Attachment I - A5_B1337.pdf
PDF 20 MB Posted
- Attached to
- P1556 10th Marines Maintenance and Operations Complex, Marine Corps Base (MCB) Camp Lejeune, North Carolina
- Solicitation number
- N4008525R2532
About this file
These documents are architectural and engineering design drawings for the P-1556 10th Marines Operational Complex Building 1337 Addition project at Marine Corps Base Camp Lejeune in North Carolina. The project involves constructing a new maintenance bay addition with approximately 2,485 square feet of conditioned space. The facility will include maintenance bays, storage areas, mechanical spaces, and infrastructure to support vehicle and equipment maintenance operations.
The comprehensive set of drawings covers architectural, structural, mechanical, electrical, plumbing, fire protection, and telecommunications systems. Key design features include a pre-engineered metal building with standing seam metal roofing, infrared radiant gas heaters, vehicle exhaust systems, make-up air units, and comprehensive electrical and communication infrastructure. The project is being designed by Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic, with a design date of March 19, 2025 and anticipated construction to support the 10th Marines operational requirements at Camp Lejeune.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
J E
U N
E
N C
F ile
P ri n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M
A
P.
STCETIHCRA
FB
BERN N.C
.NEW
CERT. NO.
UTCETIHCRA
DERET
SI
G E R
N
OI
TA
RO
PR
OC
LAR
CAROLINANORTH
50679
T
T C
E
TI
HCRAD
R E
G I S
ERE
A N
I
L
ORA
N O
R
T H
C
N
D A
R
N
DE
.J UE
ER
III
C
N
NRB E
E W
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJEUNE
S p ro je c ts
\2
\2
M
ID
L
A N
T C
L P
-1 th
M a ri n e s N
M E
S
IS
C o m p le x \2
D e s ig n \2
D w g s \2
A
R C
H
A
B
.r v t
/3
/2
:3
:4
P
M
C O
V E
R S
H E
E T
G-001
1760523
FINAL SUBMITTAL
12915312
MARCH 19, 2025
JAS JAS DJE,III
DRR/KRT
DJD
EJA
DSN
06 MAY 2025
P -1
T
H M
A R
IN
E
S O
P E
R A
T
IO
N A
L C
O M
P L
E X
BUILDING 1337 ADDITION
MARINE CORPS BASE CAMP LEJEUNE
P-1556 10TH MARINES OPERATIONAL COMPLEX
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
MID-ATLANTIC
DESIGN AND CONSTRUCTION
FACILITIES ENGINEERING AND ACQUISITION DIVISION
NORFOLK, VIRGINIA
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
R
MCB CAMP LEJEUNE
ATLANTIC OCEAN
ATLANTIC OCEAN
NEW
R
IVER
P-1556 SITE
GENERAL PROJECT NOTES GOVERNING REGULATIONS
BUILDING CODE:
UNIFIED FACILITIES CRITERIA (UFC) 1-200-01 (01 SEP 2022, W/ CHANGE 3, 26 FEB 2024) UNIFIED FACILITIES CRITERIA (UFC) 1-200-02 (01 DEC. 2020, W/CHANGE 02, 01 JUN 2022) UNIFIED FACILITIES CRITERIA (UFC) 3-110-03 (01 MAY 2012, W/CHANGE 5, 12 JUN 2020)
ACCESSIBILITY CODE:
UNIFORM ACCESSIBILITY STANDARDS (UFAS)
AMERICANS WITH DISABILITIES ACT (ADA)
ACCESSIBILITY GUIDELINES FOR BUILDINGS AND FACILITIES (ADAAG)
MECHANICAL CODE:
INTERNATIONAL MECHANICAL CODE (IMC) 2021
ELECTRICAL CODE:
NFPA 70, NATIONAL ELECTRIC CODE (2023)
PLUMBING CODE:
INTERNATIONAL PLUMBING CODE (IPC) 2021
FIRE PREVENTION & LIFE SAFETY CODE:
UNIFIED FACILITIES CRITERIA (UFC) 3-600-01 (15 DEC. 2016, W/CHANGE 6, 06 MAY 2021)
NFPA 101, LIFE SAFETY CODE (2024)
1. WHERE EXISTING CONSTRUCTION IS DAMAGED BY CONSTRUCTION REQUIRED BY THESE
DOCUMENTS. REPAIR THE DAMAGED ITEM(S) WITH MATERIALS TO MATCH THE ADJACENT
MATERIAL, TEXTURE AND COLOR.
2. FIELD VERIFY EXISTING DIMENSIONS, PRIOR TO ORDERING MATERIALS OR BEGINNING
DEMOLITION.
3. ALL ITEMS NOT SHOWING AS "EXISTING" MUST BE PROVIDED AND INSTALLED UNDER THE
REQUIREMENTS OF THIS CONTRACT.
4. COORDINATE LAY DOWN AREA WITH THE CONTRACTING OFFICER PRIOR TO THE
PRECONSTRUCTION MEETING. THE ALLOWABLE AREA SIZE MUST BE ESTABLISHED BY THE
CONTRACTING OFFICER.
5. MANUFACTURER'S TRADE NAMES LISTED ARE NOT INTENDED TO BE PROPRIETARY.
PRODUCTS OF OTHER MANUFACTURERS WILL BE ACCEPTABLE PROVIDED THEY MATCH THE
COLOR, FINISHES, TEXTURES AND PATTERNS OF THE MANUFACTURER LISTED, AND MEET THE
TECHNICAL REQUIREMENTS OF THE SPECIFICATIONS.
6. OBSERVE AND MAINTAIN BUILDING AND COMPOUND SECURITY REQUIREMENTS AS DIRECTED
BY THE CONTRACTING OFFICER.
7. CONSTRUCTION WILL BE ACCOMPLISHED IN AND AROUND AREAS WHICH WILL REMAIN
OPERATIONAL. AVOID INTERFERENCE WITH THE OPERATIONAL WORK ROUTINE.
8. ALL SUBMITTALS REQUIRED BY THESE DRAWINGS OR SPECIFICATIONS MUST BE SUBMITTED
TO THE CONTRACTING OFFICER FOR APPROVAL PRIOR TO COMMENCEMENT OF RELATED
WORK.
B1450
B1445
B1337
NEW PARKING
B1
D1
CONTROLLED
HUMID
ITY
W
AREHOUSE
A2
FIELD M
AIN
T.
SHOP
A1
A4
A5
A3-3
A3-3
PHASE 2
PHASE 1
A3
A3
HAZM
AT-
BUILDING D2
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
J E
U N
E
N C n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M
A
P.
STCETIHCRA
FB
BERN N.C
.NEW
CERT. NO.
UTCETIHCRA
DERET
SI
G E R
N
OI
TA
RO
PR
OC
LAR
CAROLINANORTH
50679
T
T C
E
TI
HCRAD
R E
G I S
ERE
A N
I
L
ORA
N O
R
T H
C
N
D A
R
N
DE
.J UE
ER
III
C
N
NRB E
E W
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJEUNE
S p ro je c ts
\2
\2
M
ID
L
A N
T C
L P
-1 th
M a ri n e s N
M E
S
IS
C o m p le x \2
D e s ig n \2
D w g s \2
A
R C
H
A
B
.r v t
/3
/2
:3
:4
P
M L O
C A
T
IO
N M
A P
S A
N D
I N
D E
X O
F D
R A
W
IN
G S
G-002
1760523
FINAL SUBMITTAL
12915313
MARCH 19, 2025
JAS JAS DJE,III
DRR/KRT
DJD
EJA
DSN
06 MAY 2025
P -1
T
H M
A R
IN
E
S O
P E
R A
T
IO
N A
L C
O M
P L
E X
ARCHITECT
MBF ARCHITECTS, P.A.
317-C POLLOCK STREET
NEW BERN, NC 28560
CIVIL
STANTEC
801 JONES FRANKLIN ROAD, SUITE 300
RALEIGH NC 27606
LANDSCAPE
STANTEC
229 PEACHTREE STREET NE, SUITE 1900
ATLANTA GA 30303
GEOTECHNICAL
ECS SOUTHEAST, LLP
6714 NETHERLANDS DRIVE
WILMINGTON, NC 28405
LIFE SAFETY
JENSEN HUGHES
4445 CORPORATION LANE, SUITE 211
VIRGINIA BEACH, VA 23455
STRUCTURAL
KAYDOS-DANIELS ENGINEERS, PLLC
400-201 WEST MORGAN STREET
RALEIGH, NC 27603
COMPREHENSIVE INTERIOR DESIGN
WITHIN INTERIOR DESIGN, INC.
1008 GRANBY STREET
NORFOLK, VA 23510
FIRE ALARM /FIRE PROTECTION
JENSEN HUGHES
4445 CORPORATION LANE, SUITE 211
VIRGINIA BEACH, VA 23455
PLUMBING / MECHANICAL / ELECTRICAL
CRENSHAW CONSULTING ENGINEERS
3516 BUSH STREET, SUITE 200
RALEIGH, NC 27609
REGIONAL MAP
VICINITY MAP
SITE MAP
PROJECT LOCATION
N
N
N
TELECOMMUNICATIONS
CRENSHAW CONSULTING ENGINEERS
3516 BUSH STREET, SUITE 200
RALEIGH, NC 27609
LIGHTNING PROTECTION
CRENSHAW CONSULTING ENGINEERS
3516 BUSH STREET, SUITE 200
RALEIGH, NC 27609
AUDIOVISUAL
THORBURN ASSOCIATES, INCORPORATED
2500 GATEWAY CENTRE BLVD., SUITE 800
MORRISVILLE, NC 27560
DESIGN TEAM INDEX OF DRAWINGS
BUILDING LOCATION AND PHASING MAP
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
X
Y
FIRE EXTINGUISHER BRACKET (4A:80B:C)
*EXISTING FIRE EXTINGUISHERS ARE NOT INDICATED
X = REQUIRED EGRESS CAPACITY (PERSONS)
Y = PROVIDED EGRESS CAPACITY (PERSONS)
ROOM AREA (SF)
OCCUPANT FACTOR (SF/PERSON)
NUMBER OF OCCUPANTS (PERSONS)
SMOKE PARTITION
1-HR FIRE BARRIER
TRAVEL PATH AND DISTANCE
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
TD = XXFT
LIFE SAFETY LEGEND
1,000
XXXXX
XXXX
XXXX
FMCP
APPLICABLE BUILDING CODES
USE GROUP/OCCUPANCY
B (IBC 304.1) / BUSINESS (LSC 6.1.11.1.) - ORDINARY HAZARD (LSC 38.1.5)
S-1 (IBC 311.2) / STORAGE (LSC 6.1.13.1) - ORDINARY HAZARD (LSC 42.1.5)
S-1 (IBC 311.2) / SPECIAL PURPOSE INDUSTRIAL OCCUPANCY (NFPA 30A 7.4.1)
FOR IBC, BUILDING IS NON-SEPARATED MIXED GROUP B AND GROUP S-1 OCCUPANCIES.
