I apologize, but I am unable to access or view the actual contents of "Attachment C Plans and Drawings Part B.pdf". While I can see the file name and ID number, I cannot see the drawings, plans, specifications or other information that would be contained within this PDF document. To provide an accurate summary of the key details, I would need access to the actual contents of the file.
View the file
Other files
Show all 24
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL NOTES
OPRD - FORT STEVENS STATE PARK, 8 STALL RESTROOM - VLMK JOB #20240218
DIVISION 1 - GENERAL
A. GENERAL
1. THESE DRAWINGS HAVE BEEN PREPARED SOLELY FOR USE IN THE CONSTRUCTION OF:
A. OREGON PARKS AND RECREATION DEPARTMENT, FORT STEVENS STATE PARK.
B. FORT STEVENS STATE PARK, 100 PETER IREDALE ROAD, HAMMOND, OR 97121.
C. POSSESSION OF THESE DRAWINGS DOES NOT GRANT A LICENSE TO CONSTRUCT OR
FABRICATE THE WHOLE, OR PARTS OF THIS PROJECT IN OTHER LOCATIONS.
2. THESE NOTES SET MINIMUM STANDARDS FOR CONSTRUCTION. THE DRAWINGS GOVERN OVER
THE GENERAL NOTES TO THE EXTENT SHOWN.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON DRAWINGS AND IN FIELD.
COORDINATE LOCATIONS OF OPENINGS THROUGH FLOORS, ROOFS AND WALLS WITH
ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. NOTIFY ENGINEER OF ANY
DISCREPANCIES OR IF ACTUAL CONDITIONS DIFFER FROM THOSE SHOWN OR NOTED.
4. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ALL
TEMPORARY BRACING, SHORING, ANCHORS, ETC., INCLUDING, BUT NOT LIMITED TO, WALL AND ROOF BRACING, LIFTING AND HANDLING INSERTS AND DEVICES, TRENCH SHORING, FORMS, ETC.
5. CONTRACTOR SHALL CONSIDER CONSTRUCTION LOADS WHENEVER SUCH LOADS ARE IN EXCESS OF NORMAL DESIGN LOADS. PARTICULAR ATTENTION SHOULD BE GIVEN TO CRANES, FORKLIFTS, WORKMAN, WHEEL LOADS, STORAGE OF MATERIALS, ETC. CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR ALL SHORING, BRACING, CRIBBING, ETC. REQUIRED TO SUPPORT
CONSTRUCTION LOADS.
6. INSPECTION AND/OR JOB SUPERVISION IS NOT PROVIDED BY ENGINEER.
7. WHERE REFERENCE IS MADE TO ASTM, AISC, ACI, ASCE OR OTHER STANDARDS, THE LATEST
ISSUE SHALL APPLY.
8. ALL WORK SHALL BE IN STRICT COMPLIANCE WITH:
A. 2022 OREGON STRUCTURAL SPECIALTY CODE. (BASED ON THE 2021 INTERNATIONAL BUILDING
CODE)
B. ALL OTHER STATE AND LOCAL BUILDING REQUIREMENTS THAT APPLY.
9. DESIGN CRITERIA:
a. ROOF LIVE LOADS (PER IBC 1603.1.2)
MINIMUM 20 PSF
b. ROOF SNOW LOAD (PER IBC 1603.1.3)
FLAT-ROOF SNOW LOAD (Pf) 25 PSF SNOW DRIFT SURCHARGE AND WIDTH (Pd, W) SEE DWGS SNOW EXPOSURE FACTOR (Ce) 1.0 SNOW LOAD IMPORTANCE FACTOR (Is) 1.0 THERMAL FACTOR (Ct) 1.2
c. LIVE LOAD (PER IBC 1607.1)
UNINHABITABLE ATTIC WITHOUT STORAGE 10 PSF
d. WIND LOAD (PER IBC 1603.1.4) ULTIMATE DESIGN WIND SPEED (Vult) 120 MPH NOMINAL DESIGN WIND SPEED (Vasd) 93 MPH
RISK CATEGORY II
WIND EXPOSURE C
INTERNAL PRESSURE COEFFICIENT (GCpi) ±0.18
e. EARTHQUAKE DESIGN DATA (PER IBC 1603.1.5) SEISMIC IMPORTANCE FACTOR (Ie) 1.0
RISK CATEGORY II
MAPPED SPECTRAL RESPONSE ACCELERATIONS Ss = 1.36 S1 = 0.71
SITE CLASS D
DESIGN SPECTRAL RESPONSE COEFFICIENTS Sds = 0.91 Sd1 = 0.80
SEISMIC DESIGN CATEGORY D
BASIC SEISMIC-FORCE-RESISTING SYSTEM SPECIAL REINFORCED MASONRY
SHEAR WALLS
ANALYSIS PROCEDURE USED EQUIVALENT LATERAL FORCE
10. MECHANICAL EQUIPMENT, MECHANICAL AND SPRINKLER PIPING LARGER THAN 2 INCHES IN
DIAMETER OR ANY OTHER ITEMS PRODUCING A HANGER OR SUPPORT LOAD OF OVER 50
POUNDS SHALL BE HUNG BY A SYSTEM APPROVED BY ENGINEER. ANY HANGER OR SUPPORT
PRODUCING A LOAD OVER 200 POUNDS SHALL HAVE ADDITIONAL FRAMING INSTALLED TO
TRANSFER THESE LOADS TO THE MAIN STRUCTURAL BEAMS OR WALL UNLESS OTHERWISE
APPROVED.
11. WHERE REQUIRED, SEISMIC BRACING FOR MECHANICAL AND ELECTRICAL EQUIPMENT,
SPRINKLER PIPING OR OTHER NON-STRUCTURAL COMPONENTS SHALL BE PROVIDED BY THE
CONTRACTOR IN ACCORDANCE WITH CHAPTER 13 OF ASCE 7. STRUCTURAL CALCULATIONS AND
DETAILS STAMPED BY A LICENSED ENGINEER SHALL BE SUBMITTED TO ENGINEER FOR REVIEW.
12. PROVIDE SHOP DRAWINGS FOR ALL STRUCTURAL PRODUCTS DELIVERED TO THE PROJECT.
ENGINEER WILL REVIEW AND MARK-UP ELECTRONIC SUBMITTALS IN PDF FORMAT OR A MAXIMUM
OF THREE HARD COPIES OF SUBMITTALS. THE CONTRACTOR WILL BE RESPONSIBLE FOR
DUPLICATING MARK-UPS IF ADDITIONAL COPIES ARE REQUIRED. SUBMITTALS WILL BE REVIEWED
AND RETURNED TO THE GENERAL CONTRACTOR WITHIN TWO WEEKS. ALL SUBMITTALS SHALL BE
REVIEWED AND STAMPED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE ENGINEER.
UNLESS OTHERWISE INDICATED, SHOP DRAWINGS SHALL BE PROVIDED ON THE FOLLOWING:
a. CONCRETE MIX DESIGNS.
b. ALL REINFORCING STEEL.
c. STRUCTURAL MASONRY MATERIALS.
DIVISION 2 - SITE WORK
A. GENERAL
1. REMOVE ALL ORGANIC MATERIAL AND TOPSOIL FROM AREAS UNDER THE BUILDING OR UNDER
PAVED AREAS.
2. FILL MATERIAL TO CONSIST OF A GRANULAR MATERIAL OR CONDITIONED SITE MATERIAL. PLACE FILL IN LIFTS NOT TO EXCEED 8 INCHES AND COMPACT TO 95% STANDARD ASTM D-1557 UNDER
FOOTINGS, UNDER PAVED AREAS AND UNDER FLOOR SLABS.
3. BASE MATERIAL IMMEDIATELY UNDER SLAB TO BE 6 INCH LAYER OF COMPACTED CRUSHED ROCK
WITH LESS THAN 5% PASSING THE #200 SIEVE.
4. SEE GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION:
A. PREPARED BY: PBS, DATED JANUARY 18, 2023
B. DESIGN SOIL PRESSURE: 2,000 (DL + LL)
5. ALL FOOTINGS TO BEAR A MINIMUM 18 INCHES BELOW FINAL GRADE ON FIRM, UNDISTURBED SOIL
OR APPROVED COMPACTED FILL. NOTIFY ENGINEER BEFORE PROCEEDING IF ANY UNUSUAL
CONDITIONS ARE ENCOUNTERED IN THE FOOTING EXCAVATIONS.
6. DO NOT EXCAVATE CLOSER THAN 2:1 SLOPE BELOW FOOTING EXCAVATIONS.
7. CLEAN ALL FOOTING EXCAVATIONS OF LOOSE MATERIAL.
8. EXCAVATIONS MAY BE MADE UNDER CONTINUOUS FOOTINGS FOR PIPES. BACKFILL TO BE
APPROVED BY GEOTECHNICAL ENGINEER.
B. REINFORCING
1. ALL REINFORCING TO BE ASTM A615 GRADE 60 UNLESS OTHERWISE NOTED.
2. FABRICATE AND INSTALL REINFORCING STEEL ACCORDING TO THE MANUAL OF STANDARD
PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES - ACI STANDARD 315.
DIVISION 4 - MASONRY
A. CONCRETE MASONRY
1. DESIGN f'm = 2000 PSI AT 28 DAYS.
2. ALL CONCRETE MASONRY UNITS TO BE MEDIUM WEIGHT UNITS PER ASTM C90.
3. NET AREA COMPRESSIVE STRENGTH (NACS) OF THE CONCRETE MASONRY UNITS SHALL
COMPLY WITH TMS 602. SEE UNIT STRENGTH METHOD TABLE BELOW.
4. MORTAR TO BE TYPE S (1800 PSI) USING THE 'PROPERTY METHOD' PER ASTM C270.
5. GROUT TO HAVE A MINIMUM 28 DAY STRENGTH OF 1.25 TIMES THE DESIGN f'm BUT NOT LESS
THAN 2000 PSI. SEE UNIT STRENGTH METHOD TABLE BELOW.
6. ALL GROUT MIX DESIGNS TO UTILIZE A FLUIDIFIER ADMIXTURE, INTRUSION AID BY SPECRETE-IP
OR APPROVED EQUAL. DOSAGE TO BE PER MANUFACTURERS RECOMMENDATION.
7. COMPLIANCE WITH f'm SHALL UTILIZE EITHER THE "UNIT STRENGTH METHOD" OR THE "PRISM
TESTING METHOD" FROM TMS 602.
8. FOR THE UNIT STRENGTH METHOD:
DESIGN f'm NACS GROUT STRENGTH
2000 PSI 2000 PSI 2500 PSI
9. ALL WORK SHALL CONFORM TO SECTION 2103 THROUGH SECTION 2108 OF THE INTERNATIONAL
BUILDING CODE.
