Drawings 11 of 15 FIRE PROTECTION.pdf

PDF 10 MB Posted

Attached to
Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334
Solicitation number
36C77623R0156
Issued by

About this file

This document provides details for a federal contract opportunity to construct a new community living center. The solicitation number is 36C77623R0156 for the project "Y1AZ--TIERED EVALUATIONS - Build New Community Living Center Minor Construction - Montrose 620-334" issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The opportunity type is a solicitation for construction of a new community living center as part of minor construction at the Montrose VA medical center. The file attached is a set of drawings numbered 11 of 15 pertaining to required fire protection systems for the project. No further information is provided on response dates, pricing terms, or other contractual requirements.

View the file

Other files

File Type Posted
620-334-Responses to Tech Questions - 1-30-24.pdf PDF
36C77623R0156 0003.pdf PDF
620-334-Pre Bid Presentation20240109.pdf PDF
36C77623R0156 0002.pdf PDF
620-334-Responses to Tech Questions - 1-25-24.pdf PDF
Site Visit Sign-In Sheet - 01-09-24.pdf PDF
36C77623R0156 0001.pdf PDF
DBA Wage Rates - Westchester County - 01-05-24.pdf PDF
Drawings 8 of 15 ARCHITECTURAL 3.pdf PDF
Site Visit Campus Map.pdf PDF
Drawings 14 of 15 ELECTRICAL 1.pdf PDF
Specifications 10-30-23.pdf PDF
Small Business Subcontracting Plan Model.docx DOCX document
Drawings 5 of 15 STRUCTURAL.pdf PDF
RFP 36C77623R0156 - 12-20-23.pdf PDF
Drawings 12 of 15 PLUMBING.pdf PDF
Drawings 1 of 15 GENERAL.pdf PDF
Drawings 4 of 15 LANDSCAPE.pdf PDF
Drawings 6 of 15 ARCHITECTURAL 1.pdf PDF
Drawings 2 of 15 CIVIL 1.pdf PDF
Drawings 7 of 15 ARCHITECTURAL 2.pdf PDF
Drawings 10 of 15 ARCH SIGN-EQUIP.pdf PDF
Drawings 13 of 15 MECHANICAL.pdf PDF
DBA Wage Rates - Westchester County - 11-17-23.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
Drawings 15 of 15 ELECTRICAL 2.pdf PDF
Brand Name J_A - Montrose.pdf PDF
Site Visit Instructions.pdf PDF
Drawings 9 of 15 ARCHITECTURAL 4.pdf PDF
Drawings 3 of 15 CIVIL 2.pdf PDF
Construction Cost Breakdown.pdf PDF
Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TEST DATA:

STATIC PRESSURE: PSI---

MEASURED FLOW: GPM1190

RESIDUAL PRESSURE: PSI50

DATE OF TEST: 10/24/2020

RESIDUAL HYDRANT LOCATION: ----

FLOW HYDRANT LOCATION: Hydrant #15

WATER FLOW TEST DATA

SCALE:

SCALE:

SCALE:

SCALE:

SCALE:

SCALE: SCALE:

NTS

NTS

NTS

NTS

NTS

NTS NTS

X X X

X X X

BOTTOM OF STRUCTURE

UPRIGHT SPRINKLER HEAD

REDUCER

1" NIPPLE

BRANCH LINE

CEILING

SPRINKLER HEAD

REDUCER

1" NIPPLE

BRANCH LINE

RECESSED PENDENT

SPRINKLER HEAD DETAIL

UPRIGHT SPRINKLER HEAD DETAIL

SPRINKLERS IN GRID CEILING SYSTEMS SHALL BE LOCATED AT THE

MIDPOINT OR QUARTERPOINT OF THE FOUR FOOT (4') DIMENSION AND

THE MIDPOINT OF THE TWO (2') DIMENSION. WHERE A CONFLICT

OCCURS, SYMMETRY ABOUT THE AXIS SHALL BE MAINTAINED.

E Q

E

Q

EQ.EQ.EQ.EQ.

E Q

E

Q

E Q

E

Q

EQ.EQ.

E Q

E

Q

.EQ. EQ.

E Q

E

Q

EQ. EQ.

SPRINKLER

SPEAKER OR

OTHER DEVICE

AIR DEVICE OR

LIGHT FIXTURE

CEILING LEGEND

SPRINKLER MOUNTING DETAIL

SWING ARM ASSEMBLY DETAIL

UNION WITH CORROSION

RESISTANT ORIFICE GIVING FLOW

EQUIVALENT TO THE SMALLEST

SPRINKLER ORIFICE IN THE

SYSTEM

TO DRAIN

SYSTEM RISER

AUXILIARY DRAIN

VALVE

SITE GLASS

INSPECTORS TEST VALVE

1" DRAIN LINE

PRESSURE GAUGE

WATER FLOW SWITCH

TO SPRINKLERS

INDICATING TYPE

FLOOR

CONTROL VALVE WITH

SUPERVISORY SWITCH

FIRE SPRINKLER ZONE

VALVE PIPING DETAIL

SYSTEM RISER

RISER FROM MAIN

WATER SUPPLY

FLOOR SLAB

RISER

TO FIRE

ALARM

SYSTEM

TAMPER SWITCH

APPROVED

NFPA-13

SUPERVISED

VALVE

TEE CONNECTION

WATER FLOW INDICATOR

TO FIRE ALARM SYSTEM

TO SPRINKLER SYSTEM

ALARM BELL

POWER BY DIV. 16

CONTROL WIRING BY

FA

CONTRACTOR

EXTERIOR WALL

CHECK VALVE

FROM FIRE

DEPARTMENT

CONNECTION

SPLASH

BLOCK

MAIN DRAIN (2" MIN.)

MAIN DRAIN VALVE

WET PIPE ALARM VALVE

WATER GAUGE (2 REQ'D)

FOR HEAD TYPES,

SEE FLOOR PLANS

AND HEAD

DETAILS

1" X 1/2" R.C.

DROP

90 EL.

ARMOVER (NOTE 1)

RISER NIPPLE

BRANCHLINE

SUSPENDED CEILING

NOTE:

1. PROVIDE HANGER FOR ARMOVERS

GREATER THAN 24" IN LENGTH.

