Attachment I - 2W for IR-CATH-EP CDs Drawings 5 of 5.pdf

PDF 10 MB Posted

Attached to
Z1DA--636A8-21-001 CON Remodel 2W for IR/CATH/EP 36C263-22-AP-3804
Solicitation number
36C26323R0002
Issued by

About this file

This attachment provides drawings related to a federal contract solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The solicitation seeks proposals to remodel space for interventional radiology, cardiac catheterization, and electrophysiology procedures at the VA Medical Center in Albany, New York. Offerors should provide pricing to complete construction drawings and specifications as well as construction services. The response deadline is April 15, 2022, with an anticipated award date of May 15, 2022. This is a small business set-aside solicitation.

View the file

Other files

File Type Posted
Attachment N - Questions Request Form-all questions combined_Response_12132022.doc DOC document
Attachment S- 2W IR CATH EP_Luminos Agile Max_Site Specific.pdf PDF
Attachment P - 2W IR CATH EP_Draeger-Boom Install_Site Specific.pdf PDF
Attachment O - 2W IR CATH EP_Cath Lab_Site Specific.pdf PDF
36C26323R0002 0001.docx DOCX document
Attachment U - Shielding Documents.pdf PDF
636A8-21-001 Pre-Proposal Conference Sign-in List 11222022.pdf PDF
Evaluation Factors -Amendment 0001.docx DOCX document
Attachment R- 2W IR CATH EP_IR Lab_Site Specific.pdf PDF
Attachment J.1 636A8-21-001 Sole Source List.pdf PDF
Attachment T - 2W IR CATH EP_Multi-Use Rad Room_Site Specific.pdf PDF
Attachment J - Brand Name Only JAs_Redacted.pdf PDF
Attachment H - 2W for IR-CATH-EP CDs Drawings 4 of 5.pdf PDF
Attachment F - 2W for IR-CATH-EP CDs Drawings 2 of 5.pdf PDF
Attachment C - 2W IR CATH EP_CDs_ SPECS Vol1.pdf PDF
Attachment K - Wage Determination IA20210068 dated 09-02-2022.pdf PDF
36C26323R0002.docx DOCX document
Attachment A - SOW 636A8-21-001 final.pdf PDF
Attachment M - Past Performance Questionnaire - 3 Pages.docx DOCX document
Attachment B - Price Schedule Breakdown Sheet - 1 page.xlsx XLSX spreadsheet
Attachment N - Questions Request Form.doc DOC document
Attachment G - 2W for IR-CATH-EP CDs Drawings 3 of 5.pdf PDF
Attachment L - NARA Contract Language 2021.pdf PDF
Attachment D - 2W IR CATH EP_CDs_ SPECS Vol2.pdf PDF
Attachment E - 2W for IR-CATH-EP CDs Drawings 1 of 5.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T T

T

T

TT

T

TT

T

TT

T

T T

T

TT

T T

T

T

T

T

T

T

A BA' C D D1 E F

0.9

G

14 M

FF

H

7'

CIRCULATION

2C07A

MED PREP/ NOURISH

2W178

TOILET

2W176

NURSE STATION

2W177

CIRCULATION

2C07

EP LAB

2W151

CONTROL

2W151A

CATH LAB

2W153

CONTROL

2W153A

IR LAB

2W154

CONTROL

2W154A

HAC

2W158

CORRIDOR

2C03A

SEMI RESTRICTED CORRIDOR

2C03B

EQUIPMENT PARK

2W181

MEN'S LOCKER

2W156

WOMEN'S LOCKER

2W157

WOMEN'S SHOWER

2W157A

RECOVERY

2W175

CLEAN LINEN

2W174

CLEAN UTILITY ROOM

2W173

ULTRASOUND

2W132

RADIOLOGY/ MULTI-PURPOSE

2W131

TOILET

2W130A

RADIOLOGY/ FLUOROSCOPY

2W130

IR MANAGER OFFICE

2W129D

NURSE MANAGER OFFICE

2W129C

OPEN OFFICE CUBICLES

2W129

ELEVATOR LOBBY

2C02

EP EQUIPMENT ROOM

2W179

PRE/POST BAY

2W175E

PRE/POST BAY

2W175D

PRE/POST BAY

2W175C

ALCOVE

2W175F

PRE/POST BAY

2W175B

PRE/POST BAY

2W175A

SHAFT

2W103

SHAFT

2W104

CORRIDOR

2C06

ELEC

2W180

STAIR

2ST07

MEN'S SHOWER

2W156A

CIRCULATION

2C05

CATH EQUIPMENT ROOM

2W134

UTILITY SOILED ROOM

2W133

STERILE SUPPLY

2W155

IR EQUIPMENT ROOM

2W150

OFFICE

2W129B

ALCOVE

2W129E

ELEC

2W152CRU-2W179

GCU-2W134

CRU-2W134

CRU-2W150

TAB-2W129A

TAB-2W129B TAB-2W129E

TAB-2C02

TAB-2W129C

TAB-2W129D

TAB-2W130

TAB-2W131

TAB-2W135

TAB-2W175E

TAB-2W175DTAB-2W175C

TAB-2W175B

TAB-2W175A

TAB-2W175

RTAB-2W175

TAB-2W151A

TAB-2W157

TAB-E

TAB-2W156

RTAB-2W158A

RTAB-2W152A RTAB-2W153A

TAB-2W153A

TAB-2W183

TAB-2W175A

TAB-2W175B TAB-2W175C TAB-2W175D TAB-2W175E

TAB-2W173

TAB-2W173

TAB-2W135

TAB-2W131

TAB-2W130

TAB-2W129B

TAB-2W129A

TAB-2W129E

TAB-2W129C TAB-2W129D

TAB-2W175

TAB-2W151

RTAB-2W151A

TAB-2W151A

TAB-2W151A

TAB-2W152A

TAB-2W153

TAB-2W152A

TAB-2W158A

TAB-2W158A

TAB-2W157

TAB-2W156

TAB-2W154

TAB-2W153A

TAB-2C02

KEY PLAN - SECOND FLOOR

1. REFER TO EQUIPMENT SCHEDULES TO CROSS REFERENCE WHICH CONTROL DIAGRAMS

APPLY TO WHICH ITEMS OF EQUIPMENT. REFER TO TERMINAL AIR BOX (TAB) SCHEDULES

FOR TEMP SENSOR REQUIREMENTS FOR EACH TAB.

2. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL CONTROL DIAGRAMS SHALL BE

DISCRETE FROM ALL OTHER POINTS EXCEPT AS SPECIFICALLY NOTED.

3. ALL WIRING, CONTROL COMPONENTS, DEVICES AND PROGRAMMING SHOWN ON THESE

CONTROL DRAWINGS SHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLY NOTED

OTHERWISE.

4. TEMPERATURE CONTROL CABLING, CONDUIT, BOXES, IDENTIFICATION: REFER TO THE

SPECIFICATIONS FOR A COMPLETE LIST OF REQUIREMENTS. THE FOLLOWING SCHEDULE IS

PROVIDED AS A CONVENIENCE.

A. CABLE/WIRE JACKET COLOR: GREY

B. CONDUIT BOX COLOR ABOVE FINISHED CEILINGS AND UNFINISHED SPACES WITHOUT

CEILINGS: GREY

C. CONDUIT BOX COLOR IN SPACES WITH EXPOSED FINISHED STRUCTURE: GREY

D. CABLE/WIRE INSTALLATION: IN CONDUIT

5. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FOR THIS PROJECT UNLESS AN

ACTUATOR IS SPECIFICALLY INDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BE

PNEUMATIC.

