This document provides details for a federal contract opportunity to construct a new community living center. The solicitation number is 36C77623R0156 and seeks bids for the Y1AZ--TIERED EVALUATIONS project to build a new community living center at the Montrose VA medical center. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The contract involves constructing a new minor construction project to expand community living center facilities for veterans. Interested vendors should review the full solicitation documents for additional requirement details, response deadlines and terms, and information on the planned award date.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATIVE OF WORK TO BE PROVIDED (FURNISHED AND
INSTALLED) UNDER THIS CONTRACT. DRAWINGS SHOULD NOT BE SCALED.
2. THE CONTRACTOR IS RESPONSIBLE TO EXAMINE THE EXISTING CONDITIONS UNDER WHICH THEY SHALL OPERATE
AND VERIFY THE EXTENT OF WORK REQUIRED TO COMPLETE THE WORK UNDER THIS CONTRACT.
3. PRIOR TO ORDERING AND FABRICATING ANY EQUIPMENT, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO EXAMINE THE PHYSICAL CONDITIONS AT THE PROJECT SITE AND VERIFY SPACE AND SUFFICIENT CLEARANCES ARE AVAILABLE FOR INSTALLING EQUIPMENT, DUCTWORK, PIPING, AND APPURTENANCES, AND TO DETERMINE ANY
NECESSARY MODIFICATIONS.
4. PERFORM ALL WORK IN COMPLIANCE WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES, REGULATIONS, AND STANDARDS ADOPTED BY THE AUTHORITY HAVING JURISDICTION. IF CONFLICTS EXIST BETWEEN THESE
ENGINEERING DOCUMENTS AND CODES, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN.
5. ALL CONSTRUCTION WORK SHALL ALSO MEET THE FOLLOWING CODE REQUIREMENTS:
• VA PLUMBING DESIGN MANUAL
• VA SMALL HOUSE DESIGN GUIDE
• INTERNATIONAL BUILDING CODE (IBC) 2018
• INTERNATIONAL EXISTING BUILDING CODE 2018
• IBC MECHANICAL 2018
• IBC PLUMBING 2018
• IBC ENERGY CONSERVATION 2018
• NFPA 1-2018, THE UNIFORM FIRE CODE
• NFPA 101-2018, THE LIFE SAFETY CODE
• NFPA 51B-2019, STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING AND OTHER HOT WORK
• NFPA 13-2019, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
• NFPA 70-2017, NATIONAL ELECTRICAL CODE
• NFPA 90A-2018, STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTING SYSTEMS.
• NFPA 99-2018, STANDARD FOR HEALTH CARE FACILITIES
• NFPA 241-2019, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION OPERATIONS.
6. CONTRACTOR SHALL COORDINATE AND SEQUENCE DEMOLITION, CLEANING, AND CONSTRUCTION WORK.
7. CONTRACTOR SHALL NOTE ANY SPECIAL REQUIREMENTS FOR INSTALLATION OF WORK UNDER THIS CONTRACT.
DISMANTLE AND REASSEMBLE EQUIPMENT AS NECESSARY FOR ENTRY INTO THE BUILDING AND THE LOCATION OF
INSTALLATION.
8. THE CONTRACTOR SHALL MAINTAIN A COMPLETE PROJECT SCHEDULE AND SHALL UPDATE THIS SCHEDULE WEEKLY. ANY CHANGES SHALL BE NOTED AND AN UPDATED SCHEDULE SHALL BE PROVIDED TO THE OWNER.
9. ALL PERMITS, FEES, TAXES, ETC SHALL BE PAID BY CONTRACTOR AS PART OF THE TOTAL PROJECT COST.
10. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS, CEILINGS, AND FLOORS. SEAL ALL PENETRATIONS THROUGH RATED ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH U.L.
REQUIREMENTS TO MAINTAIN THE ASSEMBLY RATING.
11. CONTRACTOR SHALL FURNISH U.L. APPROVED DRAWINGS FOR EACH TYPE OF FIRE AND SMOKE RATED ASSEMBLY PENETRATION BY DUCTS, PIPES, OR CONDUITS, AND SHALL DISPLAY THESE DRAWINGS ON THE JOB SITE AT ALL
TIMES DURING CONSTRUCTION.
12. CONTRACTOR SHALL REFER TO ALL DETAILS FOR PROPER GUIDANCE.
13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIPMENT SUBMITTALS FOR ALL PRODUCTS USED ON
PROJECT.
14. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR DEVIATIONS FROM THE REQUIREMENTS OF CONTRACT DOCUMENTS UNLESS THE CONTRACTOR HAS RECEIVED WRITTEN APPROVAL FROM THE ENGINEER TO THE SPECIFIC DEVIATION. THE ENGINEER'S APPROVAL OF SUBMITTAL DATA SHALL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR ERRORS OR OMISSIONS IN HIS
OR HER SUBMITTAL DATA.
15. THE CONTRACTOR IS REQUIRED TO SUBMIT THREE COMPLETE O&M MANUALS IN THREE RING BINDERS AT SUBSTANTIAL COMPLETION. MANUALS SHALL INCLUDE INSTALLATION AND MAINTENANCE DATA ON ALL NEW EQUIPMENT AND MATERIALS, CERTIFIED TECHNICAL PRODUCT DATA, EQUIPMENT SHOP DRAWINGS, SPARE PARTS
DATA, ETC. PROVIDE AN INDEX AND ASSOCIATED DIVIDERS.
16. CLOSE OUT DOCUMENTS: THE CONTRACTOR IS TO MAINTAIN ONE SET OF CONSTRUCTION DRAWINGS ON SITE AND KEEP CURRENT WITH MARK UP AS-BUILT CONDITIONS DURING CONSTRUCTION OF THE PROJECT. THIS SET IS TO INCLUDE ALL CONTRACT CHANGES, MODIFICATIONS AND CLARIFICATIONS. THIS SET ALONG WITH ALL SHOP DRAWINGS SHALL BE TURNED OVER TO THE ARCHITECT/ENGINEER AFTER CONSTRUCTION COMPLETION.
17. IT IS THE RESPONSIBILITY OF ALL BIDDERS TO THOROUGHLY REVIEW AND UNDERSTAND ALL CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO ALL DRAWINGS, SPECIFICATION SECTIONS, ETC. THE DRAWINGS ARE SCHEMATIC IN NATURE. THEREFORE BEFORE STARTING ANY WORK, THE CONTRACTOR SHALL REVIEW ALL OTHER CONSTRUCTION DOCUMENTS, VERIFY FIELD CONDITIONS AND SHALL MAKE ANY REQUIRED MINOR ADJUSTMENTS WITHOUT EXTRA COST TO THE OWNER. ANY MAJOR DISCREPANCIES FOUND SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE BASE BID SHALL REFLECT THE TOTAL COST OF NEW EQUIPMENT INSTALLATION. THIS INCLUDES LABOR, EQUIPMENT AND MATERIALS. NO CHANGE ORDERS SHALL
BE ISSUED WITHOUT WRITTEN CONSENT AND APPROVAL FROM ENGINEER AND ARCHITECT.