10. REINFORCING FOR MASONRY TO BE ASTM A615 GRADE 60 PLACED IN CENTERS OF CELLS AS
FOLLOWS (UNLESS OTHERWISE NOTED IN DRAWINGS):
a. VERTICAL: SEE FOUNDATION NOTES ON SHEET S1.0.
b. HORIZONTAL: SEE FOUNDATION NOTES ON SHEET S1.0.
c. LINTELS: (EXTEND LINTEL BARS PAST OPENING 32 INCHES MINIMUM)
LESS THAN 4 FEET WIDE: (2) #4 IN BOTTOM OF 8 INCH DEEP LINTEL.
d. CORNERS AND INTERSECTIONS: (1) #4 CORNER BAR x 24 INCHES x 24 INCHES AT EACH
BOND BEAM FOR 8 INCH WALLS.
e. SPLICES IN VERTICAL WALL REINFORCING SHALL BE LAPPED 62 BAR DIAMETERS. WHERE
NOT MORE THAN (1) BAR IS REQUIRED IN EACH CELL, A 52 BAR DIAMETER LAP MAY BE USED.
f. HORIZONTAL BOND BEAM REINFORCING SHALL BE LAPPED 52 BAR DIAMETERS.
11. ELECTRICAL BOXES, CONDUIT AND PLUMBING SHALL NOT BE PLACED IN ANY CELL THAT
CONTAINS REINFORCING.
12. SEE DRAWINGS FOR ADDITIONAL REINFORCING.
13. FOR GROUT LIFT HEIGHTS EXCEEDING 4'-0", PROVIDE BAR POSITIONERS FOR ALL VERTICAL
WALL REINFORCING.
14. SPECIAL INSPECTION IS REQUIRED FOR ALL MASONRY CONSTRUCTION. SEE DRAWINGS FOR
ADDITIONAL INFORMATION.
DIVISION 3 - CONCRETE AND REINFORCING
A. CONCRETE MIX/MATERIAL
1. STRENGTH: AVERAGE 28 DAY CONCRETE STRENGTH DETERMINED BY JOB CAST LAB CURED
CYLINDER TO BE AS INDICATED BELOW PLUS INCREASE DEPENDING ON THE PLANT'S STANDARD
DEVIATION AS SPECIFIED IN ACI 318. PROVIDE MIX DESIGNS TO THE ENGINEER FOR ALL
CONCRETE TO BE USED. CLEARLY LABEL ALL MIX DESIGNS FOR PROPOSED AREA OF USE.
2. MINIMUM MIX REQUIREMENTS:
LOCATION MIN. COMP. SLUMP MIN. CEMENT ADMIXTURES
STRENGTH (a) CONTENT
FOOTINGS AND STEMWALLS 3,000 PSI 0"-5" 470 LB NONE
INTERIOR SLAB ON GRADE 3,000 PSI 2"-4" 517 LB (b), (e) EXTERIOR SLAB ON GRADE 3,000 PSI 2"-4" 470 LB (b), (c) MISCELLANEOUS 3,000 PSI 0"-5" 470 LB (b)
(a) - SLUMP EXCEEDING SPECIFIED LIMITS SHALL NOT BE INCORPORATED IN THE PROJECT
EXCEPT BY WRITTEN APPROVAL FROM ENGINEER.
(b) - WRA = WATER REDUCING AGENT.
(c) - AE = AIR ENTRAINMENT.
(d) - UP TO 1 1/2 PERCENT CALCIUM CHLORIDE ALLOWED DURING COLD WEATHER.
(e) - POZZUTEC 20 REQUIRED FOR CONCRETE PLACED BELOW 40 DEGREES FAHRENHEIT.
3. USE TYPE I CEMENT, PER ASTM C-150 UNLESS OTHERWISE APPROVED.
4. AGGREGATES PER ASTM C33. USE 3/4 INCH MINUS UNLESS OTHERWISE NOTED OR APPROVED.
5. WATER REDUCING AGENT (WRA) SHALL BE POLYHEED 900 OR DARACEM 55 (MINIMUM 6 OZ. PER
100 POUNDS CEMENT). COMPLY WITH ASTM C-494.
6. AIR ENTRAINMENT (AE) SHALL COMPLY WITH ASTM C-260 AND SHALL BE USED ONLY WHERE
SPECIFIED AND/OR APPROVED BY ENGINEER.
7. ACCELERATORS: POZZUTEC 20+ NON-CHLORIDE FOR COMPONENTS EXPOSED TO WEATHER IN
THE COMPLETED STRUCTURE (WALLS, EXTERIOR PAVING, ETC.), CALCIUM CHLORIDE IN THE
INTERIOR SLABS ON GRADE. QUANTITY (DOSAGE) TO BE DETERMINED BY CONTRACTOR AND
APPROVAL OBTAINED FROM ENGINEER BEFORE USE OF ACCELERATORS.
8. PLACE AND CURE ALL CONCRETE PER ACI CODES AND STANDARDS.
9. PROVIDE CONTROL JOINTS IN ALL INTERIOR SLABS ON GRADE AT 25'-0" ON CENTER EACH WAY
MAXIMUM UNLESS OTHERWISE SHOWN ON PLANS.
10. SLEEVES, PIPES OR CONDUITS OF ALUMINUM SHALL NOT BE EMBEDDED IN STRUCTURAL
CONCRETE UNLESS EFFECTIVELY COATED.
DIVISION 5 - METAL
A. GENERAL
1. ALL STRUCTURAL MEMBERS TO BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE
WITH THE LATEST EDITION OF AISC STANDARDS.
B. MATERIALS
1. ANCHOR BOLTS AND WOOD CONNECTIONS TO BE A307. WHERE NOTED TO USE STAINLESS
STEEL USE TYPE 304 OR TYPE 316. PROVIDE STANDARD PLATE WASHERS UNDER ALL BOLT
HEADS AND NUTS IN CONTACT WITH WOOD.
2. LAG BOLTS IN WOOD TO BE SAE J429 GRADE 1 WITH MINIMUM DIMENSIONS MEETING ANSI/ASME B.18.2.1.
3. ALL STEEL ANGLES TO BE ASTM A36 TYPICAL UNLESS OTHERWISE NOTED.
4. UNISTRUT FRAMING TO BE 12 GAUGE AND CONFORM TO ASTM 1653 UNLESS OTHERWISE
NOTED.
5. UNISTRUT NUTS AND BOLTS TO BE 1/2" DIA AND CONFORM TO ASTM A576 GRADE 1015 MODIFIED
AND A1011 SS GRADE 45.
C. POST-INSTALLED ANCHOR BOLTS:
1. UNLESS A SPECIFIC ANCHOR PRODUCT IS NOTED IN THE DRAWINGS, POST-INSTALLED
ANCHORS MAY USE ONE OF THE ANCHORS LISTED BELOW FOR THE REQUIRED TYPE AND BASE
MATERIAL. OTHER ANCHORS ARE ACCEPTABLE ONLY WITH PRIOR WRITTEN APPROVAL OF THE
ENGINEER.
2. INSTALL ALL ANCHORS PER MANUFACTURER'S INSTRUCTIONS AND PRODUCT EVALUATION
REPORTS.
3. EMBEDMENT SPECIFIED ON DRAWINGS FOR ADHESIVE ANCHORS ARE ‘EFFECTIVE’ EMBEDMENT.
‘NOMINAL’ EMBEDMENT IS SPECIFIED FOR EXPANSION AND SCREW ANCHORS, UNLESS
OTHERWISE NOTED. REFERENCE MANUFACTURER LITERATURE FOR MEASURING TOTAL
EMBEDMENT AND HOLE DEPTH REQUIREMENTS.
4. NOTE THAT ADHESIVE ANCHOR INSTALLATION TEMPERATURES AND CURE TIMES VARY BY
PRODUCT. CONSULT MANUFACTURER LITERATURE FOR SPECIFIC REQUIREMENTS.
5. ALL EXPANSION AND SCREW ANCHORS SPECIFIED AT EXTERIOR LOCATIONS OR EXPOSED TO
THE ELEMENTS SHALL BE THE STAINLESS STEEL VERSION PER EACH APPROVED
MANUFACTURER. EPOXY ANCHORS SPECIFIED AT EXTERIOR LOCATIONS OR EXPOSED TO THE
ELEMENTS SHALL USE STAINLESS STEEL OR HOT DIPPED GALVANIZED THREADED ROD.
6. SPECIAL INSPECTION OF ANCHOR INSTALLATION IS REQUIRED UNLESS SPECIFICALLY NOTED
OTHERWISE IN DRAWINGS. SEE SPECIAL INSPECTION AND MATERIALS TESTING PROGRAM AND
NOTES.
7. NO STEEL REINFORCEMENT SHALL BE CUT TO INSTALL ANCHORS WITHOUT THE PRIOR WRITTEN
APPROVAL OF THE ENGINEER.
8. ADHESIVE ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON SET-3G EPOXY ADHESIVE ANCHOR ICC ESR-4057
CONCRETE SIMPSON AT-3G ADHESIVE ANCHOR ICC ESR-5026
CONCRETE HILTI HIT-HY 200 V3 ADHESIVE ANCHOR ICC ESR-4868
MASONRY SIMPSON SET-3G EPOXY ADHESIVE ANCHOR ICC ESR-4844
MASONRY SIMPSON ET-3G ADHESIVE ANCHOR ICC ESR-5309
MASONRY HILTI HIT-HY 270 ADHESIVE ANCHOR ICC ESR-4143
9. EXPANSION ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON STRONG-BOLT 2 WEDGE ANCHOR ICC ESR-3037
CONCRETE HILTI KWIK BOLT TZ2 ANCHOR ICC ESR-4266
MASONRY SIMPSON STRONG-BOLT 2 WEDGE ANCHOR IAPMO ES-240
MASONRY HILTI KWIK BOLT TZ2 ANCHOR ICC ESR-4561
10. SCREW ANCHORS:
BASE MATERIAL PRODUCT REPORT#
CONCRETE SIMPSON TITEN HD SCREW ANCHOR ICC ESR-2713
CONCRETE HILTI KWIK HUS-EZ SCREW ANCHOR ICC ESR-3027
MASONRY SIMPSON TITEN HD SCREW ANCHOR ICC ESR-1056
MASONRY HILTI KWIK HUS-EZ SCREW ANCHOR ICC ESR-3056
2. PROVIDE FIRE BLOCKING AS REQUIRED AND BLOCKING FOR ALL SPECIFIED WALL-MOUNTED ITEMS
INCLUDING CABINETS, DOORSTOPS, ETC.
3. CONNECTORS:
a. TIE STRAPS, FRAMING ANCHORS, HANGERS, STIRRUPS, COLUMN CAPS, COLUMN BASES, ETC., TO BE SIMPSON AS DETAILED, OR AS APPROVED.
b. FULLY FASTEN ACCORDING TO MANUFACTURER'S SCHEDULE USING LARGEST SIZE SHOWN.
c. ALL BEAMS AND JOISTS NOT BEARING ON ANOTHER MEMBER TO CONNECT WITH 'U' TYPE
HANGERS UNLESS OTHERWISE NOTED ON DRAWINGS.
d. NAILING: ALL NAILS SPECIFIED IN THE DRAWINGS TO BE "COMMON" NAILS UNLESS OTHERWISE
NOTED. ALL NAILING SHALL COMPLY WITH IBC FASTENING SCHEDULE PER CHAPTER 23.