6. ALL MODULATING DAMPER AND VALVE ACTUATORS SHOWN WITH POSITION FEEDBACK

SHALL HAVE THE VALVE POSITION DISPLAYED ON GRAPHICAL SCREEN ADJACENT TO THE

DAMPER/VALVE COMMAND SIGNAL. DISPLAYED VALVE POSITION SHALL BE FROM THE

FEEDBACK DEVICE/CIRCUIT (OUTPUT SIGNAL FROM THE FMCS TO THE ACTUATOR IS NOT

ACCEPTABLE)

7. MODULATING SIGNALS SHALL BE DISPLAYED AS % OPEN (SIGNALS DISPLAYED AS %

CLOSED ARE NOT ACCEPTABLE).

8. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DUCT STATIC

PRESSURE SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES FAN

SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.

9. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DIFFERENTIAL

PRESSURE OF ANY PUMPED WATER SYSTEM (E.G. HEATING HOT WATER, CHILLED WATER

AND THE LIKE) SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES PUMP

SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.

10. ALL CONTROL COMPONENTS SUCH AS RELAYS, SWITCHES, DDC CONTROLLERS, ETC.

SHALL BE MOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTING BACKPLATES PER

SPECIFICATIONS.

11. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPY OF THE APPLICABLE SEQUENCE OF

OPERATION AND CONTROL DIAGRAM INDICATING THE POINTS, COMPONENTS AND

OPERATION OF EQUIPMENT ASSOCIATED WITH EACH PANEL. REFER TO SECTIONS FOR

ADDITIONAL REQUIREMENTS.

12. TCC SHALL WIRE THE CONTROL SIGNAL FROM THE ASSOCIATED AIR HANDLING UNIT RTU

CONTROL PANEL TO CONTROL THE OPERATION OF SMOKE DAMPERS IN ACCORDANCE

WITH SEQUENCE OF OPERATION. TCC SHALL PROVIDE ALL WIRING, CONDUIT,

TRANSFORMERS, FUSING AND ALL OTHER ELECTRICAL COMPONENTS REQUIRED FOR

COMPLETE INSTALLATION.

13. TCC SHALL EXTEND CONTROL SIGNAL FROM ADDRESSABLE RELAY DEVICE SERVING EACH

AIR HANDLING UNIT. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS. TCC SHALL

EXTEND AND TERMINATE WIRING AS REQUIRED FOR EQUIPMENT SHUTDOWN.

14. TCC SHALL PROVIDE POWER SUPPLIES FOR ALL 24VAC POWER REQUIREMENTS TO

INCLUDE, BUT NOT LIMITED TO, [APPLICATION SPECIFIC] [TERMINAL AIR BOX] [FAN COIL UNIT]

CONTROLLERS, DAMPER AND VALVE ACTUATORS, BUILDING PRESSURE SENSORS, AND

OTHER CONTROL COMPONENTS AND DEVICES. REFER TO CONTROLS SPECIFICATIONS FOR

POWER SUPPLY REQUIREMENTS. REFER TO [TEMPERATURE CONTROL] [HEATING] FLOOR

PLANS FOR POWER SUPPLY LOCATIONS. PROVIDE LOW VOLTAGE WIRING FROM POWER

SUPPLIES TO ALL CONTROLLERS, MONITORS, COMPONENTS AND DEVICES REQUIRING 24

VAC POWER. ADDITIONAL POWER SUPPLIES NOT SHOWN AND REQUIRED FOR A COMPLETE

AND OPERATIONAL SYSTEM SHALL BE PROVIDED BY THE TEMPERATURE CONTROL

CONTRACTOR. THE TEMPERATURE CONTROL CONTRACTOR SHALL PROVIDE FINANCIAL

PROVISIONS WITHIN THEIR BID FOR THE ELECTRICAL CONTRACTOR TO PROVIDE BRANCH

POWER TO THE ADDITIONAL POWER SUPPLIES. COORDINATE THE LOCATION OF

ADDITIONAL POWER SUPPLY CABINET WITH THE ELECTRICAL CONTRACTOR.

15. ELEMENT LENGTHS FOR BOTH MIXED AIR TEMP SENSORS AND LOW LIMIT TEMP SWITCHES

SHALL BE MINIMUM 1 LINEAR FOOT PER SQUARE FOOT OF COIL SURFACE AREA. PROVIDE

MULTIPLE SENSORS AND SWITCHES AS NEEDED TO ACHIEVE REQUIRED ELEMENT

LENGTHS. LOCATE RESET SWITCHES MAX. 6'-6" ABOVE ADJACENT STANDING SURFACE (E.G.

ROOF, PLATFORM OR FLOOR) SO THE RESET SWITCH CAN BE CYCLED WITHOUT THE NEED

FOR A LADDER.

16. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL REQUIRED

CONTROL DEVICES AND COMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMS AND

DETAILS FOR ADDITIONAL CONTROL DEVICES, COMPONENTS AND REQUIREMENTS NOT

SHOWN ON THESE CONTROL DRAWINGS.

17. TCC SHALL PROVIDE ALL CONTROL COMPONENTS AND ACCESSORIES AS REQUIRED FOR

EQUIPMENT TO BE CONTROLLED AS DESCRIBED IN THE SEQUENCE OF OPERATION

REGARDLESS OF WHETHER ALL CONTROL COMPONENTS OR POINTS ARE SHOWN IN THE

ASSOCIATED CONTROL DIAGRAM.

TEMPERATURE CONTROL GENERAL NOTES:

I O W A

S E

D

PROFESS IO NA

20825

L

IC

E N

L E

N G

I N E

E R

ERIC J.

HENDERSON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T .0

V

A -V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th

-E P

C

D e lla n .J

.L le w e lly n .r v t

/8

/2

:2 :2

P

M

1-MT1

SECOND FLOOR PLAN -

TEMPERATURE CONTROLS

REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 DAVING DELLLE16133

N O R

HT

1/8" = 1'-0"

SECOND FLOOR - TEMPERATURE CONTROLS

Revisions: Date:

AIAI

AI

AODI

DO

DI

AOAI

AOAI

AO AI

AI

AI

DI DI

DO

AI

AIAO

DODI

AODI

DO

DI

DI

AI AI

DI

AI

AI

AI

AI

DI

DI

DI

AO AI

TH

FM

VFD

F M

T T T

FM

H

VFD

H T

H

T

AOAI

LL TEMP

SWITCH#1

SP

RETURN

AIR

DUCT MOUNTED

TEMPERATURE &

HUMIDITY

SENSORS

RETURN DUCT

MOUNTED LOW

STATIC SWITCH

RETURN

AIRFLOW

RETURN

FAN

COMMUNICATION LINK

BETWEEN VFD GATEWAY &

FMCS (TYPICAL EACH VFD)

MODALRM

START/

STOP

CS

FAN

STATUS

ACT

N.C.

DMPR

MOD.

DMPR

FDBK

TO ADDITIONAL RETURN

FANS. VERIFY QUANTITY OF

FANS AND VFDS WITH

SCHEDULE.

RELIEF

AIR

RELIEF

AIR

DAMPER

ACT

ACT

OUTSIDE

AIRFLOW

N.C.

O.A.

DMPR

MOD.

DMPR

FDBK

SP

MIXED AIR

LOW STATIC

SWITCH

DMPR

FDBK

DMPR

MOD.

DP DP

FILTER

STATUS

FILTER

STATUS

IFB STEAM

COIL

VALV

MOD.

STM

LL TEMP

SWITCH#2

SP

RETURN

AIR

DAMPER

N.O.

OUTSIDE

AIR

DAMPER

M.A.

TEMP

PRE-

FILTER

(30%)

PRE-

FILTER

(60%)

STEAM

SUPPLY

VALV

FDBK

OPEN/

CLOSE

MOD

VALV

FDBK

CWR

CWS

DIFF. PRESS.

SWITCH (0-1" W.G.