(E) EXISTING
AFF ABOVE FINISHED FLOOR
BFF BELOW FINISHED FLOOR
CO PIPE CLEAN OUT
CP CIRCULATOR PUMP
CTE CONNECT TO EXISTING
DCW DOMESTIC COLD WATER
DEMO DEMOLISH OR DEMOLITION
DFU DRAINAGE FIXTURE UNITS
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
(E) EXISTING
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FS FLOOR SINK
GCO GRADE CLEAN OUT
GPM GALLONS PER MINUTE
HD HUB DRAIN
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
HX HEAT EXCHANGER
IB ICE MAKER OUTLET BOX
IBC INTERNATIONAL BUILDING CODE
LAV LAVATORY
MS MOP SINK
NC NORMALLY CLOSED
NO NORMALLY OPEN
OD OVERFLOW ROOF DRAIN
OSD OVERFLOW (SECONDARY) STORM WATER DRAIN
PSD PRIMARY STORM WATER DRAIN
RD ROOF DRAIN
S SINK
SAN SANITARY
SH SHOWER
SP SUMP PUMP
TWH TANKLESS WATER HEATER
UR URINAL
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEAN OUT
WH WALL HYDRANT
WSFU WATER SUPPLY FIXTURE UNITS
ABBREVIATIONS
PLUMBING NOTES
1. REVIEW PLANS OF ALL TRADES PRIOR TO BIDDING AND BEGINNING WORK. INSTALLATIONS ARE TO INCLUDE ALL
PLUMBING FOR COMPLETE SYSTEMS SHOWN ON THE PLANS AND AS REQUIRED.
2. COORDINATE WITH OTHER TRADES TO PREVENT INTERFERENCE WITH HVAC DUCTS, STRUCTURE, ELECTRICAL, LIGHTING, AND OTHER PIPING IN THE CEILING SPACE AND PROVIDE COORDINATION DRAWINGS PRIOR TO CONSTRUCTION. VENT PIPING AND WATER PIPING SHALL BE HELD EITHER ABOVE OR BELOW HVAC DUCTWORK, AS
COORDINATED WITH THE HVAC CONTRACTOR.
3. ALL CHANGES SHALL BE REVIEWED BY THE ARCHITECT.
4. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING-IN PLUMBING FIXTURES AND EQUIPMENT
SUPPLIES.
5. THE PLUMBING SUBCONTRACTOR SHALL FURNISH AND INSTALL ALL PLUMBING FIXTURES, UNLESS NOTED
OTHERWISE.
6. VERIFY MOUNTING HEIGHT AND WATER CONNECTION SIZES OF ALL PLUMBING FIXTURES PRIOR TO ROUGH-IN.
FURNISH CUT-OUT TEMPLATES, FOR PLUMBING FIXTURES TO BE INSTALLED IN MILLWORK, TO THE GENERAL
CONTRACTOR.
7. MAKE PROPER HOT AND COLD WATER, WASTE AND VENT PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT
EVEN THOUGH ALL FITTINGS AND CONNECTIONS ARE NOT SHOWN ON DRAWINGS.
8. VERIFY LOCATION OF WATER SERVICE AND THE LOCATION/INVERTS OF SANITARY PIPING PRIOR TO INSTALLATION.
9. CUT AND PATCH CONCRETE AS REQUIRED.
10. IT IS NOT THE INTENT OF THESE DRAWINGS TO COVER ALL WORK AND MATERIAL. ANY EQUIPMENT, PLUMBING FIXTURE, TRIM HARDWARE AND/OR DEVICES USUALLY UTILIZED IN THE CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS DETERMINED BY THE ARCHITECT) SHALL BE FURNISHED AND
INSTALLED BY THE CONTRACTOR AS PART OF HIS TOTAL WORK.
11. THE EQUIPMENT ROUGH-IN ITEMS AND THEIR DIMENSIONED LOCATIONS FOR ALL CONNECTIONS ARE ACCURATE TO THE BEST OF OUR KNOWLEDGE. IN SOME INSTANCES THE OWNER OR SUPPLIER MAY MAKE SUBSTITUTIONS OR EQUIPMENT ITEMS MAY VARY FROM WHAT IS SHOWN. THEREFORE, THESE ITEMS AND DIMENSIONS SHALL BE VERIFIED WITH THE EQUIPMENT SUPPLIER, OWNER AND/OR EQUIPMENT ROUGH-IN DRAWING. FAILURE OF THE APPROPRIATE CONTRACTOR TO VERIFY ROUGH-INS OR THEIR LOCATIONS SHALL PLACE THE RESPONSIBILITY FOR ANY SUBSEQUENT RELOCATION AND/OR ADDITIONAL ROUGH-INS DIRECTLY UPON THAT CONTRACTOR.
12. CONTRACTOR SHALL SUPPLY TO THE ARCHITECT/ENGINEER THE REQUIRED COPIES OF SHOP DRAWINGS FOR APPROVAL SO THE QUALITY OF INTENDED MATERIALS OR EQUIPMENT CAN BE REVIEWED BEFORE INSTALLATION.
THERE WILL BE NO INSTALLATION UNTIL SHOP DRAWINGS HAVE BEEN SUBMITTED AND REVIEWED BY THE
ARCHITECT/ENGINEER.
13. DO NOT SCALE THIS DRAWING. REFER TO ARCHITECTURAL FLOOR PLAN FOR BUILDING DIMENSIONS.
14. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW ALL ELBOWS, OFFSETS, UNIONS, VALVES, FITTINGS, ETC. REQUIRED TO COMPLETE THE INSTALLATION OF THE WORK. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR HAS FAMILIARIZED HIMSELF WITH THE PLANS AND BUILDING SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY COULD HAVE BEEN FORESEEN HAD PROPER
EXAMINATION BEEN MADE.
15. VERIFY SERVICE POINTS AND METERING LOCATIONS FOR PROJECTS WITH LOCAL UTILITIES AND/OR LANDLORD
(DOMESTIC WATER, SANITARY SEWER, GAS, ETC.).
16. THE CONTRACTOR SHALL COOPERATE FULLY AMONG ALL TRADES.
17. ALL ROOF PENETRATIONS FOR ROOF DRAINS AND PLUMBING, GAS, AND REFRIGERANT PIPING SHALL BE MADE IN ACCORDANCE WITH ROOF SYSTEM MANUFACTURER'S GUIDELINES. COORDINATE WITH ARCHITECTURAL DETAILS
AND/OR MANUFACTURER FOR ROOF SYSTEM USED.
18. ALL PLUMBING VENTS IN EXTERIOR WALLS SHALL BE OFFSET A MINIMUM OF 3'-0" BEFORE ROOF PENETRATION.
19. INSTALL INSULATION PER SPECIFICATION ON ALL ROOF LEADERS ABOVE CEILING.
20. THE POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACKFLOW AND SIPHONAGE, BOTH NATURAL AND INDUCED. ALL EQUIPMENT CONNECTED TO THE POTABLE WATER SYSTEM BEING CAPABLE OF POLLUTING OR CONTAMINATING THE POTABLE WATER DISTRIBUTION SYSTEM OR ANY PART THEREOF BY MEANS OF A REVERSAL OF FLOW, PRESSURE DROP, PRESSURE LOSS, INDUCED VACUUM, OR BY INJECTION BECAUSE OF ANY PRIMARY OR AUXILIARY PUMPING SYSTEM CONNECTED, MUST BE ISOLATED AND CONTAINED BY MEANS OF APPROVED BACKFLOW DEVICES, CHECK VALVES, AIR GAPS, OR VACUUM BREAKERS. PLUMBING CONTRACTOR SHALL FURNISH
AND INSTALL THESE DEVICES PER LOCAL CODE REQUIREMENTS.
