Attachment I - 2W for IR-CATH-EP CDs Drawings 5 of 5.pdf
PDF 10 MB Posted
- Solicitation number
- 36C26323R0002
About this file
This attachment provides drawings related to a federal contract solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The solicitation seeks proposals to remodel space for interventional radiology, cardiac catheterization, and electrophysiology procedures at the VA Medical Center in Albany, New York. Offerors should provide pricing to complete construction drawings and specifications as well as construction services. The response deadline is April 15, 2022, with an anticipated award date of May 15, 2022. This is a small business set-aside solicitation.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T T
T
T
TT
T
TT
T
TT
T
T T
T
TT
T T
T
T
T
T
T
T
A BA' C D D1 E F
0.9
G
14 M
FF
H
7'
CIRCULATION
2C07A
MED PREP/ NOURISH
2W178
TOILET
2W176
NURSE STATION
2W177
CIRCULATION
2C07
EP LAB
2W151
CONTROL
2W151A
CATH LAB
2W153
CONTROL
2W153A
IR LAB
2W154
CONTROL
2W154A
HAC
2W158
CORRIDOR
2C03A
SEMI RESTRICTED CORRIDOR
2C03B
EQUIPMENT PARK
2W181
MEN'S LOCKER
2W156
WOMEN'S LOCKER
2W157
WOMEN'S SHOWER
2W157A
RECOVERY
2W175
CLEAN LINEN
2W174
CLEAN UTILITY ROOM
2W173
ULTRASOUND
2W132
RADIOLOGY/ MULTI-PURPOSE
2W131
TOILET
2W130A
RADIOLOGY/ FLUOROSCOPY
2W130
IR MANAGER OFFICE
2W129D
NURSE MANAGER OFFICE
2W129C
OPEN OFFICE CUBICLES
2W129
ELEVATOR LOBBY
2C02
EP EQUIPMENT ROOM
2W179
PRE/POST BAY
2W175E
PRE/POST BAY
2W175D
PRE/POST BAY
2W175C
ALCOVE
2W175F
PRE/POST BAY
2W175B
PRE/POST BAY
2W175A
SHAFT
2W103
SHAFT
2W104
CORRIDOR
2C06
ELEC
2W180
STAIR
2ST07
MEN'S SHOWER
2W156A
CIRCULATION
2C05
CATH EQUIPMENT ROOM
2W134
UTILITY SOILED ROOM
2W133
STERILE SUPPLY
2W155
IR EQUIPMENT ROOM
2W150
OFFICE
2W129B
ALCOVE
2W129E
ELEC
2W152CRU-2W179
GCU-2W134
CRU-2W134
CRU-2W150
TAB-2W129A
TAB-2W129B TAB-2W129E
TAB-2C02
TAB-2W129C
TAB-2W129D
TAB-2W130
TAB-2W131
TAB-2W135
TAB-2W175E
TAB-2W175DTAB-2W175C
TAB-2W175B
TAB-2W175A
TAB-2W175
RTAB-2W175
TAB-2W151A
TAB-2W157
TAB-E
TAB-2W156
RTAB-2W158A
RTAB-2W152A RTAB-2W153A
TAB-2W153A
TAB-2W183
TAB-2W175A
TAB-2W175B TAB-2W175C TAB-2W175D TAB-2W175E
TAB-2W173
TAB-2W173
TAB-2W135
TAB-2W131
TAB-2W130
TAB-2W129B
TAB-2W129A
TAB-2W129E
TAB-2W129C TAB-2W129D
TAB-2W175
TAB-2W151
RTAB-2W151A
TAB-2W151A
TAB-2W151A
TAB-2W152A
TAB-2W153
TAB-2W152A
TAB-2W158A
TAB-2W158A
TAB-2W157
TAB-2W156
TAB-2W154
TAB-2W153A
TAB-2C02
KEY PLAN - SECOND FLOOR
1. REFER TO EQUIPMENT SCHEDULES TO CROSS REFERENCE WHICH CONTROL DIAGRAMS
APPLY TO WHICH ITEMS OF EQUIPMENT. REFER TO TERMINAL AIR BOX (TAB) SCHEDULES
FOR TEMP SENSOR REQUIREMENTS FOR EACH TAB.
2. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL CONTROL DIAGRAMS SHALL BE
DISCRETE FROM ALL OTHER POINTS EXCEPT AS SPECIFICALLY NOTED.
3. ALL WIRING, CONTROL COMPONENTS, DEVICES AND PROGRAMMING SHOWN ON THESE
CONTROL DRAWINGS SHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLY NOTED
OTHERWISE.
4. TEMPERATURE CONTROL CABLING, CONDUIT, BOXES, IDENTIFICATION: REFER TO THE
SPECIFICATIONS FOR A COMPLETE LIST OF REQUIREMENTS. THE FOLLOWING SCHEDULE IS
PROVIDED AS A CONVENIENCE.
A. CABLE/WIRE JACKET COLOR: GREY
B. CONDUIT BOX COLOR ABOVE FINISHED CEILINGS AND UNFINISHED SPACES WITHOUT
CEILINGS: GREY
C. CONDUIT BOX COLOR IN SPACES WITH EXPOSED FINISHED STRUCTURE: GREY
D. CABLE/WIRE INSTALLATION: IN CONDUIT
5. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FOR THIS PROJECT UNLESS AN
ACTUATOR IS SPECIFICALLY INDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BE
PNEUMATIC.
6. ALL MODULATING DAMPER AND VALVE ACTUATORS SHOWN WITH POSITION FEEDBACK
SHALL HAVE THE VALVE POSITION DISPLAYED ON GRAPHICAL SCREEN ADJACENT TO THE
DAMPER/VALVE COMMAND SIGNAL. DISPLAYED VALVE POSITION SHALL BE FROM THE
FEEDBACK DEVICE/CIRCUIT (OUTPUT SIGNAL FROM THE FMCS TO THE ACTUATOR IS NOT
ACCEPTABLE)
7. MODULATING SIGNALS SHALL BE DISPLAYED AS % OPEN (SIGNALS DISPLAYED AS %
CLOSED ARE NOT ACCEPTABLE).
8. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DUCT STATIC
PRESSURE SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES FAN
SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
9. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DIFFERENTIAL
PRESSURE OF ANY PUMPED WATER SYSTEM (E.G. HEATING HOT WATER, CHILLED WATER
AND THE LIKE) SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES PUMP
SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
10. ALL CONTROL COMPONENTS SUCH AS RELAYS, SWITCHES, DDC CONTROLLERS, ETC.
SHALL BE MOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTING BACKPLATES PER
SPECIFICATIONS.
11. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPY OF THE APPLICABLE SEQUENCE OF
OPERATION AND CONTROL DIAGRAM INDICATING THE POINTS, COMPONENTS AND
OPERATION OF EQUIPMENT ASSOCIATED WITH EACH PANEL. REFER TO SECTIONS FOR
ADDITIONAL REQUIREMENTS.
12. TCC SHALL WIRE THE CONTROL SIGNAL FROM THE ASSOCIATED AIR HANDLING UNIT RTU
CONTROL PANEL TO CONTROL THE OPERATION OF SMOKE DAMPERS IN ACCORDANCE
WITH SEQUENCE OF OPERATION. TCC SHALL PROVIDE ALL WIRING, CONDUIT,
TRANSFORMERS, FUSING AND ALL OTHER ELECTRICAL COMPONENTS REQUIRED FOR
COMPLETE INSTALLATION.