FOR LSC, BUILDING IS NON-SEPARATED MIXED BUSINESS, SPECIAL PURPOSE INDUSTRIAL, AND STORAGE OCCUPANCIES.
FIRE PROTECTION SYSTEMS
WET PIPE SPRINKLER SYSTEMS
EMERGENCY VOICE/MASS NOTIFICATION FIRE ALARM SYSTEM
CONSTRUCTION TYPE
FLOOR LEVEL
REQUIRED EXIT
CAPACITY
AVAILABLE EXIT
CAPACITY
NUMBER OF EXITS
REQUIRED
NUMBER OF EXITS
PROVIDED
AFFECTED AREAS 25 340 2 2
BUILDING AREA & HEIGHT:
BASED ON SPRINKLERED GROUP S-1 ALLOWABLE PROVIDED
ALLOWABLE AREA (IBC TABLE 506.2): 52,500-SF 39,153-SF
ALLOWABLE STORIES (IBC TABLE 504.4): 4-STORIES 2-STORIES
ALLOWABLE HEIGHT (IBC TABLE 504.3): 75-FT 60-FT
TYPE II-B
EXTERIOR WALLS
EXTERIOR FIRE EXPOSURE BASED ON SEPARATION DISTANCE (TYPE II-B)
FIRE SEPARATION DISTANCE
< 5 FT
> 5 FT AND < 10 FT
> 10 FT
GROUP B
1 - HOUR
1 - HOUR
0 - HOUR
INTERIOR FINISH CLASSIFICATION LIMITS
LIMITS (BASED ON BUSINESS / INDUSTRIAL / STORAGE OCCUPANCIES WITH REDUCTION FOR SPRINKLERS)
REQUIRED PROVIDED
EXIT (TABLE A10.2.2.) MINIMUM CLASS C MINIMUM CLASS C
EXIST ACCESS CORRIDORS (TABLE A10.2.2.) MINIMUM CLASS C MINIMUM CLASS C
OTHER SPACES (TABLE A10.2.2) MINIMUM CLASS C MINIMUM CLASS C
FLOOR FINISH MINIMUM 0.1 W/CM2 MINIMUM 0.1 W/CM2
OCCUPANT LOADS
OCCUPANT LOADS (LSC TABLE 7.3.1.2)
SPECIAL PURPOSE INDUSTRIAL MAXIMUM PROBABLE
MEP SPACE 500 SF/PERSON
STORAGE 500 SF/PERSON
TRAVEL DISTANCE (LSC TABLE A.7.6)
COMMON PATH OF TRAVEL (BUSINESS / SP INDUSTRIAL / STORAGE): 100-FT / 100-FT / 100-FT TOTAL TRAVEL DISTANCE (BUSINESS / SP INDUSTRIAL / STORAGE): 300-FT / 400-FT / 400-FT
DEAD END CORRIDOR (BUSINESS / SP INDUSTRIAL / STORAGE): 50-FT / 50-FT / 100-FT
CAPACITY OF EXITS (LSC TABLE 7.3.3.1)
LEVEL COMPONENTS (WIDTH/PERSON) 0.2 IN/PERSON
NUMBER OF EXITS (LCS 7.4)
2 FOR OCCUPANT LOAD ≤ 500, 3 FOR OCCUPANT LOAD > 500 AND ≤ 1,000 (ADDITION ONLY).FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
(IBC TABLE 601, TYPE II-B CONSTRUCTION)
REQUIRED PROVIDED
PRIMARY STRUCTRUAL FRAME, INCL. COLUMNS, GIRDERS & TRUSSES 0-HOUR 0-HOUR
PRIMARY STRUCTURAL FRAME SUPPORTING A ROOF ONLY 0-HOUR 0-HOUR
BEARING WALLS, INTERIOR & EXTERIOR 0-HOUR 0-HOUR
FLOOR CONSTRUCTION 0-HOUR 0-HOUR
ROOF CONSTRUCTION (SECONDARY MEMBERS ONLY) 0-HOUR 0-HOUR
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
IBC INTERNATIONAL BUILDING CODE 2021
UFC 1-200-01 DOD BUILDING CODE, 12 JUNE 2023
UFC 3-520-01 INTERIOR ELECTRICAL SYSTEMS, 12 APRIL 2021
UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021
UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, JANUARY 2010
NFPA 10 PORTABLE FIRE EXTINGUISHER 2022
NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS 2022
NFPA 24 INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES 2022
NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE 2024
NFPA 30A MOTOR FUEL DISPENSING FACILITIES AND REPAIR GARAGES 2021
NFPA 30B MANUFACTURE AND STORAGE OF AEROSOL PRODUTS 2023
NFPA 70 NATIONAL ELECTRICAL CODE 2023
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2022
NFPA 90A INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEM 2024
NFPA 101 LIFE SAFETY CODE (LSC) 2024
THERE IS A DISTANCE OF AT LEAST 40-FT BETWEEN BUILDING A5 AND ANY OTHER STRUCTURES ON ALL SIDES. THIS PROVIDES A FIRE SEPARATION DISTANCE OF AT LEAST 30-FT FROM THE ADJACENT BUILDINGS TO AN IMAGIANRY LOT LINE AND AT LEAST 10-FT FROM THE IMAGINARY LOTE LINE TO BUILDING A5; THEREFORE, THERE IS NO FIRE RESISTANCE RATING REQUIRED ON THE EXTERIOR WALLS BASED ON THE FIRE SEPARATION DISTANCE.
INTERIOR FIRE RESISTANCE RATING REQUIREMENTS
ROOM
LIQUID STORAGE ROOMS
REQUIRED SEPARATION
2-HOUR (NFPA 30 TABLE 9.9.1)
ADDITIONAL LIFE SAFETY CRITERIA
MEANS OF EGRESS MUST BE ILLUMINATED IN ACCORDANCE WITH LSC 7.8 (LSC 38.2.8; 40.2.8; 42.2.8.1). ARTIFICIAL LIGHTING IS REQUIRED AT
LOCATIONS AND TIMES NECESSARY TO MAINTAIN ADEQUATE ILLUMINATION (LSC 7.8.1.2.1).
EMERGENCY LIGHTING SYSTEMS MUST BE PROVIDED IN ACCORDANCE WITH LSC 7.9 (LSC 38.2.9.1; 40.2.9.1; 42.2.9).
MEANS OF EGRESS MUST BE PROVIDED WITH SIGNS IN ACCORDANCE WITH LSC 7.10 AND UFC 3-600-01 2-5.2 (LSC 38.2.10; 40.2.10; 42.2.10). SIGNS MUST HAVE LETTERING ON AN OPAQUE BACKGROUND. INTERNALLY ILLUMINATED SIGNS MUST BE LIGHT EMITTING DIODE (LED) TYPE, ELECTROLUMINESCENCE (LEC), OR COLD CATHODE TYPE. INCANDESCENT FIXTURES ARE NOT PERMITTED. RADIOLUMINOUS EXIT SIGNS ARE NOT
PERMITTED (UFC 3-600-01 10-2.1).
FIRE EXTINGUISHERS ARE REQUIRED IN BUSINESS OCCUPANCIES AND MUST BE LOCATED IN ACCORDANCE WITH NFA 10 (LSC 38.3.5 & UFC 3-600-01 9-17.1 & 9-17.2).
GROUP S-1
2-HOUR
1-HOUR
0 - HOUR
PROVIDED
2-HOUR
AREA OCCUPANCY/USE APPROX.
AREA (SF)
OCCUPANT LOAD
FACTOR
(SF/PERSON)
OCCUPANT
LOAD
(PERSONS)
AUTO MAINT. BAYS SP INDUSTRIAL / SP INDUSTRIAL 5,220 18MAX
HIMARS MAINT. TOOL ROOM 436 1500
8,475TOTAL 25-
PROVIDED
0 - HOUR
SPRINKLER VALVE ROOM 1-HOUR (NFPA 24 6.2.9(6)) 1-HOUR
FUEL-FIRED EQUIPMENT ROOM SMOKE PARTITION (LSC 38.3.2.1) SMOKE PARTITION
MECHANICAL 216 0500
GENERAL STORAGE SMOKE PARTITION (LSC 38.3.2.1) SMOKE PARTITION
COMPRESSOR 129 0500
TELECOMM 99 0500
MAINT. BAY ADDITION 2,375 6MAX
SP INDUSTRIAL / STORAGE
SP INDUSTRIAL / MEP
SP INDUSTRIAL / MEP
SP INDUSTRIAL / MEP
SP INDUSTRIAL / SP INDUSTRIAL
EXISTING AFFECTED AREAS
ADDITION
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
J E
U N
E
N C n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJEUNE
C U s e rs
\a e lb o g h d a d y \D o c u m e n ts \2
F
IR
E
A
B a e lb o g h d a d y .r v t
/2
/2
:1
:2
P
M L
IF
E S
A F
E T
Y G
E N
E R
A L
N O
T E
S A
N D
L E
G E
N D
GI001
1760523
FINAL DESIGN SUBMITTAL
12915314
MARCH 19, 2025
APF AHE KEC
DRR/KRT
EJA
DSN
P -1
T
H M
A R
IN
E
S O
P E
R A
T
IO
N A
L C
O M
P L
E X
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EAL
THOF
V
IR
G
IN
IA
P R O F
E
SSIONAL EN
G
IN
E E R
06 MAY 2025
DSN
M
C P
A'A B C D E F G H J KL'L M N OPQ R S T UVWI
2.1
2.6
PX PY
P1
P2
P3
P4
P5
MAINTENANCE
BAY
CAGED EQUIP.
