B01 RFP Attachment J01a Drawings (2).pdf

PDF 5 MB Posted

Attached to
Kyle Health Center ASHRAE 170 Upgrades and Roof Replacement
Solicitation number
75H70126R00004
Issued by

About this file

These documents are architectural and engineering design drawings for the Kyle Clinic Health Center Addition project located in Kyle, South Dakota, prepared by TSP, Inc. in April 2017. The project involves a comprehensive renovation and expansion of an existing healthcare facility, with multiple detailed sets of drawings covering structural, mechanical, electrical, and lightning protection systems.

Key technical details include a new first-level addition with various medical spaces like exam rooms, dental operatories, nursing areas, and support spaces. The mechanical systems feature an air handling unit (AHU-1) with 3,135 CFM airflow, variable air volume (VAV) terminal units, and hydronic piping. The electrical design includes a new electrical distribution system with panels, a generator, and automatic transfer switches. The lightning protection plan covers comprehensive grounding and bonding methods for the building, with air terminals, conductors, and connections designed to protect the facility from electrical hazards. The project appears to be for the Indian Health Service (IHS) and involves upgrading and expanding the existing Dakota Plains Kyle Clinic Health Center.

View the file

Other files

File Type Posted
B05 Amend A00009.pdf PDF
REVISED Attachment J07 Bid Schedule.xlsx XLSX spreadsheet
REVISED Attachment J07 Bid Schedule.xlsx XLSX spreadsheet
B05 Amend A00008.pdf PDF
B01 Attachment J02 Wage Determination SD20260017.pdf PDF
B05 Amend A00007.pdf PDF
B05 Amend A00006.pdf PDF
B05 Amend A00005.pdf PDF
B05 Amend A00004.pdf PDF
Pre-Construction Risk Assessment.docx DOCX document
B05 Amend A00003.pdf PDF
KYLE_ICRA MAP.pdf PDF
Infection Control Risk Assessment.docx DOCX document
Revised B01 RFP Attachment J07 BID SCHEDULE.xlsx XLSX spreadsheet
Kyle as built LPS.pdf PDF
KHC_STRUC ONLY.pdf PDF
KHC_ELEC ONLY.pdf PDF
Example Specification.pdf PDF
B05 Amend A00002.pdf PDF
KHC_FIRE SPRINKLER.pdf PDF
KHC_CIVIL ONLY.pdf PDF
KHC_ARCH ONLY.pdf PDF
KHC ADDITION.pdf PDF
Revised B01 RFP Attachment J02 SD20250017.pdf PDF
KHC_MECH ONLY.pdf PDF
Revised B01 RFP Attachment J07 Bid Schedule.xlsx XLSX spreadsheet
B05 Amend A00001.pdf PDF
B01 RFP Attachment J05 PPQ.docx DOCX document
B01 RFP Attachment J06 IHS IEE Representation Form.pdf PDF
B01 RFP 75H70126R00004.pdf PDF
B01 RFP Attachment J01a Drawings (3).pdf PDF
B01 RFP Attachment J01c ICRA MAP.pdf PDF
B01 RFP Attachment J03 Self Performed Calculation Sheet (Construction).docx DOCX document
B01 RFP Attachment J01 Drawings (1).pdf PDF
B01 RFP Attachment J02 Wage Determination SD20250017.pdf PDF
B01 RFP Attachment J04 Company Specialized Experience Construction Form.pdf PDF
B01 RFP Attachment J07 BID SCHEDULE.xlsx XLSX spreadsheet
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FO

R

D

EP

TH

R

EF

S

C

HE

DU

LE

REF MASONRY LINTEL

SCHEDULE FOR REINF

REINF AND GROUT

CORES FULL HGT- REF

SCHEDULE FOR JAB CONSTR

2"

CONTROL JOINT WHERE

INDICATED ON ARCH DRAWINGS

END WALL & JAMBS CORNER

3000 PSI

CONC

1-#5 BAR

C BLOCKL

REF GENERAL NOTES FOR

SIZE & SPACING OF REINF.

REINF SHALL BE DOWELED

INTO FOOTING OR

FOUNDATION WALL

MASONRY LINTEL SCHEDULE

MARK DESCRIPTION DETAIL REMARKS

L1

ADDITIONAL REMARKS:

1. PROVIDE MIN. 8" BEARING AT ALL STEEL LINTELS, UNO (REF DETAIL B3/S-501)

2. EXTEND CMU LINTEL REINF PAST OPNG THRU ALL GROUT FILLED CORES OF JAMBS (REF DETAIL B5/S-501)

3. REFERENCE GENERAL STRUCTURAL NOTES ON S-001 FOR TYPICAL LINTELS FOR MECH, ELEC, AND OTHER OPENINGS NOT SHOWN. COORD OPENING SIZES AND LOCATIONS WITH MECH, ELEC AND ARCH.

4. GROUT MASONRY LINTELS FULL.

5. DO NOT PLACE CONDUIT WITHIN MASONRY LINTELS.

6. GALVANIZE ALL EXTERIOR STEEL LINTELS.

2" 16 " D

EE

P

PROVIDE FULL HGT JAMBS EA SIDE

W/ (2) FULLY GROUTED CORES

W/ (1) #5 PER CORE

16" DEEP LINTEL

REINF w/ (2) #4

L2

2" 24 " D

EE

P

24" DEEP LINTEL

REINF w/ (2) #4

PROVIDE FULL HGT JAMBS EA SIDE

W/ (2) FULLY GROUTED CORES

W/ (1) #5 PER CORE

D S

2S

D

CONT REINF TO

MATCH CONT

FTG REINF

SLEEVE THROUGH WALL MIN 2"

LARGER DIA THAN PIPE

-REF PLAN FOR LOCATIONS

-INSULATE AROUND PIPE

M

IN6"

MIN

6"

3" M

IN

BRG

6"

CMU WALL

(REF PLAN)

PROVIDE BACKER ROD

AT END OF ANGLE TO

ALLOW MOVEMENT

PROVIDE BOND BREAKER

BETWEEN BOTTOM OF

LINTEL AND MORTAR

INSTALL FLEXIBLE JOINT

SEALANT AND BACKER ROD

BRICK ANGLE

(REF PLAN)

CONTROL JOINT

AS OCCURS

EXT NON-BRG BRICK/CMU

ANGLE SCHEDULE

SPAN STEEL ANGLE REMARKS

6'-4" AND SMALLER

6'-5" TO 8'-4"

ADDITIONAL REMARKS:

1. ALL LINTELS TO BEARING A MINIMUM OF 6" ON SOLID MASONRY.

2. REFERENCE DETAIL A5/S-501 FOR BEARING CONDITIONS AT CONTROL JOINTS. REFERENCE ARCH FOR

CONTROL JOINT LOCATIONS.

3. GALVANIZE ALL EXTERIOR LINTELS.

L4x4x1/4"

L6x4x3/8" (LLV)

VERTICAL LEG OF ANGLE BACKED

UP TO EXTERIOR FACE OF CMU

VERTICAL LEG OF ANGLE BACKED

UP TO EXTERIOR FACE OF CMU

BEAM/COLUMN

ADDITIONAL REMARKS:

1. FOR CONNECTIONS SHOWN IN THIS SCHEDULE THE SUPPORTED MEMBER SHALL HAVE A MAXIMUM TOP COPE OF 2" DEEP AND 6" LONG. MINIMUM HORIZONTAL EDGE DISTANCE TO THE CENTER OF THE BOLT HOLES IS 1 1/2". MINIMUM VERTICAL EDGE DISTANCE TO THE CENTER OF BOLT HOLES IS 1-1/4".

2. FOR SHEAR TAB CONNECTIONS WHT SUPPORTING MEMBER WEB THICKNESS GREATER THAN 3/4" US 3/8" WELD AND 7/16" PL.

3. SINGLE ANGLE CONNECTION USED ONLY WHEN NOTED ON PLAN.

BEAM/BEAM

1/

4"

CL BEAM/GRID

REF BEAM CONNECTION

SCHEDULE FOR BOLT SIZE &

QUANTITY OF ROWS

1 1/2"

STEEL BEAM

(REF PLAN)

1/2"

1 1/2" t t

REF SCHED

1 1/2" 1 1/2"

CL BEAM/GRID

REF BEAM CONNECTION

SCHEDULE FOR BOLT SIZE &

QUANTITY OF ROWS

STEEL BEAM

(REF PLAN)1/2"

t t

REF SCHED

SINGLE PLATE

BEAM CONNECTION SCHEDULE

BEAM

SIZE

PLATE

SIZE

WELD

SIZE

ROWS OF

3/4"Ø A325-N

BOLTS

REMARKS

W8, W10 PL 1/4"X3 1/2"X5 1/2" 3/16" ---

W12, W14 PL 1/4"X3 1/2"X8 1/2" 3/16" ---

W16 PL 5/16"X3 1/2"X11 1/2" 1/4" ---

W18 PL 5/16"X3 1/2"X1'-2 1/2" 1/4" ---

W21 PL 5/16"X3 1/2"X1'-5 1/2" 1/4" ---

W24, W27 PL 5/16"X3 1/2"X1'-8 1/2" 1/4" ---

W30 PL 5/16"X3 1/2"X1'-11 1/2" 1/4" ---

W33 PL 3/8"X3 1/2"X2'-2 1/2" 1/4" ---

STRUCT COL

(REF PLAN)3"

S

PA

1/

4" 1 1/

4"3" S

PA

1/

4"

OUTSIDE DEEP

LEG 18GA TOP

TRACK, TYP

STEEL JOIST

(REF PLAN)

STEEL STUD WALL

STEEL DECK (REF PLAN)

INSIDE DEEP LEG 18 GA TOP

TRACK - SNUG TIGHT ONLY -

NO CONNECTION OF DEEP

LEG TRACK TO TOP TRACK

STEEL DECK (REF PLAN)

STEEL JOIST

(REF PLAN)

INSIDE DEEP LEG 18 GA TOP

TRACK - SNUG TIGHT ONLY - NO

CONNECTION OF DEEP LEG

TRACK TO TOP TRACK

OUTSIDE DEEP

LEG 18 GA TOP

TRACK, TYP

STEEL STUD WALL

MIN

8"

