportunity for construction services. The file is titled "Drawings 14 of 15 ELECTRICAL 1.pdf" and is 11MB in size. It is associated with solicitation number 36C77623R0156 from the Department of Veterans Affairs Technology Acquisition Center Austin to build a new community living center at the Montrose VA medical center. The opportunity type is listed as a solicitation for the construction of a minor facility. The solicitation seeks to award a contract to provide construction services for a new community living center to support veterans. It includes drawings to aid prospective offerors in developing their responses.

View the file

Other files

File Type Posted
620-334-Responses to Tech Questions - 1-30-24.pdf PDF
36C77623R0156 0003.pdf PDF
620-334-Pre Bid Presentation20240109.pdf PDF
36C77623R0156 0002.pdf PDF
620-334-Responses to Tech Questions - 1-25-24.pdf PDF
Site Visit Sign-In Sheet - 01-09-24.pdf PDF
36C77623R0156 0001.pdf PDF
DBA Wage Rates - Westchester County - 01-05-24.pdf PDF
Drawings 8 of 15 ARCHITECTURAL 3.pdf PDF
Site Visit Campus Map.pdf PDF
Specifications 10-30-23.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
Drawings 5 of 15 STRUCTURAL.pdf PDF
RFP 36C77623R0156 - 12-20-23.pdf PDF
Drawings 12 of 15 PLUMBING.pdf PDF
Drawings 1 of 15 GENERAL.pdf PDF
Drawings 4 of 15 LANDSCAPE.pdf PDF
Drawings 6 of 15 ARCHITECTURAL 1.pdf PDF
Drawings 2 of 15 CIVIL 1.pdf PDF
Drawings 7 of 15 ARCHITECTURAL 2.pdf PDF
Drawings 10 of 15 ARCH SIGN-EQUIP.pdf PDF
Drawings 13 of 15 MECHANICAL.pdf PDF
DBA Wage Rates - Westchester County - 11-17-23.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Drawings 15 of 15 ELECTRICAL 2.pdf PDF
Brand Name J_A - Montrose.pdf PDF
Site Visit Instructions.pdf PDF
Drawings 11 of 15 FIRE PROTECTION.pdf PDF
Drawings 9 of 15 ARCHITECTURAL 4.pdf PDF
Drawings 3 of 15 CIVIL 2.pdf PDF
Construction Cost Breakdown.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS FOR

REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT APPEAR ON THE

FOLLOWING DRAWINGS.

2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON EXISTING

UTILITIES WITH OWNER REPRESENTATIVES IN ORDER TO MINIMIZE IMPACT TO OTHER

AREAS.

3. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND

LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING

JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING DOCUMENTS AND

CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

4. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:

- NFPA 101-2018, THE LIFE SAFETY CODE

- NFPA 70-2017, NATIONAL ELECTRICAL CODE

- NFPA 72-2016, NATIONAL FIRE ALARM CODE

5. ALL WIRING SHALL BE IN CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM

CONDUCTOR SIZE SHALL BE #12 AWG. ALL NEW CIRCUITS SHALL BE PROVIDED WITH

AN INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTOR WITH THE PHASE

CONDUCTOR.

6. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE

WORK THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND

VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS

WITHOUT EXTRA COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE

BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER.

7. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY THE

CONTRACTOR UNLESS NOTED OTHERWISE.

8. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER EQUIPMENT

AND DEVICE MANUFACTURER RECOMMENDATIONS.

9. CONTRACTOR SHALL PROVIDE SUBMITTALS TO ARCHITECT/ENGINEER FOR REVIEW

AND APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN THE

SUBMITTAL REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS, DIMENSIONS,

WIRING DIAGRAMS, ACCESSORIES, OPERATION MANUALS, AND ALL NECESSARY

INFORMATION FOR REVIEWER TO MAKE A SOUND EVALUATION.

10. PROVIDE STARTUP OF ALL ELECTRICAL SYSTEMS AND COORDINATE WITH

ARCHITECT/ENGINEER FOR OWNER STARTUP WITNESSING.

11. PROVIDED LAMINATED PLASTIC NAMEPLATES FOR EACH EQUIPMENT ENCLOSURE.

EACH NAMEPLATE IDENTIFY EQUIPMENT FUNCTION, PANELBOARD CONNECTED AND

CIRCUIT NUMBER. NAMEPLATE SHALL BE MELAMINE PLASTIC (0.125 INCHES THICK),

WHITE LETTERS ON BLACK BACKGROUND. MINIMUM SIZE OF LETTERS SHALL BE 2.5

INCHES. IN ADDITION TO EQUIPMENT TAGGING, CONTRACTOR SHALL PROVIDE ARC-

FLASH WARNING SIGNS FOR PANELBOARDS.

12. PROVIDE COMPUTER PRINTED ON WHITE WRAPAROUND PAPER WITH CLEAR PLASTIC

PROTECTION TAIL FOR ALL WIRE MARKERS. MARKER SHALL STATE PANELBOARD

NAME AND CIRCUIT NUMBER ON ALL WIRES IN JUNCTION/PULL BOXES AND IN

EQUIPMENT TERMINAL BOXES.

13. PROVIDE PUNCHED TAPE LABELS ON ALL WIRING DEVICES FOR IDENTIFICATION. SHALL

BE ½” BLACK TAPE WITH WHITE RAISED LETTERS. TAPE LABELS SHALL STATE

PANELBOARD NAME AND CIRCUIT NUMBER.

14. PROVIDE DIRECTORIES ON ALL PANELBOARDS. BALANCE ALL LOADS ON PANELBOARD

WITHIN 10%.

15. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET OF RECORD

DRAWINGS TO THE VA AT THE END OF THE CONSTRUCTION.

16. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND FREE OF

DEFECTS. ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION (NEMA) STANDARDS AND SHALL BE UL LABELED. ALL

ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A WORKMANLIKE

MANNER.

17. ALL CONNECTORS AND SPLICES FOR CABLE SIZE #10 AWG AND SMALLER SHALL BE

INSULATED, PRESSURE-TYPE. FOR LARGER SIZE CONDUCTORS USE BOLTED CLAMPS

WITH INSULATING TAPE.

18. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS,

STRUCTURE, PLUMBING, AND OTHER PIPING IN THE CEILING SPACE. COORDINATE ALL

CONDUITS/WIRING ROUTING WITH ALL OTHER TRADES.

19. WHERE JOB CONDITIONS REQUIRE CHANGE FROM THE CONTRACT DOCUMENTS THAT

DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR

SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE VA. NO OTHER

CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.

20. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF

CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT

CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL

CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH

ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER

CONSTRUCTION COMPLETION.

21. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES

(FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE

RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER

WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.

GENERAL PROJECT NOTES

CONDUIT AND WIRING

BRANCH CIRCUIT RUN CONCEALED

BRANCH CIRCUIT RUN UNDER FLOOR

BRANCH CIRCUIT DOWN

BRANCH CIRCUIT UP

HOME RUN TO PANEL 2A CKTS 1,3, & 52A-1,3,5

ELECTRICAL ABBREVIATIONS

A AMP

AA AUTOMATIC ALTERNATOR

AC ALTERNATING CURRENT

ACU AIR CONDITIONER UNIT

AF AMPERAGE FRAME

AFF ABOVE FINISHED FLOOR

ANN ANNUNCIATOR

AS AMMETER SWITCH

AT AMPERE TRIP

AX AUXILIARY DELAY

BKR BREAKER

CB CIRCUIT BREAKER

COL COLUMN

CL CENTERLINE

CKT CIRCUIT

CF(P OR L) CLOSE ON FALLING

(PRESSURE OR LEVEL)

CR(P OR L) CLOSE ON RISING

(PRESSURE OR LEVEL)