21. THE WATER PIPING SYSTEM SHALL BE FLUSHED AND STERILIZED IN ACCORDANCE WITH LOCAL REGULATIONS.
22. HOT AND COLD WATER SUPPLY BRANCHES FOR ALL SYSTEMS HAVING QUICK CLOSING VALVES OF ANY TYPE SHALL HAVE WATER HAMMER ARRESTORS INSTALLED AT THE HIGH POINT ON THE END OF EACH BRANCH AND AS
REQUIRED.
23. ALL PIPES HANGING FROM SINGLE VERTICAL RODS / HANGERS SHALL NOT MOVE OR SWAY DURING OPERATION.
SUITABLE LATERAL SUPPORTS OR BRACING SHALL BE USED TO PREVENT SWAY OR MOVEMENT.
24. PROVIDE SHUTOFF BALL VALVES AND DIELECTRIC UNIONS FOR ALL EQUIPMENT HOT AND COLD WATER LINES.
PLUMBING CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. COORDINATE WITH EQUIPMENT
SUPPLIER FOR EXACT REQUIREMENTS.
25. VERIFY MOUNTING HEIGHTS OF ALL BARRIER FREE FIXTURES WITH ARCHITECTURAL PLANS.
26. PROVIDE COPPER INDIRECT WASTE PIPING REQUIRED FROM EQUIPMENT TO FLOOR DRAINS, OPEN RECEPTACLES, OR FLOOR SINKS. PIPING SHALL COMPLY WITH STATE AND LOCAL CODES. COORDINATE WITH ALL EQUIPMENT SUPPLIERS AND SIZES AS REQUIRED BY PIECE OF EQUIPMENT SERVED. HOLD PIPING TIGHT TO WALL WHERE APPLICABLE. PROPERLY SECURE AS REQUIRED. COORDINATE WITH CASEWORK SUPPLIER FOR MAXIMUM
CLEARANCE UNDER CABINETS.
27. PROVIDE CHROME PLATED ESCUTCHEONS AT ALL WALL PENETRATIONS.
28. INSTALL SANITARY, STORM, AND CONDENSATE PIPING WITH A MINIMUM SLOPE OF 1/8" PER FOOT UNLESS OTHERWISE REQUIRED. CONTRACTOR IS RESPONSIBLE FOR PROPER DRAINAGE OF ALL SYSTEMS.
29. ALL FLOOR DRAINS ARE TO BE PROVIDED WITH MINIMUM 3" DRAIN LINES, DEEP SEAL TRAPS, AND AUTOMATIC TRAP PRIMERS. TRAP PRIMERS SHALL BE LOCATED IN A SERVICEABLE LOCATION AND INSTALLED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. HOLD TOP OF FLOOR DRAINS FLUSH WITH FINISHED FLOOR; SEE ARCHITECTURAL
SHEETS FOR FLOOR SLOPES AND PROPER FINISHED FLOOR ELEVATION.
30. ALL VENT PIPE TO BE COMPATIBLE WITH STRUCTURE, MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT, AND LIGHTING. ALL VTR'S SHALL BE EXTENDED TO A MINIMUM OF 2" ABOVE PARAPET HEIGHT AND
MAINTAINED 10'-0" MINIMUM FROM ALL OUTSIDE AIR INTAKES.
31. MATERIALS, EQUIPMENT, ASSEMBLIES AND SYSTEMS SHALL MEET ALL PERTINENT REQUIREMENTS OF NATIONALLY RECOGNIZED TESTING ORGANIZATIONS SUCH AS UL, ASTM, ASSE, AWWE, AGA AND NFPA AS WELL AS THE MOST
CURRENT ADOPTED VERSION OF THE STATE AND LOCAL CODES.
32. ALL INSTALLED SYSTEMS, DEVICES AND RELATED ITEMS SHALL BE TESTED IN PLACE. REPLACE ANY AND ALL CONTRACTOR SUPPLIED DEFECTIVE DEVICES, ITEMS, OR SYSTEMS AT CONTRACTOR'S EXPENSE, BEFORE
COMPLETION OF PROJECT.
33. WHERE JOB CONDITIONS REQUIRE CHANGES FROM THE CONTRACT DOCUMENTS THAT DO NOT CHANGE THE SCOPE OR NATURE OF WORK REQUIRED, THE CONTRACTOR SHALL MAKE SUCH CHANGES WITHOUT ADDITIONAL COST TO THE OWNER. NO OTHER CHANGES MAY BE MADE WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.
34. ALL EQUIPMENT, FIXTURES AND MATERIALS SHALL BE NEW AND UNUSED, AND INSTALLED IN STRICT CONFORMANCE TO MANUFACTURER'S RECOMMENDATIONS (UNLESS OTHERWISE NOTED). PROVIDE COMPLETE WITH ALL TRIM, STOPS, HANGERS, CARRIERS, SUPPORTS, ETC., INCLUDING PROVISIONS FOR BARRIER FREE USE, IF REQUIRED. WHERE FIXTURES ARE ACCESSIBLE THEY MUST COMPLY WITH ALL FEDERAL ADA REGULATIONS.
35. CONTRACTOR SHALL GUARANTEE ALL WORK FOR WHICH MATERIALS ARE FURNISHED, FABRICATED, FIELD ERECTED, ALL FACTORY ASSEMBLED EQUIPMENT FOR WHICH NO SPECIFIC MANUFACTURER'S GUARANTEE IS FURNISHED, AND ALL WORK IN CONNECTION WITH INSTALLATION OF MANUFACTURER'S GUARANTEED EQUIPMENT.
THE CONTRACTOR'S GUARANTEE SHALL LAST ONE YEAR FROM THE FINAL OWNER ACCEPTANCE OF THE WORK
AND SHALL APPLY TO ALL DEFECTS IN MATERIALS AND WORKMANSHIP OF ANY KIND.
36. ALL FAUCET CONTROLS SHALL BE OPERABLE WITH ONE HAND AND NOT REQUIRE TIGHTGRASPING.
37. ALL BARRIER FREE WATER CLOSET CONTROLS SHALL BE LOCATED ON UNIT TOWARDS WIDE SIDE OF STALL.
VERIFY IF RIGHT OR LEFT SIDE LOCATION.
38. PENETRATIONS FOR PIPES, CONDUITS OR OTHER PURPOSES THROUGH ASSEMBLIES )FLOORS, ROOF, WALLS, PARTITIONS, ETC.) WITH A REQUIRED FIRE RESISTANCE RATING SHALL BE SEALED TO THE PENETRATING MEMBER IN AN APPROVED MANNER WHICH MAINTAINS THE REQUIRED FIRE RESISTANCE RATING OF THE ASSEMBLY.
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
(E)CW EXISTING COLD WATER
(E)SAN EXISTING SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
PLUMBING ACCESSORIES
FD-C:
FLOOR DRAIN - REFER TO SPECIFICATION FOR MORE INFORMATION.
FD-X:
FLOOR DRAIN - REFER TO SPECIFICATION FOR MORE INFORMATION.
FD-Z:
LINEAR SHOWER DRAIN, STAINLESS STEEL, 4 15/32" WIDE, REFER TO SPECIFICATIONS FOR MORE INFORMATION.
FCO:
FLOOR CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION
WCO:
WALL CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION
GCO:
GRADE CLEANOUT - REFER TO SPECIFICATIONS FOR MORE INFORMATION
RD:
ROOF DRAIN - 15" DIAMETER MAIN ROOF DRAIN LOW SILHOUETTE DOME (NO-HUB).