STOR 'S'
ORGANIC
STORAGE AREAS
(3)
OFFICE
TELE UNISEX
ELECTRICAL MENS AND
WOMENS HEAD
MECHANICAL
BOILER ROOM
VEST.
GENERAL
STORAGE
STAIR B
HIMARS MAINT.
OFFICER
HIMAR MAINT.
OFFICE
ORDO OFFICE
PRINT / FILE
BREAK ROOM
FSR OFFICE
CLASSROOM
CONFERENCE
ROOM
DISPATCH
CORRIDOR
VEST.
STAIR
'R' STG
'S' STG
'T' STG
FSR TOOL ROOM
& PARTS
STORAGE
VEST.
LEAD ACID
BATTERY
STORAGE
TELECOM
HQ STORAGE
TIRE STORAGE
HQ FAC OFFICE
BATTERY FAC
OFFICE T
BATTERY FAC
OFFICER S
BATTERY FAC
OFFICE R
LAUNCHER
MAINTENANCE
BAYS (6)
EXISTING AUTO
MAINTENANCE
BAYS (6)
HIMARS PARTS
STORAGE
HIMARS
MAINTENANCE
TOOL ROOM
CORRIDOR
TELECOM
COMPRESSOR
MECHANICAL
POL STORAGE
ELEC
T D
F
T
TD = 65 FT
5,220
MAX
2,375
MAX
EXISTING ADDITION
MATERIAL CLASS/LEVEL QUANTITY
NOTES:
* AUTOMATIC SPRINKLER PROTECTION ALLOWANCES HAVE BEEN APPLIED IN ACCORDANCE
WITH NFPA 30 SECTION 9.6.2.1.
HAZARDOUS MATERIAL STORAGE LIMITATIONS
AEROSOLS
1 UNLIMITED
IIIA 120 GAL
IIIB 1,560 GAL
COMBUSTIBLE LIQUIDS (BUSINESS OCCUPANCY)*
COMBUSTIBLE LIQUIDS (LIQUID STORAGE ROOMS)
IIIB 240 GAL
IB 20 GALFLAMMABLE LIQUIDS (BUSINESS OCCUPANCY)*
2 2,000 LB
GENERAL SHEET NOTES:
1.
2.
3.
4.
5.
FOR LIFE SAFETY LEGEND, SEE SHEET GI001.
FIRESTOP PENETRATIONS AND JOINTS TO MAINTAIN THE
INTEGRITY OF THE FIRE-RATED CONSTRUCTION. FIRE-
RESISTANCE-RATING OF WALLS, FLOORS, CEILINGS, AND
SHAFTS MUST BE MAINTAINED.
PENETRATIONS AND JOINTS MUST BE PROVIDED WITH UL
LISTED FIRESTOP SYSTEMS.
THE RATINGS OF FIRESTOP SYSTEMS MUST BE GREATER
THAN OR EQUAL TO THE RATING OF THE BARRIER.
UL ASSEMBLIES AND MATERIAL PRODUCT DATA SHEETS
FOR FIRESTOPPING SYSTEMS MUST BE SUBMITTED AND
APPROVED BEFORE ANY FIRESTOPPING IS INSTALLED.
REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS AND INFORMATION.
SATISFACTORY TO
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
D E S
IG
N A
N D
C O
N S T R U
C T
IO
N
D C
C O
R E
N A V A L S
T A T
IO
N
N O
R F O
L K V A
M A
R
IN
E C
O R
P S
B A
S E
C A
M P
L E
J E
U N
E
N C n t
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
A T
L A
N T
IC
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJEUNE
C U s e rs
\a e lb o g h d a d y \D o c u m e n ts \2
F
IR
E
A
B a e lb o g h d a d y .r v t
/2
/2
:1
:2
P
M P -1
A
D D
IT
IO
N L
IF
E
S A
F E
T Y
F L O
O R
P L A
N
GI101
1760523
FINAL DESIGN SUBMITTAL
12915315
MARCH 19, 2025
APF AHE KEC
DRR/KRT
EJA
DSN
P -1
T
H M
A R
IN
E
S O
P E
R A
T
IO
N A
L C
O M
P L
E X
GRAPHIC SCALE: 1/16"=1'-0"
16' 0 8' 16' 32'
N
SCALE: 1/16" = 1'-0"
A3
P-1495 ADDITION LIFE SAFETY FLOOR PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
Lic. No. 044409
AARON P FREIDC
O M M O
N W
EAL
THOF
V
IR
G
IN
IA
P R O F
E
SSIONAL EN
G
IN
E E R
06 MAY 2025
DSN
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
DE
SI
GN
A
ND
C
ON
ST
RU
CT
IO
N
(D C)
C
OR
E
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
Fi le
Pa th
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJUENE
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \S
TR
U
C T_
_A 5_
B1
7_ ho ne w el l.r vt 4/
/2
4:
:4
PM
C O
VE
R
S H
EE
T
S-001
1760523
FINAL SUBMITTAL
12915316
MARCH 19, 2025
BCC HON LGG
DRR/KRT
NBJ
EJA
DSN
06 MAY 2025
P-
0T H
M
AR
IN
ES
O
PE
R
AT
IO
N
AL
C
O M
PL
EX
SHEET INDEX
SHEET NO SHEET TITLE
S-001 COVER SHEET
S-002 STRUCTURAL NOTES
S-003 STRUCTURAL NOTES
S-101 FOUNDATION & ROOF FRAMING PLAN
S-501 GENERAL CONSTRUCTION DETAILS
S-502 GENERAL CONSTRUCTION DETAILS
A A
ZONE 45 5
3 2 3
3 2 3
ZO
NE
WALLS
ROOF
COMPONENTS & CLADDING PRESSURE (PSF)
SHOP DRAWINGS/SUBMITTALS:ABBREVIATIONS:
ParallelPAR.
CONT Continuous
Double Degree Demolish, Demolition
Centered Counter Sink
Depressed
Existing
Electric, Electrical
Each Face
Elevation Edge Nail
Equipment
Expansion Joint
Drawing
Diameter Diagonal Dimension
Drag Truss
Face of Steel (Studs)
Face Of
Far Side
Face of Masonry
Field Nail Floor, Flooring
Foundation
Face of Concrete
Existing
Exterior Expansion
Each Way
Finish, Finished
Finished Floor Finish Grade
Floor Joist
Future
Header Hanger
Height
Gusset
Heating/Ventilation/ Air Conditioning
Hold Down
Horizontal High Point
Grade Beam
Grade, Grading Glued Laminated Girder Truss
Footing
Each Side
Laminated Length, Angle
Include
Inside Diameter
Information
Interior Insulated
FTG
INT.
JST
L
LAM
JT. Joint Joist
HT
H.P.
HORIZ
H.V.A.C
IN
I.D.
INCL
INFO
INS
Inch
GA
GD
G.B.
FUT.
GLB
G.T.
HD
HGR
HDR
GUSS.
Gauge
Equal
F.J.
FLR
F.N.
FND
F.S.
F.O.
F.O.C.
F.O.S.
F.O.M.
FT. Feet
EQ.
EQPT.
EXP.
E.W.
F.F.
F.G.
FIN
EXT.
EXIST'G
E.S.
DO
DWG
DWL
D.T.
E.F.
E.J.
E.N.
ELV
ELEC
EA.
Dowel
Each
CSK
DBL
DEG
DEP
DEM
CTR'D
DIA
DIM
DIAG
Ditto
Pounds per Cubic Foot
Plate, Property Line
Precast Concrete
Pounds per Square Foot Pounds per Square Inch
Revision, Revised
Pressure Treated
R.,RAD.
Return
Rafters Roof
Required Reinforcement Reference
RFT.
RF.
REF.
RET.
REQ.
REINF.
REV.
Plywood Panel
Penetration
Radius
PLY.
PNL.
P.T.
P.S.I.
P.S.F.
PENT.
P.C.C.
P.C.F.
PL.
American Concrete Institute
Air Conditioning Anchor Bolt
Bottom Bottom of Footing
Above Finished Floor
American Society for Testing Materials
American Plywood Institute
Between
Blocking
Boundry Nail
Adjacent
Architect
Alternate Aluminum
Concrete Masonry Unit
Control Joint / Ceiling Joist
Connection Construction
Ceiling
Cast-in-Place
Concrete
Channel
ARCH.
C.J.
CLG
COL
CLR
CONC
CMU
C.I.P.
CONST
CONN
C
Column
Clear
A.S.T.M.
B.N.
BM
BLW.
BETWN.
BLK.
BOTT
B.O.F.
BLKG
Beam
Below
Block
A/C A.B.
A.C.I.
AL.
ADJ.
ALT.
A.P.A.
A.F.F.
Long Leg Horizontal
Mount, Mounted, Mounting
Manufacture, Manufacturer
Long Leg Vertical
Opposite Hand, Overhead Outside Diameter
MaximumMAX
Number Nominal
Opening
On Center Not To Scale
Not In Contract
Near Side
North
O.D.
O.C.
N.T.S.
OPNG
O.H.
NOM
N.S.
N.I.C.
NO.
N.
Minimum
Medium
Metal
Mezzanine
Miscellaneous Masonry Opening
Machine Bolt
Mechanical
MFR
MIN
MISC
M.O.
MTL
MT.
MECH
M.B.
MEZZ
MED
Long Pound
Live Load
Louver Masonry
Low Point
L.L.H.
L.P.
LVR
MAS
L.L.V.
L.L.
LG
LB
(E)
P PlateL
Unless Otherwise Noted Unless Noted Otherwise
Welded Wire Mesh Welded Wire Fabric WeightWT.
W.W.M.
W.W.F.