OBTAIN ENGINEERS APPROVAL OF ALL PROPRIETARY NAILING SYSTEMS.
e. NAILS AT ROOF, FLOOR, AND WALL DIAPHRAGMS TO BE DRIVEN SO THAT THEIR HEAD OR
CROWN IS FLUSH WITH THE SURFACE OF THE SHEATHING. CHECK AND RESINK IF NEEDED,
IMMEDIATELY BEFORE ROOFING.
f. BOLTS - SEE DIVISION 5, METAL.
g. CORROSION PROTECTION:
1. CONFIRM REQUIRED CORROSION PROTECTION FOR HARDWARE AND FASTENERS WITH
SPECIFIC RECOMMENDATIONS FROM PRESSURE TREATING MANUFACTURER OR HANGER
MANUFACTURER (USE MOST CONSERVATIVE) FOR SPECIFIC WOOD TREATMENTS USED.
2. MINIMUM CORROSION PROTECTION ON METAL CONNECTORS EXPOSED TO THE
ENVIRONMENT OR PRESSURE TREATED LUMBER TO BE PER ASTM A653 CLASS 185
(SIMPSON ZMAX) OR ASTM A123.
3. FASTENERS FOR PRESSURE TREATED LUMBER MUST BE MINIMUM HOT-DIP GALVANIZED,
STAINLESS STEEL, SILICON BRONZE OR COPPER.
4. HOT-DIP GALVANIZED HARDWARE AND FASTENERS MUST COMPLY WITH ASTM A153,
STAINLESS STEEL FASTENERS TO BE TYPE 304 OR TYPE 316.
5. HARDWARE AND FASTENERS USED TOGETHER MUST BE THE SAME TYPE (E.G. HOT-DIP
GALVANIZED NAILS WITH HOT-DIP GALVANIZED HANGERS, STAINLESS STEEL NAILS WITH
STAINLESS STEEL HANGERS).
4. DELIVERY AND STORAGE: ALL LUMBER AND SHEATHING DELIVERED TO THE SITE, SHALL BE
STACKED OR STORED OFF THE GROUND AND PROPERLY PROTECTED AGAINST WEATHER.
5. CUTTING AND NOTCHING OF JOISTS/RAFTERS NOT ALLOWED. A 1 INCH DIAMETER HOLE MAY BE
DRILLED IN THE CENTER 1/3 OF THE MEMBER DEPTH. ALL OTHER HOLES TO BE APPROVED BY
ENGINEER.
6. STUDS MAY BE NOTCHED IN THE LOWER 1/5 OF THE HEIGHT OF THE STUD FOR ELECTRIC AND PLUMBING PIPES, BUT NO PART OF THE NOTCH IS TO BE DEEPER THAN 25 PERCENT OF THE WIDTH OF THE STUD. HOLES OF DIAMETERS UP TO 1/3 OF WIDTH OF STUD MAY BE DRILLED IN THE STUD.
DIVISION 6 - WOOD
A. ROUGH CARPENTRY
1. LUMBER SPECIES AND GRADES TO BE AS FOLLOWS UNLESS OTHERWISE SHOWN ON DRAWINGS:
JOISTS, BEAMS & STRINGERS: DOUGLAS FIR #2
6 INCH NOMINAL AND GREATER: DOUGLAS FIR #1
BUCKS, BLOCKING, BRIDGING AND MISCELLANEOUS: DOUGLAS FIR OR HEM FIR #3
2x STUDS: DOUGLAS FIR #2
SILLS, LEDGERS, STRIPPING, ETC. IN CONTACT PRESSURE TREATED HEM FIR #2
WITH CONCRETE, AND WOOD CURBS:
PLATES AND HEADERS: KILN DRIED DOUGLAS FIR #2
POSTS, COLUMNS (SAWN): DOUGLAS FIR #1
ROOF, FLOOR AND WALL SHEATHING:
APA RATED SHEATHING, EXPOSURE 1, CONFORMING TO APA PERFORMANCE STANDARD PS
1-95 AND EXCERPT NER-108. SEE DRAWINGS FOR REQUIRED THICKNESS OF SHEATHING
AND/OR SPAN RATING. INSTALL ROOF AND FLOOR SHEATHING WITH LONG DIMENSION
PERPENDICULAR TO SUPPORTS UNLESS OTHERWISE NOTED. USE SPACERS TO PROVIDE 1/8
INCH END AND EDGE JOINTS WHENEVER SHEATHING IS EXPOSED TO WET WEATHER. FILL ANY
JOINT SPACING OVER 3/8 INCH UNLESS OTHERWISE APPROVED BY ENGINEER. INSTALL 2x4
OR THICKER BLOCKING AT UNSUPPORTED JOINTS IN WALL SHEATHING. BLOCK ROOF AND
FLOOR SHEATHING WHERE NOTED ON DRAWINGS.
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S0.0
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
ST
RU
C
TU
RA
L N O
TE
S
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
EXP. 12/31/2025
Justin Elliott
CODE REQUIRED SPECIAL INSPECTION AND MATERIALS TESTING PROGRAM
SOILS AND FOUNDATION SUBGRADE:
GRADING AND SUBGRADE COMPACTION
FOOTING EXCAVATION AND COMPACTION
CONCRETE:
VERIFY USE OF ENGINEER APPROVED CONCRETE MIX DESIGNS
FOOTING FORMWORK AND REINFORCING PLACEMENT
PLACING OF REINFORCING FOR SLAB-ON-GRADE
POST-INSTALLED ADHESIVE ANCHORS, RODS AND DOWELS IN
CONCRETE, PLACED HORIZONTALLY OR UPWARDLY INCLINED
POST-INSTALLED ADHESIVE ANCHORS, RODS AND DOWELS IN
CONCRETE, PLACED DOWNWARDLY INCLINED
POST-INSTALLED EXPANSION/WEDGE ANCHORS IN CONCRETE
POST-INSTALLED SCREW ANCHORS IN CONCRETE
STRUCTURAL WELDING AND HIGH STRENGTH BOLTING:
MATERIAL VERIFICATION OF STRUCTURAL STEEL,
DECKING, HIGH STRENGTH BOLTS, NUTS AND WASHERS,
ANCHOR RODS, AND WELD FILLER MATERIALS
STRUCTURAL MASONRY:
VERIFY USE OF ENGINEER APPROVED SUBMITTAL SHOWING
COMPLIANCE OF (fm) PRIOR TO CONSTRUCTION
PRISM PREPARATION AND TEST SPECIMENS
PREPARATIONS OF SITE-PREPARED MORTAR
AND MORTAR JOINT CONSTRUCTION
PLACEMENT OF MASONRY UNITS AND STRUCTURAL ELEMENTS
PLACEMENT OF REINFORCING STEEL
GROUTING PROCESS AND GROUT SPACE PRIOR
TO/AND DURING GROUTING OPERATIONS
INSTALLATION AND GROUT PLACEMENT FOR CAST
ANCHOR BOLTS AND EMBED PLATES
POST-INSTALLED ADHESIVE ANCHORS, RODS AND
DOWELS IN MASONRY
POST-INSTALLED EXPANSION/WEDGE ANCHORS IN MASONRY
POST-INSTALLED SCREW ANCHORS IN MASONRY
WOOD:
ROOF-DIAPHRAGM SHEATHING AND NAIL SPACING
ARCHITECTURAL:
CEILING CLIPS
STRUCTURAL OBSERVATION
WOOD FRAMING PRIOR TO COVER
AT COMPLETION OF ROOF DIAPHRAGM NAILING
(INCLUDING WALL ANCHORAGE CONNECTIONS)
STRUCTURAL OBSERVATION NOTES:
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE ENGINEER OF RECORD A MINIMUM OF 24 HOURS IN ADVANCED OF REQUIRED OBSERVATION(S). APPROVAL BY THE MUNICIPAL INSPECTOR DOES NOT PRECLUDE OBSERVATION BY THE ENGINEER OF RECORD AND APPROVAL BY THE ENGINEER OF RECORD DOES NOT PRECLUDE THE INSPECTION PROCESS BY THE MUNICIPAL INSPECTOR AND ANY OTHER CODE REQUIREMENTS FOR INSPECTION.
2. UPON COMPLETION OF WORK THE STRUCTURAL OBSERVER SHALL SUBMIT A REPORT TO OWNER AND BUILDING OFFICIAL WITH WET STAMP AND SIGNATURE ATTESTING TO THE VISUAL OBSERVATIONS MADE. THE REPORT SHALL IDENTIFY ANY
REPORTED DEFICIENCIES WHICH HAVE NOT BEEN RESOLVED.
COMMENTS
REF. PROJECT SPECIFICATIONS
DURATION INSPECTION AGENCY
P
C
C
C
C
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
TESTING LAB
ENGINEER
ENGINEER
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
UNIT STRENGTH OR PRISM
TEST METHOD
SEE NOTE 4, ITEM C
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
PER ICC EVALUATION REPORT
SEE NOTE 4, ITEM B
SEE NOTE 4, ITEM C
1. DURATION REFERS TO TIME AND FREQUENCY OF INSPECTION FOR THE PORTIONS OF WORK INDICATED.
C = CONTINUOUS INSPECTION IN WHICH THE SPECIAL INSPECTOR IS ON SITE AT ALL TIMES, OBSERVING THE WORK
REQUIRING SPECIAL INSPECTION.
P = PERIODIC INSPECTION IN WHICH THE SPECIAL INSPECTOR IS ON SITE AT TIME INTERVALS NECESSARY TO CONFIRM
THAT THE WORK REQUIRING SPECIAL INSPECTION IS IN CONFORMANCE WITH APPROVED PERMIT DRAWINGS AND
SPECIFICATIONS.
2. THE INSPECTION AGENCIES ARE AS FOLLOWS:
TESTING LAB: TO BE DETERMINED
TESTING LAB SHALL PERFORM INSPECTIONS OF ALL PORTIONS OF WORK DESIGNATED IN THE PROGRAM. THE SELECTED INSPECTION AGENCY SHALL BE AN ACCREDITED, APPROVED SPECIAL INSPECTION AGENCY EMPLOYED BY THE PROJECT
MANAGER, NOT THE CONTRACTOR OR SUB CONTRACTOR, PER IBC SECTION 1704.2.
3. DUTIES OF THE CONTRACTOR INCLUDE, BUT ARE NOT LIMITED TO:
A. NOTIFY THE SPECIAL INSPECTOR THAT THE WORK IS READY FOR INSPECTION AT LEAST 24 HOURS BEFORE SUCH
INSPECTION.
