This document provides details for a federal contract opportunity to construct a new community living center. The solicitation number is 36C77623R0156 for the project "Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334" issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity type is a solicitation for construction of a new community living center as part of minor construction at the Montrose VA medical center. The file attached is a set of drawings numbered 11 of 15 pertaining to required fire protection systems for the project. No further information is provided on response dates, pricing terms, or other contractual requirements.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEST DATA:
STATIC PRESSURE: PSI---
MEASURED FLOW: GPM1190
RESIDUAL PRESSURE: PSI50
DATE OF TEST: 10/24/2020
RESIDUAL HYDRANT LOCATION: ----
FLOW HYDRANT LOCATION: Hydrant #15
WATER FLOW TEST DATA
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE: SCALE:
NTS
NTS
NTS
NTS
NTS
NTS NTS
X X X
X X X
BOTTOM OF STRUCTURE
UPRIGHT SPRINKLER HEAD
REDUCER
1" NIPPLE
BRANCH LINE
CEILING
SPRINKLER HEAD
REDUCER
1" NIPPLE
BRANCH LINE
RECESSED PENDENT
SPRINKLER HEAD DETAIL
UPRIGHT SPRINKLER HEAD DETAIL
SPRINKLERS IN GRID CEILING SYSTEMS SHALL BE LOCATED AT THE
MIDPOINT OR QUARTERPOINT OF THE FOUR FOOT (4') DIMENSION AND
THE MIDPOINT OF THE TWO (2') DIMENSION. WHERE A CONFLICT
OCCURS, SYMMETRY ABOUT THE AXIS SHALL BE MAINTAINED.
E Q
E
Q
EQ.EQ.EQ.EQ.
E Q
E
Q
E Q
E
Q
EQ.EQ.
E Q
E
Q
.EQ. EQ.
E Q
E
Q
EQ. EQ.
SPRINKLER
SPEAKER OR
OTHER DEVICE
AIR DEVICE OR
LIGHT FIXTURE
CEILING LEGEND
SPRINKLER MOUNTING DETAIL
SWING ARM ASSEMBLY DETAIL
UNION WITH CORROSION
RESISTANT ORIFICE GIVING FLOW
EQUIVALENT TO THE SMALLEST
SPRINKLER ORIFICE IN THE
SYSTEM
TO DRAIN
SYSTEM RISER
AUXILIARY DRAIN
VALVE
SITE GLASS
INSPECTORS TEST VALVE
1" DRAIN LINE
PRESSURE GAUGE
WATER FLOW SWITCH
TO SPRINKLERS
INDICATING TYPE
FLOOR
CONTROL VALVE WITH
SUPERVISORY SWITCH
FIRE SPRINKLER ZONE
VALVE PIPING DETAIL
SYSTEM RISER
RISER FROM MAIN
WATER SUPPLY
FLOOR SLAB
RISER
TO FIRE
ALARM
SYSTEM
TAMPER SWITCH
APPROVED
NFPA-13
SUPERVISED
VALVE
TEE CONNECTION
WATER FLOW INDICATOR
TO FIRE ALARM SYSTEM
TO SPRINKLER SYSTEM
ALARM BELL
POWER BY DIV. 16
CONTROL WIRING BY
FA
CONTRACTOR
EXTERIOR WALL
CHECK VALVE
FROM FIRE
DEPARTMENT
CONNECTION
SPLASH
BLOCK
MAIN DRAIN (2" MIN.)
MAIN DRAIN VALVE
WET PIPE ALARM VALVE
WATER GAUGE (2 REQ'D)
FOR HEAD TYPES,
SEE FLOOR PLANS
AND HEAD
DETAILS
1" X 1/2" R.C.
DROP
90 EL.
ARMOVER (NOTE 1)
RISER NIPPLE
BRANCHLINE
SUSPENDED CEILING
NOTE:
1. PROVIDE HANGER FOR ARMOVERS
GREATER THAN 24" IN LENGTH.
ELBOW WITH CORROSION
RESISTANT OUTLET EQUAL
TO
ONE SPRINKLER
1" INSPECTOR TEST
PIPING, SEE PLAN FOR
CONTINUATION
1" TEST VA. IN ACCESSIBLE
LOCATION NOT OVER 7'
FOOT
ABOVE FLOOR
SPLASH BLOCK
SLEEVE
EXTERIOR WALL
PROVIDE SIGHT GLASS
FLOOR
INSPECTORS TEST
AND DRAIN DETAIL
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
SPACE TYPE
HAZARD
CLASSIFICATION
SYSTEM
TYPE
DISCHARGE
DENSITY
REMOTE
AREA
MAXIMUM
COVERAGE
AREA PER
SPRINKLER
MAXIMUM
SPACING
WATER
SUPPLY
DURATION
OUTSIDE
HOSE
ALLOWANCE TEMPERATURE
CLASSIFICATION
SPRINKLER TYPE NOTES
GPM/FT² FT² FT² FT. MINUTES GPM
GENERAL,
EXCEPT AS
LISTED BELOW
LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY
SEMI-RECESSED PENDENT, QUICK
RESPONSE, FACTORY MUTUAL
APPROVED, UL LISTED
STORAGE
ORDINARY
HAZARD
GROUP 2
WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY
SEMI-RECESSED PENDENT OR
UPRIGHT, QUICK RESPONSE,
FACTORY MUTUAL APPROVED,
UL LISTED
EQUIPMENT
ROOM
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE
QUICK RESPONSE
UPRIGHT, FACTORY MUTUAL
APPROVED, UL LISTED
HOUSEKEEPING
CLOSET
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY
PENDENT OR UPRIGHT,
QUICK RESPONSE, FACTORY
MUTUAL APPROVED, UL LISTED
NOTES:
1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.
