This document contains a government file related to a federal contract opportunity for construction services. The file is titled "Drawings 14 of 15 ELECTRICAL 1.pdf" and is 11MB in size. It is associated with solicitation number 36C77623R0156 from the Department of Veterans Affairs Technology Acquisition Center Austin to build a new community living center at the Montrose VA medical center. The opportunity type is listed as a solicitation for the construction of a minor facility. The solicitation seeks to award a contract to provide construction services for a new community living center to support veterans. It includes drawings to aid prospective offerors in developing their responses.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. THIS IS A COMPLETE LIST OF ELECTRICAL SYMBOLS AND ABBREVIATIONS FOR
REFERENCE ONLY. SYMBOLS SHOWN ON THIS DRAWING MAY NOT APPEAR ON THE
FOLLOWING DRAWINGS.
2. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED SHUTDOWNS ON EXISTING
UTILITIES WITH OWNER REPRESENTATIVES IN ORDER TO MINIMIZE IMPACT TO OTHER
AREAS.
3. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND
LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING
JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE ENGINEERING DOCUMENTS AND
CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
4. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:
- NFPA 101-2018, THE LIFE SAFETY CODE
- NFPA 70-2017, NATIONAL ELECTRICAL CODE
- NFPA 72-2016, NATIONAL FIRE ALARM CODE
5. ALL WIRING SHALL BE IN CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM
CONDUCTOR SIZE SHALL BE #12 AWG. ALL NEW CIRCUITS SHALL BE PROVIDED WITH
AN INDIVIDUAL NEUTRAL AND GROUNDING CONDUCTOR WITH THE PHASE
CONDUCTOR.
6. THE ELECTRICAL DRAWINGS ARE SCHEMATIC IN NATURE. BEFORE STARTING THE
WORK THE CONTRACTOR SHALL REVIEW ALL OTHER DISCIPLINE DRAWINGS AND
VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS
WITHOUT EXTRA COST TO THE VA. ANY MAJOR DISCREPANCIES FOUND SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER.
7. ALL DEVICES, EQUIPMENT MATERIAL AND LABOR SHALL BE PROVIDED BY THE
CONTRACTOR UNLESS NOTED OTHERWISE.
8. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE MOUNTED AS PER EQUIPMENT
AND DEVICE MANUFACTURER RECOMMENDATIONS.
9. CONTRACTOR SHALL PROVIDE SUBMITTALS TO ARCHITECT/ENGINEER FOR REVIEW
AND APPROVAL OF ALL ELECTRICAL EQUIPMENT AND DEVICES DESCRIBED IN THE
SUBMITTAL REGISTER. SUBMITTALS SHALL INCLUDE CUT SHEETS, DIMENSIONS,
WIRING DIAGRAMS, ACCESSORIES, OPERATION MANUALS, AND ALL NECESSARY
INFORMATION FOR REVIEWER TO MAKE A SOUND EVALUATION.
10. PROVIDE STARTUP OF ALL ELECTRICAL SYSTEMS AND COORDINATE WITH
ARCHITECT/ENGINEER FOR OWNER STARTUP WITNESSING.
11. PROVIDED LAMINATED PLASTIC NAMEPLATES FOR EACH EQUIPMENT ENCLOSURE.
EACH NAMEPLATE IDENTIFY EQUIPMENT FUNCTION, PANELBOARD CONNECTED AND
CIRCUIT NUMBER. NAMEPLATE SHALL BE MELAMINE PLASTIC (0.125 INCHES THICK),
WHITE LETTERS ON BLACK BACKGROUND. MINIMUM SIZE OF LETTERS SHALL BE 2.5
INCHES. IN ADDITION TO EQUIPMENT TAGGING, CONTRACTOR SHALL PROVIDE ARC-
FLASH WARNING SIGNS FOR PANELBOARDS.
12. PROVIDE COMPUTER PRINTED ON WHITE WRAPAROUND PAPER WITH CLEAR PLASTIC
PROTECTION TAIL FOR ALL WIRE MARKERS. MARKER SHALL STATE PANELBOARD
NAME AND CIRCUIT NUMBER ON ALL WIRES IN JUNCTION/PULL BOXES AND IN
EQUIPMENT TERMINAL BOXES.
13. PROVIDE PUNCHED TAPE LABELS ON ALL WIRING DEVICES FOR IDENTIFICATION. SHALL
BE ½” BLACK TAPE WITH WHITE RAISED LETTERS. TAPE LABELS SHALL STATE
PANELBOARD NAME AND CIRCUIT NUMBER.
14. PROVIDE DIRECTORIES ON ALL PANELBOARDS. BALANCE ALL LOADS ON PANELBOARD
WITHIN 10%.
15. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE SET OF RECORD
DRAWINGS TO THE VA AT THE END OF THE CONSTRUCTION.
16. ALL MATERIALS AND EQUIPMENT TO BE INSTALLED SHALL BE NEW AND FREE OF
DEFECTS. ALL ELECTRICAL EQUIPMENT SHALL COMPLY WITH NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION (NEMA) STANDARDS AND SHALL BE UL LABELED. ALL
ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE INSTALLED IN A WORKMANLIKE
MANNER.
17. ALL CONNECTORS AND SPLICES FOR CABLE SIZE #10 AWG AND SMALLER SHALL BE
INSULATED, PRESSURE-TYPE. FOR LARGER SIZE CONDUCTORS USE BOLTED CLAMPS
WITH INSULATING TAPE.
18. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS,
STRUCTURE, PLUMBING, AND OTHER PIPING IN THE CEILING SPACE. COORDINATE ALL
CONDUITS/WIRING ROUTING WITH ALL OTHER TRADES.
19. WHERE JOB CONDITIONS REQUIRE CHANGE FROM THE CONTRACT DOCUMENTS THAT
DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR
SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE VA. NO OTHER
CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.
20. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF
CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT
CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL
CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH
ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER
CONSTRUCTION COMPLETION.
21. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES
(FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE
RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER
WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.
GENERAL PROJECT NOTES
CONDUIT AND WIRING
BRANCH CIRCUIT RUN CONCEALED
BRANCH CIRCUIT RUN UNDER FLOOR
BRANCH CIRCUIT DOWN
BRANCH CIRCUIT UP
HOME RUN TO PANEL 2A CKTS 1,3, & 52A-1,3,5
ELECTRICAL ABBREVIATIONS
A AMP
AA AUTOMATIC ALTERNATOR
AC ALTERNATING CURRENT
ACU AIR CONDITIONER UNIT
AF AMPERAGE FRAME
AFF ABOVE FINISHED FLOOR
ANN ANNUNCIATOR
AS AMMETER SWITCH
AT AMPERE TRIP
AX AUXILIARY DELAY
BKR BREAKER
CB CIRCUIT BREAKER
COL COLUMN
CL CENTERLINE
CKT CIRCUIT
CF(P OR L) CLOSE ON FALLING
(PRESSURE OR LEVEL)
CR(P OR L) CLOSE ON RISING
(PRESSURE OR LEVEL)
CH CONVECTION HEATER
COMPT COMPARTMENT
COND CONDUCTOR
CDT CONDUIT
C-( ) CONTRACT-( ) ID
CPT CONTROL POWER
TRANSFORMER
CR-( ) CONTROL RELAY-( ) ID
I/I CURRENT TO CURRENT
TRANSDUCER
I/P CURRENT TO PNEUMATIC
TRANSDUCER
CT CURRENT TRANSFORMER
D EXISTING TO BE DEMOLISHED
DC DIRECT CURRENT
DF DUST FILTER
DIA DIAMETER
DISTR DISTRIBUTION
DP DIFFERENTIAL PRESSURE