B. ALL WORK REQUIRING SPECIAL INSPECTION SHALL REMAIN ACCESSIBLE AND EXPOSED UNTIL IT HAS BEEN OBSERVED
AND INDICATED TO BE IN CONFORMANCE BY THE SPECIAL INSPECTOR AND APPROVED BY THE BUILDING OFFICIAL.
C. PROVIDE THE SPECIAL INSPECTOR WITH ACCESS TO APPROVED PERMIT DRAWINGS AND SPECIFICATIONS AT THE JOB
SITE.
D. MAINTAIN AT THE JOB SITE, COPIES OF ALL REPORTS SUBMITTED BY THE SPECIAL INSPECTOR.
4. IN ADDITION TO THE INSPECTION AND TESTING REQUIREMENTS INDICATED IN THE IBC, THE FOLLOWING SHALL ALSO APPLY:
A. CONCRETE INSPECTION AND TESTING REQUIREMENTS ARE AS FOLLOWS:
1. CONTINUOUS OBSERVATION OF SLAB ON GRADE CONCRETE PLACEMENT IS REQUIRED.
2. OBTAIN (4) TEST CYLINDERS FOR EACH 100 CUBIC YARDS PLACED (OR PORTION THEREOF IF LESS THAN 100 CUBIC
YARDS ARE PLACED). BREAK (1) CYLINDER AT 7 DAYS AND (2) CYLINDERS AT 28 DAYS. (IF THE FIRST 28 DAY CYLINDER BREAK IS LESS THAN REQUIRED STRENGTH, HOLD (2) CYLINDERS FOR 56 DAY BREAK) HOLD 4TH CYLINDER FOR 56 DAY BREAK. BREAK 4TH CYLINDER ONLY IF REQUIRED STRENGTH IS NOT MET WITH (2) CYLINDERS AT 28 DAYS
3. VERIFY THAT THE APPROVED MIX DESIGNS ARE BEING DELIVERED TO THE SITE. BATCH TICKETS SHOULD BE
CHECKED FOR ALL TRUCKS ENTERING THE SITE.
B. POST INSTALLED ANCHORS IN CONCRETE AND MASONRY SHALL BE INSPECTED AS FOLLOWS:
1. PROVIDE 'CONTINUOUS' OR 'PERIODIC' INSPECTION AS INDICATED IN THE SPECIAL INSPECTION TABLE (THIS SHEET).
INSPECTIONS ARE TO BE IN ACCORDANCE WITH THE MANUFACTURER'S CURRENT PRODUCT EVALUATION REPORT
AND INSTALLATION INSTRUCTIONS.
2. A COPY OF THE EVALUATION REPORT AND INSTALLATION INSTRUCTIONS ARE TO BE MAINTAINED ON THE JOB SITE.
ICC EVALUATION REPORTS ARE AVAILABLE ONLINE AT WWW.ICC-ES.ORG, AND IAPMO EVALUATIONS REPORTS ARE
AVAILABLE AT WWW.IAPMOES.ORG.
3. WHERE PERIODIC INSPECTION IS ALLOWED:
• THE SPECIAL INSPECTOR MUST BE ON SITE INITIALLY DURING ANCHOR INSTALLATION TO VERIFY MATERIALS AND
PROCEDURES AS REQUIRED BY THE EVALUATION REPORT.
• SUBSEQUENT INSTALLATIONS OF THE SAME ANCHOR TYPE AND SIZE BY THE SAME CONSTRUCTION PERSONNEL
ARE PERMITTED TO BE PERIODICALLY INSPECTED.
• A NEW INITIAL INSPECTION SHALL BE MADE FOR ANY CHANGE IN PERSONNEL PERFORMING THE ANCHOR
INSTALLATION OR CHANGE IN THE ANCHOR PRODUCT BEING INSTALLED.
• FOR ONGOING INSTALLATIONS OVER AN EXTENDED PERIOD, THE SPECIAL INSPECTOR MUST MAKE REGULAR
INSPECTIONS TO CONFIRM CORRECT HANDLING AND INSTALLATION. IF DISCREPANCIES ARE NOTED, CONTINUOUS INSPECTION SHOULD BE PROVIDED FOR ALL SUBSEQUENT ANCHORS.
4. ADHESIVE ANCHORS IN CONCRETE SHALL ADDITIONALLY CONFORM TO THE FOLLOWING
• CONCRETE IS TO HAVE A MINIMUM AGE OF 21 DAYS AT THE TIME OF ANCHOR INSTALLATION.
• CONTINUOUS INSPECTION IS REQUIRED FOR ALL ADHESIVE ANCHORS INSTALLED IN A HORIZONTAL TO VERTICAL
OVERHEAD ORIENTATION.
• INSTALLATION OF ADHESIVE ANCHORS IN A HORIZONTAL TO VERTICAL OVERHEAD ORIENTATION ARE TO BE DONE
BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI
318-19, SECTION 26.7. (NOT REQUIRED IN OREGON).
• ADHESIVE ANCHORS INSTALLED IN A HORIZONTAL TO VERTICAL OVERHEAD ORIENTATION ARE TO UTILIZE A
PISTON PLUG OR RETAINING CAP IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
C. MASONRY INSPECTION AND TESTING REQUIREMENTS ARE AS FOLLOWS:
1. PREPARE AND TEST MASONRY PRISMS FOR EACH 5,000 SQUARE FEET OF WALL DURING CONSTRUCTION IN
ACCORDANCE WITH ASTM C1314 AS FOLLOWS:
• SOLID GROUTED WALLS: (3) GROUTED PRISMS.
• PARTIALLY GROUTED WALLS: (3) GROUTED PRISMS AND (3) UNGROUTED PRISMS.
2. PREPARE AND TEST (3) GROUTED PRISMS FOR EACH 5,000 SQUARE FEET OF WALL DURING CONSTRUCTION IN
ACCORDANCE WITH ASTM C1019.
3. GROUT LIFT HEIGHT SHOULD NOT EXCEED 5'-4" UNLESS THE FOLLOWING CONDITIONS ARE MET.
• CONTRACTOR HAS OBTAINED APPROVAL FROM THE LOCAL BUILDING OFFICIAL.
• COMPLY WITH TMS602 SPECIFICATION FOR MASONRY STRUCTURES, ARTICLE 3.5D.
• PROVIDE INSPECTION OF REBAR PLACEMENT AT EACH BOND BEAM COURSE, AND USE BAR POSITIONERS AT 4'-0"
O.C. MAXIMUM.
• PROVIDE CLEANOUTS AT THE BOTTOM OF EACH VERTICALLY REINFORCED CELL.
• GROUT LIFT HEIGHT SHALL NOT EXCEED 9'-4".
SPECIAL INSPECTION PROGRAM NOTES:
REF. STRUCTURAL NOTES
PLACING OF CONCRETE FOR SLAB-ON-GRADE P TESTING LAB
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S0.1
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
SP
EC
IA
L
IN
SP
EC
TI
O N S
AN
D
ST
RU
C
TU
RA
L O
BS
ER
VA
TI
O N S
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
B
C JC JC J C J
C JC JC JC J
C J
C J
C J
C J
C J
C J
C J
C J
SLOPE SLAB TO
DRAIN PER ARCH,
TYPICAL
5" CONCRETE SLAB WITH
#4 AT 24" O.C. EACH WAY,
TYPICAL
1 1
C J
S2.0
TYP
S2.0
S2.0
S2.0
TYP
TYP
TYP
A
S2.0
TYP
M J
M J
M J
M J
M JM J
M JM J
C J
C J
A
42' - 0"
9' - 7"8' - 8"8' - 8"15' - 1"
1 11
1 1 1
A
S2.0
TYP
S2.0
SIM
SLOPE SLAB TO
DRAIN PER ARCH,
TYPICAL
S2.0
TYP
S2.0
TYP
TYP
S2.0
S2.0
TYP
TYP
S2.0
S2.0
TYP
M J
M J
C L
C L
C J
C J
C J
C J
C J
EQEQEQEQ
TYP
S2.0
A
S2.0
TYP
TYP3
S2.0
TYP
S2.0
TYP
S2.0
7' - 0"9' - 10"18' - 8"13' - 6"5' - 0"
C L
WALL & FTG
C L
WALL & FTG
C L
WALL & FTG
W A
L L
F T
G C
L
C L C L
W A
L L
F T
G C
L
6"
TYP
6"6"6" 6"
S2.0
SIM
TYP
TYP
5' - 4"3' - 4"2' - 8"2' - 8"3' - 4"4' - 0"3' - 4"3' - 4"8' - 8"
3' - 4"
2' - 0"
9' - 10"
(2) #4 x 4'-0"
DIAGONAL BAR,
TYPICAL
6" CMU WALL
8" CMU WALL
CONCRETE FOOTING PER SCHEDULE THIS SHEET
FOUNDATION LEGEND:
COLUMN PER SCHEDULE THIS SHEET
X FOOTING PER SCHEDULE THIS SHEET
CONCRETE SLAB CONTROL JOINT PER DETAILC J
S2.0
MASONRY CONTROL JOINT PER DETAILM J 7
S2.0
FOUNDATION NOTES:
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS WITH
ARCHITECTURAL DRAWINGS.
2. CONTRACTOR TO VERIFY ALL FOOTING ELEVATIONS WITH THE
FOLLOWING CRITERIA: TOP OF FOOTING TO BE MINIMUM 12"
BELOW FINISH GRADE AND FINISH FLOOR. BOTTOM OF FOOTING
TO BE A MINIMUM OF 18" (OR AS REQUIRED FOR SITE FROST
DEPTH REQUIREMENTS) BELOW FINISH GRADE.
3. PROVIDE AN UNDER SLAB VAPOR BARRIER PER SPECIFICATIONS.
USE CURING BLANKETS FOR SLABS PLACED OVER VAPOR
BARRIERS. DO NOT WET CURE.
4. EXTERIOR CMU WALLS TO BE 8" SOLID GROUTED. TYPICAL
REINFORCING TO BE AS FOLLOWS, UNLESS OTHERWISE NOTED:
VERTICAL: (1) #5 AT 32" O.C. CENTERED, PLUS (2) #5
FULL HEIGHT EACH SIDE OF OPENINGS AND
MASONRY JOINTS.
HORIZONTAL: (2) #4 x CONTINUOUS AT 48" O.C. FOR
RUNNING BOND, OR 24" O.C. STACK BOND.
LOCATE FIRST BOND BEAM AT GROUND
FLOOR LEVEL.
5. INTERIOR CMU WALLS TO BE 6" SOLID GROUTED. TYPICAL
REINFORCING TO BE AS FOLLOWS, UNLESS OTHERWISE NOTED:
VERTICAL: (1) #5 AT 32" O.C. CENTERED.
HORIZONTAL: (1) #4 x CONTINUOUS AT 48" O.C. FOR
RUNNING BOND, OR 24" O.C. STACK BOND.