AT ONE END ONLY PROVIDE

SLOTTED HOLES IN BEAM

FLANGE & GREASE SURFACE

BETWEEN BEAM & BRG PLATE

PL 3/8"X6"X6" BRG

(2) 5/8"Ø HAB (5" EMBED)

GROUT & REINF 2 CORES MIN

(REF PLANS / GEN NOTES)

LINTEL BEAM AND

PLATE (REF PLAN) 5"

2'-0"

3" CLR

DRAINAGE COURSE

D

45°

ST

EP

V

AR

IE

S

20K4SP

125 150 275 SP1 = MECH UNIT DL

SPECIAL LOADS

SL TOTALDL

UNIFORM JOIST LOADS (PLF)

SIZE

SPECIAL JOIST LOADING SCHEDULE

P1 P1

P1 = 550 LBS

REF PLAN

UNIT

MECH REF PLAN

SP1

CONC SLAB ON METAL DECK

BEARING PL3/4"X8"X8" W/

(2)3/4"X7" EMBED HAB ATOP

1-1/2" NSNM GROUT

CONTINUE WALL & CONT FTG

REINF THRU PIER- REF EXTERIOR

FOUNDATION DETAIL

TOF

REF PLAN

GRID

GEOTECH APPROVED STIFF SILT SOILS

OR ENGINEERED FILL (REF S-001)

1" 2 1/2"

(3)#4 TIES @3"OC AT TOP

AROUND ANCHORS, THEN #4

TIE @ 12"OC (WRAP TIES

BACK PAST WALL REINF)

(4)#7 VERT/L-BAR

EACH CORNER

1' -1

0" A

PP

RO

X.

3/8" WEB STIFFENERS

EACH SIDE

SLOTTED HOLE

IN BEAM FLANGE

10"

SQ

1'-0"

EXIST FND

WALL

-VERIFY

EXISTING

CRAWLSPACE

TOC/FIRST LEVEL

REF PLAN

GRID

REF PLAN

6" 1'

-0

#5 DOWELS @ 12"OC- DRILL

& EPOXY SET (6" EMBED)

(2)#5X12"X12" DOWELS

TOP &BOT- DRILL &

EPOXY SET (4" EMBED)

#5 @ (4) LOC

SHOWN

EXIST TOF

VERIFY

GEOTECH APPROVED STIFF SILT SOILS

OR ENGINEERED FILL (REF S-001)

CONC SLAB ON METAL DECK

BEARING PL3/4"X8"X8" W/

(2)3/4"X7" EMBED HAB ATOP

1-1/2" NSNM GROUT

(3)#3 TIES @ 3"OC AT TOP

AROUND ANCHORS, THEN

#3 TIE @ 12"OC

(4)#6 VERT/L-BAR

EACH CORNER

3/8" WEB STIFFENERS

EACH SIDE

SLOTTED HOLE

IN BEAM FLANGE 1"2 1/2"

1' -1

0" A

PP

RO

X.

4" 4"

L2x2x3/16"

EA SIDE, TYP

STEEL

JOISTS 1/2"Ø A36 THD

ROD, TYP

UNISTRUT PER

EQUIPMENT SUPPLIER

OR L3X3X1/4"

L2x2x1/4" BRACING EACH END

SUPPLIER'S DRAWINGS

PER EQUIP

SUPPLIER'S DRAWINGS

PER EQUIP

SUPPLIER'S DRAWINGS

PER EQUIP

UNISTRUT PER

EQUIPMENT

SUPPLIER OR

L3X3X1/4"

L3x3x1/4" BRACING, TYP (MATCH THD

ROD SUPPORT SPACING)

1/2" DIA A36

THD ROD AT EACH

ANCHOR LOCATION-

COORDINATE W/

EQUIPMENT

PL1/4"x3" TYP

(VERIFY WIDTH)

L2x2x1/4" BRACING, TYP (MATCH THD

ROD SUPPORT

SPACING)

(4)1/2"Ø A36 THD RODS, TYP

L3x3x1/4" CONT AT EACH

THREADED ROD LINE

3/16"

TYP

LIGHT/EQUIPMENT MOUNT-

COORD LOC & LENGTHS OF

EQUIP SUPPORTS WITH

INSTALLATION REQUIREMENTS

L3X3X1/4" BRACING BACK

TO JOIST PANEL POINTS IN TWO

PERPENDICULAR DIRECTIONS

STEEL

JOISTS

L3x3x1/4" CONT AT EACH

THREADED ROD LINE

LIGHT/EQUIPMENT MOUNT-

COORD LOC & LENGTHS OF

EQUIP SUPPORTS WITH

INSTALLATION REQUIREMENTS

L3X3X1/4" BRACING BACK

TO JOIST PANEL POINTS IN TWO

PERPENDICULAR DIRECTIONS

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NOT

FO

R

CONSTR

UCTI

ON

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

ST

ED

D

R

AW

IN

G

S

SC

AL

E(

S) U

N

LE

SS

R

ED

U

C

ED

F R

O M

O R

IG

IN

AL

x

F

O

RM

AT

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

4/ 7/

1:

:0

A

M I:\

_T S

P R ev it

Lo ca l\0

D ak ot a P la in s

K yl e C lin ic

S

_W ei er sA

R .r vt

SCHEDULES &

DETAILS

S-501

0%

D

ES

IG

N

D O

C U

M

EN

TS

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

ARW04/07/2017

CSH03161153

SCALE: 3/4" = 1'-0"

B5

TYPICAL LINTEL BEARING DETAIL

SCALE: 3/4" = 1'-0"

A3

TYPICAL CORE REINF DETAIL

SCALE: 3/4" = 1'-0"

B4

SCHEDULE - MASONRY LINTEL

SCALE: 3/4" = 1'-0"

A2

TYP UTILITY THRU WALL

SCALE: 3/4" = 1'-0"

A5

TYP BRICK ANGLE BEARING @CONTROL POINT

SCALE: 3/4" = 1'-0"

A4

SCHEDULE - EXT NON-BRG BRICK/CMU ANGLE

SCALE: 1" = 1'-0"

C4

SCHEDULE - BEAM - SINGLE PLATE DESIGN

SCALE: 3/4" = 1'-0"

D2

TYP NON-LOAD BEARING STEEL STUD WALL DETAIL

SCALE: 3/4" = 1'-0"

D1

TYP NON-LOAD BEARING STEEL STUD WALL DETAIL

SCALE: 3/4" = 1'-0"

B3

TYP LINTEL BEARING

SCALE: 3/4" = 1'-0"

A1

TYP FOOTING STEP - CONC WALL

SCALE: 1/4" = 1'-0"

D3

SCHEDULE - SPECIAL JOIST LOADING

SCALE: 3/4" = 1'-0"

B1

CONCRETE PIER/BEAM BRG @ NEW

SCALE: 3/4" = 1'-0"

B2

CONCRETE PIER/BEAM BRG @ EXISTING

SCALE: 3/4" = 1'-0"

C2

TYPICAL LIGHT/EQUIPMENT SUPPORT DETAIL

MARK DATE DESCRIPTION

SHEET GENERAL NOTES:

KEY NOTES:

SHEET GENERAL NOTES:

KEY NOTES:

FIRST LEVEL

100' - 0"

T.O. JOIST BEARING

113' - 4"

T.0. MASONRY

115' - 4"

A2

A-301

W1 W1

E X

IS

T

IN

G

N E

W

3 2 1.7 1

2'-0"

FIRST LEVEL

100' - 0"

T.O. JOIST BEARING

113' - 4"

T.0. MASONRY

115' - 4"

C1

A-301

W1 W2 W2 W2

N E

W

E X

IS

T

IN

G

C B.5 B A.9 A.3 A

7 7

8 8

APPLY SEALANT AND BACKER ROD TO ALL JOINTS BETWEEN DISSIMILAR MATERIALS.A.

ALL SURFACES DAMAGED DURING DEMOLITION SHALL BE REPAIRED FOR APPLICATION OF NEW FINISHES

OR PATCHED TO MATCH EXISTING.

B.

CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS WHICH ARE TO MATCH

EXISTING CONSTRUCTION. CONTACT A/E WITH DISCREPANCIES.

C.

EXTERIOR ELEVATIONS

NOTE: NOT ALL KEYNOTES MAY BE USED ON EACH PLAN

EXTERIOR ELEVATIONS

1 FACE BRICK

2 BRICK SOLDIER COURSE

3 GLAZED BLOCK DECORATIVE BAND LAYOUT - MATCH EXISTING PATTERN

4 PRE-FINISHED METAL COPING

5 EARTH BERM TO MATCH EXISTING ADJACENT.

6 CONCRETE RETAINING WALL. REFERENCE CIVIL DRAWINGS

7 NEW BRICK LEDGE MATCH EXISTING.

8 MASONRY EXPANSION JOINT.

1/4" / 12"

1/4" / 12"

/4

/4

RD

OD

+4

+9.25"

+9.25"

+9.25"

+7.25"

+9.25"

A2

A-301

A1

A-301

A3

A-301

D5

A-501

D5

A-501

1/4" / 12"

MODIFICATIONS TO EXISTING ROOF TO BE DONE BY CERTIFIED INSTALLER TO AVOID WARRANTY ISSUES.C.

ALL SURFACES DAMAGED DURING DEMOLITION SHALL BE REPAIRED FOR APPLICATION OF NEW FINISHES

OR PATCHED TO MATCH EXISTING.

A.

CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS WHICH ARE TO MATCH

EXISTING CONSTRUCTION. CONTACT A/E WITH DISCREPANCIES.

B.

MINIMUM INSULATION THICKNESS OF 4" AT ROOF DRAINS.D.

ROOF PLAN

SEAL ALL PENETRATIONS AT ROOF MEMBRANE PER MANUFACTURER'S STANDARDS TO MAINTAIN ROOF

WARRANTY.

E.