DS DISCONNECT SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
E EXISTING TO REMAIN
EBB ELECTRIC BASED BOARD
EC ELECTRICAL CONTRACTOR
ECH ELECTRIC CEILING HEATER
EDH ELECTRIC DUCT HEATER
EF ELECTRIC FIN
EMT ELECTRIC METALLIC TUBING
ER EXISTING TO BE REMOVED AND
RELOCATED
ETM ELAPSED TIME METER
EUH ELECTRIC UNIT HEATER
EWC ELECTRIC WATER COOLER
F FLOW
FDR FEEDER
FLA FULL LOAD AMPS
FMC FLEXIBLE METALLIC CONDUIT
FOS FAST-OFF-SLOW
F-S FAST-SLOW
FT FEET
F-R FORWARD REVERSE
FR FRAME
FUSS FUSED SAFETY SWITCH
FVNR FULL VOLTAGE NON-REVERSING
G GREEN
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GPM GALLONS PER MINUTE
GND GROUND
GRV GRAVITY RELIEF VENT
GUH GAS UNIT HEATER
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HV HOUSE VACUUM
HZ HERTZ
ID IDENTIFICATION NUMBER
IC INTERRUPTING CAPACITY
IF INFRARED HEATER
IMC INTERMEDIATE METAL CONDUIT
INF IN LINE FAN
I/O INPUT/OUTPUT
IT INTERCHANGEABLE TRIP OR
INSTANTANEOUS TRIP
JB JUNCTION BOX
kcmil THOUSAND CIRCULAR MILS
KUH/EUH ELECTRIC UNIT HEATER
KVA KILOVOLT AMPERE
KV KILOVOLT
KVAR KILOVOLT AMPERES REACTIVE
KW KILOWATT
L LEVEL
LC LOUVER CONTROLLER
LFMC LIQUID-TIGHT FLEXIBLE
METAL CONDUIT
LM LOUVER MOTOR
LP( )-( ) LIGHTING CIRCUIT ( )
LP( ) LIGHTING PANELBOARD
LS LIMIT SWITCH
LV LOUVER
M MANUAL MOTOR STARTER
mA MILLIAMPERES
MC METAL CLAD CABLE
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTOR
MEZZ MEZZANINE
MF-( ) MAIN FEEDER-( ) ID
MGD MILLION GALLONS PER DAY
MS MOTOR STARTER
MTD MOUNTED
MTR MOTORIZED TIMING RELAY
MUAU MAKE UP AIR UNIT
MX MOTOR AUXILIARY RELAYS
(N) NEW
NAC NOTIFICATION APPLIANCE
CIRCUIT
NP NAMEPLATE
NF NON FUSED
NFSS NON FUSED SAFETY SWITCH
NCT NURSE CALL TERMINAL CABINET
N.O. NORMALLY OPEN
No. NUMBER
OHD OVERHEAD DOOR
( )OL OVERLOAD ( ) NUMBER OF
P PRESSURE
( )P POLES ( ) NO OF POLES
∅ or PH PHASE
P/I PNEUMATIC TO CURRENT
TRANSDUCER
PLC PROGRAMMABLE LOGIC
CONTROLLER
PRE POWER ROOF EXHAUSTER
PS PRESSURE SWITCH
PT POTENTIAL TRANSFORMER
PTAC PACKAGE TERMINAL
AIR CONDITIONER
PTR PNEUMATIC TIMING RELAY
PVC POLYVINYL CHLORIDE
RIGID CONDUIT
PVC-RSC PVC COATED RIGID
STEEL CONDUIT
PWV POWER WALL VENTILATOR
QTY QUANTITY
R RELOCATED
RAC RIGID ALUMINUM
RECPT RECEPTACLE
REQ REQUIRED
RMS ROOT MEAN SQUARE
RSC RIGID STEEL CONDUIT
RTU REMOTE TERMINAL UNIT
SAF SUPPLY AIR FAN
STP SHIELDED TWISTED PAIR
SL STOP LOCKOUT
SMC SMART MOTOR CONTROLLER
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SS SELECTOR SWITCH
S/S START/STOP
S/SL START/STOP LOCKOUT
SV SOLENOID VALVE
SYM SYMMETRICAL
T or T'STAT THERMOSTAT
T-( ) TELEPHONE CONDUIT-( )
TCC TIME-CLOSE CONTACT
TEMP TEMPERATURE
TC TEMPERATURE CONTRACTOR
TOC TIME-OPEN CONTACT
TR TIMING RELAY
TRI SHIELDED TRIPLE CABLE
TS TEMPERATURE SWITCH
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
UF UNDERGROUND FEEDER
UH UNIT HEATER
VA VOLT - AMPERE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
VS VOLTMETER SWITCH
VT VOLTAGE TRANSFORMER
W WATT
WH WATER HEATER
WP WEATHERPROOF
S S S3 4
S D
S
PB
S F
OS
RC
SINGLE-POLE, 3-WAY AND 4-WAY
SWITCHES (48"AFF)
ELECTRICAL DEVICES
(MOUNTING HEIGHT TO CENTER LINE
OF BOX UNLESS NOTED OTHERWISE)
LOCAL WALL DIMMER SWITCH (48" AFF)
PUSH-BUTTON SWITCH (48" AFF)
FAN SWITCH (48" AFF)
WALL MOUNTED OCCUPANCY SENSOR SWITCH;
DUAL TECHNOLOGY
(PASSIVE INFRARED/ULTRASONIC)
CEILING MOUNTED OCCUPANCY/VACANCY SENSOR;
DUAL TECHNOLOGY
(PASSIVE INFRARED/ULTRASONIC)
ROOM CONTROLLER (REFER TO PLANS)
TIMECLOCK (REFER TO PLANS)T
DUPLEX RECEPTACLE (18"AFF)
DOUBLE DUPLEX RECEPTACLE (18" AFF)
DUPLEX RECEPTACLE -
FLOOR BOX
SIMPLEX RECEPTACLE (18" AFF)
DUPLEX RECEPTACLE MOUNTED 6" ABOVE COUNTER
OR BACKSPLASH
GFCI DUPLEX RECEPTACLE GFCI
GFCI/WP GFCI DUPLEX RECEPTACLE WITH WHILE-IN-USE
WEATHERPROOF COVER
SPECIAL RECEPTACLE (18"AFF) - TYPE
AS NOTED
PLUG MOLD/WIRE MOLD RACEWAY
PUSH BUTTON
2X4 FIXTURE - RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
ELECTRICAL LIGHTING FIXTURE SYMBOLS
2X4 LIFE SAFETY BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED
2X2 FIXTURE - RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
2X2 LIFE SAFETY BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED
1X4 FIXTURE - RECESSED, SURFACE, OR PENDANT
MOUNTED - TYPE AS SPECIFIED
1X4 LIFE SAFETY BRANCH FIXTURE - RECESSED,
SURFACE, OR PENDANT MOUNTED - TYPE AS SPECIFIED
4' STRIP FIXTURE - TYPE AS SPECIFIED
4' STRIP LIFE SAFETY BRANCH FIXTURE - TYPE AS
SPECIFIED
1X4 FIXTURE - SURFACE MOUNTED - TYPE AS
SPECIFIED
1X4 LIFE SAFETY BRANCH FIXTURE - SURFACE
MOUNTED - TYPE AS SPECIFIED
1X4 FIXTURE - WALL MOUNTED - TYPE AS SPECIFIED
1X4 LIFE SAFETY BRANCH FIXTURE - WALL
MOUNTED - TYPE AS SPECIFIED
LIGHTING FIXTURE - RECESSED OR SURFACE
MOUNTED - TYPE AS SPECIFIED
LIFE SAFETY BRANCH LIGHTING FIXTURE -
RECESSED OR SURFACE - TYPE AS SPECIFIED
LIGHTING FIXTURE - PENDANT MOUNTED - TYPE
AS SPECIFIED
LIFE SAFETY BRANCH LIGHTING FIXTURE -
PENDANT MOUNTED - TYPE AS SPECIFIED
WALL MOUNTED - TYPE AS SPECIFIED
LIFE SAFETY BRANCH WALL FLUSH MOUNTED -
TYPE AS SPECIFIED
SELF CONTAINED EMERGENCY LIGHTING UNIT -
TYPE AS SPECIFIED
COMBINATION EXIT SIGN & SELF CONTAINED
EMERGENCY LIGHTING UNIT - TYPE AS SPECIFIED
EXIT SIGN - CEILING MOUNTED - TYPE AS SPECIFIED
EXIT SIGN - WALL MOUNTED - TYPE AS SPECIFIED
FIRE ALARM SYMBOLS
MANUAL PULL STATION (46" AFF)F
S
S
BELL/STROBE LIGHT COMBINATION (80" AFF)
STROBE LIGHT (80" AFF)
HORN (80" AFF)H
H
S
B
HORN/STROBE LIGHT COMBINATION (80" AFF)
SPEAKER/STROBE (80" AFF)
PROGRAM BELL (80" AFF)
SMOKE DETECTOR - CEILING MOUNTED
SMOKE ALARM - CEILING MOUNTED
DUCT DETECTOR
SD
SA
DD
TS
FS
D
TAMPER SWITCH
FLOW SWITCH
MAGNETIC DOOR HOLDER (72" AFF)
FIRE ALARM CONTROL PANEL
RECESSED FIRE ALARM CONTROL PANEL
FACP
FACP
GENERAL SYMBOLS
X
KEY NOTE INDICATOR
DRAWING REVISION INDICATOR
LINE TYPES
NEW WORK SCOPE OF WORK
EXISTING SCOPE OF WORK
DEMOLITION SCOPE OF WORK
FUTURE SCOPE OF WORK
-NEW BRANCH CIRCUIT W/ #12 AWG THHN WIRES
-SLASH LINES INDICATES WIRES IN CIRCUIT
-SHORT LINES DEPICTS PHASE CONDUCTOR
-LONG LINE DEPICTS NEUTRAL CONDUCTOR
-LONG LINE W/ DOT DEPICTS GROUND
UNDERGROUND ELECTRIC SECONDARY FEEDERUGPUGP
PANELBOARD
POWER DISTRIBUTION
TRANSFORMER
MOTOR CONNECTION - NUMERAL INDICATES HP
DISCONNECT SWITCH - FUSED -
