Drawings 12 of 15 PLUMBING.pdf

PDF 15 MB Posted

Attached to
Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334
Solicitation number
36C77623R0156
Issued by

About this file

This document provides details for a federal contract opportunity to construct a new community living center. The solicitation number is 36C77623R0156 and seeks bids for the Y1AZ--TIERED EVALUATIONS project to build a new community living center at the Montrose VA medical center. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The contract involves constructing a new minor construction project to expand community living center facilities for veterans. Interested vendors should review the full solicitation documents for additional requirement details, response deadlines and terms, and information on the planned award date.

View the file

Other files

File Type Posted
620-334-Responses to Tech Questions - 1-30-24.pdf PDF
36C77623R0156 0003.pdf PDF
620-334-Pre Bid Presentation20240109.pdf PDF
36C77623R0156 0002.pdf PDF
620-334-Responses to Tech Questions - 1-25-24.pdf PDF
Site Visit Sign-In Sheet - 01-09-24.pdf PDF
36C77623R0156 0001.pdf PDF
DBA Wage Rates - Westchester County - 01-05-24.pdf PDF
Drawings 8 of 15 ARCHITECTURAL 3.pdf PDF
Site Visit Campus Map.pdf PDF
Drawings 14 of 15 ELECTRICAL 1.pdf PDF
Specifications 10-30-23.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
Drawings 5 of 15 STRUCTURAL.pdf PDF
RFP 36C77623R0156 - 12-20-23.pdf PDF
Drawings 1 of 15 GENERAL.pdf PDF
Drawings 4 of 15 LANDSCAPE.pdf PDF
Drawings 6 of 15 ARCHITECTURAL 1.pdf PDF
Drawings 2 of 15 CIVIL 1.pdf PDF
Drawings 7 of 15 ARCHITECTURAL 2.pdf PDF
Drawings 10 of 15 ARCH SIGN-EQUIP.pdf PDF
Drawings 13 of 15 MECHANICAL.pdf PDF
DBA Wage Rates - Westchester County - 11-17-23.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Drawings 15 of 15 ELECTRICAL 2.pdf PDF
Brand Name J_A - Montrose.pdf PDF
Site Visit Instructions.pdf PDF
Drawings 11 of 15 FIRE PROTECTION.pdf PDF
Drawings 9 of 15 ARCHITECTURAL 4.pdf PDF
Drawings 3 of 15 CIVIL 2.pdf PDF
Construction Cost Breakdown.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE PROVIDED (FURNISHED AND

INSTALLED) UNDER THIS CONTRACT. DRAWINGS SHOULD NOT BE SCALED.

2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER WHICH THEY SHALL OPERATE

AND VERIFY THE EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS CONTRACT.

3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO DETERMINE ANY

NECESSARY MODIFICATIONS.

4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE

ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.

5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:

• VA PLUMBING DESIGN MANUAL

• VA SMALL HOUSE DESIGN GUIDE

• INTERNATIONAL BUILDING CODE (IBC) 2018

• INTERNATIONAL EXISTING BUILDING CODE 2018

• IBC MECHANICAL 2018

• IBC PLUMBING 2018

• IBC ENERGY CONSERVATION 2018

• NFPA 1-2018, THE UNIFORM FIRE CODE

• NFPA 101-2018, THE LIFE SAFETY CODE

• NFPA 51B-2019, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING AND OTHER HOT WORK

• NFPA 13-2019, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS

• NFPA 70-2017, NATIONAL ELECTRICAL CODE

• NFPA 90A-2018, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTING SYSTEMS.

• NFPA 99-2018, STANDARD FOR HEALTH CARE FACILITIES

• NFPA 241-2019, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS.

6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND CONSTRUCTION WORK.

7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF WORK UNDER THIS CONTRACT.

DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF

INSTALLATION.

8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.

9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE TOTAL PROJECT COST.

10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.

REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.

11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL

TIMES DURING CONSTRUCTION.

12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.

13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS FOR ALL PRODUCTS USED ON

PROJECT.

14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS

OR HER SUBMITTAL DATA.

15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS

DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.

16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION COMPLETION.

17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND MATERIALS. NO CHANGE ORDERS SHALL

BE ISSUED WITHOUT WRITTEN CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.

(E) EXISTING

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISHED FLOOR

CO PIPE CLEAN OUT

CP CIRCULATOR PUMP

CTE CONNECT TO EXISTING

DCW DOMESTIC COLD WATER

DEMO DEMOLISH OR DEMOLITION

DFU DRAINAGE FIXTURE UNITS

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

(E) EXISTING

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FS FLOOR SINK

GCO GRADE CLEAN OUT

GPM GALLONS PER MINUTE

HD HUB DRAIN

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

HX HEAT EXCHANGER

IB ICE MAKER OUTLET BOX

IBC INTERNATIONAL BUILDING CODE

LAV LAVATORY

MS MOP SINK

NC NORMALLY CLOSED

NO NORMALLY OPEN

OD OVERFLOW ROOF DRAIN

OSD OVERFLOW (SECONDARY) STORM WATER DRAIN

PSD PRIMARY STORM WATER DRAIN

RD ROOF DRAIN

S SINK

SAN SANITARY

SH SHOWER

SP SUMP PUMP

TWH TANKLESS WATER HEATER

UR URINAL

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEAN OUT

WH WALL HYDRANT

WSFU WATER SUPPLY FIXTURE UNITS

ABBREVIATIONS

PLUMBING NOTES

1. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL

PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.

2. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE AND PROVIDE COORDINATION DRAWINGS PRIOR TO CONSTRUCTION. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE OR BELOW HVAC DUCTWORK, AS

COORDINATED WITH THE HVAC CONTRACTOR.

3. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.

4. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT

SUPPLIES.

5. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED

OTHERWISE.

6. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN.

FURNISH CUT-OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL

CONTRACTOR.

7. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT

EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN ON DRAWINGS.

8. VERIFY LOCATION OF WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO INSTALLATION.

9. CUT AND PATCH CONCRETE AS REQUIRED.

10. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND

INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.

11. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.

12. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION.

THERE WILL BE NO INSTALLATION UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE

ARCHITECT/ENGINEER.

13. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.

14. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER

EXAMINATION BEEN MADE.

15. VERIFY SERVICE POINTS AND METERING LOCATIONS FOR PROJECTS WITH LOCAL UTILITIES AND/OR LANDLORD

(DOMESTIC WATER, SANITARY SEWER, GAS, ETC.).

16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG ALL TRADES.

17. ALL ROOF PENETRATIONS FOR ROOF DRAINS AND PLUMBING, GAS, AND REFRIGERANT PIPING SHALL BE MADE IN ACCORDANCE WITH ROOF SYSTEM MANUFACTURER'S GUIDELINES. COORDINATE WITH ARCHITECTURAL DETAILS

AND/OR MANUFACTURER FOR ROOF SYSTEM USED.

18. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" BEFORE ROOF PENETRATION.

19. INSTALL INSULATION PER SPECIFICATION ON ALL ROOF LEADERS ABOVE CEILING.

20. THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACKFLOW AND SIPHONAGE, BOTH NATURAL AND INDUCED. ALL EQUIPMENT CONNECTED TO THE POTABLE WATER SYSTEM BEING CAPABLE OF POLLUTING OR CONTAMINATING THE POTABLE WATER DISTRIBUTION SYSTEM OR ANY PART THEREOF BY MEANS OF A REVERSAL OF FLOW, PRESSURE DROP, PRESSURE LOSS, INDUCED VACUUM, OR BY INJECTION BECAUSE OF ANY PRIMARY OR AUXILIARY PUMPING SYSTEM CONNECTED, MUST BE ISOLATED AND CONTAINED BY MEANS OF APPROVED BACKFLOW DEVICES, CHECK VALVES, AIR GAPS, OR VACUUM BREAKERS. PLUMBING CONTRACTOR SHALL FURNISH

AND INSTALL THESE DEVICES PER LOCAL CODE REQUIREMENTS.

21. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.

22. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH AND AS

REQUIRED.

23. ALL PIPES HANGING FROM SINGLE VERTICAL RODS / HANGERS SHALL NOT MOVE OR SWAY DURING OPERATION.

SUITABLE LATERAL SUPPORTS OR BRACING SHALL BE USED TO PREVENT SWAY OR MOVEMENT.

24. PROVIDE SHUTOFF BALL VALVES AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES.

PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT

SUPPLIER FOR EXACT REQUIREMENTS.

25. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.

26. PROVIDE COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS, OPEN RECEPTACLES, OR FLOOR SINKS. PIPING SHALL COMPLY WITH STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM

CLEARANCE UNDER CABINETS.

27. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.

28. INSTALL SANITARY, STORM, AND CONDENSATE PIPING WITH A MINIMUM SLOPE OF 1/8" PER FOOT UNLESS OTHERWISE REQUIRED. CONTRACTOR IS RESPONSIBLE FOR PROPER DRAINAGE OF ALL SYSTEMS.

29. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS. TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE ARCHITECTURAL

SHEETS FOR FLOOR SLOPES AND PROPER FINISHED FLOOR ELEVATION.

30. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL VTR'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND

MAINTAINED 10'-0" MINIMUM FROM ALL OUTSIDE AIR INTAKES.

31. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST

CURRENT ADOPTED VERSION OF THE STATE AND LOCAL CODES.

32. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE

COMPLETION OF PROJECT.

33. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.

34. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNLESS OTHERWISE NOTED). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE ACCESSIBLE THEY MUST COMPLY WITH ALL FEDERAL ADA REGULATIONS.

35. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT.

THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK

AND SHALL APPLY TO ALL DEFECTS IN MATERIALS AND WORKMANSHIP OF ANY KIND.

36. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.

37. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT TOWARDS WIDE SIDE OF STALL.

VERIFY IF RIGHT OR LEFT SIDE LOCATION.

38. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES )FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

(E)CW EXISTING COLD WATER

(E)SAN EXISTING SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

PLUMBING ACCESSORIES

FD-C:

FLOOR DRAIN - REFER TO SPECIFICATION FOR MORE INFORMATION.

FD-X:

FLOOR DRAIN - REFER TO SPECIFICATION FOR MORE INFORMATION.

FD-Z:

LINEAR SHOWER DRAIN, STAINLESS STEEL, 4 15/32" WIDE, REFER TO SPECIFICATIONS FOR MORE INFORMATION.

FCO:

FLOOR CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION

WCO:

WALL CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION

GCO:

GRADE CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION

RD:

ROOF DRAIN - 15" DIAMETER MAIN ROOF DRAIN LOW SILHOUETTE DOME (NO-HUB).

OD:

OVERFLOW (SECONDARY) ROOF DRAIN - 15" DIAMETER MAIN ROOF DRAIN LOW SILHOUETTE DOME (NO-HUB).

WATER MONITORING EQUIPMENT

THE SPECFIED WATER MONITORING EQUIPMENT SHALL BE REQUIRED AT THE FOLLOWING LOCATIONS:

TIE WATER MONITORING SYSTEM TO BAS

MAINS/RISERS

• CW/HW - MOST REMOTE LOCATION TEMPERATURE

BRANCH

• CW/HW - MOST REMOTE FIXTURE TEMPERATURE

RECIRCULATION

• TEMPERATURE AT END OF RETURN SYSTEM AND PRIOR TO MIXING.