ELBOW WITH CORROSION

RESISTANT OUTLET EQUAL

TO

ONE SPRINKLER

1" INSPECTOR TEST

PIPING, SEE PLAN FOR

CONTINUATION

1" TEST VA. IN ACCESSIBLE

LOCATION NOT OVER 7'

FOOT

ABOVE FLOOR

SPLASH BLOCK

SLEEVE

EXTERIOR WALL

PROVIDE SIGHT GLASS

FLOOR

INSPECTORS TEST

AND DRAIN DETAIL

FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

SYSTEM

TYPE

DISCHARGE

DENSITY

REMOTE

AREA

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

WATER

SUPPLY

DURATION

OUTSIDE

HOSE

ALLOWANCE TEMPERATURE

CLASSIFICATION

SPRINKLER TYPE NOTES

GPM/FT² FT² FT² FT. MINUTES GPM

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY

SEMI-RECESSED PENDENT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

STORAGE

ORDINARY

HAZARD

GROUP 2

WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY

SEMI-RECESSED PENDENT OR

UPRIGHT, QUICK RESPONSE,

FACTORY MUTUAL APPROVED,

UL LISTED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE

QUICK RESPONSE

UPRIGHT, FACTORY MUTUAL

APPROVED, UL LISTED

HOUSEKEEPING

CLOSET

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

PENDENT OR UPRIGHT,

QUICK RESPONSE, FACTORY

MUTUAL APPROVED, UL LISTED

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

HAZARD

SYMBOL

A. THESE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS

REPRESENT THE OVERALL SCOPE, DESIGN INTENT, AND COVERAGE

AREA FOR THE FIRE PROTECTION SYSTEM WITHIN THE PROJECT SCOPE.

DELEGATED ENGINEER IS RESPONSIBLE FOR DESIGNING A FIRE

PROTECTION SYSTEM FOR THE ENTIRE BUILDING, PERMITTED AND

APPROVED PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION.

B. DELEGATED ENGINEER SHALL PROVIDE FIRE PROTECTION SYSTEM

LAYOUT DOCUMENTS TO THE ENGINEER OF RECORD AND AUTHORITY

HAVING JURISDICTION, INCLUDING THE FOLLOWING AS APPLICABLE, BUT

NOT LIMITED TO:

a. SPRINKLER SYSTEM DRAWINGS, INCLUDING SPRINKLER SYSTEM

LAYOUT, NODE IDENTIFICATION AND NODE SPOT ELEVATIONS.

b. HYDRAULIC CALCULATIONS AND PIPE SIZES. SIZE PIPING TO PROVIDE

AN EXCESS RESIDUAL PRESSURE OF 10 PSI AT THE HYDRAULICALLY

MOST DEMANDING POINT AT SYSTEM DESIGN FLOW.

c. SPRINKLER SYSTEM DESIGN, CALCULATIONS, DETAILED

WORKSHEETS, WATER SUPPLY CURVE, AND SPRINKLER SYSTEM

DEMAND CURVE.

d. SPRINKLER HEAD PRODUCT DATA SHEETS WITH SPECIFIC SYSTEM

COMPONENTS IDENTIFIED.

e. ADDITIONAL SPRINKLER SYSTEM SPECIFICATIONS AS REQUIRED FOR

COMPLIANCE WITH NFPA 13, CHAPTER 8 PLANS AND CALCULATIONS,

PRIOR TO AUTOMATIC SPRINKLER SYSTEMS INSTALLATION.

f. ALL NECESSARY COMPONENTS, SYSTEMS MATERIALS, ASSEMBLIES, EQUIPMENT, AND SUPPORT SYSTEMS REQUIRED.

C. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF

RISERS, CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL

OTHER TRADE SYSTEMS TO AVOID CONFLICTS AND MAINTAIN

ARCHITECTURAL ELEMENTS OF THE BUILDING.

D. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH

ARCHITECTURAL FINISHES AND OTHER CEILING MOUNTED DEVICES.

TITLEDELEGATED DESIGN REQUIREMENTS

1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS

INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE

TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS

ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND

NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE

INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.

REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.

2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR

THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED

PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC

CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY

TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL

APPLICABLE CODES AND CRITERIA.

3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,

AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE

2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE

CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST

RESTRICTIVE REQUIREMENTS SHALL GOVERN.

4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS

FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.

5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN

ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S

REPRESENTATIVE.

6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN

A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST

SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,

LATEST EDITION.

7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE

CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING

SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR

BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY

COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.

8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,

CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED

ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS

TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS

FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION

DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED

ASSEMBLIES.

9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE

REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL

WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO

ARE REGULARLY EMPLOYED TO DO SUCH WORK.

10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,

CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE

SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE

BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO

CONSTRUCTION.

11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.

12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS

OTHERWISE NOTED.

13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND

OBSTRUCTION REQUIREMENTS.

14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL

FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,

AND STRUCTURAL COMPONENTS.

15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL

SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE

REQUIREMENTS IN ACCORDANCE WITH NFPA 13.

16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE

RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.

17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS

AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL

SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE

WITH NFPA.

18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE

SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,

ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL

SPRINKLERS INSTALLED BELOW 7'-0" AFF.

19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND

FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10

MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.

20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES

OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL

PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED

ADJUSTABLE HANGERS.

21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT

WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA

REQUIREMENTS.

22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT

WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS

PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA

13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.

23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE

BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.

24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.

TITLEFIRE PROTECTION NOTES

FIRE SPRINKLER LEGEND

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED

IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH

DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).

DEDUCTIVE ALTERNATE NOTES

(E) EXISTING

AFF ABOVE FINISHED FLOOR

BFF BELOW FINISHED FLOOR

EXIST EXISTING

IBC INTERNATIONAL BUILDING CODE

IE INVERT ELEVATION

NC NORMALLY CLOSED

NO NORMALLY OPEN

ABBREVIATIONS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:4

P

M

F-001

FIRE PROTECTION LEGENDS & NOTES

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

DRAWING INDEX - FIRE PROTECTION

F-001 FIRE PROTECTION LEGENDS & NOTES

FS100 FIRE PROTECTION SITE PLAN

FP101 FIRE PROTECTION OVERALL FLOOR PLAN - LEVEL 1

FP101A FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A

FP101B FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B

FP102 FIRE SPRINKLER OVERALL FLOOR PLAN - PENTHOUSE

FH101A FIRE PROTECTION HAZARD PLAN - LEVEL 1 - AREA A

FH101B FIRE PROTECTION HAZARD PLAN - LEVEL 1 - AREA B

Revisions: Date: 7/21/2021

STAMP

05/09/20225/09/2022

UP

S

EXISTING FIRE HYDRANT

TO BE RELOCATED,

REFER TO CIVIL SHEET

CU101 FOR ADDITIONAL

INFORMATION.