CH CONVECTION HEATER

COMPT COMPARTMENT

COND CONDUCTOR

CDT CONDUIT

C-( ) CONTRACT-( ) ID

CPT CONTROL POWER

TRANSFORMER

CR-( ) CONTROL RELAY-( ) ID

I/I CURRENT TO CURRENT

TRANSDUCER

I/P CURRENT TO PNEUMATIC

TRANSDUCER

CT CURRENT TRANSFORMER

D EXISTING TO BE DEMOLISHED

DC DIRECT CURRENT

DF DUST FILTER

DIA DIAMETER

DISTR DISTRIBUTION

DP DIFFERENTIAL PRESSURE

DS DISCONNECT SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

E EXISTING TO REMAIN

EBB ELECTRIC BASED BOARD

EC ELECTRICAL CONTRACTOR

ECH ELECTRIC CEILING HEATER

EDH ELECTRIC DUCT HEATER

EF ELECTRIC FIN

EMT ELECTRIC METALLIC TUBING

ER EXISTING TO BE REMOVED AND

RELOCATED

ETM ELAPSED TIME METER

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

F FLOW

FDR FEEDER

FLA FULL LOAD AMPS

FMC FLEXIBLE METALLIC CONDUIT

FOS FAST-OFF-SLOW

F-S FAST-SLOW

FT FEET

F-R FORWARD REVERSE

FR FRAME

FUSS FUSED SAFETY SWITCH

FVNR FULL VOLTAGE NON-REVERSING

G GREEN

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GPM GALLONS PER MINUTE

GND GROUND

GRV GRAVITY RELIEF VENT

GUH GAS UNIT HEATER

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HV HOUSE VACUUM

HZ HERTZ

ID IDENTIFICATION NUMBER

IC INTERRUPTING CAPACITY

IF INFRARED HEATER

IMC INTERMEDIATE METAL CONDUIT

INF IN LINE FAN

I/O INPUT/OUTPUT

IT INTERCHANGEABLE TRIP OR

INSTANTANEOUS TRIP

JB JUNCTION BOX

kcmil THOUSAND CIRCULAR MILS

KUH/EUH ELECTRIC UNIT HEATER

KVA KILOVOLT AMPERE

KV KILOVOLT

KVAR KILOVOLT AMPERES REACTIVE

KW KILOWATT

L LEVEL

LC LOUVER CONTROLLER

LFMC LIQUID-TIGHT FLEXIBLE

METAL CONDUIT

LM LOUVER MOTOR

LP( )-( ) LIGHTING CIRCUIT ( )

LP( ) LIGHTING PANELBOARD

LS LIMIT SWITCH

LV LOUVER

M MANUAL MOTOR STARTER

mA MILLIAMPERES

MC METAL CLAD CABLE

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MEZZ MEZZANINE

MF-( ) MAIN FEEDER-( ) ID

MGD MILLION GALLONS PER DAY

MS MOTOR STARTER

MTD MOUNTED

MTR MOTORIZED TIMING RELAY

MUAU MAKE UP AIR UNIT

MX MOTOR AUXILIARY RELAYS

(N) NEW

NAC NOTIFICATION APPLIANCE

CIRCUIT

NP NAMEPLATE

NF NON FUSED

NFSS NON FUSED SAFETY SWITCH

NCT NURSE CALL TERMINAL CABINET

N.O. NORMALLY OPEN

No. NUMBER

OHD OVERHEAD DOOR

( )OL OVERLOAD ( ) NUMBER OF

P PRESSURE

( )P POLES ( ) NO OF POLES

∅ or PH PHASE

P/I PNEUMATIC TO CURRENT

TRANSDUCER

PLC PROGRAMMABLE LOGIC

CONTROLLER

PRE POWER ROOF EXHAUSTER

PS PRESSURE SWITCH

PT POTENTIAL TRANSFORMER

PTAC PACKAGE TERMINAL

AIR CONDITIONER

PTR PNEUMATIC TIMING RELAY

PVC POLYVINYL CHLORIDE

RIGID CONDUIT

PVC-RSC PVC COATED RIGID

STEEL CONDUIT

PWV POWER WALL VENTILATOR

QTY QUANTITY

R RELOCATED

RAC RIGID ALUMINUM

RECPT RECEPTACLE

REQ REQUIRED

RMS ROOT MEAN SQUARE

RSC RIGID STEEL CONDUIT

RTU REMOTE TERMINAL UNIT

SAF SUPPLY AIR FAN

STP SHIELDED TWISTED PAIR

SL STOP LOCKOUT

SMC SMART MOTOR CONTROLLER

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE, DOUBLE THROW

SS SELECTOR SWITCH

S/S START/STOP

S/SL START/STOP LOCKOUT

SV SOLENOID VALVE

SYM SYMMETRICAL

T or T'STAT THERMOSTAT

T-( ) TELEPHONE CONDUIT-( )

TCC TIME-CLOSE CONTACT

TEMP TEMPERATURE

TC TEMPERATURE CONTRACTOR

TOC TIME-OPEN CONTACT

TR TIMING RELAY

TRI SHIELDED TRIPLE CABLE

TS TEMPERATURE SWITCH

TSP TWISTED SHIELDED PAIR

TYP TYPICAL

UF UNDERGROUND FEEDER

UH UNIT HEATER

VA VOLT - AMPERE

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

VFD VARIABLE FREQUENCY DRIVE

VS VOLTMETER SWITCH

VT VOLTAGE TRANSFORMER

W WATT

WH WATER HEATER

WP WEATHERPROOF

S S S3 4

S D

S

PB

S F

OS

RC

SINGLE-POLE, 3-WAY AND 4-WAY

SWITCHES (48"AFF)

ELECTRICAL DEVICES

(MOUNTING HEIGHT TO CENTER LINE

OF BOX UNLESS NOTED OTHERWISE)

LOCAL WALL DIMMER SWITCH (48" AFF)

PUSH-BUTTON SWITCH (48" AFF)

FAN SWITCH (48" AFF)

WALL MOUNTED OCCUPANCY SENSOR SWITCH;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

CEILING MOUNTED OCCUPANCY/VACANCY SENSOR;

DUAL TECHNOLOGY

(PASSIVE INFRARED/ULTRASONIC)

ROOM CONTROLLER (REFER TO PLANS)

TIMECLOCK (REFER TO PLANS)T

DUPLEX RECEPTACLE (18"AFF)

DOUBLE DUPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE -

FLOOR BOX

SIMPLEX RECEPTACLE (18" AFF)

DUPLEX RECEPTACLE MOUNTED 6" ABOVE COUNTER

OR BACKSPLASH

GFCI DUPLEX RECEPTACLE GFCI

GFCI/WP GFCI DUPLEX RECEPTACLE WITH WHILE-IN-USE

WEATHERPROOF COVER

SPECIAL RECEPTACLE (18"AFF) - TYPE

AS NOTED

PLUG MOLD/WIRE MOLD RACEWAY

PUSH BUTTON

2X4 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

ELECTRICAL LIGHTING FIXTURE SYMBOLS

2X4 LIFE SAFETY BRANCH FIXTURE - RECESSED,

SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED

2X2 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

2X2 LIFE SAFETY BRANCH FIXTURE - RECESSED,

SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED

1X4 FIXTURE - RECESSED, SURFACE, OR PENDANT

MOUNTED - TYPE AS SPECIFIED

1X4 LIFE SAFETY BRANCH FIXTURE - RECESSED,

SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED

4' STRIP FIXTURE - TYPE AS SPECIFIED

4' STRIP LIFE SAFETY BRANCH FIXTURE - TYPE AS

SPECIFIED

1X4 FIXTURE - SURFACE MOUNTED - TYPE AS

SPECIFIED

1X4 LIFE SAFETY BRANCH FIXTURE - SURFACE

MOUNTED - TYPE AS SPECIFIED

1X4 FIXTURE - WALL MOUNTED - TYPE AS SPECIFIED

1X4 LIFE SAFETY BRANCH FIXTURE - WALL

MOUNTED - TYPE AS SPECIFIED

LIGHTING FIXTURE - RECESSED OR SURFACE

MOUNTED - TYPE AS SPECIFIED

LIFE SAFETY BRANCH LIGHTING FIXTURE -

RECESSED OR SURFACE - TYPE AS SPECIFIED

LIGHTING FIXTURE - PENDANT MOUNTED - TYPE

AS SPECIFIED

LIFE SAFETY BRANCH LIGHTING FIXTURE -

PENDANT MOUNTED - TYPE AS SPECIFIED

WALL MOUNTED - TYPE AS SPECIFIED

LIFE SAFETY BRANCH WALL FLUSH MOUNTED -

TYPE AS SPECIFIED

SELF CONTAINED EMERGENCY LIGHTING UNIT -

TYPE AS SPECIFIED

COMBINATION EXIT SIGN & SELF CONTAINED

EMERGENCY LIGHTING UNIT - TYPE AS SPECIFIED

EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED

EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED

FIRE ALARM SYMBOLS

MANUAL PULL STATION (46" AFF)F

S

S

BELL/STROBE LIGHT COMBINATION (80" AFF)

STROBE LIGHT (80" AFF)