• RECIRCULATION PUMP FLOW

SERVICE ENTRANCE

• CW - PROVIDE A PANEL MOUNTED SYSTEM (SAMPLER SKID) FOR AUTOMATIC MONITORING OF FREE OR TOTAL

CHLORINE RESIDUALS,PH, PRESSURE, DISSOLVED SOLIDS (CONDUCTIVITY), AND TEMPERATURE. THE SYSTEM MUST CONTINUOUSLY MONITOR THESE SENSORS AND MAKE THE DATA AVAILABLE SECURELY USING AND INTERNET CONNECTED DEVICE. THE TOTAL SYSTEM MUST BE PREWIRED AND PRE PLUMBED ON A SINGLE PANEL TO ENSURE HIGH QUALITY AND A SIMPLE INSTALLATION. PROVIDE PHIGENICS WME-1175 PWA ADVANCED

MONITORING SYSTEM 2.0 OR APPROVED EQUAL.

• HW - PROVIDE A PANEL MOUNTED SYSTEM (SAMPLER SKID) FOR AUTOMATIC MONITORING OF FREE OR TOTAL CHLORINE RESIDUALS,PH, PRESSURE, DISSOLVED SOLIDS (CONDUCTIVITY), AND TEMPERATURE. THE SYSTEM MUST CONTINUOUSLY MONITOR THESE SENSORS AND MAKE THE DATA AVAILABLE SECURELY USING AND INTERNET CONNECTED DEVICE. THE TOTAL SYSTEM MUST BE PREWIRED AND PRE PLUMBED ON A SINGLE PANEL TO ENSURE HIGH QUALITY AND A SIMPLE INSTALLATION. PROVIDE PHIGENICS WME-1175 PWA ADVANCED

MONITORING SYSTEM 2.0 OR APPROVED EQUAL. PROVIDE WITH SAMPLE COOLER.

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED

IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH

DEDUCTIVE ALTERNATE REFR TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).

DEDUCTIVE ALTERNATE #6 : REDUCE PLATFORM AT CHILLER.

DEDUCTIVE ALTERNATE NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:3

P

M

P-001

PLUMBING LEGENDS & NOTES

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS AK

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

DRAWING INDEX - PLUMBING

P-001 PLUMBING LEGENDS & NOTES

PL100 PLUMBING OVERALL FLOOR PLAN - BASEMENT

PL101 PLUMBING OVERALL FLOOR PLAN - LEVEL 1

PL101A SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA A

PL101B SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA B

PL102 PLUMBING OVERALL FLOOR PLAN - PENTHOUSE

PL201A DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA A

PL201B DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA B

PL401 PLUMBING ENLARGED FLOOR PLAN

P-501 PLUMBING DETAILS

P-502 PLUMBING DETAILS

P-503 PLUMBING SCHEMATIC

P-601 SANITARY & VENT ISOMETRICS - LEVEL 1 - AREA A

P-602 SANITARY & VENT ISOMETRICS - LEVEL 1 - AREA B

P-603 DOMESTIC WATER ISOMETRICS - LEVEL 1 - AREA A

P-604 DOMESTIC WATER ISOMETRICS - LEVEL 1 - AREA B

PLUMBING FIXTURE SCHEDULE

FIXTURE

MARK FIXTURE

COUNT

FIXTURE DESCRIPTION

ROUGH-IN PIPE SIZES FIXTURE UNITS

COLD

WATER

SUPPLY

HOT

WATER

SUPPLY

FIXTURE

TRAP

FIXTURE

DRAIN

COLD

WATER

HOT

WATER

DRAINAGE

P-107

3 WATER CLOSET, BARRIER FREE - BACK OUTLET, WALL

MOUNTED, ELONGATED RIM, 1-1/2" TOP SPUD, MANUAL

FLUSH VALVE, 1.28 GPF, VITREOUS CHINA, VACUUM

BREAKER; OPEN FRONT SEAT LESS COVER, STAINLESS

STEEL CHECK HINGE. RIM: 17". FIXTURE SHALL BE EPA

WATER SENSE LABELED WATER CONSERVING PRODUCT.

REFER TO SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

1" N/A 4" 4" 10 0 4

P-114

28 WATER CLOSET, BARRIER FREE - BACK OUTLET, WALL

MOUNTED, ELONGATED RIM, 1-1/2" TOP SPUD, MANUAL

FLUSH VALVE, 1.28 GPF, VITREOUS CHINA, VACUUM

BREAKER; OPEN FRONT SEAT LESS COVER, STAINLESS

STEEL CHECK HINGE. RIM: 17". FIXTURE SHALL BE EPA

WATER SENSE LABELED WATER CONSERVING PRODUCT.

REFER TO SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

1" N/A 4" 4" 10 0 4

P-417

29 LAVATORY - INTEGRAL TO COUNTERTOP, LAVATORY

PROVIDED BY MILLWORK CONTRACTOR, FAUCET HOLES

AS REQUIRED. REFER TO ARCHITECTURAL DETAIL D7 ON

SHEET A-401 FOR COUNTERTOP INFORMATION. PLUBMING

CONTRACTOR TO PROVIDE RIGID GOOSENECK SPOUT

WITH WRIST BLADE HANDLES FAUCET WITH ASSE 1070

COMPLIANT THERMOSTATIC ANTI-SCALD VALVE (SEE

DETAIL 1 ON SHEET P-502), 1/2 GPM, LEAD FREE, DECK

MOUNTED. PROVIDE COVER PLATES, GRID DRAIN

ASSEMBLY, P-TRAP, STOPS, SUPPLIES, ETC., FOR A

COMPLETE INSTALLATION. FIXTURE SHALL BE EPA WATER

SENSE LABELED WATER CONSERVING PRODUCT. REFER

TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

1/2" 1/2" 1 1/4" 2" 0.5 0.5 1

P-418

8 LAVATORY - BARRIER FREE, WALL HUNG. PROVIDE

CONCEALED ARM SUPPORT CARRIER. PROVIDE

SELF-POWERED, SENSOR OPERATED, 0.5 GPM, ADA

COMPLIANT, SINGLE HOLE, DECK MOUNTED FAUCET:

TOTO TEL105-D10E OR EQUAL. PROVIDE WITH ASSE 1070

THERMOSTATIC ANTI-SCALD VALVE. TOP OF RIM 34" FROM

FINISHED FLOOR. PROVIDE COVER PLATES, PERFORATED

STRAINER, P-TRAP, STOPS, SUPPLIES, ETC. FOR A

COMPLETE INSTALLATION. PROVIDE ADA COMPLIANT

PROTECTIVE PIPING COVERS FOR EXPOSED SUPPLIES,

TRAP, AND DRAIN PIPING. FIXTURE SHALL BE EPA WATER

SENSE LABELED WATER CONSERVING PRODUCT. REFER

TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

1/2" 1/2" 1 1/4" 2" 0.5 0.5 1

P-501

2 SERVICE SINK . REFER TO SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

1/2" 1/2" 3" 3" 2.25 2.25 2

P-505

2 CLINICAL SINK - FLOOR MOUNTED, PROVIDE WITH

SERVICE SINK FAUCET AND FLUSH VALVE, REFER TO

P-505FV BELOW FOR ADDITIONAL INFORMATION

REGARDING THE FLUSHVALVE. PROVIDE WITH ASSE 1070

THERMOSTATIC ANTI-SCALD VALVE. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

1/2" 1/2" 4" 4" 1 1 2

P-505FV

2 CLINICAL SINK FLUSH VALVE - REFER TO SPECIFICATION

FOR ADDITIONAL INFORMATION.

1" N/A 4" 4" 10 0 4

P-516

1 SINK - SALON HAIR WASHING. HIGH PORCELAIN WALL

MOUNTED SHAMPOO BOWL FOR HAIR WASHING. PROVIDE

WITH SPRAY NOZZLE WITH HOSE, STRAINER, AND ASSE

1070 ANTI-SCALD VALVE. REFER TO SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

1/2" 1/2" 1 1/4" 2" 0.5 0.5 1

P-524

7 TWO COMPARTMENT SINK - 29X22" STAINLESS STEEL TWO

COMPARTMENT SINK, SELF RIMMING, 7-3/4" DEEP, 3

FAUCET HOLES. BASKET STRAINER NO. LK35 GRID DRAIN.

WRIST BLADE FAUCET - ELKAY MODEL LK810HA08T4, 4"

WRISTBLADE HANDLES WITH 8" RIGID GOOSENECK SPOUT,

AERATOR, DRAIN BASKET AND STRAINER. PROVIDE WITH

ASSE 1070 ANTI-SCALD VALVE. PROVIDE STOPS,

SUPPLIES, TRAP, ETC., TO COMPLETE INSTALLATION.

1/2" 1/2" 1 1/2" 2" 1 1 1.4

P-528

2 SINK - SINGLE COMPARTMENT, STAINLESS STEEL.

PROVIDE WITH ASSE 1070 ANTI-SCALD VALVE.

1/2" 1/2" 1 1/4" 2" 0.5 0.5 1

P-701

30 SHOWER - ADA COMPLIANT, SHOWER SYSTEM WITH

SHOWER HEAD AND SINGLE LEVER HANDLE,

PRESSURE-BALANCED THERMOSTATIC ANTI-SCALD

VALVE, WITH INTEGRAL SERVICE STOPS, 1.5 GPM.

PROVIDE SHOWER FLOOR DRAIN KOHLER K-9132 OR

EQUAL, CHROME PLATED BRASS, WITH 4 3/8" ROUND

STRAINER, AND 2" OUTLET. PROVIDE STOPS, SUPPLIES,

TRAP, ETC. FOR A COMPLETE INSTALLATION. FIXTURE

SHALL BE EPA WATER SENSE LABELED WATER

CONSERVING PRODUCT. REFER TO SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

1/2" 1/2" 2" 2" 3 3 2

P-708

4 EMERGENCY EYE AND FACE WASH, WALL MOUNTED,

PROVIDE WITH ASSE 1071 THERMOSTATIC ANTI-SCALD

VALVE.

1/2" 1/2" 1 1/2" 2" 1 1 2

P-801

10 WALL HYDRANT, NON-FREEZE - ZURN NO. Z-1330-C,

ENCASED FLUSH WALL HYDRANT, NICKEL BRONZE BOX

AND HINGE COVER WITH OPERATING CYLINDER LOCK AND

"WATER" CAST ON COVER. 3/4" CW.

3/4" N/A N/A N/A 5 0 0

P-802

1 LAWN FAUCET, NON-FREEZE – BRASS FAUCET WITH

DETACHABLE WHEEL OR T-HANDLE. REFER TO

SPECIFICATION FOR MORE INFORMATION.

3/4" N/A N/A N/A 2 0 0

P-812

5 WATER SUPPLY BOX UNIT (ICE MAKER) WITH BALL TYPE

SHUT OFF VALVE.

1/2" N/A N/A N/A 0.25 0 0

CIRCULATOR PUMP SCHEDULE

MARK CAPACITY TOTAL HEAD

SHUTOFF

HEAD

MOTOR

POWER

ELECTRICAL DATA

MANUFACTURER

MODEL

NUMBERVOLTAGE PHASE

CP-1 4 GPM 7 ftH2O 11 ftH2O 0.125 hp 115 V 1 TACO 0010-SF3

CP-2 4 GPM 7 ftH2O 11 ftH2O 0.125 hp 115 V 1 TACO 0010-SF3

NOTES:

1. PUMPS SHALL OPERATE ONE AT A TIME. IF 1 PUMP FAILS, THE OTHER WILL AUTOMATICALLY TURN ON. PUMPS SHALL ALTERNATE BASED ON A SCHEDULE TO BE DETERMINED BY THE VA. PUMPS SHALL RUN CONTINUOUSLY.