FIRE RISER

FDC

2-1/2" CRAWFORD SIAMESE,

PROVIDE PLACARD FOR FDC

ON WALL. REFER TO CIVIL

SHEET CU101 FOR

ADDITIONAL INFORMATION.

MECHANICAL

PIV

LOCATION OF RELOCATED

FIRE HYDRANT, REFER TO

CIVIL SHEET CU101 FOR

ADDITIONAL INFORMATION.

REFER TO CIVIL

SHEET CU101

FOR ADDITIONAL

INFORMATION.

FIRE MAIN ROUTED

THROUGH STEAM

TUNNEL, REFER TO

SHEET FP101A

HYDRANT PIPING SHOWN

FOR REFERENCE ONLY,

REFER TO CIVIL SHEET

CU101 FOR ADDITIONAL

INFORMATION.

EXISTING FIRE HYDRANT

BUILDING 6

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:3

P

M

FS100

FIRE PROTECTION SITE PLAN

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1" = 30'-0"

FIRE PROTECTION SITE PLAN-

Revisions: Date: 7/21/2021

STAMP

PORCH-A

FOYER

RESIDENT 6

RESIDENT 9

TLT 9

127A

DINING

RESIDENT 11

SITTING ALCOVE

11/12A

RESIDENT 12

RESIDENT 13

ELEC

TLT 12

131A TLT 13

133A

LN

SITTING ALCOVE

13/14A

RESIDENT 10

TLT 8

126A

RESIDENT 1

TLT 10

128A

SITTING ALCOVE

8/9/10A

TLT 11

130A

RESIDENT 14

TLT 14

134A

RESIDENT 4

TLT 6

119A

RESIDENT 5

TLT 4

117A

SITTING ALCOVE

4/5/6/7A

RESIDENT 3

SITTING ALCOVE

2/3A

RESIDENT 2

TLT 2

114A

TLT 3

115A LOBBY

PANTRY

125A

DINING

RESIDENT 10

SITTING ALCOVE

10/11B

RESIDENT 11

RESIDENT 12

ELEC

HALLWAY

192C

TLT 11

178A

TLT 12

180A

LN

CLEAN

SITTING ALCOVE

12/13B

RESIDENT 9

TLT 9

173A

SITTING ALCOVE

6/7/8/9B

TLT 10

175A

RESIDENT 13

TLT 13

181A

RESIDENT 3

RESIDENT 14

TLT 3

162A

SITTING ALCOVE

3/4/5B

RESIDENT 2

SITTING ALCOVE

1/2B

RESIDENT 1

TLT 1

159A

TLT 2

160A

FAMILY TOILET

HAC

POWER

EMERGENCY

POWER

GAS

EXAM RM

STERILE SUPPLY

STORAGE

PT/KT

STORAGE

CENTRAL KITCHEN

ACTIVITY

CORRIDOR

164C

LN

LN

LN

LN

LN

LN

LN

LN

CORRIDOR

120C

MECHANICAL

LIVING ROOM

MAIN PORCH

IT CLOSET

PANTRY

168A

OFFICE

OFFICE

CONFERENCE

MEDS

CLEAN

SOILED

TLT 1

110A

TLT 14

183A

HOTELING

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CORRIDOR

162C

SOILED

MEDS

CRASH CART B

CHARGING B

CRASH CART

CHARGING A

SALON

WHEELCHAIR/

STRETCHER STRG

HALLWAY

209C

CLC WALKWAY

STAFF TOILET/

SHOWER

TLT 5

118A

RESIDENT 8

RESIDENT 5

RESIDENT 4

TLT 4

163A

TLT 8

172A

TLT 7

171A

RESIDENT 8

TLT 5

164A

LIVING ROOM

RESIDENT 7

SITTING ALCOVE

1A

CORRIDOR 1A

CORRIDOR

122C

CORRIDOR

163C

SITTING ALCOVE

14B

LN

RESIDENT 7

(BARIATRIC)

TLT 7

120A

HAC

PUBLIC TOILET

STORAGE

LN

RESIDENT 6

(BARIATRIC)

TLT 6

170A

STAIRS

144B

SPRINKLER ZONE 1A

(WEST)

SPRINKLER ZONE 1B

(EAST)

M A

T C

H

LI

N E

E : 1

/F H

1A

M A

T C

H

LI

E : 1

/F H

1B

6" FWP

CORR

SCREENING VESTIBULE

PORCH B

FDC1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS

INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE

TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS

ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND

NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE

INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.

REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.

2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR

THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED

PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC

CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY

TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL

APPLICABLE CODES AND CRITERIA.

3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,

AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE

2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE

CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST

RESTRICTIVE REQUIREMENTS SHALL GOVERN.

4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS

FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.

5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN

ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S

REPRESENTATIVE.

6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN

A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST

SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,

LATEST EDITION.

7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE

CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING

SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR

BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY

COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.

8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,

CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED

ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS

TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS

FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION

DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED

ASSEMBLIES.

9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE

REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL

WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO

ARE REGULARLY EMPLOYED TO DO SUCH WORK.

10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,

CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE

SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE

BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO

CONSTRUCTION.

11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.

12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS

OTHERWISE NOTED.

13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND

OBSTRUCTION REQUIREMENTS.

14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL

FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,

AND STRUCTURAL COMPONENTS.

15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL

SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE

REQUIREMENTS IN ACCORDANCE WITH NFPA 13.

16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE

RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.

17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS

AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL

SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE

WITH NFPA.

18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE

SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,

ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL

SPRINKLERS INSTALLED BELOW 7'-0" AFF.

19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND

FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10

MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.

20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES

OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL

PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED

ADJUSTABLE HANGERS.

21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT

WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA

REQUIREMENTS.

22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT

WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS

PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA

13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.

23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE

BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.

24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.

