Condition_Assessment_-_A-004.pdf

PDF 908 KB Posted

Attached to
Food & Beverage Concessions
Solicitation number
26-021-RFP Conc
Issued by
Kenton County, Kentucky

About this file

This is a Condition Assessment report for the PANDA Combined facility at Cincinnati/Northern Kentucky International Airport (CVG), conducted by the Kenton County Airport Board (KCAB) in Kentucky. The assessment evaluates the physical condition of the food and beverage concessions space across multiple building systems and components, rating each item on a scale from 1 (Critical) to 5 (New). The facility is currently in rough overall condition, with significant maintenance and replacement needs identified throughout the interior and mechanical systems. Critical findings include extremely worn wall finishes with heavy grease staining in work areas, broken and stained ceiling tiles and flooring, deteriorated plumbing infrastructure requiring replacement, and non-functional HVAC equipment. The assessment documents existing conditions to inform the Food & Beverage Concessions contract opportunity, for which proposals are due by June 25, 2026, with a pre-proposal site visit scheduled for April 21, 2026.

The condition assessment identifies multiple capital improvement requirements that prospective food and beverage concession operators should anticipate. Priority replacement items include rooftop air conditioning unit RTU#1 (noted as in terrible shape), grease traps requiring replacement, water heater and backflow preventer upgrades, copper piping replacement in the plumbing system, ceiling tile remediation, flooring repairs including broken and stained VCT tile, and wall finish restoration. Secondary maintenance needs include cleaning and servicing of exhaust fans, adding hail guards to RTU#2, securing loose handrails, modernizing old signage, and addressing water leaks caused by missing access panel screws. Equipment such as the Hoshizaki ice machine (approximately twenty years old) and refrigeration units may require replacement or significant maintenance to return to operational status. The assessment provides the physical baseline condition against which bidders can evaluate their financial obligations and operational requirements for the concessions operation.

View the file

Other files

File Type Posted
Food_&_Beverage_Concessions.pdf PDF
Proposed_Agreement_-_Food_&_Beverage_Concession.pdf PDF
2026.03.24_RFP_Release_Technical_Design_Criteria_Manual.docx DOCX document
PROTECTED_CVG_ProForma_Template_BLANK_3.2.26.xlsx XLSX spreadsheet
Proforma_Instruction_Guide_3.2.26.docx DOCX document
2025_Airline_Rankings.xlsx XLSX spreadsheet
2025_Monthly_Enplanements.xlsx XLSX spreadsheet
Condition_Assessment_Summary.pdf PDF
Condition_Assessment_-_A-031.pdf PDF
KCAB_-_RSVP_Instructional_Guide_for_OpenGov.pdf PDF
Condition_Assessment_-_A-015.pdf PDF
LOD_A-015.pdf PDF
LOD_A-004.pdf PDF
LOD_A-031.pdf PDF
CVG_Flight_Schedule_Summary_2025_06.30_-_07.06.pdf PDF
XX-XXRFP_Food_&_Beverage_Multi_Unit_Concessions_4.24.25_DRAFT.docx DOCX document
2024_Monthly_Enplanements.xlsx XLSX spreadsheet
2024_Airline_Rankings.xlsx XLSX spreadsheet
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONDITION ASSESSMENT

5 NEW SURVEY DATE

4 GOOD

3 FAIR

2 POOR

1 CRITICAL

5 4 3 2 1 N/A

1 X

2 X

3 X

4 X

5 X

6 X

7 X

8 X

9 X

10 X

11 X

12 X X

13 X

14 X

15 X 16 X 17 X

18 X

19 X X

20 X

21 X

22 X X

23 X

24 X

25 X

26 X

27 X

28 X

29 X X

30 X

31 X

32 X

33 X

34 X

35 X

36 X

37 X

38 X X

39 X

40 X

41 X

43 X

44 X

45 X

ADDRESS:B Conc.

FACILITY NAME: PANDA COMBINED

INFOR ASSET NUMBER:

CONDITION

PHOTO REF

COMMENTS / RECOMMENDED ACTION

Interior

Windows One front window appears to be in good condition

SURVEYORS Facilities

REPORT

GENERATED BY:Extremely worn or damaged; replace in next 2 Yrs.

Average wear for building age; not new but no issues to report

New or like new condition; no issues to report; no expected failures.