Revisions: Date: 7/21/2021

STAMP

05/09/20225/09/2022

PL401

STORM PIPING

UP TO FLOOR

ABOVE.

P S

D

REFER TO CIVIL

PLANS FOR

CONTINUATION.

ROUTE NEW 3" DCW

PIPING FROM EXISTING

MAIN. REFER TO CIVIL

DRAWINGS FOR

CONTINUATION AND

COORDINATION.

ROUTE 6" SANITARY PIPE TO

EXISTING SANITARY MAIN.

INVERT ELEVATION 15'

BELOW FFE. REFER TO CIVIL

DRAWINGS FOR

CONTINUATION. TIE

SANITARY PIPE TO EXISTING

SANITARY MAIN PRIOR TO

SLAB POUR.

C W

8' - 10"

9' - 0"

DEDUCT

ALTERNATE 2

EAST TUNNEL

001A

EAST TUNNEL

001A

NORTH TUNNEL

001C

INVERT ELEVATION - 101.50"

BASEMENT

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

BB

7.86.6 7.1 7.6

AA

7.76.8

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT

LOCATED ABOVE LAY-IN CEILING.

E. DOMESTIC COLD, HOT, AND HOT WATER RETURN PIPING SHOWN

ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR CEILING

UNLESS NOTED OTHERWISE.

F. COORDINATE SHUTOFF VALVE ACCESS WITH SPRINKLER HEADS

LOCATIONS.

GENERAL NOTES

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).

REFER TO COVER SHEET GI000 FOR MORE INFORMATION ON

DEDUCTIVE ALTERNATIVES.

DEDUCTIVE ALTERNATE

N

KEY PLAN

BASEMENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:4

P

M

PL100

PLUMBING OVERALL FLOOR PLAN - BASEMENT

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS NS/TR

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

3/32" = 1'-0"

PLUMBING OVERALL FLOOR PLAN - BASEMENT

KEYNOTES

1 DCW PIPE TO COLD WATER FILL LINE FOR HEATING HOT WATER

SYSTEM.

Revisions: Date: 7/21/2021

STAMP

PORCH-A

FOYER

RESIDENT 6

RESIDENT 9

TLT 9

127A

DINING

RESIDENT 11

SITTING ALCOVE

11/12A

RESIDENT 12

RESIDENT 13

ELEC

TLT 12

131A

TLT 13

133A

LN

SITTING ALCOVE

13/14A

RESIDENT 10

TLT 8

126A

RESIDENT 1

TLT 10

128A

SITTING ALCOVE

8/9/10A

TLT 11

130A

RESIDENT 14

TLT 14

134A

RESIDENT 4

TLT 6

119A

RESIDENT 5

TLT 4

117A

SITTING ALCOVE

4/5/6/7A

RESIDENT 3

SITTING ALCOVE

2/3A

RESIDENT 2

TLT 2

114A

TLT 3

115A

LOBBY

PANTRY

125A

DINING

RESIDENT 10

SITTING ALCOVE

10/11B

RESIDENT 11

RESIDENT 12

ELEC

HALLWAY

192C

TLT 11

178A

TLT 12

180A

LN

CLEAN

SITTING ALCOVE

12/13B

RESIDENT 9

TLT 9

173A

SITTING ALCOVE

6/7/8/9B

TLT 10

175A

RESIDENT 13

TLT 13

181A

RESIDENT 3

RESIDENT 14

TLT 3

162A

SITTING ALCOVE

3/4/5B

RESIDENT 2

SITTING ALCOVE

1/2B

RESIDENT 1

TLT 1

159A

TLT 2

160A

FAMILY TOILET

HAC

POWER

EMERGENCY

POWER

GAS

EXAM RM

STERILE SUPPLY

STORAGE

PT/KT

STORAGE

CENTRAL KITCHEN

ACTIVITY

CORRIDOR

164C

LN

LN

LN

LN

LN

LN

LN

LN

CORRIDOR

120C

MECHANICAL

LIVING ROOM

MAIN PORCH

IT CLOSET

PANTRY

168A

OFFICE

OFFICE

CONFERENCE

MEDS

CLEAN

SOILED

TLT 1

110A

TLT 14

183A

HOTELING

STAFF LOUNGE

OFFICE

ADMIN HALL-B

- CORRIDOR

162C

SOILED

MEDS

CRASH CART B

CHARGING B

CRASH CART

CHARGING A

SALON

WHEELCHAIR/

STRETCHER STRG

HALLWAY

209C

CLC WALKWAY

STAFF TOILET/

SHOWER

TLT 5

118A

RESIDENT 8

RESIDENT 5

RESIDENT 4

TLT 4

163A

TLT 8

172A

TLT 7

171A

RESIDENT 8

TLT 5

164A

LIVING ROOM

RESIDENT 7

SITTING ALCOVE

1A

CORRIDOR 1A

CORRIDOR

122C

CORRIDOR

163C

SITTING ALCOVE

14B

LN

RESIDENT 7

(BARIATRIC)

TLT 7

120A

HAC

PUBLIC TOILET

STORAGE

LN

169 RESIDENT 6

(BARIATRIC)

TLT 6

170A

STAIRS

144B

M A

T C

H

LI

N E

S

E : 1

/P L1

A

M A

T C

H

LI

E : 1

/P L1

B

M A

T C

H

LI

E : 1

/P L2

A

M A

T C

H

LI

E : 1

/P L2

B

PL101A

PL201A

PL201A

PL201B

PL101B

GCO

PORCH B

MATCHLINE

SEE: 2/PL201A

PL401

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT

LOCATED ABOVE LAY-IN CEILING.

E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE

FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING

SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR

CEILING UNLESS NOTED OTHERWISE.