LOCATED FIRST BOND BEAM AT GROUND
FLOOR LEVEL.
6. REFERENCE STRUCTURAL NOTES AND DETAILS ON SHEET S2.0
FOR ADDITIONAL REINFORCING REQUIREMENTS AND PLACEMENT.
SPECIAL INSPECTION IS REQUIRED FOR ALL CMU.
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S1.0
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
FO
U N D
AT
IO
N
PL
AN
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
S1.0 1/4" = 1'-0"
A FOUNDATION PLAN
COLUMN AND FOOTING SCHEDULE
MK COLUMN/WALL FOOTING SIZE REINFORCING NOTES
1 6x6 WOOD COLUMN 2'-6" x 2'-6" x 12" DEEP (4) #4 EACH WAY AT BOTTOM SEE DETAIL 3/S2.0
2 CMU WALL 8" 2'-0" WIDE x 12" DEEP x CONT (3) #5 AT TOP AND BOTTOM SEE DETAIL 4/S2.0
3 CMU WALL 6" 1'-6" WIDE x 12" DEEP x CONT (2) #5 AT BOTTOM SEE DETAIL 4/S2.0
2x6 AT 24" O.C.
S2.1
S2.1
TYP
TYP
S2.1
TYP
S2.1
TYP
A
42' - 0"
2x6 AT 24" O.C. 2x6 AT 24" O.C.2x6 AT 24" O.C. 2x6 AT 24" O.C.
2x6 AT 24" O.C. 2x6 AT 24" O.C. 2x6 AT 24" O.C.
B
S2.0
ABOVE
B
S2.0
ABOVE
S2.1
TYP
TYP
S2.1
S2.1
TYP
S2.1
TYP
NEW ERV UNIT PER
MECHANICAL DRAWINGS,
MAX WEIGHT = 504 LBS
S1.1
LEDGER PER DETAIL
CEILING FRAMING LEGEND:
COLUMN PER FOUNDATION PLAN
S2.1
6" CMU WALL PER FOUNDATION PLAN
8" CMU WALL PER FOUNDATION PLAN 1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS
WITH ARCHITECTURAL DRAWINGS.
2. CEILING DESIGN CRITERIA:
DEAD LOAD = 10 PSF
LIVE LOAD = 10 PSF
DEFLECTION = SMALLER OF LL/360, TL/240
3. ATTIC SPACE ABOVE CEILINGS IS TO BE USED FOR
MAINTENANCE ACCESS ONLY. DO NOT USE ATTICE SPACE
FOR STORAGE.
4. CEILING SHEATHING TO BE APA RATED EXPOSURE 1
SHEATHING WITH MINIMUM SPAN RATING OF 32/16 AND A
MINIMUM THICKNESS OF 15/32". ORIENT STRONG AXIS OF
SHEATHING PERPENDICULAR TO SUPPORT FRAMING.
5. CEILING NAILING TO BE 10d COMMON OR GALVANIZED BOX
NAILS. NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND
AT 12" O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT
REQUIRED.
CEILING FRAMING NOTES:
JOIST PER PLAN
CMU WALL PER PLAN
L5x5x5/16 x CONTINUOUS LEDGER, LENGTH TO
EXTEND 2" CLEAR PAST EACH END OF UNIT OR
ANY ATTACHMENTS / PROTRUSIONS, ATTACH
TO WALL WITH 1/2" DIA x 4" LONG SIMPSON
'TITEN HD' CONCRETE SCREW ANCHORS AT
48" O.C. MAX, (3) ANCHORS MINIMUM
MECHANICAL UNIT PER PLAN
3/8" DIA THREADED
ROD EACH SIDE OF
UNIT
MOUNTING RAIL
UNISTRUT 'P1000T' WITH 3/8"
DIA BOLT AT EACH MOUNTING
RAIL, MAX LENGTH = 5' - 0"
SIMPSON 'SCS62-5/118' CLIP, TYPICAL EACH
SIDE, TOP AND BOTTOM OF UNIT, ATTACH TO
UNIT WITH (2) #14 SHOULDERED SCREWS
CENTERED IN SLOT, ATTACH TO CMU WALL
WITH (1) 1/2" DIA x 4" LONG SIMPSON 'TITEN HD'
CONCRETE SCREW ANCHOR
6x8 BLOCKING WITH (2) 1/4" DIA x 8" LONG
SIMPSON 'SDS' SCREWS TO JOIST, RIP AS REQUIRED
UNISTRUT 'P1000T'
UNISTRUT 'P1063' WASHER
AND NUT, TYPICAL TOP AND
BOTTOM OF THREADED ROD
3"
/2
L3x3x3/16 x 0'-6" LONG WITH (2) 1/2" DIA x 3" LONG
LAG SCREWS
/2
T Y
P
1 1/2"
TYP
3" MINIMUM
TYPICAL
CEILING
SHEATHING
COUNTER-SINK FASTENERS FOR
MINIMUM FULL THREAD
PENETRATION TO JOISTS, TYPICAL
A
1 1/2"
VIBRATION ISOLATION
SPRING PER MECH.
DRAWINGS, TYPICAL
2" CLR 1 1/2"
/2
M A
X
T Y
P
1 1/2"
/2
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S1.1
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
C
EI
LI
N G
FR
AM
IN
G
PL
AN
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
S1.1 1/4" = 1'-0"
A CEILING FRAMING PLAN
S1.1 1" = 1'-0"
1 SUSPENDED EQUIPMENT ANCHORAGE DETAIL
6x12
6x12
6x126x12
6x12
6x12
2x10 AT 24" O.C.
S2.1
S2.1
S2.1
S2.1
S2.1
E Q
E Q
TYP
TYP
TYP
TYP
2x12
A
42' - 0"
S2.1
TYP
TYP
S2.1
TYP
6x126x126x126x126x12 x x x x x
6x12 6x12 6x126x126x12 x x x x x
E Q
E Q
(ABOVE)
(ABOVE)
(ABOVE)
(ABOVE)
(ABOVE)
(ABOVE)
2x10 AT 24" O.C.
2'-0"x2'-0" ATTIC ACCESS HATCH IN WALL BELOW, SEE ARCHITECTURAL DRAWINGS FOR LOCATION
(FRAMING NOTE #5)
6' - 0"
(FRAMING NOTE #5)
6' - 0" x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E x
(A B
O V
E
B
S2.0
BELOW, TYP
HATCHED AREA INDICATES EXTENT OF
INCREASED DIAPHRAGM NAILING , SEE
ROOF FRAMING NOTES, TYPICAL
E Q
E Q
E Q
E Q
S2.1
_____TYP
RIDGE BOARD
MECHANICAL UNIT BELOW
S1.1
BELOW
1. CONTRACTOR TO VERIFY ALL DIMENSIONS AND ELEVATIONS
WITH ARCHITECTURAL DRAWINGS.
2. ROOF DESIGN CRITERIA:
DEAD LOAD = 15 PSF
SNOW LOAD = 75 PSF
DEFLECTION = SMALLER OF LL/240, TL/180
3. ROOF SHEATHING TO BE APA RATED EXPOSURE I SHEATHING
WITH MINIMUM SPAN RATING OF 40/20 AND A MINIMIM THICKNESS
OF 19/32". ORIENT STRONG AXIS OF SHEATHING
PERPENDICULAR TO SUPPORT FRAMING AND STAGGER SHEETS.
4. ROOF NAILING TO BE 10d COMMON OR GALVANIZED BOX NAILS.
NAIL AT 6" O.C. AT ALL SUPPORTED PANEL EDGES AND AT 12"
O.C. AT INTERMEDIATE SUPPORTS. BLOCKING IS NOT
REQUIRED, U.O.N. (2) ROWS OF NAILS AT 6" O.C. AT TOP PLATE
ALONG GRIDLINES 1 AND 3.
5. INDICATES ROOF NAILS AT 4" O.C. AT ALL PANEL
EDGES, ALL EDGES TO BE SUPPORTED, USE FLAT 2x BLOCKING
AS NECESSARY. (2) ROWS OF NAILS AT TOP PLATE ALONG
GRIDLINES A AND B USING SPECIFIED EDGE NAIL SPACING FOR
EACH ROW. FOR AREA WITH INCREASED NAIL SPACING SEE
ALSO DETAIL .
6. ALL SOLID SAWN HEADERS, PLATES (OTHER THAN P.T.) AND
HORIZONTAL MEMBERS TO BE KILN DRIED (K.D.) LUMBER.
ROOF FRAMING NOTES:
S2.1
STRUCTURAL BEARING WALL BELOW
ROOF FRAMING LEGEND:
COLUMN PER FOUNDATION PLAN
6x6 KING POST
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S1.2
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
RO
O F
FR
AM
IN
G
PL
AN
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
S1.2 1/4" = 1'-0"
A ROOF FRAMING PLAN
8"
3" CLEAR
M
IN
A S
O C
C U
R S
#5 x CONTINUOUS TOP
AND BOTTOM
CONCRETE SLAB AND REINFORCING PER
PLAN, TURN DOWN EDGE AS SHOWN
TYP
WET SAWN CONTROL JOINT
/4 d C
L R
T Y
P
IC
A L d
STOP REINFORCING 0'-3"
CLEAR OF JOINT
JOINT
BACKER ROD, PLACE IMMEDIATELY
AFTER SAW CUT (SAME DAY)
SAWN JOINT, DEPTH TO BE 1/5 SLAB DEPTH,
SAWING TO OCCUR AS EARLY AS POSSIBLE
WITHOUT SPALLING CONCRETE. DO NOT
WAIT UNTIL THE FOLLOWING DAY. USE
"SOFFCUT" SAW OR APPROVED EQUAL.
NOTE:
SEE FOUNDATION PLAN FOR LOCATIONS
OF MASONRY CONTROL JOINTS
/4
C
L R
T Y
P
STOP HORIZONTAL REINFORCING
EACH SIDE OF JOINT EXCEPT BOND
BEAM AT ROOF AND BOTTOM OF
LINTELS AND WALLS TO BE
CONTINUOUS THRU JOINT
CAULK JOINT WITH BACKER ROD
TYPICAL
PROVIDE (2) VERTICAL BARS
(MATCH TYPICAL VERTICAL
REINFORCING) FULL HEIGHT
EACH SIDE OF JOINT
PREMOLDED RUBBER INSERT
SEE FOUNDATION NOTES
FOR HORZ BARS
OPENING IN WALL, SEE
ARCHITECTURAL
DRAWINGS FOR LOCATIONS
EXTEND LINTEL
REINFORCING 2' - 0"
(2) #4 BARS ABOVE AND
BELOW OPENINGS
(2) #5 BARS EACH
SIDE OF OPENINGS
CMU WALL PER PLAN
PER ARCH
PER ARCH
B.O. OPENING
PER ARCH
T.O. OPENING
PER ARCH
T.O. OPENING
+0'-0"
T.O. SLAB
CONCRETE
SLAB
PER ARCH
EXTEND LINTEL
REINFORCING 2' - 0"
CMU WALL PER PLAN
DOOR OPENINGS PER PLAN
(2) #5 BARS EACH SIDE OF
OPENING, FULL HIEGHT
LINTEL BARS ABOVE OPENING
PER STRUCTURAL NOTES
#5 DOWEL AT 32" O.C.