13. TCC SHALL EXTEND CONTROL SIGNAL FROM ADDRESSABLE RELAY DEVICE SERVING EACH
AIR HANDLING UNIT. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS. TCC SHALL
EXTEND AND TERMINATE WIRING AS REQUIRED FOR EQUIPMENT SHUTDOWN.
14. TCC SHALL PROVIDE POWER SUPPLIES FOR ALL 24VAC POWER REQUIREMENTS TO
INCLUDE, BUT NOT LIMITED TO, [APPLICATION SPECIFIC] [TERMINAL AIR BOX] [FAN COIL UNIT]
CONTROLLERS, DAMPER AND VALVE ACTUATORS, BUILDING PRESSURE SENSORS, AND
OTHER CONTROL COMPONENTS AND DEVICES. REFER TO CONTROLS SPECIFICATIONS FOR
POWER SUPPLY REQUIREMENTS. REFER TO [TEMPERATURE CONTROL] [HEATING] FLOOR
PLANS FOR POWER SUPPLY LOCATIONS. PROVIDE LOW VOLTAGE WIRING FROM POWER
SUPPLIES TO ALL CONTROLLERS, MONITORS, COMPONENTS AND DEVICES REQUIRING 24
VAC POWER. ADDITIONAL POWER SUPPLIES NOT SHOWN AND REQUIRED FOR A COMPLETE
AND OPERATIONAL SYSTEM SHALL BE PROVIDED BY THE TEMPERATURE CONTROL
CONTRACTOR. THE TEMPERATURE CONTROL CONTRACTOR SHALL PROVIDE FINANCIAL
PROVISIONS WITHIN THEIR BID FOR THE ELECTRICAL CONTRACTOR TO PROVIDE BRANCH
POWER TO THE ADDITIONAL POWER SUPPLIES. COORDINATE THE LOCATION OF
ADDITIONAL POWER SUPPLY CABINET WITH THE ELECTRICAL CONTRACTOR.
15. ELEMENT LENGTHS FOR BOTH MIXED AIR TEMP SENSORS AND LOW LIMIT TEMP SWITCHES
SHALL BE MINIMUM 1 LINEAR FOOT PER SQUARE FOOT OF COIL SURFACE AREA. PROVIDE
MULTIPLE SENSORS AND SWITCHES AS NEEDED TO ACHIEVE REQUIRED ELEMENT
LENGTHS. LOCATE RESET SWITCHES MAX. 6'-6" ABOVE ADJACENT STANDING SURFACE (E.G.
ROOF, PLATFORM OR FLOOR) SO THE RESET SWITCH CAN BE CYCLED WITHOUT THE NEED
FOR A LADDER.
16. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL REQUIRED
CONTROL DEVICES AND COMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMS AND
DETAILS FOR ADDITIONAL CONTROL DEVICES, COMPONENTS AND REQUIREMENTS NOT
SHOWN ON THESE CONTROL DRAWINGS.
17. TCC SHALL PROVIDE ALL CONTROL COMPONENTS AND ACCESSORIES AS REQUIRED FOR
EQUIPMENT TO BE CONTROLLED AS DESCRIBED IN THE SEQUENCE OF OPERATION
REGARDLESS OF WHETHER ALL CONTROL COMPONENTS OR POINTS ARE SHOWN IN THE
ASSOCIATED CONTROL DIAGRAM.
TEMPERATURE CONTROL GENERAL NOTES:
I O W A
S E
D
PROFESS IO NA
20825
L
IC
E N
L E
N G
I N E
E R
ERIC J.
HENDERSON
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T .0
V
A -V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th
-E P
C
D e lla n .J
.L le w e lly n .r v t
/8
/2
:2 :2
P
M
1-MT1
SECOND FLOOR PLAN -
TEMPERATURE CONTROLS
REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 DAVING DELLLE16133
N O R
HT
1/8" = 1'-0"
SECOND FLOOR - TEMPERATURE CONTROLS
Revisions: Date:
AIAI
AI
AODI
DO
DI
AOAI
AOAI
AO AI
AI
AI
DI DI
DO
AI
AIAO
DODI
AODI
DO
DI
DI
AI AI
DI
AI
AI
AI
AI
DI
DI
DI
AO AI
TH
FM
VFD
F M
T T T
FM
H
VFD
H T
H
T
AOAI
LL TEMP
SWITCH#1
SP
RETURN
AIR
DUCT MOUNTED
TEMPERATURE &
HUMIDITY
SENSORS
RETURN DUCT
MOUNTED LOW
STATIC SWITCH
RETURN
AIRFLOW
RETURN
FAN
COMMUNICATION LINK
BETWEEN VFD GATEWAY &
FMCS (TYPICAL EACH VFD)
MODALRM
START/
STOP
CS
FAN
STATUS
ACT
N.C.
DMPR
MOD.
DMPR
FDBK
TO ADDITIONAL RETURN
FANS. VERIFY QUANTITY OF
FANS AND VFDS WITH
SCHEDULE.
RELIEF
AIR
RELIEF
AIR
DAMPER
ACT
ACT
OUTSIDE
AIRFLOW
N.C.
O.A.
DMPR
MOD.
DMPR
FDBK
SP
MIXED AIR
LOW STATIC
SWITCH
DMPR
FDBK
DMPR
MOD.
DP DP
FILTER
STATUS
FILTER
STATUS
IFB STEAM
COIL
VALV
MOD.
STM
LL TEMP
SWITCH#2
SP
RETURN
AIR
DAMPER
N.O.
OUTSIDE
AIR
DAMPER
M.A.
TEMP
PRE-
FILTER
(30%)
PRE-
FILTER
(60%)
STEAM
SUPPLY
VALV
FDBK
OPEN/
CLOSE
MOD
VALV
FDBK
CWR
CWS
DIFF. PRESS.
SWITCH (0-1" W.G.
SCALE) (TYP.2)
ISOLATION STEAM
VALVE
N.C.
N.C.
TO ADDITIONAL SUPPLY FANS.
VERIFY QUANTITY OF FANS
AND VFDS WITH SCHEDULE.
COOLING
COIL
MOUNT FLOWMETER DISPLAY
WITHIN SERVICE VESTIBULE
OF EACH RTU OR ON
EXTERIOR OF AHU FOR
INDOOR UNITS. (TYP.)
MODALRM
CS
FAN
STATUS
DP
FINAL FILTER
STATUS
HIGH STATIC
SWITCH
DUCT MOUNTED
TEMPERATURE &
HUMIDITY
SENSORS
MOUNT IN
DISCHARGE
PLENUM OF AHU.
DUCT
MOUNTED
HUMIDITY
SWITCH
SP
SUPPLY
AIR
STATIC
PRESS.
TRANS.
LOCATE DUCT DIFFERENTIAL
STATIC PRESSURE SENSOR NEAR
MOST REMOTE TERMINAL AIR BOX.