TITLEFIRE PROTECTION NOTES

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

SPRINKLERS NOT

REQUIRED IN PIPE

BASEMENT

BASEMENT

SPRINKLER ZONE 0

F W

P

345 SF

FROM FDC

REFER TO

DETAIL 6 ON

SHEET F-001

TUNNEL EAST LEG,

REFER TO DEDUCT

ALTERNATE 2 NOTE

STAIRS

001D

STEAM TUNNEL

7 7.2 7.5 7.9 8 8.5 9

F

E.4

E.2

D.7

E

D

MECH

PENTHOUSE

SPRINKLER ZONE 2A

REFER TO

DETAIL 6 ON

SHEET F-001

STAIRS

201A

6 6.5 7 7.2 7.5 7.9 8

E.2

D.7

E

D

C.4

C.8

C.1

C

4" FWP

6" FWP

4" FWP

BACKFLOW PREVENTOR

BASEMENT ZONE VALVE

ZONE 1B VALVE (EAST)

ZONE 1A VALVE (WEST)

ZONE 2A VALVE

FDC

CIVIL

CONNECTION

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST

BE EXCERCISED IN THE ORDER PRESENTED) FOR A

DETAILED DESCRIPTION OF EACH DEDUCTIVE

ALTERNATE REFER TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST

LEG).

DEDUCT ALTERNATE

N

KEY PLAN

AREA B

(EAST)

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:1

P

M

FP101

FIRE PROTECTION OVERALL FLOOR PLAN -

LEVEL 1

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

3/32" = 1'-0"

FIRE PROTECTION ZONE FLOOR PLAN - LEVEL 1

FIRE SPRINKLER ZONE AREAS

Sprinkler Zone Area

Sprinkler Zone 0 552.66 SF

Sprinkler Zone 1A 12,923.88 SF

Sprinkler Zone 1B 10,670.47 SF

Sprinkler Zone 2A 1,500.71 SF

Grand total: 144 25,647.73 SF

1/8" = 1'-0"

FIRE PROTECTION ZONE FLOOR PLAN - BASEMENT

3/32" = 1'-0"

FIRE PROTECTION ZONE FLOOR PLAN - PENTHOUSE

FIRE RISER - ISOMETRIC

Revisions: Date: 7/21/2021

STAMP

FP101A

FOYER

RESIDENT 6

RESIDENT 9

TLT 9

127A

DINING

RESIDENT 11

SITTING ALCOVE

11/12A

RESIDENT 12

RESIDENT 13

ELEC

TLT 12

131A

TLT 13

133A

LN

SITTING ALCOVE

13/14A

RESIDENT 10

TLT 8

126A

RESIDENT 1

TLT 10

128A

SITTING ALCOVE

8/9/10A

TLT 11

130A

RESIDENT 14

TLT 14

134A

RESIDENT 4

TLT 6

119A

RESIDENT 5

TLT 4

117A

SITTING ALCOVE

4/5/6/7A

RESIDENT 3

SITTING ALCOVE

2/3A

RESIDENT 2

TLT 2

114A

TLT 3

115A LOBBY

PANTRY

125A

RESIDENT 13

TLT 13

181A

RESIDENT 14

FAMILY TOILET

STORAGE

STERILE SUPPLY

STORAGE

PT/KT

CLEAN

CENTRAL KITCHEN

ACTIVITY

LN

LN

LN

LN

111 LN

CORRIDOR

120C

MECHANICAL

PORCH-A

LIVING ROOM

MAIN PORCH

IT CLOSET

CONFERENCE

MEDS

PUBLIC TOILET

SOILED

TLT 1

110A

TLT 14

183A

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CRASH CART

CHARGING A

SALON

WHEELCHAIR/

STRETCHER STRG

HALLWAY

209C

CLC WALKWAY

STAFF TOILET/

SHOWER

HAC

TLT 5

118A

RESIDENT 8

RESIDENT 7

(BARIATRIC)

TLT 7

120A

STORAGE

M A

T C

H

LI

E : 1

/F P

1B

HOTELING

SITTING ALCOVE

1A

SITTING ALCOVE

14B

M A

T C

H

LI

E : 1

/F P

1B

MATCHLINE

SEE: 2/FP101A

FP101A

SCREENING

VESTIBULE

FIRE RISER

UP

REFER TO SHEET FP102 FOR

SPRINKLER LAYOUT IN CORRIDORS

WITH HIGH CEILINGS.

REFER TO SHEET FP102 FOR

SPRINKLER LAYOUT IN CORRIDORS

WITH HIGH CEILINGS.

1 2 3 4 5 5.2 65.7 6.5 7 7.2 7.5 7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

FIRE SPRINKLER MAIN

TO SHEET FPB102

TLT 14

134A

LN

MECHANICAL

CLC WALKWAY

B6 WALKWAY

MATCHLINE

SEE: 1/FP101A

FIRE RISER

UP

7 7.2 7.5

G.2

G.3

F

E.4

E.2

E

FP101A

BACKFLOW

PREVENTOR

TO RISER ABOVECHECK VALVE

PIPE FROM FDC

FIRE MAIN

BASEMENT

TUNNEL EAST

LEG, REFER

TO DEDUCT

ALTERNATE 2

NOTE

7 7.2 7.5 7.9 8 8.5 9

F

E.4

E.2

D.7

E

FIRE SPRINKLER LEGEND

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

UPRIGHT SPRINKLER WITH CAGE

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

8" HPS

6" FWP 3" CW

STEAM AND CONDENSATE

SHOWN FOR REFERENCE ONLY,

REFER TO MECHANICAL PLANS

FOR MORE INFORMATION.

FIRE MAIN ROUTED

TO PIV AND CIVIL

OUTSIDE OF STEAM

TUNNEL

CLC WALKWAY

SPRINKLER

IN SOFFIT

UPRIGHT

SPRINKLER

DINING

SPRINKLER MAIN

SHOWN FOR

REFERENCE

UPRIGHT

SPRINKLER

SPRINKLER

PIPING SHOWN

FOR REFERENCE

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED

IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH

DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).

DEDUCTIVE ALTERNATE NOTES

N

KEY PLAN

AREA A

(WEST)

BASEMENT

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:2

P

M

FP101A

FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS TMR

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA A

1/8" = 1'-0"

FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - COVERED WALKWAY

1/8" = 1'-0"

FIRE SPRINKLER FLOOR PLAN - BASEMENT

KEYNOTES

1 SPRINKLER SHALL BE MOUNTED TO THE SOFFIT, ASSOCIATED

SPRINKLER PIPING SHALL BE ROUTED IN THE SOFFIT.

2 SPRINKLER ZONE VALVE ASSEMBLY, REFER TO DETAIL FOR MORE

INFORMATION.

3 INSPECTOR TEST DRAIN, REFER TO DETAIL FOR MORE

INFORMATION.