HAZARD
SYMBOL
A. THESE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
REPRESENT THE OVERALL SCOPE, DESIGN INTENT, AND COVERAGE
AREA FOR THE FIRE PROTECTION SYSTEM WITHIN THE PROJECT SCOPE.
DELEGATED ENGINEER IS RESPONSIBLE FOR DESIGNING A FIRE
PROTECTION SYSTEM FOR THE ENTIRE BUILDING, PERMITTED AND
APPROVED PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION.
B. DELEGATED ENGINEER SHALL PROVIDE FIRE PROTECTION SYSTEM
LAYOUT DOCUMENTS TO THE ENGINEER OF RECORD AND AUTHORITY
HAVING JURISDICTION, INCLUDING THE FOLLOWING AS APPLICABLE, BUT
NOT LIMITED TO:
a. SPRINKLER SYSTEM DRAWINGS, INCLUDING SPRINKLER SYSTEM
LAYOUT, NODE IDENTIFICATION AND NODE SPOT ELEVATIONS.
b. HYDRAULIC CALCULATIONS AND PIPE SIZES. SIZE PIPING TO PROVIDE
AN EXCESS RESIDUAL PRESSURE OF 10 PSI AT THE HYDRAULICALLY
MOST DEMANDING POINT AT SYSTEM DESIGN FLOW.
c. SPRINKLER SYSTEM DESIGN, CALCULATIONS, DETAILED
WORKSHEETS, WATER SUPPLY CURVE, AND SPRINKLER SYSTEM
DEMAND CURVE.
d. SPRINKLER HEAD PRODUCT DATA SHEETS WITH SPECIFIC SYSTEM
COMPONENTS IDENTIFIED.
e. ADDITIONAL SPRINKLER SYSTEM SPECIFICATIONS AS REQUIRED FOR
COMPLIANCE WITH NFPA 13, CHAPTER 8 PLANS AND CALCULATIONS,
PRIOR TO AUTOMATIC SPRINKLER SYSTEMS INSTALLATION.
f. ALL NECESSARY COMPONENTS, SYSTEMS MATERIALS, ASSEMBLIES, EQUIPMENT, AND SUPPORT SYSTEMS REQUIRED.
C. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF
RISERS, CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL
OTHER TRADE SYSTEMS TO AVOID CONFLICTS AND MAINTAIN
ARCHITECTURAL ELEMENTS OF THE BUILDING.
D. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH
ARCHITECTURAL FINISHES AND OTHER CEILING MOUNTED DEVICES.
TITLEDELEGATED DESIGN REQUIREMENTS
1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS
INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE
TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS
ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND
NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE
INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.
2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR
THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS
RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED
PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC
CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY
TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL
APPLICABLE CODES AND CRITERIA.
3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,
AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE
2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE
CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST
RESTRICTIVE REQUIREMENTS SHALL GOVERN.
4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS
FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.
5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN
ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S
REPRESENTATIVE.
6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN
A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST
SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,
LATEST EDITION.
7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE
CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING
SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR
BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY
COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.
8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,
CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED
ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS
TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS
FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION
DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED
ASSEMBLIES.
9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE
REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL
WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO
ARE REGULARLY EMPLOYED TO DO SUCH WORK.
10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,
CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE
SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE
BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO
CONSTRUCTION.
11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.
12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS
OTHERWISE NOTED.
13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND
OBSTRUCTION REQUIREMENTS.
14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL
FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,
AND STRUCTURAL COMPONENTS.
15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL
SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE
REQUIREMENTS IN ACCORDANCE WITH NFPA 13.
16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE
RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.
17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS
AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL
SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE
WITH NFPA.
18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE
SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,
ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL
SPRINKLERS INSTALLED BELOW 7'-0" AFF.
19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND
FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10
MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.
20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES
OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL
PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED
ADJUSTABLE HANGERS.
21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT
WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA
REQUIREMENTS.
22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT
WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS
PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA
13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.
23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE
BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.
24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.
TITLEFIRE PROTECTION NOTES
FIRE SPRINKLER LEGEND
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED
IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH
DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).
DEDUCTIVE ALTERNATE NOTES
(E) EXISTING
AFF ABOVE FINISHED FLOOR
BFF BELOW FINISHED FLOOR
EXIST EXISTING
IBC INTERNATIONAL BUILDING CODE
IE INVERT ELEVATION
NC NORMALLY CLOSED
NO NORMALLY OPEN
ABBREVIATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:4
P
M
F-001
FIRE PROTECTION LEGENDS & NOTES
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
DRAWING INDEX - FIRE PROTECTION
F-001 FIRE PROTECTION LEGENDS & NOTES
FS100 FIRE PROTECTION SITE PLAN
FP101 FIRE PROTECTION OVERALL FLOOR PLAN - LEVEL 1
FP101A FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A
FP101B FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B
FP102 FIRE SPRINKLER OVERALL FLOOR PLAN - PENTHOUSE
FH101A FIRE PROTECTION HAZARD PLAN - LEVEL 1 - AREA A
FH101B FIRE PROTECTION HAZARD PLAN - LEVEL 1 - AREA B
Revisions: Date: 7/21/2021
STAMP
05/09/20225/09/2022
UP
S
EXISTING FIRE HYDRANT
TO BE RELOCATED,
REFER TO CIVIL SHEET
CU101 FOR ADDITIONAL
INFORMATION.