SCALE) (TYP.2)

ISOLATION STEAM

VALVE

N.C.

N.C.

TO ADDITIONAL SUPPLY FANS.

VERIFY QUANTITY OF FANS

AND VFDS WITH SCHEDULE.

COOLING

COIL

MOUNT FLOWMETER DISPLAY

WITHIN SERVICE VESTIBULE

OF EACH RTU OR ON

EXTERIOR OF AHU FOR

INDOOR UNITS. (TYP.)

MODALRM

CS

FAN

STATUS

DP

FINAL FILTER

STATUS

HIGH STATIC

SWITCH

DUCT MOUNTED

TEMPERATURE &

HUMIDITY

SENSORS

MOUNT IN

DISCHARGE

PLENUM OF AHU.

DUCT

MOUNTED

HUMIDITY

SWITCH

SP

SUPPLY

AIR

STATIC

PRESS.

TRANS.

LOCATE DUCT DIFFERENTIAL

STATIC PRESSURE SENSOR NEAR

MOST REMOTE TERMINAL AIR BOX.

AHU REPORT GENERATION:

DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND. THE TREND SHALL RUN FOR A 100-DAY (ADJ.) DURATION AT WHICH POINT THE

NEWEST VALUES SHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:

• DATE

• TIME

• GLOBAL OUTSIDE AIR TEMP [°F]

• GLOBAL OUTSIDE AIR DEWPOINT [°F]

• GLOBAL OUTSIDE AIR HUMIDITY [%RH]

• SUPPLY AIRFLOW [CFM]

• SUPPLY AIR TEMP (SAT) [°F]

• SUPPLY AIR TEMP SETPOINT [°F]

• SUPPLY AIR RELATIVE HUMIDITY [%]

• SUPPLY AIR DEWPOINT [°F]

• SUPPLY AIR DEWPOINT SETPOINT [°F]

• RETURN AIRFLOW [CFM]

• RETURN AIR TEMP (RAT) [°F]

• RETURN AIR RELATIVE HUMIDITY [%]

• OUTSIDE AIRFLOW [CFM]

• MIXED AIR TEMP [°F]

• PREHEAT COIL DISCHARGE AIR TEMP [°F]

• PREHEAT COIL DISCHARGE AIR TEMP [°F]

• PRE-FILTER ALARM (30% FILTER) [STATUS] [* PRE-FILTER LOADING [STATUS]]

• PRE-FILTER ALARM (60% FILTER) [STATUS] [* PRE-FILTER LOADING [STATUS]]

• FINAL FILTER ALARM [STATUS] [* FINAL FILTER LOADING [STATUS]]

• HEATING WATER VALVE POSITION [% OPEN]

• HEATING PUMP [ON/OFF]

• CHILLED WATER VALVE POSITION [% OPEN]

• HUMIDIFIER VALVE POSITION [% OPEN]

• HUMIDIFIER ISOLATION VALVE [OPEN/CLOSED]

• SUPPLY DUCT STATIC PRESSURE SETPOINT [INCHES W.G.]

• SUPPLY DUCT STATIC PRESSURE [INCHES W.G.]

• SUPPLY FAN VFD OUTPUT [% FULL SPEED]

• RETURN FAN VFD OUTPUT [% FULL SPEED]

• OUTSIDE AIR DAMPER POSITION [% OPEN]

• RETURN AIR DAMPER POSITION [% OPEN]

• RELIEF AIR DAMPER POSITION [% OPEN]

THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN GRAPHICAL FORM ON THE FMCS

OPERATOR WORKSTATION.

ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST AHU AIRFLOW WHICH

OCCURRED DURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER

VALUES LISTED ABOVE) THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS

INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE FMCS OPERATOR

WORKSTATION THAT IS MAINTAINED (NOT AUTOMATICALLY OVERWRITTEN).

AIR HANDLER REPORT GENERATION

SEQUENCE OF OPERATION:

WHEN AHU/RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:

• SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL OPEN.

• AFTER A 30 SECOND DELAY (ADJ.) TO ALLOW FOR OPENING OF SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS. SUPPLY FAN SHALL BE ENABLED TO RUN.

• WHEN THE SUPPLY FAN HAS STARTED THE RETURN FAN AND INTERLOCKED EXHAUST FANS SHALL START AS SHOWN IN THE FAN INTERLOCK SCHEDULE.

SUPPLY FAN OPERATION:

FMCS SHALL MODULATE SIGNAL TO SUPPLY FAN VFD TO MAINTAIN DUCT STATIC PRESSURE AS MEASURED BY STATIC PRESSURE TRANSMITTER NEAR THE END OF THE CRITICAL DUCT

BRANCH.

RETURN FAN OPERATION:

RETURN FAN SHALL BE INDEXED TO RUN WHENEVER THE SUPPLY FAN IS INDEXED TO RUN. FMCS SHALL MODULATE SIGNAL TO RETURN FAN VFD AS REQUIRED TO MAINTAIN THE AIRFLOW

OFFSET AS INDICATED IN THE RETURN FAN AIRFLOW SCHEDULE.

STATIC PRESSURE RESET:

FMCS SHALL RESET SUPPLY DUCT STATIC PRESSURE SETPOINT BELOW THE MAXIMUM SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 90% (ADJ.) OPEN. FMCS SHALL MONITOR ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.

DISCHARGE AIR TEMPERATURE SET POINT:

DISCHARGE AIR SET POINT SHALL BE 49ºF (ADJ.).

DISCHARGE AIR TEMPERATURE RESET:

RESET DISCHARGE AIR TEMPERATURE BASED ON THE ZONE WITH THE GREATEST CALL FOR COOLING. RESET THE TEMPERATURE AS FOLLOWS:

• WHEN WORST CASE TAB IS LESS THAN 90% (ADJ.) OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL INCREASE BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL

AHU MAXIMUM DISCHARGE AIR TEMPERATURE OF 60ºF (ADJ.) IS ACHIEVED.

• WHEN WORST CASE TAB IS MORE THAN 90% OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL DROP BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU

MINIMUM DISCHARGE AIR TEMPERATURE OF 55ºF (ADJ.) IS ACHIEVED.

• THE MAXIMUM ALLOWABLE RETURN AIR HUMIDITY SETPOINT SHALL BE 60% (ADJ.). IF RETURN AIR HUMIDITY IS GREATER THAN SETPOINT, RESET DISCHARGE AIR TEMPERATURE TO 55°F

UNTIL RETURN AIR HUMIDITY IS 5% LESS THAN MAXIMUM SETPOINT FOR 10 MINUTES (ADJ.).

STATIC PRESSURE AND DISCHARGE AIR TEMPERATURE RESET PRIORITY:

RESET THE DISCHARGE AIR TEMPERATURE PRIOR TO RESETTING THE DUCTWORK STATIC PRESSURE SETPOINT. ONCE THE MAXIMUM SUPPLY TEMPERATURE IS REACHED THEN THE SYSTEM

SHALL ENABLE THE STATIC PRESSURE RESET.

VENTILATION AIR CONTROL:

WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE MINIMUM OUTSIDE AIR FLOW RATE, OR TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE.

COOLING COIL OPERATION:

WHEN IN MINIMUM OUTSIDE AIR MODE, FMCS SHALL MODULATE CHILLED WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.

WHEN IN ECONOMIZER MODE, FMCS SHALL NOT MODULATE COOLING CONTROL VALVE UNLESS RETURN AIR DAMPER IS 5% (ADJ.) OPEN AND RELIEF AIR DAMPER IS 95% (ADJ.) OPEN.

PREHEAT COIL OPERATION:

PREHEAT COIL CONTROLS SHALL BE ENABLED WHEN OUTSIDE AIR TEMP DROPS BELOW 50°F (ADJ.). PREHEAT COIL CONTROLS SHALL BE DISABLED WHEN OUTSIDE AIR TEMP RISES ABOVE 54°

F (ADJ.).

WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 38°F (ADJ.) FOR 10 MINUTES (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE ONLY WHEN HEATING IS CALLED FOR (HEATING WATER VALVE IS COMMANDED TO OPEN). WHEN OUTSIDE AIR TEMP DROPS BELOW 38°F (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE CONTINUOUSLY. ONCE ENERGIZED, HEATING WATER COIL CIRCULATION PUMP SHALL REMAIN IN OPERATION FOR MINIMUM 5 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.

FMCS SHALL MODULATE HEATING WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.

ECONOMIZER OPERATION:

WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULB TEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDE AIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.)

BEFORE BEING ALLOWED TO SWITCH BACK (TO PREVENT SHORT CYCLING).

IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.

HUMIDIFIER CONTROLS:

HUMIDIFIER CONTROLS AND ALARMS SHALL BE ENABLED WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 48°F (ADJ.) AT WHICH POINT THE ISOLATION STEAM VALVE SHALL FULLY OPEN.

HUMIDIFIER CONTROLS AND ALARMS SHALL BE DISABLED WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 48°F (ADJ.) FOR 10 MINUTES (ADJ.) AT WHICH POINT THE ISOLATION STEAM VALVE

SHALL FULLY CLOSE.

WHEN HUMIDIFIER CONTROLS ARE ENABLED, FMCS CONTROLLER SHALL MODULATE STEAM VALVE AS REQUIRED TO MAINTAIN 43°F DEWPOINT (ADJ.) IN THE SUPPLY AIR DUCT. DUCT MOUNTED HUMIDITY TRANSMITTER AT FAN DISCHARGE SHALL PREVENT SUPPLY AIR RELATIVE HUMIDITY FROM EXCEEDING 80% (ADJ.).

A

B

C

D

E

F

R

A

B

C

D

E

F

AUX CONTACT TO

FMCS TO INITIATE

CONTROL

TERMINAL

STRIP SPEED

CONTROL

SIGNALRETURN FAN

VFD SECTION

SPEED

CONTROL

SIGNALSUPPLY FAN

VFD SECTION

TERMINAL

STRIP

AUX CONTACT TO

FMCS TO INITIATE

CONTROL

SAFETY

CIRCUITS

NH

D U

C T

H

IG

H S

T A

T

IC

D U

C T

L O

W S

T A

T

IC

L O

W L

IM

IT

T E

M P

S W

IT

C

H

SUPPLY & RETURN FAN VFD CONTROL

RETURN FAN AIRFLOW SCHEDULE

SYSTEM SUPPLY CFM EXHAUST FANS PRESSURIZATION

CFM

REMARKS

AH1-31 15,000 EF1-47 0 NOTES 1,2,3

FAN INTERLOCK SCHEDULE

SYSTEM INTERLOCKED EXHAUST FANS REMARKS

AH1-31 EF1-47 NOTE 1

CWR

TEMP

CWS

TEMP

P.H.

TEMP

NOTES:

1. RETURN FAN AIRFLOW SETPOINT SHALL BE THE SUPPLY FAN AIRFLOW (AS MEASURED BY THE

AFMS) MINUS THE SUM OF THE EXHAUST FAN AIRFLOWS MINUS THE PRESSURIZATION CFM.

2. FMCS SHALL DETERMINE THE OPERATIONAL STATUS OF EACH EXHAUST FAN VIA THE

CURRENT SENSING RELAY TO DETERMINE WHETHER THE CFM ASSOCIATED WITH THAT FAN

SHOULD BE INCLUDED IN THE RETURN FAN AIRFLOW CALCULATION.

3. EXHAUST FAN AIRFLOWS SHALL NOT BE THE CFM INDICATED ON THE FAN SCHEDULE, BUT

SHALL BE THE AIRFLOW INDICATED IN THE FINAL TAB REPORT.

NOTES:

1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE

AHU IN ACCORDANCE WITH AHU SEQUENCE OF OPERATION.

CONNECT FIRE ALARM TO AHU START/STOP CIRCUIT SO FIRE ALARM CAN SHUT

DOWN AND SO AHU CAN AUTOMATICALLY RESTART AFTER A FIRE ALARM TEST

FIRE ALARM SYSTEM

VALV

MOD

VALV

FDBK

N.C.

ACT

DMPR

MOD.

VALV

FDBK

ALARMS, INTERLOCKS, AND SAFETIES:

WHEN FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, AHU SHALL BE SHUTDOWN.

THE FOLLOWING CONDITIONS SHALL SHUTDOWN THE AHU AND SHALL INDICATE AN ALARM CONDITION AT THE FMCS WORKSTATION:

• LOW STATIC PRESSURE SWITCH INDICATES RETURN DUCT PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS.

• LOW STATIC PRESSURE SWITCH INDICATES MIXED AIR PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS OF THE OUTSIDE AIR DUCTWORK.

• HIGH STATIC PRESSURE SWITCH INDICATES SUPPLY DUCT STATIC PRESSURE GREATER THAN THE SPECIFIED DUCT PRESSURE CLASS.

• SHOULD ANY ONE FOOT SECTION OF THE MANUAL RESET LOW LIMIT TEMPERATURE SWITCH #1 SENSE AIR TEMP <34°F (ADJ.). IF MULTIPLE FREEZE STATS ARE REQUIRED, WIRE ALL TO A

COMMON RESET SWITCH.

THE FOLLOWING CONDITIONS SHALL INDICATE AN ALARM AT THE FMCS, HOWEVER AHU SHALL CONTINUE TO OPERATE:

• HEATING COIL CIRCULATION PUMP IS COMMANDED TO RUN AND CURRENT RELAY INDICATES INSUFFICIENT CURRENT FLOW.

• AN ALARM IS INDICATED AT ANY SUPPLY FAN VFD OR RETURN FAN VFD.

• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (30%) BANK EXCEEDS 0.6 INCHES W.G. (ADJ.)

• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (60%) BANK EXCEEDS 0.8 INCHES W.G. (ADJ.)

• DIFFERENTIAL PRESSURE SWITCH ACROSS FINAL FILTER BANK EXCEEDS 1.0 INCHES W.G. (ADJ.)

• THE TOTAL DIFFERENTIAL PRESSURE ACROSS ALL FILTER BANKS EXCEEDS 2.0 INCHES W.G. (ADJ.)

• RELATIVE HUMIDITY OF SUPPLY AIR EXCEEDS 80% RH (ADJ.) AS MEASURED BY AUTOMATIC RESET HUMIDITY SWITCH. WHEN HUMIDITY SWITCH TRIPS, STEAM CONTROL VALVE SHALL

FULLY CLOSE UNTIL ALARM IS RESET AT FMCS WORKSTATION. AN ALARM SHALL NOT INDICATE AT THE FMCS WORKSTATION UNLESS HUMIDIFIER CONTROLS ARE ENABLED.

• WHEN DUCTWORK SUPPLY AIR HUMIDITY EXCEEDS 90% RH A SEPARATE DUCT MOUNTED HUMIDITY SWITCH (MANUAL RESET) SHALL DISABLE HUMIDIFIER CONTROLS AND SHALL FULLY

CLOSE STEAM ISOLATION VALVE. AN IDENTIFIABLE ALARM CONDITION SHALL BE DISPLAYED AT THE OPERATOR WORKSTATION.

• SHOULD ANY ONE FOOT SECTION OF THE AUTO RESET LOW LIMIT TEMPERATURE SWITCH #2 SENSE AIR TEMPERATURE <38°F (ADJ.) THE FOLLOWING SHALL OCCUR:

• THE RETURN AIR DAMPER SHALL FULLY OPEN.