4 FDC PIPE TO BASEMENT BELOW.

5 FIRE RISER TO BASEMENT BELOW.

6 CONNECT SPRINKLERS SHOWN IN THE WALKWAY NEAREST

BUILDING 6 TO THE EXISTING BUILDING 6 SPRINKLER SYSTEM.

7 PAINT EXPOSED SPRINKLER PIPING IN THIS ROOM RED.

1/8" = 1'-0"

FIRE MAIN STEAM TUNNEL

1/8" = 1'-0"

DINING 125 SECTION

1/8" = 1'-0"

CORRIDOR 120C SECTION

Revisions: Date: 7/21/2021

STAMP

LN

DINING

RESIDENT 10

SITTING ALCOVE

10/11B

RESIDENT 11

RESIDENT 12

ELEC

HALLWAY

192C

TLT 11

178A

TLT 12

180A

LN

CLEAN

SITTING ALCOVE

12/13B

RESIDENT 9

TLT 9

173A

SITTING ALCOVE

6/7/8/9B

TLT 10

175A

RESIDENT 13

TLT 13

181A

RESIDENT 3

RESIDENT 14

TLT 3

162A

SITTING ALCOVE

3/4/5B

RESIDENT 2

SITTING ALCOVE

1/2B

RESIDENT 1

TLT 1

159A

TLT 2

160AGAS

POWER

EMERGENCY

POWER

EXAM RM

PT/KT

CORRIDOR

164C

LN

LN

LN

LN

PANTRY

168A

OFFICE

OFFICE

CONFERENCE

TLT 14

183A

STAFF LOUNGE

OFFICE

ADMIN HALL-B

CORRIDOR

162C

SOILED

MEDS

CRASH CART B

CHARGING B

STAFF TOILET/

SHOWER

HAC

RESIDENT 5

RESIDENT 4

TLT 4

163A

TLT 8

172A

TLT 7

171A

RESIDENT 8

TLT 5

164A

LIVING ROOM

PORCH B

RESIDENT 7

RESIDENT 6

(BARIATRIC)

TLT 6

170A

STORAGE

HOTELING

SITTING ALCOVE

14B

M A

T C

H

LI

E : 1

/F P

1A

MAIN PORCH

FP101B

REFER TO SHEET FP102 FOR

SPRINKLER LAYOUT IN CORRIDORS

WITH HIGH CEILINGS.

REFER TO SHEET FP102 FOR

SPRINKLER LAYOUT IN CORRIDORS

WITH HIGH CEILINGS.

FP101B

7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

8.6

AA

FIRE SPRINKLER MAIN

TO SHEET FP101A

FIRE RISER UP, REFER

TO SHEET FP102

FIRE SPRINKLER LEGEND

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

UPRIGHT SPRINKLER WITH CAGE

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

SPRINKLER

IN SOFFIT

UPRIGHT

SPRINKLERSPRINKLER MAIN

PIPING FOR

REFERENCE

UPRIGHT

SPRINKLER

SPRINKLER

PIPING SHOWN

FOR REFERENCE

N

KEY PLAN

AREA B

(EAST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:3

P

M

FP101B

FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS TMR

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

FIRE SPRINKLER FLOOR PLAN - LEVEL 1 - AREA B

KEYNOTES

1 SPRINKLER SHALL BE MOUNTED TO THE SOFFIT, ASSOCIATED

SPRINKLER PIPING SHALL BE ROUTED IN THE SOFFIT.

2 SPRINKLER ZONE VALVE ASSEMBLY, REFER TO DETAIL FOR MORE

INFORMATION.

3 INSPECTOR TEST DRAIN, REFER TO DETAIL FOR MORE

INFORMATION.

4 PAINT EXPOSED SPRINKLER PIPING IN THIS ROOM RED.

1/8" = 1'-0"

DINING 168 SECTION

1/8" = 1'-0"

CORRIDOR 164C SECTION

Revisions: Date: 7/21/2021

STAMP

MECH

PENTHOUSE

SPRINKLER

ZONE 2A

FP101A

FP101A

FP101B

FIRE RISER FROM

FLOOR BELOW

CHILLERS

201B

STAIRS

201A

APPROXIMATE

LOCATION OF

SPRINKLER PIPING

IN CORRIDORS

APPROXIMATE

LOCATION OF

SPRINKLER PIPING

IN CORRIDORS

FP101B

1 2 3 4 5 5.2 6

5.7

6.5 7 7.2 7.5 7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

FIRE RISER FROM

FLOOR BELOW

SPRINKLER

ZONE 2B

SPRINKLER

ZONE 2A

SPRINKLER

ZONE 2A

FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

SYSTEM

TYPE

DISCHARGE

DENSITY

REMOTE

AREA

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

WATER

SUPPLY

DURATION

OUTSIDE

HOSE

ALLOWANCE TEMPERATURE

CLASSIFICATION

SPRINKLER TYPE NOTES

GPM/FT² FT² FT² FT. MINUTES GPM

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY

SEMI-RECESSED PENDENT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

STORAGE

ORDINARY

HAZARD

GROUP 2

WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY

SEMI-RECESSED PENDENT OR

UPRIGHT, QUICK RESPONSE,

FACTORY MUTUAL APPROVED,

UL LISTED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE

QUICK RESPONSE

UPRIGHT, FACTORY MUTUAL

APPROVED, UL LISTED

HOUSEKEEPING

CLOSET

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

PENDENT OR UPRIGHT,

QUICK RESPONSE, FACTORY

MUTUAL APPROVED, UL LISTED

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

HAZARD

SYMBOL

1. MODIFY EXISTING SPRINKLER SYSTEM WITHIN THE LIMIT OF CONSTRUCTION AS

INDICATED ON THE CONTRACT DRAWINGS FOR THIS PROJECT. PROVIDE

TEMPORARY UPRIGHT SPRINKLER HEADS TO PROTECT SPACES WHERE CEILINGS

ARE REMOVED FOR CONSTRUCTION AND UNTIL NEW CEILINGS ARE INSTALLED AND

NEW DROPS TO NEW PENDENT SPRINKLER ARE INSTALLED. UNLESS OTHERWISE

INDICATED EXISTING FIRE PROTECTION SYSTEMS AND EQUIPMENT ARE TO REMAIN.

REFER TO ARCHITECTURAL DRAWINGS FOR PHASING AND WALL CONSTRUCTION.

2. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR

THE FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED

PER NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC

CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY

TO COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL

APPLICABLE CODES AND CRITERIA.