AMPS/FUSE/POLE/NEMA
DISCONNECT SWITCH - NON-FUSED -
AMPS/POLES/NEMA
DISCONNECT SWITCH -
MOTOR/STARTER COMBINATION
VARIABLE FREQUENCY DRIVE
CONTROL PANEL
JUNCTION BOX OR PULL BOX
WALL MOUNTED JUNCTION BOX OR PULL BOX
VFD
CP
J
J
COMMUNICATION DEVICES
DATA OUTLET (18" AFF); DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING WITH 1"C AND PULL STRING
TO ACCESSIBLE CEILING, PROVIDE NYLON BUSHING ON
END OF CONDUIT FOR PROTECTION OF WIRE, PROVIDE 6
PORTS, CAT6A, RJ45
(MOUNTING HEIGHT TO
CENTER LINE OF BOX
UNLESS NOTED OTHERWISE
ABOVE COUNTER DATA OUTLET (6" ABOVE COUNTER
OR BACKSPLASH); DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING WITH 1"C AND PULL
STRING TO ACCESSIBLE CEILING, PROVIDE NYLON
BUSHING ON END OF CONDUIT FOR PROTECTION OF
WIRE, PROVIDE 6 PORTS, CAT6A, RJ45
DATA OUTLET - CEILING MOUNTED; DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING WITH 1"C
AND PULL STRING TO ACCESSIBLE CEILING, PROVIDE
NYLON BUSHING ON END OF CONDUIT FOR
PROTECTION OF WIRE, PROVIDE 6 PORTS, CAT6A, RJ45
C
CABLE TV OUTLET WITH 1 CATV JACK (18" AFF);
PROVIDE 1"C WITH PULL STRING TO ACCESSIBLE
CEILING. PROVIDE INSULATED NYLON BUSHING ON END
OF CONDUIT FOR PROTECTION OF WIRE
12"x6" COMMUNICATION CABLE TRAY MOUNTED ABOVE
SUSPENDED CEILING
RECESSED PUBLIC ADDRESS SPEAKER; PROVIDED
WITH BAFFLE, GRILL AND MATCHING TRANSFORMER
S
S RECESSED PUBLIC ADDRESS SPEAKER; PROVIDED
WITH BAFFLE, GRILL AND MATCHING TRANSFORMER
CARD READER, FLUSH MOUNTED AT 42" AFF; PROVIDE
DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER
RING, 3/4" CONDUIT WITH PULL STRING TO DOOR
CONTROLLER
DOOR CONTACT; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
ELECTRIC DOOR (HINGE) STRIKE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
KEY PAD; PROVIDE DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH PULL
STRING TO DOOR CONTROLLER
INTRUSION DETECTION MOTION DETECTOR; PROVIDE
DOUBLE GANG BACK BOX WITH SINGLE GANG PLASTER
RING, 3/4" CONDUIT WITH PULL STRING TO ACCESSIBLE
CEILING
PUSH BUTTON/PUSH PLATE; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
CCTV CAMERA - FIXED; PROVIDE DOUBLE GANG BACK
BOX WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT
WITH PULL STRING TO ACCESSIBLE CEILING; WP =
WEATHERPROOF
CCTV CAMERA - 360° PTZ; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING;
WP = WEATHERPROOF
CR
DC
EH
K
MD
P
WP
WP
REQUEST TO EXIT (INFRARED); PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
RTE
DELAYED EGRESS; PROVIDE DOUBLE GANG BACK BOX
WITH SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH
PULL STRING TO DOOR CONTROLLER
DE
ELECTROMAGNETIC LOCK; PROVIDE DOUBLE GANG
BACK BOX WITH SINGLE GANG PLASTER RING, 3/4"
CONDUIT WITH PULL STRING TO DOOR CONTROLLER
ML
KEY SWITCH; PROVIDE DOUBLE GANG BACK BOX WITH
SINGLE GANG PLASTER RING, 3/4" CONDUIT WITH PULL
STRING TO DOOR CONTROLLER
KS
N NURSE STATION (46" AFF)
NURSE CALL DEVICES
CODE BLUE STATION (46" AFF)
BED NURSE CALL (46" AFF)
TOILET NURSE CALL (46" AFF)
ND
SHOWER NURSE CALL
(WEATHER PROOF) (46" AFF)
DOCTOR DICTATION (46" AFF)
DOCTOR PAGE (46" AFF)
NURSE CALL DUTY STATION (46" AFF)
NURSE CALL MASTER
NURSE CALL DOME LIGHT (CEILING)
C
B
T
S
DI
D
PILLOW SPEAKER/CONTROLP
NURSE CALL DOME ZONE LIGHT (CEILING)Z
CONNECT TO EXISTING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:1
A M
E-001
NOTES AND LEGEND - ELECTRICAL
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
DRAWING INDEX - ELECTRICAL
E-001 NOTES AND LEGEND - ELECTRICAL
ED100 ELECTRICAL DEMOLITION SITE PLAN
ES100 ELECTRICAL RENOVATION OVERALL SITE PLAN
ES100A ELECTRICAL RENOVATION SITE PLAN - AREA A
ES100B ELECTRICAL RENOVATION SITE PLAN - AREA B
EL100 LIGHTING FLOOR PLAN - BASEMENT
EL101A LIGHTING FLOOR PLAN - LEVEL 1 - AREA A
EL101B LIGHTING FLOOR PLAN - LEVEL 1 - AREA B
EL102 LIGHTING FLOOR PLAN - MECHANICAL PENTHOUSE
EP100 ELECTRICAL FLOOR PLAN - BASEMENT
EP101A POWER FLOOR PLAN - LEVEL 1 - AREA A
EP101B POWER FLOOR PLAN - LEVEL 1 - AREA B
EP102 ELECTRICAL FLOOR PLAN - MECHANICAL PENTHOUSE
EY100 SPECIAL SYSTEMS RENOVATION OVERALL SITE PLAN
EY101A SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA A
EY101B SPECIAL SYSTEMS FLOOR PLAN - LEVEL 1 - AREA B
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-503 ELECTRICAL DETAILS
E-601 SINGLE LINE DIAGRAM - ELECTRICAL
E-602 SINGLE LINE DIAGRAM - ELECTRICAL
E-603 SCHEDULES - ELECTRICAL
E-604 SCHEDULES - ELECTRICAL
Revisions: Date:
05/09/2022
UP
UP
SS #11
SS #12
EMH #26
EMH #26A
4 5
EMH #25
EXISTING TRANSFORMER12
TMH #26
TMH #27 TMH #28
EMH #24 TMH #24
A. THE DESIGN INTENT IS TO REMOVE/RELOCATE/RE-ROUTE ALL HIGH
VOLTAGE EQUIPMENT/CONDUCTORS IDENTIFIED TO BE LOCATED
UNDERNEATH THE NEW CLC'S FOOTPRINT. THIS INCLUDES THE
REMOVAL OF THE EXISTING ELECTRICAL MANHOLE EMH #26A AND
13.8 KV, 3-PH UNDERGROUND ELECTRICAL FEEDER FROM EMH #
26A TO THE (2) EXISTING PAD-MOUNTED UTILITY TRANSFORMERS
SERVICING EXISTING BUILDING #6.
B. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT
ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,
ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO
COMMENCING ANY WORK ON THIS SITE.
C. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW
VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION
LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS
PRIOR TO COMMENCING ANY WORK ON THIS SITE.
D. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY
UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING
ON THIS SITE.
E. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH WITH CIVIL
PRIOR TO WORKING ON THIS SITE.
F. CONTRACTOR SHALL FIELD VERIFY ACTUAL SIZES AND QUANTITIES
OF EXISTING CONDUCTORS AND DUCTBANKS. THE DESIGN INTENT
IS TO MATCH SIZES AND QUATNITIES OF EXISTING FOR NEW WORK.
GENERAL NOTES
IT IS THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO
INSPECT ALL OF THE EXISTING ELECTRICAL GEAR INCLUDING BUT NOT
LIMITED TO SECTIONAL SWITCHES, DUCTBANKS, CONDUITS.
MANHOLES THAT ARE SHOWN TO BE REUSED ARE TO BE INSPECTED
TO VERIFY THEY ARE IN CURRENT CODE COMPLIANT AND WORKING
CONDITION. CONTRACTOR SHALL REPORT DISCREPANCIES TO THE VA
PRIOR TO DISTURBING EXISTING INSTALLATION.