HORN (80" AFF)H

H

S

B

HORN/STROBE LIGHT COMBINATION (80" AFF)

SPEAKER/STROBE (80" AFF)

PROGRAM BELL (80" AFF)

SMOKE DETECTOR - CEILING MOUNTED

SMOKE ALARM - CEILING MOUNTED

DUCT DETECTOR

SD

SA

DD

TS

FS

D

TAMPER SWITCH

FLOW SWITCH

MAGNETIC DOOR HOLDER (72" AFF)

FIRE ALARM CONTROL PANEL

RECESSED FIRE ALARM CONTROL PANEL

FACP

FACP

GENERAL SYMBOLS

X

KEY NOTE INDICATOR

DRAWING REVISION INDICATOR

LINE TYPES

NEW WORK SCOPE OF WORK

EXISTING SCOPE OF WORK

DEMOLITION SCOPE OF WORK

FUTURE SCOPE OF WORK

-NEW BRANCH CIRCUIT W/ #12 AWG THHN WIRES

-SLASH LINES INDICATES WIRES IN CIRCUIT

-SHORT LINES DEPICTS PHASE CONDUCTOR

-LONG LINE DEPICTS NEUTRAL CONDUCTOR

-LONG LINE W/ DOT DEPICTS GROUND

UNDERGROUND ELECTRIC SECONDARY FEEDERUGPUGP

PANELBOARD

POWER DISTRIBUTION

TRANSFORMER

MOTOR CONNECTION - NUMERAL INDICATES HP

DISCONNECT SWITCH - FUSED -

AMPS/FUSE/POLE/NEMA

DISCONNECT SWITCH - NON-FUSED -

AMPS/POLES/NEMA

DISCONNECT SWITCH -

MOTOR/STARTER COMBINATION

VARIABLE FREQUENCY DRIVE

CONTROL PANEL

JUNCTION BOX OR PULL BOX

WALL MOUNTED JUNCTION BOX OR PULL BOX

VFD

CP

J

J

COMMUNICATION DEVICES

DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING

TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON

END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6

PORTS, CAT6A, RJ45

(MOUNTING HEIGHT TO

CENTER LINE OF BOX

UNLESS NOTED OTHERWISE

ABOVE COUNTER DATA OUTLET (6" ABOVE COUNTER

OR BACKSPLASH); DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING WITH 1"C AND PULL

STRING TO ACCESSIBLE CEILING, PROVIDE NYLON

BUSHING ON END OF CONDUIT FOR PROTECTION OF

WIRE, PROVIDE 6 PORTS, CAT6A, RJ45

DATA OUTLET - CEILING MOUNTED; DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING WITH 1"C

AND PULL STRING TO ACCESSIBLE CEILING, PROVIDE

NYLON BUSHING ON END OF CONDUIT FOR

PROTECTION OF WIRE, PROVIDE 6 PORTS, CAT6A, RJ45

C

CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);

PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE

CEILING. PROVIDE INSULATED NYLON BUSHING ON END

OF CONDUIT FOR PROTECTION OF WIRE

12"x6" COMMUNICATION CABLE TRAY MOUNTED ABOVE

SUSPENDED CEILING

RECESSED PUBLIC ADDRESS SPEAKER; PROVIDED

WITH BAFFLE, GRILL AND MATCHING TRANSFORMER

S

S RECESSED PUBLIC ADDRESS SPEAKER; PROVIDED

WITH BAFFLE, GRILL AND MATCHING TRANSFORMER

CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER

RING, 3/4" CONDUIT WITH PULL STRING TO DOOR

CONTROLLER

DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

ELECTRIC DOOR (HINGE) STRIKE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

KEY PAD; PROVIDE DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH PULL

STRING TO DOOR CONTROLLER

INTRUSION DETECTION MOTION DETECTOR; PROVIDE

DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER

RING, 3/4" CONDUIT WITH PULL STRING TO ACCESSIBLE

CEILING

PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

CCTV CAMERA - FIXED; PROVIDE DOUBLE GANG BACK

BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT

WITH PULL STRING TO ACCESSIBLE CEILING; WP =

WEATHERPROOF

CCTV CAMERA - 360° PTZ; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;

WP = WEATHERPROOF

CR

DC

EH

K

MD

P

WP

WP

REQUEST TO EXIT (INFRARED); PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

RTE

DELAYED EGRESS; PROVIDE DOUBLE GANG BACK BOX

WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH

PULL STRING TO DOOR CONTROLLER

DE

ELECTROMAGNETIC LOCK; PROVIDE DOUBLE GANG

BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"

CONDUIT WITH PULL STRING TO DOOR CONTROLLER

ML

KEY SWITCH; PROVIDE DOUBLE GANG BACK BOX WITH

SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH PULL

STRING TO DOOR CONTROLLER

KS

N NURSE STATION (46" AFF)

NURSE CALL DEVICES

CODE BLUE STATION (46" AFF)

BED NURSE CALL (46" AFF)

TOILET NURSE CALL (46" AFF)

ND

SHOWER NURSE CALL

(WEATHER PROOF) (46" AFF)

DOCTOR DICTATION (46" AFF)

DOCTOR PAGE (46" AFF)

NURSE CALL DUTY STATION (46" AFF)

NURSE CALL MASTER

NURSE CALL DOME LIGHT (CEILING)

C

B

T

S

DI

D

PILLOW SPEAKER/CONTROLP

NURSE CALL DOME ZONE LIGHT (CEILING)Z

CONNECT TO EXISTING

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:1

A M

E-001

NOTES AND LEGEND - ELECTRICAL

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

DRAWING INDEX - ELECTRICAL

E-001 NOTES AND LEGEND - ELECTRICAL

ED100 ELECTRICAL DEMOLITION SITE PLAN

ES100 ELECTRICAL RENOVATION OVERALL SITE PLAN

ES100A ELECTRICAL RENOVATION SITE PLAN - AREA A

ES100B ELECTRICAL RENOVATION SITE PLAN - AREA B

EL100 LIGHTING FLOOR PLAN - BASEMENT

EL101A LIGHTING FLOOR PLAN - LEVEL 1 - AREA A

EL101B LIGHTING FLOOR PLAN - LEVEL 1 - AREA B

EL102 LIGHTING FLOOR PLAN - MECHANICAL PENTHOUSE

EP100 ELECTRICAL FLOOR PLAN - BASEMENT

EP101A POWER FLOOR PLAN - LEVEL 1 - AREA A

EP101B POWER FLOOR PLAN - LEVEL 1 - AREA B

EP102 ELECTRICAL FLOOR PLAN - MECHANICAL PENTHOUSE

EY100 SPECIAL SYSTEMS RENOVATION OVERALL SITE PLAN

EY101A SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA A

EY101B SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA B

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-503 ELECTRICAL DETAILS

E-601 SINGLE LINE DIAGRAM - ELECTRICAL

E-602 SINGLE LINE DIAGRAM - ELECTRICAL

E-603 SCHEDULES - ELECTRICAL

E-604 SCHEDULES - ELECTRICAL

Revisions: Date:

05/09/2022

UP

UP

SS #11

SS #12

EMH #26

EMH #26A

4 5

EMH #25

EXISTING TRANSFORMER12

TMH #26

TMH #27 TMH #28

EMH #24 TMH #24

A. THE DESIGN INTENT IS TO REMOVE/RELOCATE/RE-ROUTE ALL HIGH

VOLTAGE EQUIPMENT/CONDUCTORS IDENTIFIED TO BE LOCATED

UNDERNEATH THE NEW CLC'S FOOTPRINT. THIS INCLUDES THE

REMOVAL OF THE EXISTING ELECTRICAL MANHOLE EMH #26A AND

13.8 KV, 3-PH UNDERGROUND ELECTRICAL FEEDER FROM EMH #

26A TO THE (2) EXISTING PAD-MOUNTED UTILITY TRANSFORMERS

SERVICING EXISTING BUILDING #6.

B. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT

ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,

ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO

COMMENCING ANY WORK ON THIS SITE.

C. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW

VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION

LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS

PRIOR TO COMMENCING ANY WORK ON THIS SITE.

D. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY

UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING

ON THIS SITE.

E. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH WITH CIVIL

PRIOR TO WORKING ON THIS SITE.

F. CONTRACTOR SHALL FIELD VERIFY ACTUAL SIZES AND QUANTITIES

OF EXISTING CONDUCTORS AND DUCTBANKS. THE DESIGN INTENT

IS TO MATCH SIZES AND QUATNITIES OF EXISTING FOR NEW WORK.

