P1495 (B1337)_Drawings_Excerpt.pdf
PDF 2 MB Posted
- Attached to
- P1556 10th Marines Maintenance and Operations Complex, Marine Corps Base (MCB) Camp Lejeune, North Carolina
- Solicitation number
- N4008525R2532
About this file
This document is a comprehensive fire alarm and mass notification system design specification for a U.S. Marine Corps HIMARS site. The technical drawings and specifications detail a complete addressable fire alarm system to be installed across a two-floor facility, with requirements for equipment, device placement, wiring, and system performance. Key specifications include using Simplex, Notifier, or Fire-Lite systems, installing devices according to UFC 3-600-01 and NFPA standards, providing Class A wiring, and ensuring 48-hour battery backup with an additional 15-minute alarm capability.
The design covers extensive requirements for device installation, including mounting heights for control panels, manual pull stations, and notification appliances, with specific guidelines for smoke/heat detectors, speakers, and strobes. The system must provide comprehensive coverage across all floors, including maintenance bays, offices, mechanical rooms, and storage areas, with notification devices synchronized and placed to meet intelligibility and visibility standards. The specification emphasizes coordination with mechanical systems, proper conduit installation, surge protection, and compliance with multiple fire safety and building codes.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FAAP
FMCP
DACT
NAC
LOC
SPD
CM
MM
F
P
ID
C
S
C
S
V
F S
ST
F
CF
TRAN
DOC
FIRE ALARM LEGEND
SYMBOL DESCRIPTION
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
DIGITAL ALARM COMMUNICATOR TRANSMITTER
NOTIFICATION APPLIANCE CIRCUIT PANEL
LOCAL OPERATOR CONSOLE
SURGE PROTECTION DEVICE
CONTROL MODULE
MONITOR MODULE
MANUAL PULL STATION
SMOKE DETECTOR / PHOTOELECTRIC
SMOKE DETECTOR / IN DUCT
CO CARBON MONOXIDE SENSOR
COMBINATION SPEAKER / VISIBLE WALL MOUNTED.
CD INDICATES CANDELA RATING.
COMBINATION SPEAKER / VISIBLE CEILING MOUNTED.
CD INDICATES CANDELA RATING.
CD
CD
SPEAKER WALL MOUNTED.
SPEAKER CEILING MOUNTED.
ELECTRIC BELL - VIBRATING
FLOW SWITCH
TAMPER SWITCH
FIRE ALARM WALL MOUNTED VISUAL ONLY STROBE.
CD INDICATES CANDELA RATING.
FIRE ALARM CEILING MOUNTED VISUAL ONLY STROBE.
CD INDICATES CANDELA RATING.
CD
CD
RADIO TRANSCEIVER (GOVERNMENT PROVIDED)
WEATHERPROOF
EXPLOSION PROOF
WP
EX
DOCUMENT CABINET
1. PROVIDE A COMPLETE, ADDRESSABLE, FIRE ALARM AND MASS NOTIFICATION SYSTEM IN THE FACILITY. FIRE ALARM AND MASS NOTIFICATION SYSTEM MUST BE DESIGNED AND INSTALLED TO MEET THE REQUIREMENTS OF UFC 3-600-01, UFC 4-021-01, NFPA 70, NFPA 72, AND NFPA 101. SYSTEM SHALL BE SIMPLEX, NOTIFIER, OR
FIRE-LITE.
2. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE DESIGN, MATERIALS, AND EQUIPMENT FOR A TOTALLY FUNCTIONING AND OPERATING FIRE ALARM AND MASS NOTIFICATION SYSTEMS, INCLUDING THE PROPER
INTERFACING AND COORDINATION WITH OTHER BUILDING SYSTEMS.
3. THE GENERAL CHARACTER AND SCOPE OF THE WORK IS ILLUSTRATED IN THE SPECIFICATIONS AND THE DRAWINGS. THE SPECIFICATIONS AND DRAWINGS ARE DIVIDED INTO SEVERAL SECTIONS FOR CONVENIENCE ONLY AND THE CONTRACT DOCUMENTS MUST BE CONSIDERED AS A WHOLE. THE CONTRACTOR MUST BE RESPONSIBLE FOR THE COORDINATION OF ALL TRADES, SUBCONTRACTORS, AND VENDORS ENGAGED IN THIS
WORK.
4. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF FIRE ALARM AND MASS NOTIFICATION SYSTEM EQUIPMENT AND FIELD DEVICES. FINAL LOCATIONS, QUANTITIES, APPLIANCE RATINGS, ETC. MUST BE PROVIDED BY THE INSTALLING CONTRACTOR IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND CONTRACT
DOCUMENTS.
5. THE CONTRACTOR MUST OBTAIN REQUIRED PERMITS AND APPROVALS AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR MUST PAY FOR AND SECURE PERMITS AND FEES FOR FIRE
PROTECTION SYSTEMS WORK.
6. PROVIDE FINAL SYSTEM LAYOUT DRAWINGS INCLUDING BATTERY CALCULATIONS AND VOLTAGE DROP CALCULATIONS AND OBTAIN APPROVAL OF THE FIRE MARSHAL AND ALL AUTHORITIES HAVING JURISDICTION.
BATTERY CALCULATIONS MUST INCLUDE 20 PERCENT SAFETY MARGIN TO THE CALCULATED AMP-HOUR RATING PER NFPA 72. A BILL OF MATERIAL AND CONTACT ID POINT DESCRIPTION TABLE MUST BE INCLUDED IN
THE FIRE ALARM AS-BUILT DRAWINGS.
7. PROVIDE FIRE ALARM AND MASS NOTIFICATION SPEAKERS AND STROBES THROUGHOUT THE PROJECT AREAS.
PROVIDE ADDITIONAL NOTIFICATION APPLIANCE CIRCUIT (NAC) PANELS AS REQUIRED. EACH NAC LOADING
MUST NOT EXCEED 75% OF ITS RATED OUTPUT.
8. PROVIDE DUCT SMOKE DETECTORS IN ALL SUPPLY DUCTS OF AIR HANDLING UNITS GREATER THAN 2,000 CFM .
PROVIDE RELAYS FOR SHUT DOWN OF ASSOCIATED AIR HANDLING UNITS.
9. PROVIDE MONITOR MODULES, TAMPER AND FLOW SWITCHES FOR THE SPRINKLER RISER AND CONTROL
VALVES.
10. WIRING FOR DEVICES MUST BE CLASS A. PROVIDE ALL FIRE ALARM CIRCUITS IN ELECTRICAL METALLIC
TUBING (EMT) OR INTERMEDIATE METAL CONDUIT (IMC).
11. ALL RACEWAYS MUST BE FACTORY PAINTED RED. FLEXIBLE METALLIC OCNDUIT (FMC) SHALL NOT EXCEED 6 FEET AND MUST ONLY BE PERMITTED FOR CONNECTIONS TO JUNCTION BOXES TO FIELD DEVICES. PROVIDE A RACEWAY LISTED FOR THE INSTALLATION IN WET LOCATIONS, SUCH AS RIGID METALLIC CONDUIT (RMC) AND LIQUID TIGHT FLEXIBLE METAL CONDUIT (LFMC). WET LOCATIONS ARE CONSIDERED ANY LOCATION WITHIN A 5
FOOT RADIUS OF FIRE SUPPRESSION EQUIPMENT AS DEFINED BY NFPA 70.
12. DEVICES MUST BE FACTORY FINISHED WHITE.
13. PROVIDE RECHARGEABLE SEALED LEAD ACID TYPE BATTERIES TO OPERATE THE FIRE ALARM SYSTEM UNDER
SUPERVISORY CONDITIONS FOR 48 HOURS AND AUDIBLE AND ALARM DEVICES FOR AN ADDITIONAL 15 MINUTES OR 60 MINUTES FOR THE MASS NOTIFICATION SYSTEM IMMEDIATELY UPON LOSS OF POWER, WHICHEVER IS GREATER.