AHU REPORT GENERATION:
DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND. THE TREND SHALL RUN FOR A 100-DAY (ADJ.) DURATION AT WHICH POINT THE
NEWEST VALUES SHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:
• DATE
• TIME
• GLOBAL OUTSIDE AIR TEMP [°F]
• GLOBAL OUTSIDE AIR DEWPOINT [°F]
• GLOBAL OUTSIDE AIR HUMIDITY [%RH]
• SUPPLY AIRFLOW [CFM]
• SUPPLY AIR TEMP (SAT) [°F]
• SUPPLY AIR TEMP SETPOINT [°F]
• SUPPLY AIR RELATIVE HUMIDITY [%]
• SUPPLY AIR DEWPOINT [°F]
• SUPPLY AIR DEWPOINT SETPOINT [°F]
• RETURN AIRFLOW [CFM]
• RETURN AIR TEMP (RAT) [°F]
• RETURN AIR RELATIVE HUMIDITY [%]
• OUTSIDE AIRFLOW [CFM]
• MIXED AIR TEMP [°F]
• PREHEAT COIL DISCHARGE AIR TEMP [°F]
• PREHEAT COIL DISCHARGE AIR TEMP [°F]
• PRE-FILTER ALARM (30% FILTER) [STATUS] [* PRE-FILTER LOADING [STATUS]]
• PRE-FILTER ALARM (60% FILTER) [STATUS] [* PRE-FILTER LOADING [STATUS]]
• FINAL FILTER ALARM [STATUS] [* FINAL FILTER LOADING [STATUS]]
• HEATING WATER VALVE POSITION [% OPEN]
• HEATING PUMP [ON/OFF]
• CHILLED WATER VALVE POSITION [% OPEN]
• HUMIDIFIER VALVE POSITION [% OPEN]
• HUMIDIFIER ISOLATION VALVE [OPEN/CLOSED]
• SUPPLY DUCT STATIC PRESSURE SETPOINT [INCHES W.G.]
• SUPPLY DUCT STATIC PRESSURE [INCHES W.G.]
• SUPPLY FAN VFD OUTPUT [% FULL SPEED]
• RETURN FAN VFD OUTPUT [% FULL SPEED]
• OUTSIDE AIR DAMPER POSITION [% OPEN]
• RETURN AIR DAMPER POSITION [% OPEN]
• RELIEF AIR DAMPER POSITION [% OPEN]
THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN GRAPHICAL FORM ON THE FMCS
OPERATOR WORKSTATION.
ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST AHU AIRFLOW WHICH
OCCURRED DURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER
VALUES LISTED ABOVE) THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS
INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE FMCS OPERATOR
WORKSTATION THAT IS MAINTAINED (NOT AUTOMATICALLY OVERWRITTEN).
AIR HANDLER REPORT GENERATION
SEQUENCE OF OPERATION:
WHEN AHU/RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:
• SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL OPEN.
• AFTER A 30 SECOND DELAY (ADJ.) TO ALLOW FOR OPENING OF SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS. SUPPLY FAN SHALL BE ENABLED TO RUN.
• WHEN THE SUPPLY FAN HAS STARTED THE RETURN FAN AND INTERLOCKED EXHAUST FANS SHALL START AS SHOWN IN THE FAN INTERLOCK SCHEDULE.
SUPPLY FAN OPERATION:
FMCS SHALL MODULATE SIGNAL TO SUPPLY FAN VFD TO MAINTAIN DUCT STATIC PRESSURE AS MEASURED BY STATIC PRESSURE TRANSMITTER NEAR THE END OF THE CRITICAL DUCT
BRANCH.
RETURN FAN OPERATION:
RETURN FAN SHALL BE INDEXED TO RUN WHENEVER THE SUPPLY FAN IS INDEXED TO RUN. FMCS SHALL MODULATE SIGNAL TO RETURN FAN VFD AS REQUIRED TO MAINTAIN THE AIRFLOW
OFFSET AS INDICATED IN THE RETURN FAN AIRFLOW SCHEDULE.
STATIC PRESSURE RESET:
FMCS SHALL RESET SUPPLY DUCT STATIC PRESSURE SETPOINT BELOW THE MAXIMUM SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 90% (ADJ.) OPEN. FMCS SHALL MONITOR ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
DISCHARGE AIR TEMPERATURE SET POINT:
DISCHARGE AIR SET POINT SHALL BE 49ºF (ADJ.).
DISCHARGE AIR TEMPERATURE RESET:
RESET DISCHARGE AIR TEMPERATURE BASED ON THE ZONE WITH THE GREATEST CALL FOR COOLING. RESET THE TEMPERATURE AS FOLLOWS:
• WHEN WORST CASE TAB IS LESS THAN 90% (ADJ.) OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL INCREASE BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL
AHU MAXIMUM DISCHARGE AIR TEMPERATURE OF 60ºF (ADJ.) IS ACHIEVED.
• WHEN WORST CASE TAB IS MORE THAN 90% OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL DROP BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU
MINIMUM DISCHARGE AIR TEMPERATURE OF 55ºF (ADJ.) IS ACHIEVED.
• THE MAXIMUM ALLOWABLE RETURN AIR HUMIDITY SETPOINT SHALL BE 60% (ADJ.). IF RETURN AIR HUMIDITY IS GREATER THAN SETPOINT, RESET DISCHARGE AIR TEMPERATURE TO 55°F
UNTIL RETURN AIR HUMIDITY IS 5% LESS THAN MAXIMUM SETPOINT FOR 10 MINUTES (ADJ.).
STATIC PRESSURE AND DISCHARGE AIR TEMPERATURE RESET PRIORITY:
RESET THE DISCHARGE AIR TEMPERATURE PRIOR TO RESETTING THE DUCTWORK STATIC PRESSURE SETPOINT. ONCE THE MAXIMUM SUPPLY TEMPERATURE IS REACHED THEN THE SYSTEM
SHALL ENABLE THE STATIC PRESSURE RESET.
VENTILATION AIR CONTROL:
WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE MINIMUM OUTSIDE AIR FLOW RATE, OR TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE.
COOLING COIL OPERATION:
WHEN IN MINIMUM OUTSIDE AIR MODE, FMCS SHALL MODULATE CHILLED WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
WHEN IN ECONOMIZER MODE, FMCS SHALL NOT MODULATE COOLING CONTROL VALVE UNLESS RETURN AIR DAMPER IS 5% (ADJ.) OPEN AND RELIEF AIR DAMPER IS 95% (ADJ.) OPEN.
PREHEAT COIL OPERATION:
PREHEAT COIL CONTROLS SHALL BE ENABLED WHEN OUTSIDE AIR TEMP DROPS BELOW 50°F (ADJ.). PREHEAT COIL CONTROLS SHALL BE DISABLED WHEN OUTSIDE AIR TEMP RISES ABOVE 54°
F (ADJ.).
WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 38°F (ADJ.) FOR 10 MINUTES (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE ONLY WHEN HEATING IS CALLED FOR (HEATING WATER VALVE IS COMMANDED TO OPEN). WHEN OUTSIDE AIR TEMP DROPS BELOW 38°F (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE CONTINUOUSLY. ONCE ENERGIZED, HEATING WATER COIL CIRCULATION PUMP SHALL REMAIN IN OPERATION FOR MINIMUM 5 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.
FMCS SHALL MODULATE HEATING WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
ECONOMIZER OPERATION:
WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULB TEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDE AIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.)
BEFORE BEING ALLOWED TO SWITCH BACK (TO PREVENT SHORT CYCLING).
IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.