GENERAL NOTES

IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO

INSPECT ALL OF THE EXISTING ELECTRICAL GEAR INCLUDING BUT NOT

LIMITED TO SECTIONAL SWITCHES, DUCTBANKS, CONDUITS.

MANHOLES THAT ARE SHOWN TO BE REUSED ARE TO BE INSPECTED

TO VERIFY THEY ARE IN CURRENT CODE COMPLIANT AND WORKING

CONDITION. CONTRACTOR SHALL REPORT DISCREPANCIES TO THE VA

PRIOR TO DISTURBING EXISTING INSTALLATION.

FOR ALL EXISTING CABLES OR CONDUCTORS WITHIN DUCT BANKS OR

MANHOLES WITHIN THE SCOPE OF THIS PROJECT SHALL BE VERIFIED

FOR USE AND CONTINUITY. PROVIDE VA COR LIST OF CABLES THAT

ARE ABANDONED, NO LONGER IN USE, OR IN USE AND WHAT THEY

SERVE. ANY CABLES ABANDONED OR NO LONGER IN USE SHALL BE

REMOVED TO ORIGIN.

THERE SHALL BE NO SPLICES OR RE-USE OF CABLES OR

CONDUCTORS WITHIN THE SCOPE OF THIS PROJECT. ALL WIRING

ASSOCIATED WITH THE SCOPE OF THIS PROJECT SHALL BE NEW

UNLESS OTHERWISE NOTED.

SEE CIVIL PLANS FOR COORDINATION EFFORTS AND DETAILS,

F5 ON SHEET CG506.

EXISTING CONDITION NOTES

PHASE 1:

A. CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE

DEMOLITION/RENOVATION PLANS AND IDENTIFY ALL

UNDERGROUND ROUTING OF NEW WORK ENSURING EXISTING

INSTALLATION OF UNDERGROUND UTILITIES ARE NOT DISTURBED.

B. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

EXISTING SECTIONAL SWITCH (SS) #12 TO NEW ELECTRICAL

MANHOLE (EMH) #26A. PREP AREA WHERE FINAL CONNECTION OF

SS #12 IS TO BE MADE. DO NOT MAKE FINAL CONNECTION UNTIL

SHUT DOWN OF SS #12 IS COMPLETED DURING PHASE 4. PROVIDE

PULL CORD AS REQUIRED.

C. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26A TO NEW EMH#26B. PROVIDE PULL CORD AS

REQUIRED.

D. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26B UP TO EXISTING BUILDING 6'S 300KVA PAD

MOUNTED TRANSFORMER. PREP AREA WHERE FINAL CONNECTION

OF BUILDING 6'S TRANSFORMER IS TO BE MADE. DO NOT MAKE

FINAL CONNECTION UNTIL SHUT DOWN OF BUILDING 6'S

TRANSFORMER IS COMPLETED DURING PHASE 4. PROVIDE PULL

CORD AS REQUIRED.

E. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE,

EPB #25 MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. PREP

AREA WHERE FINAL CONNECTION OF EMH #25 IS TO BE MADE. DO

NOT MAKE FINAL CONNECTION UNIT SHUT DOWN OF LOOP C AND D

ARE COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS

REQUIRED.

F. INSTALL NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27

MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. INSTALL NEW

UNDERGROUND 13.8KV DUCTBANK FEEDER ON BOTH SIDES TO

CONNECT TO EXISTING AS REQUIRED.

G. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM

NEW EMH #26 TONEW EPB #27. PROVIDE PULL CORD AS REQUIRED.

H. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM

NEW EMH #26 TO NEW EMH #26A. COORDINATE WITH CIVIL PLANS

AND NEW UNDERGROUND TUNNEL. PROVIDE PULL CORD AS

REQUIRED.

PHASE 2:

A. INSTALL NEW UNDERGROUND DUCTBANK FROM NEW 300KVA PAD

MOUNTED TRANSFORMER TO EXISTING 225KVA PAD MOUNTED

TRANSFORMER PREVIOUSLY SERVICING BUILDING #25. DO NOT

MAKE FINAL CONNECTION UNTIL SHUT DOWN OF SS #11 IS

COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS REQUIRED.

B. INSTALL CONCRETE PAD AND 300KVA TRANSFORMER WITH

INTEGRAL FUSE. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.

ENSURE TRANSFORMER SWITCH/FUSE ARE IN THE "OFF" POSITION

UNTIL NEW CLC IS READY FOR SERVICE.

PHASE 3:

A. CONTRACTOR SHALL PROVIDE AND INSTALL A SEPARATE DIESEL

GENERATOR FOR EACH BUILDING 6 AND 7 AND MAN THE

OPERATIONS. GENERATOR WILL ACT AS NORMAL POWER DURING

PHASE 4. VA'S EMERGENCY GENERATOR SHALL NOT BE USED FOR

NORMAL WORKING ACTIVITIES. HOWEVER, MAY BE USED FOR

CONTRACTOR PROVIDED GENERATOR INSPECTION PURPOSES

ONLY. PROVIDE SUPERVISION, FUEL AND REQUIRED RECORD

DOCUMENTATION DURING RUNTIME AND TESTING.

1) BUILDING 6'S TEMPORARY GENERATOR SHALL BE SIZED

FOR A MINIMUM OF 400KVA OR 1000A WITH AT LEAST 96

HOURS OF FUEL TIME.

2) BUILDING 7'S TEMPORARY GENERATOR SHALL BE SIZED

FOR A MINIMUM OF 720KVA OR 2000A WITH AT LEAST 96 HOURS

OF FUEL TIME.

B. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN

BUILDING 6 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT

MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED

DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.

C. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN

BUILDING 7 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT

MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED

DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.

PHASE 4:

A. COORDINATE ELECTRICAL SERVICE SHUT DOWN OF LOOP C AND D

WITH THE VA COR. CONTRACTOR SHALL PROVIDE A PLAN IN

WRITTEN FORM FOR APPROVAL FROM THE COR. CONTRACTOR

SHALL COORDINATE AT LEAST THREE (3) MONTHS PRIOR WITH THE

VA COR FOR ACTUAL SHUT DOWN; ONLY (1) ONE SHUT DOWN WILL

BE ACCEPTABLE. CONTRACTOR SHALL ENSURE SUFFICIENT

STAFFS (A MINIMUM OF A TWO-MAN CREW AT EACH AFFECTED

MANHOLE) SHALL BE PROVIDED ON SITE TO MINIMIZE SHUT DOWN

DURATION. COMPLETION OF WORK DURING SHUT DOWN SHALL BE

DONE OVER ONE WEEKEND AND MUST NOT EXCEED TWO DAYS.

B. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL

SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING

BUILDING 6 AND MAKE CONNECTION FROM TEMPORARY

GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START

UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.

C. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL

SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING

BUILDING 7 AND MAKE CONNECTION FROM TEMPORARY

GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START

UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.

D. SEVER LOOP C AND D AT EXISTING EMH #26A. PULL BACK 13.8KV

FEEDERS FROM EXISTING EMH #26A TO EXISTING EMH #27. ON THE

OTHER SIDE, PULL BACK 13.8KV FEEDERS FROM EMH #26A TO

EXISTING EMH #25. DEMOLISH ASSOCIATED DUCTBANK AS

REQUIRED.

E. DISCONNECT CONNECTION OF UNDERGROUND 13.8KV FEEDER

FROM SS #12 AND BUILDING 6'S TRANSFORMER. DEMOLISH

ASSOCIATED DUCTBANK AS REQUIRED.

F. REMOVE EXISTING 225KVA PAD MOUNTED TRANSFORMER

PREVIOUSLY SERVICING DEMOLISHED BUILDING #25. REMOVE

EXISTING CONDUCTORS FROM EXISTING 225KVA PAD MOUNTED

TRANSFORMER TO EXISTING EXISTING SS #11 VIA EXISTING

ELECTRICAL MANHOLE #28. ENSURE EXISTING CONCRETE

ENCASED DUCTBANK IS PROTECTED TO BE REUSED. EXTEND

EXISTING DUCTBANK TO NEW DUCTBANK AS SHOWN ON ES100.

PULL NEW CONDUCTORS AS REQUIRED FROM EXISTING SS #11 TO

NEW CLC'S TRANSFORMER LOCATION.

G. BORE EXISTING ELECTRICAL MANHOLES #27 AND #25 AS SHOWN

ON SHEET ES100.