FIRE RISER
FDC
2-1/2" CRAWFORD SIAMESE,
PROVIDE PLACARD FOR FDC
ON WALL. REFER TO CIVIL
SHEET CU101 FOR
ADDITIONAL INFORMATION.
MECHANICAL
PIV
LOCATION OF RELOCATED
FIRE HYDRANT, REFER TO
CIVIL SHEET CU101 FOR
ADDITIONAL INFORMATION.
REFER TO CIVIL
SHEET CU101
FOR ADDITIONAL
INFORMATION.
FIRE MAIN ROUTED
THROUGH STEAM
TUNNEL, REFER TO
SHEET FP101A
HYDRANT PIPING SHOWN
FOR REFERENCE ONLY,
REFER TO CIVIL SHEET
CU101 FOR ADDITIONAL
INFORMATION.
EXISTING FIRE HYDRANT
BUILDING 6
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:3
P
M
FS100
FIRE PROTECTION SITE PLAN
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1" = 30'-0"
FIRE PROTECTION SITE PLAN-
Revisions: Date: 7/21/2021
STAMP
PORCH-A
FOYER
RESIDENT 6
RESIDENT 9
TLT 9
127A
DINING
RESIDENT 11
SITTING ALCOVE
11/12A
RESIDENT 12
RESIDENT 13
ELEC
TLT 12
131A TLT 13
133A
LN
SITTING ALCOVE
13/14A
RESIDENT 10
TLT 8
126A
RESIDENT 1
TLT 10
128A
SITTING ALCOVE
8/9/10A
TLT 11
130A
RESIDENT 14
TLT 14
134A
RESIDENT 4
TLT 6
119A
RESIDENT 5
TLT 4
117A
SITTING ALCOVE
4/5/6/7A
RESIDENT 3
SITTING ALCOVE
2/3A
RESIDENT 2
TLT 2
114A
TLT 3
115A LOBBY
PANTRY
125A
DINING
RESIDENT 10
SITTING ALCOVE
10/11B
RESIDENT 11
RESIDENT 12
ELEC
HALLWAY
192C
TLT 11
178A
TLT 12
180A
LN
CLEAN
SITTING ALCOVE
12/13B
RESIDENT 9
TLT 9
173A
SITTING ALCOVE
6/7/8/9B
TLT 10
175A
RESIDENT 13
TLT 13
181A
RESIDENT 3
RESIDENT 14
TLT 3
162A
SITTING ALCOVE
3/4/5B
RESIDENT 2
SITTING ALCOVE
1/2B
RESIDENT 1
TLT 1
159A
TLT 2
160A
FAMILY TOILET
HAC
POWER
EMERGENCY
POWER
GAS
EXAM RM
STERILE SUPPLY
STORAGE
PT/KT
STORAGE
CENTRAL KITCHEN
ACTIVITY
CORRIDOR
164C
LN
LN
LN
LN
LN
LN
LN
LN
CORRIDOR
120C
MECHANICAL
LIVING ROOM
MAIN PORCH
IT CLOSET
PANTRY
168A
OFFICE
OFFICE
CONFERENCE
MEDS
CLEAN
SOILED
TLT 1
110A
TLT 14
183A
HOTELING
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CORRIDOR
162C
SOILED
MEDS
CRASH CART B
CHARGING B
CRASH CART
CHARGING A
SALON
WHEELCHAIR/
STRETCHER STRG
HALLWAY
209C
CLC WALKWAY
STAFF TOILET/
SHOWER
TLT 5
118A
RESIDENT 8
RESIDENT 5
RESIDENT 4
TLT 4
163A
TLT 8
172A
TLT 7
171A
RESIDENT 8
TLT 5
164A
LIVING ROOM
RESIDENT 7
SITTING ALCOVE
1A
CORRIDOR 1A
CORRIDOR
122C
CORRIDOR
163C
SITTING ALCOVE
14B
LN
RESIDENT 7
(BARIATRIC)
TLT 7
120A
HAC
PUBLIC TOILET
STORAGE
LN
RESIDENT 6
(BARIATRIC)
TLT 6
170A
STAIRS
144B
SPRINKLER ZONE 1A
(WEST)
SPRINKLER ZONE 1B
(EAST)
M A
T C
H
LI
N E
E : 1
/F H
1A
M A
T C
H
LI
E : 1
/F H
1B
6" FWP
CORR
SCREENING VESTIBULE
PORCH B
FDC1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS
INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE
TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS
ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND
NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE
INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.
2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR
THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS
RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED
PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC
CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY
TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL
APPLICABLE CODES AND CRITERIA.
3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,
AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE
2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE
CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST
RESTRICTIVE REQUIREMENTS SHALL GOVERN.
4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS
FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.
5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN
ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S
REPRESENTATIVE.
6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN
A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST
SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,
LATEST EDITION.
7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE
CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING
SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR
BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY
COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.
8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,
CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED
ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS
TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS
FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION
DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED
ASSEMBLIES.
9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE
REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL
WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO
ARE REGULARLY EMPLOYED TO DO SUCH WORK.