OD:
OVERFLOW (SECONDARY) ROOF DRAIN - 15" DIAMETER MAIN ROOF DRAIN LOW SILHOUETTE DOME (NO-HUB).
WATER MONITORING EQUIPMENT
THE SPECFIED WATER MONITORING EQUIPMENT SHALL BE REQUIRED AT THE FOLLOWING LOCATIONS:
TIE WATER MONITORING SYSTEM TO BAS
MAINS/RISERS
• CW/HW - MOST REMOTE LOCATION TEMPERATURE
BRANCH
• CW/HW - MOST REMOTE FIXTURE TEMPERATURE
RECIRCULATION
• TEMPERATURE AT END OF RETURN SYSTEM AND PRIOR TO MIXING.
• RECIRCULATION PUMP FLOW
SERVICE ENTRANCE
• CW - PROVIDE A PANEL MOUNTED SYSTEM (SAMPLER SKID) FOR AUTOMATIC MONITORING OF FREE OR TOTAL
CHLORINE RESIDUALS,PH, PRESSURE, DISSOLVED SOLIDS (CONDUCTIVITY), AND TEMPERATURE. THE SYSTEM MUST CONTINUOUSLY MONITOR THESE SENSORS AND MAKE THE DATA AVAILABLE SECURELY USING AND INTERNET CONNECTED DEVICE. THE TOTAL SYSTEM MUST BE PREWIRED AND PRE PLUMBED ON A SINGLE PANEL TO ENSURE HIGH QUALITY AND A SIMPLE INSTALLATION. PROVIDE PHIGENICS WME-1175 PWA ADVANCED
MONITORING SYSTEM 2.0 OR APPROVED EQUAL.
• HW - PROVIDE A PANEL MOUNTED SYSTEM (SAMPLER SKID) FOR AUTOMATIC MONITORING OF FREE OR TOTAL CHLORINE RESIDUALS,PH, PRESSURE, DISSOLVED SOLIDS (CONDUCTIVITY), AND TEMPERATURE. THE SYSTEM MUST CONTINUOUSLY MONITOR THESE SENSORS AND MAKE THE DATA AVAILABLE SECURELY USING AND INTERNET CONNECTED DEVICE. THE TOTAL SYSTEM MUST BE PREWIRED AND PRE PLUMBED ON A SINGLE PANEL TO ENSURE HIGH QUALITY AND A SIMPLE INSTALLATION. PROVIDE PHIGENICS WME-1175 PWA ADVANCED
MONITORING SYSTEM 2.0 OR APPROVED EQUAL. PROVIDE WITH SAMPLE COOLER.
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED
IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH
DEDUCTIVE ALTERNATE REFR TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).
DEDUCTIVE ALTERNATE #6 : REDUCE PLATFORM AT CHILLER.
DEDUCTIVE ALTERNATE NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:3
P
M
P-001
PLUMBING LEGENDS & NOTES
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS AK
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
DRAWING INDEX - PLUMBING
P-001 PLUMBING LEGENDS & NOTES
PL100 PLUMBING OVERALL FLOOR PLAN - BASEMENT
PL101 PLUMBING OVERALL FLOOR PLAN - LEVEL 1
PL101A SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA A
PL101B SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA B
PL102 PLUMBING OVERALL FLOOR PLAN - PENTHOUSE
PL201A DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA A
PL201B DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA B
PL401 PLUMBING ENLARGED FLOOR PLAN
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-503 PLUMBING SCHEMATIC
P-601 SANITARY & VENT ISOMETRICS - LEVEL 1 - AREA A
P-602 SANITARY & VENT ISOMETRICS - LEVEL 1 - AREA B
P-603 DOMESTIC WATER ISOMETRICS - LEVEL 1 - AREA A
P-604 DOMESTIC WATER ISOMETRICS - LEVEL 1 - AREA B
PLUMBING FIXTURE SCHEDULE
FIXTURE
MARK FIXTURE
COUNT
FIXTURE DESCRIPTION
ROUGH-IN PIPE SIZES FIXTURE UNITS
COLD
WATER
SUPPLY
HOT
WATER
SUPPLY
FIXTURE
TRAP
FIXTURE
DRAIN
COLD
WATER
HOT
WATER
DRAINAGE
P-107
3 WATER CLOSET, BARRIER FREE - BACK OUTLET, WALL
MOUNTED, ELONGATED RIM, 1-1/2" TOP SPUD, MANUAL
FLUSH VALVE, 1.28 GPF, VITREOUS CHINA, VACUUM
BREAKER; OPEN FRONT SEAT LESS COVER, STAINLESS
STEEL CHECK HINGE. RIM: 17". FIXTURE SHALL BE EPA
WATER SENSE LABELED WATER CONSERVING PRODUCT.
REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
1" N/A 4" 4" 10 0 4
P-114
28 WATER CLOSET, BARRIER FREE - BACK OUTLET, WALL
MOUNTED, ELONGATED RIM, 1-1/2" TOP SPUD, MANUAL
FLUSH VALVE, 1.28 GPF, VITREOUS CHINA, VACUUM
BREAKER; OPEN FRONT SEAT LESS COVER, STAINLESS
STEEL CHECK HINGE. RIM: 17". FIXTURE SHALL BE EPA
WATER SENSE LABELED WATER CONSERVING PRODUCT.
REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
1" N/A 4" 4" 10 0 4
P-417
29 LAVATORY - INTEGRAL TO COUNTERTOP, LAVATORY
PROVIDED BY MILLWORK CONTRACTOR, FAUCET HOLES
AS REQUIRED. REFER TO ARCHITECTURAL DETAIL D7 ON
SHEET A-401 FOR COUNTERTOP INFORMATION. PLUBMING
CONTRACTOR TO PROVIDE RIGID GOOSENECK SPOUT
WITH WRIST BLADE HANDLES FAUCET WITH ASSE 1070
COMPLIANT THERMOSTATIC ANTI-SCALD VALVE (SEE
DETAIL 1 ON SHEET P-502), 1/2 GPM, LEAD FREE, DECK
MOUNTED. PROVIDE COVER PLATES, GRID DRAIN
ASSEMBLY, P-TRAP, STOPS, SUPPLIES, ETC., FOR A
COMPLETE INSTALLATION. FIXTURE SHALL BE EPA WATER
SENSE LABELED WATER CONSERVING PRODUCT. REFER
TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1/2" 1/2" 1 1/4" 2" 0.5 0.5 1
P-418
8 LAVATORY - BARRIER FREE, WALL HUNG. PROVIDE
CONCEALED ARM SUPPORT CARRIER. PROVIDE
SELF-POWERED, SENSOR OPERATED, 0.5 GPM, ADA
COMPLIANT, SINGLE HOLE, DECK MOUNTED FAUCET:
TOTO TEL105-D10E OR EQUAL. PROVIDE WITH ASSE 1070
THERMOSTATIC ANTI-SCALD VALVE. TOP OF RIM 34" FROM
FINISHED FLOOR. PROVIDE COVER PLATES, PERFORATED
STRAINER, P-TRAP, STOPS, SUPPLIES, ETC. FOR A
COMPLETE INSTALLATION. PROVIDE ADA COMPLIANT
PROTECTIVE PIPING COVERS FOR EXPOSED SUPPLIES,
TRAP, AND DRAIN PIPING. FIXTURE SHALL BE EPA WATER
SENSE LABELED WATER CONSERVING PRODUCT. REFER
TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1/2" 1/2" 1 1/4" 2" 0.5 0.5 1
P-501
2 SERVICE SINK . REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
1/2" 1/2" 3" 3" 2.25 2.25 2
P-505
2 CLINICAL SINK - FLOOR MOUNTED, PROVIDE WITH
SERVICE SINK FAUCET AND FLUSH VALVE, REFER TO
P-505FV BELOW FOR ADDITIONAL INFORMATION
REGARDING THE FLUSHVALVE. PROVIDE WITH ASSE 1070
THERMOSTATIC ANTI-SCALD VALVE. REFER TO
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
1/2" 1/2" 4" 4" 1 1 2
P-505FV
2 CLINICAL SINK FLUSH VALVE - REFER TO SPECIFICATION
FOR ADDITIONAL INFORMATION.