OS

OVERFLOW SCUPPER

RD ROOF DRAIN

OD OVERFLOW ROOF DRAIN

REVISION TAG

KEYNOTE TAG

SECTION TAG

DETAIL TAG

ROOF PLAN LEGEND

A-101

A1

SIM

EPDM WALKMATS -

PROVIDE AROUND MECHANICAL EQUIPMENT

AND AS SHOWN

VTR VENT THROUGH ROOF - REF PLUMBING

REV

A1

A-301

3"

APPROXIMATE ROOF INSULATION

THICKNESS

NOTE: NOT ALL KEYNOTES MAY BE USED ON EACH PLAN

ROOF PLAN

1 EXISTING ROOFING TO REMAIN.

2 NEW PREFINISHED METAL COPING OVER EXISTING PARAPET AND NEW ROOF MEMBRANE.

PROVIDE ADEQUATE OVERLAP BETWEEN NEW AND EXISTING ROOF MEMBRANE TO MAINTAIN

ROOFING WARRANTY.

3 OVERLAP AND SEAL NEW COPING WITH EXISTING COPING TO PROVIDE A WETHERTIGHT SEAL.

4 PROTECTIVE SECONDARY WEAR/WALKING MEMBRANE. 30" WIDE TYPICAL.

5 MECHANICAL ROOF TOP UNIT. REFERENCE MECHANICAL DRAWINGS.

6 MECHANICAL ROOF VENT. REFERENCE MECHANICAL DRAWINGS.

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

N O T

FO

R

C O N S

TR

U C

TI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:3

:0

P

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic A jo h n s o n d p

.r v t

EXTERIOR

ELEVATIONS & ROOF

PLAN

A-201

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

AJP04/07/2017

DPJ03161153

SCALE: 1/8" = 1'-0"

D1

NORTH ELEVATION

SCALE: 1/8" = 1'-0"

C1

WEST ELEVATION

SCALE: 1/16" = 1'-0"

A1

ROOF PLAN

D

TH

TS

T

SW

S

CO2

CO

NO2

HS

H

M C

F

FS B

(E)

16"x8"

16"/8"

16"Ø

2"

4" RD-1

PLUG

2"

4"

4" 4"

PLUMBING AND PIPING SYMBOLS

GRILLES, REGISTERS, AND DIFFUSERS TAG

CFM

KEYNOTE

CONTINUATION SYMBOL

OVAL DUCT SIZE TAG (WIDTH / HEIGHT)

SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)

NUMBER OF SHEET WHERE DETAIL APPEARS

NUMBER OF DETAIL ON SHEET

REVISION NUMBER - SHOWN ON PLANS

GENERAL MECHANICAL SYMBOLS

ROOM NAME AND NUMBER

POINT WHERE NEW CONNECTS TO EXISTING

HVAC SYMBOLS

MECHANICAL EQUIPMENT TAG

EXISTING MECHANICAL EQUIPMENT TAG

(TYPICAL FOR ALL EXISTING TAGS)

& AND

Ø ROUND

A AIR

AB ABOVE BASE

ABV ABOVE

AC AIR CONDITIONING

ACOUS ACOUSTICAL

AD AREA DRAIN

ADD ADDENDUM

ADDL ADDITIONAL

AFF ABOVE FINISHED FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AG ABOVE GROUND

ALT ALTERNATE

ALUM ALUMINUM

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT/ARCHITECTURAL

AV ACID RESISTANT VENT

AW ACID RESISTANT WASTE

AUTO AUTOMATIC

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BLW BELOW

BM BEAM

BO BY OTHER

BOT BOTTOM

BSMT BASEMENT

BTU BRITISH THERMAL UNITS

BTUH BRITISH THERMAL UNITS PER HOUR

BTWN BETWEEN

CAP CAPACITY

CB CATCH BASIN

CCW COUNTER CLOCKWISE

CFCV CONSTANT FLOW CONTROL VALVE

CFM CUBIC FEET PER MINUTE

CHW CIRCULATING HOT WATER

CI CAST IRON

CLG CEILING

CLG COOLING

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

COND CONDENSATE

CONF CONFERENCE

CONN CONNECT

CONST CONSTRUCTION

CONT CONTINUE/CONTINUATION

CONTR CONTRACT/CONTRACTOR

COORD COORDINATE

CTR CENTER

CUFT CUBIC FEET

CV CHECK VALVE

CW COLD WATER

CW CLOCKWISE

D DEGREE

DB DRY BULB

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DISCH DISCHARGE

DIV DIVISION

DI DEIONIZED WATER

DMPR DAMPER

DN DOWN

DWG DRAWING

DW DISTILLED WATER

EA EACH

EAT ENTERING AIR TEMPERATURE

EL ELBOW

ELEC ELECTRICAL

ELEV ELEVATION

EP EXPLOSION PROOF

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMPERATURE

E/A EXHAUST AIR

EAH EXHAUST HOOD

EXIST EXISTING

EXP EXPANSION

EXPJT EXPANSION JOINT

EXT EXTERIOR

F DEGREES FAHRENHEIT

FCO FLOOR CLEAN OUT

FD FLOOR DRAIN

FD FIRE DAMPER

FDV FIRE DEPARTMENT VALVE

FHC FIRE HOSE CABINET

FL FLOOR

FLEX FLEXIBLE

FLG FLANGE

FO FUEL OIL

FOV FUEL OIL VENT

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED PIPE

FS FULL SIZE

FS FLOOR SINK

FT FOOT/FEET

FTG FOOTING

FTR FIN TUBE RADIATION

FUT FUTURE

GA GAGE/GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GENL GENERAL

GPH GALLONS PER MINUTE

GR GRADE

GW GREASE WASTE

HB HOSE BIB

HD HEAD

HORZ HORIZONTAL

HP HORSE POWER

HP HIGH PRESSURE

HTG HEATING

HTR HEATER

HW HOT WATER

HYD HYDRANT

ID INDIRECT

IN INCH

INL INLET

INSUL INSULATION

INT INTERIOR

INV INVERT

INWG INCHES WATER GAUGE

JST SPC JOIST SPACE

JT JOINT

LAB LABORATORY

LB POUND

LB/HR POUNDS PER HOUR

LAT LEAVING AIR TEMPERATURE

LF LINEAL FOOT

LOC LOCATION

LP LOW PRESSURE

LPG LIQUEFIED PETROLEUM GAS

LR LIQUID REFRIGERANT

LS LAWN SPRINKLER

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M/A MIXED AIR

MAN MANUAL

MATL MATERIAL

MAV MANUAL AIR VENT

MAX MAXIMUM

MBD MOTORIZED BYPASS DAMPER

MBH ONE THOUSAND BTU PER HOUR

MCF ONE THOUSAND CUBIC FEET

MCW MAKE-UP COLD WATER

MD MOTORIZED DAMPER

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MTR MOTOR

MU/A MAKE-UP/AIR

N NECK

NC NOISE CRITERIA

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NUMBER

NO NORMALLY OPEN

NOM NOMINAL

NTS NOT TO SCALE

O OXYGEN

O/A OUTSIDE AIR

OC ON CENTER

OF OVERFLOW

OPNG OPENING

ORD OVERFLOW ROOF DRAIN

PD PRESSURE DROP

PIV POST INDICATOR VALVE

PLBG PLUMBING

PR PAIR

PREL PRELIMINARY

PRESS PRESSURE

PRIM PRIMARY

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH GAUGE

PW POTABLE WATER

PWR POWER

R DUCT RISER

R/A RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF DRAIN

REC RECESSED

RED REDUCER

REFR REFRIGERATION

RH RELATIVE HUMIDITY

REQD REQUIRED

REV REVERSE

RL/A RELIEF AIR

RM ROOM

RPM REVOLUTIONS PER MINUTE

RW RAIN WATER

SF SQUARE FOOT

S/A SUPPLY AIR

SAN SANITARY

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT

SD SMOKE DAMPER

SHT SHEET

SIM SIMILAR

SLV SLEEVE

SM SURFACE MOUNT

SP STANDPIPE

SP STATIC PRESSURE

SPEC SPECIFICATION

SPS STATIC PRESSURE STATION

SQ SQUARE

SR SUCTION REFRIGERANT

SSD SOIL SUBDRAIN

SS STAINLESS STEEL

STD STANDARD

STM STEAM

STRUCT STRUCTURAL

SUCT SUCTION

SUSP SUSPENDED

T THERMOSTAT

TCP TEMPERATURE CONTROL PANEL

TD TEMPERATURE DROP

TDR TRENCH DRAIN

TEFC TOTALLY ENCLOSED FAN COOLED

TEMP TEMPERATURE

TYP TYPICAL

UFD UNDER FLOOR DUCT

UG UNDERGROUND

VAC VACUUM

V VENT

VAV VARIABLE AIR VOLUME

VEL VELOCITY

VENT VENTILATION

VERT VERTICAL

VOL VOLUME

VTR VENT THROUGH ROOF

W WASTE

WB WET BULB

WCO WALL CLEAN OUT

WH WALL HYDRANT

ABBREVIATIONS

FIRE DAMPER

SMOKE DAMPER

MOTORIZED DAMPER

MANUAL BALANCING DAMPER

BACKDRAFT DAMPER

COMBINATION FIRE/SMOKE DAMPER

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

HUMIDISTAT

HUMIDITY SENSOR

NITROGEN DIOXIDE SENSOR

SENSOR

TEMPERATURE & HUMIDITY SENSOR

SUPPLY OUTLET

RETURN / EXHAUST INLET

LINEAR DIFFUSER

RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE

RECTANGULAR RETURN/TRANSFER AIR DUCT RISE

MECHANICAL EQUIPMENT

ROUND DUCT SIZE TAG (DIAMETER)