H. MAKE FINAL CONNECTION AND PULL NEW CONDUCTORS AT THE

FOLLOWING LOCATION:

1) EXISTING EMH #27 TO NEW EPB #27.

2) NEW EPB #27 TO NEW EMH #26.

3) NEW EMH #26 TO NEW EMH #26A.

4) NEW EMH #26A TO NEW EPB #25

5) NEW EPB #25 TO EXISTING EMH #25.

6) EXISTING SS #12 TO NEW EMH #26A.

7) NEW EMH #26A TO NEW EMH #26B.

8) NEW EMH #26B TO EXISTING BUILDING 6'S 300KVA

TRANSFORMER.

9) EXISTING SS #11 TO NEW 300KVA PAD MOUNTED

TRANSFORMER. ENSURE TRANSFORMER FUSE IS IN THE OFF

POSITION UNTIL NEW CLC IS READY FOR SERVICE.

SEQUENCE OF OPERATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:3

A M

ED100

ELECTRICAL DEMOLITION SITE PLAN

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1" = 30'-0"

ELECTRICAL DEMOLITION SITE PLAN

KEYNOTES

1 EXISTING UNDERGROUND ELECTRIC 13.8 KV, 3-PH CONDUCTORS TO

REMAIN.

2 EXISTING ELECTRICAL MANHOLE TO REMAIN.

3 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING

ELECTRICAL MANHOLE #26A TOWARDS EXISTING EMH #27 VIA EMH

#26. CONNECT EXISTING CONDUCTORS TO NEW CONDUCTORS FOR

C AND D LOOPS ON A TERMINAL BLOCK WITH LOAD BLOCK ELBOWS

ON BOTH SIDES IN NEW NEMA 4X ENCLOSURE ON CONCRETE PAD

EPB #27. SEE ES100 FOR ADDITIONAL INFORMATION. DEMOLISH

EXISTING DUCTBANK FROM EMH #26A TO EXISTING EMH #27.

4 SEVER ALL C AND D LOOP CONDUCTORS IN EXISTING ELECTRICAL

MANHOLE #26A AND PULL BACK TO EXISTING ELECTRICAL MANHOLE

#27 ON ONE SIDE AND TO EXISTING ELECTRICAL MANHOLE #25 ON

OTHER SIDE. LEAVE ENOUGH SLACK TO COME INTO NEW ABOVE

GRADE NEMA 4X ENCLOSURE AND CONNECT TO TERMINAL BLOCK.

5 REMOVE EXISTING ELECTRICAL MANHOLE EMH #26A.

6 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING

ELECTRICAL MANHOLE EMH #26A TO SS #12. DISCONNECT AND

REMOVE CONDUCTORS.

7 PULL BACK EXISTING UNDERGROUND ELECTRIC 13.8 KV, 3-PH

CONDUCTORS FROM EXISTING ELECTRICAL MANHOLE EMH #26A TO

EXISTING PAD-MOUNTED UTILITY TRANSFORMER #1 SERVICING

BUILDING #6. DISCONNECT AND REMOVE CONDUCTORS.

8 APPROXIMATE LOCATION OF EXISTING PAD-MOUNTED UTILITY

TRANSFORMER #1 SERVICING BUILDING #6.

9 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING

ELECTRICAL MANHOLE #26A TOWARDS MANHOLE #25 TO THE

PROPOSED NEW NEMA 4X ENCLOSURE AT THIS LOCATION.

CONNECT EXISTING CONDUCTORS TO NEW CONDUCTORS FOR C

AND D LOOPS ON A TERMINAL BLOCK WITH LOAD BLOCK ELBOWS

ON BOTH SIDES IN NEW NEMA 4X ENCLOSURE ON CONCRETE PAD.

10 EXISTING SECTIONAL SWITCH, SS#12 TO REMAIN.

11 EXISTING SECTIONAL SWITCH, SS#11 TO REMAIN.

12 EXISTING 225KVA PAD MOUNTED TRANSFORMER PREVIOUSLY

SERVICING DEMOLISHED BUILDING #25 TO BE REMOVED.

13 EXISTING UNDERGROUND DUCTBANK FEEDER TO REMAIN AND

REUSED DURING NEW WORK AS DIRECTED BY OWNER.

CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE FILL CAPACITY

AND THE EXISTING DUCTBANK/CONDUITS ARE IN CURRENT CODE

COMPLIANT CONDITION FOR REUSE. PROTECT DURING DEMOLITION

AND REMOVE ASSOCIATED CONDUCTORS.

14 EXISTING TELECOMMUNICATION MANHOLE TO REMAIN.

15 EXISTING UNDERGROUND TELECOMMUNICATION CABLES IN

DUCTBANKS TO REMAIN.

16 EXISTING CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH

13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N. DISCONNECT AND REMOVE

CONDUCTORS AND DEMOLISH EXISTING DUCTBANK.

17 EXISTING CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 -

30#16 RHL. 1 - 24#16 RHL AND 2-3/C #16 RHL. 1 2#12 RHL. 1 -

TELEPHONE. 1 - SPARE. DISCONNECT AND REMOVE CONDUCTORS

AND DEMOLISH EXISTING DUCTBANK.

18 SEVER ALL TELECOMMUNICATION CABLES AT THIS LOCATION AND

PULL BACK TO EXISTING TELECOMMUNICATION MANHOLE, TMH #27

ON ONE SIDE AND TO NEW TELECOMMUNICATION PULL BOX, TPB

#25. LEAVE ENOUGH SLACK TO COME INTO NEW ABOVE GRADE

NEMA 4X ENCLOSURE AND CONNECT TO TERMINAL BLOCK.

DEMOLISH ASSOCIATED DUCTBANK AS REQUIRED. SEE

RENOVATION PLANS FOR LOCATION OF NEW TPB #25.

19 REMOVE EXISTING FEEDER CONDUCTORS AND RE-USE DUCT BANK

BETWEEN SS#11 AND EXISTING TRANSFORMER. RUN NEW FEEDER

CONDUCTORS FROM SS#11 TO NEW CLC BUILDING.

20 EXISTING CONCRETE ENCASED DUCTBANKS - (2) 3" ONE CONDUIT

WITH 13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N AND ONE SPARE

CONDUIT. DISCONNECT AND REMOVE CONDUCTORS AND DEMOLISH

EXISTING DUCTBANK. SEE CIVIL PLAN CD101 FOR LOCATIONS OF

EXISTING CONCRETE DUCTBANK TO BE REMOVED AT NEW UTILITY

CROSSINGS.

21 EXISTING MANHOLES EMH#26 AND TMH#26 TO BE REMOVED.

22 CUTOFF POINT 3LF EAST OF EXISTING SS #12.

23 CUTOFF POINT 3LF WEST OF EXISTING TRANSFORMER #1.

24 CUTOFF POINT 3LF SOUTH OF EXISTING EMH #25.

25 REMOVE EXISTING CONCRETE ENCASED DUCTBANK FROM TMH #27

TO CUTOFF POINT 3LF SOUTH OF EMH #25.

26 EXISTING CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH

13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N. DISCONNECT AND REMOVE

CONDUCTORS AND DEMOLISH EXISTING DUCTBANK. SEE CIVIL PLAN

CD101 FOR LOCATIONS OF EXISTING CONCRETE DUCTBANK TO BE

REMOVED AT NEW UTILITY CROSSINGS.

1/16" = 1'-0"

OVERALL CAMPUS KEYPLAN

EMH #27

EMH #28

Revisions: Date:

J

J

S

J

J

SS #12

SS #11

EPB #27

EMH #26A

EMH #26B

EPB #25

EMH #25

R

R

R

R

R

2"ø

2"ø

2"ø

2"ø

2"ø

2"ø

2"ø

2"ø

R

R

R

C2-30

C2-30

C2-30

C2-40

C2-40

C2-40

C2-40

C2-40

EMH #27

EMH #28

BUILDING 6NEW CLCES100A

ES100B

DP - 8

EQ1-38

EQ1-40

EQ1-39,41

DP-10

DP-12

DP - 14

DP - 16

V

V

V V

V

V

V

V

V

V

VVV

V

V

V

V

U

U

U

U

U

W W

W

W

W

W W W

W

W

W

W

W

W

W

W

NL - 29

NL - 31

NL - 33

TMH #28

TMH #27

EMH #24 TMH #24

TPB #27

TPB #25

EMH #26

TMH #26

TMH #25 34

A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT

ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION, ROUTING OF

CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO COMMENCING ANY

WORK ON THIS SITE.