1" N/A 4" 4" 10 0 4
P-516
1 SINK - SALON HAIR WASHING. HIGH PORCELAIN WALL
MOUNTED SHAMPOO BOWL FOR HAIR WASHING. PROVIDE
WITH SPRAY NOZZLE WITH HOSE, STRAINER, AND ASSE
1070 ANTI-SCALD VALVE. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
1/2" 1/2" 1 1/4" 2" 0.5 0.5 1
P-524
7 TWO COMPARTMENT SINK - 29X22" STAINLESS STEEL TWO
COMPARTMENT SINK, SELF RIMMING, 7-3/4" DEEP, 3
FAUCET HOLES. BASKET STRAINER NO. LK35 GRID DRAIN.
WRIST BLADE FAUCET - ELKAY MODEL LK810HA08T4, 4"
WRISTBLADE HANDLES WITH 8" RIGID GOOSENECK SPOUT,
AERATOR, DRAIN BASKET AND STRAINER. PROVIDE WITH
ASSE 1070 ANTI-SCALD VALVE. PROVIDE STOPS,
SUPPLIES, TRAP, ETC., TO COMPLETE INSTALLATION.
1/2" 1/2" 1 1/2" 2" 1 1 1.4
P-528
2 SINK - SINGLE COMPARTMENT, STAINLESS STEEL.
PROVIDE WITH ASSE 1070 ANTI-SCALD VALVE.
1/2" 1/2" 1 1/4" 2" 0.5 0.5 1
P-701
30 SHOWER - ADA COMPLIANT, SHOWER SYSTEM WITH
SHOWER HEAD AND SINGLE LEVER HANDLE,
PRESSURE-BALANCED THERMOSTATIC ANTI-SCALD
VALVE, WITH INTEGRAL SERVICE STOPS, 1.5 GPM.
PROVIDE SHOWER FLOOR DRAIN KOHLER K-9132 OR
EQUAL, CHROME PLATED BRASS, WITH 4 3/8" ROUND
STRAINER, AND 2" OUTLET. PROVIDE STOPS, SUPPLIES,
TRAP, ETC. FOR A COMPLETE INSTALLATION. FIXTURE
SHALL BE EPA WATER SENSE LABELED WATER
CONSERVING PRODUCT. REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
1/2" 1/2" 2" 2" 3 3 2
P-708
4 EMERGENCY EYE AND FACE WASH, WALL MOUNTED,
PROVIDE WITH ASSE 1071 THERMOSTATIC ANTI-SCALD
VALVE.
1/2" 1/2" 1 1/2" 2" 1 1 2
P-801
10 WALL HYDRANT, NON-FREEZE - ZURN NO. Z-1330-C,
ENCASED FLUSH WALL HYDRANT, NICKEL BRONZE BOX
AND HINGE COVER WITH OPERATING CYLINDER LOCK AND
"WATER" CAST ON COVER. 3/4" CW.
3/4" N/A N/A N/A 5 0 0
P-802
1 LAWN FAUCET, NON-FREEZE – BRASS FAUCET WITH
DETACHABLE WHEEL OR T-HANDLE. REFER TO
SPECIFICATION FOR MORE INFORMATION.
3/4" N/A N/A N/A 2 0 0
P-812
5 WATER SUPPLY BOX UNIT (ICE MAKER) WITH BALL TYPE
SHUT OFF VALVE.
1/2" N/A N/A N/A 0.25 0 0
CIRCULATOR PUMP SCHEDULE
MARK CAPACITY TOTAL HEAD
SHUTOFF
HEAD
MOTOR
POWER
ELECTRICAL DATA
MANUFACTURER
MODEL
NUMBERVOLTAGE PHASE
CP-1 4 GPM 7 ftH2O 11 ftH2O 0.125 hp 115 V 1 TACO 0010-SF3
CP-2 4 GPM 7 ftH2O 11 ftH2O 0.125 hp 115 V 1 TACO 0010-SF3
NOTES:
1. PUMPS SHALL OPERATE ONE AT A TIME. IF 1 PUMP FAILS, THE OTHER WILL AUTOMATICALLY TURN ON. PUMPS SHALL ALTERNATE BASED ON A SCHEDULE TO BE DETERMINED BY THE VA. PUMPS SHALL RUN CONTINUOUSLY.
Revisions: Date: 7/21/2021
STAMP
05/09/20225/09/2022
PL401
STORM PIPING
UP TO FLOOR
ABOVE.
P S
D
REFER TO CIVIL
PLANS FOR
CONTINUATION.
ROUTE NEW 3" DCW
PIPING FROM EXISTING
MAIN. REFER TO CIVIL
DRAWINGS FOR
CONTINUATION AND
COORDINATION.
ROUTE 6" SANITARY PIPE TO
EXISTING SANITARY MAIN.
INVERT ELEVATION 15'
BELOW FFE. REFER TO CIVIL
DRAWINGS FOR
CONTINUATION. TIE
SANITARY PIPE TO EXISTING
SANITARY MAIN PRIOR TO
SLAB POUR.
C W
8' - 10"
9' - 0"
DEDUCT
ALTERNATE 2
EAST TUNNEL
001A
EAST TUNNEL
001A
NORTH TUNNEL
001C
INVERT ELEVATION - 101.50"
BASEMENT
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
BB
7.86.6 7.1 7.6
AA
7.76.8
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.
D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT
LOCATED ABOVE LAY-IN CEILING.
E. DOMESTIC COLD, HOT, AND HOT WATER RETURN PIPING SHOWN
ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR CEILING
UNLESS NOTED OTHERWISE.
F. COORDINATE SHUTOFF VALVE ACCESS WITH SPRINKLER HEADS
LOCATIONS.
GENERAL NOTES
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).
REFER TO COVER SHEET GI000 FOR MORE INFORMATION ON
DEDUCTIVE ALTERNATIVES.
DEDUCTIVE ALTERNATE
N
KEY PLAN
BASEMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:4
P
M
PL100
PLUMBING OVERALL FLOOR PLAN - BASEMENT
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS NS/TR
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
3/32" = 1'-0"
PLUMBING OVERALL FLOOR PLAN - BASEMENT
KEYNOTES
1 DCW PIPE TO COLD WATER FILL LINE FOR HEATING HOT WATER
SYSTEM.