EXISTING PIPE TAG

DOMESTIC

WATER METER

AC AIR CONDITIONING UNIT

ACC AIR COOLED CONDENSER

ACCU AIR COOLING CONDENSING UNIT

AFMS AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

B BOILER

CF CABINET FAN

CF CHEMICAL FEEDER

CFP CHEMICAL FEEDER PUMP

CH CHILLER

CRU CONDENSATE RETURN UNIT

CT COOLING TOWER

CUH CABINET UNIT HEATER

CWP CONDENSER WATER PUMP

CHWP CHILLED WATER PUMP

DBP DOMESTIC WATER BOOSTER PUMP

DC DUCT MOUNTED COIL

DCP DOMESTIC WATER CIRCULATING PUMP

EF EXHAUST FAN

EDC ELECTRIC DUCT COIL

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCU FAN COIL UNIT

FP FIRE PUMP

GI GREASE INTERCEPTOR

GRV GRAVITY ROOF VENTILATOR

H HUMIDIFIER

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

HPU HEAT PUMP UNIT

HRU HEAT RECOVERY UNIT

ILC INLINE CENTRIFUGAL

PF PROPELLER FAN

PRV POWER ROOF VENTILATOR

PWF POWER WALL FAN

RE RETURN/EXHAUST FAN

RTU ROOFTOP UNIT

SA SHOCK ABSORBER

SAT SOUND ATTENUATOR

SEP SEWAGE EJECTOR PUMP

SF SUPPLY FAN

SP SUMP PUMP

UH UNIT HEATER

US UTILITY SET

UV UNIT VENTILATOR

WFMS WATER FLOW MEASURING STATION

WH WATER HEATER

EQUIPMENT ABBREVIATIONS

PIPING BEING DEMOLISHED

THERMOSTAT

TEMPERATURE SENSOR

MANUAL SWITCH

TYPE (SEE SCHEDULE)

ROUND SUPPLY/OUTSIDE AIR DUCT RISE

ROUND RETURN/TRANSFER AIR DUCT RISE

RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE

ROUND EXHAUST/RELIEF AIR DUCT RISE

ABOVE GROUND PIPING

PIPE SIZE TAG (DIAMETER)

DROP

DROP

DROP

DROP

DROP

DROP

EXISTING MECHANICAL EQUIPMENT

FLOOR

CLEAN OUT

DRAIN SIZE

ROOF DRAIN FIXTURE

TYPE (SEE SCHEDULE)

DRAIN TAG

PLUMBING FIXTURE TAG

PLUMBING FIXTURE

REDUCING 45 DEGREE TEE

45 DEGREE TEE

Room

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

PIPE SLOPE TAG

INV. ELEV:-5' - 1"

1/8" / 12" SLOPE

* NOTE *

ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS

SET.THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN

THIS SET OF DRAWINGS.

MECHANICAL EQUIPMENT TAG

(REFER TO OTHER DISCIPLINE FOR ADDITIONAL

INFORMATION)

MECHANICAL EQUIPMENT FOR REFERENCE

4" OFD-1

WH-1

TYPE (SEE SCHEDULE)

S-3

FP-D

FP-O

FP-PA

FP

FIRE PROTECTION PRE-ACTION

FIRE PROTECTION WET

FIRE PROTECTION OTHER

FIRE PROTECTION DRY

FIRE PROTECTION SYMBOLS

UPRIGHT SPRINKLER HEAD

PENDENT SPRINKLER HEAD

RECESSED SPRINKLER HEAD

CONCEALED SPRINKLER HEAD

'D' REPRESENTS DRY SPRINKLER HEAD

SIDEWALL SPRINKLER HEAD

EXTENDED COVERAGE

SIDEWALL SPRINKLER HEAD

FP-DOM-W COMBINATION FIRE & DOMESTIC

OBSTRUCTION FROM

DUCTWORK 48" AND GREATER

48"x18" S/A

V

W

ORDB

ORD

SANITARY VENT

SANITARY WASTE

STORM DRAINAGE OVERFLOW BELOW

STORM DRAINAGE OVERFLOW

RD STORM DRAINAGE

ORDB STORM DRAINAGE OVERFLOW BELOW

SANITARY WASTE-BELOW

NO

O

MEDICAL NITROUS OXIDE

MEDICAL OXYGEN

MV MEDICAL VACUUM

N MEDICAL NITROGEN

MGAS

H

MEDICAL GAS

MEDICAL HYDROGEN

CO2 MEDICAL CO2

LV

MA

LAB VACUUM

MEDICAL AIR

LDE

LDI

LAB DEIONIZED WATER

LAB DISTILLED WATER

LA LAB AIR

LG LAB GAS

LAB AND MEDICAL SYMBOLS

CWS

CWR CHILLED WATER RETURN

CHILLED WATER SUPPLY

AW

AWB

AV ACID VENT

ACID WASTE

ACID WASTE BELOW

CR

CS

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

A

CD

CDR

COMPRESSED AIR

CONDENSATE DRAINAGE

CONDENSATE RETURN

CWV COMBINATION WASTE & VENT

DE

DI

DEIONIZED WATER

DISTILLED WATER

CW

F-CW

HCW

SCW

TW

HW 140°

RHW

RHW 140°

DOMESTIC COLD WATER

DOMESTIC COLD WATER-FILTERED

DOMESTIC COLD WATER-HARD

DOMESTIC COLD WATER-SOFT

DOMESTIC TEMPERED WATER

DOMESTIC HOT WATER 140°

DOMESTIC HOT WATER RECIRCULATING

DOMESTIC HOT WATER RECIRCULATING 140°

G-2LB NATURAL GAS 2LB

DUAL TEMP WATER RETURN

DUAL TEMP WATER SUPPLY

GEOTHERMAL RETURN

GEOTHERMAL SUPPLY

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

GREASE VENT

GREASE WASTE

DTWR

DTWS

GTR

GTS

GHR

GHS

GV

GW

HWR

HWS

HEATING WATER RETURN

HEATING WATER SUPPLY

G NATURAL GAS

MIT MITIGATION VENT

PRO PROPANE GAS

OV

OW

OIL VENT

OIL WASTE

HPS STEAM - HP

RL

RS

REFRIGERANT LIQUID

REFRIGERANT SUCTION

RHG REFRIGERANT HOT GAS

REF REFRIGERANT

PD PUMP DISCHARGE

HPR STEAM - HP CONDENSATE

MPS STEAM - MP

MPR STEAM - MP CONDENSATE

LPS STEAM - LP

LPR STEAM - LP CONDENSATE

1. SIDE CONNECTION

2. ELBOW DOWN

3. ELBOW UP

4. SHUT OFF VALVE

5. BALANCING VALVE

6. CONTROL VALVE

7. PRESSURE REDUCING VALVE

8. PRESSURE RELIEF VALVE

9. CHECK VALVE

10. AIR VENT

11. PRESSURE GAUGE

12. THERMOMETER

13. PIPE ANCHOR

14. PIPE GUIDE

15. CONCENTRIC REDUCER

16. ECCENTRICL REDUCER

17. STRAINER

18. UNION

19. DIRECTION OF FLOW

20. PITCH PIPE DOWN

21. 3-WAY CONTROL VALVE

22. PUMP

23. FLOW SWITCH

24. PRESSURE TEMPERATURE TAP

25. MANUAL CALIBRATED BALANCING VALVE

26. AUTOMATIC FLOW CONTROL VALVE

27. MEDICAL GAS OUTLET

28. HOSE-BIBB OR WALL HYDRANT

29. INSERTION FLOW METER

30. FLOW METER

31. REDUCED PRESSURE BACKFLOW PREVENTER

32. AQUASTAT

33. 3-WAY VALVE

END CAP

1 2 3 4 5 6 7 98

11 1210 13 14 15 16 17 18

20 21 22 25

FS

23 24 26 27 28

FM

A

3230 31

FCO

GAS METERFLOOR

DRAIN

WALL

CLEAN OUT

WCO

PIPE BREAK

DOWNSPOUT NOZZLE

FLEX DUCT

XXX-X

(E)XXX-X

XXX-X

WB

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NO

T

FO

R

CO

NSTR

UCTI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:5

:5

A

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic M m a k s c h .r v t

MECHANICAL TITLE

SHEET

M-001

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

CHM04/07/2017

SMT03161153

FIRE PROTECTION GENERAL NOTES

* EXST 1 PROVIDE ALTERATIONS TO THE EXISTING FIRE SUPPRESSION SYSTEM AS REQUIRED TO

ACCOMMODATE THE NEW FLOOR PLAN AND NEW CEILING TYPES. PROVIDE A COMPLETE WET

TYPE SYSTEM INCLUDING NEW MAINS, BRANCHES, HEADS, VALVES, AND ACCESSORIES AS

REQUIRED. REUSE EXISTING SYSTEM EQUIPMENT WHERE APPLICABLE. THE SYSTEM SHALL BE

INSTALLED ACCORDING TO MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS AND

AS PER REQUIREMENTS OF THE STATE BUILDING CODE, LOCAL FIRE DEPARTMENT, AND ALL

FEDERAL, STATE, AND LOCAL AUTHORITIES, NFPA, AND FACTORY MUTUAL.

* EXST 2 THE BUILDINGS COMPLETE OPERATIONAL FIRE SUPPRESSION SYSTEMS SHALL REMAIN IN

PLACE. THIS CONTRACTOR SHALL REPAIR ANY DAMAGE TO THIS SYSTEM CREATED BY THE

REMOVAL OF ANY OTHER MECHANICAL SYSTEMS OR COMPONENTS.

* EXST 3 THIS CONTRACTOR SHALL COORDINATE PHASING OF WORK WITH THE GENERAL CONTRACTOR

PRIOR TO STARTING WORK.

* NEW 1 PROVIDE A COMPLETE WET TYPE FIRE SUPPRESSION SYSTEM AS REQUIRED TO

ACCOMMODATE THE FLOOR PLAN AND CEILING TYPES INCLUDING MAINS, BRANCHES, HEADS,

VALVES, AND ACCESSORIES AS REQUIRED. THE SYSTEM SHALL BE INSTALLED ACCORDING TO

MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS OF THE STATE BUILDING CODE,

LOCAL FIRE DEPARTMENT, AND ALL FEDERAL, STATE, AND LOCAL AUTHORITIES, NFPA, AND

FACTORY MUTUAL.

* NEW 2 THE FIRE SUPPRESSION SYSTEM SHALL BE DESIGNED BASED UPON ACTUAL WATER FLOW

TEST DATA OBTAINED AT OR NEAR THE JOB SITE.

* NEW 3 REFER TO REFLECTED CEILING PLANS FOR ADDITIONAL INFORMATION REGARDING SPRINKLER

LOCATION AND PIPE, UNLESS NOTED OTHERWISE.

* NEW 4 DIVISION 21 CONTRACTOR SHALL COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR

PROPER INSTALLATION OF THE FIRE SUPPRESSION SYSTEMS ALARM DEVICES INVOLVED WITH

FIRE SPRINKLER SYSTEM.