Vapor Barrier Vertical
Without
West Wood
Water Proof Working Point
With
W/O W.P.
W.PT.
W.
WD.
V.B.
U.O.N.
VERT.
U.N.O.
W/
Toe Nail
Typical Tube Steel Top of Wall
Top of Beam
Top of Steel Top of Parapet Top of Footing Top of Concrete
T.O.S.
T.S.
TYP.
T.O.W
T.N.
T.O.B.
T.O.P.
T.O.F.
T.O.C.
Sheet Metal Screw Specification(s)
Thick, Thickness
R.T. Roof Truss
S.S. Stainless Steel
Steel Structural
Stiffener Standard
Tongue & Groove Top & Bottom Symmetrical Suspended
Top of Curb
SYM
THK
T.C.
T&G T&B
STL.
STD.
STRUCT
STIFF.
SUSP.
South Schedule Section
Similar Sheet
Square
Separation
SHT.
SIM.
SPEC.
S.M.S.
SQ.
SEC.
SEP.
SCHED.
S.
Room
Rough Sawn Rough Opening
R.S.
R.O.
RM.
International Building CodeIBC Seismic Lateral Resisting SystemSLRS
GalvanizedGAL
Grade BeamGB
Masonry Control JointMCJ
Pre-Engineered Metal BuildingPEMB.
Powder Acuated FastenersP.A.F.
S-XXX
A1
A1
S-XXX
A1
S-XXX
GRID LINES - CENTER LINE
DETAIL NO.
ELEVATION NO.
SECTION NO.
SECTION
ELEVATION
DETAIL BUBBLE
GRID LINES - F.O. STUD/WALL
GRID NO.
SHEET NO. WHERE
SECTION IS SHOWN
SHEET NO. WHERE
ELEVATION IS SHOWN
SHEET NO. WHERE
DETAIL IS SHOWN
DESIGN BASIS: SYMBOLS:
RO
OF
COMPONENTS & CLADDING NEW DESIGN WIND PRESSURE (ULTIMATE)
ZONE
EFFECTIVE
WIND
AREA
(+) PRESSURE
(PSF)
(-) PRESSURE
(PSF)
1 10 36 -64
1 20 31 -57
1 50 25 -47
1 100 20 -40
2 10 -88
2 20 -79
2 50 -66
2 100 -57
3 10
3 20
3 50
3 100
4 10 48 -52
4 20 46 -50
4 50 48 -47
4 100 41 -45
4 500 36 -40
5 10 -64
5 20 -60
5 50 -54
5 100 -50
5 500 -40
W
AL
LS
-88
-79
-66
-57
ZO
NE
REFERENCE SPECIFICATIONS FOR
SPECIAL INSPECTION REQUIREMENTS
DESIGN CRITERIA
1. BUILDING CODES..............................2021 IBC "INTERNATIONAL BUILDING CODE"
UFC 1-200-01, CHANGE 2, 12 JUN 2023 "GENERAL BUILDING REQUIREMENTS"
UFC 3-301-01, CHANGE 1, 02 OCT 2023 "STRUCTURAL ENGINEERING"
UFC 4-010-01, CHANGE 2, 30 JUL 2022 "MINIMUM ANTI-TERRORISM
STANDARDS FOR BUILDINGS"
2. BUILDING RISK CATEGORY........................................................................................... II
3. SUPERIMPOSED DEAD LOADS:
a) ROOF...................................................................................................... 20 PSF
4. DESIGN LIVE LOADS:
a) ROOF...................................................................................................... 20 PSF
b) FLOOR.................................................................................................. 100 PSF
c) VEHICLE BAY (AXLE LOAD) ...................................................................... 16K
5. SNOW:
a) GROUND SNOW LOAD ........................................................................ 10 PSF
b) FLAT ROOF SNOW LOAD..................................................................... 10 PSF
c) SNOW EXPOSURE FACTOR, Ce ............................................................... 1.0
d) IMPORTANCE FACTOR, Is ........................................................................ 1.0
e) THERMAL FACTOR, Ct ............................................................................... 1.0
f) SNOW SURCHARGE LOADING..........................SEE ROOF FRAMING PLAN
6. WIND
a) ULTIMATE WIND SPEED (RISK CAT. II)........................................... 144 MPH
b) NOMINAL WIND SPEED.................................................................... 112 MPH
c) WIND EXPOSURE CATEGORY..................................................................... B
d) INTERNAL PRESSURE COEFFICIENT .................................................... 0.18
e) ROOF COMPONENTS AND CLADDING .......... SEE TABLE ON SHEET S001
f) WALL COMPONENTS AND CLADDING .......... SEE TABLE ON SHEET S001
g) WIND BASE SHEAR (ULTIMATE).............. Vx & Vy - SEE PEMB DRAWINGS
7. SEISMIC:
a) SITE CLASS .................................................................................................. D
b) IMPORTANCE FACTOR, Ie ........................................................................ 1.0
c) MAPPED SPECTRAL RESPONSE ACCELERATION, Ss ................... 0.115 G
d) ONE SECOND PERIOD SPECTRAL RESPONSE COEFFICIENT, ..... 0.055 G
e) SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT, SDS ........ 0.123 G
f) ONE SEC PERIOD SPECTRAL RESPONSE COEFFICIENT, SD1...... 0.088 G
g) SEISMIC RESPONSE COEFFICIENT, Cs ............................................... 0.041
h) RESPONSE MODIFICATION FACTOR, R
i) SEISMIC DESIGN CATEGORY .................................................................... B
j) BASIC SEISMIC FORCE RESISTING SYSTEM ........... STEEL SYSTEM NOT
SPECIFICALLY DETALED FOR SEISMIC RESISTANCE
k) ANALYSIS PROCEDURE ............................ EQUIVALENT LATERAL FORCE
l) SEISMIC BASE SHEAR ...................................... V = SEE PEMB DRAWINGS
8. RAIN:
a) RAIN INTENSITY, i ............................................................................ 4.25 in/hr
1.
2.
3.
4.
5.
SEE SPECIFICATIONS AND DEFERRED SUBMITTAL REQUIREMENTS ON SHEET
S-002 FOR REQUIRED SHOP DRAWING AND SUBMITTAL REQUIRMENTS TO BE
PROVIDED TO THE CONTRACTING OFFICER FOR REVIEW AND COMMENT.
STEEL REINFORCING LISTS AND QUANTITIES AND LENGTH OF ALL MATERIALS
ARE THE RESPONSIBILITY OF THE CONTRACTOR TO ASSURE COMPLIANCE
WITH THE PLANS. THE ENGINEER WILL NOT REVIEW THESE ITEMS.
REVIEW OF SHOP DRAWINGS IS FOR THE PURPOSE OF GENERAL COMPLIANCE
WITH THE CONTRACT DOCUMENTS. ALL ERRORS IN DETAILING, FABRICATION,
AND CORRECT FITTING OF ALL STRUCTURAL MEMBERS INCLUDING
COORDINATION WITH OTHER TRADES ARE THE RESPONSIBILITY OF THE
CONTRACTOR. SHOP DRAWING SUBMITTAL REVIEW DOES NOT CONSTITUTE
CHANGE ORDERS. ANY PROPOSED CHANGES MUST BE SUBMITTED IN A
LETTER OR DETAIL FOR APPROVAL.
SHOP DRAWINGS MUST BE SUBMITTED AT LEAST TWO WEEKS PRIOR TO THE
SCHEDULED FABRICATION DATE.
REPRODUCTION OF THESE STRUCTURAL DRAWINGS IS PROHIBITED FOR THE
PURPOSE OF PREPARING SHOP DRAWINGS. SUBCONTRACTOR/FABRICATOR
MUST PROVIDE INDEPENDENTLY CREATED DRAWINGS BASED ON THE
INFORMATION SHOWN IN THE CONTRACT DOCUMENTS.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
AP
PR
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
DE
SI
GN
A
ND
C
ON
ST
RU
CT
IO
N
(D C)
C
OR
E
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJUENE
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \S
TR
U
C T_
_A 5_
B1
7_ ho ne w el l.r vt 4/
/2
4:
:4
PM
ST
R
U C
TU
R
AL
N
O
TE
S
S-002
1760523
FINAL SUBMITTAL
12915317
MARCH 19, 2025
BCC HON LGG
DRR/KRT
NBJ
EJA
DSN
06 MAY 2025
P-
0T H
M
AR
IN
ES
O
PE
R
AT
IO
N
AL
C
O M
PL
EX
3.0
STRUCTURAL NOTES
2.0 FOUNDATION:1.0 GENERAL NOTES: 3.3 MECHANICAL ANCHORS IN HARDENED
CONCRETE AND MASONRY
(EXPANSION ANCHORS):
CONCRETE: 3.2 ADHESIVE, ANCHOR RODS AND REBAR
IN HARDENED CONCRETE (EPOXY
ANCHORS):
1.0.1
1.0.2
1.0.3
1.0.4
1.0.5
1.0.6
1.0.8
1.0.9
1.0.10
1.0.11
1.0.12
1.0.13
A.
B.
C.
D.
E.
F.
G.
A.
B.
C.
D.
THE PROJECT SPECIFICATIONS (A BOOK OF SPECIFICATIONS WHEN PROVIDED)
ARE A PART OF THE CONTRACT DOCUMENTS. IF THERE IS A DISCREPANCY
FOUND BETWEEN THE SPECIFICATIONS AND THE DRAWINGS, SPECIFICATIONS
TAKE PRECEDENCE, HOWEVER THE MATTER MUST BE PROMPTLY SUBMITTED
TO THE CONTRACTING OFFICER FOR CLARIFICATION. WORK PERFORMED BY
THE CONTRACTOR WITHOUT SUCH A CLARIFICATION MUST BE AT
CONTRACTOR'S OWN RISK AND EXPENSE.