Revisions: Date: 7/21/2021
STAMP
PORCH-A
FOYER
RESIDENT 6
RESIDENT 9
TLT 9
127A
DINING
RESIDENT 11
SITTING ALCOVE
11/12A
RESIDENT 12
RESIDENT 13
ELEC
TLT 12
131A
TLT 13
133A
LN
SITTING ALCOVE
13/14A
RESIDENT 10
TLT 8
126A
RESIDENT 1
TLT 10
128A
SITTING ALCOVE
8/9/10A
TLT 11
130A
RESIDENT 14
TLT 14
134A
RESIDENT 4
TLT 6
119A
RESIDENT 5
TLT 4
117A
SITTING ALCOVE
4/5/6/7A
RESIDENT 3
SITTING ALCOVE
2/3A
RESIDENT 2
TLT 2
114A
TLT 3
115A
LOBBY
PANTRY
125A
DINING
RESIDENT 10
SITTING ALCOVE
10/11B
RESIDENT 11
RESIDENT 12
ELEC
HALLWAY
192C
TLT 11
178A
TLT 12
180A
LN
CLEAN
SITTING ALCOVE
12/13B
RESIDENT 9
TLT 9
173A
SITTING ALCOVE
6/7/8/9B
TLT 10
175A
RESIDENT 13
TLT 13
181A
RESIDENT 3
RESIDENT 14
TLT 3
162A
SITTING ALCOVE
3/4/5B
RESIDENT 2
SITTING ALCOVE
1/2B
RESIDENT 1
TLT 1
159A
TLT 2
160A
FAMILY TOILET
HAC
POWER
EMERGENCY
POWER
GAS
EXAM RM
STERILE SUPPLY
STORAGE
PT/KT
STORAGE
CENTRAL KITCHEN
ACTIVITY
CORRIDOR
164C
LN
LN
LN
LN
LN
LN
LN
LN
CORRIDOR
120C
MECHANICAL
LIVING ROOM
MAIN PORCH
IT CLOSET
PANTRY
168A
OFFICE
OFFICE
CONFERENCE
MEDS
CLEAN
SOILED
TLT 1
110A
TLT 14
183A
HOTELING
STAFF LOUNGE
OFFICE
ADMIN HALL-B
- CORRIDOR
162C
SOILED
MEDS
CRASH CART B
CHARGING B
CRASH CART
CHARGING A
SALON
WHEELCHAIR/
STRETCHER STRG
HALLWAY
209C
CLC WALKWAY
STAFF TOILET/
SHOWER
TLT 5
118A
RESIDENT 8
RESIDENT 5
RESIDENT 4
TLT 4
163A
TLT 8
172A
TLT 7
171A
RESIDENT 8
TLT 5
164A
LIVING ROOM
RESIDENT 7
SITTING ALCOVE
1A
CORRIDOR 1A
CORRIDOR
122C
CORRIDOR
163C
SITTING ALCOVE
14B
LN
RESIDENT 7
(BARIATRIC)
TLT 7
120A
HAC
PUBLIC TOILET
STORAGE
LN
169 RESIDENT 6
(BARIATRIC)
TLT 6
170A
STAIRS
144B
M A
T C
H
LI
N E
S
E : 1
/P L1
A
M A
T C
H
LI
E : 1
/P L1
B
M A
T C
H
LI
E : 1
/P L2
A
M A
T C
H
LI
E : 1
/P L2
B
PL101A
PL201A
PL201A
PL201B
PL101B
GCO
PORCH B
MATCHLINE
SEE: 2/PL201A
PL401
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.
D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT
LOCATED ABOVE LAY-IN CEILING.
E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE
FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING
SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR
CEILING UNLESS NOTED OTHERWISE.
GENERAL NOTES
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
N
KEY PLAN
AREA B
(EAST)
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:5
P
M
PL101
PLUMBING OVERALL FLOOR PLAN - LEVEL 1
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS AK
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
3/32" = 1'-0"
PLUMBING OVERALL FLOOR PLAN - LEVEL 1
Revisions: Date: 7/21/2021
STAMP
P-114
P-417
P-114
P-417
FD-ZFD-Z
P-114
P-417
FD-Z
P-114 P-417
P-114 P-417
FD-Z
FD-Z
P-114
P-417
FD-Z
P-418
FOYER
RESIDENT 6
RESIDENT 9
TLT 9
127A
DINING
RESIDENT 11
SITTING ALCOVE
11/12A
RESIDENT 12
RESIDENT 13
ELEC
TLT 12
131A
TLT 13
133A
LN
SITTING ALCOVE
13/14A
RESIDENT 10
TLT 8
126A
RESIDENT 1
TLT 10
128A
SITTING ALCOVE
8/9/10A
TLT 11
130A
RESIDENT 14
TLT 14
134A
RESIDENT 4
TLT 6
119A
RESIDENT 5
TLT 4
117A
SITTING ALCOVE
4/5/6/7A
RESIDENT 3
SITTING ALCOVE
2/3A
RESIDENT 2
TLT 2
114A
TLT 3
115A
LOBBY
PANTRY
125A
RESIDENT 13
TLT 13
181A
RESIDENT 14
FAMILY TOILET
STERILE SUPPLY
STORAGE
PT/KT
STORAGE
CENTRAL KITCHEN
ACTIVITY
LN
LN
116 LN
LN
CORRIDOR
120C
MECHANICAL
PORCH-A
LIVING ROOM
MAIN PORCH
IT CLOSET
CONFERENCE
MEDS
CLEAN
SOILED
TLT 1
110A
TLT 14
183A
HOTELING
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CRASH CART
CHARGING A
SALON
WHEELCHAIR/
STRETCHER STRG
HALLWAY
209C
CLC WALKWAY
STAFF TOILET/
SHOWER
TLT 5
118A
RESIDENT 8
SITTING ALCOVE
1A
CORRIDOR 1A
CORRIDOR
122C
SITTING ALCOVE
14B
RESIDENT 7
(BARIATRIC)
TLT 7
120A
HAC
PUBLIC TOILET
STORAGE
P-114 P-417
FD-Z
P-114
FD-Z
P-417
GCO
3" VTR
2" VTR
3" VTR
M A
T C
H
LI
E : 1
/P L1
B
P-505
P-418 P-708
P-418
P-107
P-524
P-114
FD-Z
P-417P-417
P-114
FD-Z
P-516
P-528
P-708
P-501
P-524
P-812
P-418 P-107
P-107
P-418
P-524
FD-ZFD-Z
P-114 P-114
P-417P-417
FD-Z
P-114
P-417 P-417
P-114
FD-Z
P-417 P-417
P-114 P-114
FD-Z FD-Z
FD-Z
P-524
P-528
3" VTR
3" VTR
3" SAN
UP TO FIXTURE
ON FLOOR
ABOVE.
3" SAN
4" SAN
FCO
FCO
WCOWCO
WCO
WCO WCO WCO
WCO
M A
T C
H
LI
E : 1
/P L1
B
WCO
CO
WCO
WCO
WCO
WCO
FD-C
FD-C
FD-C
FD-C
FD-C FD-C FD-C
FD-C
FD-C
FD-CFD-C FD-C FD-C FD-C
FD-C
WCO
WCO
WCO
SCREENING
VESTIBULE
3 3
3 3
SITTING ALCOVE
14B
4" SAN
2" VENT
2" VENT
STORAGE
4" SAN
3" SAN
2" SAN
2" SAN
3" SAN
4" SAN
4" SAN 4" SAN
2" SAN
FD-S
FD-S FD-S
FD-E
4" SAN
4" PSD
6" OSD
1 1/2" VENT2" VENT2" VENT
4" SAN
2" VENT
4" SAN
4" SAN
4" SAN
4" SAN
2" VENT
4" SAN
6" SAN
4" SAN
2" VENT
4" SAN 4" SAN
6" OSD
6" OSD
4" PSD
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
FCO
WCO
WCO
WCO
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.