B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW VOLTAGE

SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION LOCATION,

ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO

COMMENCING ANY WORK ON THIS SITE.

C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY

UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING ON

THIS SITE.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH STRUCTURAL

ENGINEER FOR CONDUIT OPENING IN STRUCTURAL SUPPORT.

E. REFER TO SINGLE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

F. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE RATED

NEMA 3R.

G. SITE AND LANDSCAPE LIGHTING SHALL BE CONTROLLED VIA PHOTOCELL-

ON AND TIMECLOCK-OFF. FIXTURES SHALL BE PROVIDED WITH INTEGRAL

PHOTOCELL.

GENERAL NOTES

PHASE 1:

A. CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE

DEMOLITION/RENOVATION PLANS AND IDENTIFY ALL

UNDERGROUND ROUTING OF NEW WORK ENSURING EXISTING

INSTALLATION OF UNDERGROUND UTILITIES ARE NOT DISTURBED.

B. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

EXISTING SECTIONAL SWITCH (SS) #12 TO NEW ELECTRICAL

MANHOLE (EMH) #26A. PREP AREA WHERE FINAL CONNECTION OF

SS #12 IS TO BE MADE. DO NOT MAKE FINAL CONNECTION UNTIL

SHUT DOWN OF SS #12 IS COMPLETED DURING PHASE 4. PROVIDE

PULL CORD AS REQUIRED.

C. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26A TO NEW EMH#26B. PROVIDE PULL CORD AS

REQUIRED.

D. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26B UP TO EXISTING BUILDING 6'S 300KVA PAD

MOUNTED TRANSFORMER. PREP AREA WHERE FINAL CONNECTION

OF BUILDING 6'S TRANSFORMER IS TO BE MADE. DO NOT MAKE

FINAL CONNECTION UNTIL SHUT DOWN OF BUILDING 6'S

TRANSFORMER IS COMPLETED DURING PHASE 4. PROVIDE PULL

CORD AS REQUIRED.

E. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM

NEW EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE,

EPB #25 MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. PREP

AREA WHERE FINAL CONNECTION OF EMH #25 IS TO BE MADE. DO

NOT MAKE FINAL CONNECTION UNIT SHUT DOWN OF LOOP C AND D

ARE COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS

REQUIRED.

F. INSTALL NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27

MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. INSTALL NEW

UNDERGROUND 13.8KV DUCTBANK FEEDER ON BOTH SIDES TO

CONNECT TO EXISTING AS REQUIRED.

G. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM

NEW EMH #26 TONEW EPB #27. PROVIDE PULL CORD AS REQUIRED.

H. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM

NEW EMH #26 TO NEW EMH #26A. COORDINATE WITH CIVIL PLANS

AND NEW UNDERGROUND TUNNEL. PROVIDE PULL CORD AS

REQUIRED.

PHASE 2:

A. INSTALL NEW UNDERGROUND DUCTBANK FROM NEW 300KVA PAD

MOUNTED TRANSFORMER TO EXISTING 225KVA PAD MOUNTED

TRANSFORMER PREVIOUSLY SERVICING BUILDING #25. DO NOT

MAKE FINAL CONNECTION UNTIL SHUT DOWN OF SS #11 IS

COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS REQUIRED.

B. INSTALL CONCRETE PAD AND 300KVA TRANSFORMER WITH

INTEGRAL FUSE. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.

ENSURE TRANSFORMER SWITCH/FUSE ARE IN THE "OFF" POSITION

UNTIL NEW CLC IS READY FOR SERVICE.

PHASE 3:

A. CONTRACTOR SHALL PROVIDE AND INSTALL A SEPARATE DIESEL

GENERATOR FOR EACH BUILDING 6 AND 7 AND MAN THE

OPERATIONS. GENERATOR WILL ACT AS NORMAL POWER DURING

PHASE 4. VA'S EMERGENCY GENERATOR SHALL NOT BE USED FOR

NORMAL WORKING ACTIVITIES. HOWEVER, MAY BE USED FOR

CONTRACTOR PROVIDED GENERATOR INSPECTION PURPOSES

ONLY. PROVIDE SUPERVISION, FUEL AND REQUIRED RECORD

DOCUMENTATION DURING RUNTIME AND TESTING.

1) BUILDING 6'S TEMPORARY GENERATOR SHALL BE SIZED

FOR A MINIMUM OF 400KVA OR 1000A WITH AT LEAST 96

HOURS OF FUEL TIME.

2) BUILDING 7'S TEMPORARY GENERATOR SHALL BE SIZED

FOR A MINIMUM OF 720KVA OR 2000A WITH AT LEAST 96 HOURS

OF FUEL TIME.

B. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN

BUILDING 6 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT

MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED

DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.

C. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN

BUILDING 7 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT

MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED

DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.

PHASE 4:

A. COORDINATE ELECTRICAL SERVICE SHUT DOWN OF LOOP C AND D

WITH THE VA COR. CONTRACTOR SHALL PROVIDE A PLAN IN

WRITTEN FORM FOR APPROVAL FROM THE COR. CONTRACTOR

SHALL COORDINATE AT LEAST THREE (3) MONTHS PRIOR WITH THE

VA COR FOR ACTUAL SHUT DOWN; ONLY (1) ONE SHUT DOWN WILL

BE ACCEPTABLE. CONTRACTOR SHALL ENSURE SUFFICIENT

STAFFS (A MINIMUM OF A TWO-MAN CREW AT EACH AFFECTED

MANHOLE) SHALL BE PROVIDED ON SITE TO MINIMIZE SHUT DOWN

DURATION. COMPLETION OF WORK DURING SHUT DOWN SHALL BE

DONE OVER ONE WEEKEND AND MUST NOT EXCEED TWO DAYS.

B. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL

SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING

BUILDING 6 AND MAKE CONNECTION FROM TEMPORARY

GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START

UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.

C. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL

SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING

BUILDING 7 AND MAKE CONNECTION FROM TEMPORARY

GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START

UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.

D. SEVER LOOP C AND D AT EXISTING EMH #26A. PULL BACK 13.8KV

FEEDERS FROM EXISTING EMH #26A TO EXISTING EMH #27. ON THE

OTHER SIDE, PULL BACK 13.8KV FEEDERS FROM EMH #26A TO

EXISTING EMH #25. DEMOLISH ASSOCIATED DUCTBANK AS

REQUIRED.

E. DISCONNECT CONNECTION OF UNDERGROUND 13.8KV FEEDER

FROM SS #12 AND BUILDING 6'S TRANSFORMER. DEMOLISH

ASSOCIATED DUCTBANK AS REQUIRED.

F. REMOVE EXISTING 225KVA PAD MOUNTED TRANSFORMER

PREVIOUSLY SERVICING DEMOLISHED BUILDING #25. REMOVE

EXISTING CONDUCTORS FROM EXISTING 225KVA PAD MOUNTED

TRANSFORMER TO EXISTING EXISTING SS #11 VIA EXISTING

ELECTRICAL MANHOLE #28. ENSURE EXISTING CONCRETE

ENCASED DUCTBANK IS PROTECTED TO BE REUSED. EXTEND

EXISTING DUCTBANK TO NEW DUCTBANK AS SHOWN ON ES100.

PULL NEW CONDUCTORS AS REQUIRED FROM EXISTING SS #11 TO

NEW CLC'S TRANSFORMER LOCATION.

G. BORE EXISTING ELECTRICAL MANHOLES #27 AND #25 AS SHOWN

ON SHEET ES100.

H. MAKE FINAL CONNECTION AND PULL NEW CONDUCTORS AT THE

FOLLOWING LOCATION:

1) EXISTING EMH #27 TO NEW EPB #27.

2) NEW EPB #27 TO NEW EMH #26.

3) NEW EMH #26 TO NEW EMH #26A.

4) NEW EMH #26A TO NEW EPB #25

5) NEW EPB #25 TO EXISTING EMH #25.

6) EXISTING SS #12 TO NEW EMH #26A.

7) NEW EMH #26A TO NEW EMH #26B.

8) NEW EMH #26B TO EXISTING BUILDING 6'S 300KVA

TRANSFORMER.

9) EXISTING SS #11 TO NEW 300KVA PAD MOUNTED

TRANSFORMER. ENSURE TRANSFORMER FUSE IS IN THE OFF

POSITION UNTIL NEW CLC IS READY FOR SERVICE.