GENERAL NOTES

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

N

KEY PLAN

AREA B

(EAST)

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:5

P

M

PL101

PLUMBING OVERALL FLOOR PLAN - LEVEL 1

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS AK

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

3/32" = 1'-0"

PLUMBING OVERALL FLOOR PLAN - LEVEL 1

Revisions: Date: 7/21/2021

STAMP

P-114

P-417

P-114

P-417

FD-ZFD-Z

P-114

P-417

FD-Z

P-114 P-417

P-114 P-417

FD-Z

FD-Z

P-114

P-417

FD-Z

P-418

FOYER

RESIDENT 6

RESIDENT 9

TLT 9

127A

DINING

RESIDENT 11

SITTING ALCOVE

11/12A

RESIDENT 12

RESIDENT 13

ELEC

TLT 12

131A

TLT 13

133A

LN

SITTING ALCOVE

13/14A

RESIDENT 10

TLT 8

126A

RESIDENT 1

TLT 10

128A

SITTING ALCOVE

8/9/10A

TLT 11

130A

RESIDENT 14

TLT 14

134A

RESIDENT 4

TLT 6

119A

RESIDENT 5

TLT 4

117A

SITTING ALCOVE

4/5/6/7A

RESIDENT 3

SITTING ALCOVE

2/3A

RESIDENT 2

TLT 2

114A

TLT 3

115A

LOBBY

PANTRY

125A

RESIDENT 13

TLT 13

181A

RESIDENT 14

FAMILY TOILET

STERILE SUPPLY

STORAGE

PT/KT

STORAGE

CENTRAL KITCHEN

ACTIVITY

LN

LN

116 LN

LN

CORRIDOR

120C

MECHANICAL

PORCH-A

LIVING ROOM

MAIN PORCH

IT CLOSET

CONFERENCE

MEDS

CLEAN

SOILED

TLT 1

110A

TLT 14

183A

HOTELING

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CRASH CART

CHARGING A

SALON

WHEELCHAIR/

STRETCHER STRG

HALLWAY

209C

CLC WALKWAY

STAFF TOILET/

SHOWER

TLT 5

118A

RESIDENT 8

SITTING ALCOVE

1A

CORRIDOR 1A

CORRIDOR

122C

SITTING ALCOVE

14B

RESIDENT 7

(BARIATRIC)

TLT 7

120A

HAC

PUBLIC TOILET

STORAGE

P-114 P-417

FD-Z

P-114

FD-Z

P-417

GCO

3" VTR

2" VTR

3" VTR

M A

T C

H

LI

E : 1

/P L1

B

P-505

P-418 P-708

P-418

P-107

P-524

P-114

FD-Z

P-417P-417

P-114

FD-Z

P-516

P-528

P-708

P-501

P-524

P-812

P-418 P-107

P-107

P-418

P-524

FD-ZFD-Z

P-114 P-114

P-417P-417

FD-Z

P-114

P-417 P-417

P-114

FD-Z

P-417 P-417

P-114 P-114

FD-Z FD-Z

FD-Z

P-524

P-528

3" VTR

3" VTR

3" SAN

UP TO FIXTURE

ON FLOOR

ABOVE.

3" SAN

4" SAN

FCO

FCO

WCOWCO

WCO

WCO WCO WCO

WCO

M A

T C

H

LI

E : 1

/P L1

B

WCO

CO

WCO

WCO

WCO

WCO

FD-C

FD-C

FD-C

FD-C

FD-C FD-C FD-C

FD-C

FD-C

FD-CFD-C FD-C FD-C FD-C

FD-C

WCO

WCO

WCO

SCREENING

VESTIBULE

3 3

3 3

SITTING ALCOVE

14B

4" SAN

2" VENT

2" VENT

STORAGE

4" SAN

3" SAN

2" SAN

2" SAN

3" SAN

4" SAN

4" SAN 4" SAN

2" SAN

FD-S

FD-S FD-S

FD-E

4" SAN

4" PSD

6" OSD

1 1/2" VENT2" VENT2" VENT

4" SAN

2" VENT

4" SAN

4" SAN

4" SAN

4" SAN

2" VENT

4" SAN

6" SAN

4" SAN

2" VENT

4" SAN 4" SAN

6" OSD

6" OSD

4" PSD

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

FCO

WCO

WCO

WCO

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT

LOCATED ABOVE LAY-IN CEILING.

E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE

FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING

SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR

CEILING UNLESS NOTED OTHERWISE.

GENERAL NOTES

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

KEY PLAN

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:0

P

M

PL101A

SANITARY AND VENT FLOOR PLAN - LEVEL 1 -

AREA A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS AK

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA A

KEYNOTES

1 PROVIDE FLEXIBLE JOINT IN PIPING AT EXPANSION JOINT

CROSSING.

2 STORM DRAIN PIPING RD-1 AND OD-1 FROM FLOOR ABOVE.

3 VENT PIPING OVERLAY SANITARY LINE WORK. REFER TO

ISOMETRICS FOR ADDITIONAL INFORMATION.

4 ROUTE 6" SANITARY PIPE TO EXISTING SANITARY MAIN. REFER TO

CIVIL DRAWINGS FOR CONTINUATION.

5 REFER TO CIVIL DRAWINGS FOR CONTINUATION.REFER TO DETAIL

T/S-201 FOR FOOTING AND FOR PENETRATION REFER TO DETAIL

F/S-202.

6 VENT PIPE CONTINUED THROUGH PLENUM SPACE ABOVE TO VTR.

REFER TO PL102 FOR CONTINUATION.