14. INSTALLING CONTRACTOR MUST COORDINATE WITH MECHANICAL, ELECTRICAL AND OTHER TRADES TO FACILITATE INSTALLATION THAT IS COORDINATED AND CONSISTENT WITH BUILDING DESIGN, USE AND INTENT.
15. COORDINATE FINAL SYSTEM TESTING WITH OTHER CONTRACTORS TO PROVIDE FULL SYSTEM OPERATION AT
TIME OF TESTING.
16. THE FIRE PROTECTION CONTRACTOR MUST BE RESPONSIBLE FOR SCHEDULING AND PERFORMING
INSPECTIONS AND TESTS AS REQUIRED BY THE CONTRACTING OFFICER.
17. FLOOR AND WALL CONDUIT PENETRATIONS MUST BE SLEEVED AND SEALED AS REQUIRED.
18. PENETRATIONS OF THE BUILDING AIR BARRIER MUST BE SEALED TO MAINTAIN THE INTEGRITY OF THE AIR
BARRIER.
19. CONDUIT SIZE AND PERCENTAGE OF FILL TO BE DETERMINED BY INSTALLING CONTRACTOR AND MUST
COMPLY WITH APPLICABLE STANDARDS AND SYSTEM MANUFACTURER'S REQUIREMENTS.
20. CONDUIT AND WIRING MUST BE CONCEALED ABOVE CEILINGS IN FINISHED AREAS AND AREAS WITH DROPPED
CEILINGS. CONDUIT AND WIRING INSTALLED ABOVE CEILINGS MUST NOT INTERFERE WITH THE REMOVAL OF THE CEILING TILES, AND HVAC UNIT AIR FILTERS. IN AREAS WITHOUT CEILING, CONDUIT AND WIRING MUST BE INSTALLED AS TIGHT AS POSSIBLE TO UNDERSIDE OF FLOOR SLAB, UNLESS OBSTRUCTIONS REQUIRE
OTHERWISE.
21. FIRE ALARM WIRING MUST NOT BE INSTALLED IN THE SAME CONDUITS OR JUNCTION BOXES AS LIGHTING, POWER OR OTHER WIRING.
22. RUN WIRING TO CONTROL PANELS IN THE VERTICAL OR HORIZONTAL PLANE, MAKE TURNS AT 90 DEGREE ANGLES, AND TIGHTLY BUNDLE, WRAP, AND IDENTIFY CONDUCTORS INDIVIDUALLY WITH PERMANENT
MARKINGS.
23. PULL CONDUCTORS SPLICE FREE. THE USE OF WIRE NUTS, CRIMPED CONNECTORS, OR TWISTING OF
CONDUCTORS IS PROHIBITED.
24. TERMINATIONS MUST BE AT A TERMINAL STRIP. DEVICES MUST HAVE SCREW TERMINALS.
25. SIGNALING LINE CIRCUITS MUST BE MINIMUM 18 GAUGE WIRE. INITIATING DEVICE AND NOTIFICATION
APPLIANCE CIRCUITS MUST BE MINIMUM 16 GAUGE WIRE.
26. ALL ADDRESSABLE CONTROL MODULES AND ADDRESSABLE MONITOR MODULES MUST BE LOCATED WITHIN 10
FEET OF THE DEVICES BEING MONITORED. DUCT SMOKE DETECTORS MUST BE WITHIN 3 FEET OF
ADDRESSABLE RELAY.
27. CONTRACTOR MUST PROVIDE ADEQUATE AUDIBLE NOTIFICATION DEVICES TO MEET THE AUDIBILITY AND INTELLIGIBILITY REQUIREMENTS OF NFPA 72 AND UFC 4-021-01. THE MINIMUM REQUIRED COMMON
INTELLIGIBILITY SCALE IS 0.7.
28. PROVIDE SPEAKERS MOUNTED ON THE EXTERIOR OF THE BUILDING IN ADDITION TO NOTIFICATION IN ANY AREAS COMMONLY USED BY BUILDING OCCUPANTS. AREAS INCLUDE COURTYARDS, COVERED BREAK AREAS, DESIGNATED SMOKING AREAS, AND SIDEWALKS LEADING FROM THE BUILDING'S EXIT DOORS TO A PUBLIC
STREET OR FROM PARKING AREAS FOR A DISTANCE UP TO 16 FEET FROM THE BUILDING.
29. PROVIDE VISIBLE NOTIFICATION APPLIANCES IN ALL NORMALLY OCCUPIED, PUBLIC AND COMMON USE AREAS SUCH AS BREAK ROOMS, CORRIDORS, AUDITORIUMS, OR CONFERENCE ROOMS. VISUAL NOTIFICATION MUST BE PROVIDED IN ALL OFFICES THAT ARE DESIGNED FOR, OR MAY CONTAIN, MORE THAN 4 PERSONS AT ANY
ONE TIME. REFER TO INTERIOR SHEETS FOR FURNITURE PLANS.
30. PROVIDE CLEAR STROBE MARKED "ALERT" FOR FIRE ALARM AND MASS NOTIFICATION SYSTEM NOTIFICATIONS.
31. COORDINATE DUCT SMOKE DETECTION WITH MECHANICAL DESIGN CONTRACTOR. DUCT SMOKE DETECTOR
REMOTE LAMPS AND TEST STATION MUST BE WALL MOUNTED, ACCESSIBLE, VISIBLE, AND PERMANENTLY LABELED. THE DUCT DETECTORS MUST RECEIVE THEIR POWER AND RESET FROM THE FIRE ALARM CONTROL
UNIT.
32. PROVIDE REMOTE TEST LAMPS FOR ANY INACCESSIBLE DEVICES.
33. PROVIDE SURGE PROTECTION FOR CIRCUITS THAT ENTER OR EXIT A BUILDING.
34. PROVIDE WEATHERPROOF DEVICES AS REQUIRED AND AS INDICATED.
35. DEVICES MOUNTED IN SUSPENDED CEILING MUST BE MOUNTED IN THE CENTER OF THE CEILING TILE.
36. PROVIDE A DOCUMENTATION CABINET ADJACENT TO FIRE ALARM CONTROL PANEL. CABINET MUST BE STEEL
WITH LOCKING, HINGE MOUNTED DOOR PROMINENTLY LABELED "SYSTEM RECORD DOCUMENTS". CABINET MUST STORE LIFE SAFETY, FIRE ALARM, AND SPRINKLER AS-BUILT DRAWINGS AND NFPA 72 RECORD OF COMPLETION IN PAPER FORMAT. CD/DVD OF SITE-SPECIFIC SOFTWARE, FIRE ALARM AND SPRINKLER AS-BUILT DRAWINGS, NFPA 72 RECORD OF COMPLETION, AND OPERATIONS AND MAINTENANCE MANUALS MUST BE
STORED IN A CD JEWEL CASE.
37. PROVIDE A PARTS BOX ADJACENT TO THE FMCP. CABINET MUST BE STEEL, LOCKING, WITH HINGE-MOUNTED DOOR, KEYED THE SAME AS THE FMCP. CABINET MUST INCLUDE SPARE PARTS AS DEFINED IN THE PROJECT
SPECIFICATIONS, PLUS FOUR (4) FUSES FOR EACH FUSED CONDUIT.
38. DUAL-ACTION, MANUAL FIRE PULL STATIONS MUST BE PROVIDED WITHIN 5 FEET OF EVERY EXIT OF THE BUILDING. MANUAL PULL STATIONS MUST BE RESET WITH THE USE OF A KEY ONLY. USE OF A WRENCH, HEX KEY, ALLEN KEY, OR ALLEN WRENCH TO OPEN A MANUAL PULL STATION MUST NOT BE PERMITTED.
39. WATER FLOW ALARM AND VALVE TAMPER SWITCHES ATTACHED TO THE BUILDING WET-PIPE SPRINKLER SYSTEM TO PROVIDE REQUIRED SUPERVISION MUST BE CONNECTED TO THE FIRE ALARM SYSTEM.