EXAMINE THE STRUCTURAL DRAWINGS AND THE SPECIFICATIONS AND NOTIFY
THE ENGINEER & CONTRACTING OFFICER OF DISCREPANCIES IN ELEVATIONS,
DIMENSIONS, AND SITE CONDITIONS INCLUDING ERRORS BEFORE PROCEEDING
WITH WORK. OMISSIONS AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS
OF THE DRAWINGS (AND SPECIFICATIONS) MUST BE RESOLVED IN WRITING
WITH THE ENGINEER/ARCHITECT & CONTRACTING OFFICER PRIOR TO START OF
WORK.
THE DRAWINGS (AND SPECIFICATIONS) REPRESENT THE COMPLETED
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION.
PROVIDE MEASURES AND MEANS NECESSARY TO PROTECT PERSONS AND THE
STRUCTURE DURING CONSTRUCTION. SUCH MEASURES MUST INCLUDE, BUT
NOT BE LIMITED TO BRACING, SHORING, ETC. OBSERVATION VISITS BY THE
ARCHITECT OR ENGINEER DOES NOT INCLUDE REVIEW OF THESE MEASURES.
TYPICAL DETAILS MUST BE USED WHENEVER APPLICABLE WHETHER
SPECIFICALLY REFERENCED OR NOT.
DRAWINGS MUST NOT BE SCALED FOR CONSTRUCTION PURPOSES.
PIPES OR DUCTS MUST NOT BE PLACED IN STRUCTURAL MEMBERS UNLESS
SPECIFICALLY DETAILED OR APPROVED BY THE ENGINEER & CONTRACTING
OFFICER.
REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS, UNLESS
OTHERWISE NOTED.
SIZE AND LOCATION OF INTERIOR AND EXTERIOR NON-BEARING
PARTITIONS.
SIZE AND LOCATION OF CURBS, FLOOR DRAINS, SLOPES, DEPRESSED
AREAS, CHANGES IN LEVEL, RAMPS, CHAMFERS, GROOVES, INSERTS,
ETC., EXCEPT AS SHOWN.
SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS, EXCEPT AS
SHOWN.
FLOOR AND ROOF FINISHES.
STAIR FRAMING AND DETAILS, EXCEPT AS SHOWN.
DIMENSIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE
FOLLOWING:
PIPE RUNS, SLEEVES, HANGERS, TRENCHES, SLAB OPENINGS, ETC.,
EXCEPT AS SHOWN OR NOTED.
ELECTRICAL CONDUITS, BOXES, OUTLETS.
CONCRETE INSERTS FOR ELECTRICAL, MECHANICAL AND PLUMBING
FIXTURES.
SIZE AND LOCATION OF MACHINE AND EQUIPMENT BASES, ANCHOR
BOLTS, ETC.
ASTM REFERENCES ARE FROM THE LATEST ISSUE AND LATEST REVISION,
UNLESS OTHERWISE NOTED.
INVESTIGATE THE SITE DURING CLEARING AND EXCAVATION FOR UNSUITABLE
CONDITIONS, UNCONSOLIDATED AND UNDOCUMENTED FILLS, BURIED
STRUCTURES, UTILITIES, ETC., AND IMMEDIATELY NOTIFY THE
ARCHITECT/ENGINEER & CONTRACTING OFFICER OF SITE CONDITIONS NOT
REFLECTED ON THE DRAWINGS OR DIFFERENT FROM MAXIMUM OR MINIMUM
DIMENSIONS INDICATED, INCLUDING CONFLICT IN GRADES, ADVERSE SOIL
CONDITIONS, GROUNDWATER PRESENT, DEEPENED FOOTINGS, UNCOVERED
AND UNEXPECTED UTILITY LINES, ETC.
CONSTRUCTION MATERIALS, IF PLACED ON STRUCTURAL MEMBERS, MUST BE
SPREAD OUT SUCH THAT THE LOADING DOES NOT EXCEED THE DESIGN LIVE
LOADS. PROVIDE SHORING AND BRACING WHERE CONSTRUCTION LOADING
EXCEEDS THE DESIGN STRENGTH OF THE STRUCTURAL MEMBERS OR THE
STRUCTURAL STRENGTH HAS NOT BEEN ATTAINED OR THE STRUCTURE IS NOT
COMPLETE.
DETERMINE THE LOCATION OF UTILITY SERVICES IN AREAS TO BE EXCAVATED
BEFORE BEGINNING EXCAVATION. EXERCISE EXTREME CAUTION IN
EXCAVATING AND TRENCHING. DAMAGE CAUSED AS A RESULT OF FAILING TO
EXACTLY LOCATE AND PRESERVE EXISTING UNDERGROUND UTILITIES IS THE
RESPONSIBILITY OF THE CONTRACTOR.
STRUCTURAL DRAWINGS TO BE USED IN CONJUNCTION WITH ARCHITECTURAL
DRAWINGS BY: MBF ARCHITECTS
1.0.7
2.0.1
2.0.2
2.0.3
2.0.4
2.0.5
2.0.6
2.0.7
2.0.8
2.0.9
SUBMIT COMPACTION TEST REPORTS FOR FILL BY A QUALIFIED TESTING LAB
TO ARCHITECT/ENGINEER & CONTRACTING OFFICER BEFORE FOUNDATION
PLACEMENT. LOOSE SOIL AND FILL DIRT MUST BE COMPACTEDTO A MINIMUM
OF 95% MAXIMUM DENSITY.
THE FOOTING EXCAVATIONS MUST BE KEPT FREE FROM LOOSE MATERIAL AND
STANDING WATER AND MUST BE NEAT AND TRUE TO LINE BEFORE CONCRETE
IS PLACED.
ABANDONED FOOTINGS, UTILITIES, ETC. THAT INTERFERE WITH NEW
CONSTRUCTION MUST BE REMOVED.
WALL FOOTINGS ARE CONTINUOUS POURED CONCRETE WITH CONTINUOUS
REINFORCING PLACED 3" CLEAR OF BOTTOM AND SIDES.
UNLESS OTHERWISE NOTED, WALL FOOTINGS ARE CENTERED UNDER WALLS
AND COLUMN FOOTINGS UNDER COLUMNS.
PROVIDE FOR DESIGN AND INSTALLATION OF CRIBBING, SHEATHING AND
SHORING REQUIRED TO SAFELY RETAIN GRADES.
PROVIDE FOR DE-WATERING OF EXCAVATIONS FROM SURFACE, GROUND, AND
OR SEEPAGE WATER.
FOUNDATION DESIGN IS BASED ON A MAXIMUM ALLOWABLE SOIL BEARING
PRESSURE OF 2,000 PSF PER THE PROVIDED EXISTING BUILDING DRAWINGS
AND GEOTECHNCIAL REPORT FOR PROJECT P1495.
FOOTING DEPTHS SHOWN ARE A MINIMUM AND MAY REQUIRE DEEPENING
BASED ON SITE CONDITIONS.
3.1.9
3.1.10
3.1.11
REINFORCING STEEL:3.1
SLAB ON GRADE
FOOTINGS & ALL OTHER CONCRETE
MIN. f'c
4,000 psi 3,000 psi
SLAB ON GRADE REINFORCEMENT MUST BE POSITIONED AT MID-DEPTH.
SHOP DRAWINGS FOR SIZE AND LAYOUT OF REINFORCING REBARS ARE
REQUIRED WHEN NOTED IN THE LIST OF REQUIRED SHOP DRAWINGS.
3.0.11 PROVIDE CONSTRUCTION OR CONTROL JOINTS IN SLAB ON GRADE AS SHOWN
ON PLANS UNLESS SPECIFIED OTHERWISE. LOCATION OF JOINTS NOT
SPECIFICALLY INDICATED MUST BE REVIEWED BY THE STRUCTURAL ENGINEER &
CONTRACTING OFFICER PRIOR TO PLACING REINFORCING STEEL.
DRY PACK MUST BE ONE PART CEMENT AND 2 3/4 PARTS SAND WITH JUST
ENOUGH WATER TO HYDRATE CEMENT AND FORM A BALL SHOWING MOISTURE
ON THE SURFACE WHEN SQUEEZED. IT MUST BE RAMMED IN TIGHT TO MAXIMUM
DENSITY ATTAINABLE, AND MUST BE FROM A PRODUCT THAT SPECIFIES A
MINIMUM STRENGTH AT 28 DAYS OF 5000 psi.
NON-SHRINK GROUT MUST BE FROM A PRODUCT THAT SPECIFIES A MINIMUM
COMPRESSIVE STRENGTH AT 28 DAYS OF 7,000 psi PER ASTM C109. GROUTING
OF BASE PLATES PRIOR TO PLUMBING OF COLUMN IS NOT PERMITTED.
PROJECTING CORNERS OF SLABS, BEAMS, WALLS, COLUMNS, ETC., MUST BE
FORMED WITH A 3/4" CHAMFER OR TOOLED EDGE, UNLESS OTHERWISE NOTED.
CONCRETE WHICH DURING THE LIFE OF THE STRUCTURE WILL BE SUBJECT TO
FREEZING TEMPERATURES WHILE WET, MUST HAVE A WATER CEMENT RATIO
NOT EXCEEDING 0.45 BY WEIGHT AND MUST CONTAIN ENTRAINED AIR PER ACI
613. SUCH CONCRETE MUST INCLUDE EXTERIOR SLABS, PERIMETER
FOUNDATIONS, EXTERIOR CURBS, ETC.
3.0.12
3.0.13
3.0.14
3.0.15
3.0.1 CEMENT MUST CONFORM TO ASTM C150, TYPE II / V
AGGREGATES FOR NORMAL WEIGHT CONCRETE MUST CONFORM TO ASTM C33,
1 1/2" MAXIMUM SIZE.
ADMIXTURES MUST NOT BE USED WITHOUT PRIOR APPROVAL OF THE ENGINEER
& CONTRACTING OFFICER. ADMIXTURES USED TO INCREASE THE WORKABILITY
OF THE CONCRETE MUST NOT REDUCE THE STRENGTH OF CONCRETE. FLY ASH
(POZZOLAN) IF PERMITED BY SPECIFICATIONS MUST NOT EXCEED 25% FOR SLAB
ON GRADE AND 25% FOR OTHER CONCRETE.