HUMIDIFIER CONTROLS:
HUMIDIFIER CONTROLS AND ALARMS SHALL BE ENABLED WHEN OUTSIDE AIR TEMPERATURE DROPS BELOW 48°F (ADJ.) AT WHICH POINT THE ISOLATION STEAM VALVE SHALL FULLY OPEN.
HUMIDIFIER CONTROLS AND ALARMS SHALL BE DISABLED WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 48°F (ADJ.) FOR 10 MINUTES (ADJ.) AT WHICH POINT THE ISOLATION STEAM VALVE
SHALL FULLY CLOSE.
WHEN HUMIDIFIER CONTROLS ARE ENABLED, FMCS CONTROLLER SHALL MODULATE STEAM VALVE AS REQUIRED TO MAINTAIN 43°F DEWPOINT (ADJ.) IN THE SUPPLY AIR DUCT. DUCT MOUNTED HUMIDITY TRANSMITTER AT FAN DISCHARGE SHALL PREVENT SUPPLY AIR RELATIVE HUMIDITY FROM EXCEEDING 80% (ADJ.).
A
B
C
D
E
F
R
A
B
C
D
E
F
AUX CONTACT TO
FMCS TO INITIATE
CONTROL
TERMINAL
STRIP SPEED
CONTROL
SIGNALRETURN FAN
VFD SECTION
SPEED
CONTROL
SIGNALSUPPLY FAN
VFD SECTION
TERMINAL
STRIP
AUX CONTACT TO
FMCS TO INITIATE
CONTROL
SAFETY
CIRCUITS
NH
D U
C T
H
IG
H S
T A
T
IC
D U
C T
L O
W S
T A
T
IC
L O
W L
IM
IT
T E
M P
S W
IT
C
H
SUPPLY & RETURN FAN VFD CONTROL
RETURN FAN AIRFLOW SCHEDULE
SYSTEM SUPPLY CFM EXHAUST FANS PRESSURIZATION
CFM
REMARKS
AH1-31 15,000 EF1-47 0 NOTES 1,2,3
FAN INTERLOCK SCHEDULE
SYSTEM INTERLOCKED EXHAUST FANS REMARKS
AH1-31 EF1-47 NOTE 1
CWR
TEMP
CWS
TEMP
P.H.
TEMP
NOTES:
1. RETURN FAN AIRFLOW SETPOINT SHALL BE THE SUPPLY FAN AIRFLOW (AS MEASURED BY THE
AFMS) MINUS THE SUM OF THE EXHAUST FAN AIRFLOWS MINUS THE PRESSURIZATION CFM.
2. FMCS SHALL DETERMINE THE OPERATIONAL STATUS OF EACH EXHAUST FAN VIA THE
CURRENT SENSING RELAY TO DETERMINE WHETHER THE CFM ASSOCIATED WITH THAT FAN
SHOULD BE INCLUDED IN THE RETURN FAN AIRFLOW CALCULATION.
3. EXHAUST FAN AIRFLOWS SHALL NOT BE THE CFM INDICATED ON THE FAN SCHEDULE, BUT
SHALL BE THE AIRFLOW INDICATED IN THE FINAL TAB REPORT.
NOTES:
1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE
AHU IN ACCORDANCE WITH AHU SEQUENCE OF OPERATION.
CONNECT FIRE ALARM TO AHU START/STOP CIRCUIT SO FIRE ALARM CAN SHUT
DOWN AND SO AHU CAN AUTOMATICALLY RESTART AFTER A FIRE ALARM TEST
FIRE ALARM SYSTEM
VALV
MOD
VALV
FDBK
N.C.
ACT
DMPR
MOD.
VALV
FDBK
ALARMS, INTERLOCKS, AND SAFETIES:
WHEN FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, AHU SHALL BE SHUTDOWN.
THE FOLLOWING CONDITIONS SHALL SHUTDOWN THE AHU AND SHALL INDICATE AN ALARM CONDITION AT THE FMCS WORKSTATION:
• LOW STATIC PRESSURE SWITCH INDICATES RETURN DUCT PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS.
• LOW STATIC PRESSURE SWITCH INDICATES MIXED AIR PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS OF THE OUTSIDE AIR DUCTWORK.
• HIGH STATIC PRESSURE SWITCH INDICATES SUPPLY DUCT STATIC PRESSURE GREATER THAN THE SPECIFIED DUCT PRESSURE CLASS.
• SHOULD ANY ONE FOOT SECTION OF THE MANUAL RESET LOW LIMIT TEMPERATURE SWITCH #1 SENSE AIR TEMP <34°F (ADJ.). IF MULTIPLE FREEZE STATS ARE REQUIRED, WIRE ALL TO A
COMMON RESET SWITCH.
THE FOLLOWING CONDITIONS SHALL INDICATE AN ALARM AT THE FMCS, HOWEVER AHU SHALL CONTINUE TO OPERATE:
• HEATING COIL CIRCULATION PUMP IS COMMANDED TO RUN AND CURRENT RELAY INDICATES INSUFFICIENT CURRENT FLOW.
• AN ALARM IS INDICATED AT ANY SUPPLY FAN VFD OR RETURN FAN VFD.
• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (30%) BANK EXCEEDS 0.6 INCHES W.G. (ADJ.)
• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (60%) BANK EXCEEDS 0.8 INCHES W.G. (ADJ.)
• DIFFERENTIAL PRESSURE SWITCH ACROSS FINAL FILTER BANK EXCEEDS 1.0 INCHES W.G. (ADJ.)
• THE TOTAL DIFFERENTIAL PRESSURE ACROSS ALL FILTER BANKS EXCEEDS 2.0 INCHES W.G. (ADJ.)
• RELATIVE HUMIDITY OF SUPPLY AIR EXCEEDS 80% RH (ADJ.) AS MEASURED BY AUTOMATIC RESET HUMIDITY SWITCH. WHEN HUMIDITY SWITCH TRIPS, STEAM CONTROL VALVE SHALL
FULLY CLOSE UNTIL ALARM IS RESET AT FMCS WORKSTATION. AN ALARM SHALL NOT INDICATE AT THE FMCS WORKSTATION UNLESS HUMIDIFIER CONTROLS ARE ENABLED.
• WHEN DUCTWORK SUPPLY AIR HUMIDITY EXCEEDS 90% RH A SEPARATE DUCT MOUNTED HUMIDITY SWITCH (MANUAL RESET) SHALL DISABLE HUMIDIFIER CONTROLS AND SHALL FULLY
CLOSE STEAM ISOLATION VALVE. AN IDENTIFIABLE ALARM CONDITION SHALL BE DISPLAYED AT THE OPERATOR WORKSTATION.
• SHOULD ANY ONE FOOT SECTION OF THE AUTO RESET LOW LIMIT TEMPERATURE SWITCH #2 SENSE AIR TEMPERATURE <38°F (ADJ.) THE FOLLOWING SHALL OCCUR:
• THE RETURN AIR DAMPER SHALL FULLY OPEN.
• THE OUTSIDE AIR AND RELIEF DAMPERS SHALL FULLY CLOSE.
• THIS ACTION SHALL OCCUR INDEPENDENT OF THE FMCS AHU CONTROLLER. ONCE THE LOW LIMIT TEMPERATURE SWITCH #2 AIR TEMPERATURE RISES ABOVE SET POINT, OPERATION OF
THE OUTSIDE AIR, RELIEF AIR, AND RETURN AIR DAMPERS SHALL BE RESTORED. HOWEVER, THE ALARM SHALL CONTINUE UNTIL ACKNOWLEDGED AND MANUALLY RESET BY THE FMCS
OPERATOR.