10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,
CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE
SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE
BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO
CONSTRUCTION.
11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.
12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS
OTHERWISE NOTED.
13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND
OBSTRUCTION REQUIREMENTS.
14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL
FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,
AND STRUCTURAL COMPONENTS.
15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL
SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE
REQUIREMENTS IN ACCORDANCE WITH NFPA 13.
16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE
RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.
17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS
AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL
SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE
WITH NFPA.
18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE
SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,
ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL
SPRINKLERS INSTALLED BELOW 7'-0" AFF.
19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND
FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10
MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.
20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES
OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL
PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED
ADJUSTABLE HANGERS.
21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT
WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA
REQUIREMENTS.
22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT
WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS
PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA
13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.
23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE
BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.
24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.
TITLEFIRE PROTECTION NOTES
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
SPRINKLERS NOT
REQUIRED IN PIPE
BASEMENT
BASEMENT
SPRINKLER ZONE 0
F W
P
345 SF
FROM FDC
REFER TO
DETAIL 6 ON
SHEET F-001
TUNNEL EAST LEG,
REFER TO DEDUCT
ALTERNATE 2 NOTE
STAIRS
001D
STEAM TUNNEL
7 7.2 7.5 7.9 8 8.5 9
F
E.4
E.2
D.7
E
D
MECH
PENTHOUSE
SPRINKLER ZONE 2A
REFER TO
DETAIL 6 ON
SHEET F-001
STAIRS
201A
6 6.5 7 7.2 7.5 7.9 8
E.2
D.7
E
D
C.4
C.8
C.1
C
4" FWP
6" FWP
4" FWP
BACKFLOW PREVENTOR
BASEMENT ZONE VALVE
ZONE 1B VALVE (EAST)
ZONE 1A VALVE (WEST)
ZONE 2A VALVE
FDC
CIVIL
CONNECTION
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST
BE EXCERCISED IN THE ORDER PRESENTED) FOR A
DETAILED DESCRIPTION OF EACH DEDUCTIVE
ALTERNATE REFER TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST
LEG).
DEDUCT ALTERNATE
N
KEY PLAN
AREA B
(EAST)
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:1
P
M
FP101
FIRE PROTECTION OVERALL FLOOR PLAN -
LEVEL 1
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
3/32" = 1'-0"
FIRE PROTECTION ZONE FLOOR PLAN - LEVEL 1
FIRE SPRINKLER ZONE AREAS
Sprinkler Zone Area
Sprinkler Zone 0 552.66 SF
Sprinkler Zone 1A 12,923.88 SF
Sprinkler Zone 1B 10,670.47 SF
Sprinkler Zone 2A 1,500.71 SF
Grand total: 144 25,647.73 SF
1/8" = 1'-0"
FIRE PROTECTION ZONE FLOOR PLAN - BASEMENT
3/32" = 1'-0"
FIRE PROTECTION ZONE FLOOR PLAN - PENTHOUSE
FIRE RISER - ISOMETRIC
Revisions: Date: 7/21/2021
STAMP
FP101A
FOYER
RESIDENT 6
RESIDENT 9
TLT 9
127A
DINING
RESIDENT 11
SITTING ALCOVE
11/12A
RESIDENT 12
RESIDENT 13
ELEC
TLT 12
131A
TLT 13
133A
LN
SITTING ALCOVE
13/14A
RESIDENT 10
TLT 8
126A
RESIDENT 1
TLT 10
128A
SITTING ALCOVE
8/9/10A
TLT 11
130A
RESIDENT 14
TLT 14
134A
RESIDENT 4
TLT 6
119A
RESIDENT 5
TLT 4
117A
SITTING ALCOVE
4/5/6/7A
RESIDENT 3
SITTING ALCOVE
2/3A
RESIDENT 2
TLT 2
114A
TLT 3
115A LOBBY
PANTRY
125A
RESIDENT 13
TLT 13
181A
RESIDENT 14
FAMILY TOILET
STORAGE
STERILE SUPPLY
STORAGE
PT/KT
CLEAN
CENTRAL KITCHEN
ACTIVITY
LN
LN
LN
LN
111 LN
CORRIDOR
120C
MECHANICAL
PORCH-A
LIVING ROOM
MAIN PORCH
IT CLOSET
CONFERENCE
MEDS
PUBLIC TOILET
SOILED
TLT 1
110A
TLT 14
183A
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CRASH CART
CHARGING A
SALON
WHEELCHAIR/
STRETCHER STRG
HALLWAY
209C
CLC WALKWAY
STAFF TOILET/
SHOWER
HAC
TLT 5
118A
RESIDENT 8
RESIDENT 7
(BARIATRIC)
TLT 7
120A
STORAGE
M A
T C
H
LI
E : 1
/F P
1B
HOTELING
SITTING ALCOVE
1A
SITTING ALCOVE
14B
M A
T C
H
LI
E : 1
/F P
1B
MATCHLINE
SEE: 2/FP101A
FP101A
SCREENING
VESTIBULE
FIRE RISER
UP
REFER TO SHEET FP102 FOR
SPRINKLER LAYOUT IN CORRIDORS
WITH HIGH CEILINGS.
REFER TO SHEET FP102 FOR
SPRINKLER LAYOUT IN CORRIDORS
WITH HIGH CEILINGS.