FOR ALL EXISTING CABLES OR CONDUCTORS WITHIN DUCT BANKS OR
MANHOLES WITHIN THE SCOPE OF THIS PROJECT SHALL BE VERIFIED
FOR USE AND CONTINUITY. PROVIDE VA COR LIST OF CABLES THAT
ARE ABANDONED, NO LONGER IN USE, OR IN USE AND WHAT THEY
SERVE. ANY CABLES ABANDONED OR NO LONGER IN USE SHALL BE
REMOVED TO ORIGIN.
THERE SHALL BE NO SPLICES OR RE-USE OF CABLES OR
CONDUCTORS WITHIN THE SCOPE OF THIS PROJECT. ALL WIRING
ASSOCIATED WITH THE SCOPE OF THIS PROJECT SHALL BE NEW
UNLESS OTHERWISE NOTED.
SEE CIVIL PLANS FOR COORDINATION EFFORTS AND DETAILS,
F5 ON SHEET CG506.
EXISTING CONDITION NOTES
PHASE 1:
A. CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE
DEMOLITION/RENOVATION PLANS AND IDENTIFY ALL
UNDERGROUND ROUTING OF NEW WORK ENSURING EXISTING
INSTALLATION OF UNDERGROUND UTILITIES ARE NOT DISTURBED.
B. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
EXISTING SECTIONAL SWITCH (SS) #12 TO NEW ELECTRICAL
MANHOLE (EMH) #26A. PREP AREA WHERE FINAL CONNECTION OF
SS #12 IS TO BE MADE. DO NOT MAKE FINAL CONNECTION UNTIL
SHUT DOWN OF SS #12 IS COMPLETED DURING PHASE 4. PROVIDE
PULL CORD AS REQUIRED.
C. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26A TO NEW EMH#26B. PROVIDE PULL CORD AS
REQUIRED.
D. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26B UP TO EXISTING BUILDING 6'S 300KVA PAD
MOUNTED TRANSFORMER. PREP AREA WHERE FINAL CONNECTION
OF BUILDING 6'S TRANSFORMER IS TO BE MADE. DO NOT MAKE
FINAL CONNECTION UNTIL SHUT DOWN OF BUILDING 6'S
TRANSFORMER IS COMPLETED DURING PHASE 4. PROVIDE PULL
CORD AS REQUIRED.
E. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE,
EPB #25 MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. PREP
AREA WHERE FINAL CONNECTION OF EMH #25 IS TO BE MADE. DO
NOT MAKE FINAL CONNECTION UNIT SHUT DOWN OF LOOP C AND D
ARE COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS
REQUIRED.
F. INSTALL NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27
MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. INSTALL NEW
UNDERGROUND 13.8KV DUCTBANK FEEDER ON BOTH SIDES TO
CONNECT TO EXISTING AS REQUIRED.
G. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM
NEW EMH #26 TONEW EPB #27. PROVIDE PULL CORD AS REQUIRED.
H. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM
NEW EMH #26 TO NEW EMH #26A. COORDINATE WITH CIVIL PLANS
AND NEW UNDERGROUND TUNNEL. PROVIDE PULL CORD AS
REQUIRED.
PHASE 2:
A. INSTALL NEW UNDERGROUND DUCTBANK FROM NEW 300KVA PAD
MOUNTED TRANSFORMER TO EXISTING 225KVA PAD MOUNTED
TRANSFORMER PREVIOUSLY SERVICING BUILDING #25. DO NOT
MAKE FINAL CONNECTION UNTIL SHUT DOWN OF SS #11 IS
COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS REQUIRED.
B. INSTALL CONCRETE PAD AND 300KVA TRANSFORMER WITH
INTEGRAL FUSE. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.
ENSURE TRANSFORMER SWITCH/FUSE ARE IN THE "OFF" POSITION
UNTIL NEW CLC IS READY FOR SERVICE.
PHASE 3:
A. CONTRACTOR SHALL PROVIDE AND INSTALL A SEPARATE DIESEL
GENERATOR FOR EACH BUILDING 6 AND 7 AND MAN THE
OPERATIONS. GENERATOR WILL ACT AS NORMAL POWER DURING
PHASE 4. VA'S EMERGENCY GENERATOR SHALL NOT BE USED FOR
NORMAL WORKING ACTIVITIES. HOWEVER, MAY BE USED FOR
CONTRACTOR PROVIDED GENERATOR INSPECTION PURPOSES
ONLY. PROVIDE SUPERVISION, FUEL AND REQUIRED RECORD
DOCUMENTATION DURING RUNTIME AND TESTING.
1) BUILDING 6'S TEMPORARY GENERATOR SHALL BE SIZED
FOR A MINIMUM OF 400KVA OR 1000A WITH AT LEAST 96
HOURS OF FUEL TIME.
2) BUILDING 7'S TEMPORARY GENERATOR SHALL BE SIZED
FOR A MINIMUM OF 720KVA OR 2000A WITH AT LEAST 96 HOURS
OF FUEL TIME.
B. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN
BUILDING 6 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT
MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED
DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.
C. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN
BUILDING 7 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT
MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED
DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.
PHASE 4:
A. COORDINATE ELECTRICAL SERVICE SHUT DOWN OF LOOP C AND D
WITH THE VA COR. CONTRACTOR SHALL PROVIDE A PLAN IN
WRITTEN FORM FOR APPROVAL FROM THE COR. CONTRACTOR
SHALL COORDINATE AT LEAST THREE (3) MONTHS PRIOR WITH THE
VA COR FOR ACTUAL SHUT DOWN; ONLY (1) ONE SHUT DOWN WILL
BE ACCEPTABLE. CONTRACTOR SHALL ENSURE SUFFICIENT
STAFFS (A MINIMUM OF A TWO-MAN CREW AT EACH AFFECTED
MANHOLE) SHALL BE PROVIDED ON SITE TO MINIMIZE SHUT DOWN
DURATION. COMPLETION OF WORK DURING SHUT DOWN SHALL BE
DONE OVER ONE WEEKEND AND MUST NOT EXCEED TWO DAYS.
B. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL
SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING
BUILDING 6 AND MAKE CONNECTION FROM TEMPORARY
GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START
UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.
C. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL
SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING
BUILDING 7 AND MAKE CONNECTION FROM TEMPORARY
GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START
UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.
D. SEVER LOOP C AND D AT EXISTING EMH #26A. PULL BACK 13.8KV
FEEDERS FROM EXISTING EMH #26A TO EXISTING EMH #27. ON THE
OTHER SIDE, PULL BACK 13.8KV FEEDERS FROM EMH #26A TO
EXISTING EMH #25. DEMOLISH ASSOCIATED DUCTBANK AS
REQUIRED.
E. DISCONNECT CONNECTION OF UNDERGROUND 13.8KV FEEDER
FROM SS #12 AND BUILDING 6'S TRANSFORMER. DEMOLISH
ASSOCIATED DUCTBANK AS REQUIRED.
F. REMOVE EXISTING 225KVA PAD MOUNTED TRANSFORMER
PREVIOUSLY SERVICING DEMOLISHED BUILDING #25. REMOVE
EXISTING CONDUCTORS FROM EXISTING 225KVA PAD MOUNTED
TRANSFORMER TO EXISTING EXISTING SS #11 VIA EXISTING
ELECTRICAL MANHOLE #28. ENSURE EXISTING CONCRETE
ENCASED DUCTBANK IS PROTECTED TO BE REUSED. EXTEND
EXISTING DUCTBANK TO NEW DUCTBANK AS SHOWN ON ES100.
PULL NEW CONDUCTORS AS REQUIRED FROM EXISTING SS #11 TO
NEW CLC'S TRANSFORMER LOCATION.
G. BORE EXISTING ELECTRICAL MANHOLES #27 AND #25 AS SHOWN
ON SHEET ES100.
H. MAKE FINAL CONNECTION AND PULL NEW CONDUCTORS AT THE
FOLLOWING LOCATION:
1) EXISTING EMH #27 TO NEW EPB #27.
2) NEW EPB #27 TO NEW EMH #26.
3) NEW EMH #26 TO NEW EMH #26A.
4) NEW EMH #26A TO NEW EPB #25
5) NEW EPB #25 TO EXISTING EMH #25.
6) EXISTING SS #12 TO NEW EMH #26A.
7) NEW EMH #26A TO NEW EMH #26B.
8) NEW EMH #26B TO EXISTING BUILDING 6'S 300KVA
TRANSFORMER.
9) EXISTING SS #11 TO NEW 300KVA PAD MOUNTED
TRANSFORMER. ENSURE TRANSFORMER FUSE IS IN THE OFF
POSITION UNTIL NEW CLC IS READY FOR SERVICE.
SEQUENCE OF OPERATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:3
A M
ED100
ELECTRICAL DEMOLITION SITE PLAN
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1" = 30'-0"
ELECTRICAL DEMOLITION SITE PLAN
KEYNOTES
1 EXISTING UNDERGROUND ELECTRIC 13.8 KV, 3-PH CONDUCTORS TO
REMAIN.