Good condition; no reported issues or concerns;

Worn from use -end of expected lifecycle. Replace within 2 - 4 yrs. when funds are available

Main Entry Hardware Gate control is key operated Other Exterior Doors Other Exterior Door Hardware

Curtain Wall Systems East & West wall no problems Louvers and Vents Main Entry Doors No entry main doors, only roll-up gate

Wall Finishes (Restrooms) Wall Finishes Work Areas Extremely greasy and dirty, heavy staining Cabinetry

Specialty Doors Wall Finishes - Offices No office space Wall Finishes (Corridors)

Hallway Fire Doors Tenant Security Gates / Roll-up Doors Roll up gate seems to be ok, did not operate Ceiling (Grid, tile, hard) Broken, missing, and stained tiles

Moveable / Operable Walls Door & Frame Condition Hardware Condition Key controls for entry gate in good condition

Terrazzo

Sealed Concrete

Other Overall, space is in rough condition

Carpet

VCT

Tile Broken, stained, heavy grease, stained grout

Handrails Old handrail bolted to floor, needs re-secured

Restroom Accessories Toilet Partitions

Stairwells Stair treads Stair nosings

ADA Accessibility (Large Stall)

Water Closets

Screen Partitions Walls No holes, just heavy staining, grease covered

Signage Old signage still in place

Plumbing

Sanitary Piping

Water Heaters

Tanks

Urinals

Lavatories / Sinks needs chrome trap. No plastic!

ADA Fixture Provisions (heights)

Booster Pumps (Vented interior regulators?)

Insulation

Backflow Backflow could use replaced

5 4 3 2 1 N/A

CONDITION

PHOTO REF

COMMENTS / RECOMMENDED ACTION

46 X

47 X

48 X

49 X

50 X X

51 X

52 X X

53 X

54 X

55 X

56 X

57 X

58 X

59 X

60 X

61 X

62 X

63 X

64 X

65 X

66 X

67 X

68 X

69 X

70 X

72 X

76 X

77 X

82 X

83 X X

84 X

85 X

86 X

87 X

Custodial Closets (Mop Sinks)

Auxiliary Sinks

Eyewash/Emerg. Shower (Floor drains/Tepid Water)

Storage rooms

Boilers (Age, Fuel Type, Input/Output)

Pumps (VFD / Sound / Suction Pressure) copper piping should be replaced

Grease Traps (Indoor/outdoor?) old and covered in grease needs replaced

Water Fountains

Lift Stations / Septic System

Kitchenettes (POU Grease Trap?)

Showers (Self metering? Shutoff?}

Roof Drain Piping

HVAC

Water Heaters (dedicated or part of bldg htg?)

Dedicated Heater for Kitchen

Water Heaters (Age / Fuel Type / Tankless / Capacity)

Piping & Valves (Corroded, Isolation Valves?)

Water Treatment

Boiler Room E-Stop

Makeup Water: Secondary Backflow Preventer

Duct Furnaces (Fuel, Type, Age, Mission)

Unit Heaters (Fuel, Type, Age, Mission)

Heating-Only Unit Ventilators (year, condition) was able to get motor to turn on but was not able to get heater to fire up. No data plate was located so MFD and manufacture can not be determined. Duct work for this unit is in good condition but may want to clean inside and invetiga

Tanks (Age / Size)

Recirculation Pump (Operating- Yes/No?)

Heating-Only Air Handling Units (Age)

Ventilation Airflow Monitoring (Last calibrated?)

Controls

Exhaust Fan / Exhaust Hoods There are two exhaust fans that both currently work. They both need some regular maintenance (new belt, bearings greased, etc). EF-1 needs the grease cleaned from the unit as well and both will need the fan blades cleaned.

Outside Air Units (Age, HR Type, ERV, Unitary, VAV)

Rooftop ACUs (Age, Gas Heat or Heat Pump)

There are two rooftop units that serve this space. RTU#2 is in decent shape and feeds the main kitchen and out front in the lobby area. I would recommend getting hail guards for the condensor to try and protect it better and have the unit cleaned and maintained to increase longevity of this unit. The panels on this unit are missing a few screws which has led to some new water leaks inside the space. RTU#1 is powered down and in terrible shape. This unit has had problems in the past which is evident because of an old compressor that is still sitting in this unit and the wiring that is dangiling inside the access panels. This unit appears older than unit #2 and I would recommend replacement.

AHUs (Age, Type/Geometry, VAV, typ. SAT, dual path unit)

Other (Vented Interior Regulators?)

Gas PRV (Proximity to OA intakes?)

Switchgear

RTU-product freezer These units are currently turned off but were working very well before they were turned off. The inside units are in very good shape and only require basic maintenance to keep units going.The line set needs new insulation.

Piping

Gas Delivery

Electrical

Feeders

Wiring/Conduit

Transformers Needs to be moved into tenant space V3

Identify Multiple Service Feeds

Panels No flash ratings

5 4 3 2 1 N/A

CONDITION

PHOTO REF

COMMENTS / RECOMMENDED ACTION

88 X x

89 X

90 X

91 X

93 X

104 X

130 0 2 10 13 8 51

Devices (Switches & Receptacles)

Transformers

Lighting

Airport Security/Card Readers

TSS - Surge Suppression

Generator

UPS

Technology

Fire Alarm System

Sprinkler System

Fire Extinguishers

Airport Security Camera

Audio Enhancements

Cable management

Safety

Refrigeration There is one Hoshizaki ice machine in this space that is disassembled and unplugged so the unit may only need some maintenance to get the unit started.

The unit is almost twenty years old and may just need to be replaced.

Air Compressors

CO2 Detection System

Kitchen equipment

Other

Facility Condition Assessment
Sheet1