1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
FIRE SPRINKLER MAIN
TO SHEET FPB102
TLT 14
134A
LN
MECHANICAL
CLC WALKWAY
B6 WALKWAY
MATCHLINE
SEE: 1/FP101A
FIRE RISER
UP
7 7.2 7.5
G.2
G.3
F
E.4
E.2
E
FP101A
BACKFLOW
PREVENTOR
TO RISER ABOVECHECK VALVE
PIPE FROM FDC
FIRE MAIN
BASEMENT
TUNNEL EAST
LEG, REFER
TO DEDUCT
ALTERNATE 2
NOTE
7 7.2 7.5 7.9 8 8.5 9
F
E.4
E.2
D.7
E
FIRE SPRINKLER LEGEND
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
UPRIGHT SPRINKLER WITH CAGE
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
8" HPS
6" FWP 3" CW
STEAM AND CONDENSATE
SHOWN FOR REFERENCE ONLY,
REFER TO MECHANICAL PLANS
FOR MORE INFORMATION.
FIRE MAIN ROUTED
TO PIV AND CIVIL
OUTSIDE OF STEAM
TUNNEL
CLC WALKWAY
SPRINKLER
IN SOFFIT
UPRIGHT
SPRINKLER
DINING
SPRINKLER MAIN
SHOWN FOR
REFERENCE
UPRIGHT
SPRINKLER
SPRINKLER
PIPING SHOWN
FOR REFERENCE
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED
IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH
DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).
DEDUCTIVE ALTERNATE NOTES
N
KEY PLAN
AREA A
(WEST)
BASEMENT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:2
P
M
FP101A
FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS TMR
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A
1/8" = 1'-0"
FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - COVERED WALKWAY
1/8" = 1'-0"
FIRE SPRINKLER FLOOR PLAN - BASEMENT
KEYNOTES
1 SPRINKLER SHALL BE MOUNTED TO THE SOFFIT, ASSOCIATED
SPRINKLER PIPING SHALL BE ROUTED IN THE SOFFIT.
2 SPRINKLER ZONE VALVE ASSEMBLY, REFER TO DETAIL FOR MORE
INFORMATION.
3 INSPECTOR TEST DRAIN, REFER TO DETAIL FOR MORE
INFORMATION.
4 FDC PIPE TO BASEMENT BELOW.
5 FIRE RISER TO BASEMENT BELOW.
6 CONNECT SPRINKLERS SHOWN IN THE WALKWAY NEAREST
BUILDING 6 TO THE EXISTING BUILDING 6 SPRINKLER SYSTEM.
7 PAINT EXPOSED SPRINKLER PIPING IN THIS ROOM RED.
1/8" = 1'-0"
FIRE MAIN STEAM TUNNEL
1/8" = 1'-0"
DINING 125 SECTION
1/8" = 1'-0"
CORRIDOR 120C SECTION
Revisions: Date: 7/21/2021
STAMP
LN
DINING
RESIDENT 10
SITTING ALCOVE
10/11B
RESIDENT 11
RESIDENT 12
ELEC
HALLWAY
192C
TLT 11
178A
TLT 12
180A
LN
CLEAN
SITTING ALCOVE
12/13B
RESIDENT 9
TLT 9
173A
SITTING ALCOVE
6/7/8/9B
TLT 10
175A
RESIDENT 13
TLT 13
181A
RESIDENT 3
RESIDENT 14
TLT 3
162A
SITTING ALCOVE
3/4/5B
RESIDENT 2
SITTING ALCOVE
1/2B
RESIDENT 1
TLT 1
159A
TLT 2
160AGAS
POWER
EMERGENCY
POWER
EXAM RM
PT/KT
CORRIDOR
164C
LN
LN
LN
LN
PANTRY
168A
OFFICE
OFFICE
CONFERENCE
TLT 14
183A
STAFF LOUNGE
OFFICE
ADMIN HALL-B
CORRIDOR
162C
SOILED
MEDS
CRASH CART B
CHARGING B
STAFF TOILET/
SHOWER
HAC
RESIDENT 5
RESIDENT 4
TLT 4
163A
TLT 8
172A
TLT 7
171A
RESIDENT 8
TLT 5
164A
LIVING ROOM
PORCH B
RESIDENT 7
RESIDENT 6
(BARIATRIC)
TLT 6
170A
STORAGE
HOTELING
SITTING ALCOVE
14B
M A
T C
H
LI
E : 1
/F P
1A
MAIN PORCH
FP101B
REFER TO SHEET FP102 FOR
SPRINKLER LAYOUT IN CORRIDORS
WITH HIGH CEILINGS.
REFER TO SHEET FP102 FOR
SPRINKLER LAYOUT IN CORRIDORS
WITH HIGH CEILINGS.
FP101B
7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
8.6
AA
FIRE SPRINKLER MAIN
TO SHEET FP101A
FIRE RISER UP, REFER
TO SHEET FP102
FIRE SPRINKLER LEGEND
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
UPRIGHT SPRINKLER WITH CAGE
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
SPRINKLER
IN SOFFIT
UPRIGHT
SPRINKLERSPRINKLER MAIN
PIPING FOR
REFERENCE
UPRIGHT
SPRINKLER
SPRINKLER
PIPING SHOWN
FOR REFERENCE
N
KEY PLAN
AREA B
(EAST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:3
P
M
FP101B
FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS TMR
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B
KEYNOTES
1 SPRINKLER SHALL BE MOUNTED TO THE SOFFIT, ASSOCIATED
SPRINKLER PIPING SHALL BE ROUTED IN THE SOFFIT.