SEQUENCE OF OPERATIONS

N

KEY PLAN

AREA B

(EAST)

AREA A

(WEST)

LEVEL 2

PENTHOUSE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:2

A M

ES100

ELECTRICAL RENOVATION OVERALL SITE PLAN

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1" = 30'-0"

ELECTRICAL RENOVATION SITE PLAN

KEYNOTES

1 PROVIDE NEW UNDERGROUND CONCRETE ENCASED DUCTBANK SERVICE FEEDER FROM

NEW PAD MOUNTED TRANSFORMER UP TO EXISTING DUCTBANK. PROVIDE NEW 13.8 KV,

3-PHASE CONDUCTORS FROM EXISTING SECTIONAL SWITCH SS#11 THROUGH EXISTING

ELECTRICAL MANHOLE #28 TO NEW PAD MOUNTED TRANSFORMER. COORDINATE ALL

REQUIREMENTS WITH VA. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.

2 APPROXIMATE LOCATION OF 208/120V-3PH, PAD-MOUNTED TRANSFORMER. COORDINATE

FINAL LOCATION WITH VA.

3 UNDERGROUND 208/120V-3PH DIRECT BURIAL SECONDARY ELECTRIC SERVICE

CONDUCTORS TO MAIN DISTRIBUTION PANEL, MDP. COORDINATE STUB-UP REQUIREMENTS

IN SECONDARY COMPARTMENT OF TRANSFORMER WITH VA.

4 APPROXIMATE LOCATION OF NORMAL POWER ELECTRICAL ROOM. SEE FLOOR PLANS FOR

ADDITIONAL INFORMATION.

5 36" UNDERGROUND DIRECT BURIAL EMERGENCY ELECTRIC SERVICE FEEDER FROM

GENERATOR TO EMERGENCY ENCLOSED CIRCUIT BREAKERS. SEE FLOOR PLANS AND

SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION.

6 APPROXIMATE LOCATION OF IT CLOSET. SEE FLOOR PLANS FOR ADDITIONAL INFORMATION.

7 APPROXIMATE LOCATION OF TELEPHONE TERMINAL BACKBOARD. SEE FLOOR PLANS FOR

ADDITIONAL INFORMATION.

8 PROVIDE (2) 1" CONDUITS UNDERGROUND WITH PULL STRINGS FROM GENERATOR

CONTROLS TO IT ROOM. MAA AT THE BOILER PLANT SHALL MONITOR GENERATOR.

9 PROVIDE (2) 4" CONDUITS WITH PULL STRINGS BURIED 30" B.F.G. TO EXISTING EMH #24 FOR

TELEPHONE AND DATA SERVICES; CAP AND MARK FOR INSTALLATION FOR COMMUNICATION

SERVICES. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL TELEPHONE REQUIREMENTS

AND TERMINATION POINT WITH SERVICE PROVIDER/VA. SEE SHEET EY100 FOR ADDITIONAL

INFORMATION.

10 90" X 72" X 24" (HxWxD) NEW FREESTANDING NEMA 4X ENCLOSURE WITH LOAD BREAK

ELBOWS ON BOTH SIDES OF THE TERMINAL BLOCKS MOUNTED ON CONCRETE PAD FOR 13.8

KV, 3-PH POWER FEED CONNECTIONS. TERMINATE BACK TO EXISTING ELECTRICAL C AND D

LOOPS. BASIS OF DESIGN IS HUBBELL WRD907224SSFSDN4.

11 NEW ELECTRICAL MANHOLE.

12 NEW UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM NEW FREESTANDING

NEMA 4X ENCLOSURE, ELECTRICAL PULL BOX EPB #27 TO NEW ELECTRICAL MANHOLE EMH

#26A VIA NEW ELECTRICAL MANHOLE EMH #26.

13 NEW UNDERGROUND 13.8 KV, 3-PH CONDUCTORS FROM NEW ELECTRICAL MANHOLE EMH

#26A TO NEW ELECTRICAL MANHOLE EMH #26B.

14 NEW UNDERGROUND 13.8 KV, 3-PH UTILITY SERVICE FEEDER TO EXISTING UTILTY

TRANSFORMER #1 SERVICING EXISTING BUILDING #6.

15 APPROXIMATE LOCATION OF EXISTING PAD-MOUNTED UTILITY TRANSFORMER #1 SERVICING

BUILDING #6.

16 NEW UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM NEW ELECTRICAL

MANHOLE EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE, ELECTRICAL PULL BOX

EPB #25.

17 WP JUNCTION BOX FOR GENERATOR CONTROL PANEL.

18 WP JUNCTION BOX FOR JACKET WATER HEATER.

19 WP JUNCTION BOX FOR BATTERY CHARGER.

20 APPROXIMATE LOCATION OF EMERGENCY STAND-BY GENERATOR. SEE SINGLE LINE

DIAGRAM, DETAILS H ON SHEET E501 AND CG503 FOR ADDITIONAL INFORMATION.

21 ABOVE GROUND 1000 GALLON DIESEL FUEL TANK WITH TANK SUPPORTS "FEET".

CONTRACTOR SHALL ENSURE BOTTOM OF TANK TO BE 1" OFF OF CONCRETE CURB/PAD

THAT IT SITS ON. SEE DETAIL 'H' ON SHEET E501 AND F1/CG503 FOR ADDITIONAL

INFORMATION.

22 ENCLOSURE AROUND GENERATOR. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.

23 WP DUPLEX FOR IRRIGATION CONTROLLER MOUNTED ON PEDESTAL. SEE LANDSCAPE

PLANS FOR ADDITIONAL INFORMATION.

24 WP JUNCTION BOX FOR MONUMENT SIGN. TIE CONTROLS TO TIME CLOCK-LCP. COORDINATE

ON/OFF REQUIREMENTS WITH COR.

25 NEW C AND D LOOP CONDUCTORS FROM EXISTING SS #12 TO NEW ELECTRICAL MANHOLE

#26A.

26 EXISTING UNDERGROUND DUCTBANK WITH NEW FEEDER.

27 BORE EXISTING ELECTRICAL MANHOLE #25 FOR NEW UNDERGROUND 13.8 KV, 3-PH C AND D

LOOP CONDUCTORS FROM NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #25. AT

EXISTING MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS REQUIRED

AND PRESERVE THE STEEL IN THE STRUCTURAL WALL. CUT STEEL AND EXTEND INTO THE

DUCT BANK ENVELOPE. CHIP THE PERIMETER SURFACE OF THE DUCT BANK OPENING TO

FORM A KEY OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR ADDITIONAL

INFORMATION.

28 PULL NEW TELECOMMUNICATION CABLES IN NEW CONCRETE ENCASED DUCTBANK.

29 NEW CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH 13.8KV, 3/C 2/0 PRIMARY AND

1#1 B/N AND TWO SPARE CONDUITS.

30 NEW CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 - 30#16 RHL. 1 - 24#16 RHL AND

2-3/C #16 RHL. 1 2#12 RHL. 1 - TELEPHONE. 1 - SPARE.

31 NEW FREESTANDING NEMA 4X ENCLOSURE MOUNTED ON CONCRETE PAD FOR

TELECOMMUNICATION CABLES FEED CONNECTIONS. TERMINATE BACK TO EXISTING

TELEPHONE CABLES.

32 REFER TO SPEC 26 05 41 SECTION 3.3.E FOR DIRECTION ON CONNECTING NEW DUCT TO

EXISTING.

33 BORE EXISTING ELECTRICAL MANHOLE #27 FOR NEW UNDERGROUND 13.8 KV, 3-PH C AND D

LOOP CONDUCTORS FROM NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27. AT

EXISTING MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS REQUIRED

AND PRESERVE THE STEEL IN THE STRUCTURAL WALL. CUT STEEL AND EXTEND INTO THE

DUCT BANK ENVELOPE. CHIP THE PERIMETER SURFACE OF THE DUCT BANK OPENING TO

FORM A KEY OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR ADDITIONAL

INFORMATION. REMOVE AND CONSTRUCT NEW MANHOLE #27.

34 NEW TELECOMMUNICATION MANHOLE.

35 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK. SEE DETAIL F5-CG506.

36 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF WEST OF TRANSFORMER #1.

SEE DETAIL F5-CG506.

37 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF EAST OF SS #12. SEE DETAIL

F5-CG506.

38 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF SOUTH EMH #25. SEE DETAIL

F5-CG506.