Revisions: Date: 7/21/2021

STAMP

P-418

P-524

P-417

P-417

FD-Z

DINING

RESIDENT 10

SITTING ALCOVE

10/11B

RESIDENT 11

RESIDENT 12

ELEC

HALLWAY

192C

TLT 11

178A

TLT 12

180A

LN

CLEAN

SITTING ALCOVE

12/13B

RESIDENT 9

TLT 9

173A

SITTING ALCOVE

6/7/8/9B

TLT 10

175A

RESIDENT 13

TLT 13

181A

RESIDENT 3

RESIDENT 14

TLT 3

162A

SITTING ALCOVE

3/4/5B

RESIDENT 2

SITTING ALCOVE

1/2B

RESIDENT 1

TLT 1

159A

TLT 2

160A

FAMILY TOILET

HAC

POWER

EMERGENCY

POWER

GAS

152EXAM RM

PT/KT

CORRIDOR

164CLN

LN

LN

LN

MAIN PORCH

PANTRY

168A

OFFICE

OFFICE

CONFERENCE

TLT 14

183A

HOTELING

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CORRIDOR

162C

SOILED

MEDS

CRASH CART B

CHARGING B

STAFF TOILET/

SHOWER

RESIDENT 5

RESIDENT 4

TLT 4

163A

TLT 8

172A

TLT 7

171A

RESIDENT 8

TLT 5

164A

LIVING ROOM

165 PORCH B

RESIDENT 7

CORRIDOR

163C

LN

RESIDENT 6

(BARIATRIC)

TLT 6

170A

3" VTR

M A

T C

H

LI

E : 1

/P L1

A

P-418

P-107

P-418

P-501

P-418

P-417

P-114

FD-Z

P-114

P-417P-417

P-114

FD-Z

FD-Z

P-417 P-114

P-417 P-114 FD-Z

P-708

P-418

P-505

P-708

FD-ZFD-Z

P-114 P-114

P-417P-417

P-114 P-114

P-417P-417

FD-Z FD-Z

P-417 P-417

P-114 P-114

FD-Z FD-Z

P-114

FD-Z

P-114

P-417

P-114

FD-Z

FD-Z

P-524

P-528

FD-Z

P-524

3" VTR

3" VTR

3" VTR

FCO

WCO

WCO

WCO

WCOWCO

M A

T C

H

LI

E : 1

/P L1

A

CO

WCO

WCO

WCO

WCO

WCO

FD-C

FD-C

FD-C FD-C FD-C FD-C

FD-C

FD-C

FD-C

FD-C FD-CFD-C

WCO

WCO

WCO

WCO

2 2 2

SITTING ALCOVE

14B

STORAGE

2" SAN

3" SAN

4" SAN

2" SAN

FD-S

FD-S

2" VENT

4" SAN

4" SAN

4" PSD

6" OSD

4" SAN

2" VENT

4" SAN

2" VENT

2" VENT

2" VENT1 1/2" VENT

1 1/2" VENT

6" OSD

4" PSD

44 4

7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

8.6

AA

WCO

FD-C

FD-C

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT

LOCATED ABOVE LAY-IN CEILING.

E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE

FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING

SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR

CEILING UNLESS NOTED OTHERWISE.

GENERAL NOTES

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

KEY PLAN

AREA B

(EAST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:0

P

M

PL101B

SANITARY AND VENT FLOOR PLAN - LEVEL 1 -

AREA B

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS AK

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA B

KEYNOTES

1 STORM DRAIN PIPING RD-1 AND OD-1 FROM FLOOR ABOVE.

2 VENT PIPING OVERLAY SANITARY LINE WORK. REFER TO

ISOMETRICS FOR ADDITIONAL INFORMATION.

3 REFER TO CIVIL DRAWINGS FOR CONTINUATION.REFER TO DETAIL

T/S-201 FOR FOOTING AND FOR PENETRATION REFER TO DETAIL

F/S-202.

4 VENT PIPE CONTINUED THROUGH PLENUM SPACE ABOVE TO VTR.

REFER TO PL102 FOR CONTINUATION.

Revisions: Date: 7/21/2021

STAMP

B F

P

MECH

PENTHOUSE

FD-X

FD-X

2-AH02

2-AH01

RD-1

CH-1

CH-2

EF-01 EF-02

DSSO-01

OD-1

2-CSG01

CWP-1

CWP-2

2" VTR

3" VTR

3" VTR

2" VTR

2" VTR

3" VTR

3" VTR

3" VTR

3" VTR

3" VTR

STAIRS

201A

CHILLERS

201B

PIPE TO

CEILING OF

FLOOR BELOW

DEDUCT

ALTERNATE

#7

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

P-801 P-802

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT

LOCATED ABOVE LAY-IN CEILING.

E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE

FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING

SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR

CEILING UNLESS NOTED OTHERWISE.

F. DOMESTIC COLD, HOT AND HOT WATER RETURN PIPING SHOWN

ON THIS PLAN IS LOCATED BELOW THE PENTHOUSE FLOOR SLAB

UNLESS NOTED OTHERWISE.

GENERAL NOTES

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED

IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH

DEDUCTIVE ALTERNATE REFR TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #7 : REDUCE PLATFORM AT CHILLER

DEDUCTIVE ALTERNATE NOTES

N

KEY PLAN

LEVEL 2

PENTHOUSE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:4

P

M

PL102

PLUMBING OVERALL FLOOR PLAN - PENTHOUSE

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 NPS AK

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

3/32" = 1'-0"

PLUMBING OVERALL FLOOR PLAN - PENTHOUSE

KEYNOTES

1 DCW PIPE TO COLD WATER FILL LINE FOR CHILLED WATER SYSTEM.

2 DCW PIPE TO WATER TREATMENT SYSTEM WHICH SERVES THE

CLEAN STEAM GENERATOR. PROVIDE BACKFLOW PREVENTOR.