THE MIX DESIGN, INCLUDING PROPORTIONS OF MATERIALS FOR A ONE YARD
BATCH, MUST BE SUBMITTED TO THE ENGINEER OF RECORD & CONTRACTING
OFFICER FOR REVIEW PRIOR TO ORDERING CONCRETE.
READY-MIX CONCRETE MUST BE MIXED AND DELIVERED IN ACCORDANCE WITH
ASTM C94.
REINFORCING BARS AND INSERTS MUST BE SECURED IN PLACE PRIOR TO
PLACING CONCRETE.
CONDUITS EMBEDDED HORIZONTALLY IN THE SLAB MUST HAVE AN OUTSIDE
DIAMETER NO GREATER THAN 1/3 THE THICKNESS OF THE SLAB. CONDUIT MUST
NOT BE EMBEDDED IN A SLAB THAT IS LESS THAN 3 1/2" THICK. EXCEPT FOR
LOCAL OFFSETS, MIN. CLEAR DISTANCE BETWEEN CONDUITS MUST BE 6".
NON-STRUCTURAL STEEL MEMBERS EMBEDDED IN CONCRETE MUST BE
GALVANIZED OR PAINTED. DAMAGED GALVANIZED AREAS MUST BE REPAIRED
PRIOR TO EMBEDMENT.
CONCRETE MUST HAVE A MAXIMUM DRY DENSITY OF 150 pcf.
MINIMUM CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS.
3.0.2
3.0.3
3.0.4
3.0.5
3.0.6
3.0.7
3.0.8
3.0.9
3.0.10
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED
TO EARTH:.............................................................................. 3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
NO.6 THROUGH NO.18 BAR ................................... 2"
NO.5 BAR, W31 OR D31 WIRE, AND SMALLER ....1 1/2"
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT
WITH GROUND:
SLABS, WALLS, JOISTS:
NO.14 AND NO.18 BAR .............................................1 1/2"
NO.11 BAR AND SMALLER ...................................... 3/4"
3.1.1 DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS MUST BE IN
ACCORDANCE WITH ACI MANUAL OF STANDARD PRACTICE FOR DETAILING
REINFORCED CONCRETE STRUCTURES, ACI 315-LATEST ADOPTED EDITION.
REINFORCING MUST BE ADEQUATELY SUPPORTED TO PREVENT DISPLACEMENT
BY CONCRETE PLACEMENT OR WORKERS.
REINFORCING BARS EXCEPT BARS TO BE WELDED MUST CONFORM TO THE
"STANDARD SPECIFICATION FOR DEFORMED BILLET STEEL BARS FOR
CONCRETE REINFORCEMENT", ASTM A615 GRADE 60. BARS TO BE WELDED
MUST CONFORM TO ASTM A706.
WELDING OF REINFORCING BARS TO BE IN ACCORDANCE WITH "STRUCTURAL
WELDING CODE-REINFORCING STEEL", AWS D1.4. REINFORCING STEEL TO BE
WELDED MUST HAVE A MAXIMUM CARBON EQUIVALENT (CE) OF 0.75. SPECIAL
INSPECTION IS REQUIRED. TESTING IS REQUIRED FOR WELDS THICKER THAN
5/16".
WHERE CONTINUOUS BARS ARE CALLED OUT IN FOOTINGS, SPLICES MAY BE
USED. WHERE BARS ARE SHOWN SPLICED, THEY MAY RUN CONTINUOUS AT
CONTRACTOR'S OPTION.
REINFORCING BAR BENDS MUST BE MADE COLD.
UNLESS OTHERWISE SHOWN, WALL VERTICAL REINFORCING MUST BE
POSITIONED AT THE CENTER OF THE WALL.
DOWELS BETWEEN FOOTINGS AND WALLS MUST BE THE SAME GRADE, SIZE,
AND SPACING AS VERTICAL REINFORCING.
REINFORCING BARS MUST BE PROVIDED WITH THE FOLLOWING CONCRETE
COVER:
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.2.11
A.
B.
ADHESIVE ANCHOR INSTALLATIONS MUST COMPLY WITH MANUFACTURER'S
WRITTEN INSTRUCTIONS AND SPECIFICATIONS, INLCUDING ICC-ES REPORTS
DUST MUST BE BLOWN FROM THE HOLE WITH COMPRESSED AIR TO
ENSURESURFACE. ADDITIONALLY, THE HOLE MUST BE BRUSHED WITH A NYLON
BRUSH THEN BLOWN AGAIN WITH COMPRESSED AIR.
ADHESIVE MUST ONLY BE APPLIED TO DRY SURFACES.
BASE MATERIAL TEMPERATURE MUST BE 40°F OR ABOVE AT TIME OF
INSTALLATION. FOR BEST RESULTS, MATERIAL SHOULD BE 70°F-80°F.
WHEN INSTALLING EPOXY ANCHORS INTO MASONRY, ANCHORS MUST BE
INSTALLED IN SOLID GROUTED CELLS ONLY.
CHEMICAL ANCHOR SYSTEMS:
CONCRETE: USE ONLY ADHESIVE ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH PROVISIONS OF OF
ICC-ES AC308. ANCHOR SYSTEM SHOULD BE APPROVED FOR USE IN
CRACKED CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER
SECTION 2.0 OF THE ICC-ES EVALUATION SERVICES REPORT. ANCHOR
SYSTEM MUST BE INSTALLED PER REQUIREMENTS OF THE ICC-ES
EVALUATION SERVICES REPORT FOR SPECIFIC ANCHOR, AND AS
REQUIRED BY THE MANUFACTURER.
GROUT-FILLED MASONRY UNITS: USE ONLY ADHESIVE
ANCHORSYSTEMS THAT HAVE BEEN ISSUED AN ICC-ES REPORT
INACCORDANCE WITH PROVISIONS OF ISS-ES AC58. ANCHORSYSTEMS
MUST BE INSTALLED PER REQUIREMENTS OF ICC-ESEVALUATION
SERVICES REPORT FOR THE SPECIFIC ANCHOR,AND AS REQUIRED BY
THE MANUFACTURER.
ANCHOR RODS:
RODS MUST BE ASTM A36 THREADED RODS WITH ASTM A563 GRADE A NUTS
AND ANSI B18.22.1 TYPE A WASHERS, UNLESS OTHERWISE NOTED. ANCHORS
DESIGNATED AS ASTM A193 GRADE B7 THREADED RODS MUST USE ASTM A563
GRADE DH HEAVY HEX NUTS AND ASTM F436 WASHERS.
REINFORCEMENT BARS: ASTM A615 GRADE 60 STEEL.
REMOVE GREASE, OIL, RUST AND OTHER LAITANCE FROM RODS AND DOWELS
PRIOR TO INSTALLATION.
SPECIAL INSPECTION REQUIREMENTS MUST BE DICTATED BY SECTION 4.0 OF
THE ICC-ES EVALUATION SERVICES REPORT. SPECIAL INSPECTION MUST
VERIFY ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, CONCRETE
COMPRESSIVE STRENGTH, HOLE DIMENSIONS, ANCHOR SPACINGS, EDGE
DISTANCES, SLAB THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING
TORQUE.
CONTRACTOR'S OPTION TO USE OTHER MANUFACTURER'S PRODUCTS ONLY
WITH PRIOR APPROVAL OF THE ENGINEER & CONTRACTING OFFICER. SUBMIT
MANUFACTURER'S LITERATURE AND PRODUCT INSTALLATION FOR REVIEW.
3.3.4
3.3.1
3.3.2
3.3.3
3.3.5
3.3.6
3.3.7
3.3.8
3.3.9
A.
B.
ANCHORS TO BE INSTALLED IN HOLES DRILLED WITH CARBIDE-TIPPED DRILL
BITS. ANCHORS TO BE INSTALLED PER MANUFACTURER'S WRITTEN
INSTRUCTIONS.
WHEN INSTALLING DRILLED EXPANSION ANCHORS IN EXISTING REINFORCED
CONCRETE, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING THE
EXISTING REINFORCEMENT.
MAINTAIN A MINIMUM CLEARANCE OF 25 mm[1"] BETWEEN THE REINFORCEMENT
AND THE DRILLED EXPANSION ANCHORS. EXPANSION ANCHORS MUST NOT BE
USED AT CONCRETE CURBS.
EXPANSION ANCHOR SYSTEMS:
CONCRETE: USE ONLY EXPANSION ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF
ICC-ES AC193. ANCHOR SYSTEMS SHOULD BE APPROVED FOR USE WITH
CRACKED CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER
SECTION 2.0 OF THE ICC EVALUATIONS SERVICES REPORT. ANCHOR
SYSTEM MUST BE INSTALLED PER THE REQUIREMENTS OF THE ICC-ES
EVALUATION SERVICES REPORT FOR THE SPECIFIC ANCHOR, AND AS
REQUIRED BY THE MANUFACTURER.
MASONRY: USE ONLY EXPANSION ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF
ICC-ES AC01. ANCHOR SYSTEMS SHOULD BE APPROVED FOR SEISMIC
USE DETAILED IN THE CONDITIONS OF USE LISTED IN THE ICC-ES
EVALUATION SERVICES REPORT. ANCHOR SYSTEM MUST BE INSTALLED
PER THE REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES
REPORT FOR THE SPECIFIC ANCHOR, AND AS REQUIRED BY THE
MANUFACTURER.
UNDERCUT ANCHOR SYSTEMS:
CONCRETE: USE ONLY UNDERCUT ANCHOR SYSTEMS THAT HAVE BEEN ISSUED
AN ICC-ES REPORT IN ACCORDANCE WITH THE PROVISIONS OF ICC-ES AC193.
ANCHOR SYSTEMS SHOULD BE APPROVED FOR USE IN CRACKED CONCRETE
AND SEISMIC DESIGN CATEGORIES A-F PER SECTION 2.0 OF THE ICC
EVALUATIONS SERVICES REPORT. ANCHOR SYSTEM MUST BE INSTALLED
PER THE REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT
FOR SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER.