3. ALL FIRE PROTECTION WORK SHALL MEET ALL THE REQUIREMENTS OF NFPA 13, 14,

AND 101, VA FIRE PROTECTION DESIGN MANUAL, INTERNATIONAL BUILDING CODE

2018, AND APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES. WHERE

CONFLICTS BETWEEN CODE AND CONSTRUCTION DOCUMENTS OCCUR, THE MOST

RESTRICTIVE REQUIREMENTS SHALL GOVERN.

4. THE CONTRACTOR SHALL SUBMIT A SEPARATE PERMIT APPLICATION AND PLANS

FOR REVIEW ACCORDING TO NFPA 1 (2018 EDITION), SECTION 1.14.

5. A CONTRACTOR'S MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED IN

ACCORDANCE WITH NFPA 13 AND FORWARDED TO THE OWNER'S

REPRESENTATIVE.

6. ALL MATERIAL SHALL BE OF APPROVED QUALITY AND THE WORK SHALL BE DONE IN

A THOROUGH AND WORKMANLIKE MANNER. THE WORK, MATERIALS AND TEST

SHALL BE IN ACCORDANCE WITH THE CURRENT REQUIREMENTS OF NFPA 13,

LATEST EDITION.

7. THE SUBMISSION OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT THE

CONTRACTOR HAS FAMILIARIZED THEMSELVES WITH THE PLANS AND BUILDING

SITE. CLAIMS MADE SUBSEQUENT TO THE PROPOSAL FOR MATERIALS AND LABOR

BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED IF THEY

COULD HAVE BEEN FORSEEN HAD PROPER EXAMINATION BEEN MADE.

8. MAINTAIN THE INTEGRITY OF ALL FIRE AND SMOKE RATED WALLS, PARTITIONS,

CEILINGS, AND FLOOR ASSEMBLIES. SEAL ALL PENETRATIONS THROUGH RATED

ASSEMBLIES WITH FIRESTOP MATERIAL IN ACCORDANCE WITH UL REQUIREMENTS

TO MAINTAIN THE ASSEMBLY RATING. REFER TO ARCHITECTURAL DOCUMENTS

FOR LOCATIONS OF SMOKE AND/OR FIRE RATED WALLS; REFER TO PENETRATION

DETAILS FOR FIRE PROTECTION PIPING PENETRATIONS THROUGH RATED

ASSEMBLIES.

9. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE

REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL

WHO HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO

ARE REGULARLY EMPLOYED TO DO SUCH WORK.

10. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF RISERS,

CROSS MAINS, BRANCH LINES, AND SPRINKLER HEADS WITH ALL OTHER TRADE

SYSTEMS TO AVOID CONFLICTS AND MAINTAIN ARCHITECTURAL ELEMENTS OF THE

BUILDING. CONTRACTOR TO PROVIDE COORDINATION DRAWING TO COR PRIOR TO

CONSTRUCTION.

11. PIPE HANGERS SHALL BE SPACED AND LOCATED ACCORDING TO NFPA 13.

12. ALL BRANCH LINES SERVING ONE SPRINKLER SHALL BE 1" MINIMUM, UNLESS

OTHERWISE NOTED.

13. INSTALL ALL SPRINKLERS ACCORDING TO THEIR LISTINGS, SPACING, AND

OBSTRUCTION REQUIREMENTS.

14. COORDINATE SPRINKLER HEAD TYPES AND LOCATIONS WITH ARCHITECTURAL

FINISHES, CEILING, LIGHTING, DUCTS, PIPING, OTHER CEILING MOUNTED DEVICES,

AND STRUCTURAL COMPONENTS.

15. LIGHT FIXTURES AND HVAC DIFFUSERS TAKE PRECEDENCE. ADD ADDITIONAL

SPRINKLERS AT NO ADDITIONAL COST AND AS NECESSARY TO MEET COVERAGE

REQUIREMENTS IN ACCORDANCE WITH NFPA 13.

16. INSTALL SPRINKLERS IN THE CENTER OF CEILING TILES WHEN POSSIBLE. PROVIDE

RETURN BENDS AT ALL SPRINKLER LOCATIONS TO ALLOW FIELD ADJUSTMENT.

17. FOR MECHANICAL ROOMS, DETERMINE THE FINAL LOCATION OF SPRINKLERS

AFTER EQUIPMENT AND DUCTWORK ARE INSTALLED. PROVIDE ADDITIONAL

SPRINKLERS, IF NECESSARY, TO PROVIDE ADEQUATE COVERAGE IN ACCORDANCE

WITH NFPA.

18. PROVIDE A UL LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS ARE

SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,

ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL

SPRINKLERS INSTALLED BELOW 7'-0" AFF.

19. PIPING: SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE AND

FITTINGS CONFORMING TO ASTM A53. MINIMUM SIZE IS ONE (1") INCH. SCHEDULE 10

MAY BE USED FOR 2 1/2" AND LARGER. DO NOT THREAD THINWALL PIPE.

20. PIPE SUPPORTS: PROVIDE HANGERS, CLAMPS, RODS AND OTHER ACCESSORIES

OF AN APPROVED TYPE AND IN SUFFICIENT NUMBER TO PROPERLY SUPPORT ALL

PIPING. PIPING SHALL BE SUPPORTED BY ROUND WROUGHT U-TYPE APPROVED

ADJUSTABLE HANGERS.

21. SPRINKLERS SHALL BE FM APPROVED QUICK RESPONSE IN ALL AREAS EXCEPT

WHERE SPECIFICALLY PROHIBITED, IN COMPLIANCE WITH VA GUIDELINES AND NFPA

REQUIREMENTS.

22. SPRINKLERS SHALL BE 1/2" ORIFICE TYPE OF ORDINARY DEGREE RATING EXCEPT

WHERE EXCESSIVE TEMPERATURES ARE ANTICIPATED. IN THESE LOCATIONS

PROVIDE HIGH TEMPERATURE SPRINKLERS INSTALLED IN ACCORDANCE WITH NFPA

13. PROVIDE QUICK RESPONSE SPRINKLERS IN LIGHT HAZARD AREAS.

23. PROVIDE AND MAINTAIN A MINIMUM OF 18 INCHES CLEARANCE BETWEEN THE

BOTTOM OF THE SPRINKLER DEFLECTOR AND THE TOP OF STORAGE, FILES, ETC.