• THE OUTSIDE AIR AND RELIEF DAMPERS SHALL FULLY CLOSE.

• THIS ACTION SHALL OCCUR INDEPENDENT OF THE FMCS AHU CONTROLLER. ONCE THE LOW LIMIT TEMPERATURE SWITCH #2 AIR TEMPERATURE RISES ABOVE SET POINT, OPERATION OF

THE OUTSIDE AIR, RELIEF AIR, AND RETURN AIR DAMPERS SHALL BE RESTORED. HOWEVER, THE ALARM SHALL CONTINUE UNTIL ACKNOWLEDGED AND MANUALLY RESET BY THE FMCS

OPERATOR.

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT.

IN THE EVENT SUPPLY FAN IS NOT RUNNING (AS INDICATED BY THE CURRENT SENSING RELAYS) RETURN AIR FAN SHALL BE DE-ENERGIZED.

WHENEVER AHU/RTU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:

• THE OUTSIDE AIR DAMPER AND RELIEF AIR DAMPER SHALL FULLY CLOSE.

• RETURN AIR DAMPER SHALL FULLY OPEN.

• PREHEAT COIL HEATING WATER CIRCULATION PUMP AND HEATING WATER CONTROL VALVE SHALL REMAIN UNDER CONTROL OF ITS INPUT SENSOR.

• ALL SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL FULLY CLOSE.

• CHILLED WATER CONTROL VALVE SHALL FULLY CLOSE.

• ISOLATION STEAM VALVE SHALL FULLY CLOSE.

• SUPPLY FAN AND RETURN FAN VFDS SHALL BE DE-ENERGIZED.

• INTERLOCKED EXHAUST FANS SHALL BE DE-ENERGIZED.

UNOCCUPIED MODE:

PROVIDE TIME OF DAY SCHEDULE TO ALLOW AHU TO ENTER UNOCCUPIED MODE PER SCHEDULE. COORDINATE SCHEDULE WITH OWNER.

• THE SUPPLY AND RETURN FANS SHALL CONTINUE RUNNING. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND THE SUPPLY

FAN SHALL BE LIMITED TO THE MAXIMUM RETURN FAN AIRFLOW.

• THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.

• ALL SPACE TEMPERATURES SHALL BE ALLOWED TO VARY +/- 10°F (ADJ.) FROM OCCUPIED SETPOINT.

HEATING OPTIMUM START-UP:

• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC

SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO WARM THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 68ºF

(ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.

COOLING OPTIMUM START-UP:

• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC

SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO COOL THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES ARE LESS THAN A SETPOINT OF

75ºF (ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.

GRAPHICAL DISPLAY:

DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON AHU GRAPHIC PAGE.

FINAL

FILTER

I O W A

S E

D

PROFESS IO NA

20825

L

IC

E N

L E

N G

I N E

E R

ERIC J.

HENDERSON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T .0

V

A -V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th

-E P

C

D e lla n .J

.L le w e lly n .r v t

/8

/2

:2 :2

P

M

1-MT2

AHU CONTROL DIAGRAM REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 DAVING DELLLE16133

NO SCALE

AIR HANDLING UNIT CONTROL - AH1-31

DO

DI

AI

AIAO

AI

AO

AO

AI

AIDIDI DI

AI AI

AIDI

DI

TH

H

FS

T H

AI

AIAO

AI

AO

AI

T

T

AO

AI

FAN

STATUS

CS

START/

STOP

EXHAUST

AIR

ACT

SEQUENCE OF OPERATION:

EXHAUST FAN SHALL BE INTERLOCKED TO RUN CONTINUOUSLY WHEN

RESPECTIVE AHU IS OPERATING.

2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED. WHEN FAN

IS DE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.

ALARMS, INTERLOCKS AND SAFETIES:

AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN

THE EVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE

CURRENT SENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.

WALL

MOUNTED

OCCUPANCY

SENSOR

PRIMARY AIR FROM ZONE

CONDITIONING AHU

SUPPLY

AIR

ACTVELOCITY AND

STATIC SENSOR

PRESSURE INDEPENDENT

TERMINAL AIR BOX (TAB)

DAMPER ACTUATOR DAMPER

MOD.

TAB

AIRFLOW

HWS

HWR

FLOATING 2-WAY CONTROL VALVE

(REFER TO FLOOR

PLANS FOR WHERE 3-

WAY VALVES ARE REQ'D)

FAIL IN

PLACE

ACTVELOCITY AND

STATIC SENSOR

PRESSURE INDEPENDENT

TERMINAL AIR BOX (TAB)

DAMPER ACTUATOR

DAMPER

MOD.

TAB

AIRFLOW

ROOM

RETURN AIR

RETURN

AIR

DIFFERENTIAL PRESSURE

MONITOR PROVIDE ONE PER

ROOM & MOUNT AT

LOCATIONS SHOWN ON

PLANS

DIFF.

PRESS.

ALARM

STATUS

MD MD

WALL MOUNTED

MOTION

DETECTORS

WALL MTD

TEMP SENSOR

WALL MTD

HUMIDITY

SENSOR

NOTE: WALL MOUNTED TEMPERATURE &

HUMIDITY SENSORS SHALL HAVE THE

FOLLOWING FEATURES:

· LOCAL TEMPERATURE & HUMIDITY

ADJUSTMENT

· DIGITAL DISPLAY OF ROOM

TEMPERATURE & HUMIDITY

SETPOINTS

DUCT MTD TEMP

& HUMIDITY

SENSORS

DUCT

MTD

HUMIDITY

SWITCH

AIRFLOW

SWITCH

DS

DOOR POSITION

SWITCH

SEQUENCE OF OPERATION:

WHEN ANY ROOM OCCUPANCY SENSOR DETECTS MOTION FMCS SHALL ENABLE OCCUPIED MODE AND THE FOLLOWING SHALL OCCUR:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB HW REHEAT COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE SETPOINT WITH 2°F (ADJ.)

DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR.

• PRIMARY SUPPLY TAB SHALL SUPPLY MAX. SCHEDULED AIRFLOW PER TAB SCHEDULE

• LOCAL TEMP SETPOINT ADJUSTMENT SHALL BE ENABLED ALLOWING TEMP SETTINGS 60°F - 80°F (ADJ.).

• SECONDARY SUPPLY TAB DAMPER SHALL REMAIN FULLY CLOSED.

• FMCS SHALL MODULATE RETURN TAB DAMPERS AS REQUIRED TO MAINTAIN THE ROOM AT MIN. +0.010 INCHES W.G. RELATIVE TO ADJACENT CORRIDOR.

• FMCS SHALL MODULATE REHEAT COIL HW CONTROL VALVE AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT (68°F).

IN THE EVENT REHEAT COIL HW CONTROL VALVE IS FULLY CLOSED AND ADDITIONAL COOLING IS REQUIRED, FMCS SHALL MODULATE THE SECONDARY SUPPLY TAB DAMPER AS

REQUIRED TO MAINTAIN SPACE TEMP SETPOINT.

WHEN BOTH ROOM OCCUPANCY SENSORS DO NOT DETECT MOTION FOR 15 MINUTES (ADJ.), FMCS SHALL ENABLE UNOCCUPIED MODE AND THE FOLLOWING SHALL OCCUR:

• PRIMARY SUPPLY TAB SHALL SUPPLY MIN. SCHEDULED AIRFLOW PER TAB SCHEDULE.

• PRIMARY SUPPLY TAB DAMPER SHALL MODULATE OPEN TO MAINTAIN ROOM SETPOINT.

• LOCAL TEMP SETPOINT ADJUSTMENT SHALL BE DISABLED AND ROOM TEMP SETPOINT SHALL BE 68°F (ADJ.).

• SECONDARY SUPPLY TAB DAMPER SHALL FULLY CLOSE.