* NEW 5 ALL FIRE SUPPRESSION SYSTEM PIPING SHALL BE CONCEALED ABOVE THE SUSPENDED

CEILING SYSTEM, UNLESS NOTED OTHERWISE. WRITTEN AUTHORIZATION SHALL BE OBTAINED

FROM THE ARCHITECT PRIOR TO EXPOSING ANY PIPING IN ANY ROOM WHICH HAS A

SUSPENDED CEILING.

* NEW 6 AUXILIARY DRAINS SHALL BE EXPOSED WITH 1" DRAIN VALVES. WHEN 5 OR MORE GALLONS

ARE TRAPPED, THIS CONTRACTOR SHALL PROVIDE FIXED PIPING TO AN ADEQUATELY SIZED

RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE DRAIN. WHEN LESS

THAN 5 GALLONS ARE TRAPPED, A HOSE BIB SHALL BE PROVIDED AT THE DRAIN VALVE.

* NEW 7 AUXILIARY DRAINS SHALL NOT BE LOCATED ABOVE PLASTER OR GYPSUM BOARD CEILING

SYSTEMS.

* NEW 8 AN INSPECTOR'S TEST CONNECTION SHALL BE PROVIDED FOR EACH FIRE SUPPRESSION ZONE.

THIS CONTRACTOR SHALL PROVIDE FIXED PIPING FROM THE TEST CONNECTION TO AN

ADEQUATELY SIZED RECEPTOR WHICH IS CAPABLE OF ACCEPTING THE FULL FLOW OF THE

TEST. EXTERIOR DISCHARGE OF THE TEST CONNECTION SHALL BE PERMITTED ONLY BY

SPECIFIC WRITTEN INSTRUCTION FROM THE ENGINEER.

* NEW 9 SHOW ALL ROOM NAMES & NUMBERS ON SHOP DRAWING PLANS.

* NEW 10 THE CONTRACTOR SHALL PERFORM A FIRE FLOW TEST IN ACCORDANCE WITH NFPA 291.

* NEW 11 ROUTE PIPING SUCH THAT IT DOES NOT RUN ABOVE ELECTRICAL PANELS, SWITCHGEAR, OR

SIMILAR EQUIPMENT. MAINS SHALL NOT RUN THROUGH ELECTRICAL OR COMMUNICATION

ROOMS. SPRINKLERS IN THESE ROOMS SHALL BE SERVED BY A DEDICATED BRANCH LINE FOR

EACH ROOM.

* NEW 12 THIS DRAWING INDICATES A GENERAL PIPING ARRANGEMENT AND SUGGESTED SIZING ONLY.

THIS CONTRACTOR SHALL DETERMINE THE PIPE ROUTING AND SIZING REQUIRED AND

COORDINATE WORK WITH ALL OTHER TRADES TO AVOID CONFLICTS.

* NEW 13 THIS CONTRACTOR SHALL PREPARE HYDRAULIC CALCULATIONS BASED UPON THE

CONFIGURATION OF THE ACTUAL SYSTEM DESIGN AS SHOWN ON THIS CONTRACTOR'S SHOP

DRAWINGS.

* NEW 14 FIRE STOPPING & SEALING: ALL PIPE AND DUCT WHICH PENETRATE RATED WALLS AND OR

CEILING ASSEMBLIES SHALL BE PROPERLY FIRE STOPPED AND SEALED AS REQUIRED BY THE

LOCAL BUILDING CODE AUTHORITIES. SEE DETAILS.

* NEW 15 THE FIRE SUPPRESSION CONTRACTOR SHALL SUBMIT DETAILED WORKING PLANS SHOWING

PROPER SPRINKLER PLACEMENT, HYDRAULIC CALCULATIONS AND PIPE SIZE FOR THIS

PROJECT PRIOR TO COMMENCING INSTALLATION.

* NEW 16 FIRE SUPPRESSION CONTRACTOR SHALL VERIFY ALL EXISTING FIRE SUPPRESSION PIPING AND

SPRINKLERS WITH RESPECT TO ALL NEW MECHANICAL EQUIMENT LOCATION. IF THERE IS ANY

INTERFERENCE NOTED, THE FIRE SUPPRESSION CONTRACTOR SHALL BE RESPONSIBLE TO

RELOCATE EXISTING PIPING AND SPRINKLERS TO MEET REQUIREMENTS.

* NEW 17 SPRINKLER AND PIPING INSTALLATION SHALL BE COORDINATED CAREFULLY WIHT NEW AND

EXISTING LIGHTS, GRILLES, SPREAKERS, ETC., TO AVOID CONFLICTS.

* NEW 18 CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND REINSTALLATION OF EXISTING

CEILINGS REQUIRED TO INSTALL PIPING (UNLESS NOTED OTHERWISE).

HVAC GENERAL NOTES

* NEW 1 SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.

* NEW 2 CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE SENSORS AT 4'-0" AFF, A

MINIMUM OF 8" FROM LIGHT SWITCH.

* NEW 3 REFER TO PIPING DRAWINGS FOR THERMOSTAT AND TEMPERATURE SENSOR LOCATIONS.

* NEW 4 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR

SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE,

AND LOCAL CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER.

* NEW 5 PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT.

COORDINATE SIZES WITH MECHANICAL EQUIPMENT SELECTED.

* NEW 6 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMENT AFTER

ALL DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL

PUNCH.

PLUMBING GENERAL NOTES

* EXST 1 FIELD VERIFY ALL NEW WATER, WASTE, AND VENT PIPING CONNECTIONS AND

PROVIDE NEW CONNECTIONS AS REQUIRED FOR PROPERLY OPERATING

SYSTEMS.

* NEW 1 PITCH UNDERFLOOR SANITARY WASTE AND STORM PIPING 3" AND GREATER AT

1/8" PER FOOT, UNLESS NOTED OTHERWISE. PITCH ALL OTHER WASTE PIPING AT

1/4" PER FOOT UNLESS OTHERWISE NOTED.

* NEW 2 FIELD VERIFY LOCATION AND INVERTS OF SITE UTILITIES PRIOR TO

INSTALLATION.

* NEW 3 ROUTE DOMESTIC WATER, FIRE PROTECTION, SANITARY SEWER, AND STORM

SEWER SERVICES TO SITE UTILITIES 5'-0" FROM BUILDING UNLESS NOTED

OTHERWISE. REFER TO CIVIL PLANS.

* NEW 4 WASTE AND VENT PIPING BELOW FLOOR AND THROUGH FLOOR SHALL BE 2"

MINIMUM.

* NEW 5 PROVIDE CLEANOUT IN ACCESSIBLE LOCATION AT THE BASE OF ALL PLUMBING

RISERS.

PROJECT GENERAL NOTES

* DEMO 1 WHERE EQUIPMENT AND/OR FIXTURES ARE INDICATED TO BE REMOVED, THE

EXISTING SERVICES SHALL BE CAPPED AND CONCEALED BEHIND FINISHED

SURFACES. ABANDONED BRANCH SERVICES SHALL BE REMOVED BACK TO THE

MAINS AND CAPPED, UNLESS OTHERWISE INDICATED.

* DEMO 2 CAP ANY ABANDONED OR UNUSED PIPE AND/OR DUCT OPENINGS.

* DEMO 3 THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND PAINTING TO

MATCH EXISTING WALLS, FLOORS, AND CEILINGS.

* DMEO 4 HYDRONIC AND DOMESTIC PIPING SHALL BE THOROUGHLY CLEANED BEFORE

PUTTING INTO PERMANENT SERVICE.

* EXST 1 REMOVE ALL UNUSED PIPING, DUCTWORK AND ACCESSORIES.

* EXST 2 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING,

PRIOR TO FINAL BID, ALL EXISTING CONDITIONS FOR PLUMBING AND

MECHANICAL SYSTEMS WITHIN TENANT SPACE AND WITHIN CLOSE PROXIMITY

OF TENANT SPACE.

* EXST 3 THE MECHANICAL CONTRACTOR SHALL PERFORM SERVICE AND REPAIR ON THE

EXISTING EQUIPMENT AND ITS ACCESSORIES AS FOLLOWS: CLEAN ALL COILS,

REPLACE THE FILTERS AND BELTS, INSPECT, REPAIR, OR REPLACE THE

ECONOMIZERS, DRIVES AND FAN BEARINGS, MOTORS, CONTROL COMPONENTS,

VALVES AND ANY OTHER ITEM NECESSARY FOR A COMPLETE AND PROPER

OPERATING SYSTEM. THIS CONTRACTOR SHALL ALSO VISIT THE SITE, PRIOR TO

FINAL BIDDING, AND VERIFY ALL EXISTING SITE CONDITIONS. PROVIDE ALL

MATERIAL AND COMPONENTS AS NEEDED TO BRING THE UNITS TO FULL

COMPLIANCE OF THE LANDLORD'S CRITERIA AND LOCAL AUTHORITY HAVING

JURISDICTION.

* EXST 4 WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION,

PREVENT CONSTRUCTION DEBRIS FROM ENTERING DRAIN BODY BY SEALING

DRAIN OPENING PRIOR TO START OF WORK.

* NEW 1 COORDINATE AND COOPERATE WITH THE OTHER TRADES ON THE

INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY,

STRUCTURE, AND EQUIPMENT TO PREVENT CONFLICTS.

* NEW 2 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH

EXISTING AND THOSE ILLUSTRATED BY THESE DOCUMENTS AS WELL AS THOSE

WHICH CAN BE REASONABLY ANTICIPATED INCLUDING, BUT NOT LIMITED TO

ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS

INVOLVED ON THIS PROJECT.

* NEW 3 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL

CONFORM TO ALL REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL

CODES, INCLUDING BUT NOT LIMITED TO THE INTERNATIONAL BUILDING CODE

AND INTERNATIONAL MECHANICAL CODE.

* NEW 4 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.

* NEW 5 ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10'-0" FROM EDGE OF

ROOF.

* NEW 6 LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT AWAY FROM THE

SPACE ABOVE ELECTRICAL PANELS. TRANSFORMERS AND OTHER ELECTRICAL

EQUIPMENT.

* NEW 7 ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO

MECHANICAL EQUIPMENT.