ALTERNATE BEND
AND LAP 2'-0" WITH
SLAB REINFORCING
C L R
CONCRETE SLAB PER PLAN
RUN #5 x CONT
WALL REINFORCING
THROUGH OPENING
CMU WALL BEYOND
SIDEWALK/GRADE
SEE ARCH
U .O
.N
RADIUS
SEE SCHEDULE FOR
FOOTING SIZE AND
REINFORCING
3" CLR
TYP
T Y
P
SIZE AND SPACING PER FOUNDATION PLAN
TYPICAL VERTICAL WALL
REINFORCING PER PLAN
SEE FOUNDATION NOTES
FOR HORZ BARS
(2) #5 FULL HEIGHT AT OPENINGS
/4
C
L R
T Y
P
DOWEL x 3'-0" TO MATCH
VERTICAL WALL REINFORCING
SIZE AND SPACING, (ONE PER
CELL), ALTERNATE BEND.
COMPACTED AGGREGATE BASE
PER NOTES AND GEOTECHNICAL
REPORT
C L R1
M
IN
IM
U
M
CONCRETE SLAB PER PLAN
#4 DOWEL x 0'-6"
AT 32" O.C., HOOK OVER
REINFORCING
2'-6"
#5 x CONTCMU WALL PER PLAN
SIDEWALK/GRADE
SEE ARCH
U .O
.N
3" CLR
SEE SCHEDULE FOR
FOOTING SIZE AND
REINFORCING
NOTE: AT SIMILAR CONDITION INTERIOR SLAB IS ON BOTH SIDES OF WALL
SLAB REINFORCING
PER PLAN
CONCRETE PEIR WITH (4) #4
VERTICAL BARS, HOOK INTO
FOOTINGROUGHEN SURFACE OR
POUR MONOLITHIC
RUN TYPICAL SLAB EDGE
REINFORCING THROUGH FOOTING
SEE FOOTING
SCHEDULE FOR SIZE
AND REINFORCING
POST PER PLAN
STAINLESS STEEL SIMPSON
'CB' POST BASE
(3) #3 TIES IN TOP 6",
BALANCE AT 12" O.C.
SQUARE
1' - 0"
(P E
R G
E O
T E
C H
C L R
THICKENED
SLAB EDGE
BEYOND
T Y
P
EQ EQ
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S2.0
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
FO
U N D
AT
IO
N
AN
D W
AL
L D
ET
AI
LS
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
S2.0 1" = 1'-0"
2 SLAB EDGE DETAIL
S2.0 1 1/2" = 1'-0"
1 SLAB CONTROL JOINT DETAILS
S2.0 1 1/2" = 1'-0"
7 MASONRY CONTROL JOINT
S2.0 1/2" = 1'-0"
B CMU WALL OPENING ELEVATION
S2.0 1/2" = 1'-0"
A CMU DOOR OPENING ELEVATION
S2.0 1" = 1'-0"
5 FOOTING AT CMU WALL OPENING
S2.0 1 1/2" = 1'-0"
6 REINFORCING AT OPENING
S2.0 1" = 1'-0"
4 FOOTING AT CMU WALL
S2.0 1" = 1'-0"
3 COLUMN AT SLAB EDGE
COLUMN PER
PLAN, TYPICAL
6x BEAM PER PLAN, TYPICAL
RAFTER PER PLAN,
AS OCCURS
(2) STAINLESS STEEL SIMPSON 'H2.5A'
TIES AT THIS RAFTER/BEAM
CONNECTION, (1) EACH SIDE
RIDGE BOARD PER PLAN, ATTACH
TO 6x BEAM BELOW WITH
SIMPSON 'A34' CLIPS AT 24' O.C.
TOE NAIL RAFTER TO
RIDGE BOARD WITH (2)
10d NAILS
SHEATHING PER PLAN
2x BLOCKING BETWEEN
RAFTERS, TYPICAL
STAINLESS STEEL
SIMPSON 'LS50' ANGLE,
EACH SIDE OF COLUMN,
TYPICAL
STAINLESS STEEL SIMPSON
'HU612' WITH SLOPED SEAT,
TYPICAL
FASCIA
PER ARCH
6"
STAINLESS STEEL TIE PER EACH
SIDE OF FRAMING, FASTEN EACH PLATE
WITH (4) 3/8" DIA x 2" LONG STAINLESS
STEEL SCREWS
E Q
E Q
STAINLESS STEEL
SIMPSON 'HU612'
STAINLESS STEEL
SIMPSON 'AC' POST CAP,
EACH SIDE OF COLUMN,
TYPICAL
STAINLESS STEEL SIMPSON
'2.5A' TIE AT RAFTER/BEAM
CONNECTION, TYPICAL
CMU WALL
PER PLAN
SIMPSON 'RBC' AT 24" O.C.
AT 8" SHEAR WALLS
2x SHEAR BLOCKING
WITH BOUNDARY
EDGE NAILING
CMU WALL PER PLAN
TYPICAL BOND BEAM
COLUMN PER PLAN
BEAM PER PLAN
RAFTER PER PLAN
SIMPSON 'HGA10KT' HURRICANE
GUSSET ANGLE AT EACH RAFTER,
TYPICAL
STAINLESS STEEL
SIMPSON 'H2.5A' TIE AT
EACH RAFTER
TOP PLATE PER DETAIL
RIDGE BOARD PER PLAN
TOE NAIL RAFTER TO RIDGE
BOARD WITH (2) 10d NAILS
SHEATHING PER PLAN
2x BLOCKING
BETWEEN RAFTERS
2x BLOCKING BETWEEN
RAFTERS AT SUPPORTS,
TYPICAL
STAINLESS STEEL SIMPSON 'AC6'
POST CAP EACH SIDE OF COLUMN
FASCIA
PER ARCH
FLAT 2x BLOCKING
PER ROOF FRAMING
NOTE #5, AS OCCURS
FINISHES PER ARCH
S2.1
4x6 TOP PLATE, ANCHOR PER DETAIL
S2.1
5"
/4
/2
T Y
P
12 GAUGE
STAINLESS STEEL
1"
TYP
/4
T Y
P
CEILING JOIST PER
PLAN WITH SIMPSON
'LUS' HANGER
CMU WALL PER PLAN
2x6 LEDGER WITH 1/2" DIA x 3" EMBED SCREW
ANCHORS AT 24" O.C.
FINISHES PER ARCH
SHEATHING PER PLAN
2x BLOCKING AT 4'-0" O.C. IN
FIRST JOIST BAY WITH SIMPSON
'LUS' HANGER EACH ENDCMU WALL PER PLAN
LEDGER PER
DETAIL
FINISHES PER ARCH
SHEATHING PER PLAN
S2.1
CEILING JOIST
PER PLAN, TYP
TOP PLATE PER DETAIL
BEAM PER PLAN
STAINLESS STEEL
SIMPSON 'MBHU5.50'
BEAM HANGER
S2.1
SHEATHING PER PLAN
FINISHES PER ARCH
FASTEN 2x RAFTER
TO CMU WALL WITH
1/2" DIA x 3 1/2"
EMBED EXPANSION
ANCHORS AT 8" O.C.
4x8 TOP PLATE WITH 5/8" DIA x 7" J-BOLTS
AT 24" O.C.,
COUNTERSINK AS
REQUIRED
SIMPSON 'MSTA24' STRAP
AT 4'-0" O.C., ALIGN WITH
TENSION TIES
SIMPSON 'LTTP2' TENSION TIES
AT 4'-0" O.C. WITH 5/8" DIA.
EPOXY ANCHOR WITH 5 5/8"
EMBED INTO CMU WALL
4x6 BLOCKING FIRST (2) BAYS AT
4'-0" O.C. WITH SIMPSON 'U44'
FACE MOUNT HANGERS AT EACH
END, ALIGN WITH TENSION TIES
RAFTER PER PLAN, TYP
FINISHES
PER ARCH,
TYP
FOR NAILS WITH INCREASED EDGE
NAIL SPACING PLACE NAILS AT TOP
PLATE AS OCCURS, WHERE TOP PLATE
DOES NOT OCCUR PLACE NAILS AT 2x
RAFTER FOR REMAINDER OF ROOF
2x BLOCKING AT 4'-0" O.C. IN
FIRST JOIST BAY WITH SIMPSON
'LUS' HANGER EACH END, TYP
CMU WALL PER PLAN
LEDGER PER DETAIL , TYPICAL
EACH SIDE OF WALL, OFFSET
ANCHOR LOCATIONS ON OPPOSITE
SIDES OF WALL, TYP
FINISHES PER ARCH, TYP
SHEATHING PER PLAN,
TYPICAL
JOIST PER PLAN,
TYPICAL
S2.1
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
1183838318
S2.1
FO
RT
ST
EV
EN
S
ST
AT
E
PA
RK
RE
ST
RO
O M S
RO
O F D
ET
AI
LS
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
JJ
E
JJ
E
RJ
S
RJ
S
S2.1 3/4" = 1'-0"
7 ROOF SECTION
S2.1 3/4" = 1'-0"
6 ROOF SECTION
S2.1 1" = 1'-0"
1 CEILING/SOFFIT JOIST PERPENDICULAR
S2.1 1" = 1'-0"
2 CEILING/SOFFIT JOIST PARALLEL
S2.1 1" = 1'-0"
5 ROOF FRAMING DETAIL
S2.1 1" = 1'-0"
4 ROOF FRAMING DETAIL
S2.1 1" = 1'-0"
3 CEILING/SOFFIT JOIST PARALLEL
MISC. VALVES & COCKS
SHUTOFF VALVE
GLOBE VALVE
GATE VALVE OS&Y
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
WYE STRAINER
WYE STRAINER WITH BLOWDOWN
DRAIN VALVE
BALANCING VALVE
PRESSURE REDUCING VALVE
RELIEF VALVE
TWO-WAY CONTROL VALVE
DOUBLE CHECK VALVE ASSEMBLY (DCVA)
REDUCED PRESSURE BACKFLOW PREVENTER (RPBP)
THERMOMETER
PRESSURE GAUGE
PRESSURE-TEMPERATURE TEST PLUG
MANUAL AIR VENT
AUTOMATIC AIR VENT
FLOW SWITCH
TEMPERATURE SENSOR
SHOCK ARRESTOR
VACUUM BREAKER
SHUTOFF VALVE WITH TAMPER SWITCH
THRUST BLOCK
SOLENOID VALVE
S
S
S
V
T
F
AAV
MAV
CLEANOUT
FLOOR CLEANOUT
CLEANOUT TO GRADE
WALL CLEANOUT
AREA DRAIN
CATCH BASIN
FLOOR DRAIN
OVERFLOW ROOF DRAIN
ROOF DRAIN
TRENCH SHOWER DRAIN
TRENCH DRAIN
HOSE BIBB
GROUND HYDRANT
WALL BOX HYDRANT
FLOOR SINK
PLUMBING SPECIALITIES
SYMBOLS
A
E
B
X
K
R
F
ACCESS PANEL
POINT OF CONNECTION
EXISTING TO REMAIN
BELOW GRADE / FLOOR
REVISION NUMBER
NUMBERED NOTE
REMOVE EXISTING
CAP EXISTING / CAP FOR FUTURE
RELOCATE EXISTING
FUTURE
EQUIPMENT
XXX
TAG NUMBER
XX-XXX
XXX
EQUIPMENT PROVIDED
FIXTURE NUMBER
FIXTURE UNITS
FIXTURE TYPE
FIXTURES DETAIL CALLOUT
X
XX.XX
X
XX
RISER TAG
DETAIL NUMBER
SHEET NUMBER
SYSTEM TYPE
RISER NUMBER
MISC. FITTINGS & SYMBOLS
DIRECTION OF FLOW
DIRECTION OF SLOPE
PIPE SLEEVE
REDUCER
ANCHOR
ELBOW (90 DEGREE)
PIPING CONNECTIONS
TEE
JOINT OR COUPLING POINT
PIPE CONTINUATION
HEAT TRACE
FLEXIBLE HOSE CONNECTOR
TEE DOWN
TEE UP
ELBOW DOWN
ELBOW UP
RISER
PLUG OR BLIND FLANGE
CAP
FLANGED CONNECTION
UNION
ELBOW (45 DEGREE)
MC
MECHANICAL COUPLING
PLUMBING PIPING
G
W WASTE ABOVE GRADE
W WASTE BELOW GRADE
STORM DRAIN ABOVE GRADE
STORM DRAIN BELOW GRADE
DRAIN (CONDENSATE/INDIRECT)
VENT
COLD WATER
HOT WATER
RECIRCULATING HOT WATER
IRRIGATION
NON-POTABLE WATER
SD
SD
D
V
CW
HW
RHW
IRR
NPW
BY OTHERS
GENERAL NOTES:
A. THIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAY APPEAR ON THIS SHEET
THAT DO NOT APPEAR ON THE DRAWINGS.