40. INSTALL A POINT REPORTING DIGITAL ALARM COMMUNICATOR TRANSMITTER THAT IS COMPATIBLE WITH THE SUR-GARD SYSTEM III MULTI-PLATFORM DIGITAL TELEPHONE RECEIVER AND IS PROGRAMMED TO REPORT BY POINTS VIA CONTACT ID PROTOCOL. PROVIDE TWO (2) CAT 6 UTP CABLES INSIDE 1-INCH CONDUIT FROM THE
FMCP TO THE TELEPHONE EQUIPMENT ROOM.
41. THE GOVERNMENT WILL INSTALL THE TRX-401 MASS NOTIFICATION TRANSCEIVER. THE CONTRACTOR MUST PROVIDE CONDUIT FOR MOUNTING THE MASS NOTIFICATION ANTENNA, CONDUIT FOR THE MASS NOTIFICATION ANTENNA CABLE, CONDUIT TO CONNECT THE TRANSCEIVER TO THE FIRE ALARM CONTROL PANEL, AND 120V
POWER FOR THE TRANSCEIVER.
42. PROVIDE AND ATTACH A LEGIBLE, TYPED LABEL ON ALL ADDRESSABLE DEVICES TO INDICATE ITS ADDRESS.
FOR ANY DEVICE LOCATED ABOVE A FALSE CEILING, CONTRACTOR MUST PROVIDE A LEGIBLE, TYPED LABEL
ATTACHED TO THE CEILING GRID THE DEVICE NOMENCLATURE AND ADDRESS.
FIRE ALARM AND MASS NOTIFICATION GENERAL NOTES FIRE ALARM AND MASS NOTIFICATION GENERAL NOTES (CONTINUED)
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
* A SUPERVISORY SIGNAL SHALL BE TRANSMITTED BY MNS OPERATIONS ONLY WHEN THE MNS OVERRIDES THE ACTIVE FIRE ALARM SIGNAL
CONFIGURATOIN
SIGNAL FROM WIDE AREA MASS NOTIFICATION SYSTEM* 19 X X X X X
LOC ACTIVATION OR PRE-RECORDED MNS MESSAGES* 18 X X X X X X
LOCAL MICROPHONE MNS OPERATION* 17 X X X X X X
ACTIVATION OF MASS NOTIFICATION SYSTEM* 16 X X X X X
ACTIVATION OF DUCT SMOKE DETECTOR 3 X X X X
TAMPER SWITCH 15 X X
SU
PE
RV
IS
OR
Y
CO
ND
IT
IO
NS COMMON SUPERVISORY 14 X X
GROUND FAULT 13 X X
CIRCUIT DISCONNECT 12 X X
LOW BATTERY 11 X X
NAC SHORT 10 X X
OPEN CIRCUIT 9 X X
LOSS OF PRIMARY AC POWER 8 X X
FIELD WIRING OR SYSTEM COMPONENT FAULT 7 X X
TR
OU
BL
E
CO
ND
IT
IO
NS
COMMON TROUBLE 6 X X
ACTIVATION OF A CARBON MONOXIDE DETECTOR 5 X X X X X X X
ACTIVATION OF WATERFLOW SWITCH 4 X X X X X X X
ACTIVATION OF AREA SMOKE DETECTOR 2 X X X X X X
AL
AR
M
CO
ND
IT
IO
NS
ACTIVATION OF A MANUAL FIRE ALARM PULL STATION 1 X X X X X X
A B C D E F G H I J K L M N O P
AN
NU
NC
IA
TE
A
LA
RM
S
IG
NA
L A
T
CO
NT
RO
L P
AN
EL
AN
NU
NC
IA
TE
T
RO
UB
LE
S
IG
NA
L A
T
CO
NT
RO
L P
AN
EL
AN
NU
NC
IA
TE
S
UP
ER
VI
SO
RY
S
IG
NA
L A T
CO
NT
RO
L P
AN
EL
AC
TI
VA
TE
F
IR
E
AL
AR
M/
MA
SS
N
OT
IF
IC
AT
IO
N
VI
SU
AL
A
ND
A
UD
IB
LE
A
PP
LIA
NC
ES
SE
ND
A
LA
RM
S
IG
NA
L T O
SU
PE
RV
IS
IN
G
ST
AT
IO
N
SE
ND
T
RO
UB
LE
S
IG
NA
L T
O
SU
PE
RV
IS
IN
G
ST
AT
IO
N
SE
ND
S
UP
ER
VI
SO
RY
S
IG
NA
L T
O
SU
PE
RV
IS
IN
G
ST
AT
IO
N
SH
UT
DO
W
N
AS
SO
CI
AT
ED
A
IR
H
AN
DL
IN
G
UN
IT
S
AC
TI
VA
TE
W
AT
ER
FL
OW
A
LA
RM
E
LE
CT
RI
C
BE
LL
DE
AC
TI
VA
TE
F
IR
E
AL
AR
M
AU
DI
BL
E
SI
GN
AL
S
AC
TI
VA
TE
E
GR
ES
S
LIG
HT
IN
G
SE
ND
S
IG
NA
L T
O
BA
SE
W
ID
E
MA
SS
N
OT
IF
IC
AT
IO
N
SY
ST
EM
SH
UT
DO
W
N
HI
GH
V
OL
UM
E, LO
W S
PE
ED
(H
VL
S) F
AN
S
SI
LE
NC
E
PA
S
YS
TE
M
SE
ND
U
NI
QU
E
CA
RB
ON
M
ON
OX
ID
E
AL
AR
M
SI
GN
AL
T O
SU
PE
RV
IS
IN
G
ST
AT
IO
N
IN
IT
IA
TE
U
NI
QU
E
CA
RB
ON
M
ON
OX
ID
E
MA
SS
N
OT
IF
IC
AT
IO
N
ME
SS
AG
E
SCALE: NOT TO SCALE
FIRE ALARM/MASS NOTIFICATION SYSTEM SEQUENCE OF OPERATIONS
FE
FEC
FE
C
FF
F
F
F
F
C 30
C 15
S
F
C 95 C 95
S
C 95 C 95
S
SS
S S
S S S
S
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
2. FINAL FIRE ALARM AUDIBLE AND VISUAL DEVICE PLACEMENT SHALL BE
DETERMINED BY THE INSTALLING CONTRACTOR.
ELECTRICAL
WOMEN'S HEAD
G102
ORGANIC STORAGE
AREAS (3)
CAGED EQUIP STOR 'R'
144r
CAGED EQUIP STOR 'S'
144s
CAGED EQUIP STOR 'T'
144t
OFFICE
UNISEX
G103
TELE
3.8
2.6
2.1
A'
A'
A
A
B
B
C
C
D
D
E
E F'
F
F
WPWP
WP
WP
WP WP WP
WP
WP
FA
FA
CM2
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE ALARM - 1ST FLOOR PLAN - AREA A
KEYNOTES
1 STROBES MUST BE MOUNTED SUCH THAT THE MAXIMUM HEIGHT OF THE
LENS IS 30 FEET.
2 PROVIDE CONTROL MODULE TO ACTIVATE THE LIGHTING CONTROL DEVICE(S)
UPON ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM IN ACCORDANCE
WITH NFPA 101: 7.8.1.2.2.
SCALE: 1/8" = 1'-0"
0 4'-0" 8'-0" 16'-0"
K
FE
C
FM
CP
TR
AN
DA
CT
F F
F S
MM
ST
MM
DO
C
SP
D
F
P
F
FA
AP
F
F F F
ID
CM
LO
C
C
S
C
S
C 15
C
S
C
S
C
S
C
S
C 30
C 15
C 30
C 15F
C 15
C 30
C 75
C 15
C 75
C 15 C 15
C 15
C 15
C 15
C 15 30
C 30
C 15
C 30
C 30
C
S
C 15F
C
S
C
S
C
S
C
S
C
S
C 15
S
C 15 F
30 30 30
ID
CM
ID
CM
ID
CM
S
S S
S S
C 15F
C 15F75 75
V
X 4
X
FSR OFFICE
ORDO OFFICE
HQ FAC OFFICE
BATTERY FAC OFFICE S
HIMARS MAINT. OFFICER
110a
BATTERY FAC OFFICE R
BREAK ROOM
CONFERENCE ROOM
CLASSROOM
HIMAR MAINT. OFFICE
FSR TOOL ROOM + PARTS
STORAGE
PRINT/ FILE
CORRIDOR
C101
VEST
V100
VEST
V101
JAN.