Revisions: Date: 7/21/2021

STAMP

FOYER

RESIDENT 6

RESIDENT 9

TLT 9

127A

DINING

RESIDENT 11

SITTING ALCOVE

11/12A

RESIDENT 12

RESIDENT 13

ELEC

TLT 12

131A

TLT 13

133A

LN

SITTING ALCOVE

13/14A

RESIDENT 10

TLT 8

126A

RESIDENT 1

TLT 10

128A

SITTING ALCOVE

8/9/10A

TLT 11

130A

RESIDENT 14

TLT 14

134A

RESIDENT 4

TLT 6

119A

RESIDENT 5

TLT 4

117A

SITTING ALCOVE

4/5/6/7A

RESIDENT 3

SITTING ALCOVE

2/3A

RESIDENT 2

TLT 2

114A

TLT 3

115A

LOBBY

PANTRY

125A

RESIDENT 13

TLT 13

181A

RESIDENT 14

FAMILY TOILET

STERILE SUPPLY

STORAGE

PT/KT

STORAGE

CENTRAL KITCHEN

ACTIVITY

LN

LN

LN

111 LN

CORRIDOR

120C

MECHANICAL

PORCH-A

LIVING ROOM

MAIN PORCH

IT CLOSET

CONFERENCE

MEDS

CLEAN

SOILED

TLT 1

110A

TLT 14

183A

HOTELING

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CRASH CART

CHARGING A

SALON

WHEELCHAIR/

STRETCHER STRG

HALLWAY

209C

CLC WALKWAY

STAFF TOILET/

SHOWER

TLT 5

118A

RESIDENT 8

SITTING ALCOVE

1A

CORRIDOR 1A

CORRIDOR

122C

SITTING ALCOVE

14B

RESIDENT 7

(BARIATRIC)

TLT 7

120A

HAC

PUBLIC TOILET

STORAGE

M A

T C

H

LI

E : 1

/P L2

B

P-701

P-114

P-417 P-417

P-114

P-701

P-417

P-701

P-701 P-114 P-417

P-417P-114

P-701 P-114

P-418

P-114

P-701

P-114

P-417 P-417

P-114

P-524

P-107

P-107

P-418

P-418

P-524

P-701

P-114

P-417P-417

P-114

P-701

P-114

P-417P-417

P-114

P-701

P-114

P-417P-417

P-114

P-528

P-528

P-501

P-418

P-708

P-708

P-418

P-516

P-417

P-114

P-701

P-701

P-417

P-417P-114 P-701

P-524

P-505

P-107 P-524

WCO 1 1/4" CW

3/4" HW

P-701

P-701 P-701 P-701

P-701

M A

T C

H

LI

E : 1

/P L2

B

CORR

STAIRS

144B

SCREENING

VESTIBULE

1" HWR

5 5

P-812

P-812

P-812

MATCHLINE

SEE: 2/PL201A

1 1/2" HW

2 1/2" CW

1 1/2" HW

2 1/2" CW

2" HW

2 1/2" CW

2 1/2" CW

1 1/2" HW

1 1/4" HW

2 1/2" CW

2 1/2" CW

1 1/4" HW

1 1/2" CW

1" HW

1" HWR

2" HW

2 1/2" CW

1" HW

2" CW

1" HWR

2 1/2" CW

1 1/2" HW

3/4" CW

3" CW

1 1/2" HW

1" HW

1" HWR

3/4" CW

1 1/2" CW

1" HW

1" HWR

1" HWR

1" HWR

1 1/4" CW

1 1/4" CW

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

P-801

P-801

P-801

P-801

P-801

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

RESIDENT 14

TLT 14

134A

LN

MECHANICAL

CLC WALKWAY

B6 WALKWAY

P-701

P-417

P-114

3" CW

1 1/2" HW

STAIRS

144B

MATCHLINE

SEE: 1/PL201A

7 7.2 7.5

G.2

G.3

F

E.4

E.2

E

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

KEY PLAN

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:5

P

M

PL201A

DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA

A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA A

1/8" = 1'-0"

DOMESTIC WATER FLOOR PLAN - LEVEL 1 - COVERED WALKWAY

KEYNOTES

1 2" DCW, 2" DHW, 1" HWR DOWN TO HOT WATER HEAT EXCHANGERS

IN MECHANICAL ROOM.

2 PROVIDE FLEXIBLE JOINT IN PIPING AT EXPANSION JOINT

CROSSING.

3 3"DCW PIPING IN THE STEAM TUNNEL.

4 ROUTE NEW 3" DCW PIPING FROM EXISTING MAIN. REFER TO CIVIL

DRAWINGS FOR CONTINUATION AND COORDINATION.

5 PROVIDE WITH ASSE 1070 THERMOSTATIC ANYI-SCALD MIXING

VALVE PER DETAIL 1 ON SHEET P-502.

6 PROVIDE WITH ASSE 1071 THERMOSTATIC ANYI-SCALD MIXING

VALVE PER DETAIL 1 ON SHEET P-502.

7 ROUTE 3/4" DCW PIING TO WALL HYDRANT IN ATTIC SPACE.

8 ROUTE 3/4" DCW, DHW PIPING DOWN TO PLUMBING FIXTURES.

9 ROUTE PIPING TIGHT TO WALL, PAINT TO MATCH WALL.

10 1/2" DCW CONNECTION FOR COFFEE MAKER, COORDINATE EXACT

LOCATION.

Revisions: Date: 7/21/2021

STAMP

DRAWING KEYNOTE#

EQUIPMENT MARK

POINT OF NEW CONNECTION

POINT OF CONNECTION TO CIVIL

CW COLD WATER PIPING

HW HOT WATER PIPING

HWR HOT WATER RETURN PIPING

SAN SANITARY PIPING

V SANITARY VENT PIPING

PIPE UP

PIPE DOWN

GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR

OR VTR VENT THRU ROOF

WCO WALL CLEAN OUT

FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR

PIPE CAP

WCO

FLOOR DRAIN

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

GATE VALVE

PLUG VALVE

STRAINER

UNION

PRESSURE RELIEF VALVEPRV

BACKFLOW PREVENTER

PLUMBING LEGEND

FD

P-XXX

A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE

SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A

MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE

REQUIREMENTS WITH THE COR.

B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE

APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD

VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,

SIZES, AND CONDITIONS OF EXISTING COMPONENTS.

C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO

EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.

This is the start of the file's text. The full file is on GovTribe.