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT.
IN THE EVENT SUPPLY FAN IS NOT RUNNING (AS INDICATED BY THE CURRENT SENSING RELAYS) RETURN AIR FAN SHALL BE DE-ENERGIZED.
WHENEVER AHU/RTU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:
• THE OUTSIDE AIR DAMPER AND RELIEF AIR DAMPER SHALL FULLY CLOSE.
• RETURN AIR DAMPER SHALL FULLY OPEN.
• PREHEAT COIL HEATING WATER CIRCULATION PUMP AND HEATING WATER CONTROL VALVE SHALL REMAIN UNDER CONTROL OF ITS INPUT SENSOR.
• ALL SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS SHALL FULLY CLOSE.
• CHILLED WATER CONTROL VALVE SHALL FULLY CLOSE.
• ISOLATION STEAM VALVE SHALL FULLY CLOSE.
• SUPPLY FAN AND RETURN FAN VFDS SHALL BE DE-ENERGIZED.
• INTERLOCKED EXHAUST FANS SHALL BE DE-ENERGIZED.
UNOCCUPIED MODE:
PROVIDE TIME OF DAY SCHEDULE TO ALLOW AHU TO ENTER UNOCCUPIED MODE PER SCHEDULE. COORDINATE SCHEDULE WITH OWNER.
• THE SUPPLY AND RETURN FANS SHALL CONTINUE RUNNING. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND THE SUPPLY
FAN SHALL BE LIMITED TO THE MAXIMUM RETURN FAN AIRFLOW.
• THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.
• ALL SPACE TEMPERATURES SHALL BE ALLOWED TO VARY +/- 10°F (ADJ.) FROM OCCUPIED SETPOINT.
HEATING OPTIMUM START-UP:
• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC
SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO WARM THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 68ºF
(ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
COOLING OPTIMUM START-UP:
• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC
SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO COOL THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES ARE LESS THAN A SETPOINT OF
75ºF (ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
GRAPHICAL DISPLAY:
DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON AHU GRAPHIC PAGE.
FINAL
FILTER
I O W A
S E
D
PROFESS IO NA
20825
L
IC
E N
L E
N G
I N E
E R
ERIC J.
HENDERSON
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T .0
V
A -V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th
-E P
C
D e lla n .J
.L le w e lly n .r v t
/8
/2
:2 :2
P
M
1-MT2
AHU CONTROL DIAGRAM REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 DAVING DELLLE16133
NO SCALE
AIR HANDLING UNIT CONTROL - AH1-31
DO
DI
AI
AIAO
AI
AO
AO
AI
AIDIDI DI
AI AI
AIDI
DI
TH
H
FS
T H
AI
AIAO
AI
AO
AI
T
T
AO
AI
FAN
STATUS
CS
START/
STOP
EXHAUST
AIR
ACT
SEQUENCE OF OPERATION:
EXHAUST FAN SHALL BE INTERLOCKED TO RUN CONTINUOUSLY WHEN
RESPECTIVE AHU IS OPERATING.
2-POSITION DAMPER SHALL FULLY OPEN WHEN FAN IS ENERGIZED. WHEN FAN
IS DE-ENERGIZED, 2-POSITION DAMPER SHALL FULLY CLOSE.
ALARMS, INTERLOCKS AND SAFETIES:
AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN
THE EVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE
CURRENT SENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.
WALL
MOUNTED
OCCUPANCY
SENSOR
PRIMARY AIR FROM ZONE
CONDITIONING AHU
SUPPLY
AIR
ACTVELOCITY AND
STATIC SENSOR
PRESSURE INDEPENDENT
TERMINAL AIR BOX (TAB)
DAMPER ACTUATOR DAMPER
MOD.
TAB
AIRFLOW
HWS
HWR
FLOATING 2-WAY CONTROL VALVE
(REFER TO FLOOR
PLANS FOR WHERE 3-
WAY VALVES ARE REQ'D)
FAIL IN
PLACE
ACTVELOCITY AND
STATIC SENSOR
PRESSURE INDEPENDENT
TERMINAL AIR BOX (TAB)
DAMPER ACTUATOR
DAMPER
MOD.
TAB
AIRFLOW
ROOM
RETURN AIR
RETURN
AIR
DIFFERENTIAL PRESSURE
MONITOR PROVIDE ONE PER
ROOM & MOUNT AT
LOCATIONS SHOWN ON
PLANS
DIFF.
PRESS.
ALARM
STATUS
MD MD
WALL MOUNTED
MOTION
DETECTORS
WALL MTD
TEMP SENSOR
WALL MTD
HUMIDITY
SENSOR
NOTE: WALL MOUNTED TEMPERATURE &
HUMIDITY SENSORS SHALL HAVE THE
FOLLOWING FEATURES:
· LOCAL TEMPERATURE & HUMIDITY
ADJUSTMENT
· DIGITAL DISPLAY OF ROOM
TEMPERATURE & HUMIDITY
SETPOINTS
DUCT MTD TEMP
& HUMIDITY
SENSORS
DUCT
MTD
HUMIDITY
SWITCH
AIRFLOW
SWITCH
DS
DOOR POSITION
SWITCH
SEQUENCE OF OPERATION:
WHEN ANY ROOM OCCUPANCY SENSOR DETECTS MOTION FMCS SHALL ENABLE OCCUPIED MODE AND THE FOLLOWING SHALL OCCUR:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB HW REHEAT COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE SETPOINT WITH 2°F (ADJ.)
DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTED TEMPERATURE SENSOR.
• PRIMARY SUPPLY TAB SHALL SUPPLY MAX. SCHEDULED AIRFLOW PER TAB SCHEDULE
• LOCAL TEMP SETPOINT ADJUSTMENT SHALL BE ENABLED ALLOWING TEMP SETTINGS 60°F - 80°F (ADJ.).
• SECONDARY SUPPLY TAB DAMPER SHALL REMAIN FULLY CLOSED.
• FMCS SHALL MODULATE RETURN TAB DAMPERS AS REQUIRED TO MAINTAIN THE ROOM AT MIN. +0.010 INCHES W.G. RELATIVE TO ADJACENT CORRIDOR.
• FMCS SHALL MODULATE REHEAT COIL HW CONTROL VALVE AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT (68°F).
IN THE EVENT REHEAT COIL HW CONTROL VALVE IS FULLY CLOSED AND ADDITIONAL COOLING IS REQUIRED, FMCS SHALL MODULATE THE SECONDARY SUPPLY TAB DAMPER AS
REQUIRED TO MAINTAIN SPACE TEMP SETPOINT.
WHEN BOTH ROOM OCCUPANCY SENSORS DO NOT DETECT MOTION FOR 15 MINUTES (ADJ.), FMCS SHALL ENABLE UNOCCUPIED MODE AND THE FOLLOWING SHALL OCCUR:
• PRIMARY SUPPLY TAB SHALL SUPPLY MIN. SCHEDULED AIRFLOW PER TAB SCHEDULE.
• PRIMARY SUPPLY TAB DAMPER SHALL MODULATE OPEN TO MAINTAIN ROOM SETPOINT.
• LOCAL TEMP SETPOINT ADJUSTMENT SHALL BE DISABLED AND ROOM TEMP SETPOINT SHALL BE 68°F (ADJ.).