TELECOM
TIRE STORAGE
LEAD ACID BATTERY
STORAGE
MECHANICAL
WOMEN'S HEAD
G102
MEN'S HEAD
G101
STAIR A
STA1
HQ STORAGE
BOILER ROOM
DISPATCH
STAIR B
STB1
'R' STORAGE
105r
'S' STORAGE
105s
'T' STORAGE
105t
GENERAL STORAGE
MEN'S SHOWERS
G101a
BATTERY FAC OFFICE T
CORRIDOR
C100
CORRIDOR
C102
CORRIDOR
C103
CORRIDOR
C104
3.8
F'
F
F
G
G
H
H
J
J
K
K
L'
L'
L
L
1.6
1.9
2.5
3.3
WP
WP WP
NA
C
WP WP
MOTHER'S ROOM
G102a
VEST
V102
CO
FA
FA
FA
FA
1 2 3
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
2. FINAL FIRE ALARM AUDIBLE AND VISUAL DEVICE PLACEMENT SHALL BE
DETERMINED BY THE INSTALLING CONTRACTOR.
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE ALARM - 1ST FLOOR PLAN - AREA B
KEYNOTES
1 PROVIDE CONTROL MODULE TO SHUT DOWN AIR HANDLING UNIT AHU-01A
UPON ACTIVATION OF DUCT SMOKE DETECTOR IN SUPPLY AIR DUCTWORK.
2 PROVIDE CONTROL MODULE TO SHUT DOWN AIR HANDLING UNIT AHU-01B
UPON ACTIVATION OF DUCT SMOKE DETECTOR IN SUPPLY AIR DUCTWORK.
3 PROVIDE CONTROL MODULE TO SHUT DOWN AIR HANDLING UNIT AHU-02
UPON ACTIVATION OF DUCT SMOKE DETECTOR IN SUPPLY AIR DUCTWORK.
4 PROVIDE CONTROL MODULE TO SHUT DOWN AIR HANDLING UNIT AHU-03
UPON ACTIVATION OF DUCT SMOKE DETECTOR IN SUPPLY AIR DUCTWORK.
5 THE GOVERNMENT WILL INSTALL THE MASS NOTIFICATION TRANSCEIVER.
THE CONTRACTOR MUST PROVIDE CONDUIT FOR MOUNTING THE MASS
NOTIFICATION ANTENNA, CONDUIT FOR THE MASS NOTIFICATION ANTENNA
CABLE, CONDUIT TO CONNECT THE TRANSCEIVER TO THE FACP, AND 120V
POWER FOR THE TRANSCEIVER. ADEQUATE CLEAR SPACE FOR FUTURE
PANEL MOUNTING SHALL BE PROVIDED.
6 PROVIDE SEPARATE NAC PANELS PER FLOOR. FINAL NUMBER OF NAC
PANELS MUST BE DETERMINED BY FIRE ALARM CONTRACTOR BASED ON
SHOP DRAWING CALCULATIONS.
7 PROVIDE ANTENNA FOR MASS NOTIFICATION SYSTEM RADIO TRANSCEIVER
AT THE ROOF.
F
F
F
F
C 15
S
C 75
C 75 C 75
C 75
NA
C
P
C 15
C
S
C 75C 75
C 75C 75
C 75C 75
C
S
C
S
S
S
S S
S
C
S
SP
D
LAUNCHER MAINTENANCE
BAYS [6]
AUTO MAINTENANCE
BAYS [6]
POL STORAGE
HIMARS MAINTENANCE
TOOL ROOM
HIMARS PARTS STORAGE
TELECOM
CORRIDOR
C105
COMPRESSOR
L
L
M
M
N
N
P
P
P'
P'
R
R
S
S
T
T
U
U
V
V
V'
V'
2.4
2.8
3.2
1.6
1.9
2.5
3.3
WP
WP
WP
WP
WP
ELEC
MECHANICAL
FA
FA
EX
EX
3 44
F
CM CM55
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
2. FINAL FIRE ALARM AUDIBLE AND VISUAL DEVICE PLACEMENT SHALL BE
DETERMINED BY THE INSTALLING CONTRACTOR.
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE ALARM - 1ST FLOOR PLAN - AREA C
KEYNOTES
1 LOCATE AND SPACE CARBON MONOXIDE DETECTORS IN ACCORDANCE WITH
MANUFACTURER SPECIFICATION.
2 ROOM IS TO BE RATED CLASS 1 DIVISION 1 HAZARDOUS CLASSIFICATION
RATING. ALL DEVICES IN ROOM TO BE EXPLOSION PROOF. SEE ELECTRICAL
SHEETS.
3 CO DETECTION IS NOT REQUIRED IN SPACES WITH CEILINGS GREATER THAN
12 FEET IN ACCORDANCE WITH UFC 3-600-01 SECTION 9-19.2.3.
4 STROBES MUST BE MOUNTED SUCH THAT THE MAXIMUM HEIGHT OF THE
LENS IS 30 FEET.
5 PROVIDE CONTROL MODULE TO SHUT DOWN HIGH-VOLUME, LOW SPEED
(HVLS) FANS UPON FIRE ALARM/MASS NOTIFICATION SYSTEM ACTIVATION IN
ACCORDANCE WITH UFC 3-600-01: 7-6.
C
S
C
S
C 15
C 15 C 15
C 15 C 15
C
S
C
S
C 30
C 30
C 30
C
S
C
S
C
S
C
S
C
S
C
S
C 15C 15
C 15
NAC
SPDP
BATTERY OFFICE R
BATTERY OFFICE S
OFFICE R
205a
BATTERY OFFICE T
209STAIR B
STB2
BATALLION OFFICER
203a
BATALLION OFFICE
MEN'S HEAD
G202
OFFICE S
207a
OFFICE T
209a
BATTALION OPEN OFFICE
CLASSROOM
CORRIDOR
C202
STAIR A
STA2
JAN.
CONF ROOM
COPY
CORRIDOR
C201
CORRIDOR
C203
H
H
J
J
K
K
L'
L'
L
L
1.6
1.9
2.5
3.3
ELEC
WOMEN'S HEAD
G201
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
2. FINAL FIRE ALARM AUDIBLE AND VISUAL DEVICE PLACEMENT SHALL BE
DETERMINED BY THE INSTALLING CONTRACTOR.
N
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE ALARM - 2ND FLOOR PLAN
FINISHED
FLOOR
42" TO 48" AFF TO TOP OF
MESSAGE BUTTONS ON
LOC
NAC
PANEL
NO HIGHER THAN 60" TO
CENTER OF PANEL
LOC
72"
60"NOTE:
RECESSED OR SEMI-RECESSED
IN FINISHED SPACES AND SURFACE
MOUNTED IN UNFINISHED SPACES
TOP OF CABINET 72" ABOVE
FINISHED FLOOR OR CENTER
OF CABINET AT 60" ABOVE
FINISHED FLOOR, WHICHEVER
IS LOWER.
CONTROL
PANEL
FAAP
80" MIN (NFPA)
ALERT ALERT
CEILING
96" MAX (NFPA)
ABOVE FINISHED FLOORSYNCHRONIZE MORE THAN
TWO APPLIANCES IN ANY
FIELD OF VIEW.
REF. 80" MIN
REF. 96" MAX
ABOVE FINISHED FLOOR
NOTE: REFER TO THE PROPER DEVICE
INSTALLATION INSTRUCTIONS FOR
BACKBOX MOUNTING HEIGHT.
AUDIO / VISUAL
& VISUAL ONLY
DEVICES
FINISHED FLOOR
90" TO TOP
OF DEVICE
AUDIO ONLY
DEVICES
FIRE ALARM
PULL DOWN
TO EXIT
DOOR 5'
(MAX.)