WHERE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS OR APPLICABLE
ICC-ES EVALUATION SERVICES REPORT CALL FOR THE APPLICATION OF AN
INSTALLATION TORQUE, THE SPECIFIED TORQUE MUST BE APPLIED WITH
CALIBRATED TORQUE WRENCH. THE SPECIFIED INSTALLATION TORQUE MUST
NOT BE EXCEEDED.
ANCHORS ARE TYPICALLY AVAILABLE IN ELECTRO-GALVANIZED CARBON STEEL,
HOT DIPPED GALVANIZED CARBON STEEL, AND STAINLESS STEEL. USE OF
ELECTRO-GALVANIZED CARBON STEEL ANCHORS IS TYPICALLY LIMITED TO DRY,
INTERIOR LOCATIONS, UNLESS OTHERWISE NOTED. STAINLESS STEEL OR HOT-
DIPPED GALVANIZED ANCHORS ARE GENERALLY. SUITABLE FOR APPLICATIONS
EXPOSED TO EXTERIOR WEATHER CONDITIONS. FINAL AUTHORITY ON TYPE OF
ANCHOR COATING UTILIZED RESTS WITH THE STRUCTURAL ENGINEER OF
RECORD & CONTRACTING OFFICER AND MUST BE APPROVED BY SUCH.
EXPANSION ANCHORS FOR NON-VIBRATION ISOLATED MECHANICAL EQUIPMENT
RATED OVER 10HP ARE NOT PERMITTED BY ASCE 7-10 SECTION 13.6.5.5.
ANCHORS INSTALLED IN OVERHEAD CONDITIONS FOR NON- VIBRATION
ISOLATED EQUIPMENT WITH RECIPROCATING OR ROTATING MECHANISMS MUST
BE UNDERCUT ANCHORS.
THE SPECIAL INSPECTOR MUST BE ON THE JOBSITE CONTINUOUSLY DURING
ANCHOR INSTALLATIONS, UNLESS OTHERWISE NOTED IN ICC-ES ESR, TO VERIFY
ANCHOR TYPE, ANCHOR DIMENSIONS, CONCRETE TYPE, CONCRETE
COMPRESSIVE STRENGTH, HOLE DIMENSIONS ANCHOR SPACINGS, EDGE
DISTANCES, SLAB THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING
TORQUE.
1.
A.
B.
C.
D.
E.
2.
DEFERRED SUBMITTALS:
THE DEFERRED SUBMITTAL ITEMS MUST NOT BE INSTALLED UNTIL
THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN
REVIEWED BY THE ARCHITECT OR ENGINEER OF RECORD AND
THAT THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE
WITH THE DESIGN OF THE BUILDING.
LADDERS, GUARDRAILS, HANDRAILS AND THEIR COMPONENTS
PRE-ENGINEERED BUILDING SHOP DRAWINGS AND COLUMN
BASE REACTIONS FOR FOUNDATOIN VERIFICATION
SUPPORT ANCHORAGE OF MECHANICAL, ELECTRICAL AND
PLUMBING EQUIPMENT AND COMPONENTS
COLD-FORMED FRAMING /METAL STUDS CALCULATIONS AND
SHOP DRAWINGS INCLUDING LAYOUT, TYPICAL CONSTRUCTION
DETAILS, AND CONNECTIONS (ITEMS SHOWN IN PLANS ARE
MINIMUM SIZES REQUIRED)
SLAB ON GRADE CONTROL JOINT PLAN (PE SEAL NOT
REQUIRED FOR THIS ITEM)
THE ABOVE LISTED SUBMITTAL DOCUMENTS MUST BE STAMPED
AND SIGNED BY A REGISTERED PROFESSIONAL ENGINEER IN THE
STATE OF NORTH CAROLINA.
SY
M
D
ES
C R
IP
TI
O N
D
AT
E
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
EPROJECT NO.:
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
DE
SI
GN
A
ND
C
ON
ST
RU
CT
IO
N
(D C)
C
OR
E
NA
VA
L
ST
AT
IO
N
- N
OR
FO
LK
, V A
M
AR
IN
E
C O
R
PS
B
AS
E C
AM
P
LE
JE
U N
E, N
C
P rin t D at e:
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G
S
YS
TE
M
S C
O M
M
AN
D
M
ID
AT
LA
N
TI
C
AS INDICATED
B1337
A5
APPROVED BY SOFIA SCHWARTZ
AMB DIRECTOR
MCB CAMP LEJUENE
C :\U se rs
\h en ry .K
AY
D
O S-
D
AN
IE
LS
\D oc um en ts \S
TR
U
C T_
_A 5_
B1
7_ ho ne w el l.r vt 4/
/2
4:
:4
PM
ST
R
U C
TU
R
AL
N
O
TE
S
S-003
1760523
FINAL SUBMITTAL
12915318
MARCH 19, 2025
BCC HON LGG
DRR/KRT
NBJ
EJA
DSN
06 MAY 2025
P-
0T H
M
AR
IN
ES
O
PE
R
AT
IO
N
AL
C
O M
PL
EX
4.0.1
4.0.2
4.0.3
4.0.4
5.0.1
5.0.2
5.0.3
5.0.4
5.0.5
5.0.6
5.0.7
5.0.8
5.0.9
5.0.10
5.0.11
5.0.12
STRUCTURAL NOTES
4.0 MASONRY:
STRUCTURAL STEEL:5.0
CONCRETE MASONRY UNITS
MASONRY COMPONENTS
DESIGN STRENGTH: f'm = 2000 psi
MORTAR (TYPE S)
GROUT
STRENGTH @ 28 DAYS
2000 psi
3000 psi
1800 psi
MASONRY WORK MUST CONFORM TO INTERNATIONAL BUILDING CODE
(IBC), LATEST ADOPTED EDITION AS LISTED HEREIN.
CONCRETE MASONRY UNITS MUST BE MEDIUM WEIGHT UNITS IN
ACCORDANCE WITH ASTM C90 WITH MAXIMUM LINEAR SHRINKAGE OF 0.065%.
CEMENT MUST BE AS SPECIFIED FOR CONCRETE.
MORTAR MUST CONFORM TO ASTM C270
EXCERPTS FROM ASTM C270:
3.4.1
3.4.2
3.4.3
3.4.4
3.4.5
3.4.6
3.4.7
3.4 POWDER ACTUATED FASTENERS IN
HARDENED CONCRETE, MASONRY,
AND STEEL (SHOT PINS):
A.
B.
C.
POWDER ACTUATED FASTENING SYSTEMS:
CONCRETE: FOR GENERAL CONCRETE AND LIGHTWEIGHT
CONCRETE: POWDER ACTUATED FASTENING SYSTEMS MUST BE
INSTALLED PER REQUIREMENTS OF THE ICC-ES EVALUATION
SERVICES REPORT FOR THE SPECIFIC FASTENER, AND AS
REQUIRED BY THE MANUFACTURER.
MASONRY: POWDER ACTUATED FASTENING SYSTEMS MUST BE
INSTALLED PER THE REQUIREMENTS OF THE ICC-ES EVALUATION
SERVICES REPORT FOR SPECIFIC FASTENER, AND AS REQUIRED
BY THE MANUFACTURER.
STEEL: POWDER ACTUATED FASTENING SYSTEMS MUST BE
INSTALLED PER THE REQUIREMENTS OF THE ICC-ES EVALUATION
SERVICES REPORT FOR THE SPECIFIC FASTENER, AND AS
REQUIRED BY THE MANUFACTURER.
WHEN INSTALLING POWDER ACTUATED FASTENERS IN EXISTING NON-
PRESTRESSED REINFORCED CONCRETE, USE CARE AND CAUTION TO AVOID
HITTING OR DAMAGE TO THE EXISTING REINFORCING BARS. MAINTAIN A
MINIMUM CLEARANCE OF 1" BETWEEN THE REINFORCEMENT AND THE
FASTENER.
POWDER ACTUATED FASTENERS ARE NOT PERMITTED BY ASCE 7-16 SECTION
13.4.5 FOR SEISMIC TENSION LOAD APPLICATIONS. POWDER ACTUATED
FASTENERS MUST NOT BE USED TO CARRY SEISMIC TENSION LOADS (EXCEPT
FOR VERTICAL SEISMIC LOAD PRODUCED BY SELF-WEIGHT OF THE
COMPONENTS SUPPORTED) OR IN CRACKED CONCRETE UNLESS PRE-
APPROVED FOR SUCH LOADING BY THE ENFORCEMENT AGENCY.
THE USE OF POWDER DRIVEN FASTENERS FOR TENSION LOADS IS LIMITED TO
SUPPORT OF MINOR LOADS LIKE ACOUSTICAL CEILINGS, DUCTWORK CONDUITS,
ETC.
ALLOWABLE TENSION LOADS MUST BE LIMITED TO LESS THAN 100 POUNDS.
POWDER ACTUATED FASTENERS MAY BE USED FOR SEISMIC SHEAR, WHEN
THEY ARE SPECIFICALLY LISTED FOR SERVICE IN RESISTING LATERAL LOADS IN
AREAS SUBJECT TO EARTHQUAKE.
MINIMUM EDGE DISTANCE FOR ACTUATED FASTENERS MUST BE THE LARGER
OF THE VALUES GIVEN IN ASTM E 1190 OR THE APPLICABLE ICC-ES EVALUATION
SERVICES REPORT.
PROPORTIONS BY VOLUME (CEMENTITIOUS MATERIALS)
MORTAR TYPE
PORTLAND
CEMENT OR
BLENDED
CEMENT
CEMENT-
LIME
MORTAR
CEMENT
M
S
N
O
M
M
S
S
N
O
1/2
M
M
S
S
N
O
1/2
M S N M S N
TABLE 1 PROPORTION SPECIFICATION REQUIREMENTS
MASONRY
CEMENT
MORTAR
CEMENT
NOT LESS THAN
2 1
4 AND NOT
MORE THAN 31
THE SUM OF
SEPARATE
VOLUMES OF
CEMENTITIOUS
MATERIALS
AGGREGATE
RATIO
(MEASURED IN
DAMP, LOOSE
CONDITIONS)
HYDRATED
LIME OR LIME
PUTTY
1/4
OVER 1/4 TO 1/2
OVER 1/2 TO 1 1/4
OVER 1 1/4 TO 2 1/2
4.0.8
4.0.9
4.0.10
4.0.11
4.0.12
4.0.13
4.0.14
4.0.15
4.0.17
4.0.18
4.0.19
4.0.20
4.0.21
4.0.5
4.0.6
4.0.7
4.0.16
4.0.22
CELLS BELOW GRADE MUST BE FULLY GROUTED UNLESS OTHERWISE NOTED.