2 SPRINKLER ZONE VALVE ASSEMBLY, REFER TO DETAIL FOR MORE
INFORMATION.
3 INSPECTOR TEST DRAIN, REFER TO DETAIL FOR MORE
INFORMATION.
4 PAINT EXPOSED SPRINKLER PIPING IN THIS ROOM RED.
1/8" = 1'-0"
DINING 168 SECTION
1/8" = 1'-0"
CORRIDOR 164C SECTION
Revisions: Date: 7/21/2021
STAMP
MECH
PENTHOUSE
SPRINKLER
ZONE 2A
FP101A
FP101A
FP101B
FIRE RISER FROM
FLOOR BELOW
CHILLERS
201B
STAIRS
201A
APPROXIMATE
LOCATION OF
SPRINKLER PIPING
IN CORRIDORS
APPROXIMATE
LOCATION OF
SPRINKLER PIPING
IN CORRIDORS
FP101B
1 2 3 4 5 5.2 6
5.7
6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
FIRE RISER FROM
FLOOR BELOW
SPRINKLER
ZONE 2B
SPRINKLER
ZONE 2A
SPRINKLER
ZONE 2A
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
SPACE TYPE
HAZARD
CLASSIFICATION
SYSTEM
TYPE
DISCHARGE
DENSITY
REMOTE
AREA
MAXIMUM
COVERAGE
AREA PER
SPRINKLER
MAXIMUM
SPACING
WATER
SUPPLY
DURATION
OUTSIDE
HOSE
ALLOWANCE TEMPERATURE
CLASSIFICATION
SPRINKLER TYPE NOTES
GPM/FT² FT² FT² FT. MINUTES GPM
GENERAL,
EXCEPT AS
LISTED BELOW
LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY
SEMI-RECESSED PENDENT, QUICK
RESPONSE, FACTORY MUTUAL
APPROVED, UL LISTED
STORAGE
ORDINARY
HAZARD
GROUP 2
WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY
SEMI-RECESSED PENDENT OR
UPRIGHT, QUICK RESPONSE,
FACTORY MUTUAL APPROVED,
UL LISTED
EQUIPMENT
ROOM
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE
QUICK RESPONSE
UPRIGHT, FACTORY MUTUAL
APPROVED, UL LISTED
HOUSEKEEPING
CLOSET
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY
PENDENT OR UPRIGHT,
QUICK RESPONSE, FACTORY
MUTUAL APPROVED, UL LISTED
NOTES:
1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.
HAZARD
SYMBOL
1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS
INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE
TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS
ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND
NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE
INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.
REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.
2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR
THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS
RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED
PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC
CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY
TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL
APPLICABLE CODES AND CRITERIA.
3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,
AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE
2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE
CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST
RESTRICTIVE REQUIREMENTS SHALL GOVERN.
4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS
FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.
5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN
ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S
REPRESENTATIVE.
6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN
A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST
SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,
LATEST EDITION.
7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE
CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING
SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR
BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY
COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.
8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,
CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED
ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS
TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS
FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION
DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED
ASSEMBLIES.
9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE
REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL
WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO
ARE REGULARLY EMPLOYED TO DO SUCH WORK.
10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,
CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE
SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE
BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO
CONSTRUCTION.
11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.
12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS
OTHERWISE NOTED.
13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND
OBSTRUCTION REQUIREMENTS.
14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL
FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,
AND STRUCTURAL COMPONENTS.
15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL
SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE
REQUIREMENTS IN ACCORDANCE WITH NFPA 13.
16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE
RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.
17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS
AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL
SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE
WITH NFPA.
18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE
SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,
ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL
SPRINKLERS INSTALLED BELOW 7'-0" AFF.
19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND
FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10
MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.
20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES
OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL
PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED
ADJUSTABLE HANGERS.
21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT
WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA
REQUIREMENTS.
22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT
WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS
PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA
13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.
23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE
BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.
24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.