* NEW 8 REFER TO PLUMBING SERIES DRAWINGS FOR GAS AND A.C. CONDENSATE

DRAIN PIPING.

* NEW 9 PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL

ANOTHER SIZE IS SHOWN.

* NEW 10 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE

SEGMENTS, REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.

* NEW 11 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE

MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.

* NEW 12 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE

DRAWING, ARE APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE

FIELD. WORK SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID

INTERFERENCE IN THE FIELD.

* NEW 13 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS

WITHOUT CEILINGS.

* NEW 14 MATERIALS AND EQUIPMENT SHOWN ON PLANS SHALL BE NEW AND FURNISHED

BY THIS CONTRACTOR UNLESS OTHERWISE INDICATED.

* NEW 15 THIS CONTRACTOR IS RESPONSIBLE FOR ALL SLEEVES AND/OR OPENINGS

WHERE REQUIRED TO RUN PIPES AND DUCTS THROUGH FOUNDATIONS,FLOOR

SLABS, WALLS, BRIDGING AND BEAMS EXCEPT WHERE OTHERWISE INDICATED.

* NEW 16 CEILING ACCESS IS REQUIRED AT ALL REHEAT COILS, VALVES, FIRE DAMPERS,

MANUAL AND MOTORIZED DAMPERS LOCATED ABOVE CEILING. CEILING

ACCESS PANELS WILL BE PROVIDED UNDER THE GENERAL SECTION OF

CONSTRUCTION AND SHALL BE MINIMUM OF 24" X 24" UNLESS OTHERWISE

INDICATED. COORDINATE WITH GENERAL CONTRACTOR.

* NEW 17 THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS

AND DIMENSIONS. NOTIFY THE A/E IMMEDIATELY OF ANY DISCREPANCIES.

* NEW 18 WHERE NEW SERVICES ARE SHOWN CONNECTING TO EXISTING, VERIFY EXACT

LOCATION AND SIZE OF EXISTING.

* NEW 19 EXISTING SERVICES SHALL BE MAINTAINED UNLESS OTHERWISE INDICATED.

* NEW 20 ALL DUCTS, PIPING, FIXTURES, ETC., WHICH ARE DASHED AND/OR INDICATED BY

NOTE ON DEMOLITION PLANS SHALL BE REMOVED.

* NEW 21 ALL PLUMBING SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH

NATIONAL, STATE, AND LOCAL CODES.

* NEW 22 SEAL ALL SHEET METAL DUCTWORK JOINTS.

* NEW 23 WHERE MATERIAL IS INDICATED TO BE REMOVED, IT SHALL REMAIN THE

PROPERTY OF THE OWNER. THIS CONTRACTOR SHALL DISPOSE OF MATERIAL

AS DIRECTED BY THE OWNER.

* NEW 24 BALANCING OF AIR AND HYDRONIC SYSTEMS SHALL BE PERFORMED BY AN

NEBB OR AABC CERTIFIED TEST AND BALANCE AGENCY.

* NEW 25 PIPE PENETRATIONS OF RATED WALLS AND FLOORS SHALL BE SLEEVED AND

PROPERLY FIRE SEALED.

* NEW 26 ALL PIPE AND DUCT PENETRATIONS OF SMOKE PARTITION WALLS SHALL BE

PROPERLY SEALED TO RESIST THE PASSAGE OF SMOKE AS REQUIRED BY THE

LOCAL AUTHORITY.

* NEW 27 INSTALL FLUSH VALVE OPERATORS ON WIDE SIDE OF ACCESSIBLE STALLS.

* NEW 28 THE HEATING AND/OR COOLING HYDRONIC SYSTEM SHALL BE PROVIDED AND

FILLED WITH AN ANTIFREEZE GLYCOL SOLUTION (AS INDICATED ON THE

EQUIPMENT SCHEDULES) BY THE PIPING CONTRACTOR WHO SHALL BE

RESPONSIBLE FOR DETERMINING THE AMOUNT OF GLYCOL REQUIRED.

* NEW 29 GREASE DUCTS: PROVIDE 2-INCH THICK U.L. 2-HOUR FIRE RATED DUCT WRAP

ON GREASE DUCTS BETWEEN CEILING AND ROOF PENETRATION.

* NEW 30 MECHANICAL CONTRACTOR SHALL PROVIDE BALANCING DAMPERS WHERE

INDICATED. IN ADDITION CONTRACTOR SHALL PROVIDE BALANCING DAMPERS

ON DUCT TAKE-OFFS TO DIFFUSERS, GRILLES, AND REGISTERS, REGARDLESS

OF WHETHER DAMPERS ARE SPECIFIED AS PART OF THE DIFFUSER, GRILLE, OR

REGISTER ASSEMBLY. THE BALANCING DAMPER SHALL BE LOCATED IN THE

DUCT IMMEDIATELY AFTER THE DUCT TAKE-OFF AT THE MAIN DUCT

CONNECTION.

SHEET INDEX - MECHANICAL

D D

Is su e

C D

Is su e

SHEET # SHEET NAME

M-001 MECHANICAL TITLE SHEET

PD100 PLUMBING DEMOLITION PLAN - ADDITION CRAWLSPACE

PD101 PLUMBING DEMOLITION PLAN - ADDITION FIRST LEVEL

PL100 PLUMBING PLAN - ADDITION CRAWLSPACE

PL101 PLUMBING PLAN - ADDITION FIRST LEVEL

PL110 PLUMBING ROOF PLAN

PL601 PLUMBING SCHEDULES

M-100 OVERALL CRAWL SPACE PIPING PLAN

M-101 OVERALL BUILDING PIPING PLAN

MD101 MECHANICAL DEMOLITION PLAN - ADDITION FIRST LEVEL

MH100 MECHANICAL HVAC PLAN - ADDITION CRAWLSPACE

MH101 MECHANICAL HVAC PLAN - ADDITION FIRST LEVEL

MP100 MECHANICAL PIPING PLAN - ADDITION CRAWLSPACE

MP101 MECHANICAL PIPING PLAN - ADDITION FIRST LEVEL

M-120 MECHANICAL ROOF PLAN

M-601 MECHANICAL SCHEDULES

MARK DATE DESCRIPTION

DD MM/DD/YY DESIGN

DEVELOPMENT

M

1 2 3

C

B

A

1.7

A.3

B.5

A.9

SHARED

OFFICE

LOUNGE 337

SHARED STOR

LAB

MED. ALC.

EXAM

EXAM

CORR.

CORR.

N.S.

EXAM

EXAM

TREAT/ PROC

OFFICE

FAMILY TLT

CORR.

NURSING

SOIL

CLEAN

STORAGE

X-RAY

HALL

SUP.OFF.

EXAM

EXAM

EXAM

TLT

HALL

VITALS

O.P.D SUB-WAIT

N.S.

EXAM

C-3

CORRIDOR

RECORD STOR

RECPT.

C-2

CORRIDOR

DENTAL

RECEPT.

DENT. OPER

DENT. OPER

DENT. OPER

DENT. OPER

LKR.

JANITOR

STORAGE

DENT. OPER

DENT. OPER

323A

VEST.

CORR.

10"x10" S/A

20"x10" S/A

10"x8" E/A

12"x14" S/A

10"x8" E/A 20"x10" E/A10"x8" E/A

10"x8" E/A

10"x10" S/A

2 2

S-1

R-2

S-2

R-2

S-1

R-1

S-2

R-2

R-4

S-5

R-2

S-2

S-4

R-3

S-5

S-1

R-1

S-1 100S-1

S-3

R-1

S-1

S-2

S-1

S-2

S-2

R-2

R-1

S-1

R-2

R-1

R-2

S-2

R-2

R-2

R-4

S-2

VAV-338VAV-335

VAV-334

VAV-330

VAV-332

VAV-326

VAV-327

VAV-322

VAV-324

VAV-320VAV-321

18"x12" S/A 14"x10" S/A

10"x10" S/A 8"x10" S/A

12"x10" S/A

"x

S /A

"x

S /A

R-1

8"x10" R/A10"x12" R/A

"x

R /A

"x

R /A

"x

R /A

"x

R /A

18"x14" R/A

"x

R /A

"x

R /A

16"x12" R/A16"x14" R/A

"x

R /A

"x

R /A

R-5

R-5

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NO

T

FO

R

CO

NSTR

UCTI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:0

:1

P

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic M m a k s c h .r v t

MECHANICAL HVAC

PLAN - ADDITION

FIRST LEVEL

MH101

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

CHM04/07/2017

SMT03161153

KEYNOTES

1 CAP DUCT TAKEOFF AT MAIN.

2 ADJUST EXISTING AIR DEVICE TO FIT IN NEW CEILING GRID.

3 RELOCATE EXISTING EXHAUST AIR DEVICE TO FIT IN NEW CEILING GRID. BALANCE

TO 50 CFM.

MARK DATE DESCRIPTION

SCALE: 3/16" = 1'-0"

A1

HVAC PLAN - FIRST LEVEL

TT

T

T T

T

T T

T

T

T 1 2 3

C

B

A

1.7

A.3

B.5

A.9

2 1/2" HWR

2" HWS

1 1/2" HWS

1" HWS

1" HWS 3/4" HWS

1 1/2" HWR 1 1/2" HWR 1 1/2" HWR

2" HWS

2 1/2" HWR

1 1/2" HWR

1 1/4" HWR

1 1/4" HWS

1 1/4" HWR

1 1/4" HWS

1" HWR

1 1/2" HWS

3/4" HWR

1 1/2" HWS 3/4" HWS

3/4" HWR

2" CWS 2" CWR

2" CWR

2" CWS

2" CWR

2" CWS

SHARED

OFFICE

LOUNGE

SHARED STOR

LAB

MED. ALC.

EXAM

EXAM

CORR.

CORR.

N.S.

EXAM

EXAM

TREAT/ PROC

OFFICE

FAMILY TLT

CORR.

NURSING

SOIL

CLEAN

STORAGE

X-RAY

HALL

SUP.OFF.

EXAM

EXAM

EXAM

TLT

HALL

VITALS

O.P.D SUB-WAIT

N.S.

EXAM

C-3

CORRIDOR

RECORD STOR

RECPT.

C-2

CORRIDOR

DENTAL

RECEPT.