2 EXISTING ELECTRICAL MANHOLE TO REMAIN.
3 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING
ELECTRICAL MANHOLE #26A TOWARDS EXISTING EMH #27 VIA EMH
#26. CONNECT EXISTING CONDUCTORS TO NEW CONDUCTORS FOR
C AND D LOOPS ON A TERMINAL BLOCK WITH LOAD BLOCK ELBOWS
ON BOTH SIDES IN NEW NEMA 4X ENCLOSURE ON CONCRETE PAD
EPB #27. SEE ES100 FOR ADDITIONAL INFORMATION. DEMOLISH
EXISTING DUCTBANK FROM EMH #26A TO EXISTING EMH #27.
4 SEVER ALL C AND D LOOP CONDUCTORS IN EXISTING ELECTRICAL
MANHOLE #26A AND PULL BACK TO EXISTING ELECTRICAL MANHOLE
#27 ON ONE SIDE AND TO EXISTING ELECTRICAL MANHOLE #25 ON
OTHER SIDE. LEAVE ENOUGH SLACK TO COME INTO NEW ABOVE
GRADE NEMA 4X ENCLOSURE AND CONNECT TO TERMINAL BLOCK.
5 REMOVE EXISTING ELECTRICAL MANHOLE EMH #26A.
6 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING
ELECTRICAL MANHOLE EMH #26A TO SS #12. DISCONNECT AND
REMOVE CONDUCTORS.
7 PULL BACK EXISTING UNDERGROUND ELECTRIC 13.8 KV, 3-PH
CONDUCTORS FROM EXISTING ELECTRICAL MANHOLE EMH #26A TO
EXISTING PAD-MOUNTED UTILITY TRANSFORMER #1 SERVICING
BUILDING #6. DISCONNECT AND REMOVE CONDUCTORS.
8 APPROXIMATE LOCATION OF EXISTING PAD-MOUNTED UTILITY
TRANSFORMER #1 SERVICING BUILDING #6.
9 PULL BACK SEVERED C AND D LOOP CONDUCTORS FROM EXISTING
ELECTRICAL MANHOLE #26A TOWARDS MANHOLE #25 TO THE
PROPOSED NEW NEMA 4X ENCLOSURE AT THIS LOCATION.
CONNECT EXISTING CONDUCTORS TO NEW CONDUCTORS FOR C
AND D LOOPS ON A TERMINAL BLOCK WITH LOAD BLOCK ELBOWS
ON BOTH SIDES IN NEW NEMA 4X ENCLOSURE ON CONCRETE PAD.
10 EXISTING SECTIONAL SWITCH, SS#12 TO REMAIN.
11 EXISTING SECTIONAL SWITCH, SS#11 TO REMAIN.
12 EXISTING 225KVA PAD MOUNTED TRANSFORMER PREVIOUSLY
SERVICING DEMOLISHED BUILDING #25 TO BE REMOVED.
13 EXISTING UNDERGROUND DUCTBANK FEEDER TO REMAIN AND
REUSED DURING NEW WORK AS DIRECTED BY OWNER.
CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE FILL CAPACITY
AND THE EXISTING DUCTBANK/CONDUITS ARE IN CURRENT CODE
COMPLIANT CONDITION FOR REUSE. PROTECT DURING DEMOLITION
AND REMOVE ASSOCIATED CONDUCTORS.
14 EXISTING TELECOMMUNICATION MANHOLE TO REMAIN.
15 EXISTING UNDERGROUND TELECOMMUNICATION CABLES IN
DUCTBANKS TO REMAIN.
16 EXISTING CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH
13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N. DISCONNECT AND REMOVE
CONDUCTORS AND DEMOLISH EXISTING DUCTBANK.
17 EXISTING CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 -
30#16 RHL. 1 - 24#16 RHL AND 2-3/C #16 RHL. 1 2#12 RHL. 1 -
TELEPHONE. 1 - SPARE. DISCONNECT AND REMOVE CONDUCTORS
AND DEMOLISH EXISTING DUCTBANK.
18 SEVER ALL TELECOMMUNICATION CABLES AT THIS LOCATION AND
PULL BACK TO EXISTING TELECOMMUNICATION MANHOLE, TMH #27
ON ONE SIDE AND TO NEW TELECOMMUNICATION PULL BOX, TPB
#25. LEAVE ENOUGH SLACK TO COME INTO NEW ABOVE GRADE
NEMA 4X ENCLOSURE AND CONNECT TO TERMINAL BLOCK.
DEMOLISH ASSOCIATED DUCTBANK AS REQUIRED. SEE
RENOVATION PLANS FOR LOCATION OF NEW TPB #25.
19 REMOVE EXISTING FEEDER CONDUCTORS AND RE-USE DUCT BANK
BETWEEN SS#11 AND EXISTING TRANSFORMER. RUN NEW FEEDER
CONDUCTORS FROM SS#11 TO NEW CLC BUILDING.
20 EXISTING CONCRETE ENCASED DUCTBANKS - (2) 3" ONE CONDUIT
WITH 13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N AND ONE SPARE
CONDUIT. DISCONNECT AND REMOVE CONDUCTORS AND DEMOLISH
EXISTING DUCTBANK. SEE CIVIL PLAN CD101 FOR LOCATIONS OF
EXISTING CONCRETE DUCTBANK TO BE REMOVED AT NEW UTILITY
CROSSINGS.
21 EXISTING MANHOLES EMH#26 AND TMH#26 TO BE REMOVED.
22 CUTOFF POINT 3LF EAST OF EXISTING SS #12.
23 CUTOFF POINT 3LF WEST OF EXISTING TRANSFORMER #1.
24 CUTOFF POINT 3LF SOUTH OF EXISTING EMH #25.
25 REMOVE EXISTING CONCRETE ENCASED DUCTBANK FROM TMH #27
TO CUTOFF POINT 3LF SOUTH OF EMH #25.
26 EXISTING CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH
13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N. DISCONNECT AND REMOVE
CONDUCTORS AND DEMOLISH EXISTING DUCTBANK. SEE CIVIL PLAN
CD101 FOR LOCATIONS OF EXISTING CONCRETE DUCTBANK TO BE
REMOVED AT NEW UTILITY CROSSINGS.
1/16" = 1'-0"
OVERALL CAMPUS KEYPLAN
EMH #27
EMH #28
Revisions: Date:
J
J
S
J
J
SS #12
SS #11
EPB #27
EMH #26A
EMH #26B
EPB #25
EMH #25
R
R
R
R
R
2"ø
2"ø
2"ø
2"ø
2"ø
2"ø
2"ø
2"ø
R
R
R
C2-30
C2-30
C2-30
C2-40
C2-40
C2-40
C2-40
C2-40
EMH #27
EMH #28
BUILDING 6NEW CLCES100A
ES100B
DP - 8
EQ1-38
EQ1-40
EQ1-39,41
DP-10
DP-12
DP - 14
DP - 16
V
V
V V
V
V
V
V
V
V
VVV
V
V
V
V
U
U
U
U
U
W W
W
W
W
W W W
W
W
W
W
W
W
W
W
NL - 29
NL - 31
NL - 33
TMH #28
TMH #27
EMH #24 TMH #24
TPB #27
TPB #25
EMH #26
TMH #26
TMH #25 34
A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT
ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION, ROUTING OF
CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO COMMENCING ANY
WORK ON THIS SITE.
B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW VOLTAGE
SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION LOCATION,
ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO
COMMENCING ANY WORK ON THIS SITE.
C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY
UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING ON
THIS SITE.
D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH STRUCTURAL
ENGINEER FOR CONDUIT OPENING IN STRUCTURAL SUPPORT.
E. REFER TO SINGLE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
F. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE RATED
NEMA 3R.
G. SITE AND LANDSCAPE LIGHTING SHALL BE CONTROLLED VIA PHOTOCELL-
ON AND TIMECLOCK-OFF. FIXTURES SHALL BE PROVIDED WITH INTEGRAL
PHOTOCELL.
GENERAL NOTES
PHASE 1:
A. CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE
DEMOLITION/RENOVATION PLANS AND IDENTIFY ALL
UNDERGROUND ROUTING OF NEW WORK ENSURING EXISTING
INSTALLATION OF UNDERGROUND UTILITIES ARE NOT DISTURBED.
B. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
EXISTING SECTIONAL SWITCH (SS) #12 TO NEW ELECTRICAL
MANHOLE (EMH) #26A. PREP AREA WHERE FINAL CONNECTION OF
SS #12 IS TO BE MADE. DO NOT MAKE FINAL CONNECTION UNTIL
SHUT DOWN OF SS #12 IS COMPLETED DURING PHASE 4. PROVIDE
PULL CORD AS REQUIRED.
C. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26A TO NEW EMH#26B. PROVIDE PULL CORD AS
REQUIRED.
D. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26B UP TO EXISTING BUILDING 6'S 300KVA PAD
MOUNTED TRANSFORMER. PREP AREA WHERE FINAL CONNECTION
OF BUILDING 6'S TRANSFORMER IS TO BE MADE. DO NOT MAKE
FINAL CONNECTION UNTIL SHUT DOWN OF BUILDING 6'S
TRANSFORMER IS COMPLETED DURING PHASE 4. PROVIDE PULL
CORD AS REQUIRED.
E. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDERS FROM
NEW EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE,
EPB #25 MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. PREP
AREA WHERE FINAL CONNECTION OF EMH #25 IS TO BE MADE. DO
NOT MAKE FINAL CONNECTION UNIT SHUT DOWN OF LOOP C AND D
ARE COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS
REQUIRED.
F. INSTALL NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27
MOUNTED ON CONCRETE PAD AS SHOWN ON ES100. INSTALL NEW
UNDERGROUND 13.8KV DUCTBANK FEEDER ON BOTH SIDES TO
CONNECT TO EXISTING AS REQUIRED.
G. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM
NEW EMH #26 TONEW EPB #27. PROVIDE PULL CORD AS REQUIRED.
H. INSTALL NEW UNDERGROUND 13.8KV DUCTBANK FEEDER FROM
NEW EMH #26 TO NEW EMH #26A. COORDINATE WITH CIVIL PLANS
AND NEW UNDERGROUND TUNNEL. PROVIDE PULL CORD AS
REQUIRED.
PHASE 2:
A. INSTALL NEW UNDERGROUND DUCTBANK FROM NEW 300KVA PAD
MOUNTED TRANSFORMER TO EXISTING 225KVA PAD MOUNTED
TRANSFORMER PREVIOUSLY SERVICING BUILDING #25. DO NOT
MAKE FINAL CONNECTION UNTIL SHUT DOWN OF SS #11 IS
COMPLETED DURING PHASE 4. PROVIDE PULL CORD AS REQUIRED.
B. INSTALL CONCRETE PAD AND 300KVA TRANSFORMER WITH
INTEGRAL FUSE. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.
ENSURE TRANSFORMER SWITCH/FUSE ARE IN THE "OFF" POSITION
UNTIL NEW CLC IS READY FOR SERVICE.
PHASE 3:
A. CONTRACTOR SHALL PROVIDE AND INSTALL A SEPARATE DIESEL
GENERATOR FOR EACH BUILDING 6 AND 7 AND MAN THE
OPERATIONS. GENERATOR WILL ACT AS NORMAL POWER DURING
PHASE 4. VA'S EMERGENCY GENERATOR SHALL NOT BE USED FOR
NORMAL WORKING ACTIVITIES. HOWEVER, MAY BE USED FOR
CONTRACTOR PROVIDED GENERATOR INSPECTION PURPOSES
ONLY. PROVIDE SUPERVISION, FUEL AND REQUIRED RECORD
DOCUMENTATION DURING RUNTIME AND TESTING.
1) BUILDING 6'S TEMPORARY GENERATOR SHALL BE SIZED
FOR A MINIMUM OF 400KVA OR 1000A WITH AT LEAST 96
HOURS OF FUEL TIME.
2) BUILDING 7'S TEMPORARY GENERATOR SHALL BE SIZED
FOR A MINIMUM OF 720KVA OR 2000A WITH AT LEAST 96 HOURS
OF FUEL TIME.
B. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN
BUILDING 6 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT
MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED
DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.
C. PREP AREA WHERE TEMPORARY CONNECTION WILL BE MADE IN
BUILDING 7 UP TO THE SERVICE ENTRANCE EQUIPMENT. DO NOT
MAKE CONNECTION UNTIL SHUT DOWN OF SS #12 IS COMPLETED
DURING PHASE 4. PROVIDE PULL STRINGS AS REQUIRED.
PHASE 4:
A. COORDINATE ELECTRICAL SERVICE SHUT DOWN OF LOOP C AND D
WITH THE VA COR. CONTRACTOR SHALL PROVIDE A PLAN IN
WRITTEN FORM FOR APPROVAL FROM THE COR. CONTRACTOR
SHALL COORDINATE AT LEAST THREE (3) MONTHS PRIOR WITH THE
VA COR FOR ACTUAL SHUT DOWN; ONLY (1) ONE SHUT DOWN WILL
BE ACCEPTABLE. CONTRACTOR SHALL ENSURE SUFFICIENT
STAFFS (A MINIMUM OF A TWO-MAN CREW AT EACH AFFECTED
MANHOLE) SHALL BE PROVIDED ON SITE TO MINIMIZE SHUT DOWN
DURATION. COMPLETION OF WORK DURING SHUT DOWN SHALL BE
DONE OVER ONE WEEKEND AND MUST NOT EXCEED TWO DAYS.
B. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL
SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING
BUILDING 6 AND MAKE CONNECTION FROM TEMPORARY
GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START
UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.
C. CONTRACTOR SHALL TEMPORARILY DISCONNECT NORMAL
SERVICE IN EXISTING SERVICE ENTRANCE EQUIPMENT SERVICING
BUILDING 7 AND MAKE CONNECTION FROM TEMPORARY
GENERATOR TO EXISTING SERVICE ENTRANCE EQUIPMENT. START
UP GENERATOR, ENSURE BUILDING IS FULLY FUNCTIONING.
D. SEVER LOOP C AND D AT EXISTING EMH #26A. PULL BACK 13.8KV
FEEDERS FROM EXISTING EMH #26A TO EXISTING EMH #27. ON THE
OTHER SIDE, PULL BACK 13.8KV FEEDERS FROM EMH #26A TO
EXISTING EMH #25. DEMOLISH ASSOCIATED DUCTBANK AS
REQUIRED.
E. DISCONNECT CONNECTION OF UNDERGROUND 13.8KV FEEDER
FROM SS #12 AND BUILDING 6'S TRANSFORMER. DEMOLISH
ASSOCIATED DUCTBANK AS REQUIRED.
F. REMOVE EXISTING 225KVA PAD MOUNTED TRANSFORMER
PREVIOUSLY SERVICING DEMOLISHED BUILDING #25. REMOVE
EXISTING CONDUCTORS FROM EXISTING 225KVA PAD MOUNTED
TRANSFORMER TO EXISTING EXISTING SS #11 VIA EXISTING
ELECTRICAL MANHOLE #28. ENSURE EXISTING CONCRETE
ENCASED DUCTBANK IS PROTECTED TO BE REUSED. EXTEND
EXISTING DUCTBANK TO NEW DUCTBANK AS SHOWN ON ES100.
PULL NEW CONDUCTORS AS REQUIRED FROM EXISTING SS #11 TO
NEW CLC'S TRANSFORMER LOCATION.
G. BORE EXISTING ELECTRICAL MANHOLES #27 AND #25 AS SHOWN
ON SHEET ES100.
H. MAKE FINAL CONNECTION AND PULL NEW CONDUCTORS AT THE
FOLLOWING LOCATION:
1) EXISTING EMH #27 TO NEW EPB #27.
2) NEW EPB #27 TO NEW EMH #26.
3) NEW EMH #26 TO NEW EMH #26A.
4) NEW EMH #26A TO NEW EPB #25
5) NEW EPB #25 TO EXISTING EMH #25.
6) EXISTING SS #12 TO NEW EMH #26A.
7) NEW EMH #26A TO NEW EMH #26B.
8) NEW EMH #26B TO EXISTING BUILDING 6'S 300KVA
TRANSFORMER.
9) EXISTING SS #11 TO NEW 300KVA PAD MOUNTED
TRANSFORMER. ENSURE TRANSFORMER FUSE IS IN THE OFF
POSITION UNTIL NEW CLC IS READY FOR SERVICE.
SEQUENCE OF OPERATIONS
N
KEY PLAN
AREA B
(EAST)
AREA A
(WEST)
LEVEL 2
PENTHOUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:2
A M
ES100
ELECTRICAL RENOVATION OVERALL SITE PLAN
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1" = 30'-0"
ELECTRICAL RENOVATION SITE PLAN
KEYNOTES
1 PROVIDE NEW UNDERGROUND CONCRETE ENCASED DUCTBANK SERVICE FEEDER FROM
NEW PAD MOUNTED TRANSFORMER UP TO EXISTING DUCTBANK. PROVIDE NEW 13.8 KV,
3-PHASE CONDUCTORS FROM EXISTING SECTIONAL SWITCH SS#11 THROUGH EXISTING
ELECTRICAL MANHOLE #28 TO NEW PAD MOUNTED TRANSFORMER. COORDINATE ALL
REQUIREMENTS WITH VA. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.