42" MIN/48" MAX
(NFPA) NFPA 72 2010
EDITION (SECTION
17.14.4)
MANUAL
PULL STATION
FINISHED
WALL
FINISHED
FLOOR
CEILING
3' (MIN)
A/C
SUPPLY
OR
RETURN
DIFFUSER
4"
NOTE:
MEASUREMENTS
SHOWN ARE TO THE
CLOSEST EDGE OF
THE DETECTOR.
12" (MAX)
4"
CEILING MOUNTED
SMOKE / HEAT
DETECTOR
ACCEPTED HERE
WALL MOUNTED
SMOKE / HEAT
DETECTOR
FINISHED WALL
HEAT DETECTOR
NEVER HERE
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: NOT TO SCALE C1CONTROL PANEL, NAC PANEL, AND LOC MOUNTING HEIGHT
SCALE: NOT TO SCALE A3
AUDIO / VISUAL DEVICE
INSTALLATION DETAIL
SCALE: NOT TO SCALE C3MANUAL PULL STATION HEIGHTS
SCALE: NOT TO SCALE A1SMOKE / HEAT DETECTOR INSTALLATION REQUIREMENTS
MM
F S
F ID
(TYP)
NAC
TYPICAL NOTIFICATION APPLIANCE CIRCUIT
SS
WPWP
FMCP
SPD120 VAC POWER TO 20A
DEDICATED CIRCUIT BREAKER
(TYP)
WET-PIPE
SPRINKLER SYSTEM
MM
(TYP)
T S
TWO DEDICATED
PHONE LINES
DACT P
FIRST FLOOR
SECOND FLOOR
JB
NAC
TYPICAL NOTIFICATION APPLIANCE CIRCUIT
(TYP)
SPD 120 VAC POWER TO 20A
DEDICATED CIRCUIT BREAKER
SIGNALING LINE CIRCUIT
F SIGNALING LINE CIRCUIT
FAAP
LOC
CM
RTL
SHUTDOWN ASSOCIATED
AIR HANDLING UNIT
TO NAC
TO NAC
TO FMCP
TO FMCP
TO FMCP
CO
INSTALL 8" X 8" X 8" PULL BOX ABOVE/ADJACENT TO THE MNS EQUIPMENT
AREA. INSTALL 1.5" RMC FROM THE PULL BOX TO A POINT 4 FEET ABOVE
THE APEX OF THE ROOFLINE. INSTALL THE RMC IN THE MOST DIRECT
VERTICAL ROUTE POSSIBLE, IF SHARP BENDS ARE REQUIRED THEN UTILIZE
ADDITIONAL PULL BOXES APPROPRIATELY. TERMINATE THE TOP OF THE
EXTERIOR RMC WITH A U.L. LISTED WEATHER HEAD. INSTALL 50 OHM,
LMR-400 RF CABLE IN THE RMC. PROVIDE A THREE FOOT CABLE LENGTH
MAINTENANCE LOOP AT BOTH ENDS OF THE CABLE ROUTE AND
TERMINAT4E ROOF CABLE WITH A STRAIGHT MALE N-TYPE CONNECTOR;
LEAVE THE RF CABLE UNTERMINATED AT THE MNS MOUNTING AREA AND
CLEARLY LABEL THE RF CABLE "FOR MNS", TEST RF CABLE FOR PROPER
CONNECTIVITY. INSTALL ONE 9DBI OMNI-DIRECTIONAL ANTENNA, COOPER
ANT-109-OM OR, MOBILE MARK OD9-2400 OR EQUAL, ON TOP OF ROOFTOP
ANTENNA MAST. DIRECTIONAL ANTENNAE MAY BE MOUNTED ON FACILITIES
BELOW ROOFLINE IF PLACEMENT OF ANTENNA LOCATION IS PRE-
APPROVED BY SPAWAR OR PHYSICAL SECURITY PERSONNEL DURING THE
DESIGN STAGES. REFER ANY QUESTIONS TO PMO PHYSICAL SECURITY
OFFICE OR SPAWAR MNS SME.
USMC MNS
MOUNTING
AREA AND
ENCLOSURE
1.5" RMC
MAXIMUM CONDUIT LENGTH TO
ROOF TERMINATION = 115'
8"x8"x8" PULL BOX 1.5"
INSTALL USMC MASS NOTIFICATION SYSTEM
MOUNTING BOARD. PROVIDE DEDICATED WALL
SPACE FOR A 24"x24"x1" MOUNTING BOARD
ADJACENT TO THE FACP. ENSURE THE
MOUNTING BOARD IS CLEARLY MARKED FOR
"BASE-WIDE MNS USE". ENSURE MNS
EQUIPMENT AREA IS WITHIN 15 CONDUIT FEET
OF THE FACP.
MOUNT A NON-METALLIC 18"Hx16"Wx10"D NEMA 4X ENCLOSURE
WITH RAISED COVER AND PAD LOCKABLE LATCHES W/ INTERIOR
MOUNTING PLATE (INTEGRA 181610HLL OR EQUAL), CENTERED ON
THE MNS MOUNTING AREA BOARD. INSTALL 3/4" RMC WITH 3
CONDUCTORS, 12 GAUGE ELECTRICAL WIRE FROM THE
ENCLOSURE TO A DEDICATED LOCKABLE BREAKER FROM THE
SAME POWER PANEL UTILIZED BY THE FACP. INSTALL AC SURGE
PROTECTION DEVICE (120V, 15A MAX, ISLATROL HASP-121BT1RU
OR EQUAL) IN LINE WITH POWER CIRCUIT INSIDE THE LOWER
RIGHT CORNER OF THE ENCLOSURE. THE AC SURGE DEVICE
MUST BE WIRED IN SERIES WITH A DUAL AC ELECTRICAL OUTLET
MOUNTED INSIDE THE MNS ENCLOSURE LOCATED ABOVE THE
SURGE DEVICE ON THE BOTTOM RIGHT SIDE OF THE MNS
ENCLOSURE.
INSTALL TWO (2) 3/4-INCH ELECTRICAL METAL TUBING
WITH 18 AWG SHIELDED AUDIO WIRE FROM THE NEMA-4
ENCLOSURE TO TWO (2) DIFFERENT CENTRAL FACILITY
LOCATIONS (E.G. DUTY ROOM, ADMINISTRATION AREA,
CENTRAL HALLWAY, ETC.). AT THESE LOCATIONS
TERMINATE RMVC IN A FLUSH MOUNTED 4"x4"x2" EMT
BOX. ENSURE THE TWO CONDUIT RUNS AND THE EMT
FLUSH MOUNT ENCLOSURES ARE LABELED "FOR MNS
USE"
MAY BE COMBINED INTO ONE CONDUIT FOR
ROUTING PURPOSES.
CM
EGRESS LIGHTING
GENERAL NOTES
1. REFER TO SHEET FA001 FOR GENERAL NOTES AND SYMBOLS.
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE:NTS
SCHEMATIC FIRE ALARM / MASS NOTIFICATION SYSTEM RISER DIAGRAM
1. PROVIDE AN AUTOMATIC, SUPERVISED WET PIPE FIRE SPRINKLER SYSTEM THROUGHOUT THE FACILITY.
2. THE CONTRACTOR MUST PERFORM A FIRE HYDRANT FLOW TEST IN ACCORDANCE WITH NFPA 291.
3. THE FIRE PROTECTION SYSTEM MUST COMPLY WITH NFPA 13 (2019), UFC 3-600-01 (7 FEBRUARY 2020), AND
WITH THESE CONTRACT DRAWINGS.
4. FIRE PROTECTION MATERIALS MUST BE UL LISTED AND/OR FM APPROVED.
5. INSTALLING CONTRACTOR MUST OBTAIN APPROVAL OF AUTHORITIES HAVING JURISDICTION.
6. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE DESIGN, MATERIALS AND EQUIPMENT FOR A TOTALLY
FUNCTIONING AND OPERATING FIRE PROTECTION SYSTEM, INCLUDING THE PROPER INTERFACING AND
COORDINATING WITH ALL OTHER BUILDING SYSTEMS.