TITLEFIRE PROTECTION NOTESFIRE SPRINKLER LEGEND
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
UPRIGHT SPRINKLER WITH CAGE
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
N
KEY PLAN
AREA B
(EAST)
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:3
P
M
FP102
FIRE SPRINKLER OVERALL FLOOR PLAN -
PENTHOUSE
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
3/32" = 1'-0"
FIRE PROTECTION FLOOR PLAN - PENTHOUSE
HAZARD CLASSIFICATION
HAZARD CLASSIFICATION AREA
Equipment Room - Ordinary 1 3,875.08 SF
HAC - Ordinary 1 143.56 SF
Light 25,034.65 SF
Ordinary 2 1,360.84 SF
Revisions: Date: 7/21/2021
STAMP
FOYER
555 SF
RESIDENT 6
232 SF
RESIDENT 9
238 SF
TLT 9
127A
78 SF
DINING
499 SF
RESIDENT 11
247 SF
SITTING ALCOVE
11/12A
128 SF
RESIDENT 12
247 SF
RESIDENT 13
230 SF
ELEC
99 SF
TLT 12
131A
89 SF
TLT 13
133A
89 SF
LN
14 SF
SITTING ALCOVE
13/14A
127 SF
RESIDENT 10
231 SF
TLT 8
126A
78 SF
RESIDENT 1
248 SF
TLT 10
128A
89 SF
SITTING ALCOVE
8/9/10A
154 SF
TLT 11
130A
89 SF
RESIDENT 14
232 SF
TLT 14
134A
88 SF
RESIDENT 4
231 SF
TLT 6
119A
78 SF
RESIDENT 5
238 SF
TLT 4
117A
89 SF
SITTING ALCOVE
4/5/6/7A
209 SF
RESIDENT 3
247 SF
SITTING ALCOVE
2/3A
131 SF
RESIDENT 2
247 SF
TLT 2
114A
89 SF
TLT 3
115A
89 SF
LOBBY
166 SF
PANTRY
125A
90 SF
RESIDENT 13
231 SF
TLT 13
181A
89 SF
RESIDENT 14
225 SF
FAMILY TOILET
66 SF
STORAGE
70 SF
STERILE SUPPLY
STORAGE
123 SF
PT/KT
348 SF
CLEAN
69 SF
CENTRAL KITCHEN
68 SF
ACTIVITY
553 SF
LN
14 SF
LN
7 SF
LN
14 SF
LN
14 SF
LN
14 SF
CORRIDOR
120C
536 SF
MECHANICAL
145 SF
PORCH-A
336 SF
LIVING ROOM
402 SF
MAIN PORCH
1815 SF
IT CLOSET
142 SF
CONFERENCE
276 SF
MEDS
136 SF
PUBLIC TOILET
63 SF
SOILED
71 SF
TLT 1
110A
88 SF
TLT 14
183A
89 SF
HOTELING
209 SF
STAFF LOUNGE
184 SF
OFFICE
112 SF
ADMIN HALL-B
90 SF
CRASH CART
54 SF
CHARGING A
34 SF
SALON
150 SF
WHEELCHAIR/
STRETCHER STRG
106 SF
HALLWAY
209C
160 SF
CLC WALKWAY
483 SF
STAFF TOILET/
SHOWER
76 SF
HAC
68 SF
TLT 5
118A
78 SF
RESIDENT 8
221 SF
RESIDENT 7
(BARIATRIC)
254 SF
TLT 7
120A
91 SF
M A
T C
H
LI
E : 1
/F H
1B
MATCHLINE
SEE: 2/FH101A
CLC WALKWAY
483 SF
STORAGE
82 SF
CORR
59 SF
SCREENING
VESTIBULE
1 2 3 4 5 5.2 65.7 6.5
7 7.2 7.5
7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
D
C.4
C.8
C.1
C
B
A.5
A
7.86.6 7.1 7.6 8.6
AA
7.76.8
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
SPACE TYPE
HAZARD
CLASSIFICATION
SYSTEM
TYPE
DISCHARGE
DENSITY
REMOTE
AREA
MAXIMUM
COVERAGE
AREA PER
SPRINKLER
MAXIMUM
SPACING
WATER
SUPPLY
DURATION
OUTSIDE
HOSE
ALLOWANCE TEMPERATURE
CLASSIFICATION
SPRINKLER TYPE NOTES
GPM/FT² FT² FT² FT. MINUTES GPM
GENERAL,
EXCEPT AS
LISTED BELOW
LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY
SEMI-RECESSED PENDENT, QUICK
RESPONSE, FACTORY MUTUAL
APPROVED, UL LISTED
STORAGE
ORDINARY
HAZARD
GROUP 2
WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY
SEMI-RECESSED PENDENT OR
UPRIGHT, QUICK RESPONSE,
FACTORY MUTUAL APPROVED,
UL LISTED
EQUIPMENT
ROOM
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE
QUICK RESPONSE
UPRIGHT, FACTORY MUTUAL
APPROVED, UL LISTED
HOUSEKEEPING
CLOSET
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY
PENDENT OR UPRIGHT,
QUICK RESPONSE, FACTORY
MUTUAL APPROVED, UL LISTED
NOTES:
1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.
HAZARD
SYMBOL
TLT 14
134A
88 SF
LN
7 SF
MECHANICAL
145 SF
CLC WALKWAY
483 SF
MATCHLINE
SEE: 1/FH101A
B6 WALKWAY
CLC WALKWAY
483 SF
7 7.2 7.5
G.2
G.3
F
E.4
E.2
E
SPRINKLERS NOT
REQUIRED IN PIPE
BASEMENT
BASEMENT
BASEMENT ON ZONE 0
SPRINKLER SYSTEM
345 SF
TUNNEL EAST LEG,
REFER TO DEDUCT
ALTERNATE 2 NOTE
7 7.2 7.5
7.9 8 8.5 9
G.2
G.3
F
E.4
E.2
D.7
E
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED
IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH
DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000
DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).