• FMCS SHALL MODULATE RETURN TAB DAMPERS AS REQUIRED TO MAINTAIN THE ROOM AT MIN. +0.010 INCHES W.G. RELATIVE TO ADJACENT CORRIDOR.

• FMCS SHALL MODULATE REHEAT COIL HW CONTROL VALVE (WITH TAB DAMPER IN MINIMUM POSITION) AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT.

SEQUENCING OF SUPPLY AND RETURN TAB DAMPERS SHALL MAINTAIN A POSITIVE PRESSURE WITHIN THE ROOM AT ALL TIMES WHEN TRANSITIONING BETWEEN OCCUPIED AND

UNOCCUPIED MODES AND VICE VERSA.

FMCS SHALL RE-ZERO ALL DAMPER AND VALVE ACTUATOR POSITIONS WHEN BOTH CONDITIONS ARE MET:

• 120 HOURS (ADJ.) HAS PASSED SINCE THE LAST RE-ZEROING.

• THE ROOM IS IN UNOCCUPIED MODE.

FMCS SHALL MONITOR ROOM DIFFERENTIAL PRESSURE AND SHALL DISPLAY THE VALUE ON THE TAB GRAPHICAL SCREEN AT THE OPERATOR WORKSTATION.

THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITION TO RESET THE SUPPLY AND RETURN DUCT DIFFERENTIAL STATIC PRESSURE.

HUMIDIFIER OPERATION:

FMCS SHALL ENABLE HUMIDIFIER CONTROLS WHEN OA DEWPOINT DROPS BELOW 38°F (ADJ.) AND SHALL FULLY OPEN STEAM ISOLATION VALVE. FMCS SHALL MODULATE HUMIDIFIER STEAM VALVE AS REQUIRED TO MAINTAIN ROOM HUMIDITY SETPOINT (40% RH, ADJ.). FMCS SHALL LIMIT STEAM VALVE OPERATION TO PREVENT DUCT MOUNTED HUMIDITY LEVELS FROM EXCEEDING 70% RH (ADJ.) AT DUCT MOUNTED HUMIDITY TRANSMITTER.

HUMIDIFIER STEAM VALVE SHALL NOT BE ENABLED UNLESS AIRFLOW IN SUPPLY DUCT IS PROVEN BY AN AIRFLOW SWITCH.

FMCS SHALL DISABLE HUMIDIFIER CONTROLS AND ALARMS WHEN OA DEWPOINT RISES ABOVE 40°F (ADJ.) AND SHALL FULLY CLOSE STEAM ISOLATION VALVE.

SMOKE EVACUATION MODE:

ELECTRICAL CONTRACTOR SHALL INSTALL SMOKE DETECTOR. UPON DETECTION OF SMOKE, THE OPERATING ROOM SHALL ENTER PURGE MODE

• THE COOLING ONLY TAB SHALL CLOSE. IN EACH OR ROOM CONNECTED TO THE AHU IN PURGE MODE. (DOES NOT APPLY TO TREATMENT)

• THE REHEAT TAB SHALL BE OPEN IF ROOM IS OCCUPIED OR CLOSED IF ROOM IS UNOCCUPIED.

• THE RETURN TAB SHALL MODULATE TO MAXIMUM CFM.

• THE AIR HANDLING UNIT SHALL ENTER 100% OA.

• OCCUPIED LOCAL SETPOINT ADJUSTMENT SHALL BE 70°F - 80°F (ADJ.)

• ALL OTHER ROOMS SHALL REMAIN IN NORMAL OPERATION.

ALARMS, INTERLOCKS & SAFETIES:

AN ALARM SHALL BE INDICATED AT THE OPERATING WORKSTATION IN THE EVENT ANY OF THE FOLLOWING OCCUR:

• WHEN SUPPLY AIR HUMIDITY EXCEEDS 80% RH A SEPARATE DUCT MOUNTED HUMIDITY SWITCH (MANUAL RESET) SHALL DISABLE HUMIDIFIER CONTROLS AND SHALL FULLY

CLOSE STEAM ISOLATION VALVE. AN IDENTIFIABLE ALARM CONDITION SHALL BE DISPLAYED AT THE OPERATOR WORKSTATION.

• ROOM POSITIVE PRESSURE (RELATIVE TO ADJACENT CORRIDOR) DROPS BELOW 0.01 INCHES W.G. (ADJ.) FOR MORE THAN 45 SECONDS (ADJ.) AS MEASURED BY ROOM

DIFFERENTIAL PRESSURE MONITOR (AUTO RESET).

• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.

WALL MTD

TEMP SENSOR

HWS

HWR

PRIMARY AIR FROM ZONE

CONDITIONING AHU

SUPPLY

AIR

ACTVELOCITY AND

STATIC SENSOR

PRESSURE INDEPENDENT

TERMINAL AIR BOX (TAB)

FAIL IN

PLACE

DAMPER ACTUATORDAMPER

MOD.

TAB

AIRFLOW

2-WAY CONTROL VALVE

(REFER TO FLOOR

PLANS FOR WHERE 3-

WAY VALVES ARE REQ'D)

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB HW

REHEAT COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F

(ADJ.) WITH 5°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTED

TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR

REQUIREMENTS. SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°

F (ADJ.) OFFSET FROM THE DDC SETPOINT.

• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE

REHEAT COIL CONTROL VALVE SHALL BE CLOSED.

• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED

UNTIL SPACE SETPOINT IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM

SCHEDULED CFM POSITION PER THE TAB SCHEDULE. THE REHEAT COIL

CONTROL VALVE SHALL BE CLOSED.

• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE REHEAT COIL CONTROL

VALVE SHALL MODULATE OPEN TO MAINTAIN SPACE SETPOINT UNTIL THE

SUPPLY AIR TEMPERATURE IS 20°F ABOVE ROOM TEMPERATURE SETPOINT.

• UPON A FURTHER FALL IN SPACE TEMPERATURE, TAB SHALL OPEN TO MAINTAIN

SETPOINT UNTIL TAB AIRFLOW REACHES ITS MAXIMUM HEATING SETTING. THE

REHEAT CONTROL VALVE SHALL CONTINUE TO MODULATE OPEN TO MAINTAIN

MAXIMUM DELTA T LISTED ABOVE.

• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TO

RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.

• WHEN FLOATING CV'S ARE USED, FMCS SHALL PERFORM AN AUTO-ZERO

FUNCTION EVERY NIGHT DURING UNOCCUPIED TIMES. THE FMCS SHALL

STAGGER AUTO-ZERO SEQUENCES SO THAT ALL VALVES DO NOT

SIMULTANEOUSLY CLOSE.

ALARMS, INTERLOCKS & SAFETIES:

SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE

IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.

SUPPLY AIR TEMP

LOCATE TEMPERATURE SENSOR 4'-0"

DOWNSTREAM OF COIL IN THE

CENTER OF DUCT

MOD

VLV

FDBK

RETURN AIR

FROM SPACE

ACTVELOCITY AND

STATIC SENSOR

PRESSURE INDEPENDENT

TERMINAL AIR BOX (TAB)

DAMPER ACTUATORDAMPER

MOD.

TAB

AIRFLOW

RETURN AIR

TO AHU

SEQUENCE OF OPERATION:

• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO

CFM OFFSET FROM ASSOCIATED SUPPLY AIR TAB.

• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX

POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC

PRESSURE.

I O W A

S E

D

PROFESS IO NA

20825

L

IC

E N

L E

N G

I N E

E R

ERIC J.