7. THE GENERAL CHARACTER AND SCOPE OF THE WORK IS ILLUSTRATED IN THE SPECIFICATIONS AND DRAWINGS. THE SPECIFICATIONS AND DRAWINGS ARE DIVIDED INTO SEVERAL SECTIONS FOR CONVENIENCE ONLY AND THE CONTRACT DOCUMENTS MUST BE CONSIDERED AS A WHOLE. THE CONTRACTOR MUST BE RESPONSIBLE FOR THE COORDINATION OF ALL TRADES, SUBCONTRACTORS, AND VENDORS ENGAGED IN
WORK.
8. THE SPRINKLER SYSTEM DESIGNER MUST BE RESPONSIBLE FOR AVOIDING CONFLICTS BETWEEN FIRE PROTECTION SYSTEMS AND LIGHTING FIXTURES, DIFFUSERS, GRILLES, DUCTS, EQUIPMENT FIXTURES, STRUCTURAL MEMBERS, PIPES, CONDUITS, AND OTHER OBSTRUCTIONS ENCOUNTERED.
9. PIPING LAYOUTS, WHERE SHOWN, ARE DIAGRAMMATIC AND SHOW SYSTEM INTENT. PIPING MAY REQUIRE ADDITIONAL OFFSETS, DROPS, AND RISERS. CONTRACTOR MUST BE RESPONSIBLE FOR FINAL PIPING LAYOUT
AND HYDRAULIC CALCULATIONS.
10. SPRINKLER PIPING MUST BE INSTALLED SO THAT ALL PORTIONS OF THE SYSTEM CAN BE DRAINED BACK THROUGH THE MAIN DRAIN VALVES. WHERE TRAPPED SECTIONS OF PIPING CANNOT BE AVOIDED, AUXILIARY
DRAINS MUST BE PROVIDED. PROVIDE TEST AND DRAIN CONNECTIONS IN ACCORDANCE WITH
SPECIFICATIONS AND NFPA 13.
11. THE INCOMING SPRINKLER SERVICE MUST BE PROVIDED WITH A REDUCED PRESSURE ZONE BACKFLOW PREVENTER. NEW BACKFLOW PREVENTER MUST INCLUDE A FORWARD FLOW TEST CONNECTION, WITH ONE 2 1/2 INCH HOSE CONNECTION FOR EVERY 250 GPM OF ANTICIPATED FLOW OF THE SPRINKLER SYSTEM.
PROVIDE A MEANS OF DRAINING THE BACKFLOW PREVENTER PRESSURE RELIEF DISCHARGE. DRAIN TO
OUTSIDE. SIZE DRAIN PIPE ACCORDING TO MANUFACTURER RECOMMENDATION.
12. DRAINS MUST TERMINATE TO THE EXTERIOR OF THE BUILDING AND BE PROVIDED WITH A SPLASH BLOCK.
DRAINS MAY NOT TERMINATE AT JANITOR'S CLOSETS OR OTHER INTERNAL DRAINS.
13. LOCATE CONTROL VALVES, TEST VALVES, AND LOW POINT DRAIN VALVES IN READILY ACCESSIBLE AREAS WITHIN 5 FEET OF THE FLOOR. TEST VALVES MUST DISCHARGE TO THE OUTSIDE OF THE BUILDING ONTO A
SPLASH BLOCK IF NOT DISCHARGING TO A PAVED SURFACE.
14. SPRINKLER HYDRAULIC DESIGN MUST BE BASED ON NEW HYDRANT FLOW TESTS PERFORMED BY THE CONTRACTOR. NEW FIRE HYDRANT FLOW TESTS MUST BE PERFORMED IN ACCORDANCE WITH NFPA 291.
15. HYDRAULIC CALCULATIONS MUST BE BASED ON AREA/DENSITY APPROACH ONLY. SPECIAL DESIGN
APPROACHES, SUCH AS ROOM DESIGN MUST NOT BE USED.
16. PROVIDE AT LEAST ONE HYDRAULIC CALCULATION FOR EACH HAZARD CLASSIFICATION. HYDRAULIC CALCULATIONS MUST INCLUDE A MINIMUM PRESSURE DROP ACROSS THE BACKFLOW PREVENTERS OF 12 PSI
OR THE ACTUAL PRESSURE DROP WHICHEVER IS GREATER, REGARDLESS OF TYPE OR SIZE.
17. THE SPRINKLER SYSTEMS MUST BE DESIGNED HYDRAULICALLY FOR UNIFORM DISCHARGE DENSITIES ON THE
FOLLOWING BASIS.
18. HIGH PILE STORAGE AND TIRE STORAGE AREAS MUST BE PROTECTED IN ACCORDANCE WITH THE APPLICABLE REQUIREMENTS OF NFPA 13. TIRE STORAGE 125 MUST BE PROTECTED IN ACCORDANCE WITH THE MISCELLANEOUS TIRE STORAGE PROVISIONS OF NFPA 13: 4.3.1.6. AND TABLE 4.3.1.7.1. TIRE STORAGE SHALL BE PROTECTED IN ACCORDANCE WITH NFPA 13: TABLE 4.3.1.7.1. FOR ON FLOOR, ON SIDE STORAGE UP
TO 12 FEET.
19. MAXIMUM SPRINKLER PROTECTION AREA MUST BE 225 SQUARE FEET PER SPRINKLER FOR LIGHT HAZARD AREAS, 130 SQUARE FEET PER SPRINKLER FOR ORDINARY HAZARD AREAS, AND 100 SQUARE FEET PER SPRINKLER FOR EXTRA HAZARD AREAS. EXTENDED COVERAGE SPRINKLERS ARE NOT PERMITTED.
20. PROVIDE PROTECTIVE CAGES ON SPRINKLERS LOCATED LESS THAN 7 FEET ABOVE THE FINISHED FLOOR AND
IN AREAS SUBJECT TO MECHANICAL DAMAGE.
21. PROVIDE INTERMEDIATE AND HIGH TEMPERATURE HEADS AS NEEDED TO MEET NFPA 13, SECTION 8.3.2.5.
THIS INCLUDES BUT IS NOT LIMITED TO UNIT HEATERS, HEATING DUCTS AND DIFFUSERS.
22. CENTER SPRINKLERS IN CENTER OF CEILING TILE.
23. WHERE FREEZE PROTECTION IS REQUIRED FOR A SPECIFIC SPACE, DRY-TYPE SPRINKLERS MAY BE USED.
24. SPRINKLER CONTROL VALVES MUST BE ELECTRICALLY SUPERVISED UNLESS OTHERWISE NOTED.
25. GALVANIZED PIPING IS NOT PERMITTED TO BE USED IN DRY PIPE, PREACTION, OR WET PIPE SPRINKLER
SYSTEMS.
26. PIPING MUST BE INSTALLED TO MAINTAIN CEILING HEIGHTS OR CLEARANCES IN ACCORDANCE WITH NFPA 13, NFPA 101, AND THE CONTRACT DOCUMENTS.
27. SPRINKLER SYSTEM MUST NOT REQUIRE PROTECTION OF PIPING AGAINST DAMAGE FROM EARTHQUAKES IN
ACCORDANCE WITH NFPA 13 AS THE BUILDING IS CLASSIFIED AS SEISMIC DESIGN CATEGORY B.
28. PENETRATIONS OF THE BUILDING AIR BARRIER MUST BE SEALED TO MAINTAIN THE INTEGRITY OF THE AIR
BARRIER. REFER TO ARCHITECTURE DRAWINGS FOR LOCATION AND DETAILS OF AIR BARRIERS.
29. DAMAGE TO WALLS, PARTITIONS, CEILINGS AND FLOORS FROM PENETRATIONS, INSTALLATION OR OTHER
ACTIONS OF THE SPRINKLER INSTALLER MUST BE PATCHED, REPAIRED, PAINTED WITH NEW MATERIALS TO
ORIGINAL CONDITION.
30. STRUCTURAL MEMBERS MUST NOT BE CUT, DRILLED OR BURNED UNLESS PREVIOUSLY APPROVED BY THE
PROJECTS STRUCTURAL ENGINEER AND CONTRACTING OFFICER.