D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT
LOCATED ABOVE LAY-IN CEILING.
E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE
FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING
SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR
CEILING UNLESS NOTED OTHERWISE.
GENERAL NOTES
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
N
KEY PLAN
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:0
P
M
PL101A
SANITARY AND VENT FLOOR PLAN - LEVEL 1 -
AREA A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS AK
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA A
KEYNOTES
1 PROVIDE FLEXIBLE JOINT IN PIPING AT EXPANSION JOINT
CROSSING.
2 STORM DRAIN PIPING RD-1 AND OD-1 FROM FLOOR ABOVE.
3 VENT PIPING OVERLAY SANITARY LINE WORK. REFER TO
ISOMETRICS FOR ADDITIONAL INFORMATION.
4 ROUTE 6" SANITARY PIPE TO EXISTING SANITARY MAIN. REFER TO
CIVIL DRAWINGS FOR CONTINUATION.
5 REFER TO CIVIL DRAWINGS FOR CONTINUATION.REFER TO DETAIL
T/S-201 FOR FOOTING AND FOR PENETRATION REFER TO DETAIL
F/S-202.
6 VENT PIPE CONTINUED THROUGH PLENUM SPACE ABOVE TO VTR.
REFER TO PL102 FOR CONTINUATION.
Revisions: Date: 7/21/2021
STAMP
P-418
P-524
P-417
P-417
FD-Z
DINING
RESIDENT 10
SITTING ALCOVE
10/11B
RESIDENT 11
RESIDENT 12
ELEC
HALLWAY
192C
TLT 11
178A
TLT 12
180A
LN
CLEAN
SITTING ALCOVE
12/13B
RESIDENT 9
TLT 9
173A
SITTING ALCOVE
6/7/8/9B
TLT 10
175A
RESIDENT 13
TLT 13
181A
RESIDENT 3
RESIDENT 14
TLT 3
162A
SITTING ALCOVE
3/4/5B
RESIDENT 2
SITTING ALCOVE
1/2B
RESIDENT 1
TLT 1
159A
TLT 2
160A
FAMILY TOILET
HAC
POWER
EMERGENCY
POWER
GAS
152EXAM RM
PT/KT
CORRIDOR
164CLN
LN
LN
LN
MAIN PORCH
PANTRY
168A
OFFICE
OFFICE
CONFERENCE
TLT 14
183A
HOTELING
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CORRIDOR
162C
SOILED
MEDS
CRASH CART B
CHARGING B
STAFF TOILET/
SHOWER
RESIDENT 5
RESIDENT 4
TLT 4
163A
TLT 8
172A
TLT 7
171A
RESIDENT 8
TLT 5
164A
LIVING ROOM
165 PORCH B
RESIDENT 7
CORRIDOR
163C
LN
RESIDENT 6
(BARIATRIC)
TLT 6
170A
3" VTR
M A
T C
H
LI
E : 1
/P L1
A
P-418
P-107
P-418
P-501
P-418
P-417
P-114
FD-Z
P-114
P-417P-417
P-114
FD-Z
FD-Z
P-417 P-114
P-417 P-114 FD-Z
P-708
P-418
P-505
P-708
FD-ZFD-Z
P-114 P-114
P-417P-417
P-114 P-114
P-417P-417
FD-Z FD-Z
P-417 P-417
P-114 P-114
FD-Z FD-Z
P-114
FD-Z
P-114
P-417
P-114
FD-Z
FD-Z
P-524
P-528
FD-Z
P-524
3" VTR
3" VTR
3" VTR
FCO
WCO
WCO
WCO
WCOWCO
M A
T C
H
LI
E : 1
/P L1
A
CO
WCO
WCO
WCO
WCO
WCO
FD-C
FD-C
FD-C FD-C FD-C FD-C
FD-C
FD-C
FD-C
FD-C FD-CFD-C
WCO
WCO
WCO
WCO
2 2 2
SITTING ALCOVE
14B
STORAGE
2" SAN
3" SAN
4" SAN
2" SAN
FD-S
FD-S
2" VENT
4" SAN
4" SAN
4" PSD
6" OSD
4" SAN
2" VENT
4" SAN
2" VENT
2" VENT
2" VENT1 1/2" VENT
1 1/2" VENT
6" OSD
4" PSD
44 4
7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
8.6
AA
WCO
FD-C
FD-C
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.
D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT
LOCATED ABOVE LAY-IN CEILING.
E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE
FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING
SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR
CEILING UNLESS NOTED OTHERWISE.
GENERAL NOTES
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
N
KEY PLAN
AREA B
(EAST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:0
P
M
PL101B
SANITARY AND VENT FLOOR PLAN - LEVEL 1 -
AREA B
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS AK
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
SANITARY AND VENT FLOOR PLAN - LEVEL 1 - AREA B
KEYNOTES
1 STORM DRAIN PIPING RD-1 AND OD-1 FROM FLOOR ABOVE.
2 VENT PIPING OVERLAY SANITARY LINE WORK. REFER TO
ISOMETRICS FOR ADDITIONAL INFORMATION.
3 REFER TO CIVIL DRAWINGS FOR CONTINUATION.REFER TO DETAIL
T/S-201 FOR FOOTING AND FOR PENETRATION REFER TO DETAIL
F/S-202.
4 VENT PIPE CONTINUED THROUGH PLENUM SPACE ABOVE TO VTR.
REFER TO PL102 FOR CONTINUATION.
Revisions: Date: 7/21/2021
STAMP
B F
P
MECH
PENTHOUSE
FD-X
FD-X
2-AH02
2-AH01
RD-1
CH-1
CH-2
EF-01 EF-02
DSSO-01
OD-1
2-CSG01
CWP-1
CWP-2
2" VTR
3" VTR
3" VTR
2" VTR
2" VTR
3" VTR
3" VTR
3" VTR
3" VTR
3" VTR
STAIRS
201A
CHILLERS
201B
PIPE TO
CEILING OF
FLOOR BELOW
DEDUCT
ALTERNATE
#7
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
P-801 P-802
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.
D. PROVIDE ACCESS PANELS AS REQUIRED FOR ALL VALVES NOT
LOCATED ABOVE LAY-IN CEILING.
E. SANITARY PIPING SHOWN ON THIS PLAN IS LOCATED BENEATH THE
FIRST FLOOR SLAB UNLESS NOTED OTHERWISE. VENT PIPING
SHOWN ON THIS PLAN IS LOCATED ABOVE THE FIRST FLOOR
CEILING UNLESS NOTED OTHERWISE.
F. DOMESTIC COLD, HOT AND HOT WATER RETURN PIPING SHOWN
ON THIS PLAN IS LOCATED BELOW THE PENTHOUSE FLOOR SLAB
UNLESS NOTED OTHERWISE.
GENERAL NOTES
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED
IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH
DEDUCTIVE ALTERNATE REFR TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #7 : REDUCE PLATFORM AT CHILLER
DEDUCTIVE ALTERNATE NOTES
N
KEY PLAN
LEVEL 2
PENTHOUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:4
P
M
PL102
PLUMBING OVERALL FLOOR PLAN - PENTHOUSE
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 NPS AK
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
3/32" = 1'-0"
PLUMBING OVERALL FLOOR PLAN - PENTHOUSE
KEYNOTES
1 DCW PIPE TO COLD WATER FILL LINE FOR CHILLED WATER SYSTEM.
2 DCW PIPE TO WATER TREATMENT SYSTEM WHICH SERVES THE
CLEAN STEAM GENERATOR. PROVIDE BACKFLOW PREVENTOR.