• SECONDARY SUPPLY TAB DAMPER SHALL FULLY CLOSE.
• FMCS SHALL MODULATE RETURN TAB DAMPERS AS REQUIRED TO MAINTAIN THE ROOM AT MIN. +0.010 INCHES W.G. RELATIVE TO ADJACENT CORRIDOR.
• FMCS SHALL MODULATE REHEAT COIL HW CONTROL VALVE (WITH TAB DAMPER IN MINIMUM POSITION) AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT.
SEQUENCING OF SUPPLY AND RETURN TAB DAMPERS SHALL MAINTAIN A POSITIVE PRESSURE WITHIN THE ROOM AT ALL TIMES WHEN TRANSITIONING BETWEEN OCCUPIED AND
UNOCCUPIED MODES AND VICE VERSA.
FMCS SHALL RE-ZERO ALL DAMPER AND VALVE ACTUATOR POSITIONS WHEN BOTH CONDITIONS ARE MET:
• 120 HOURS (ADJ.) HAS PASSED SINCE THE LAST RE-ZEROING.
• THE ROOM IS IN UNOCCUPIED MODE.
FMCS SHALL MONITOR ROOM DIFFERENTIAL PRESSURE AND SHALL DISPLAY THE VALUE ON THE TAB GRAPHICAL SCREEN AT THE OPERATOR WORKSTATION.
THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITION TO RESET THE SUPPLY AND RETURN DUCT DIFFERENTIAL STATIC PRESSURE.
HUMIDIFIER OPERATION:
FMCS SHALL ENABLE HUMIDIFIER CONTROLS WHEN OA DEWPOINT DROPS BELOW 38°F (ADJ.) AND SHALL FULLY OPEN STEAM ISOLATION VALVE. FMCS SHALL MODULATE HUMIDIFIER STEAM VALVE AS REQUIRED TO MAINTAIN ROOM HUMIDITY SETPOINT (40% RH, ADJ.). FMCS SHALL LIMIT STEAM VALVE OPERATION TO PREVENT DUCT MOUNTED HUMIDITY LEVELS FROM EXCEEDING 70% RH (ADJ.) AT DUCT MOUNTED HUMIDITY TRANSMITTER.
HUMIDIFIER STEAM VALVE SHALL NOT BE ENABLED UNLESS AIRFLOW IN SUPPLY DUCT IS PROVEN BY AN AIRFLOW SWITCH.
FMCS SHALL DISABLE HUMIDIFIER CONTROLS AND ALARMS WHEN OA DEWPOINT RISES ABOVE 40°F (ADJ.) AND SHALL FULLY CLOSE STEAM ISOLATION VALVE.
SMOKE EVACUATION MODE:
ELECTRICAL CONTRACTOR SHALL INSTALL SMOKE DETECTOR. UPON DETECTION OF SMOKE, THE OPERATING ROOM SHALL ENTER PURGE MODE
• THE COOLING ONLY TAB SHALL CLOSE. IN EACH OR ROOM CONNECTED TO THE AHU IN PURGE MODE. (DOES NOT APPLY TO TREATMENT)
• THE REHEAT TAB SHALL BE OPEN IF ROOM IS OCCUPIED OR CLOSED IF ROOM IS UNOCCUPIED.
• THE RETURN TAB SHALL MODULATE TO MAXIMUM CFM.
• THE AIR HANDLING UNIT SHALL ENTER 100% OA.
• OCCUPIED LOCAL SETPOINT ADJUSTMENT SHALL BE 70°F - 80°F (ADJ.)
• ALL OTHER ROOMS SHALL REMAIN IN NORMAL OPERATION.
ALARMS, INTERLOCKS & SAFETIES:
AN ALARM SHALL BE INDICATED AT THE OPERATING WORKSTATION IN THE EVENT ANY OF THE FOLLOWING OCCUR:
• WHEN SUPPLY AIR HUMIDITY EXCEEDS 80% RH A SEPARATE DUCT MOUNTED HUMIDITY SWITCH (MANUAL RESET) SHALL DISABLE HUMIDIFIER CONTROLS AND SHALL FULLY
CLOSE STEAM ISOLATION VALVE. AN IDENTIFIABLE ALARM CONDITION SHALL BE DISPLAYED AT THE OPERATOR WORKSTATION.
• ROOM POSITIVE PRESSURE (RELATIVE TO ADJACENT CORRIDOR) DROPS BELOW 0.01 INCHES W.G. (ADJ.) FOR MORE THAN 45 SECONDS (ADJ.) AS MEASURED BY ROOM
DIFFERENTIAL PRESSURE MONITOR (AUTO RESET).
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.
WALL MTD
TEMP SENSOR
HWS
HWR
PRIMARY AIR FROM ZONE
CONDITIONING AHU
SUPPLY
AIR
ACTVELOCITY AND
STATIC SENSOR
PRESSURE INDEPENDENT
TERMINAL AIR BOX (TAB)
FAIL IN
PLACE
DAMPER ACTUATORDAMPER
MOD.
TAB
AIRFLOW
2-WAY CONTROL VALVE
(REFER TO FLOOR
PLANS FOR WHERE 3-
WAY VALVES ARE REQ'D)
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB HW
REHEAT COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F
(ADJ.) WITH 5°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTED
TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR
REQUIREMENTS. SPACES WITH ADJUSTABLE THERMOSTATS WILL ALLOW A +/- 3°
F (ADJ.) OFFSET FROM THE DDC SETPOINT.
• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THE
REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED
UNTIL SPACE SETPOINT IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUM
SCHEDULED CFM POSITION PER THE TAB SCHEDULE. THE REHEAT COIL
CONTROL VALVE SHALL BE CLOSED.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE REHEAT COIL CONTROL
VALVE SHALL MODULATE OPEN TO MAINTAIN SPACE SETPOINT UNTIL THE
SUPPLY AIR TEMPERATURE IS 20°F ABOVE ROOM TEMPERATURE SETPOINT.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, TAB SHALL OPEN TO MAINTAIN
SETPOINT UNTIL TAB AIRFLOW REACHES ITS MAXIMUM HEATING SETTING. THE
REHEAT CONTROL VALVE SHALL CONTINUE TO MODULATE OPEN TO MAINTAIN
MAXIMUM DELTA T LISTED ABOVE.
• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TO
RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
• WHEN FLOATING CV'S ARE USED, FMCS SHALL PERFORM AN AUTO-ZERO
FUNCTION EVERY NIGHT DURING UNOCCUPIED TIMES. THE FMCS SHALL
STAGGER AUTO-ZERO SEQUENCES SO THAT ALL VALVES DO NOT
SIMULTANEOUSLY CLOSE.
ALARMS, INTERLOCKS & SAFETIES:
SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE
IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.
SUPPLY AIR TEMP
LOCATE TEMPERATURE SENSOR 4'-0"
DOWNSTREAM OF COIL IN THE
CENTER OF DUCT
MOD
VLV
FDBK
RETURN AIR
FROM SPACE
ACTVELOCITY AND
STATIC SENSOR
PRESSURE INDEPENDENT
TERMINAL AIR BOX (TAB)
DAMPER ACTUATORDAMPER
MOD.
TAB
AIRFLOW
RETURN AIR
TO AHU
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER TO
CFM OFFSET FROM ASSOCIATED SUPPLY AIR TAB.
• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX
POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC
PRESSURE.
I O W A
S E
D
PROFESS IO NA
20825
L
IC
E N
L E
N G
I N E
E R
ERIC J.
HENDERSON
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T .0
V
A -V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th
-E P
C
D e lla n .J
.L le w e lly n .r v t
/8
/2
:2 :2
P
M
1-MT3
CONTROL DIAGRAMS REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 DAVING DELLLE16133
NO SCALE
EXHAUST FAN CONTROL - AHU INTERLOCK - EF1-47
NO SCALE
TAB OPERATING ROOM CONTROL - TYPE C
NO SCALE
TAB CONTROL W/ HOT WATER REHEAT - TYPE A
NO SCALE
TAB CONTROL RETURN - TYPE B
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UNO UNLESS NOTED OTHERWISE
GFI GROUND FAULT INTERRUPTER
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS
SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.
WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING
THE NORMAL BRANCH.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM
FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND
OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO
7. CONNECTION FOR ELECTRIC WATER COOLERS (EWC) SHALL BE A JUNCTION BOX
CONCEALED BEHIND WATER COOLER ACCESS PLATE OR BE A GFI RECEPTACLE LOCATED
DIRECTLY BELOW AND CENTERED ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
8. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
9. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL
BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
11. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
12. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
14. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF ANY
WELDERS ASSIGNED TO THE JOB.
15. GENERAL CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED
FOR THE EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES
WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
16. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
17. ELECTRICAL IDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FOR COLOR/LABEL
REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
NORMAL BRANCH LUMINAIRE
CRITICAL BRANCH LUMINAIRE
EMERGENCY LIFE SAFETY BRANCH LUMINAIRE
[UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE']
LUMINAIRE SYMBOL KEY
SYMBOL: DESCRIPTION:
DP-# DISTRIBUTION PANEL 26 24 16
26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE
R-# RELAY 26 09 39
C-# GENERAL PURPOSE CONTACTOR 26 28 21
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:
RELATED
SPECIFICATION
FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
V1 V3
V7 VH
FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE - WALL MOUNTED
A1 A3
A7 AH
AS
FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
V1 V3
V7 VH
FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION
DEVICE - CEILING MOUNTED
A1 A3
A7 AH
SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING
MOUNTED
SD FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR
SD FA-123 28 31 00 FIRE ALARM IN DUCT SMOKE DETECTOR
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR H
FA-131 28 31 00 FIRE ALARM MANUAL PULL STATION W/ COVERFT
FA-161 28 31 00 FIRE ALARM RELAYAR
FA-160 28 31 00 FIRE ALARM ADDRESSABLE MONITOR MODULEMM
FA-270 28 31 00 FIRE ALARM ELECTROMAGNETIC DOOR
HOLD DEVICE
DH
FA-241 28 31 00 FIRE ALARM REMOTE INDICATORRI
FA-242 28 31 00 FIRE ALARM REMOTE INDICATOR
AND TEST SWITCH
RTS/I
PP ARCH PUSH PADPP
VS
VS
SW-1P 26 09 33 SWITCH - SINGLE POLE
SW-3W 26 09 33 SWITCH - THREE WAY3
SW-4W 26 09 33 SWITCH - FOUR WAY4
SW-OC-P-O SWITCH - OCCUPANCY SENSOR
WALL SWITCH
O
OCCUPANCY SENSOR - PASSIVE INFRARED
100 DEGREE COVERAGE - WALL MOUNT
OCCUPANCY SENSOR - ULTRASONIC 360
DEGREE COVERAGE - WALL MOUNT
OCCUPANCY SENSOR - DUAL
TECHNOLOGY - WALL MOUNTED
ETD ALCR20 UL924 TRANSFER RELAY - LIGHTING
26 09 33
26 09 33
CB-# 26 28 16 CIRCUIT BREAKER - SURFACE MOUNTED.
REFER TO DISC/STA SCHEDULE
CB-# 26 28 16 CIRCUIT BREAKER - FLUSH MOUNTED.
REFER TO DISC/STA SCHEDULE
DS-#/FDS-#/DSS-# 26 28 16 DISCONNECT. REFER TO DISC/STA SCHEDULE
AS
SW-D-LED DIMMER - LED
D
26 09 33
SW-D3-LED DIMMER - LED - 3-WAY
D3
26 09 33
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:FB-# or PT-# 26 27 26 FLOOR BOX or POKE THROUGH
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
WW-# 26 05 35 ELECTRICAL WIREWAY w/ DEVICES SHOWN
WM-# 26 05 35 MULTI OUTLET SYSTEM
PANEL '###' 26 24 16 PANELBOARD - SURFACE MOUNT
PANEL '###' 26 24 16 PANELBOARD - RECESS MOUNT
ISO-# 26 24 21 ISOLATED POWER PANEL
GB 26 05 26 GROUND BUSGB
IBT 26 05 26 INTERSYSTEM BONDING TERMINATIONIBT
EPO 26 09 16 EMERGENCY STOP, N.O. CONTACTEPO
MX-#/MS-#
/CB-#/CS-#
26 24 19 MANUAL SWITCH / STARTER / COMBINATION
STARTER/ CIRCUIT BREAKER. REFER TO
DISC/STA SCHEDULE
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
TR-#/DTR-# 26 22 00 TRANSFORMER. REFER TO
TRANSFORMER SCHEDULE
FA-280 28 31 00 ISOLATION MODULEIM
26 32 13
LINEAR LUMINAIRES
TROFFER
DOWNLIGHT LUMINAIRE
INDUSTRIAL LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
REC-DUP-GFI-R 26 27 26 GROUND FAULT DEVICEG
REC-TAMP 26 27 26 DUPLEX RECEPTACLE, TAMPER RESISTANT, 125V
REC-TAMP-GFI 26 27 26 GFI DUPLEX RECEPTACLE,
TAMPER RESISTANT, 125V
REC-TAMP-QUAD 26 27 26 QUAD RECEPTACLE, TAMPER RESISTANT, 125V
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
REC-QUAD-GFI 26 27 26 QUAD GFI RECEPTACLE, 125V
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
REFER TO LUMINAIRE
SCHEDULE
RIM 26 24 21 REMOTE LINE ISOLATION MONITORRIM
SW-OC-D-W
D
26 09 33##
SW-OC-P-W
P
26 09 33##
SW-OC-U-W
U
26 09 33##
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS
BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING
FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK
AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF
WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH HIS/HER WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR
CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT
THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAIN
SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIED
SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE
PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TEXT INDICATES ADDITIONAL INFORMATION CAN BE FOUND
ELSEWHERE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONTRACTING OFFICER'S REPRESENTATIVEC.O.R
CONTACT PERSONS:
PROJECT MANAGER
MECHANICAL
ELECTRICAL
TECHNOLOGY
STRUCTURAL
ERIC HENDERSON
ERIC HENDERSON
ISAAC STOLL
DAMON DEEN
JOHN PAUL GOEDKEN
DESCRIPTION: PERSON:
BUILDING CODE: IBC 2018 EDITION
FIRE CODE: IFC 2018 EDITION, VA FIRE PROTECTION DESIGN
MANUAL
PLUMBING CODE: IPC 2018 EDITION, VA PLUMBING DESIGN MANUAL
MECHANICAL CODE: IMC 2018 EDITION, VA HVAC DESIGN MANUAL
ELECTRICAL CODE: NFPA 70 (NEC) 2020 EDITION
LIFE SAFETY CODE: NFPA 101 2021 EDITION
ENERGY CONSERVATION CODE: IECC 2012
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR
SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT
NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL
EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET 1-E9.
3. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
4. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND
OPERATES FROM EMERGENCY BATTERY WHERE SPECIFIED (EXTEND UNSWITCHED CIRCUIT
LEG TO BATTERY) OTHERWISE VIA EMERGENCY CIRCUIT UPON LOSS OF POWER.
5. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
6. REFER TO SHEET 1-E9 FOR LUMINAIRE SCHEDULE.
7. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR
DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER
SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA
OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING
MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC
MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT
DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.
ELECTRICAL MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
C MOUNT AT CEILING
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
R MOUNT IN SURFACE RACEWAY
EWC ELECTRIC WATER COOLER
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
Z = ZONE DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL SHEET INDEX
1-E0 ELECTRICAL COVERSHEET
1-ED1 SECOND FLOOR DEMOLITION - ELECTRICAL
1-ED2 THIRD FLOOR DEMOLITION - ELECTRICAL
1-EL1 SECOND FLOOR PLAN - LIGHTING
1-EL2 THIRD FLOOR PLAN - LIGHTING
1-EP1 SECOND FLOOR PLAN - POWER
1-EP2 THIRD FLOOR PLAN - POWER
1-EP3 ROOF PLAN - POWER
1-ES1 SECOND FLOOR PLAN - SYSTEMS
1-ES2 THIRD FLOOR PLAN - SYSTEMS
1-E4 ELECTRICAL ENLARGED PLANS
1-E5 ELECTRICAL ENLARGED PLANS
1-E6 ELECTRICAL DETAILS
1-E7 ELECTRICAL DETAILS
1-E8 ELECTRICAL RISER DIAGRAMS
1-E9 ELECTRICAL SCHEDULES
1-E10 ELECTRICAL SCHEDULES
1-E11 ELECTRICAL SCHEDULES
1-E12 ELECTRICAL SCHEDULES
GRAND TOTAL: 19
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T
.0
V A
-V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th -E
P C z a c h a ry
.r .r o s s .r v t
/8
/2
:1
:4
P M
1-E0
ELECTRICAL COVERSHEET REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 KLS ZRR16133Revisions: Date:
I O W A
S E
D
PROFESS IONA
15842
L
IC
E N
L E
N G
I N E
E R
ANDREW D.
THIELEN
I O W A
S E
D
PROFESS IONA
15842
L
IC
E N
L E
N G
I N E
E R
ANDREW D.
THIELEN
OCOCOCOC
OC OC
OC
E
E
E J
PP
EPO
E P
O
EPO
EPO E
PP
E
E
P P
PP
P P
E P
O E
P O
E
E
E
A1
SDSD
SD
SD
A
A
A
SD
SD
V
V
V
V1
A
A1
V7
V7
V7
A1
AA
AA
A
SD
SD SDSD SD
SD
F
F
SD
V
V
V
E P
O
EPO
E P
O
E P
O
E
E
E
E E
E
E E
E
E
E
OC
OC
E
A BA' C D D1 E F
0.9
G
14 M
FF
H
7'
RADIOLOGY
PANEL
80A CB
RADIOLOGY
EQUIP. SYSTEM
COMPONENTS
RADIOLOGY
EQUIP.
DOOR DOOR
DOOR
MED GAS
ALARM
MED GAS
ALARM
BOOM
BOOM
BOOM
BOOM
ANGIO
PANEL
CATH PANEL
SC1
PU2
PU1
SC1
PU2
PU1
1-AC-A3
1-AC-A4
N221 CB
FDS-TC221
TN221
TC221
EXISTING PANEL N221
EXISTING PANEL C221
TN220
N220 CB
EXISTING PANEL N220
DISTRIBUTION PANEL X220H
CB-C220
PANEL L220H
PANEL L220
EXISTING DISTRIBUTION PANEL N220H
DISTRIBUTION PANEL X220HJB
DISTRIBUTION PANEL NX220H
EXISTING PANEL C220H
(SQUARE D NQOB)
(SQUARE D NQOB)
(SQUARE D NQOB)
(SQUARE D I-LINE)
(SQUARE D NEHB)
(SQUARE D I-LINE)
(SQUARE D I-LINE)
(SQUARE D NQOB)
(SQUARE D NEHB)
PANEL C220
TC220
KEY PLAN - SECOND FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T
.0
V A
-V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th -E
P C z a c h a ry
.r .r o s s .r v t
/8
/2
:1
:3
A
M
1-ED1
SECOND FLOOR DEMOLITION -
ELECTRICAL
REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 KLS ZRR16133
N O R
HT
1/8" = 1'-0"
SECOND FLOOR DEMOLITION - ELECTRICAL
KEYNOTES:
1. DEMO FOR THIS AREA IS PART OF A
DIFFERENT PROJECT'S SCOPE. REMOVE ANY
REMAINING DEVICES AS NECESSARY.
2. ELECTRICAL CONNECTION FOR EXISTING LAB
EQUIPMENT.
3. CIRCUIT BREAKER PREVIOUSLY SERVING
RADIOLOGY LAB EQUIPMENT.
Revisions: Date:
CONSTRUCTION
DOCUMENTS
I O W A
S E
D
PROFESS IONA
15842
L
IC
E N
L E
N G
I N E
E R
3W103B
3ST07
3W103
3W105
MECH SHAFT
3W103A
3W104
3ST06
3W101
3W09
3S01
3C01
3CW01A
3W100
3W07
DW-2
3W102A
3W102
3CO1A
3C03
MECH SHAFT
3W19A3W11
3CW02A
3C02
3W17A
3W101A
CL-1
3W17
3W17B
3W101B
3W17C
3S08D
3W19B
B1
S H A F T
S H A F T
3W103D
3W19C
SHAFT
3W223
B3
C1
C2
3W103C
3W222
B2
3W101C
J
E
E
A BA' C D D1 E F
0.9
G
14 M
FF
H
7'
T-CATH
T-IR
PANEL A300
TA300
PANEL A300H
PANEL N300
TN300
PANEL N300H
ANGIO CATH
CATH LAB UPS
MCC A321H
LIEBERT UNIT COMPRESSOR
(1) BUS DUCT
(3) 4" C.
+7'-0" TO BOTTOM
(SQUARE D NQOD)
(SQUARE D NEHB)
(SQUARE D NQOD)
(SQUARE D I-LINE)
CHILLER
KEY PLAN - THIRD FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
2882 106th Street, Des Moines, IA 50322 630-717-2433 WWW. imegcorp.com
C R e v it L o c a l F ile s \M
E P
T
.0
V A
-V
IS
N
-I o w a C it y -R e m o d e l
IR
-C a th -E
P C z a c h a ry
.r .r o s s .r v t
/8
/2
:1
:4
A
M
1-ED2
THIRD FLOOR DEMOLITION -
ELECTRICAL
REMODEL 2W IR-CATH-EP
IOWA CITY VAHCS
636A8-21-001
BUILDING 1
04/08/2022 KLS ZRR16133
N O R
HT
1/8" = 1'-0"
THIRD FLOOR DEMOLITION - ELECTRICAL
KEYNOT…