31. PROVIDE SPRINKLER PROTECTION UNDER OBSTRUCTIONS, INCLUDING DUCTS, THAT ARE GREATER THAN 4
FEET.
32. PAINT CONCEALED PIPING AND PIPING IN NORMALLY UNOCCUPIED SPACES WITH PRIMER AND TWO COATS OF
RED OIL BASED PAINT.
33. PAINT EXPOSED PIPING IN OCCUPIED SPACES WITH PRIMER AND TWO COATS OF OIL BASE MATCHING THE
CEILING PAINT IN THE SPACE.
34. PROVIDE SPRINKLER GAUGE INSTALLATION LABELS ON EACH SPRINKLER GAUGE SHOWING SPRINKLER
GAUGES HAVE BEEN TEST OR REPLACED WITHIN FIVE YEARS.
35. PROVIDE A FIVE-INCH, 30 DEGREE ELBOW STORZ CONNECTION MOUNTED TO THE WALL FOR THE FIRE
DEPARTMENT CONNECTION.
36. ISOLATE THE SERVICE LATERAL CONNECTION TO THE SERVICE MAIN WITH AN UNDERGROUND GATE VALVE IN
AN APPROVED ROADWAY BOX INSTALLED IN ACCORDANCE WITH NFPA 24.
FIRE PROTECTION GENERAL NOTESFIRE PROTECTION ABBREVIATIONS AND LEGEND
SYMBOL ABBREVIATION DESCRIPTION
ORDINARY HAZARD
EXTRA HAZARD
ORDINARY
EXTRA
STORAGE AREA DESIGNED WITH
NFPA 13 APPLICABLE CRITERIANFPA 13
[ X / X ] SPRINKLER DESIGN DENSITY
[GPM/SF / SF]
OH
EH
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
K-FACTOR 11.2 11.2 11.2 25.2EXTRA DESIGN 0.3/2,500 0.3/3,600 0.5/3,000 12 SPRINKLERS AT 7 PSI K-FACTOR 8.0 11.2 11.2 25.2ORDINARY DESIGN 0.2/2,500 0.2/2,500 0.2/2,500 12 SPRINKLERS AT 7 PSI K-FACTOR 5.6 11.2 11.2 25.2LIGHT DESIGN 0.1/1,500 0.2/2,500 0.2/2,500 12 SPRINKLERS AT 7 PSI
CEILING HEIGHT
UP TO 30 FEET
CEILING HEIGHT
30 TO 45 FEET
CEILING HEIGHT
45 TO 60 FEET
CEILING HEIGHT 60 TO 100
FEET
HAZARD CLASSIFICATION
WET-PIPE SPRINKLERS: (GPM/FT2)/FT2 [MINIMUM K-FACTOR]
BASED ON HYDRANT FLOW TEST DATA, 61.9 PSI IS AVAILABLE AT 850 GPM. THIS LEAVES 14.3 PSI FOR AVAILABLE INTERIOR LOSSES. A PRELIMINARY COMPUTER GENERATED FRICTION LOSS CALCULATION WAS PERFORMED FOR THE BUILDING USING HRS HASS SOFTWARE. THE CALCULATION UTILIZED SCHEDULE 10, 8-INCH MAINS AND SCHEDULE 10 AND SCHEDULE 40 PIPE WHERE PERMITTED BY UFC 3-600-01. CALCULATIONS INDICATED THAT A PRESSURE OF 54.6 PSI AT A FLOW OF 903 GPM IS REQUIRED FOR THE BUILDING. THIS EQUATES TO A SAFETY
FACTOR OF 13.0 PERCENT.
TOTAL PRESSURE NOT INCLUDING INTERIOR LOSSES 47.6 PSI
UNDERGROUND LOSS 8 INCH AT 600 GPM = 0.428 PSI/100 FT X 1,200 FT 5.2 PSI
BACKFLOW PREVENTER UFC 3-600-01 12.0 PSI
SPRINKLER ELEVATION 54 FT X 0.433 = 23.4 PSI
END HEAD PRESSURE (130 SF X 0.2 GPM/SF / 11.2)^2 7.0 PSI
TOTAL FIRE WATER DEMAND 850 GPM
EXTERIOR HOSE DEMAND 250 GPM 250 GPM
TOTAL SPRINKLER DEMAND 600 GPM
HYDRAULIC IMBALANCE 20% 100 GPM
SPRINKLER DEMAND (0.2 GPM/SF X 2,500 SF) 500 GPM
EXTERIOR HOSE DEMAND 250 GPM UFC 3-600-01
SPRINKLER K-FACTOR 11.2 MINIMUM UFC 3-600-01
DESIGN AREA 2,500 SF UFC 3-600-01
DESIGN DENSITY 0.2 GPM/SF UFC 3-600-01
HAZARD CLASSIFICATION ORDINARY HAZARD UFC 3-600-01
FLOW: 1,210 GPM
RESIDUAL PRESSURE: 60 PSI
STATIC PRESSURE: 64 PSI
PRESSURE HYDRANT: INTERSECTION OF BIRCH AND O STREETS
FLOW HYDRANT: INTERSECTION OF BIRCH AND DUNCAN STREETS
TESTED BY: A. DOBLADO LARA, MBI & D. WALTER, MBI
TEST DATE: 21 APRIL 2021
HYDRANT FLOW DATA
10TH MARINES HIMARS SITE
FE
FE FE
FE
FE
FEC
FE
FE
FE
FE
FE
FE
FE
FE
C
GENERAL NOTES
1. REFER TO SHEET FX001 FOR GENERAL NOTES AND SYMBOLS.
2. ALL AREAS ARE CONSIDERED LIGHT HAZARD UNLESS NOTED OTHERWISE.
3. FIRE SPRINKLER PIPING, WHERE SHOWN, IS FOR REFERENCE ONLY AND
INTENDED TO SHOW SYSTEM INTENT. IT IS THE RESPONSIBLITY OF THE
INSTALLING CONTRACTOR TO DETERMINE FINAL PIPING LAYOUT.
ORDINARY
ORDINARY
ELECTRICAL
ORGANIC STORAGE
AREAS (3)
CAGED EQUIP STOR 'R'
144r
CAGED EQUIP STOR 'S'
144s
CAGED EQUIP STOR 'T'
144t
OFFICE
UNISEX
G103
TELE
3.83.8
2.6
2.1
A'
A'
A
A
B
B
C
C
D
D
E
E F'
F
F
ORDINARY
ORDINARY
ORDINARY
CEILING HEIGHT: 12'-0"
CEILING HEIGHT: 12'-0"
CEILING HEIGHT: 12'-0"
MAXIMUM CEILING HEIGHT: 35'-0"
FX
FX
ORDINARY
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
KEYNOTES
1 SPRINKLER PIPING MUST NOT BE PERMITTED TO TRAVEL THROUGH THE
ROOM UNLESS IT IS SERVING THE ROOM. COMPLY WITH NFPA 70 FOR
CLEARANCES WITH ELECTRICAL EQUIPMENT. SIDEWALL SPRINKLERS ARE
RECOMMENDED.
2 PROVIDE PROTECTIVE GUARDS ON SPRINKLERS IN THIS ROOM.
SCALE: 1/8" = 1'-0"
FIRE PROTECTION - 1ST FLOOR PLAN - AREA A
C
FE
C
FE
C
FE
FE FE FE
FE
FEFE FE
FE FE FE
FE
C
FE
C
FE
C
FE
FE
C
ORDINARY
ORDINARY
ORDINARY
ORDINARY
NFPA 13
FSR OFFICE
ORDO OFFICE
HQ FAC OFFICE
BATTERY FAC OFFICE S
HIMARS MAINT. OFFICER
110a BATTERY FAC OFFICE R
BREAK ROOM
CONFERENCE ROOM
CLASSROOM
HIMAR MAINT. OFFICE
FSR TOOL ROOM + PARTS
STORAGE
PRINT/ FILE
CORRIDOR
C101
VEST
V100
VEST
V101
JAN.