2 APPROXIMATE LOCATION OF 208/120V-3PH, PAD-MOUNTED TRANSFORMER. COORDINATE
FINAL LOCATION WITH VA.
3 UNDERGROUND 208/120V-3PH DIRECT BURIAL SECONDARY ELECTRIC SERVICE
CONDUCTORS TO MAIN DISTRIBUTION PANEL, MDP. COORDINATE STUB-UP REQUIREMENTS
IN SECONDARY COMPARTMENT OF TRANSFORMER WITH VA.
4 APPROXIMATE LOCATION OF NORMAL POWER ELECTRICAL ROOM. SEE FLOOR PLANS FOR
ADDITIONAL INFORMATION.
5 36" UNDERGROUND DIRECT BURIAL EMERGENCY ELECTRIC SERVICE FEEDER FROM
GENERATOR TO EMERGENCY ENCLOSED CIRCUIT BREAKERS. SEE FLOOR PLANS AND
SINGLE LINE DIAGRAM FOR ADDITIONAL INFORMATION.
6 APPROXIMATE LOCATION OF IT CLOSET. SEE FLOOR PLANS FOR ADDITIONAL INFORMATION.
7 APPROXIMATE LOCATION OF TELEPHONE TERMINAL BACKBOARD. SEE FLOOR PLANS FOR
ADDITIONAL INFORMATION.
8 PROVIDE (2) 1" CONDUITS UNDERGROUND WITH PULL STRINGS FROM GENERATOR
CONTROLS TO IT ROOM. MAA AT THE BOILER PLANT SHALL MONITOR GENERATOR.
9 PROVIDE (2) 4" CONDUITS WITH PULL STRINGS BURIED 30" B.F.G. TO EXISTING EMH #24 FOR
TELEPHONE AND DATA SERVICES; CAP AND MARK FOR INSTALLATION FOR COMMUNICATION
SERVICES. ELECTRICAL CONTRACTOR SHALL COORDINATE ALL TELEPHONE REQUIREMENTS
AND TERMINATION POINT WITH SERVICE PROVIDER/VA. SEE SHEET EY100 FOR ADDITIONAL
INFORMATION.
10 90" X 72" X 24" (HxWxD) NEW FREESTANDING NEMA 4X ENCLOSURE WITH LOAD BREAK
ELBOWS ON BOTH SIDES OF THE TERMINAL BLOCKS MOUNTED ON CONCRETE PAD FOR 13.8
KV, 3-PH POWER FEED CONNECTIONS. TERMINATE BACK TO EXISTING ELECTRICAL C AND D
LOOPS. BASIS OF DESIGN IS HUBBELL WRD907224SSFSDN4.
11 NEW ELECTRICAL MANHOLE.
12 NEW UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM NEW FREESTANDING
NEMA 4X ENCLOSURE, ELECTRICAL PULL BOX EPB #27 TO NEW ELECTRICAL MANHOLE EMH
#26A VIA NEW ELECTRICAL MANHOLE EMH #26.
13 NEW UNDERGROUND 13.8 KV, 3-PH CONDUCTORS FROM NEW ELECTRICAL MANHOLE EMH
#26A TO NEW ELECTRICAL MANHOLE EMH #26B.
14 NEW UNDERGROUND 13.8 KV, 3-PH UTILITY SERVICE FEEDER TO EXISTING UTILTY
TRANSFORMER #1 SERVICING EXISTING BUILDING #6.
15 APPROXIMATE LOCATION OF EXISTING PAD-MOUNTED UTILITY TRANSFORMER #1 SERVICING
BUILDING #6.
16 NEW UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM NEW ELECTRICAL
MANHOLE EMH #26A TO NEW FREESTANDING NEMA 4X ENCLOSURE, ELECTRICAL PULL BOX
EPB #25.
17 WP JUNCTION BOX FOR GENERATOR CONTROL PANEL.
18 WP JUNCTION BOX FOR JACKET WATER HEATER.
19 WP JUNCTION BOX FOR BATTERY CHARGER.
20 APPROXIMATE LOCATION OF EMERGENCY STAND-BY GENERATOR. SEE SINGLE LINE
DIAGRAM, DETAILS H ON SHEET E501 AND CG503 FOR ADDITIONAL INFORMATION.
21 ABOVE GROUND 1000 GALLON DIESEL FUEL TANK WITH TANK SUPPORTS "FEET".
CONTRACTOR SHALL ENSURE BOTTOM OF TANK TO BE 1" OFF OF CONCRETE CURB/PAD
THAT IT SITS ON. SEE DETAIL 'H' ON SHEET E501 AND F1/CG503 FOR ADDITIONAL
INFORMATION.
22 ENCLOSURE AROUND GENERATOR. SEE CIVIL PLANS FOR ADDITIONAL INFORMATION.
23 WP DUPLEX FOR IRRIGATION CONTROLLER MOUNTED ON PEDESTAL. SEE LANDSCAPE
PLANS FOR ADDITIONAL INFORMATION.
24 WP JUNCTION BOX FOR MONUMENT SIGN. TIE CONTROLS TO TIME CLOCK-LCP. COORDINATE
ON/OFF REQUIREMENTS WITH COR.
25 NEW C AND D LOOP CONDUCTORS FROM EXISTING SS #12 TO NEW ELECTRICAL MANHOLE
#26A.
26 EXISTING UNDERGROUND DUCTBANK WITH NEW FEEDER.
27 BORE EXISTING ELECTRICAL MANHOLE #25 FOR NEW UNDERGROUND 13.8 KV, 3-PH C AND D
LOOP CONDUCTORS FROM NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #25. AT
EXISTING MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS REQUIRED
AND PRESERVE THE STEEL IN THE STRUCTURAL WALL. CUT STEEL AND EXTEND INTO THE
DUCT BANK ENVELOPE. CHIP THE PERIMETER SURFACE OF THE DUCT BANK OPENING TO
FORM A KEY OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR ADDITIONAL
INFORMATION.
28 PULL NEW TELECOMMUNICATION CABLES IN NEW CONCRETE ENCASED DUCTBANK.
29 NEW CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH 13.8KV, 3/C 2/0 PRIMARY AND
1#1 B/N AND TWO SPARE CONDUITS.
30 NEW CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 - 30#16 RHL. 1 - 24#16 RHL AND
2-3/C #16 RHL. 1 2#12 RHL. 1 - TELEPHONE. 1 - SPARE.
31 NEW FREESTANDING NEMA 4X ENCLOSURE MOUNTED ON CONCRETE PAD FOR
TELECOMMUNICATION CABLES FEED CONNECTIONS. TERMINATE BACK TO EXISTING
TELEPHONE CABLES.
32 REFER TO SPEC 26 05 41 SECTION 3.3.E FOR DIRECTION ON CONNECTING NEW DUCT TO
EXISTING.
33 BORE EXISTING ELECTRICAL MANHOLE #27 FOR NEW UNDERGROUND 13.8 KV, 3-PH C AND D
LOOP CONDUCTORS FROM NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27. AT
EXISTING MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS REQUIRED
AND PRESERVE THE STEEL IN THE STRUCTURAL WALL. CUT STEEL AND EXTEND INTO THE
DUCT BANK ENVELOPE. CHIP THE PERIMETER SURFACE OF THE DUCT BANK OPENING TO
FORM A KEY OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR ADDITIONAL
INFORMATION. REMOVE AND CONSTRUCT NEW MANHOLE #27.
34 NEW TELECOMMUNICATION MANHOLE.
35 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK. SEE DETAIL F5-CG506.
36 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF WEST OF TRANSFORMER #1.
SEE DETAIL F5-CG506.
37 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF EAST OF SS #12. SEE DETAIL
F5-CG506.
38 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK 3 LF SOUTH EMH #25. SEE DETAIL
F5-CG506.
Revisions: Date:
J
S
SS #11
2"ø
2"ø
R
R
R
ES100A
ES100B
C2-30
C2-30
2"øC2-30
NEW CLC
BUILDING 6
DP - 8
EQ1-38
EQ1-39,41
EQ1-40
EMH #28
NL - 29
V
V
V V
V
V
V
U
EMH #27 TMH #27
EPB #2718 TPB #27 19
EMH #26 TMH #2621 22
25 26
A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT
ENGINEER AT THE SITE TO VERIFY TERMINATION LOCATION,
ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS PRIOR TO
COMMENCING ANY WORK ON THIS SITE.
B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW
VOLTAGE SYSTEM PROVIDER AT THE SITE TO VERIFY TERMINATION
LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS
PRIOR TO COMMENCING ANY WORK ON THIS SITE.
C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY
UNDERGROUND LOCATING SERVICE COMPANY PRIOR TO DIGGING
ON THIS SITE.
D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH
STRUCTURAL ENGINEER FOR CONDUIT OPENING IN STRUCTURAL
SUPPORT.