HENDERSON

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T .0

V

A -V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th

-E P

C

D e lla n .J

.L le w e lly n .r v t

/8

/2

:2 :2

P

M

1-MT3

CONTROL DIAGRAMS REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 DAVING DELLLE16133

NO SCALE

EXHAUST FAN CONTROL - AHU INTERLOCK - EF1-47

NO SCALE

TAB OPERATING ROOM CONTROL - TYPE C

NO SCALE

TAB CONTROL W/ HOT WATER REHEAT - TYPE A

NO SCALE

TAB CONTROL RETURN - TYPE B

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

ABBR: DESCRIPTION:

TYP TYPICAL

C CONDUIT

UNO UNLESS NOTED OTHERWISE

GFI GROUND FAULT INTERRUPTER

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS

SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.

WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING

THE NORMAL BRANCH.

4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE

DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED

WHEN CONDUIT IS SPECIFIED EXPOSED.

5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM

FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND

OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO

7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX

CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED

DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO

BE INSTALLED.

8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)

EXCEPT WHERE OTHERWISE NOTED.

9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED

FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE

NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.

10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL

BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.

11. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT

LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.

PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL

ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE

FURNITURE AND/OR EQUIPMENT.

12. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE

EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

14. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.

CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING

EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE

RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF ANY

WELDERS ASSIGNED TO THE JOB.

15. GENERAL CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED

FOR THE EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES

WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

16. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

17. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL

REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.

ELECTRICAL INSTALLATION NOTES:

NORMAL BRANCH LUMINAIRE

CRITICAL BRANCH LUMINAIRE

EMERGENCY LIFE SAFETY BRANCH LUMINAIRE

[UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE']

LUMINAIRE SYMBOL KEY

SYMBOL: DESCRIPTION:

DP-# DISTRIBUTION PANEL 26 24 16

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

R-# RELAY 26 09 39

C-# GENERAL PURPOSE CONTACTOR 26 28 21

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:

RELATED

SPECIFICATION

FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

V1 V3

V7 VH

FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

A1 A3

A7 AH

AS

FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

V1 V3

V7 VH

FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

A1 A3

A7 AH

SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING

MOUNTED

SD FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

SD FA-123 28 31 00 FIRE ALARM IN DUCT SMOKE DETECTOR

FA-140 28 31 00 FIRE ALARM HEAT DETECTOR H

FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVERFT

FA-161 28 31 00 FIRE ALARM RELAYAR

FA-160 28 31 00 FIRE ALARM ADDRESSABLE MONITOR MODULEMM

FA-270 28 31 00 FIRE ALARM ELECTROMAGNETIC DOOR

HOLD DEVICE

DH

FA-241 28 31 00 FIRE ALARM REMOTE INDICATORRI

FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR

AND TEST SWITCH

RTS/I

PP ARCH PUSH PADPP

VS

VS

SW-1P 26 09 33 SWITCH - SINGLE POLE

SW-3W 26 09 33 SWITCH - THREE WAY3

SW-4W 26 09 33 SWITCH - FOUR WAY4

SW-OC-P-O SWITCH - OCCUPANCY SENSOR

WALL SWITCH

O

OCCUPANCY SENSOR - PASSIVE INFRARED

100 DEGREE COVERAGE - WALL MOUNT

OCCUPANCY SENSOR - ULTRASONIC 360

DEGREE COVERAGE - WALL MOUNT

OCCUPANCY SENSOR - DUAL

TECHNOLOGY - WALL MOUNTED

ETD ALCR20 UL924 TRANSFER RELAY - LIGHTING

26 09 33

26 09 33

CB-# 26 28 16 CIRCUIT BREAKER - SURFACE MOUNTED.

REFER TO DISC/STA SCHEDULE

CB-# 26 28 16 CIRCUIT BREAKER - FLUSH MOUNTED.

REFER TO DISC/STA SCHEDULE

DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT. REFER TO DISC/STA SCHEDULE

AS

SW-D-LED DIMMER - LED

D

26 09 33

SW-D3-LED DIMMER - LED - 3-WAY

D3

26 09 33

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:FB-# or PT-# 26 27 26 FLOOR BOX or POKE THROUGH

JB 26 05 33 JUNCTION BOX

J

J

ECONN 26 05 33 ELECTRICAL CONNECTION

E

E

WW-# 26 05 35 ELECTRICAL WIREWAY w/ DEVICES SHOWN

WM-# 26 05 35 MULTI OUTLET SYSTEM

PANEL '###' 26 24 16 PANELBOARD - SURFACE MOUNT

PANEL '###' 26 24 16 PANELBOARD - RECESS MOUNT

ISO-# 26 24 21 ISOLATED POWER PANEL

GB 26 05 26 GROUND BUSGB

IBT 26 05 26 INTERSYSTEM BONDING TERMINATIONIBT

EPO 26 09 16 EMERGENCY STOP, N.O. CONTACTEPO

MX-#/MS-#

/CB-#/CS-#

26 24 19 MANUAL SWITCH / STARTER / COMBINATION

STARTER/ CIRCUIT BREAKER. REFER TO

DISC/STA SCHEDULE

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

TR-#/DTR-# 26 22 00 TRANSFORMER. REFER TO

TRANSFORMER SCHEDULE

FA-280 28 31 00 ISOLATION MODULEIM

26 32 13

LINEAR LUMINAIRES

TROFFER

DOWNLIGHT LUMINAIRE

INDUSTRIAL LUMINAIRE

SINGLE FACE EXIT SIGN

DOUBLE FACE EXIT SIGN

EMERGENCY UNIT

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

REC-DUP-GFI-R 26 27 26 GROUND FAULT DEVICEG

REC-TAMP 26 27 26 DUPLEX RECEPTACLE, TAMPER RESISTANT, 125V

REC-TAMP-GFI 26 27 26 GFI DUPLEX RECEPTACLE,

TAMPER RESISTANT, 125V

REC-TAMP-QUAD 26 27 26 QUAD RECEPTACLE, TAMPER RESISTANT, 125V

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V

REC-QUAD-GFI 26 27 26 QUAD GFI RECEPTACLE, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

REFER TO LUMINAIRE

SCHEDULE

RIM 26 24 21 REMOTE LINE ISOLATION MONITORRIM

SW-OC-D-W

D

26 09 33##

SW-OC-P-W

P

26 09 33##

SW-OC-U-W

U

26 09 33##

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING

CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS

BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING

FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK

AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF

WORK.

5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED

WITH HIS/HER WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

ELECTRICAL PHASING NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO

ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR

CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT

THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY

DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF

THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.

WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN

SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED

SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10' - 0" HEIGHT ABOVE

PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG-1 UNDERLINED TEXT INDICATES ADDITIONAL INFORMATION CAN BE FOUND

ELSEWHERE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

TEMPERATURE CONTROLS CONTRACTORT.C.C.

FIRE PROTECTION CONTRACTORF.P.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

CONTRACTING OFFICER'S REPRESENTATIVEC.O.R

CONTACT PERSONS:

PROJECT MANAGER

MECHANICAL

ELECTRICAL

TECHNOLOGY

STRUCTURAL

ERIC HENDERSON

ERIC HENDERSON

ISAAC STOLL

DAMON DEEN

JOHN PAUL GOEDKEN

DESCRIPTION: PERSON:

BUILDING CODE: IBC 2018 EDITION

FIRE CODE: IFC 2018 EDITION, VA FIRE PROTECTION DESIGN

MANUAL

PLUMBING CODE: IPC 2018 EDITION, VA PLUMBING DESIGN MANUAL

MECHANICAL CODE: IMC 2018 EDITION, VA HVAC DESIGN MANUAL

ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION

LIFE SAFETY CODE: NFPA 101 2021 EDITION

ENERGY CONSERVATION CODE: IECC 2012

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

M

A X

20" MAX.

M

A X

20"-25" MAX.

M

A X

M

IN

. 4

M

A X

M

A X

10" MAX. 10"-24" MAX.