Revisions: Date:

J

S

SS #11

2"ø

2"ø

R

R

R

ES100A

ES100B

C2-30

C2-30

2"øC2-30

NEW CLC

BUILDING 6

DP - 8

EQ1-38

EQ1-39,41

EQ1-40

EMH #28

NL - 29

V

V

V V

V

V

V

U

EMH #27 TMH #27

EPB #2718 TPB #27 19

EMH #26 TMH #2621 22

25 26

A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT

ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,

ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO

COMMENCING ANY WORK ON THIS SITE.

B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW

VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION

LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS

PRIOR TO COMMENCING ANY WORK ON THIS SITE.

C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY

UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING

ON THIS SITE.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH

STRUCTURAL ENGINEER FOR CONDUIT OPENING IN STRUCTURAL

SUPPORT.

E. REFER TO SINGLE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

F. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE

RATED NEMA 3R.

G. SITE AND LANDSCAPE LIGHTING SHALL BE CONTROLLED VIA

PHOTOCELL-ON AND TIMECLOCK-OFF. FIXTURES SHALL BE

PROVIDED WITH INTEGRAL PHOTOCELL.

H. SEE SHEET ES100 ELECTRICAL RENOVATION OVERALL SITE PLAN

FOR ADDITIONAL INFORMATION.

GENERAL NOTES

N

KEY PLAN

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:0

:2

A M

ES100A

ELECTRICAL RENOVATION SITE PLAN - AREA A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

05/09/2022 DK SC

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/16" = 1'-0"

ELECTRICAL RENOVATION SITE PLAN - AREA A

KEYNOTES

1 APPROXIMATE LOCATION OF TELEPHONE TERMINAL BACKBOARD.

SEE FLOOR PLANS FOR ADDITIONAL INFORMATION.

2 PROVIDE NEW UNDERGROUND CONCRETE ENCASED DUCTBANK

SERVICE FEEDER FROM NEW PAD MOUNTED TRANSFORMER UP TO

EXISTING DUCTBANK. PROVIDE NEW 13.8 KV, 3-PHASE

CONDUCTORS FROM EXISTING SECTIONAL SWITCH SS#11 THROUGH

EXISTING ELECTRICAL MANHOLE #28 TO NEW PAD MOUNTED

TRANSFORMER. COORDINATE ALL REQUIREMENTS WITH VA. SEE

CIVIL PLANS FOR ADDITIONAL INFORMATION.

3 APPROXIMATE LOCATION OF 208/120V-3PH, PAD-MOUNTED

TRANSFORMER. COORDINATE FINAL LOCATION WITH VA.

4 UNDERGROUND 208/120V-3PH DIRECT BURIAL SECONDARY

ELECTRIC SERVICE CONDUCTORS TO MAIN DISTRIBUTION PANEL,

MDP. COORDINATE STUB-UP REQUIREMENTS IN SECONDARY

COMPARTMENT OF TRANSFORMER WITH VA.

5 APPROXIMATE LOCATION OF IT CLOSET. SEE FLOOR PLANS FOR

ADDITIONAL INFORMATION.

6 PROVIDE (2) 4" CONDUITS WITH PULL STRINGS BURIED 30" B.F.G. TO

EXISTING EMH #24 FOR TELEPHONE AND DATA SERVICES; CAP AND

MARK FOR INSTALLATION FOR COMMUNICATION SERVICES.

ELECTRICAL CONTRACTOR SHALL COORDINATE ALL TELEPHONE

REQUIREMENTS AND TERMINATION POINT WITH SERVICE

PROVIDER/VA. SEE SHEET EY100 FOR ADDITIONAL INFORMATION.

7 WP JUNCTION BOX FOR GENERATOR CONTROL PANEL.

8 WP JUNCTION BOX FOR BATTERY CHARGER.

9 WP JUNCTION BOX FOR JACKET WATER HEATER.

10 36" UNDERGROUND DIRECT BURIAL EMERGENCY ELECTRIC

SERVICE FEEDER FROM GENERATOR TO EMERGENCY ENCLOSED

CIRCUIT BREAKERS. SEE FLOOR PLANS AND SINGLE LINE DIAGRAM

FOR ADDITIONAL INFORMATION.

11 PROVIDE (2) 1" CONDUITS UNDERGROUND WITH PULL STRINGS

FROM GENERATOR CONTROLS TO IT ROOM. MAA AT THE BOILER

PLANT SHALL MONITOR GENERATOR.

12 APPROXIMATE LOCATION OF EMERGENCY STAND-BY GENERATOR.

SEE SINGLE LINE DIAGRAM, DETAILS H ON SHEET E501 AND CG503

FOR ADDITIONAL INFORMATION.

13 ABOVE GROUND 1000 GALLON DIESEL FUEL TANK WITH TANK

SUPPORTS "FEET". CONTRACTOR SHALL ENSURE BOTTOM OF TANK

TO BE 1" OFF OF CONCRETE CURB/PAD THAT IT SITS ON. SEE

DETAIL 'H' ON SHEET E501 AND F1/CG503 FOR ADDITIONAL

INFORMATION.

14 ENCLOSURE AROUND GENERATOR. SEE CIVIL PLANS FOR

ADDITIONAL INFORMATION.

15 WP DUPLEX FOR IRRIGATION CONTROLLER MOUNTED ON

PEDESTAL. SEE LANDSCAPE PLANS FOR ADDITIONAL INFORMATION.

16 EXISTING UNDERGROUND DUCTBANK WITH NEW FEEDER.

17 NEW CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH

13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N AND TWO SPARE CONDUITS.

18 90" X 72" X 24" (HxWxD) NEW FREESTANDING NEMA 4X ENCLOSURE

WITH LOAD BREAK ELBOWS ON BOTH SIDES OF THE TERMINAL

BLOCKS MOUNTED ON CONCRETE PAD FOR 13.8 KV, 3-PH POWER

FEED CONNECTIONS. TERMINATE BACK TO EXISTING ELECTRICAL C

AND D LOOPS. BASIS OF DESIGN IS HUBBELL WRD907224SSFSDN4.

19 NEW FREESTANDING NEMA 4X ENCLOSURE MOUNTED ON

CONCRETE PAD FOR TELECOMMUNICATION CABLES FEED

CONNECTIONS. TERMINATE BACK TO EXISTING TELEPHONE

CABLES.

20 BORE EXISTING ELECTRICAL MANHOLE #27 FOR NEW

UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM

NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27. AT EXISTING

MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS

REQUIRED AND PRESERVE THE STEEL IN THE STRUCTURAL WALL.

CUT STEEL AND EXTEND INTO THE DUCT BANK ENVELOPE. CHIP THE

PERIMETER SURFACE OF THE DUCT BANK OPENING TO FORM A KEY

OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR

ADDITIONAL INFORMATION. REMOVE AND CONSTRUCT NEW

MANHOLE #27.

21 NEW ELECTRICAL MANHOLE.

22 NEW TELECOMMUNICATION MANHOLE.

23 REFER TO SPEC 26 05 41 SECTION 3.3.E FOR DIRECTION ON

CONNECTING NEW DUCT TO EXISTING.

24 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK. SEE

DETAIL F5-CG506.

25 PULL NEW TELECOMMUNICATION CABLES IN NEW CONCRETE

ENCASED DUCTBANK.

26 NEW CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 - 30#16

RHL. 1 - 24#16 RHL AND 2-3/C #16 RHL. 1 2#12 RHL. 1 - TELEPHONE. 1 -

SPARE.

Revisions: Date:

SS #12

EMH #26A

EMH #26B

EPB #25

EMH #25

R

R

R

R

R

2"ø

2"ø

2"ø

2"ø

2"ø

ES100A

ES100B

C2-40

C2-40

C2-40

C2-40

C2-40

DP - 16

DP - 14

NL - 33

NL - 31

V

W

W

V

U

U

U

V

W

W

V

VV

U

V

W

V

V

V

W

W W

W

W

W

W

W W

W

W

TPB #25 19

TMH #25 22

A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT ENGINEER AT THE SITE TO

VERIFY TERMINATION LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS

PRIOR TO COMMENCING ANY WORK ON THIS SITE.

B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW VOLTAGE SYSTEM PROVIDER AT THE

SITE TO VERIFY TERMINATION LOCATION, ROUTING OF CONDUITS AND ROUGH-IN

REQUIREMENTS PRIOR TO COMMENCING ANY WORK ON THIS SITE.

C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY UNDERGROUND LOCATING

SERVICE COMPANY PRIOR TO DIGGING ON THIS SITE.

D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER FOR CONDUIT

OPENING IN STRUCTURAL SUPPORT.

E.…

This is the start of the file's text. The full file is on GovTribe.