Revisions: Date: 7/21/2021
STAMP
FOYER
RESIDENT 6
RESIDENT 9
TLT 9
127A
DINING
RESIDENT 11
SITTING ALCOVE
11/12A
RESIDENT 12
RESIDENT 13
ELEC
TLT 12
131A
TLT 13
133A
LN
SITTING ALCOVE
13/14A
RESIDENT 10
TLT 8
126A
RESIDENT 1
TLT 10
128A
SITTING ALCOVE
8/9/10A
TLT 11
130A
RESIDENT 14
TLT 14
134A
RESIDENT 4
TLT 6
119A
RESIDENT 5
TLT 4
117A
SITTING ALCOVE
4/5/6/7A
RESIDENT 3
SITTING ALCOVE
2/3A
RESIDENT 2
TLT 2
114A
TLT 3
115A
LOBBY
PANTRY
125A
RESIDENT 13
TLT 13
181A
RESIDENT 14
FAMILY TOILET
STERILE SUPPLY
STORAGE
PT/KT
STORAGE
CENTRAL KITCHEN
ACTIVITY
LN
LN
LN
111 LN
CORRIDOR
120C
MECHANICAL
PORCH-A
LIVING ROOM
MAIN PORCH
IT CLOSET
CONFERENCE
MEDS
CLEAN
SOILED
TLT 1
110A
TLT 14
183A
HOTELING
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CRASH CART
CHARGING A
SALON
WHEELCHAIR/
STRETCHER STRG
HALLWAY
209C
CLC WALKWAY
STAFF TOILET/
SHOWER
TLT 5
118A
RESIDENT 8
SITTING ALCOVE
1A
CORRIDOR 1A
CORRIDOR
122C
SITTING ALCOVE
14B
RESIDENT 7
(BARIATRIC)
TLT 7
120A
HAC
PUBLIC TOILET
STORAGE
M A
T C
H
LI
E : 1
/P L2
B
P-701
P-114
P-417 P-417
P-114
P-701
P-417
P-701
P-701 P-114 P-417
P-417P-114
P-701 P-114
P-418
P-114
P-701
P-114
P-417 P-417
P-114
P-524
P-107
P-107
P-418
P-418
P-524
P-701
P-114
P-417P-417
P-114
P-701
P-114
P-417P-417
P-114
P-701
P-114
P-417P-417
P-114
P-528
P-528
P-501
P-418
P-708
P-708
P-418
P-516
P-417
P-114
P-701
P-701
P-417
P-417P-114 P-701
P-524
P-505
P-107 P-524
WCO 1 1/4" CW
3/4" HW
P-701
P-701 P-701 P-701
P-701
M A
T C
H
LI
E : 1
/P L2
B
CORR
STAIRS
144B
SCREENING
VESTIBULE
1" HWR
5 5
P-812
P-812
P-812
MATCHLINE
SEE: 2/PL201A
1 1/2" HW
2 1/2" CW
1 1/2" HW
2 1/2" CW
2" HW
2 1/2" CW
2 1/2" CW
1 1/2" HW
1 1/4" HW
2 1/2" CW
2 1/2" CW
1 1/4" HW
1 1/2" CW
1" HW
1" HWR
2" HW
2 1/2" CW
1" HW
2" CW
1" HWR
2 1/2" CW
1 1/2" HW
3/4" CW
3" CW
1 1/2" HW
1" HW
1" HWR
3/4" CW
1 1/2" CW
1" HW
1" HWR
1" HWR
1" HWR
1 1/4" CW
1 1/4" CW
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
P-801
P-801
P-801
P-801
P-801
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
RESIDENT 14
TLT 14
134A
LN
MECHANICAL
CLC WALKWAY
B6 WALKWAY
P-701
P-417
P-114
3" CW
1 1/2" HW
STAIRS
144B
MATCHLINE
SEE: 1/PL201A
7 7.2 7.5
G.2
G.3
F
E.4
E.2
E
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
N
KEY PLAN
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:5
P
M
PL201A
DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA
A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
DOMESTIC WATER FLOOR PLAN - LEVEL 1 - AREA A
1/8" = 1'-0"
DOMESTIC WATER FLOOR PLAN - LEVEL 1 - COVERED WALKWAY
KEYNOTES
1 2" DCW, 2" DHW, 1" HWR DOWN TO HOT WATER HEAT EXCHANGERS
IN MECHANICAL ROOM.
2 PROVIDE FLEXIBLE JOINT IN PIPING AT EXPANSION JOINT
CROSSING.
3 3"DCW PIPING IN THE STEAM TUNNEL.
4 ROUTE NEW 3" DCW PIPING FROM EXISTING MAIN. REFER TO CIVIL
DRAWINGS FOR CONTINUATION AND COORDINATION.
5 PROVIDE WITH ASSE 1070 THERMOSTATIC ANYI-SCALD MIXING
VALVE PER DETAIL 1 ON SHEET P-502.
6 PROVIDE WITH ASSE 1071 THERMOSTATIC ANYI-SCALD MIXING
VALVE PER DETAIL 1 ON SHEET P-502.
7 ROUTE 3/4" DCW PIING TO WALL HYDRANT IN ATTIC SPACE.
8 ROUTE 3/4" DCW, DHW PIPING DOWN TO PLUMBING FIXTURES.
9 ROUTE PIPING TIGHT TO WALL, PAINT TO MATCH WALL.
10 1/2" DCW CONNECTION FOR COFFEE MAKER, COORDINATE EXACT
LOCATION.
Revisions: Date: 7/21/2021
STAMP
DRAWING KEYNOTE#
EQUIPMENT MARK
POINT OF NEW CONNECTION
POINT OF CONNECTION TO CIVIL
CW COLD WATER PIPING
HW HOT WATER PIPING
HWR HOT WATER RETURN PIPING
SAN SANITARY PIPING
V SANITARY VENT PIPING
PIPE UP
PIPE DOWN
GCO GRADE CLEAN OUT (1-WAY OR 2-WAY)OR
OR VTR VENT THRU ROOF
WCO WALL CLEAN OUT
FCO FLOOR CLEAN OUT (1-WAY OR 2-WAY)OR
PIPE CAP
WCO
FLOOR DRAIN
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
PLUG VALVE
STRAINER
UNION
PRESSURE RELIEF VALVEPRV
BACKFLOW PREVENTER
PLUMBING LEGEND
FD
P-XXX
A. ALL SERVICE INTERUPTIONS TO THIS FACILITY MUST BE
SCHEDULED AT LEAST 3 WEEKS IN ADVANCE AND BE KEPT TO A
MINIMUM. COORDINATE ALL DISRUPTIVE WORK AND OUTAGE
REQUIREMENTS WITH THE COR.
B. EXISTING PIPE ROUTING SHOWN ON DRAWINGS ARE
APPROXIMATE LOCATIONS AND FOR REFERENCE ONLY. FIELD
VERIFY AND COORDINATE WITH EXACT LOCATIONS, ELEVATIONS,
SIZES, AND CONDITIONS OF EXISTING COMPONENTS.
C. CONTRACTOR TO FIELD VERIFY ALL CONNECTION POINTS TO
EXISTING SYSTEM PIPING AND IDENTIFY ALL RISERS AFFECTED.