ADA GUIDELINES - FRONT ACCESS

ADA STANDARDS FOR ACCESSIBLE DESIGN

INSTALL ABOVE COUNTER

DEVICE AT 44" ABOVE

FINISHED FLOOR.

INSTALL ABOVE COUNTER

DEVICE AT 40" ABOVE

FINISHED FLOOR.

INSTALL DEVICE AT 18"

ABOVE FINISHED FLOOR.

ADA GUIDELINES - SIDE ACCESS

INSTALL DEVICE AT 44"

ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 42"

ABOVE FINISHED FLOOR.

1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR

SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT

NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL

EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.

2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE

LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET 1-E9.

3. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

4. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND

OPERATES FROM EMERGENCY BATTERY WHERE SPECIFIED (EXTEND UNSWITCHED CIRCUIT

LEG TO BATTERY) OTHERWISE VIA EMERGENCY CIRCUIT UPON LOSS OF POWER.

5. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN

EMERGENCY CIRCUIT.

6. REFER TO SHEET 1-E9 FOR LUMINAIRE SCHEDULE.

7. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR

DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER

SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA

OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING

MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC

MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT

DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

EWC ELECTRIC WATER COOLER

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG

1 = CIRCUIT NUMBER

a = SWITCH DESIGNATION

NL = SUBSCRIPT (IF APPLICABLE)

Z = ZONE DESIGNATION

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: F1 / 1 / a / NL

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL SHEET INDEX

1-E0 ELECTRICAL COVERSHEET

1-ED1 SECOND FLOOR DEMOLITION - ELECTRICAL

1-ED2 THIRD FLOOR DEMOLITION - ELECTRICAL

1-EL1 SECOND FLOOR PLAN - LIGHTING

1-EL2 THIRD FLOOR PLAN - LIGHTING

1-EP1 SECOND FLOOR PLAN - POWER

1-EP2 THIRD FLOOR PLAN - POWER

1-EP3 ROOF PLAN - POWER

1-ES1 SECOND FLOOR PLAN - SYSTEMS

1-ES2 THIRD FLOOR PLAN - SYSTEMS

1-E4 ELECTRICAL ENLARGED PLANS

1-E5 ELECTRICAL ENLARGED PLANS

1-E6 ELECTRICAL DETAILS

1-E7 ELECTRICAL DETAILS

1-E8 ELECTRICAL RISER DIAGRAMS

1-E9 ELECTRICAL SCHEDULES

1-E10 ELECTRICAL SCHEDULES

1-E11 ELECTRICAL SCHEDULES

1-E12 ELECTRICAL SCHEDULES

GRAND TOTAL: 19

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T

.0

V A

-V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th -E

P C z a c h a ry

.r .r o s s .r v t

/8

/2

:1

:4

P M

1-E0

ELECTRICAL COVERSHEET REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 KLS ZRR16133Revisions: Date:

I O W A

S E

D

PROFESS IONA

15842

L

IC

E N

L E

N G

I N E

E R

ANDREW D.

THIELEN

I O W A

S E

D

PROFESS IONA

15842

L

IC

E N

L E

N G

I N E

E R

ANDREW D.

THIELEN

OCOCOCOC

OC OC

OC

E

E

E J

PP

EPO

E P

O

EPO

EPO E

PP

E

E

P P

PP

P P

E P

O E

P O

E

E

E

A1

SDSD

SD

SD

A

A

A

SD

SD

V

V

V

V1

A

A1

V7

V7

V7

A1

AA

AA

A

SD

SD SDSD SD

SD

F

F

SD

V

V

V

E P

O

EPO

E P

O

E P

O

E

E

E

E E

E

E E

E

E

E

OC

OC

E

A BA' C D D1 E F

0.9

G

14 M

FF

H

7'

RADIOLOGY

PANEL

80A CB

RADIOLOGY

EQUIP. SYSTEM

COMPONENTS

RADIOLOGY

EQUIP.

DOOR DOOR

DOOR

MED GAS

ALARM

MED GAS

ALARM

BOOM

BOOM

BOOM

BOOM

ANGIO

PANEL

CATH PANEL

SC1

PU2

PU1

SC1

PU2

PU1

1-AC-A3

1-AC-A4

N221 CB

FDS-TC221

TN221

TC221

EXISTING PANEL N221

EXISTING PANEL C221

TN220

N220 CB

EXISTING PANEL N220

DISTRIBUTION PANEL X220H

CB-C220

PANEL L220H

PANEL L220

EXISTING DISTRIBUTION PANEL N220H

DISTRIBUTION PANEL X220HJB

DISTRIBUTION PANEL NX220H

EXISTING PANEL C220H

(SQUARE D NQOB)

(SQUARE D NQOB)

(SQUARE D NQOB)

(SQUARE D I-LINE)

(SQUARE D NEHB)

(SQUARE D I-LINE)

(SQUARE D I-LINE)

(SQUARE D NQOB)

(SQUARE D NEHB)

PANEL C220

TC220

KEY PLAN - SECOND FLOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T

.0

V A

-V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th -E

P C z a c h a ry

.r .r o s s .r v t

/8

/2

:1

:3

A

M

1-ED1

SECOND FLOOR DEMOLITION -

ELECTRICAL

REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 KLS ZRR16133

N O R

HT

1/8" = 1'-0"

SECOND FLOOR DEMOLITION - ELECTRICAL

KEYNOTES:

1. DEMO FOR THIS AREA IS PART OF A

DIFFERENT PROJECT'S SCOPE. REMOVE ANY

REMAINING DEVICES AS NECESSARY.

2. ELECTRICAL CONNECTION FOR EXISTING LAB

EQUIPMENT.

3. CIRCUIT BREAKER PREVIOUSLY SERVING

RADIOLOGY LAB EQUIPMENT.

Revisions: Date:

CONSTRUCTION

DOCUMENTS

I O W A

S E

D

PROFESS IONA

15842

L

IC

E N

L E

N G

I N E

E R

3W103B

3ST07

3W103

3W105

MECH SHAFT

3W103A

3W104

3ST06

3W101

3W09

3S01

3C01

3CW01A

3W100

3W07

DW-2

3W102A

3W102

3CO1A

3C03

MECH SHAFT

3W19A3W11

3CW02A

3C02

3W17A

3W101A

CL-1

3W17

3W17B

3W101B

3W17C

3S08D

3W19B

B1

S H A F T

S H A F T

3W103D

3W19C

SHAFT

3W223

B3

C1

C2

3W103C

3W222

B2

3W101C

J

E

E

A BA' C D D1 E F

0.9

G

14 M

FF

H

7'

T-CATH

T-IR

PANEL A300

TA300

PANEL A300H

PANEL N300

TN300

PANEL N300H

ANGIO CATH

CATH LAB UPS

MCC A321H

LIEBERT UNIT COMPRESSOR

(1) BUS DUCT

(3) 4" C.

+7'-0" TO BOTTOM

(SQUARE D NQOD)

(SQUARE D NEHB)

(SQUARE D NQOD)

(SQUARE D I-LINE)

CHILLER

KEY PLAN - THIRD FLOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com

C R e v it L o c a l F ile s \M

E P

T

.0

V A

-V

IS

N

-I o w a C it y -R e m o d e l

IR

-C a th -E

P C z a c h a ry

.r .r o s s .r v t

/8

/2

:1

:4

A

M

1-ED2

THIRD FLOOR DEMOLITION -

ELECTRICAL

REMODEL 2W IR-CATH-EP

IOWA CITY VAHCS

636A8-21-001

BUILDING 1

04/08/2022 KLS ZRR16133

N O R

HT

1/8" = 1'-0"

THIRD FLOOR DEMOLITION - ELECTRICAL

KEYNOT…