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE
XX-XXX XXXX-XX-XXXXX
UNIT NUMBER
FLOOR UNIT IS
LOCATED ON
EQUIPMENT TYPE
STANDARD ABBREVIATIONS
AREA DRAINAD
AMERICANS WITH DISABILITIES ACTADA
ABOVE FINISHED FLOORAFF
ALTERNATIVEALT
APPROXIMATELYAPPROX
ARCHITECT, ARCHITECTURALARCH
ACCESS PANELAP
BELOW FINISHED FLOORBFF
BUILDINGBLDG
BOTTOM OF PIPEBOP
BOTTOM OF STRUCTUREBOS
BRITISH THERMAL UNITBTU
BRITISH THERMAL UNITS PER HOURBTUH
BUTTERFLY VALVEBTV
BALANCING VALVEBV
CATCH BASINCB
CUBIC FEET PER HOURCFH
CUBIC FEET PER MINUTECFM
CUBIC FEET PER SECONDCFS
CALCULATIONCALC
CENTERLINECL
CLEANOUTCO
CONNECT, CONNECTIONCONN
CONTINUED, CONTINUATIONCONT
CIRCULATING PUMPCP
CLEANOUT TO GRADECTG
CONCRETECONC
CHECK VALVECV
DRAINAGE FIXTURE UNITDFU
DIAMETERDIA
DRINKING FOUNTAINDF
DOWN (PENETRATES FLOOR)DN
DRAINDR
DRAIN VALVEDV
DRAWINGDWG
EXISTING(E), EXIST
ELECTRONICALLY COMMUTATED MOTORECM
EMERGENCY EYE WASHEEW
ELECTRIC, ELECTRICALELEC
ELEVATIONELEV
ENGINEERENGR
EFFICIENCYEFF
EQUALEQ
EQUIPMENTEQUIP
EMERGENCY SHOWERES
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
ENTERING WATER TEMPERATUREEWT
EXPANSION TANKET
EXTRACTOREX
EXPANSIONEXP
EXHAUST OR EXHAUST AIREXH
DEGREES FAHRENHEITF
FLOOR CLEANOUTFCO
FLOOR DRAIN (PLUMBING)FD
FIRE DEPARTMENT CONNECTIONFDC
FINISHED FLOOR ELEVATIONFFE
FIGUREFIG
FLOORFL
FULL LOAD AMPACITYFLA
FIRE PUMPFP
FEET PER MINUTEFPM
FEET PER SECONDFPS
FLEXIBLEFLEX
FLOOR SINKFS
FEET/FOOTFT
FIXTURE UNITFU
FLUSH VALVEFV
FUTURE(F)
GRADEG
FLUSH TANKFLT
GAGE/GAUGEGA
GALLONGAL
GALVANIZEDGALV
GLYCOLGLY
GALLONS PER HOURGPH
GALLONS PER MINUTEGPM
GATE VALVEGV
HEIGHTH
GROUND HYDRANTGH
HOSE BIBBHB
HUB DRAINHD
HORIZONTALHORIZ
HORSEPOWERHP
HEAT TRACEHT
HOURHR
INSIDE DIAMETER, INSIDE DIMENSIONID
MAXIMUMMAX
THOUSAND BTU PER HOURMBH
MINIMUM CIRCUIT AMPACITYMCA
MECHANICALMECH
MINIMUM EFFICIENCY REPORTING VALUEMERV
MANUFACTURERMFR
MISCELLANEOUSMISC
MAXIMUM OVERCURRENT PROTECTIONMOCP
MOP SINKMS
MOUNTEDMTD
MINIMUMMIN
NORMALLY CLOSEDNC
NOT IN CONTRACTNIC
NORMALLY OPENNO
NOMINAL PIPE SIZENPS
NOT TO SCALENTS
OVERFLOW DRAINOD
OUTSIDE SCREW & YOKE GATE VALVEOS&Y
PHASEPH
POST INDICATING VALVEPIV
POLYPROPYLENEPP
PRESSURE REDUCING VALVEPRV
PRESSURE GAUGEPG
PRESSURE SWITCHPS
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE INCH (GAUGE)PSIG
POLYVINYL CHLORIDEPVC
RADIUSR, RAD
ROOF DRAINRD
REVISIONREV
REVOLUTIONS PER MINUTERPM
SINKS
STANDARD CUBIC FEET PER MINUTESCFM
SHOWER DRAIN (PLUMBING)SD
SMOKE DAMPER (MECHANICAL)SD
SEWAGE EJECTORSE
SQUARE FOOT, SQUARE FEETSF
SHOWERSH
SIMILARSIM
SECTIONSECT
SHUTOFF VALVESOV
SPECIFICATIONSPEC
SQUARESQ
STAINLESS STEEL (ALL)SS
SQUARE INCH, SQUARE INCHESSQ IN
TRENCH DRAINTD
TOTAL DEVELOPED LENGTHTDL
TEMPERATURETEMP
THERMOSTATIC MIXING VALVETMV
TOP OF PIPETOP
TOTAL DISCHARGE HEADTDH
TRAP PRIMER VALVETP
TAMPER SWITCHTS
TOTAL STATIC PRESSURETSP
TYPICALTYP
UNDERGROUNDUG
UP (PENETRATES FLOOR SLAB)UP
VOLTSV
URINALU
VACUUM BREAKERVB
VOLUME DAMPERVD
VELOCITYVEL
VERTICALVERT
VENT THROUGH ROOFVTR
WIDTHW
WATER CLOSETWC
VARIABLE FREQUENCY DRIVEVFD
WALL CLEANOUTWCO
WATER FIXTURE UNITSWFU
WATER GAUGEWG
WALL HYDRANTWH
WITHW/
WATER HAMMER ARRESTORWHA
WITHOUTW/O
LAVATORYLAV
POUNDLB
LINEAR FEETLF
KILOWATTKW
KILOWATT HOURKWH
ISOMETRICISO
LENGTHL
IRON PIPE SIZEIPS
INSULATIONINSUL
INVERT ELEVATIONIE
INCH, INCHESIN
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
P0.01
PA
E
PA
E
PA
E
PA
E
O
PR
D
FO
RT
ST
EV
EN
S
RE
ST
RO
O M S
SH
O W
ER
S
SY
M
BO
LS
AN
D
LE
G
EN
D S
PL
U M
BI
N G
36881 WOC 9193
PLUMBING SHEET LIST
SHEET # SHEET NAME
P0.01 SYMBOLS AND LEGENDS - PLUMBING
P0.02 SCHEDULES - PLUMBING
P2.11 FLOOR PLAN - PLUMBING
P5.01 DETAILS - PLUMBING
P6.01 DIAGRAMS - PLUMBING
Grand total: 5
L
R E
N
G
O
R
I
E
I
S
ST
S
E
E
N
ER
F
E
E
G
OD R
N
EXPIRES: 12/31/2024
P
A
I
82128PE
OREGON
M
A Y 2 2 , 2
15C
H A
RLES H. NOR
R
IS
9/13/24
38318 11838
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
P0.02
PA
E
PA
E
PA
E
PA
E
O
PR
D
FO
RT
ST
EV
EN
S
RE
ST
RO
O M S
SH
O W
ER
S
SC
H
ED
U
LE
S
PL
U M
BI
N G
36881 WOC 9193
JACKET UV RESISTANT POLYMER ASTM E84. ANSI LC1/CSA 6.26.
ABOVE GRADE
CORRUGATED STAINLESS STEEL TUBING (CSST), ASTM A240 TYPE 304 STAINLESS STEEL WITH PROTECTIVEPRPOPANE
BELOW GRADE POLYETHYLENE, MEDIUM DENISTY: ASTM D2513.
SANITARY WASTE AND VENT SCHEDULE 40 SOLID WALL PVC: ASTM D2665-85a, ASTM D3311-82.
COPPER MANIFOLDS WITH INTEGRAL VALVES. PEX-A COLD EXPANSION TYPE FITTINGS, ASTM F1960.
DOMESTIC WATER
CROSS-LINKED POLYETHYLENE (PEX): PEX-A OR PEROXIDE METHOD, ASTM F876, ASTM F877, CAN/CDA-B137.5.
SERVICE MATERIAL
PIPE SCHEDULE
ALL WASTE PIPING SIZED AT 1/4"/FT. SLOPE UNLESS OTHERWISE NOTED.
BASIS OF DESIGN: 2023 OREGON PLUMBING SPECIALTY CODE, CHAPTER 7, 'SANITARY DRAINAGE'.
WASTE AND VENT PIPING SYSTEM:
AND NOT TO EXCEED 5 FT./SEC. (HOT WATER).