DEDUCTIVE ALTERNATE NOTES
N
KEY PLAN
AREA A
(WEST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:5
P
M
FH101A
FIRE PROTECTION HAZARD PLAN - LEVEL 1 -
AREA A
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - LEVEL 1 - AREA A
HAZARD CLASSIFICATION
HAZARD CLASSIFICATION AREA
Equipment Room - Ordinary 1 3,875.08 SF
HAC - Ordinary 1 143.56 SF
Light 25,034.65 SF
Ordinary 2 1,360.84 SF
1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - LEVEL 1 - COVERED WALKWAY
1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - BASEMENT
Revisions: Date: 7/21/2021
STAMP
LN
10 SF
DINING
498 SF
RESIDENT 10
246 SF
SITTING ALCOVE
10/11B
130 SF
RESIDENT 11
245 SF
RESIDENT 12
227 SF
ELEC
98 SF
HALLWAY
192C
162 SF
TLT 11
178A
89 SF
TLT 12
180A
89 SF
LN
14 SF
CLEAN
81 SF
SITTING ALCOVE
12/13B
132 SF
RESIDENT 9
231 SF
TLT 9
173A
89 SF
SITTING ALCOVE
6/7/8/9B
195 SF
TLT 10
175A
88 SF
RESIDENT 13
231 SF
TLT 13
181A
89 SF
RESIDENT 3
234 SF
RESIDENT 14
225 SF
TLT 3
162A
89 SF
SITTING ALCOVE
3/4/5B
149 SF
RESIDENT 2
226 SF
SITTING ALCOVE
1/2B
127 SF
RESIDENT 1
227 SF
TLT 1
159A
85 SF
TLT 2
160A
89 SF
FAMILY TOILET
66 SF
GAS
56 SF
POWER
95 SF
EMERGENCY
POWER
115 SF
EXAM RM
98 SF
PT/KT
348 SF
CORRIDOR
164C
868 SFLN
14 SF
LN
14 SF
LN
14 SF
LN
8 SF
MAIN PORCH
1815 SF
PANTRY
168A
94 SF
OFFICE
116 SF
OFFICE
124 SF
CONFERENCE
276 SF
TLT 14
183A
89 SF
HOTELING
209 SF
STAFF LOUNGE
184 SF
OFFICE
112 SF
ADMIN HALL-B
90 SF
CORRIDOR
162C
943 SF
SOILED
94 SF
MEDS
142 SF
CRASH CART B
53 SF
CHARGING B
35 SF
WHEELCHAIR/
STRETCHER STRG
106 SF
STAFF TOILET/
SHOWER
76 SF
HAC
76 SF
RESIDENT 5
219 SF
RESIDENT 4
244 SF
TLT 4
163A
81 SF
TLT 8
172A
78 SF
TLT 7
171A
78 SF
RESIDENT 8
239 SF
TLT 5
164A
81 SF
LIVING ROOM
390 SF
PORCH B
319 SF
RESIDENT 7
230 SF
RESIDENT 6
(BARIATRIC)
257 SF
TLT 6
170A
87 SF
M A
T C
H
LI
E : 1
/F H
1A
STORAGE
82 SF
CORR
59 SF
7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8
G.2
G.3
13 13.2 14 15 16
F
E.4
E.2
D.7
E
16.2
D
C.4
C.8
C.1
C
B
A.5
A
8.6
AA
FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA
SPACE TYPE
HAZARD
CLASSIFICATION
SYSTEM
TYPE
DISCHARGE
DENSITY
REMOTE
AREA
MAXIMUM
COVERAGE
AREA PER
SPRINKLER
MAXIMUM
SPACING
WATER
SUPPLY
DURATION
OUTSIDE
HOSE
ALLOWANCE TEMPERATURE
CLASSIFICATION
SPRINKLER TYPE NOTES
GPM/FT² FT² FT² FT. MINUTES GPM
GENERAL,
EXCEPT AS
LISTED BELOW
LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY
SEMI-RECESSED PENDENT, QUICK
RESPONSE, FACTORY MUTUAL
APPROVED, UL LISTED
STORAGE
ORDINARY
HAZARD
GROUP 2
WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY
SEMI-RECESSED PENDENT OR
UPRIGHT, QUICK RESPONSE,
FACTORY MUTUAL APPROVED,
UL LISTED
EQUIPMENT
ROOM
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE
QUICK RESPONSE
UPRIGHT, FACTORY MUTUAL
APPROVED, UL LISTED
HOUSEKEEPING
CLOSET
ORDINARY
HAZARD
GROUP 1
WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY
PENDENT OR UPRIGHT,
QUICK RESPONSE, FACTORY
MUTUAL APPROVED, UL LISTED
NOTES:
1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.
HAZARD
SYMBOL
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
N
KEY PLAN
AREA B
(EAST)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
550 North Reo Street, Suite 203 Tampa, FL 33609
(813) 289-4700 Nicholas Stephenson, PE
Structural 315 West James Street, Suite 102 Lancaster, PA 17603
(717) 481-2991 Jason Vannoy, SE, PE
Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001
(212) 967-4890 Corrine Tan, SE
Landscape Architect 418 North Toole Avenue Tucson, AZ 85701
(520) 622-9565 Josh Orth., PLA
B
IM
/6
-3
N e w
C o m m u n it y L iv in g C e n te r/
M
E P
V
A M o n tr o s e C
L C
R
.r v t
/2
/2
:3
:0
P
M
FH101B
FIRE PROTECTION HAZARD PLAN - LEVEL 1 -
AREA B
TRIPLE C - The A/E Group
201 E. Jefferson Street, Suite 200
Syracuse, NY 13202
(315) 484-5958
Mat Perkins
620-334
CLC
07/21/2021 CJF/NPS NS
NEW COMMUNITY LIVING
CENTER
2094 Albany Post Road, Montrose, NY 10548
ISSUED FOR
CONSTRUCTION
1/8" = 1'-0"
FIRE PROTECTION FLOOR PLAN - LEVEL 1 - AREA B
HAZARD CLASSIFICATION
HAZARD CLASSIFICATION AREA
Equipment Room - Ordinary 1 3,875.08 SF
HAC - Ordinary 1 143.56 SF
Light 25,034.65 SF
Ordinary 2 1,360.84 SF
Revisions: Date: 7/21/2021