DENT. OPER

DENT. OPER

DENT. OPER

DENT. OPER

LKR.

JANITOR

STORAGE

DENT. OPER

DENT. OPER

323A

VEST.

CORR.

VAV-338

VAV-335

VAV-334

VAV-330

VAV-332

VAV-326

VAV-327

VAV-322

VAV-324

VAV-320

VAV-321

RP-1

RP-1

RP-1

RP-1

RP-1

RP-1

RP-1

RP-1

RP-1

RP-1 RP-1

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NO

T

FO

R

CO

NSTR

UCTI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:0

:2

P

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic M m a k s c h .r v t

MECHANICAL PIPING

PLAN - ADDITION

FIRST LEVEL

MP101

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

CHM04/07/2017

SMT03161153

KEYNOTES

SCALE: 3/16" = 1'-0"

A1

HYDRONIC PIPING PLAN - FIRST LEVEL

1 2 3

C

B

A

1.7

A.3

B.5

A.9

ROOF

CC-1

HC-1

RF-1

SF-1

EF-2

EF-1

EF-3

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NO

T

FO

R

CO

NSTR

UCTI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:0

:0

P

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic M m a k s c h .r v t

MECHANICAL ROOF

PLAN

M-120

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

CHM04/07/2017

SMT03161153

KEYNOTES

MARK DATE DESCRIPTION

SCALE: 3/16" = 1'-0"

MECHANICAL PLAN - ROOF

NORTH

(ACTUAL)

NORTH

(REFERENCE)

ISSUES

SHEET NUMBER

SHEET TITLE

A

2 3

1 2 3

4 5

4 5

A

TSP, Inc.

PROJECT

NO

T

FO

R

CO

NSTR

UCTI

O N

600 Kansas City St.

Rapid City, SD 57701

(605) 343-6102 www.teamtsp.com

C C

B B

D D

© TSP, Inc. 2017

ISSUE DATE

CHECKED BY

DRAWN BY

PROJECT #

LI

S

TE

D

D R

A W

IN

G

S S

C A

LE

(S

) U N

LE

S

S R

E D

U C

E D

F R

O M

O R

IG

IN

A L x

F O

R M

A T

CONSULTANTS

Architecture Engineering

Planning

KEY PLAN

EXTG. BLDG.

NEW ADDITION

/7

/2

:0

:0

P

M

I:

T S

P R e v it L o c a l\

D a k o ta P la in s

K y le

C lin ic M m a k s c h .r v t

MECHANICAL

SCHEDULES

M-601

0%

D E

S

IG

N D

O C

U M

E N

T S

Kyle, South Dakota

KYLE CLINIC HEALTH

CENTER ADDITION -

IHS

DAKOTA PLAINS

CHM04/07/2017

SMT03161153

MARK DATE DESCRIPTION

AIR HANDLING UNIT SCHEDULE

MECHANICAL REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT NO. LOCATION

AREA

SERVED MANUFACTURER MODEL NO. AIRFLOW

MIN. OA

AIRFLOW

FANS COILS

ENERGY

RECOVERY ECONOMIZER FILTER

UNIT

WEIGHT

MECHANICAL

NOTES VOLTAGE PHASESUPPLY FAN RETURN FAN

COOLING

COIL

HEATING

COIL

AHU-1 ROOF ADDITION DAIKIN APPLIED OAH008GDAC 3,135 CFM 793 CFM SF-1 RF-1 CC-1 HC-1 - YES MERV 12 4,581 lb ALL 208 V 3

AHU SUPPLY FAN SCHEDULE

MECHANICAL REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT

NO. MANUFACTURER SERVES AIRFLOW

TOTAL

SP

EXTERNAL

SP

FAN

RPM BHP HP

MOTOR

RPM VFD FAN TYPE

FAN

CLASS

WHEEL

DIA.

MECHANICAL

NOTES VOLT/PH FLA MOCP

WIRE SIZE /

CONDUIT

CONTROLLER CONTROL

BY

DISCONNECT ELECTRICAL

NOTESTYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

SF-1 DAIKIN APPLIED AHU-1 3,135 CFM 5.00 in-wg 2.00 in-wg 3072 4.02 5 1750 NEMA 3R CENTRIFIGUAL DWDI 2 13.2" 208/3 17.5 35 A SEE SCHEDULE VFD - INT - - DIV. 23 BMS INT DIV. 23

AHU RETURN FAN SCHEDULE

MECHANICAL REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT

NO. MANUFACTURER SERVES AIRFLOW TOTAL SP

EXTERNAL

SP

FAN

RPM HP BHP

MOTOR

RPM VFD FAN TYPE

FAN

CLASS

WHEEL

DIA.

MECHANICAL

NOTES VOLT/PH FLA MOCP

WIRE SIZE /

CONDUIT

CONTROLLER CONTROL

BY

DISCONNECT ELECTRICAL

NOTESTYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

RF-1 DAIKIN APPLIED AHU-1 3,135 CFM 1.18 in-wg 1.00 in-wg 2307 2.0 1.4 1750 NEMA 3R CENTRIFUGAL DWDI 1 13.2" 208/3 7.8 20 SEE SCHEDULE VFD - INT - - DIV. 23 BMS INT DIV. 23

HEATING WATER COIL SCHEDULE

COIL NO. SERVES

MANUFACTURER

MODEL NO. TYPE AIRFLOW

CAPACITY

MBH

AIR SIDE WATER SIDE

MECHANICAL

NOTES

FACE

VELOCIT

Y EAT DB LAT DB AIR PD EWT LWT GPM WATER PD PG% ROWS

HC-1 AHU-1 DAIKIN APPLIED HW 3,135 CFM 59.1 448 FPM 49.0 °F 67.9 °F 0.10 in-wg 180 °F 156 °F 5.6 GPM 0.1 ftH2O 50 2

COOLING WATER COIL SCHEDULE

COIL NO. SERVES

MANUFACTURER

MODEL NO. TYPE AIRFLOW

TOTAL CAP.

MBH

AIRSIDE WATERSIDE

MECHANICAL

NOTES

FACE

VELOCIT

Y EAT DB EAT WB LAT DB LAT WB AIR PD EWT LWT GPM WATER PD FLUID ROWS

CC-1 AHU-1 DAIKIN APPLIED CW 3135 CFM 112 418 FPM 80.0 °F 66.0 °F 54.1 °F 53.9 °F 0.75 in-wg 45 °F 55 °F 23.2 GPM 12.6 ftH2O 30% PG 8

VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE

UNIT NO. MANUFACTURER

MODEL

NO.

MAXIMUM

AIRFLOW

MINIMUM

AIRFLOW

INLET

DIAMETE

R INLET SP

MAX.

BOX NC

AIRSIDE HOT WATER

MECHANICAL

NOTESHEATING CAP. (MBH) HEATING AIRFLOW EAT LAT FLOW PIPE DIAMETER

VAV-320 KRUEGER LMHS 215 CFM 107 CFM 5" 1.5 in-wg 25 5.2 107 CFM 55.0 °F 100.0 °F 0.5 GPM 1/2" ALL

VAV-321 KRUEGER LMHS 140 CFM 70 CFM 4" 1.5 in-wg 25 3.4 70 CFM 55.0 °F 100.0 °F 0.3 GPM 1/2" ALL

VAV-322 KRUEGER LMHS 215 CFM 108 CFM 4" 1.5 in-wg 25 6.4 108 CFM 55.0 °F 110.0 °F 0.6 GPM 1/2" ALL

VAV-324 KRUEGER LMHS 190 CFM 95 CFM 4" 1.5 in-wg 25 4.6 95 CFM 55.0 °F 100.0 °F 0.5 GPM 1/2" ALL

VAV-326 KRUEGER LMHS 470 CFM 235 CFM 6" 1.5 in-wg 25 11.4 235 CFM 55.0 °F 100.0 °F 1.1 GPM 3/4" ALL

VAV-327 KRUEGER LMHS 420 CFM 210 CFM 6" 1.5 in-wg 25 12.5 210 CFM 55.0 °F 110.0 °F 1.2 GPM 3/4" ALL

VAV-330 KRUEGER LMHS 400 CFM 200 CFM 6" 1.5 in-wg 25 9.7 200 CFM 55.0 °F 100.0 °F 1.0 GPM 3/4" ALL

VAV-332 KRUEGER LMHS 385 CFM 193 CFM 6" 1.5 in-wg 25 9.4 193 CFM 55.0 °F 100.0 °F 0.9 GPM 3/4" ALL

VAV-334 KRUEGER LMHS 225 CFM 113 CFM 4" 1.5 in-wg 25 6.7 113 CFM 55.0 °F 110.0 °F 0.7 GPM 1/2" ALL

VAV-335 KRUEGER LMHS 310 CFM 155 CFM 6" 1.5 in-wg 25 9.2 155 CFM 55.0 °F 110.0 °F 0.9 GPM 3/4" ALL

VAV-338 KRUEGER LMHS 165 CFM 83 CFM 5" 1.5 in-wg 25 4.9 83 CFM 55.0 °F 110.0 °F 0.5 GPM 1/2" ALL

EXHAUST FAN & POWER ROOF VENT SCHEDULE

MECHANICAL REQUIREMENTS ELECTRICAL REQUIREMENTS

UNIT NO. LOCATION SERVES MANUFACTURER MODEL NO. TYPE AIRFLOW TSP RPM POWER SONES

MECHANICAL

NOTES VOLT/PH FLA

WIRE SIZE /

CONDUIT

CONTROLLER CONTRO

L BY

DISCONNECT ELECTRICAL

NOTESTYPE SIZE LOCATION CTL DEVICE AUX BY TYPE BY

EF-1 ROOF 325, 331 COOK 70C2B DOWNBLAST 220 CFM 0.38 in-wg 1725 0.17 hp 9 1,2,3,4 120/1 SEE SCHEDULE - - - - - - DIV. 23 INT DIV. 23

EF-2 ROOF 322 COOK 70C2B DOWNBLAST 265 CFM 0.50 in-wg 1725 0.25 hp 12 1,2,3,5 120/1 SEE SCHEDULE - - - - - - DIV. 26 INT DIV. 23 E1

EF-3 ROOF 338 COOK 70C2B DOWNBLAST 265 CFM 0.50 in-wg 1725 0.25 hp 12 1,2,3,4 120/1 SEE SCHEDULE - - - - - - DIV. 23 INT DIV. 23

MECHANICAL NOTES:

1. UNIT SHALL BE HORIZONTAL OUTDOOR UNIT MOUNTED ON ROOF, RF AND SF VFD, DRAW THROUGH, LOW/MEDIUM PRESSURE.

2. UNIT SHALL BE COMPLETE WITH MIXING BOX, FACE AND BYPASS DAMPERS, ACCESS SECTIONS.

3. PREFILTERS SHALL BE THROW AWAY, 2" OR 4" THICK, MINIMUM 30% EFFICIENCY BASED ON DOP METHOD, APD=0.50 (MAXIMUM).

4. FINAL FILTERS SHALL BE THROW AWAY, MINIMUM 90% EFFICIENCY BASED ON DOP METHOD, APD=0.50 (MAXIMUM).

5. PREHEAT HW COIL 50% PG, CHILLED WATER COIL 30% PG.

6. PROVIDE INTEGRAL DISCONNECT FOR SUPPLY FAN AND RETURN FAN.

7. PROVIDE 120V CONVENIENCE OUTLET. PROVIDE WEATHERPROOFGFCI WITH IN-USE COVER.

8. PROVIDE 24" CURB TO MATCH UNIT FOOTPRINT.

MECHANICAL NOTES:

1.