24. PAINT ALL EXPOSED FIRE SPRINKLER PIPING RED.

TITLEFIRE PROTECTION NOTESFIRE SPRINKLER LEGEND

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

UPRIGHT SPRINKLER WITH CAGE

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

KEY PLAN

AREA B

(EAST)

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:3

P

M

FP102

FIRE SPRINKLER OVERALL FLOOR PLAN -

PENTHOUSE

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

3/32" = 1'-0"

FIRE PROTECTION FLOOR PLAN - PENTHOUSE

HAZARD CLASSIFICATION

HAZARD CLASSIFICATION AREA

Equipment Room - Ordinary 1 3,875.08 SF

HAC - Ordinary 1 143.56 SF

Light 25,034.65 SF

Ordinary 2 1,360.84 SF

Revisions: Date: 7/21/2021

STAMP

FOYER

555 SF

RESIDENT 6

232 SF

RESIDENT 9

238 SF

TLT 9

127A

78 SF

DINING

499 SF

RESIDENT 11

247 SF

SITTING ALCOVE

11/12A

128 SF

RESIDENT 12

247 SF

RESIDENT 13

230 SF

ELEC

99 SF

TLT 12

131A

89 SF

TLT 13

133A

89 SF

LN

14 SF

SITTING ALCOVE

13/14A

127 SF

RESIDENT 10

231 SF

TLT 8

126A

78 SF

RESIDENT 1

248 SF

TLT 10

128A

89 SF

SITTING ALCOVE

8/9/10A

154 SF

TLT 11

130A

89 SF

RESIDENT 14

232 SF

TLT 14

134A

88 SF

RESIDENT 4

231 SF

TLT 6

119A

78 SF

RESIDENT 5

238 SF

TLT 4

117A

89 SF

SITTING ALCOVE

4/5/6/7A

209 SF

RESIDENT 3

247 SF

SITTING ALCOVE

2/3A

131 SF

RESIDENT 2

247 SF

TLT 2

114A

89 SF

TLT 3

115A

89 SF

LOBBY

166 SF

PANTRY

125A

90 SF

RESIDENT 13

231 SF

TLT 13

181A

89 SF

RESIDENT 14

225 SF

FAMILY TOILET

66 SF

STORAGE

70 SF

STERILE SUPPLY

STORAGE

123 SF

PT/KT

348 SF

CLEAN

69 SF

CENTRAL KITCHEN

68 SF

ACTIVITY

553 SF

LN

14 SF

LN

7 SF

LN

14 SF

LN

14 SF

LN

14 SF

CORRIDOR

120C

536 SF

MECHANICAL

145 SF

PORCH-A

336 SF

LIVING ROOM

402 SF

MAIN PORCH

1815 SF

IT CLOSET

142 SF

CONFERENCE

276 SF

MEDS

136 SF

PUBLIC TOILET

63 SF

SOILED

71 SF

TLT 1

110A

88 SF

TLT 14

183A

89 SF

HOTELING

209 SF

STAFF LOUNGE

184 SF

OFFICE

112 SF

ADMIN HALL-B

90 SF

CRASH CART

54 SF

CHARGING A

34 SF

SALON

150 SF

WHEELCHAIR/

STRETCHER STRG

106 SF

HALLWAY

209C

160 SF

CLC WALKWAY

483 SF

STAFF TOILET/

SHOWER

76 SF

HAC

68 SF

TLT 5

118A

78 SF

RESIDENT 8

221 SF

RESIDENT 7

(BARIATRIC)

254 SF

TLT 7

120A

91 SF

M A

T C

H

LI

E : 1

/F H

1B

MATCHLINE

SEE: 2/FH101A

CLC WALKWAY

483 SF

STORAGE

82 SF

CORR

59 SF

SCREENING

VESTIBULE

1 2 3 4 5 5.2 65.7 6.5

7 7.2 7.5

7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

D

C.4

C.8

C.1

C

B

A.5

A

7.86.6 7.1 7.6 8.6

AA

7.76.8

FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

SYSTEM

TYPE

DISCHARGE

DENSITY

REMOTE

AREA

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

WATER

SUPPLY

DURATION

OUTSIDE

HOSE

ALLOWANCE TEMPERATURE

CLASSIFICATION

SPRINKLER TYPE NOTES

GPM/FT² FT² FT² FT. MINUTES GPM

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY

SEMI-RECESSED PENDENT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

STORAGE

ORDINARY

HAZARD

GROUP 2

WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY

SEMI-RECESSED PENDENT OR

UPRIGHT, QUICK RESPONSE,

FACTORY MUTUAL APPROVED,

UL LISTED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE

QUICK RESPONSE

UPRIGHT, FACTORY MUTUAL

APPROVED, UL LISTED

HOUSEKEEPING

CLOSET

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

PENDENT OR UPRIGHT,

QUICK RESPONSE, FACTORY

MUTUAL APPROVED, UL LISTED

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

HAZARD

SYMBOL

TLT 14

134A

88 SF

LN

7 SF

MECHANICAL

145 SF

CLC WALKWAY

483 SF

MATCHLINE

SEE: 1/FH101A

B6 WALKWAY

CLC WALKWAY

483 SF

7 7.2 7.5

G.2

G.3

F

E.4

E.2

E

SPRINKLERS NOT

REQUIRED IN PIPE

BASEMENT

BASEMENT

BASEMENT ON ZONE 0

SPRINKLER SYSTEM

345 SF

TUNNEL EAST LEG,

REFER TO DEDUCT

ALTERNATE 2 NOTE

7 7.2 7.5

7.9 8 8.5 9

G.2

G.3

F

E.4

E.2

D.7

E

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

(DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE EXCERCISED

IN THE ORDER PRESENTED) FOR A DETAILED DESCRIPTION OF EACH

DEDUCTIVE ALTERNATE REFER TO COVER SHEET ON GI000

DEDUCTIVE ALTERNATE #2 : ELIMINATE TUNNEL (EAST LEG).