TELECOM
TIRE STORAGE
LEAD ACID BATTERY
STORAGE
MECHANICAL
WOMEN'S HEAD
G102
MEN'S HEAD
G101
STAIR A
STA1
HQ STORAGE
DISPATCH
STAIR B
STB1
'R' STORAGE
105r
'S' STORAGE
105s
'T' STORAGE
105t
GENERAL STORAGE
MEN'S SHOWERS
G101a
BATTERY FAC OFFICE T
CORRIDOR
C100
CORRIDOR
C102
CORRIDOR
C103
CORRIDOR
C104
FX401
C3
NFPA 13 NFPA 13 NFPA 13
3.8
F'
F
F
G
G
H
H
J
J
K
K
L'
L'
L
L
1.6
1.9
2.5
3.3
ORDINARY
BOILER ROOM
ORDINARY
[0.3 GPM/SF / 395 SF]
VEST
V102
[0.24 GPM/SF / 860 SF]
MOTHER'S ROOM
G102a
CEILING HEIGHT: 13'-7"
FX
FX
FX
FX
ORDINARY
GENERAL NOTES
1. REFER TO SHEET FX001 FOR GENERAL NOTES AND SYMBOLS.
2. ALL AREAS ARE CONSIDERED LIGHT HAZARD UNLESS NOTED OTHERWISE.
3. FIRE SPRINKLER PIPING, WHERE SHOWN, IS FOR REFERENCE ONLY AND
INTENDED TO SHOW SYSTEM INTENT. IT IS THE RESPONSIBLITY OF THE
INSTALLING CONTRACTOR TO DETERMINE FINAL PIPING LAYOUT.
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
KEYNOTES
1 SPRINKLER PIPING MUST NOT BE PERMITTED TO TRAVEL THROUGH THE
ROOM UNLESS IT IS SERVING THE ROOM. COMPLY WITH NFPA 70 FOR
CLEARANCES WITH ELECTRICAL EQUIPMENT. SIDEWALL SPRINKLERS ARE
RECOMMENDED.
2 PROVIDE PROTECTIVE GUARDS ON SPRINKLERS IN THIS ROOM.
SCALE: 1/8" = 1'-0"
FIRE PROTECTION - 1ST FLOOR PLAN - AREA B
BOILER ROOM 117 36,580 4,020
SPRINKLER RISER LOCATION FIRST FLOOR FIRE
AREA PROTECTED (SF)
SECOND FLOOR FIRE
AREA PROTECTED (SF)
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
ORDINARY
ORDINARY
ORDINARY
ORDINARY
LAUNCHER MAINTENANCE
BAYS [6]
AUTO MAINTENANCE
BAYS [6]
POL STORAGE
HIMARS MAINTENANCE
TOOL ROOM
HIMARS PARTS STORAGE
TELECOM
CORRIDOR
C105
COMPRESSOR
EXTRA
L
L
M
M
N
N
P
P
P'
P'
R
R
S
S
T
T
U
U
V
V
V'
V'
2.4
2.8
3.2
1.6
1.9
2.5
3.3
ORDINARY
[0.4 GPM/SF / 187 SF]
MAXIMUM CEILING HEIGHT: 54'-0"
ELEC
MECHANICAL
MAXIMUM CEILING HEIGHT: 36'-0"
ORDINARY
ORDINARY
ORDINARY
2 2
GENERAL NOTES
1. REFER TO SHEET FX001 FOR GENERAL NOTES AND SYMBOLS.
2. ALL AREAS ARE CONSIDERED LIGHT HAZARD UNLESS NOTED OTHERWISE.
3. FIRE SPRINKLER PIPING, WHERE SHOWN, IS FOR REFERENCE ONLY AND
INTENDED TO SHOW SYSTEM INTENT. IT IS THE RESPONSIBLITY OF THE
INSTALLING CONTRACTOR TO DETERMINE FINAL PIPING LAYOUT.
N
KEYPLAN
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE PROTECTION - 1ST FLOOR PLAN
KEYNOTES
1 SPRINKLER PIPING MUST NOT BE PERMITTED TO TRAVEL THROUGH THE
ROOM UNLESS IT IS SERVING THE ROOM. COMPLY WITH NFPA 70 FOR
CLEARANCES WITH ELECTRICAL EQUIPMENT. SIDEWALL SPRINKLERS ARE
RECOMMENDED.
2 PROVIDE PROTECTIVE GUARDS ON SPRINKLERS IN THIS ROOM.
FEC
H
H
J
J
K
K
L'
L'
L
L
1.6
1.9
2.5
3.3
STAIR A
STA2
COPY
BATALLION OFFICE
CORRIDOR
C201
BATTALION OPEN OFFICE
BATALLION OFFICER
203a
OFFICE R
205a
CORRIDOR
C202
CONF ROOM
CLASSROOM
BATTERY OFFICE R
BATTERY OFFICE S
OFFICE S
207a
CORRIDOR
C203
STAIR B
STB2
MEN'S HEAD
G202
BATTERY OFFICE T
OFFICE T
209a
WOMEN'S HEAD
G201
JAN.
ELEC
GENERAL NOTES
1. REFER TO SHEET FX001 FOR GENERAL NOTES AND SYMBOLS.
2. ALL AREAS ARE CONSIDERED LIGHT HAZARD UNLESS NOTED OTHERWISE.
3. FIRE SPRINKLER PIPING, WHERE SHOWN, IS FOR REFERENCE ONLY AND
INTENDED TO SHOW SYSTEM INTENT. IT IS THE RESPONSIBLITY OF THE
INSTALLING CONTRACTOR TO DETERMINE FINAL PIPING LAYOUT.
N
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
SCALE: 1/8" = 1'-0"
FIRE PROTECTION - 2ND FLOOR PLAN
KEYNOTES
1 FIRE SPRINKLER SYSTEM MUST EXTEND TO SECOND FLOOR THROUGH THIS
LOCATION.
BOILER ROOM
H
B3
FX401
B3
FX401
GENERAL NOTES
1. REFER TO SHEET FX001 FOR GENERAL NOTES AND SYMBOLS.
2. FIRE SPRINKLER PIPING, WHERE SHOWN, IS FOR REFERENCE ONLY AND
INTENDED TO SHOW SYSTEM INTENT. IT IS THE RESPONSIBLITY OF THE
INSTALLING CONTRACTOR TO DETERMINE FINAL PIPING LAYOUT.
FLOW SWITCH
TEST AND DRAIN VALVE
CHECK VALVE
BUTTERFLY VALVE
TEST HEADER
5-INCH STORZ
FIRE DEPARTMENT CONNECTION
LOW POINT DRAIN
CONCRETE SPLASH BLOCK
CHECK VALVE
BUTTERFLY VALVE
(NORMALLY CLOSED)
8-INCH INCOMING FIRE
SERVICE LATERAL
REDUCED PRESSURE ZONE
BACKFLOW PREVENTER
TO WET-PIPE
SPRINKLER SYSTEM
RPZ DRAIN WITH AIR GAP WITH DRAIN TO
FLOOR DRAIN OR OUTSIDE
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
DP-02 IFC - 06/08/2021
KEYNOTES
1 FIRE WATER SERVICE ENTRANCE
2 LOW POINT DRAIN
3 BACKFLOW PREVENTER FORWARD FLOW TEST HEADER
4 FIRE SPRINKLER RISER
5 5-INCH STORZ FIRE DEPARTMENT CONNECTION
6 REDUCED PRESSURE ZONE BACKFLOW PREVENTER
7 THRUST ROD AND SLEEVE ALL PIPE PENETRATIONS THROUGH THE GRADE
FLOOR SLAB IN ACCORDANCE WITH UFC 3-600-01.
SCALE: NOT TO SCALE C3
FIRE PROTECTION - ENLARGED
RISER PLAN
SCALE: A3
FIRE PROTECTION - RISER
ISOMETRIC
SCALE: NOT TO SCALE B3FIRE PROTECTION - RISER DETAIL
File details come from the government source that posted it. Updated .