ELECTRICAL NOTES:

1.

MECHANICAL NOTES:

1.

ELECTRICAL NOTES:

1.

MECHANICAL NOTES:

1.

MECHANICAL NOTES:

1.

MECHANICAL NOTES:

1. PROVIDE BIRDSCREEN AND BACKDRAFT DAMPER.

2. PROVIDE ROOF CURB DESIGNED TO MATE WITH UNIT.

3. PROVIDE FLEXIBLE DUCT CONNECTIONS AT FAN INLET.

4. CONTROL ON BAS.

5. WALL SWITCH, BAS SHALL CLOSE RETURN AIR DAMPER WHEN ENERGIZED.

6. PROVIDE FACTORY MOUNTED DISCONNECT.

ELECTRICAL NOTES:

1. DIV. 26 TO PROVIDE TOGGLE SWITCH IN ROOM FOR FAN CONTROL.

MECHANICAL NOTES:

1. NOISE CRITERIA IS BASED ON 1.0" APR AIR TERMINAL STATIC PRESSURE DROP AND THE SCHEDULED NC VALUES ARE RADIATED

NC'S WITH NO SOUND ATTENUATORS, NO LINED DUCTWORK, NO MULTIPLE TAKEOFF ALLOWANCE, AND NO ROOM ABSORPTION.

2. INSULATION SHALL NOT BE EXPOSED TO THE AIR STREAM.

3. INLET AND OUTLET DUCT SIZES SHALL MATCH VAV INLET AND OUTLET UNLESS OTHERWISE NOTED ON DRAWINGS.

4. PRESSURE DROP OF VAV BAX SHALL NOT EXCEED 0.4 INCHES AT DESIGN CFM.

5. CONTRACTOR SHALL ALLOW 5 STRAIGHT DUCT DIAMTERS ON VAV INLET WHEN POSSIBLE.

6. PROVIDE A COIL ACCESS DOOR, AND AN EMPTY BOX FOR DDC CONTROLS BY TEMPERATURE CONTROLS CONTRACTOR.

7. HWS AND HWR RUNOUTS TO HEATING COIL SHALL BE AS NOTED ON PLANS, OR PER SCHEDULE WHICHEVER IS LARGEST.

8. TWO ROW HOT WATER COIL.

GRILLES, REGISTERS AND DIFFUSERS SCHEDULE

TYPE SYSTEM MANUFACTURER MODEL NO. FACE SIZE NECK SIZE

MOUNTING

TYPE SPECIFICATION

MAX NC

(dB)

MAX PD

("WG)

INTEGRAL

DAMPER FINISH COLOR MATERIAL REMARKS

S-1 SUPPLY KRUEGER SHPCR 24x24 6"Ø LAY-IN LOUVER FACE, ROUND NECK, VERT/HORIZ ADJ AIRFLOW, 10 FT VERT THROW 20 0.05 - WHITE STEEL

S-2 SUPPLY KRUEGER SHPCR 24x24 8"Ø LAY-IN LOUVER FACE, ROUND NECK, VERT/HORIZ ADJ AIRFLOW, 10 FT VERT THROW 20 0.05 - WHITE STEEL

S-3 SUPPLY KRUEGER SHPCR 24x24 10"Ø LAY-IN LOUVER FACE, ROUND NECK, VERT/HORIZ ADJ AIRFLOW, 10 FT VERT THROW 20 0.05 - WHITE STEEL

S-4 SUPPLY KRUEGER SHPCR 24x24 12"Ø LAY-IN LOUVER FACE, ROUND NECK, VERT/HORIZ ADJ AIRFLOW, 10 FT VERT THROW 20 0.05 - WHITE STEEL

S-5 SUPPLY KRUEGER SHPCR 12x12 8"Ø SURFACE LOUVER FACE, ROUND NECK, VERT/HORIZ ADJ AIRFLOW, 10 FT VERT THROW 20 0.05 - WHITE STEEL

M15 EXHAUST KRUEGER EGC15 12x12 10"x10" SURFACE 1/2"X1/2"X1" CUBE CORE, 1" FRAME 20 0.12 - WHITE ALUMINUM

R-4 RETURN KRUEGER EGC15 12x12 8"x8" SURFACE 1/2"X1/2"X1" CUBE CORE, 1" FRAME 20 0.12 - WHITE ALUMINUM

R-5 RETURN KRUEGER EGC15 12x12 10"x10" SURFACE 1/2"X1/2"X1" CUBE CORE, 1" FRAME 20 0.12 - WHITE ALUMINUM

R-1 CEILING RETURN / TRANSFER

GRILLE

KRUEGER EG5 24 x 24 8"Ø LAY-IN 1/2" x 1/2" x 1" EGGCRATE GRID. 0 0.00 --- WHITE ENAMEL ALUMINUM

R-2 CEILING RETURN / TRANSFER

GRILLE

KRUEGER EG5 24 x 24 10"Ø LAY-IN 1/2" x 1/2" x 1" EGGCRATE GRID. 0 0.00 --- WHITE ENAMEL ALUMINUM

R-3 CEILING RETURN / TRANSFER

GRILLE

KRUEGER EG5 24 x 24 12"Ø LAY-IN 1/2" x 1/2" x 1" EGGCRATE GRID. 0 0.00 --- WHITE ENAMEL ALUMINUM

HYDRONIC RADIANT CEILING PANEL SCHEDULE

UNIT NO. MANUFACTURER MODEL NO. TYPE LENGTH WIDTH GPM/CIRCUIT BTU/LF WPD/LF GLYCOL AVE WTR TEMP AVE AIR TEMP FINISH MECH REMARKS

RP-1 AIRTEX HEF AS NOTED ON PLANS 24", 3-TUBE 0.0 GPM 0 0.00 ftH2O 0% -460 °F 70.0 °F WHITE

E - 5 0 1

A N N NA

SHEET SEQUENCE

NUMBER 01-99

SHEET TYPE

DESIGNATOR

DISCIPLINE

CHARACTER

MODIFIER

CHARACTER

SHEET TYPE DESIGNATORS

0 GENERAL (SYMBOLS LEGEND)

1 PLANS (HORIZONTAL VIEWS)

2 ELEVATIONS (VERTICAL VIEWS)

3 SECTIONS (SECTIONAL VIEWS)

4 LARGE SCALE VIEWS

5 DETAILS

6 SCHEDULES AND DIAGRAMS

7 USER DEFINED

8 USER DEFINED

9 3D REPRESENTATIONS

1 2 3 4 5 6

E2 E3 E4

C5

A4A1

A

B

C

D

E

TSP

A

B

C

D

E

1 2 3 4 5 6

DISCIPLINE CHARACTERS

S SITE

D DEMOLITION

L LIGHTING

P POWER

Y AUXILIARY

I INSTRUMENTATION

T TELECOMMUNICATION

SHEET IDENTIFICATIONELECTRICAL ABBREVIATIONS LIST

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC AIR CONDITIONER

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AIC AVAILABLE INTERRUPTING FAULT

CURRENT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT

SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CB-XX RECESSED CEILING BOX (SEE SCHEDULE)

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CM CORNER MOUNT

CMPR COMPRESSOR

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR

CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER

CIRCULATING PUMP

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DT DOUBLE THROW

DTS DUAL TECHNOLOGY SENSOR

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FB-XX FLOOR BOX (SEE SCHEDULE)

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FVNR FULL VOLTAGE NON-REVERSING

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI/GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL

(CONDUIT)

GYP BD GYPSUM BOARD

HOA HANDS-OFF-AUTOMATIC

SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT

SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSB MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S

ASSOCIATION

NFDS NON-FUSED SAFETY

DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

OS OCCUPANCY SENSOR

PA PUBLIC ADDRESS

PB PULL BOX

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIR PASSIVE INFRARED

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

(CONDUIT)

PWR POWER

QUAN QUANTITY

REC RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

VS VACANCY SENSOR

W WATT

W/ WITH

WB-XX RECESSED WALL BOX (SEE SCHEDULE)

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

Y WYE-CONNECTED

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

ROOM TAG

REVISION TAG

KEYNOTE TAG

SECTION TAG

DETAIL TAG

ELEVATION TAG

EXISTING WORK

NEW WORK

EXISTING ITEMS TO BE REMOVED

NAME

A1

A-301

A1

A-501

A-201A1

NORTH ARROW

MATCH LINE

SEE - - - -

A1

PLAN OR DETAIL

SCALE: 1'-0" = 1'-0"

GRID COLUMN/FND GRID INDICATOR

MATCH LINE INDICATOR

DETAIL/SECTION/PLAN

INDICATOR

CONVENTIONS LEGEND

PLAN NORTH

MECHANICAL EQUIPMENT TAGX-#

A2

12b

E

16c

1,3,5

SF-1

2,4,6

LPN-102

ELECTRICAL SYMBOL…