ADDITIONALLY, CELLS WITH REINFORCING MUST BE FILLED SOLID WITH
GROUTED UNLESS OTHERWISE NOTED WITHIN THE SECTIONS AND TYPICAL
DETAILS.
GROUT MUST BE CONSOLIDATED WITH A MECHANICAL VIBRATOR.
MINIMUM 4000 rpm, 3/4" MAXIMUM HEAD. PROVIDE INSPECTION AND
CLEANOUT HOLES AT THE BASE OF GROUTED CELLS FOR ALL LIFTS
GREATER THAN 5'-0".
WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL
CONSTRUCTION JOINTS MUST BE FORMED BY STOPPING THE GROUT
POUR 1 1/2" BELOW TOP OF THE UPPERMOST UNIT.
UNLESS OTHERWISE NOTED, MASONRY MUST BE CONSTRUCTED
WITH A RUNNING BOND PATTERN.
ELECTRIC CONDUIT BOXES AND/OR OTHER OBSTRUCTIONS ARE NOT
PERMITTED IN CELLS CONTAINING REINFORCING, UNLESS APPROVED BY
THE ENGINEER & CONTRACTING OFFICER.
UNLESS OTHERWISE SHOWN ON THE PLANS, LAP SPLICES OF
REINFORCING STEEL IN MASONRY MUST BE PER SCHEDULE.
HORIZONTAL REINFORCEMENT BARS MUST BE PLACED IN BOND BEAM
MASONRY UNITS.
LINTEL REINFORCEMENT BARS MUST BE PLACED IN LINTEL BEAM BLOCK.
VERTICAL REINFORCEMENT BARS MUST BE PLACED AT THE CENTER OFTHE
WALL UNLESS OTHERWISE SHOWN. VERTICAL BARS ARE TO BE TIED OR
OTHERWISE FIXED IN POSITION AT INTERVALS OF NOT MORE THAN 200
BAR DIAMETERS AND AT TOP AND BOTTOM.
ANCHOR BOLTS MUST BE SET WITH TEMPLATES AND HELD IN PLACE
PRIOR TO GROUTING.
PROVIDE A MINIMUM OF ONE BAR DIAMETER OF GROUT BETWEEN MAIN
REINFORCING AND MASONRY UNITS. PROVIDE A MINIMUM OF 1"
GROUT AROUND ALL BOLTS EMBEDDED IN MASONRY.
NOT USED
TABLE 2 PROPERTY SPECIFICATION REQUIREMENTSA
MORTAR TYPE
AVG. COMPRESSIVE
STRENGTH AT 28
DAYS, MIN.
WATER
RETENTION,
MIN. %
AIR
CONTENT,
MAX. %B
AGGREGATE RATIO
(MEASURED IN DAMP,
LOOSE CONDITIONS)
GROUT MUST CONFORM TO ASTM C476.
EXCERPTS FROM ASTM C476:
CEMENT-
LIME
MORTAR
CEMENT
MASONRY
CEMENT
M
S
N
O
M
S
N
O
M
S
N
O
2500 psi
1800 psi
750 psi
350 psi
2500 psi
1800 psi
750 psi
350 psi
2500 psi
1800 psi
750 psi
350 psi
75 12
75 12
75 14
75 14
75 12
75 12
75 18
75 18
75 20
75 20
C
C
C
C
D
D
NOT LESS THAN 2 1
AND NOT MORE THAN
3 1
2 THE SUM OF
SEPARATE VOLUMES
OF CEMENTITIOUS
MATERIALS
A
LABORATORY PREPARED MORTAR ONLY
B
SEE NOTE
C
WHEN STRUCTURAL REINFORCEMENT IS INCORPORATED IN CEMENT-LINE OR
CEMENT MORTAR, THE MAX. AIR CONTENT MUST BE 12%.
D
WHEN STRUCTURAL REINFORCEMENT IS INCORPORATED IN MASONRY OR
CEMENT MORTAR, THE MAX. AIR CONTENT MUST BE 18%.
MORTAR JOINTS MUST BE STRAIGHT, CLEAN AND UNIFORM IN THICKNESS,
AND MUST BE TOOLED AS SHOWN ON THE PLANS OR AS SPECIFIED (FLUSH
JOINTS IF NO SPECIAL TREATMENT SPECIFIED). UNLESS OTHERWISE
SPECIFIED OR DETAILED ON THE PLANS, HORIZONTAL AND VERTICAL MORTAR
JOINTS WILL BE 3/8" THICK WITH FULL MORTAR COVERAGE ON THE
FACE SHELL.
OVERHANGING MORTAR DROPPINGS AND DEBRIS MUST BE REMOVED
FROM CELLS RECEIVING GROUT. FAILURE TO REMOVE DEBRIS MUST BE
CAUSE FOR REJECTION OF WALL AND REPAIR OR REWORK NECESSARY
MUST BE ENTIRELY AT CONTRACTOR'S EXPENSE.
VERTICAL HEAD JOINTS MUST BE BUTTERED WELL FOR A THICKNESS EQUAL
TO THE FACE SHELL OF THE BLOCK AND THESE JOINTS MUST BE SHOVED
TIGHTLY SO THAT THE MORTAR BONDS WELL TO BOTH BLOCKS. IF IT IS
NECESSARY TO MOVE A BLOCK SO AS TO OPEN A JOINT, THE BLOCK MUST
BE REMOVED FROM THE WALL, CLEANED AND SET IN FRESH MORTAR
TABLE 2103.12
GROUT PROPORTIONS BY VOLUME FOR MASONRY CONSTRUCTION
PARTS BY VOLUME
OF PORTLAND
CEMENT OR
BLENDED CEMENT
PARTS BY
VOLUME OF
HYDRATED
LIME OR LIME
PUTTY
AGGREGATE, MEASURED IN A DAMP,
LOOSE CONDITION
FINE COARSE
TYPE
FINE GROUT 1 0-1/10
1 0-1/10COARSE
GROUT
2 1/4-3 TIMES THE
SUM OF THE
VOLUMES OF THE
CEMENTITIOUS
MATERIALS
2 1/4-3 TIMES THE
SUM OF THE
VOLUMES OF THE
CEMENTITIOUS
MATERIALS
1-2 TIMES THE SUM
OF THE VOLUMES
OF THE
CEMENTITIOUS
MATERIALS
4.0.8.1 SPECIFIED COMPRESSIVE STRENGTH- PROPORTIONS ESTABLISHED
BY 28-DAY COMPRESSIVE STRENGTH TESTS IN ACCORDANCE WITH
TEST METHOD C 1019 THAT OBTAIN THE SPECIFIED COMPRESSIVE
STRENGTH. THE GROUT MUST BE MIXED TO A SLUMP OF 8 in. TO 11
in. AS DETERMNINED BY TEST METHOD C 143/C 143M AND MUST HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 psi AT 28 DAYS.
FOR MASONRY WORK INSPECTIONS SEE INSPECTION AND TESTING
SPECIFICATIONS.
REFER TO MASONRY CONSTRUCTION DETAILS ON SHEET S501 & S502.
A. ANGLES AND CHANNELS ASTM A36 (Fy=36 ksi) B. PLATES ASTM A36 (Fy=36 ksi) C. HSS (RECTANGULAR) ASTM A500 GRADE C (Fy=50 ksi)
ASTM F992 (Fy=50 ksi)D. WIDE FLANGE
THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL MUST BE IN
ACCORDANCE WITH "AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
AND STEEL CONSTRUCTION MANUAL AISC 360, LATEST ADOPTED EDITION.
EXCEPT AS AMMENDED IN IBC CHAPTER 22.
NOT USED.
CONNECTIONS WILL BE DETAILED IN ACCORDANCE WITH LATEST EDITION OF
AISC "DETAILING FOR STEEL CONSTRUCTION".
STEEL FURNISHED FOR STRUCTURAL LOAD-CARRYING PURPOSES MUST BE
PROPERLY IDENTIFIED FOR CONFORMITY TO THE SPECIFIED GRADES SHOWN
BELOW AND IN ACCORDANCE WITH ASTM STANDARDS AND PROVISIONS OF IBC
CHAPTER 22. STEEL THAT IS NOT READILY IDENTIFIABLE AS TO GRADE FROM
MARKING AND TEST RECORDS MUST BE TESTED TO DETERMINE CONFORMITY TO:
COLUMN ENDS TO BE MILLED.
EXTERIOR STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE WEATHER
MUST BE HOT-DIPPED GALVANIZED AFTER FABRICATION. ZINC COATING MUST
CONFORM TO ASTM A123 (G-60 U.O.N.).
STEEL FABRICATION MUST BE PERFORMED IN AN APPROVED
FABRICATION SHOP.
STEEL FABRICATOR MUST VERIFY DIMENSIONS WITH ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
METAL ITEMS, INCLUDING CONNECTORS, EXPOSED TO THE WEATHER
MUST BE HOT-DIPPED GALVANIZED AFTER FABRICATION.
STRUCTURAL STEEL MUST BE DELIVERED TO THE JOB SITE FREE OF
EXCESSIVE RUST, MILL SCALE, GREASE, ETC.
SUBMIT SHOP DRAWINGS TO THE STRUCTURAL ENGINEER & CONTRACTING
OFFICER FOR REVIEW PRIOR TO FABRICATION FOR STRUCTURAL STEEL
MEMBERS AND ACCESSORIES.
WELDING DONE AFTER GALVANIZING MUST BE PROTECTED WITH TWO COATS
OF GALVANIZING PROTECTANT METALLIC BARRIER.
This is the start of the file's text. The full file is on GovTribe.