WATER SUPPLY SYSTEM'. PIPING SIZED ON 3 PSI/100 FT. DROP, VELOCITIES NOT TO EXCEED 8 FT./SEC. (COLD WATER)
BASIS OF DESIGN: 2023 OREGON PLUMBING SPECIALTY CODE, APPENDIX A 'RECOMMENDED RULES FOR SIZING THE
DOMESTIC WATER PIPING SYSTEM:
PLUMBING DESIGN CRITERIA (OREGON)
FS-11 FLOOR SINK 3 - - - - - 1/2 GRATE, CAST IRON BODY, SEDIMENT BUCKET, ALUMINUM STRAINER
FD-11 FLOOR DRAIN 3 - - - - - ROUND NICKEL BRONZE VANDAL RESISTANT GRATE, CAST IRON BODY
WB-11 WALL BOX HYDRANT - - 3/4 - - - FREEZE PROOF, BOX/FLUSH TYPE w/LOCKING COVER, INTEGRAL VACUUM BREAKER
HB-12 HOSE BIB - - 3/4 - - - INGETRAL VACUUM BREAKER, REMOVABLE KEY, THREADED OUTLET
HB-11 HOSE BIB - - 3/4 - - - INGETRAL VACUUM BREAKER, REMOVABLE KEY, THREADED OUTLET, IN RECESSED BOX
EEW-11 EMERGENCY EYE WASH 2 1-1/2 - - 3/4 3 PEDESTAL TYPE, BUILT IN DRAIN BOWL, PUSH VALVE ACTIVATION, WITH ACCESSORY MIXING VALVE
DF-11 DRINKING FOUNTAIN 2 1-1/2 1/2 - - - WALL HUNG DUAL HEIGHT, FREEZE PROOF, W/ BOTTLE FILLER ATTACHEMENT
MS-11 MOP SINK 3 2 3/4 3/4 - - FLOOR MOUNT, WALL HUNG MANUAL FAUCET
S-11 SINK 2 1-1/2 1/2 1/2 - 1.5 STAINLESS STEEL WORKTABLE WITH RIGHT SIDE SINK, 48-INCH WIDE BY 30-INCH DEEP, MANUAL FAUCET.
SH-11 SHOWER 2 1-1/2 1/2 1/2 - 1.5 VALVE AND SHOWERHEAD ONLY, ARCHITECTURAL ENCLOSURE
L-11 LAVATORY 2 1-1/2 1/2 1/2 - 0.5 COUNTER, DROP IN, ENAMELED CAST IRON, METERED FAUCET, ADA
WC-11 WATER CLOSET 4 2 1 1/2 - - 1.6 FLOOR MOUNT, REAR OUTLET, VITREOUS CHINA, MANUAL FLUSH VALVE, ADA
NUMBER FIXTURE TYPE W V CW HW TW GPM/GPF DESCRIPTION NOTES
TAG ROUGH-IN SIZE (INCHES)
PLUMBING FIXTURE SCHEDULE
1. NUMBER OF CONNECTIONS TO BE DETERMINED BY THE CONTRACTOR BASED ON THE NUMBER OF DRAINS NEEDING TO BE CONNECTED.
NOTES:
BASED ON: PRECISION PLUMBING PRODUCTS PRIMETIME ELECTRONIC TRAP PRIMER, PT SERIES
DISTRIBUTION, 3/4" INLET CONNECTION
TP-1 1-16 OPENING MANIFOLD CALIBRATED FOR EQUAL WATER 120 V, 1 PH 1
ELECTRONIC TRAP PRIMER
NUMBER LOCATION DESCRIPTION ELECTRICAL NOTES
TAG
MISCELLANEOUS PLUMBING EQUIPMENT SCHEDULE
2. PROVIDE CONDENSATE NEUTRALIZER ON FLUE DRAIN.
1. COORDINATE POWER SUPPLY WITH DIVISION 26
NOTES:
PWH-103 PROPANE WATER HEATER CHASE DOMESTIC HOT WATER PROPANE INSTANTANEOUS - 3.9 0.4 PROPANE 15,000 199,000 120/1 RINNAI - CU199 1,2
PWH-102 PROPANE WATER HEATER CHASE DOMESTIC HOT WATER PROPANE INSTANTANEOUS - 3.9 0.4 PROPANE 15,000 199,000 120/1 RINNAI - CU199 1,2
PWH-101 PROPANE WATER HEATER CHASE DOMESTIC HOT WATER PROPANE INSTANTANEOUS - 3.9 0.4 PROPANE 15,000 199,000 120/1 RINNAI - CU199 1,2
NUMBER DESCRIPTION LOCATION SERVICE TYPE (GAL) (GPM) (GPM) TYPE (BTU) (BTU) PHASE & MODEL NOTES
TAG CAPACITY @ 100F RISE ACTIVATION MIN MAX VOLT/ MANUFACTURER
STORAGE FLOW RATE MIN FLOW
FUEL ELEC
WATER HEATER SCHEDULE
EQUIVALENT LENGTH OF PIPE: 75 FT. (LP)
SECTION C402.4(28), 'PIPE SIZING'.
BASIS OF DESIGN (OREGON): 2021 OREGON MECHANICAL SPECIALTY CODE, APPENDIX C, 'FUEL GAS', NATURAL GAS SYSTEM:
TOTAL 597 1 1/4
PWH-103 PROPANE WATER HEATER CHASE 199 3/4
PWH-102 PROPANE WATER HEATER CHASE 199 3/4
PWH-101 PROPANE WATER HEATER CHASE 199 3/4
(CFH) (IN) NOTES
TAG DESCRIPTION LOCATION
GAS INPUT SIZE
PROPANE UTILITY LOADS
L
R E
N
G
O
R
I
E
I
S
ST
S
E
E
N
ER
F
E
E
G
OD R
N
EXPIRES: 12/31/2024
P
A
I
82128PE
OREGON
M
A Y 2 2 , 2
15C
H A
RLES H. NOR
R
IS
PWH-101
PWH-102
PWH-103
CTG
4" W
4" W
CTG
4" W
4" W
2" CW DN
B
A
TP-1
4" V UP
S-11
L-11
FD-11
WC-11L-11
HB-11HB-11
WC-11
FD-11FD-11
L-11
HB-11
WC-11
SH-11
L-11
FD-11
HB-11
WC-11
B
HB-12
FS-11
MS-11
EEW-11
FS-11
SH-11
HB-11
L-11
WC-11
FD-11B
SH-11
FD-11
HB-11
SH-11
HB-11
FD-11
SH-11
HB-11
FD-11
DF-11 8
S-11
B
B
HB-12FS-11
3/4" LP
1 1/4" LP1" LP
CTG
4" V UP
CTG
CTG
CTG
4" W B
4" W B
P A R K
SO
N
E G
O R S T A T E
O
RE
G O N
PA
RK
S
AN
D
RE
C
RE
AT
IO
N
D
EP
AR
TM
EN
T
D E S
IG
N E D
B Y
A P P R O V E D
B Y
C H E C K E D
B Y
D R A W N
B Y
D A
TE
R E V
IS
IO
N
D A
TE
B Y
SHEET:
OPRIS#: CONTRACT #:
P2.11
PA
E
PA
E
PA
E
PA
E
O
PR
D
FO
RT
ST
EV
EN
S
RE
ST
RO
O M S
SH
O W
ER
S
FL
O O R
PL
AN
U M
BI
N G
36881 WOC 9193
1/4" = 1'-0"
FLOOR PLAN - PLUMBING
A. RUN PIPING CONCEALED IN FINISHED AREAS,
AND EXPOSED IN THE ACCESSIBLE CHASE.
ALL PIPING SHALL BE INSTALLED AS CLOSE
AS POSSIBLE TO WALL TO LEAVE CLEAR
ACCESS SPACE.
B. ALL WORK SHALL BE COORDINATED WITH ALL
TRADES INVOLVED. OFFETS IN PIPING AND
TRANSITIONS AROUND OBSTRUCTIONS SHALL
BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
C. VERIFY ALL EQUIPMENT CONNECTIONS WITH
MANUFACTURER'S CERTIFIED DRAWINGS.
FIELD VERIFY AND COORDINATE ALL
DIMENSIONS BEFORE FABRICATION.
D. PROVIDE FINAL CONNECTION TO ALL
PLUMBING FIXTURES.
E. BELOW GRADE PIPING ROUTED AT 2% SLOPE.
COORDINATE UNDERGROUND WASTE PIPE
ROUTINGS WITH STRUCTURAL FOOTING
LOCATIONS AND DEPTHS.
F. PROVIDE SHUT OFF VALVES IN ACCESSIBLE
CHASE BEHIND FIXTURES.
G. PROVIDE WATER HAMMER ARRESTORS ON
EACH BRANCH PIPING SERVING A FLUSHING
FIXTURE.
H. PROVIDE LOW POINT DRAIN VALVES IN
WATER SYSTEM PIPING TO ALLOW FOR
DRAINAGE OF SYSTEM.
GENERAL NOTES:
1. BUILDING COLD WATER SUPPLY FROM SITE
WATER DISTRIBUTION SYSTEM.
COORDINATE CONNECTION POINT WITH
CIVIL.
2. BUILDING SANITARY WASTE CONNECTION
TO SITE SEWER SYSTEM. COORDINATE
CONNECTION POINT WITH CIVIL.
3. BUILDING PROPANE SUPPLY FROM SITE
DISTRIBUTION. COORDINATE CONNECTION
POINT WITH CIVIL. BUILDING GAS
PRESSURE REGULATOR SET AT 11 IN W.C.
WITH MAX SITE SUPPLY PRESSURE OF 10
PSI.
4. BUILDING GAS PRESSURE REGULATOR ON
BUILDING EXERIOR WALL SET AT 11 IN W.C.
WITH MAX SITE SUPPLY OF 10 PSI.
CONTRACTOR TO VERIFY SITE GAS
PRESSURE SUPPLY WITH EQUIPMENT
SUPPLY REQUIREMENTS. SUPPLY TO
PENETRATE BUILDING WALL ABOVE GRADE.
5. MAIN COLD WATER SHUT OFF VALVE ON
BUILDING RISER. CONTRACTOR TO VERIFY
MINIMUM 55 PSI SITE WATER PRESSURE
AND PROVIDE WATER PRESSURE
REDUCING VALVE IF WATER PRESSURE IS
ABOVE 80 PSI. PROVIDE SYSTEM DRAIN
VALVE ON INCOMING PIPE RISER.
6. ROUTE EYE WASH DRAIN TO SPILL INTO
FLOOR SINK.
7. EXTERIOR SINK UTILITY PIPING ROUTED IN
BACKER BOARD LAYER INTERIOR TO BLOCK
WALL. PROVIDE WINTERIZATION SHUT OFF
VALVES ON HOT AND COLD WATER SUPPLY
TO EXTERIOR…