DEDUCTIVE ALTERNATE NOTES

N

KEY PLAN

AREA A

(WEST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:5

P

M

FH101A

FIRE PROTECTION HAZARD PLAN - LEVEL 1 -

AREA A

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - LEVEL 1 - AREA A

HAZARD CLASSIFICATION

HAZARD CLASSIFICATION AREA

Equipment Room - Ordinary 1 3,875.08 SF

HAC - Ordinary 1 143.56 SF

Light 25,034.65 SF

Ordinary 2 1,360.84 SF

1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - LEVEL 1 - COVERED WALKWAY

1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - BASEMENT

Revisions: Date: 7/21/2021

STAMP

LN

10 SF

DINING

498 SF

RESIDENT 10

246 SF

SITTING ALCOVE

10/11B

130 SF

RESIDENT 11

245 SF

RESIDENT 12

227 SF

ELEC

98 SF

HALLWAY

192C

162 SF

TLT 11

178A

89 SF

TLT 12

180A

89 SF

LN

14 SF

CLEAN

81 SF

SITTING ALCOVE

12/13B

132 SF

RESIDENT 9

231 SF

TLT 9

173A

89 SF

SITTING ALCOVE

6/7/8/9B

195 SF

TLT 10

175A

88 SF

RESIDENT 13

231 SF

TLT 13

181A

89 SF

RESIDENT 3

234 SF

RESIDENT 14

225 SF

TLT 3

162A

89 SF

SITTING ALCOVE

3/4/5B

149 SF

RESIDENT 2

226 SF

SITTING ALCOVE

1/2B

127 SF

RESIDENT 1

227 SF

TLT 1

159A

85 SF

TLT 2

160A

89 SF

FAMILY TOILET

66 SF

GAS

56 SF

POWER

95 SF

EMERGENCY

POWER

115 SF

EXAM RM

98 SF

PT/KT

348 SF

CORRIDOR

164C

868 SFLN

14 SF

LN

14 SF

LN

14 SF

LN

8 SF

MAIN PORCH

1815 SF

PANTRY

168A

94 SF

OFFICE

116 SF

OFFICE

124 SF

CONFERENCE

276 SF

TLT 14

183A

89 SF

HOTELING

209 SF

STAFF LOUNGE

184 SF

OFFICE

112 SF

ADMIN HALL-B

90 SF

CORRIDOR

162C

943 SF

SOILED

94 SF

MEDS

142 SF

CRASH CART B

53 SF

CHARGING B

35 SF

WHEELCHAIR/

STRETCHER STRG

106 SF

STAFF TOILET/

SHOWER

76 SF

HAC

76 SF

RESIDENT 5

219 SF

RESIDENT 4

244 SF

TLT 4

163A

81 SF

TLT 8

172A

78 SF

TLT 7

171A

78 SF

RESIDENT 8

239 SF

TLT 5

164A

81 SF

LIVING ROOM

390 SF

PORCH B

319 SF

RESIDENT 7

230 SF

RESIDENT 6

(BARIATRIC)

257 SF

TLT 6

170A

87 SF

M A

T C

H

LI

E : 1

/F H

1A

STORAGE

82 SF

CORR

59 SF

7.9 8 8.5 9 9.8 10 119.9 11.4 1211.8

G.2

G.3

13 13.2 14 15 16

F

E.4

E.2

D.7

E

16.2

D

C.4

C.8

C.1

C

B

A.5

A

8.6

AA

FIRE PROTECTION SPRINKLER SYSTEM DESIGN CRITERIA

SPACE TYPE

HAZARD

CLASSIFICATION

SYSTEM

TYPE

DISCHARGE

DENSITY

REMOTE

AREA

MAXIMUM

COVERAGE

AREA PER

SPRINKLER

MAXIMUM

SPACING

WATER

SUPPLY

DURATION

OUTSIDE

HOSE

ALLOWANCE TEMPERATURE

CLASSIFICATION

SPRINKLER TYPE NOTES

GPM/FT² FT² FT² FT. MINUTES GPM

GENERAL,

EXCEPT AS

LISTED BELOW

LIGHT HAZARD WET PIPE 0.10 1,500 225 15 30 100 ORDINARY

SEMI-RECESSED PENDENT, QUICK

RESPONSE, FACTORY MUTUAL

APPROVED, UL LISTED

STORAGE

ORDINARY

HAZARD

GROUP 2

WET PIPE 0.20 1,500 130 15 60-90 250 ORDINARY

SEMI-RECESSED PENDENT OR

UPRIGHT, QUICK RESPONSE,

FACTORY MUTUAL APPROVED,

UL LISTED

EQUIPMENT

ROOM

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 INTERMEDIATE

QUICK RESPONSE

UPRIGHT, FACTORY MUTUAL

APPROVED, UL LISTED

HOUSEKEEPING

CLOSET

ORDINARY

HAZARD

GROUP 1

WET PIPE 0.15 1,500 130 15 60-90 250 ORDINARY

PENDENT OR UPRIGHT,

QUICK RESPONSE, FACTORY

MUTUAL APPROVED, UL LISTED

NOTES:

1. WATER DEMAND REQUIREMENTS ARE FOR HYDRAULIC CALCULATION METHOD. IF OTHER METHOD IS USED ADJUST VALUES ACCORDING TO NFPA 13 REQUIREMENTS.

HAZARD

SYMBOL

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

N

KEY PLAN

AREA B

(EAST)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

550 North Reo Street, Suite 203 Tampa, FL 33609

(813) 289-4700 Nicholas Stephenson, PE

Structural 315 West James Street, Suite 102 Lancaster, PA 17603

(717) 481-2991 Jason Vannoy, SE, PE

Protective Design Specialist 240 West 35th St. Suite 1004 New York, NY 10001

(212) 967-4890 Corrine Tan, SE

Landscape Architect 418 North Toole Avenue Tucson, AZ 85701

(520) 622-9565 Josh Orth., PLA

B

IM

/6

-3

N e w

C o m m u n it y L iv in g C e n te r/

M

E P

V

A M o n tr o s e C

L C

R

.r v t

/2

/2

:3

:0

P

M

FH101B

FIRE PROTECTION HAZARD PLAN - LEVEL 1 -

AREA B

TRIPLE C - The A/E Group

201 E. Jefferson Street, Suite 200

Syracuse, NY 13202

(315) 484-5958

Mat Perkins

620-334

CLC

07/21/2021 CJF/NPS NS

NEW COMMUNITY LIVING

CENTER

2094 Albany Post Road, Montrose, NY 10548

ISSUED FOR

CONSTRUCTION

1/8" = 1'-0"

FIRE PROTECTION FLOOR PLAN - LEVEL 1 - AREA B

HAZARD CLASSIFICATION

HAZARD CLASSIFICATION AREA

Equipment Room - Ordinary 1 3,875.08 SF

HAC - Ordinary 1 143.56 SF

Light 25,034.65 SF

Ordinary 2 1,360.84 SF

Revisions: Date: 7/21/2021

STAMP

File details come from the government source that posted it. Updated .