E. REFER TO SINGLE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.
F. ALL EXTERIOR ELECTRICAL DEVICES AND ENCLOSURE SHALL BE
RATED NEMA 3R.
G. SITE AND LANDSCAPE LIGHTING SHALL BE CONTROLLED VIA
PHOTOCELL-ON AND TIMECLOCK-OFF. FIXTURES SHALL BE
PROVIDED WITH INTEGRAL PHOTOCELL.
H. SEE SHEET ES100 ELECTRICAL RENOVATION OVERALL SITE PLAN
FOR ADDITIONAL INFORMATION.
GENERAL NOTES
N
KEY PLAN
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:0
:2
A M
ES100A
ELECTRICAL RENOVATION SITE PLAN - AREA A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
05/09/2022 DK SC
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/16" = 1'-0"
ELECTRICAL RENOVATION SITE PLAN - AREA A
KEYNOTES
1 APPROXIMATE LOCATION OF TELEPHONE TERMINAL BACKBOARD.
SEE FLOOR PLANS FOR ADDITIONAL INFORMATION.
2 PROVIDE NEW UNDERGROUND CONCRETE ENCASED DUCTBANK
SERVICE FEEDER FROM NEW PAD MOUNTED TRANSFORMER UP TO
EXISTING DUCTBANK. PROVIDE NEW 13.8 KV, 3-PHASE
CONDUCTORS FROM EXISTING SECTIONAL SWITCH SS#11 THROUGH
EXISTING ELECTRICAL MANHOLE #28 TO NEW PAD MOUNTED
TRANSFORMER. COORDINATE ALL REQUIREMENTS WITH VA. SEE
CIVIL PLANS FOR ADDITIONAL INFORMATION.
3 APPROXIMATE LOCATION OF 208/120V-3PH, PAD-MOUNTED
TRANSFORMER. COORDINATE FINAL LOCATION WITH VA.
4 UNDERGROUND 208/120V-3PH DIRECT BURIAL SECONDARY
ELECTRIC SERVICE CONDUCTORS TO MAIN DISTRIBUTION PANEL,
MDP. COORDINATE STUB-UP REQUIREMENTS IN SECONDARY
COMPARTMENT OF TRANSFORMER WITH VA.
5 APPROXIMATE LOCATION OF IT CLOSET. SEE FLOOR PLANS FOR
ADDITIONAL INFORMATION.
6 PROVIDE (2) 4" CONDUITS WITH PULL STRINGS BURIED 30" B.F.G. TO
EXISTING EMH #24 FOR TELEPHONE AND DATA SERVICES; CAP AND
MARK FOR INSTALLATION FOR COMMUNICATION SERVICES.
ELECTRICAL CONTRACTOR SHALL COORDINATE ALL TELEPHONE
REQUIREMENTS AND TERMINATION POINT WITH SERVICE
PROVIDER/VA. SEE SHEET EY100 FOR ADDITIONAL INFORMATION.
7 WP JUNCTION BOX FOR GENERATOR CONTROL PANEL.
8 WP JUNCTION BOX FOR BATTERY CHARGER.
9 WP JUNCTION BOX FOR JACKET WATER HEATER.
10 36" UNDERGROUND DIRECT BURIAL EMERGENCY ELECTRIC
SERVICE FEEDER FROM GENERATOR TO EMERGENCY ENCLOSED
CIRCUIT BREAKERS. SEE FLOOR PLANS AND SINGLE LINE DIAGRAM
FOR ADDITIONAL INFORMATION.
11 PROVIDE (2) 1" CONDUITS UNDERGROUND WITH PULL STRINGS
FROM GENERATOR CONTROLS TO IT ROOM. MAA AT THE BOILER
PLANT SHALL MONITOR GENERATOR.
12 APPROXIMATE LOCATION OF EMERGENCY STAND-BY GENERATOR.
SEE SINGLE LINE DIAGRAM, DETAILS H ON SHEET E501 AND CG503
FOR ADDITIONAL INFORMATION.
13 ABOVE GROUND 1000 GALLON DIESEL FUEL TANK WITH TANK
SUPPORTS "FEET". CONTRACTOR SHALL ENSURE BOTTOM OF TANK
TO BE 1" OFF OF CONCRETE CURB/PAD THAT IT SITS ON. SEE
DETAIL 'H' ON SHEET E501 AND F1/CG503 FOR ADDITIONAL
INFORMATION.
14 ENCLOSURE AROUND GENERATOR. SEE CIVIL PLANS FOR
ADDITIONAL INFORMATION.
15 WP DUPLEX FOR IRRIGATION CONTROLLER MOUNTED ON
PEDESTAL. SEE LANDSCAPE PLANS FOR ADDITIONAL INFORMATION.
16 EXISTING UNDERGROUND DUCTBANK WITH NEW FEEDER.
17 NEW CONCRETE ENCASED DUCTBANKS - (4) 3" CONDUITS WITH
13.8KV, 3/C 2/0 PRIMARY AND 1#1 B/N AND TWO SPARE CONDUITS.
18 90" X 72" X 24" (HxWxD) NEW FREESTANDING NEMA 4X ENCLOSURE
WITH LOAD BREAK ELBOWS ON BOTH SIDES OF THE TERMINAL
BLOCKS MOUNTED ON CONCRETE PAD FOR 13.8 KV, 3-PH POWER
FEED CONNECTIONS. TERMINATE BACK TO EXISTING ELECTRICAL C
AND D LOOPS. BASIS OF DESIGN IS HUBBELL WRD907224SSFSDN4.
19 NEW FREESTANDING NEMA 4X ENCLOSURE MOUNTED ON
CONCRETE PAD FOR TELECOMMUNICATION CABLES FEED
CONNECTIONS. TERMINATE BACK TO EXISTING TELEPHONE
CABLES.
20 BORE EXISTING ELECTRICAL MANHOLE #27 FOR NEW
UNDERGROUND 13.8 KV, 3-PH C AND D LOOP CONDUCTORS FROM
NEW FREESTANDING NEMA 4X ENCLOSURE, EPB #27. AT EXISTING
MANHOLE, BREAK THE STRUCTURE WALL OUT TO THE DIMENSIONS
REQUIRED AND PRESERVE THE STEEL IN THE STRUCTURAL WALL.
CUT STEEL AND EXTEND INTO THE DUCT BANK ENVELOPE. CHIP THE
PERIMETER SURFACE OF THE DUCT BANK OPENING TO FORM A KEY
OR FLARED SURFACE. REFER TO SPECS AND CIVIL PLANS FOR
ADDITIONAL INFORMATION. REMOVE AND CONSTRUCT NEW
MANHOLE #27.
21 NEW ELECTRICAL MANHOLE.
22 NEW TELECOMMUNICATION MANHOLE.
23 REFER TO SPEC 26 05 41 SECTION 3.3.E FOR DIRECTION ON
CONNECTING NEW DUCT TO EXISTING.
24 MAKE CONNECTION TO EXISTING CONCRETE DUCTBANK. SEE
DETAIL F5-CG506.
25 PULL NEW TELECOMMUNICATION CABLES IN NEW CONCRETE
ENCASED DUCTBANK.
26 NEW CONCRETE ENCASED DUCTBANKS - (5) 3" CONDUITS. 1 - 30#16
RHL. 1 - 24#16 RHL AND 2-3/C #16 RHL. 1 2#12 RHL. 1 - TELEPHONE. 1 -
SPARE.
Revisions: Date:
SS #12
EMH #26A
EMH #26B
EPB #25
EMH #25
R
R
R
R
R
2"ø
2"ø
2"ø
2"ø
2"ø
ES100A
ES100B
C2-40
C2-40
C2-40
C2-40
C2-40
DP - 16
DP - 14
NL - 33
NL - 31
V
W
W
V
U
U
U
V
W
W
V
VV
U
V
W
V
V
V
W
W W
W
W
W
W
W W
W
W
TPB #25 19
TMH #25 22
A. ELECTRICAL CONTRACTOR SHALL MEET WITH THE VA PROJECT ENGINEER AT THE SITE TO
VERIFY TERMINATION LOCATION, ROUTING OF CONDUITS AND ROUGH-IN REQUIREMENTS
PRIOR TO COMMENCING ANY WORK ON THIS SITE.
B. ELECTRICAL CONTRACTOR SHALL MEET WITH LOCAL LOW VOLTAGE SYSTEM PROVIDER AT THE
SITE TO VERIFY TERMINATION LOCATION, ROUTING OF CONDUITS AND ROUGH-IN
REQUIREMENTS PRIOR TO COMMENCING ANY WORK ON THIS SITE.
C. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL UTILITY UNDERGROUND LOCATING
SERVICE COMPANY PRIOR TO DIGGING ON THIS SITE.
D. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER FOR CONDUIT
OPENING IN STRUCTURAL SUPPORT.
E.…